Correspondence • . -6064 November 23, 2002 CITY OF OREGON Roger Superneau Ankrom Moisan Associated Architects 6720 SW Macadam, Suite 100 Portland, OR 97129 Re: Revised Exiting and Alternate Methods of Construction Green Office Building, 11560 SW 67 BUP2001 -00061 Dear Mr. Superneau, We have reviewed the revised exiting plans for the above referenced project as well as the request for alternate methods of construction. Based on the structural conditions of moving the stairways and the stage of construction this project is in, we are approving the alternates subject to the following conditions. This review was performed under the provisions of the State of Oregon Structural Specialty Code (OSSC), 1998 edition and the International Building Code (IBC), 2000 edition. • The current configuration of the exit enclosures does not meet the provisions of OSSC Section 1004.2.4. The overall diagonal of the building is 114 feet requiring the exits to be separated a distance of 57 feet. They are currently 32.5 feet apart. The revised plans show one -hour rated exit passageways on all three floors at the north end of the building. This puts the required exits approximately 38 feet apart. You have requested Exception 2 of IBC Section 1004.2.2.1 be utilized as an alternate which allows the exit separation to be reduced to one -third the overall diagonal when the building is equipped throughout with an automatic sprinkler system. One -third of 114 feet is 38 feet. We understand that an automatic sprinkler system will be installed. The IBC is a nationally recognized document containing similar provisions as the OSSC. In accordance with OSSC Section 104.2.8, for alternates, we believe this provides an equal degree of safety and this request is hereby approved. • OSSC Section 1005.3.4.4 states that openings into exit passageways shall be limited to those necessary for egress from normally occupied areas. The revised • plans show the main floor restrooms opening into the main floor exit passageway. Due to the hardship of reconfiguring the under -slab plumbing and to minimize the possibility of compromising the structural footings, you have requested that we approve an alternate for the existing configuration. Your proposal' is to construct the walls separating the restroom and exit passageway with 2 -hour fire - resistive construction with 90- minute doors. These two restrooms contain only 1 water closet and 1 lavatory each and will only be used by a single occupant at any given time. In accordance with OSSC Section 104.2.8 for alternates methods of construction, we believe this provides an equal degree of safety and this request is hereby approved. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 w The submitted revised drawings by Ankrom Moisan Associated Architects are approved subject to the following conditions. 1. All doors opening into the exit passageways and exit enclosures shall be provided with doors with a maximum transmitted temperature end point not exceeding 450 F above ambient at the end of 30 minutes of the fire exposure specified in UBC Standard 7 -2. OSSC 1005.3.3.5, 1005.3.4.4. 2. Penetrations into or through exit passageways are prohibited except for those serving the exit passageway such as sprinkler piping, standpipes, and electrical conduit terminating is a listed box not exceeding 16 square inches. OSSC 1005.3.4.4. 3. Penetrations into or through exit enclosures are prohibited except for those serving the exit enclosure such as ductwork and equipment necessary for independent stairway pressurization, sprinkler piping, standpipes, and electrical conduit terminating is a listed box not exceeding 16 square inches. OSSC 1005.3.4.4. 4. Automatic - closing fire assemblies shall have one heat - actuating device installed on each side of the wall at the top of the opening and one on each side of the wall at the ceiling height where the ceiling is more than 3 feet above the top of the opening. OSSC Section 713.2, 713.6.1 5. There shall not be enclosed usable space under stairways or ramps in an exit enclosure. The open space under such stairways shall not be used for any purpose. OSSC Section 1005.3.3.6. 6. Exit signs shall be provided and illuminated in accordance with OSSC Sections 1003.2.8 and 1003.2.9. 7. A copy of the approved plans shall be kept on site at all times and made available for inspection purposes. OSSC 106.4.2. If you have any questions or concerns, please contact me at (503) 718 -2448. Sincerely, Gary Lampella Building Official c. Joe Green Mark Hoyt Hap Watkins, Supervising Inspector Jim Hendryx, Director of Community Development File