Specifications . 1 go 4 6roatEir54 ( A March 21, 2006 a '�' "��u1 ` CITY OF TIGARD Point Monitor Corp. OREGON Joanne Corrigan 4755 SW Oelson Rd Suite 102 Portland, OR 97225 RE: MODIFICATION- FIRE ALARM SYSTEM Project Information Building Permit: BUP2006 -10010 Hazard: Light Tenant Name: Joe Green Building Occupancy Type: B Address: 11550 SW 67 Sprinklers: Yes Stories: 3 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; Oregon Fire Code 2004 edition and NFPA 72. The submitted plans are approved subject to the following. General requirements 1. Before requesting final approval of the installation, the installing contractor shall furnish a written statement to the fire code official that the subject fire protection system has been installed in accordance with approved plans and has been tested in accordance with the manufacturer's specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations shall be attached to the written statement. 901.2.1 OFC 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the building official and fire code official. All functions of the system or alteration shall be tested. 901.5 OSSC and NFPA 72 3. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. NFPA 72 4.4.1.4, 907.5 OFC 5. All power supplies shall be installed in conformity with NFPA 70. NFPA 72, 4.4.1.2 6. All primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system. Failure of either supply shall result in a trouble signal in accordance with 4.4.3.5. The trouble signal also shall be visually and audibly indicated at the protected premises. NFPA 72, 4.4.7.3 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 7. Visual alarm signal appliances shall be integrated into the building or facility alarm system. At a minimum, visual signal appliances shall be provided in buildings and facilities in each of the following areas: 1109.14 OSSC • restrooms and any other general usage areas • meeting rooms • classrooms • hallways, lobbies, and any other area for common use. 8. Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at least 6 inches below the ceiling. 1109.14 OSSC, NFPA 72, 7.5.4 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 1063.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Val Henzel, Senior Plans Examiner s - s INTT LLIKNIGHTFIREAL -ARM CDNTROLPANEL` • I t r! 1 '. 1 4 `` t;1 7 IntelliKnight® Model 5820XL 4 7 ` ;; • ',T ;; L n f° P � { Addressable Fire Alarm '1 t t , . ` s x n ,/ r } t� ;, ; Control System A ,: � , I , f . ,. ti - ECE1VED : ' ; The IntelliKnight System is the way Y �" -� 1a '` to make the most of fire alarm technopogy0 3 2006 PY �` `` r + ti CITY OF TIGARD IntelliKnight is the first fire alarm system to provide you with the revolutionary value ek►"c- p2PP of addressable sensing technology combined with exclusive, built -in digital communication, distributed intelligent power, a modular design and an expanded, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1- 800 -446 -6444, or in Minnesota, call 763 -493 -6435. Description • Built -in Form C trouble relay rated at f • ., The IntelliKnight 5820XL performs drift 2.5 amps at 24 VDC. t � t L *1, �, compensation and calibration checks Two built -in Form C programmable af on each of the sensors in the system. relays rated at 2.5 amps at 24 VDC. !'�n " , The basic IntelliKnight 5820XL system • Supports Sounder Bases. .`° : ,. `"j can be expanded by adding modules Specifications '*' t K'',,�,r � s such as the Model 5860 Remote Primary AC: 120 VRMS at 50 / 60 hz '' i, ,a J< '' ‘ ,' a �, fJ .. 3 t` r ,¢ Annunciator, Model 5815XL Signalling 2.5A ! i Line Circuit Expander, the Model 5824 Total Accessory Load: 5A at 24 VDC ' �t ;. 4 " f " { Serial /Parallel Interface (for printing 5 amps at 24 VDC of power - limited € F i -4 '71. ' M s system reports), and the 5895XL (' f s y notification power R IS * , Intelligent Power Module. The Model '. 3r- -- ' Standby Current 140 mA 034 .1' - T�. ` , �' , 5820XL also features a powerful built -in i et + 4 7;i , Alarm Current: 260 m A 2 u "" ,. dual line fire communicator that allows 1 n �� ` h � 3 is " � ,r Inn Circuits y j v ati r r ii , � . r ✓g for reporting of all system activity to a Flexput �,� � � ��.�� � l_ �p , � ,Og ; �� remote monitoring location. r.t z „ r if i Six programmable circuits which can T r s; + t , ,- „ ' -.k ` . .. , Features be programmed individually as: 1 • Up to 508 addressable points. Notification circuits: 3 amps of %x ° - � • Uses standard wire —no shielded or Power limited power per circuit at 24 � ry e � t..-- twisted pair required. VDC. y • Built -in digital communicator. Auxiliary power circuits: 3 amps of Approvals: • Central station reporting by Point or Power - limited power per circuit at 24 by Zone. VDC. UL Listing Built -in synchronization for Initiation Circuits: 100 mA of power NFPA 72 - Central Station • appliances from 4MSECO ®, limited power per circuits at 24 VDC. - Remote Signalling Gentex®, Faraday, and Wheelock® Mechanical -Local Protective • Supports Class B (Style 4) and Signalling System Class A (Style 6) configuration for Specifications: - Auxiliary Protected SLC, SBUS, and Flexput circuits. Flush Mount Premises Unit • Distributed, intelligent power. Dimensions: -Water Deluge • Drift compensation. 14 -1/2 "W x 24 -3 /4 "H x 3 -7/8 "D Releasing Service • FlexputTM I/O circuits. (36.8 W x 62.9 H x 9.8 D cm) CFSM: 7170 -0559: 135 • Eight pre-programmed output Overall Dimensions: MEA 429 -92 -E Vol. 9 cadences, (including ANSI - 3.41), 16 -1/8 "W x 26 -3/8 "H x 4 -1/8 "D FM approved and 4 programmable outputs. (40.6 W x 67 H x 11.8 D cm) • Built -in annunciator with 80- Weight: 28 lbs. (12.8 kg) character LCD display. Color: Red SILENT • RS-485 bus provides communication Telephone Requirements: • to system accessories. FCC Part 15 and Part 68 approved KNIGHT Built -in RS -232 interface for Type of Jack: RJ31X (two required) programming via PC. by Honeywell • IN LLIKNIGHT�I ALARMCDN D L PAN ' r . � , ' I* ' +$ , a G tY; s X P ...9:.. v SKr >' ?