Specifications •
OUP ati-1
June 21, 2004
CITY OF TIG D
OREGON
McKinstry Company
5400 NE Columbia Boulevard
Portland, OR 97218
RE: SHELL FIRE SPRINKLER SYSTEM
Project Information
Building Permit: BUP2004 -00279 Construction Type: VN
Tenant Name: Green Office Occupancy Type: B
Address: 11560 SW 67 Avenue Occupant Load: NA
Area: NA Stories: 3
Hazard: Light
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
FLUSHING
The fire service mains shall be completely flushed before connection is made to the sprinkler
piping. The flow rate shall not be less than 346.8 gpm. Standard 9 -1, section 8 -2.1 OSSC.
HYDROSTATIC TESTING
All interior piping shall be hydrostatically tested at 200 psi and shall maintain that pressure
without loss for 2 hours. The test pressure shall be read from a gauge located at the low
elevation point of the system or portion being tested. Standard 9 -1, section 8 -2.2.1 OSSC.
GENERAL
1. A key box shall be installed within 20 feet of the riser room entrance. The bottom of
the key box shall be not less than 8 feet nor more than 10 feet above the walking
surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 Contact TVF &R for
keybox at 503- 612 -7010
2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises
so that any sprinklers that have operated or been damaged in any way can be
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
promptly replaced. These sprinklers shall correspond to the types and temperature
ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC
3. A special sprinkler wrench shall be provided and kept in the cabinet along with the
spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1,
section 2 -2.7.2 OSSC
4. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4
inches from walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC
5. Clearances shall be provided around all piping extending through walls, floors,
platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2
inches shall be not less than 1 inch. Minimum clearance for pipes 4 inches and larger
shall be 2 inches. Standard 9 -1, section 4- 5.4.3.4
6. Monitoring, Section 904.3.1 OSSC. All valves controlling the water supply shall be
electrically monitored.
7. An approved audible sprinkler flow alarm shall be provided on the exterior of the
building in an approved location. An approved audible sprinkler flow alarm to alert
the occupants shall be provided in the interior of the building in a normally occupied
location. 904.3.2 OSSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfu
Bria , : lalock,
S 'or Plans Examiner
HYDRAULIC CALCULATIONS
FOR RECEIVED
�-- SUN 15 2004
CITY OF TIGARD
l c(p0 SR) '7 71 AV UILDING DIVISION
) a j 22)
FILE NUMBER: 6W-Ea.
DATE: .. /1 / ,/,;04,..
- DESIGN DATA-
.
OCCUPANCY CLASSIFICATION: 1 604-7' Hazard
DENSITY: gpm /sq. ft.
AREA OF APPLICATION: r500 sq. ft.
COVERAGE PER SPRINKLER: Z Z sq. ft. M4 >-
NUMBER OF SPRINKLERS CALCULATED: 14 sprinklers
TOTAL SPRINKLER' WATER FLOW REQUIRED: Z,-( � gpm
TOTAL WATER REQUIRED (including hose) 34 -i.ia, gpm
FLOW & PRESSURE (at base of riser) : ZL ,, ;, gpm @4 psi
SPRINKLER ORIFICE SIZE: • // V� inch K= o
5". (
NAME OF CONTRACTOR: f1/IL 1 1 ( -- .
DESIGN /LAYOUT BY: ;
AUTHORITY HAVING JURISDICTION: 4, U)
HYDRAULIC CALC'S PERFORMED BY: 67,
•
A SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
4 DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE
JOB TITLE: THE GREEN BUILDING
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 60.0 45.0 1325.0 58.7 346.8 53.1
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 346.8 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 246.8 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 36.0 K= 5.60 7.8 15.6
5 36.0 K= 5.60 8.6 16.5
10 36.0 K= 5.60 9.5 17.3
15 36.0 K= 5.60 11.5 19.0
20 36.0 K= 5.60 7.2 15.0
25 36.0 K= 5.60 8.0 15.8
30 36.0 K= 5.60 8.8 16.6
35 36.0 K= 5.60 11.9 19.3
40 36.0 K= 5.60 8.2 16.1
45 36.0 K= 5.60 9.2 16.9
50 36.0 K= 5.60 10.1 17.8
55 36.0 K= 5.60 12.1 19.5
60 36.0 K= 5.60 13.5 20.6
65 36.0 K= 5.60 13.9 20.9
100 36.0 - - - - 12.3 - - -
105 36.0 - - - - 12.5 - - -
110 36.0 - - - - 13.0 - - -
115 36.0 - - - - 14.2 - - -
200 35.0 - - - - 12.5 - - -
210 35.0 - - - - 13.2 - - -
215 35.0 - - - - 14.6 - - -
TOR 35.0 - - - - 26.2 - - -
BOR 1.0 - - - - 43.6 - - -
DCOUT -3.0 - - - - 47.6 - - -
DCIN -3.0 - - - - 55.6 - - -
SOURCE 3.0 SOURCE 53.1 246.8
.