`. ` :. :, ..., �. A. 1 ir. -. ..:I. �, .' , . i Xt•- ., i , : i . _... _,. } G ' - IntelliKnight Model 582OXL 3, � ` Addressable Fire Alarm Control Panel q -- t ,, (I`. Indicator Lights: in excess of 17 amp hours. capability and touchtone or rotary GENERAL ALARM (Red) - On for Flexput" m circuits on the Model dialing. The communicator is alarm 5820XL control can be individually compatible with SIA and Ademco programmed to function as notifi- Contact ID. The format is SUPERVISORY (Yellow) - On cation circuits, auxiliary power selectable by account number. when a supervisory condition outputs, or initiation circuits that User Interface exists. support both 2- and 4 -wire smoke The IntelliKnight's built -in SYSTEM TROUBLE (Yellow) - On detectors. annunciator with 80 character LCD when a trouble condition exists. The IntelliKnight system operates display and large easy -to -use SYSTEM SILENCED (Yellow) - On on non - twisted, unshielded cable tactile touchpad can be used for when an alarm, trouble or when wired in compliance with system operation, programming supervisory condition has been standard wiring practices as called and maintenance. It has five LEDs silenced but not yet cleared. out in the National Electric Code for alarm, supervisory, system SYSTEM POWER (Green) - On 760 specifications for power - limited trouble, system silenced and when power systems are normal; fire protective signalling cables. No system power. System operations flashes for AC or DC failure. special wiring is required. include silencing alarms and System Application The Model 5820XL provides seven troubles, resetting alarms and the The IntelliKnight Model 5820XL preset notification cadence patterns display of alarm troubles and control panel has one built -in including ANSI 3.41 and four user memory. The system's non - volatile Signalling Line Circuit (SLC) which programmable selections for fire event history buffer stores 1000 alarm notification. events for viewing from the built-in supports 127 devices. Three 9 additional loops can be added Two programmable general •.:- using the 5815XL SLC expanders purpose Form C relay outputs are l am = 1i to increase overall capacity to 508 Provided on the Model 5820XL i,_ F ? -' - -- , ' := IQ�4 q d t '� St 1 t devices. t L I r c , '� 1gr -. ��raY k Additionally, the IntelliKnight x 7 { ! , I The Model 5820XL's SLC loops Y �,r z ri< ht , support multiple device es: system features a built -in walk test ,,, -A . NN' su PP P types: mu , tip a and auto - programming. Its F r„, k r , �+ • Addressable photoelectric smoke A� y� . innovative, dead -front cabinet j 110::!;-46-,-, . detector t,��: , ^ " _ ''. i k 74,,t l' S 4 design allows for flush or surface L F • Addressable ionization smoke i , !� r ,41013,1 ,41013,1 detector mounting. System maintenance is 5 t� x ti rr , r easy to perform. ,a„. 7 n ya - • Addressable heat sensor _�.: . r t ` °` ik �<r r Built -In Digital � ; _t; • Addressable duct smoke or remote annunciator. System detector Communicator operation can be initiated with a • Contact module The IntelliKnight Model 5820XL mechanical firefighter's key or a • Relay output module features a built -in UL listed digital valid 4- to 7 -digit operator's code. • Addressable notification module communicator for remote reporting programming The following advanced sensor of system activity and system capabilities are available using the programming. The communicator The IntelliKnight system offers IntelliKnight Model 5820XL: has the ability to seize two several options to simplify and • Automatic drift compensation telephone lines to report alarms speed up programming. The • Maintenance alert and troubles to a monitoring facility. JumpStartTM feature minimizes • Built -in sensor test to comply The communicator supervises two programming required to start a phone lines and will activate a with NFPA 72 calibration testing P new system. The built -in keypad requirements trouble signal if a line failure is and the 5860 Remote Annunciator sustained for more than 45 give on -site access to all The IntelliKnight 5820XL features a You can also 5 amp power supply and maximum seconds. Other communication programming. battery charging capacity of 33 features include: retry if communi- program remotely using the amp hours. An additional cabinet cation fails, two phone number Windows Download Software. capability, download phone number enclosure is required for batteries ANTE lillKNIBH;rEi XL'ARMCDWRDLPANEL '1 1 • . IntelliKnight Model 5820XL - .. A - ' Addressable Fire Alarm Control Panel ir;' }' f . -4 ...1 IntelliKnight 5820XL Addressable Fire Alarm System Wfrro.esBa see r orate tamer. rmn 3oforse .. or W sows Bash l I - . 11 iS.232 - S nave e 1 1 idea 9800 9500 amanounne raware RIDee ` Mac 5895XL 5820XL Dq�.mlPn?uwar 0800 „ a lRacerre INeleeri PO 'Mod We 4 + '11 _P i i + 3r0eMC Relay.: 3FOtmC Raises • Event Prim p Ai..,. p L y } 1 fiF -132 56 60 5824 -- a - Remo IeA nca1 PrmIe rlG eewsy Mow le I �, l 12UnnealeaAy9Mn) i 5815XL 5815XL A l ® SLC Fagan der ELC EAmnOnl Flex - Flex '•i el n 1 r, 1 - y l b aorta. Drme Htar and NAG - NIA Marione emeenlonal Serer. °� Smarm Defectors T i I I I I 10 SD505 -APS S0505 - AIS SD505 - 6SB SD505.AHS SD505 - SDM °' acares!a14e Ap7reesable Sounder base A a1,seaW4Hea 7lrr -- PIIntOOectet Ialaataln Deader Gmmk HOdu'e . Detector Detector 5860 Re materennuntmor J_ ' I , ' «• SD505 -DTS , • Hol • walYplY % . aiJLAar > El DaCf Tel 6 fle l� 1 1 1 l 5D500 - ANM SD505.6RB 50505.616 SD505.6AB 5880 -- -1>ri j9 ,' AdareG:-0le Relay Dace IO4s N' CDelmer Bare LE[,Drwe,S N U0je Base - MC2NP IN]OI M Cable 1 ° - - -- I I 1 - 5883 —J Peal' OMire A"odule SD505 - ADHR SD500 - PS SD505 - ADH S0500 50500 - ARM SD500 - LIM 1 P. dfr 0.4I. Derr A :Y.ree-• etre Aat0Lmale nth! Dn Crel'1,1 Ad*01001.1e A}1 li,u 5 cye R ety FASta -, Du ;■: tl 4 tic II;ntl11 Rely 0t drle Lrrre Isla (11, or 0+0+1(00 +1) Meal ere 00040 llen 0, P`WO aEGIIIc 1 :ma 5865-4 or 5865-3 I I I LEN. rrunm101 1 I Use the 588010 control up to 4 1_ _ .. 15L66 cnlwo) •i 5883 Relay Interface Modules 1 J 1 1 k -T..,;..• S :. ) .1 . .': k Y _. .i:! y •� 4 . f � ' < S i 1 . ' 1 f • 'INTfLLIKNIGiH ALARM .DDNT RDLIDAN , '' } �; t , y , , .. ' ; : IntelliKnight System Accessories mount on a 4 inch square electrical 5860 Remote Fire box. Provides indicator LED to show Annunciator ' , x 3 7 . s ander Ex Line Circuit Signal II �- output status and comes with a The 5860 features the E ' l'''•-' ,� +� "- .4 ,, ` ;-, i, i t E coverplate. same 80 character ; 7 ; 4 - ,. -. , '� g.-4 -, Model SD505 -ADH backlit LCD display `. 7 �,. Duct Housing Detects smoke in HVAC keypad and firefighters hg ,x r „ , 10, > -� Y ; } i ( ducts. keyswitch as the 5820 t . :;:t. , ::::::;,: - t, , 4 • • ��t ' " Model SD505 -ADHR The system can be fully programmed • + '' < I Duc detector base with relay. Provides and operated from any remote ' v k„ form C alarm contact. For use with annunciator. y � �'r, ���'l ra � ` � � i ' � ' SD505 -APS and AIS sensors. 5 815XL Si 9 p �$ "- Compatible with SD505 -DTS remote The SLC expander is used to add more ' test switch. addressable devices to the IntelliKnight Model SD505 -DTS system. The 5820XL can support three Compatible Devices Remote test switch. Used with SD505 5815XLs. Each 5815XL can support IntelliKnight's devices feature a low 127 devices. ADHR. Provides remote key operated profile design and EEprom addressing. test function and annunciation of 5895XL Intelligent Power Module EEprom addressing prevents water detector alarm. Adds 5 amps of power, 6 FlexputTM I/O intrusion problems via the back of the Model SD505 -6SB circuits and 2 Form C relay circuits to sensor and eliminates mechanical an IntelliKnight system. failures related to decade switches. Six -inch sounder base. Operates in single and multi- station modes and /or 5880 LED/I0 Module Model SD505 -APS as a system sounder. Used with Features 40 LED outputs, 8 normally Addressable photoelectric smoke existing sensor and base. Requires 2 open dry contact inputs and one piezo detector. additional wires for power. output. Model SD505 -AIS Model SD505 -61B 5865 -3 and 5865 -4 Addressable ionization smoke detector. Six -inch isolator base. Used with Remote LED Annunciator Model SD505 -AHS existing base and the SD505 -APS, Features 30 Programmable LEDs (15 Addressable heat sensor. AIS, and AHS sensors. Provides red and 15 yellow) outputs and piezo Model SD505 -6AB isolation for style 7 circuits. sounder. The 5865 -4 adds a silence Six inch base designed for use with Model SD505 -6RB and reset switch to the package. detector head models SD505 -APS, Six -inch relay base. Used with existing 5883 Relay Board SD505 -AIS and SD505 -AHS. sensor and base. Provides one Form C Features 10 General purpose Form C Model SD505 -4AB contact. relays. Used with 5880 module. Four inch base designed for use with Model SD500 -SDM 5824 Serial /Parallel Gateway Module detector head models SD505 -APS, Two -wire detector input module. Allows Has one parallel and one RS -232 serial SD505 -AIS and SD505 -AHS. for the connection of conventional 2- port for connecting any standard IBM - Model SD500 -AIM wire detectors on the SLC loop. compatible printer to the IntelliKnight Dry Contact Input Module. Designed to Requires two additional wires for system. Interfaces with building control used with normally open dry contacts. Power. system. Mounts in a 4 inch square electrical Model SD500 -LIM 5496 Intelligent Power Module box. It features an indicator LED to Loop Isolator Module. Provides The Model 5496 is a 6 amp.notification show alarm status and a coverplate. isolation for style 7 circuits. power expander that provides four Model SD500 -MIM Model SD500 -LED additional power - limited notification Mini Dry Contact Input Module. A An Addressable LED driver module that appliance circuit outputs. miniature version of the addressable connects to the SLC loop and is SKSS Silent Knight Software Suite input module which is designed to be capable of driving 80 LEDs. Up to 40 5660 Upload /Download Software used with pull stations and other SD500 -LED modules can be used SLC User- friendly, WindowsTM software for normally open dry contact inputs where loop with a maximum or 100 SD500- remote programming of the IntelliKnight a smaller size is desired. LED modules per system. panel using a PC. Model SD500 -ANM Model SD500 -PS 5670 Facility Management Software Addressable Notification Module Addressable Pull Station Powerful end -user software allows providing a single Class A or Class B S -BUS Accessories viewing of detector status and event notification circuit on the SLC. The following items listed are devices history via modem or direct connection. Model SD500 -ARM that connected to the IntelliKnight's RS- Addressable Relay Module. Features 2 485 Bus - Form C output relays, designed to SILENT This document is not intended to be used for installation purposes. We try to MADE I N AMERICA N KNIGHT keep our product information up - - date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350210 Rev C, 01/06 g' subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, MN 55369 -4927. Copyright © 2005 Silent Knight Phone: (800) 328 -0103, Fax: (763) 493 -6475. IntelliKnight is a Registered Trademark of Silent Knight Flexput is a Trademark of Silent Knight 71:R'.; .,ji4 ? y K' 7 , 4 , S 3 ,,.„ F .t S -!- �,' t Mr k , } 4- t t :,; ', X .5 t � t .� 4- :' , :,== 7 v.{ 1" . r r b t 5(: fi 3 �h 1c5 i:., A Y.,,,. +.t ,U.z. t i,� 1 ? ,s v i �S s L . :" u t ti v I y I r s . y 4 \ t a'I n s 3 I . {NI . ' 1 ' I_.f;Si Y �, #':. 11 j' t Li J. ' -,.'1,1';:-W,':':;,::,1 1 t r k Y Y ( K- \ Model 5895XL oP y., w,ry. 4 . ' u i at r ,� i r � 1 , ; • k . + t �- n , . 5 g ` zt a & Y ...,g a a o:,. 6 ui j Sew , S' ` `, a ' 1. f, e}-.7 r� +c ry ,,} ■ 1 fit .; W ri. 4 l,o i n M i ii j 'Q" 5 � r 9 ,„ The i ntelligent way to distribute power 8 c t 4 ,,,', 0 , �„� A X , 5 � F` " throughout your installation With 5.0 amps of output power, six programmable FlexputTM I/O circuits, and two Form C relay contacts, the Model 5895XL Intelligent Power Module allows you to greatly enhance the capabilities of an IntelliKnight system, distributing power where needed throughout a facility. 5895XL modules connect via the RS 485 system bus. Up to eight 5895XL modules can be used per IntelliKnight system. Each 5895XL has its own optically isolated RS 485 bus to which other modules, such as 5860 remote annunciators and 5824 printer interface modules, can be connected. You can also connect 5815XL SLC expansion modules, adding flexibility and wiring distance. Each 5895XL supports its own backup batteries and monitors the AC power. Model 5895XL for SBUS & Flexput circuits iit .,Y• F- ' ?' , Intelligent Power Module • 2 Form C programmable relays wipe ,' ;* °M b ' Y The Model 5895XL adds 5.0 amps rated at 2.5A at `` k z ,'-'5':.",7":; ; , x ' .. of power, six Flexput I/O circuits, 24 VDC' ` . � . t and two Form C relay circuits to an =c k <," %� «'' c, 4 't, y • Ground loop isolation IntelliKnight installation. The � 1� .s � R • Transient protection , d �n : Y o - 5895XL is optically isolated r *, providing ground loop isolation and • SBUS repeater conditions the a , ? ; RS 485 signal ""A , transient protection. The 5895XL conditions the RS 485 system bus • 6,000 feet wiring distance from , s" 0 1 , ; . 5895XL (same distance as main j allowing an additional 6,000 feet of ( ��- �;t �* y ,, ' `�, ' ��Y wiring. FACP) ���} 'nip Operation • Large cabinet can house two 17 1 . The green LED on the 5895XL amp hour batteries ,� Wt� ' ' � . 