. ; SPRINKLER SYSTEM HYDRAULIC ANALYSIS Pave 2
` DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE
JOB TITLE: THE GREEN BUILDING
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL /FT (PSI)
Pipe: 1 15.6 1.049 PL 10.75 PF 0.9
5 36.0 5.6 8.6 16.5 5.8 120 FTG - - -- PE 0.0
1 36.0 5.6 7.8 15.6 0.082 TL 10.75 PV
Pipe: 5 32.1 1.380 PL 10.75 PF 0.9
10 36.0 5.6 9.5 17.3 6.9 120 FTG - - -- PE 0.0
5 36.0 5.6 8.6 16.5 0.082 TL 10.75 PV
Pipe: 10 49.4 1.380 PL 10.75 PF 2.0
15 36.0 5.6 11.5 19.0 10.6 120 FTG - - -- PE 0.0
10 36.0 5.6 9.5 17.3 0.182 TL 10.75 PV
Pipe: 15 68.3 1.610 PL 3.92 PF 0.6
200 35.0 0.0 12.5 0.0 10.8 120 FTG - - -- PE -0.4
15 36.0 5.6 11.5 19.0 0.157 TL 3.92 PV
Pipe: 20 15.0 1.049 PL 10.75 PF 0.8
25 36.0 5.6 8.0 15.8 5.6 120 FTG - - -- PE 0.0
20 36.0 5.6 7.2 15.0 0.076 TL 10.75 PV
Pipe: 25 30.8 1.380 PL 10.75 PF 0.8
30 36.0 5.6 8.8 16.6 6.6 120 FTG - - -- PE 0.0
25 36.0 5.6 8.0 15.8 0.076 TL 10.75 PV
Pipe: 30 47.5 1.380 PL 12.00 PF 3.0
35 36.0 5.6 11.9 19.3 10.2 120 FTG 2E PE 0.0
30 36.0 5.6 8.8 16.6 0.169 TL 18.00 PV
Pipe: 35 66.7 1.610 PL 3.92 PF 0.6
105 36.0 0.0 12.5 0.0 10.5 120 FTG - - -- PE 0.0
35 36.0 5.6 11.9 19.3 0.150 TL 3.92 PV
Pipe: 40 16.1 1.049 PL 10.75 PF 0.9
45 36.0 5.6 9.2 16.9 6.0 120 FTG - - -- PE 0.0
40 36.0 5.6 8.2 16.1 0.087 TL 10.75 PV
Pipe: 45 33.0 1.380 PL 10.75 PF 0.9
50 36.0 5.6 10.1 17.8 7.1 120 FTG - - -- PE 0.0
45 36.0 5.6 9.2 16.9 0.086 TL 10.75 PV
Pipe: 50 50.8 1.380 PL 10.75 PF 2.1
55 36.0 5.6 12.1 19.5 10.9 120 FTG - - -- PE 0.0
50 36.0 5.6 10.1 17.8 0.192 TL 10.75 PV
Pipe: 55 70.3 1.610 PL 3.92 PF 0.6
210 35.0 0.0 13.2 0.0 11.1 120 FTG - - -- PE -0.4
55 36.0 5.6 12.1 19.5 0.165 TL 3.92 PV
Pipe: 60 20.6 1.380 PL 10.75 PF 0.4
65 36.0 5.6 13.9 20.9 4.4 120 FTG - - -- PE 0.0
60 36.0 5.6 13.5 20.6 0.036 TL 10.75 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 3/1/2004F:\PORTLAND\PROJECTS\7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE
JOB TITLE: THE GREEN BUILDING
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL /FT (PSI)
Pipe: 65 41.4 1.610 PL 3.92 PF 0.2
215 35.0 0.0 14.6 0.0 6.5 120 FTG - - -- PE -0.4
65 36.0 5.6 13.9 20.9 0.062 TL 3.92 PV
Pipe: 200 -68.3 1.610 PL 1.25 PF 0.2
200 35.0 0.0 12.5 0.0 10.8 120 FTG - - -- PE -0.4
100 36.0 0.0 12.3 0.0 0.157 TL 1.25 PV
Pipe: 210 70.3 1.610 PL 1.25 PF 0.2
110 36.0 0.0 13.0 0.0 11.1 120 FTG - - -- PE 0.4
210 35.0 0.0 13.2 0.0 0.165 TL 1.25 PV
Pipe: 215 41.4 1.610 PL 1.25 PF 0.1
115 36.0 0.0 14.2 0.0 6.5 120 FTG - - -- PE 0.4
215 35.0 0.0 14.6 0.0 0.062 TL 1.25 PV
Pipe: 100 68.3 2.635 PL 11.00 PF 0.2
105 36.0 0.0 12.5 0.0 4.0 120 FTG - - -- PE 0.0
100 36.0 0.0 12.3 0.0 0.014 TL 11.00 PV
Pipe: 105 135.1 2.635 PL 11.00 PF 0.6
110 36.0 0.0 13.0 0.0 7.9 120 FTG - - -- PE 0.0
105 36.0 0.0 12.5 0.0 0.050 TL 11.00 PV
Pipe: 110 205.4 2.635 PL 11.00 PF 1.2
115 36.0 0.0 14.2 0.0 12.1 120 FTG - - -- PE 0.0
110 36.0 0.0 13.0 0.0 0.109 TL 11.00 PV
Pipe: 115 246.8 2.635 PL 29.71 PF 11.6
TOR 35.0 0.0 26.2 0.0 14.5 120 FTG 2L2T PE -0.4
115 36.0 0.0 14.2 0.0 0.153 TL 75.71 PV
Pipe: TOR 246.8 3.260 PL 34.00 PF 2.6
BOR 1.0 0.0 43.6 0.0 9.5 120 FTG B PE -14.7
TOR 35.0 0.0 26.2 0.0 0.054 TL 48.00 PV
Pipe: BOR 246.8 4.240 PL 180.00 PF 2.3
DCOUT -3.0 0.0 47.6 0.0 5.6 150 FTG 4L PE -1.7
BOR 1.0 0.0 43.6 0.0 0.010 TL 228.00 PV
Pipe: DCOUT FIXED PRESSURE LOSS DEVICE
DCIN -3.0 0.0 55.6 0.0 8.0 psi, 246.8 gpm
DCOUT -3.0 0.0 47.6 0.0
Pipe: DCIN 246.8 6.280 PL 30.00 PF 0.1
SOURCE 3.0 SRCE 53.1 (N /A) 2.6 140 FTG GT PE 2.6
DCIN -3.0 0.0 55.6 0.0 0.002 TL 82.00 PV
' SPRINKLER SYSTEM HYDh.AULIC ANALYSIS Page 4
DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE
JOB TITLE: THE GREEN BUILDING
NOTES:
(1) Calculations were performed by the HASS 7.5 computer program
under license no. 3806024810 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.008 gpm and a maximum
imbalance at any node of 0.189 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 14.5 ft /sec at pipe 115.
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 5.00
1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00
1.610 4.00 8.00 2.00 9.00 6.00 1.00 10.00 10.00 8.00
PAGE: B MATERIAL: THNWL HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee
2.635 8.00 17.00 6.00 19.00 10.00 1.00 14.00 14.00 17.00
3.260 10.00 20.00 7.00 22.00 14.00 1.00 18.00 18.00 20.00
PAGE: D MATERIAL: DIRON HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G N
Ell Tee LngEll ChkV1v BfyVly GatV1v NPTee
6.280 22.00 47.00 14.00 51.00 16.00 5.00 47.00
PAGE: E MATERIAL: PVC150 HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in)
Ell Tee LngEll ChkV1v BfyVly GatV1v NPTee
4.240 20.00 39.00 12.00 43.00 23.00 4.00 39.00
o ,
WATER SUPPLY ANALYSIS y
80.0
Static: 60.00 psi Resid: 45.00 psi Flow: 1325.0 gpm O w
LEGEND
Available pressure
1 58.74 psi „ 346.8 gpm y d
70.0 2 Required pressure x 0 .,
51.13 psi 146.8 gpm [t]
A. Source Supply Cure '2]
e. Syetem Demand Curve M -
G L p
A 60.0 �1� W y ro •
U G m
G H z H
L
b z
E 2 x
H ro r
50.0 0 O M
P c,
LT] to
n
c O
S 40.0
3
s
Nx
u o ic
R H u
E 30.0 • >
( M
p 20.0 O z
s
o r
i m Ec
m m
H H
10.0
n m
ro
u
0.0 13'
• z
n
ro
m
-14.7 I I I I I I I I
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM) G)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
' DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE.