14 ' board indicates communication with • UL 864 listed, complies with t' h i t -� e4 � the IntelliKnight FACP. NFPA 72 and 101 , 9 " 4 4,- '�" °s ' .; The Flex utTM' circuits can be • CSFM 't k `��i a 5y • notification appliance circuits, • MEA 429 -92 -E, Vol. 9 � � : m y � � , , continuous power, resettable • FM a roved 1 ▪ ,` " z "� • , V. X V�� 5 � power, door holder power or - . l i p At , a , w , , , Spec h�t „f fg initiation circuits that can support Primary AC: 120 VRMS @ Model 5895XL both 2- and 4 -wire smoke 60 hz, 2.5 A Power: 3A per circuit (5A detectors. All Flexput T"^ circuits Total Accessory total per system) and relay outputs are individually Load: 5A @ 24 VDC Flush Mount mappable from the IntelliKnight 5820XL FACP. Current: Dimensions: Features Standby 40 mA 14 -1/2 "W x 24 -3/4 "H x 3 -7/8 "D • S.OA output power Alarm 160 mA (36.8 W.x 62.9 H x 9.8 D cm ) • Flexput I/O circuits, 3A each I/O Circuit Overall Dimensions: programmable as notification 16 -1/8 "W x 26 -3/8 "H x 4 -118 °D circuits, auxiliary power circuits, SILENT (40.6 W x 67 H x 11.8 D cm) or initiation circuits. :,. Color: Red N � ICN IGEIT • Supports Class A configuration �JFd ` CC + DRY t f. t Y t 8 6.- Y < . r .'3 0.V., 3' ,p. � r.E6 f t y t1N TELLIKNIp t - T c/4 r , = I -'I�r 7 : 1 ` .t c• 1 Model 5895XL _ Intelligent Power Module t ' 1 + M' a y ; l ''' Engineering Specifications 1 The contractor shall supply a power module compatible with the IntelliKnight Model 5820XL FACP. The power module must have 5.0 amps of output power, Flexput I/O circuits rated 3.0 amps each, and two Form C relay contacts rated at 2.5 amps at 24 VDC. The power module shall connect to the main FACP via an RS 485 system bus (SBUS). The power module shall contain an additional RS 485 bus that is completely compatible with all IntelliKnight add -on modules, including 5815XL SLC Expanders, 5860 Remote Annunciators, 5824 Serial /Parallel Modules. The power module RS 485 bus shall be optically isolated providing ground loop isolation and transient protection. The unit shall be an SBUS repeater that conditions the signal driving 6,000 feet of additional wiring. 5895XL installation Example 5895XL Connection to FACP I :R4101,...- 582 0XL FRCP .5895XL'' ° "r `� , r -" _ __ __._ ._......__,...._.____._._.__.._ r �F iN - . SBUS rw 4UT ..._......._.._ � _._.„..M._..._ 23 22 21 20 19 18 1 7 16 a 33 32 31 30 23 22 21 20 19 18 17 16 i I f ` + 0 d )0c , C f 1 ; ,n, A f B ± A B I ` r. SLC ( NACS, Aux: power. etc.. ! j'1 r_. L ( • i4" C) 0 0 f ' il l C�:!' I .. — r i ' J l, y Y -- l ------1 r , -- I � i L � � , �662a; 15864 T, - - i Y Us d 1 To next Class A - - Class 'A ,.;:, SBUS device C . configurations ;, Up to 6:000 feet. non- shielded configurations m u) w a R 4, 1t‘ - ' - ‘4 1 MAN' tt -- NACS. Aux. power.. etc- 't 5895XL -1 sous 5895XL - SBUS 4' sLC , I es. )58801 15660 15&241 'r- nr )88D� 15850.; To next 5895XL xL sic - z SILENT N KNIGHT MADE IN AMERICA ® FORM# 350212, Rev. 09/01 7550 Meridian Circle, Maple Grove, MN 55369 - 4927 800 -446 -6444 or in Minnesota 763 - 493 - 6435 Copyright © 2001 Silent Knight FAX: 763 -493 -6475 IntelliKnight is a Registered Trademark or Silent Knight World Wide Web: http: / /www.silentknight.com Flexput is a Trademark of Silent Knight iINTEL•L'1KNIGHTAGDESSDRY , i . t Model 5860 c.' �, ) , .,. °° ' Remote Annunciator � . " � F n `i r . 1 „.- iw ', x 8 , � Bring the power to control IntelliKnight® ,,,,. " r• . ' to every area within your facility. : ., .ate it,./.40;:.4 1 i a slim Now you can operate and program your IntelliKnight system from up to 8 locations throughout your facility. The Model 5860 Remote Annunciator provides the same advanced, easy -to -use interface found on the IntelliKnight panel's built -in annunciator. The 80- character display and ergonomically designed keypad allow for simple and error -free system operation. All operations — including reset, silence, detector status checking, fire drill, and programming —are identical. Access to the system is through a firefighter's key or an access code. For security, a special installation code is needed for programming functions. . The 5860 connects to the IntelliKnight panel via the RS -485 system bus. Wire runs can be up to 6000 feet from the panel. Model 5860 Users identify themselves to the Remote Annunciator control panel by entering a c ode on the annunciator or by turning the The 5860 is designed to look and firefighter's key. When a user . operate exactly the same as the presses a button, the annunciator ht built -in annunciator. "' g piezo beeps and the LCD prompts - w,,"4� , Wt-.3:. , � IntelliKnight Features include an 80- character the user to enter a code or other ``" '`'` El . L.. .41 backlit LCD providing easy -to- relevant information. understand system messages. The annunciator is ergonomically Multiple users can work at different 5860 Remote Annunciator designed with over -sized buttons annunciators simultaneously for the most frequently used without affecting each other. Specifications features, like Reset and Silence. Operating Voltage: 24 VDC Features Standby Current: 20 mA In addition to status messages • 80- character display displayed on the LCD, there are Alarm Current: 25 mA • five LEDs for alarm, supervisory, Tactile /audible feedback Max. per system: 8 trouble, silence, and AC power • ` Accepts user codes or firefighter's key Ambient Temperature: 32 °F to 120 °F status. (0 °C to 49 °C) • RS -485 interface to panel The annunciator is available in gray Can be flush- or surface- Mounting: Surface or flush • to match virtually any decor and red for applications where the mounted. Trim ring available for IntelliKnight Kniight panel: Up to 6,000 feet annunciator must stand out. The surface mounting. annunciator enclosure can be • Operation and appearance Dimensions. Height: 7 -3/8" identical to on -board annunciator Width: -1" Depth: or flush mounted. A trim Depp1 th: 1 -1/2/2" ring kit is available for surface • Supports simultaneous use by Colors: Lt. gray (5860) mounting. multiple users Red (5860R) Operation • UL listed, complies with NFPA 72 • When the system is normal and CSFM Approved receiving AC power, the power LED • MEA Listed is lit and all other LEDs are off. • FM Approved Other LEDs turn on as the . " SILENT conditions occur. N KNIGHT m 1Ni fLL1KNI�+�T A�Lt�SDRY, ` d r .:r.l. i,4,..r t.. n �... �. iii ^. .'. ,.. t...,f,i u t.r���„ �;� tidy" • Model 5860 4K 3 ,fu�fit • Remote Annunciator r • Engineering Specifications The main control must have a built -in annunciator and must support up to eight remote annunciators. Remote annunciators shall have the same control and display layout so as to match the appearance of the built -in annunciator. Remote annunciators shall be available in two colors, red or light gray. Remote annunciators shall have identical functionality and operation as the built -in annunciator. All annunciators must have an 80- character LCD display and must feature five LEDs for: General Alarm, Supervisory, System Trouble, System Silence, and System Power. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of .040 inches. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad or by using a firefighter's key. The annunciator must have two levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple user input simultaneously. 5860 Block Diagram R ff4 4 ✓ Y x l� 4:1')4 J s� Up to 6000 feet from panel V +a..@ zc- .a „. t "c, v i+ - a y' '� a � '" } ,6i `. ( , r Up to 8 devices per system. 0 qtr ibx ' `, ,y ` a53'�'x e a ,d SILENT r. NI; KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800- 446 -6444 or in Minnesota 763 -493 -6435 FORM# 350224, Rev. 01/01 FAX: 763 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2001 Silent Knight • °' ' INT.EILIKNIDHT.ccEsSDRY Model SD500 -ANM ' ``' ` . :: ' , r q Wr �%,.. Addressable Notification ) � $$ . , ' Module 1 4 i 4 !, ` , " = ,- The cost effective way to expand the '` .. ; ;' � f '� x ;..- ' . IntelliKnight's notification circuits. The SD500 -ANM gives you the flexibility to add notification circuits wherever you need them. The SD500 -ANM is a supervised addressable notification device that provides you with additional notification circuits on the IntelliKnight SLC loop. Up to 127 SD500 -ANM modules can be used on an SLC loop. The SD500 -ANM provides a reverse polarity Class A or Class B notification appliance circuit with an aux power input. Each SD500 -ANM is provided power from a separate power supply and is controlled and supervised by the main panel. Power can be provided near the signaling appliance to reduce the wire gauge requirements or can come from a main power supply and be controlled separately by the individual notification modules. The SD500 -ANM can produce all 16 of the notification patterns available on the FACP. Model SD500 -ANM Features Specifications Addressable Notification • Class A (Style Z) or Class B Operating Voltage: 24 VDC Module (Style Y) Notification Circuit. SLC Current: .55 mA The SD500 -ANM is an Addressable • Flexible programming— choose Aux. Power Current: Notification Module for use with the the cadence pattern (twelve Alarm: 56 mA IntelliKnight fire alarm control standard & four user - defined). Standby: 6 mA panel. The SD500 -ANM provides a • Polling LED visible through cover Notification single class A or B circuit that is plate. Appliance Current: 2 Amp Max. controlled by the IntelliKnight's • UL listed, complies with NFPA Ambient Temperature: 32 °F to 120 °F Signaling Line Circuit. Power for 72 (o °C to 49 °C) the circuit is provided to the CSFM Approved. Mounting: 4- square SD500 -ANM module from a electrical box. separate power supply, making it • MEAApproved 429 -92 -E, Vol. 9 Compatible Control Panel: 5820XL easy to power remote devices. • Adds up to 127 independent The notification circuit, remote output circuits on each SLC loop. power and communication to the • Supervised auxiliary power SD500 -ANM are supervised by the source input. IntelliKnight control panel. Completely supervised. • Operation Each notification module is -__ programmed with a unique SLC 11_ _=i____ loop address. When an event that controls the notification module I O • 1 �� occurs, the notification switches its u ih • built -in relay feeding power from O the auxiliary power input to the �' ''' ;} notification appliance. { SILENT % 47 :,- KNIGHT -. by Honeywell Model SD500 -ANM t.INTELLIKNIGff ACCRSSDRY,= } r• Model SD500-ANM Addressable Notification Module ' i i' cr Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable notification modules, Silent Knight SD500 -ANM. The modules shall be UL listed compatible with a Silent Knight IntelliKnight fire alarm control panel. The notification module must provide one Class A (Style Z) or Class B (Style Y) notification output with one auxiliary power input. The notification module must be suitable for mounting in a standard 4- square electrical box and must include a plastic cover plate. The notification module must provide an LED that is visible from the outside of the cover plate. The notification output must be fully programmable for such applications as are required by the installation. FRONT VIEW E r t 4-7/8 i v -I I EI E # I C i , I'1 bra S � MIGHT } fr P ( Th. I E I 4 -7/8" 1/4" 1" • Model SD500 -ANM Addressable Notification Module - Gz >•ta�.z.a ..-a. x... . �zs.. �.:. �zs, ..:t„_..c.<w.x..ro.- m. «..r.e�, .rw_.. SILENT KNIGHT by Honeywell MADE I N AMERICA 7550 Meridian Circle, Maple Grove, MN 55369 -4927 FORM# 350220, Rev. 02 /04 800 - 446 -6444 or in Minnesota 763 - 493 -6435 Copyright © 2004 Silent Knight FAX: 763 -493 -6475 World Wide Web: http: / /www.silentknight.com IntelliKnight® is a registered trademark of Silent Knight • ,'PX Y r " w t r �` � ' 'r Fs r -2ch "' gi rt "`': r , `Ar yy5�3 , ?I•ra $-. �t; yi '' '' „;.• r ?. .` fit 7f . rte �,'t !. e s`�;roT�t^{•.. .. ; .r k, n < » 3nrti .r ...a y ". 6 «� '•' `� p r a �s..,n.... �� ',m "`I'+t)s?�t.z - ..•,ra'w.Y' � �,y •Yti ..... �`. `�'s,�`'�'s�,srs y;,, w : ek a :�4� � }. . +miF �y {. m.� '?a„ ��.gk �)E � t - r.7.t S�• , S' . ..., s�T & 5L..- p , , t F. h. , x•..,s"F+t r,,, .la t - � . y . ( i # ;v '`'; %; s� T IN„ 'sw,' a", I^�t �J: '�iAt� Y+,'e. rr y . 3 i rt �i �j ;�W ' 'D,� i9+' � �, , � +� � er'r: arr `^Y" .�S; l+,...t.,.,yr, ��, r„ t „ '� 4.o-., .,:d�'.u'f `�{,k2 t'.`, ;: ,.. a">• .. #...,, ...a`�S`... s :,, _fi., ,..a,;2 ># 't s . x. �vr..x � Ct;.,: -r.. .� . TL �a '. ..,✓ re"'t :.?• wC.a � +>, ;'' - +Y-t s fir. ,, Sa rµ :. ;;,•(s..s.,.. t.. - x •.� ,, � + ,.<'. �".t�y' „,I.F_1: Y",rJ '^'� ..:� } 7 d F ,�! .; , , o-' y.. >..,,- ;.�,� p+d,�Y- .4 -: >x..wR � ,• y„ +/ : ,f. .Y� .,a,n 4 - -:� T ^n Y 1' $ : tm:.ilr f 4 , .' fi '? 3 � ' 3nr{. • �+ t .✓^ T._ , !G--t' rcv, w".nE;y X , tF .. `t J , t 3 �?; ¢ -tN a .?a. -,•i va ° {� x ".+^.� s'. 'r11� v r,- S k -�� L kt x 4 ,E:., rt. s §r :i e "!,!'�d.S a; ;' t -f p . ..+.. « .}' i>�.. • a .!r:.. � : .. t :; n 4 �' � �v X, d ,�} �.I- s, Irk d , to v >d `f ;a 7 . 2,' K LT 1 5p'+y t v "'}x L , l y F j' +'j,,, l,SC .,F 1 � 4.: a. r l y a - :,, ."a E -i' �ti'+k7.f 4 4 ''gyp. t J Q f y.?/{". § ✓ M1}.l: '1'�rbt{.�p l ., 4 't :..,"g - fY '1 .: r .. z. r "� t y� � �Y }n . � N.-- .:,-t� f.,• fi r* � P "j r.:'+, fact 5 ,,fi - K., �ij ?'• "'N � �- `� ^�-L •-+ F' t .� r r . � ,J ,-k � a r 1� v r 43� r t a` y r• brt x'" „_, � .c {' � t - -v."Lii.' 3.'fh i rJ `k . k P x : fg w? « , g . r s _E :, t'' .- d , is �' i- , 'X' a - .ri. n r 3 ,: t. S 'S� B I P- .. 's`s" Li � ". f is ' S `�'` . �': r - .-:1 x i b .. .. ,Ta,S t ' s r' Y' ,. ,.-s. A c !' Sr 'si ti 1 iFSr I lam- Y tc'.c'i r ,,}° k.S� Efs f Y4 ' j "_'- - '�t,i:. t ? ic r . '3' _::... t i u . I` • i -, s3 ` r '2t' ", �� : 6 F (.. I Y' ., �7 - 4A Y>` nt - - � � �, r -: e i •^' c� € .� I 2 pk�l. >r �'� : r u- +. 1 ��* y. �'.� ,r rs,.: ra y ' , � r '-�- -� f� r , y t ,� .rr L, I I{ - � a •� '� �. P + �. �~ti " :;. "'� ,r R X' ::- I r�- ' ,..p r s�' *.'+€ ., °, �,.x:s 7 il v+ '+. r.. r : 1 ..:. �' x: � _ �. F'u t.:'" f � ; <':i z . x5:..- } >y ;.. c:' { � �. w� � 5:1�. i� - .�s 7 � gr, r ; tr` r - tF ✓ te�`k k.. ,f. n.t�✓ trT... ti � g. . I .,G... .Y'7 YN�`_'+.. tar s'.d -,:r � '.+'�' t� �,J�s ,;.'; � :t^°�Lr, r1 ., �s 1 : a�. - }Qt � � , }., }.vim. s kt. ��., s.S 5 T^ I ` t .+.. I S r . `••F , { { is , i ,-,, r : u_.. f., t ,, .� a4 .....: ...>rr� --� , x`r r. "•+�.�# .:' 1 t A� E s... "�r. 1 aS..Y � J F.1 4+�'} i T t e� .3 t1'7,"' ,1 . 1 u s y`.S *,s: -pv x 7,J',t, r + F .:;: }5 L:- W Ut!- qtr.: '.5. L T r a+'a ,. c'e A a...; {.G 4T ¢ >" q -i s kf`YY s ' Y,N'q _ -! l+.-y+ F7• . t": '4 k . 0 5.. ° r � 1 .>r. '. 4 .�i: rv. r;�r-4fwr <. .fx .�� ?' ;' , :4y zs y . . e^' y sr : „, ? 7 ../' _.. A' �+y . r :'�^” eY.'y s.,•. e 3 Y E Ti�:tLM V II� I: { }. �` 4 Y "' ✓ {I ,4 : n2 l St '� t.�it �X�.. ,:1ra•.E $,.,5'�, r ��li� L .';t(f �aY ' I;.a a ss "'e i .r �' � .. Y^ f y i y X 4.3 .Y:v�'J .:: y r•, t '':�": i. a:: ,''„F' . S. f }`! i, I ,...�,,. -T- ::u'•sr> a ,ty1,!- i't , :.,p ?, 0i I 'I'I -+'F- ,,��',. a:-�4,� n t:rr:.: x }v• Tx' u- t t L c r. e ' .F.v3',:' e< .>�� r �s d ,E �?.zr >n e r �. r + � � .,t r ,^ Y x*Sd �r ' �^a rArr. � £, . f ' x - n > ar ?-d F'• a rx t Y < . !3 . ' (✓f:.: - i4 . 4 �L b ( 't, +. t..Y.. t Lr y qac ? rlf ,$44 " �.•iL , y .SI! ,�} . � : fi rr 'Y " [.' �2 ;1 t:. JT. �i { tit Ft C'rl4 .`� i 'f .�.r � rt.3iv,.•r {r -w' -� w 1, .aW. ?.r" {.-+ ....:'1 ;•L a' 1 •+f t C "- ?' } f .s,�:,i 1 E. .*1 f :c 1 .i!t . s ,+ fc'.: s ; M1 ^I e, , 4.t.Vi . .f ;, J. Y y .Y n, �:. y 7p. c,� t ...- �4:3:.,r .�i_. ? , h t.- . :...� �..�.:.._ ;. , Y , r ..x. -<;._ ,>F .- i :..,ayu rv' 5. s .x<n..at.,..:.. 7, w : .4...... -.a.W $ . < -. Yi t� . " , ' ,.W?L:wisr. �t... Wiring Diagram GE3 Series with Gentex Synchronization Module FAC.P. • END OF LINE RESISTOR Cg FOR TO NEXT SIGNAL TO NOTIFlCATION ALARM CIRCUIT WIRING ONLY. ___ _____ TO NEXT SIGNAL ,��� TO NOTIFICATION ALARM CIRCUIT REMOVE JUMPER , FOR INDEPENDENT 000 0 0 0. SYNCHRONIZED STROBE AUDIBLE SIGNAL,,v END OF LINE AND HORN OPERATION ""'' " "' °' " RESISTOR FOR CIRCUIT cuss e S YNCH RONIZAT ION ,' w oONLY. LEAVE JUMPERIN PLACE TO ELIMINATE NEED FOR MODULE LEAVE JUMPER IN PLACE ON 0 0 ® HORN INPUT ON AVSM / STAVE UNITS UNLESS SEPARATE ' • / AND OPER SIGNAL IN UNISON MODE ® m m REQWRED IS EORED Z; CONTROL U CRT S YNCHRONIZATION hC/ . • MODULE signal S. S. 5- H+ f+ 0 .2 • •2 . s ® s VISIBLE SIGNAL „ + ' ENO OF LINE ' RESISTOR FOR CIRCUIT _ CUSS WIRING ONLY • END Of LINE • - _____ - -_ -- --- .���_- �__�_�- _ - -_ -� 1 I I I RESISTOR FOR U imic _ -�- GLASSA mead ONLY. ' ' • Note: See Technical Bulletin 015 for proper synchronization module for application. Note: When synchronizing the GE3 12 VDC Series, the AVSM synchronization module MUST be used. • Architect & Engineering Specifications: • • The audible and /or visible signal shall be Gentex GE3 Series or approved equal and shall be listed by Underwriters Laboratories Inc. per UL 1971 and /or UL 464. The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of Standards and Appeals (NYC). • The notification appliance (combination audible /visible) shall produce a peak sound output of 100dBA or greater at 12 or 24V as measured in an ane- choic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the abil- ity to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible /visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 55mA or less at 24 VDC for the 15Cd strobe circuit and 106mA or less at 12 VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with termi- nals with barriers for input /output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16 -33 volts with either direct current of full wave rectified power for 24 volt models or a voltage range of 8 -17.5 volts for 12 volt models. • The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box. The unit shall also be able to verify voltage at the unit without removing unit. • 24 units per carton . 28 pounds per carton "*�.� > , ` r r• T , Ev " ; � _: • r,'x �.+ a .t 2 . N • : ,.. ,y - e' y, �r . J K,y . •. f h AR aT .- „ a`: p ?� ''' ' r " 5 , •' +f . „T�'dL: , >: § r� ::,� "wv"'SS v 4 ,r'�'< �� vhx ^., ' 0;0- l ` n'"� °+ 5 . vS`".T -C : ' J , ' ; y_ , w . a ,'•, ms s:. �{ • Important Notice: "fit -' t • +iry� These materials have been prepared by Gentex Corporation ('Gentex') for informational purposes only, are GE30201 -12 , kd . t necessarily summary. and are not purpoded to serve as legal advice and should not be used as such. � "' Gentex makes no representations and warranties. express or implied. that these materials are complete CORPORATION and accurate. up- to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as mere is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws. regulations and rules to panic - Fire Protection Products: www.gentex.com ular tact padems. Each person's activities can differently affect the obligations that exist under applicable taws, regulations or rules. Therefore, these materials should be used only for informational purposes and 10985 Chicago Drive Box 310 • Zeeland, Michigan 49464 should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax any action or failure to act in reliance upon the information contained in this material. Gentex corporation reserves the right to make changes to the product data sheets at their discretion. Co Printed on Recycled Paper • w Mounting Super Slide'" Switch. Locations Z A r' —� – SMTCH POSITION 5 ' ' Mechamcal-Temp. . ON ON ON h • Mechaniw4Lonk OFF • ON ON tr �% p. .� ,J Hi t. ON OFF ON - '✓ Hi - Coot. OFF OFF ON Chime - Temp. ON ON OFF ,„ r^ . 1� 1 Chime - font OFF - ON OFF �M `' II � ;, f Whoop ON _ OFF OFF \iL a V9fiooa OFF OFF OFF a j I Switch Position 6 w l ON > HIGH dB _.., � ry 1 r % OFF >LOWdB �yn Switch positions 1 and 2 I 1 bl �ry, I f, �� �/ in the off position to select _`� ' y 1 i I [ ' isolated horn and strobe �i power inputs. Die Cast Metal Mounting Plate: Mounts to single gang, 11 ':J '`w , F A 1;1 . ;1 double gang 4" square boxes or GSB box. 1 ON (V(IH .4 3 t� R p H ., H p Checkmate" - Instant Voltage Verification L • Iy r 1 2 3 4 5 6 . El 666.66 UI► - s+ ! o Ca ndela Sel ::::::.: _gl. 1, s+ I ir INN I 1} lr a 3 ' ' _ Candela selection slider switch Depress center ` �__ ��i� /) an d slide s lev el. red t :.+ _ -.r, �;, i •�..,, 1 �'^' 1411 1 l „I Id The access holes are provided in the back of the terminal Break off pin and insert into , hole a to be measured directly without oto r to lock candela setting. at the bottom of the ' block to allow the voltage Y seledo ` A�� removing the device. Typically this would be done at the Signal must be removed from . I l model bracket and pin pushed forward selecton 1 r • • end of the line to confirm design criteria. Most measure- from backside out or hole 1 ments will be taken using the S+ and S- locations ' to changecandda I " a \}� + � ;` 4 i although access is provided to other locations. NOTE: 9 f � Care should be taken to not short the test probes. 42 • Conventional GES3 /GEC3 Series Wiring Diagrams UL Listed UL Listed Control Control Panel Signal Si Panel Signal Signal S+ S+ S- H+ H- S+ S+ S- H+ H- S+ S+ S - H+ H - S+ S+ S - H+ H- Supervised 6 5 0 0 e. O. 0 9 Supervised �. • Signal circuit Signal Circuit g " 11111 11111 OF \ + / END OF LINE \ o I''1 ""II ENO RES STOR O / _ RESISTOR m ill II END OF LINE NE a RESISTOR . • GEH 12 or 24 Volt Low Profile Evacuation Horn Model Number Part Number - Nominal Reverberant dBA @ in Anechoic Room Voltage 10ft. Per UL 464 dBA @10ft. GEH12 -R 904- 1239 -002 12 VDC 62 -82 100 • GEH12 -W . 904 -1241 -002 12 VDC 62 -82 • 100 GEH24 -H 904 -1205 -002 24 VDC 62 -82 100 ' GEH24 -W 904 -1207 -002 24 VDC 62 -82 100 GES3 12 or 24 Volt Selectable Candela Low Profile Evacuation Strobe Model Number Part Number Nominal Candela Voltage (UL 1971) GES3 -12WR 904 - 1235 -002 12 VDC 15, 30, 60, 75 Model designations: tiN .`kEPari9MIN 96 37 -002 =MOM 15, 30, 60, 75 "W" = Wall Mount SN `T IPa,UU:i. •04- 236 -002 15, 30, 61, 7 "R" = Red Faceplate sfN4Yc3Pa,rAryr- • 1.SPAIVINT1MII • 15, 30, 60, 75 "W" = Off -White Faceplate Sei *iPZtii: 904- 321 -002 24 7 B 15, 30, 60, 75, 1 0 "P" = Plain (no lettering) Available 3 -2 904- 319 -012 24 Y If 1 , 31, 60, 5, 110 with all models. GES3 -24PWR 904- 1322 -002 24 VDC 15, 30, 60, 75, 110 These units are non-returnable. GES3 -24PWW •904- 1320 -002 24 VDC 15, 30, 60, 75, 110 "Agent" bezel also available. • GEC3 12 or 24 Volt Selectable Candela Low Profile Evacuation Horn /Strobe Model Number Part Number Nominal Candela Reverberant dBA @ in Anechoic Room Voltage (UL 1971) 10ft Per UL 4641 dBA @ 10ft. GEC3 -12WR 904 -1231 -002 12 VDC 15, 30, 60, 75 62 -82 100 Se1allici5 ►PUirIFIE5PARIiTilti 15, 30, • 0, 7 62 -82 101 SellX0615161 11:1F11131P0C 21711111111111P mmorkm . -: .1 •TV1t 90 1234 -112 1 VI - I, .1, 62 -8 111 904- 1317 -002 24 VDC 15, 30, 60, 75, 110 62 -82 100 .►,y, •I - -11 • v 1 I .0 -_ 1 . -. 11 GEC3 -24PWR 904 - 1318 -002 24•VDC 15, 30, 60, 75, 110 62 -82 100 GEC3 -24PWW 904 - 1316 -002 24 VDC 15, 30, 60, 75, 110 62 -82 100 Notes: • The GE3 Series is not listed for outdoor use. • Operating temperature: 32 °to 120 °F (0° to 49° C). • For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual." 12 volt models are DC only.' • Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products (see Technical Bulletin Number 014). GE3 -12 Product Strobe Current Ratings Candela 15cd nod - 60cd 75cd GE3 -24 Product Strobe Current Ratings 24 voc 106mA 131mA 186mA 237mA Candela 15cd 30cd 60cd 75cd 110cd UL Max 163mA 212mA 331 mA 436mA 24 VDC 55mA 63mA 88mA 112mA 136mA • UL Maxz 78mA 96mA _ 180mA 224mA GE3 -12 Product Horn Current Ratings - Horn Mode Minimum Minimum Regulated GE3 -24 Product Horn Current Ratings dBA @ 10ft. dBA q 10ft. 24VDC Max. Horn Mode Minimum Minimum Regulated per UL464 per UL464 Operating @ dBA @ 10ft. dBA @ 10ft. 24VDC Max. (HIGH) (LOW) High Setting (mA) per UL464 per UL464 Operating @ (HIGH) (LOW) High Setting (mA) Temp 3 2400Hz 76 69 29 Temp 3 2400Hz 78 71' 28 Temp 3 Mechanical 75 68 26 Temp 3 Chime 62 60' 13 T 3 Mechanical 76 70' 25 Temp 3 Chime 70' 66* 15 Continuous 2400Hz 79 74' • 29 Continuous 2400Hz 81 74* 28 tontinuous Mechanical 78 72' 26 Continuous Mechanical 80 72* 25 W 78 71" 55 C Continuous 63* 71' 13 ontmuous Chime 70' 66' 15 w Whoop 82 69' 56 'Operating the horn in this mode at this voltage wit result in not meeting the minimum UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for pub- lic mode application (not applicable when using the chime tone. The chime tone is always private mode). Notes: The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in . the temporal 3 mode its sound pressure is the same as the continuous mode. To obtain the hom /strobe current draw, add the strobe current draw and the hom current draw. 1 The listed reverberant dBA are for the Continuous Tone mode. The Temporal 3 Tone has a reverberant dBA @ 10ft. per UL 464 is 77 -83 with a horn currenedraw of 34mA. 2 RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16 -33VDC for 24VDC units) (8-17VDC for 12VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units) (8VDC for 12VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual. I Y't r: u ,..�.,, !s;r �', e •. .tsf£r' 7+� r - : a .' -^-'!e� ,Sl " ` r ,w <r "�• .,rs y fr "'Ca+ � r`' �{ � „ ��� 1 �r L YI a t''' <. d , ^. : � - •i°'9 ` d t � r '� -''r'� � +� t � na..rt,,:. 5 •kt r s' S A. 4 °` r � ��.•. "' t°x j >; _.�"�' fie,, "..fw'a. •+, N, A'.. >• • F v a,t *r .. -. ,*.,-:,.. 1 x .`�` f, 0 -. , .e�i "' n.'+i 0A . t,..v�! - it7. ..r+� -,s•? x. ��i,�3 -' ,tT�s,. y .•c;. �.. t.>� ..A. ' :'� ? y .,� �{s,r. F.,,C- w .'S�rtC.- y 4. ��:s� F'* '�;fi ���5''� .;�•�- � t :� + L• },- `i .' ,.q.y [. <. �"..> . H'��• "?�,]Yr. ..nJt.: ..6� . �Z�h r {'� u *'�'�.y; r � -:� = •,g:�TS•rn C „.,r,t�{'� ,..,,.�.' � s'�i ,{. � y.,4�• - ... r '?�i•4'r,�; r ' n r�. . �z ::. �f -t b !? Y r. -..., S 'u ��� +t �w"�>,,•� 3 ' t � .: a. a• +, r .'F+ ,a °: I f E 7•�.. "�,.: s$t a . t, ry. �i+t7r ,:� p�.t -• 'S.s�... @' �, ,'?' t i , »•rr. c . .arc � . 1'z'.�. P ... 2• >� ,v, ..d , r . �.ti , rirt, . 7`i, t r�., n � _e,-k: ..t! �. ,: n =si a3 r:. � , ,,., • � 1F rt5 . � i , +9 - k`a,�a ^�`+`"k��n�1. ;r t• -ss< `�� .. �!� ; +,"�� ° �•T�..•,r. ° t tit -'m - , - �' r.,. ..... s ..'�sAw a ,. �. .:, ti,• ,..�.. x - , ,,, , .. :x..>a. , r r, m : , ,.. a .; M .. ;. r, k .rF , y- :~'... { , t •. •. .� f : !•`�� -. .,.. a.:�ar -.. ., r'` .. '4 .k.,:w+, .. llP ^e t r ,l , t- r.L� c ..r rtr A . . . 1 ., ,,, +; •X fy. S' ,t .2r; Yr. r. h�, 3�: '� ✓ �c . ad i s I' i r ti k .; n : a * ,! �' :..tf t x k t :1: 5 .. ... . , t 4 V . i�-S '': =�"'r ;;n• r�.. h:�. .• ��at.,r... c�J'r ,., �,c..rr;^tk, . :'i`��^ 4.; f � .FSt�r r ,...” r 1�-at -°t 4 .y��.t;'SY. �.c,. '�. ?,�`,.+.atf4 r �. .;�;.�r .:. x�] { -.. ¢,. r 1 • { •,N'• � t^ _ a � , ' ti•. "':'� � � h t� � ' y , . c�h��: s fit` vY. x... • ;r�, , i f al.'n', �: al i' s+k f r u a I£ € � ' tii � y � s �� ,cA• ' ,SCN :..,.�„i. w . _ y...s„• a. t_ H . r � . G }S vm r ' ;., rt',sn �' �� � tc ?� r..... � ,�! r±`;''tt ; 3 fria n 2 :gym .�"'} ;. .e,• � T:3'€t' tf. : � �r�f�;..: s3'. .,, i. R«. i ar :; zsL. t+'•b ,4 _. A�i )!.S ,tt . dR ;,7 •'� • . yc ' v.: it _! r x s ri - 1 r Y5, �s --'. } y:' s `r cn' L r .:;J r ' Y c. >! ..,,. +la .,, r ,. c �t { .� z1 c•43 � '� ?� ti s . rz .:�' r �. --c', ,ar �, er r� r:f h, � � - i� ,t-� x +aa- .,� t � ,t} ,�a � .: � � y� F . ,.k. >%�5= � k1 T� �: r T r „ v ws.:< �;�;, 's ..fs �a5'rr� � h � a :. ;.. �'L i - 1 Y. - fI - r''r 3 i1 i W a- „t' Y t-s - t ;.• i } t � t. .+? .J ��""'T' 7� J , 3 �. x. � � t ( r , :tw,Y },"�. a <'�f.,n n,. - s f 1�. , � t rtb,� .r r r, ^r`�. - r. >:, ' ,�:.. r t�. �.. �• r w rei• 11 b�c t ,r . � �. t z t 7` '"{, v - a >6:... 9 - „,, -f �. 2!S vrFr,.;� f m*'. � v +r,,t 3•..Y. e, �,� *'r?L ,sf..:� 3 r -q e '� , t.. e' F�7. ? . r J "S :: ti; .iyrt w hj � r � ti n �t ..k '7s v -, '• ,� rt r' 9} � ' ,. y7 1� � (' ".i, , �, 9 + �9 c � 5 s �. "� Y Y t Taq'. � }r .�- ii-. � 1 t _ l r i�}'�'S::;•t: ; ,,tr ,,.:� z „}t:.�.tht + > >+. y f . .2�::x r f.... •t ......,- . :f .5:^ . {.'. -:. .ti % ..f U v 4 a fx-a:t . { :.�:` : S :� r. "''`{- 1„"�'�.3 i F S` -C i +• ` SG':s t yz f k t � v , _ : ,1 1 .4 , f• ; ;4 71 . • r r, :..- s 4 e77'd.. k +r` �• i. ✓ '� •+� ,�5 ? 1`' s , : t . �� "1�'�� {:t,��5f sa�• d .ft °'1 3'^g3�ra'. t ` • �'e ?�{� . . • - z''y{ 7 rc ' �F,�?;% t u � ..'�,�..n• -tk �t zi'k�i � r _ r . 3 .r -�w r;- �r :; ,�tY t�Y� � .- •,:. -�, raX ,� ks.,� , . n S � r y . „-.3 ., �'�,t1�". "����� � �r,'�, ��JJ �, 9 .. t t f xrN . � �cr�i �'2� r :r. 'd-'"srt4 s� .. � x t�. - .,,a- 7 �� ��.^� �. � r ' ;�� 9 r _ '''.. �• �ts..:.-s. - :. � , :... ,t: .� .. �� ,...�:i�y��,' 3. I�,J -..dL � 3 yI' � � f t ,f r. k 1 p n Y .5� � - d).ii .rt a 4k,Si?,. j.) •i Y 9 fF,. . . Fk .! ,`,,�1,, } 'I.tnLi�A' f �:'{ df } Y t }.: "(I >; ::� ': {� f M ` l J £37 .!R. f E'f� - , 4 ,' ,Ti ,n) - ;,('�.)' 1 ' h '�i 'Y_ N �. ,>r. iL. +htt ,a sf . •Axr.w -:r.. , . .z _: ..ahr .S• .>!:;, ,3 ..- � a%, r'r �.F: .1 ; t r' } It:;. �ii ,M:hi� y , y „; v la,"� *.. t_ 42�3z fi. n.. �,,. +!, , .. r,� t { t�. �, .�ac y ,. t, ,t .. x -•1 1 >`. .. - 1.I , r r �, �5 ��... _.s'v'Y” ,. : -. .,[ X"t Fj.i r•..*'a s "+..f'ii..a�•}r r:', -r W, Y..t �`r; . . .. :x .. !w nPa. 3 $h.,. 51y, „ + r ,.v, ?dc,.?,• I ,.t -i R . J .. ,.: r , � e,rt ; r :4 .. � r. _,.., ,K,x, ... '�:...: r 'r.. J;.a3 r .r... :;: r 'u.: k�. .,,t t i $1"'�!:.. INir ;:r , � , .:.��w Xr _'M 4T: -. 'S .� ..E T . A . 4B ,r � - � :: , r ty -C z It , :,., n 5• a:r.. � ... k � r� � . . ,:e . x.. a A i : i t Cyst . �, •t, „� .. :t kN : t f', r✓iFt f , Jiff,41,14i t ^24 c ,% vr�+ ^ X, ' a' r . M L w K « ` ' yv S ri. . 1, 6..:.r ?y w I _ NR r - .>k'r 1 t �r.J . £�h - .' _. , x �,d . _ r rr ;`! . .� �. . a >.... Q r ? +3 r p ,: t. . �Y n. r nt_�' R "$(�, 9 33 � s.,. ,•• s 3 x 3. ? .A,`�} r`; $a, ` r k .a;.z�>'"”' .' r� � ' r °y L +v4 1 a -p J .T , {j aS4 a rat -;.r '?i.. � •� r I 1 tth_'rt '4F�r'r� K' . •+:E. .s�" R- •(7' "f 1":+ 'Y`t, L. ..d F { !S i D 5 e' ��3 ; /'Jtl r ,.... .. • ._. � '-•- -.:::� ,. t .,, ..., � . _ r r t ntn �: 4rt4s '� x'c- �i ' •r+ -. ' ^ . S Commander Series Selectable GEC3 /GES3 Candela Evacuation Signals 12 & 24 VDC Applications SERIES The Commander Series is a low profile strobe or horn /strobe combination that offers dependable audible and visual alarms and the lowest current available. The GE3 Series 24VDC offers tamperproof field selectable candela options of { 15, 30, 60, 75, and 110 candela. The 12VDC offers tamperproof field selectable 5;„., t`..tj . i � Y candela options of 15, 30, 60, and 75 candela. 0.4` � "'` The Commander 3 Series horn offers a continuous or synchable temporal three R` W ¢' • in 2400Hz and mechanical tone, a chime as well as a whoop tone. All tones are t,t0 a N q easy for the professional to change in the field by using switches. 1 . .:::.r� The GE3 Series has a minimal operation current and has a minimum flash rate of 1 Hz regardless of input voltage. The Commander is shipped with the standard 4" mounting plate which Product Listings incorporates the popular Super-Slide TM feature that allows the installer to easily test for supervision. The product also features a locking mechanism which "' secures the product to the bracket without any screws showing. C US � ', • } Ths symhd on the weeders nameplate mans It is The Commander3 also features the Checkmate - Instant Voltage Verification Lstetl by UNDERWRITERS LAOORATORIES. INC. feature which allows the installer to check the voltage without removing the sig- • BFP (City of Chicago) nal, • BS+A/MEA #285 -91 -E • CSFM 7135 -0569:122 (GEC3 -24 & GEH -24) The GE3 Series appliances are UL 464 and UL 1971, listed for use with fire pro- 7125-0569:123 (GES3-24) (GES3 -12 12) tective systems and are warranted for three years from date of purchase. 7135 - 0569:130 (GEC3 -12 & GEH -12) Standard Features • UL 464 & UL 1971 Listed • CAN /ULC S526 -M87 Listed • Nominal Voltage 12 & 24 VDC • 24 VDC units have field selectable candela options of Product Compliance 15, 30, 60, 75, and 110 candela • NFPA 72 • 12 VDC units have field selectable candela options of • Americans with Disabilities Act (ADA) 15, 30, 60, and 75 candela • GEH horn is available in 12 or 24 Volt ArgWissri • Unit Dimensions: 5" high x 4.5" wide x 2.5" deep MEMBER ASSEMBLED Iw • Prewire Entire System, Then Install Your Signals 1HE W° • Super - SlideTM Bracket - Ease of Supervision Testing • CheckmateTM - Instant Voltage Verification • Surface Mount with the GSB (Gentex Surface • Lower Installation and Operating Costs Mount Box) • Input Terminals 12 to 18 AWG • Synchronize Strobe and /or Horn with AVSM Series • Switch Selection for High or Low dBA Control Module (12 Volt product must use the AVSM • Switch for Chime, Whoop, Mechanical and 2400Hz Module). Tone • Silence Horn While Strobes Remain Flashing • Switch for Continuous or Temporal 3 (not available on • Wide Voltage Range 8 -17.5 VDC (12 Volt Models) whoop tone) 16 -33 VDC or FWR (24 Volt Models) • Tamperproof Re- entrant Grill • Faceplate Available in Red or Off-White