JOB TITLE: THE GREEN BUILDING
WATER SUPPLY CURVE
60 * \\
1 0\
1 \\\
1 \\
55+ \ \\ •
1 X \\
1 \ \\
1 \\
50+ \ \\
\\
1 \\
45+ * < -45.0 psi @ 1325 gpm
Flow Test Point
P 40+
R 1
E 1
S 1
S 35+
U I
R I
E I
30+
( 1
P 1
• S 1
I 25+
1
20+
15+
1
I
10+ LEGEND
1 X = Required Water Supply "
53.13 psi @ 346.8 gpm "
5+
1 0 = Available Water Supply "
58.74 psi @ 346.8 gpm
I '
0 + + - + - - -+
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
t t - C .iii; Fire & Building
Products
P.
.� h6
Customer Service /Sales:
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (414) 570 -5000 / (800) 558 -5236
Fax: (414) 570 -5010 / (800) 877 -1295
Series TY- L — 5 ®6 iGfactor
Horizontal Sidewall Sprinklers
Quick lies .onse, Standard Coverage
General Model/Sprinkler
Description Identification
The Series TY -FRL, 5.6 K- factor, Hori- Numbers ;.
zontal Sidewall Sprinklers are quick
response - standard coverage, solder TY3321 - NSW 5.6K, 1 /2 "NPT
type spray sprinklers designed for use +. �
TY3321 is a redesignation for S1878 „•
in light and ordinary hazard, commer- and G8946.
vial occupancies such as banks, ho-
tels, shopping malls, offices, etc. They �.
are designed for installation along a -'
wall or the side of a beam and just
beneath a smooth ceiling. Horizontal
sidewall sprinklers are commonly used Technical
instead of pendent or upright sprin- operation
klers due to aesthetics or building con- Data
struction considerations, where piping The fusible link (heat collector) assem-
across the ceiling is not desirable. Approvals bly is comprised of two halves that are
UL and C -UL Listed. joined together by a thin layer of solder.
WARNINGS FM Approved. When the rated temperature is
The Series TY -FRL Sprinklers de- (Refer to Table A for complete approval reached, the solder melts and the two
scribed herein must be installed and information.) link halves separate, allowing the
maintained in compliance with this sprinkler to operate.
document, as well as with the applica- Maximum Working Pressure
ble standards of the National Fire Pro- 175 psi (12,1 bar)
tection Association, in addition to the Discharge Coefficient Design
standards of any other authorities hav- K = 5.6 GPM /psi (80,6 LPM /bar1 /2) C ie ®teioia
ing jurisdiction. Failure to do so may
impair the integrity of these devices. Temperature Ratings
Refer to Table A The 5.6 K- Factor, Series TY FRL Hori-
The owner is responsible for maintain- F inishes zontal Sidewall Sprinklers are fin-
ing their fire protection system and de- tended for fire protection systems de-
vices in proper operating condition. Sprinkler: Refer to Table A signed in accordance with the
The installing contractor or sprinkler Physical Characteristics standard installation rules recognized
manufacturer should be contacted Frame Bronze by the applicable Listing or Approval
relative to any questions. Strut Monel agency (e.g., UL Listing is based on
Deflector Bronze NFPA 13 requirements); however, the
Hook Monel minimum distance between sprinklers
Link Assembly Nickel to prevent cold soldering is 8 feet (2,4
Ejection Spring Inconel m). The Series TY -FRL Horizontal
Button Bronze Sidewall Sprinkler must be installed
Seal Teflont with a deflector to ceiling distance of 4
t DuPont Registered Trademark to 6 inches (100 to 150 mm). To meet
this requirement the centerline of the
sprinkler waterway must be located 4-
5/16 to 6 -5/16 inches (110 to 160 mm)
below the ceiling. Installation of the
Series TY -FRL Horizontal Sidewall
Sprinklers in recessed escutcheons
will void all manufacturer's warranties,
as well as possibly void the sprinkler's
Approvals and /or Listings.
Page 1 of 4 JANUARY, 2003 YFP140
•
•
Page 2 of 4 TFP140
� 1 /2" "
1 -5/8'
NPT
p i�_ � 1 � � � + �(l
(41.3 mm) Willi 1 1� 1 ���I
WRENCH WRENCH
DEFLECTOR* 6 FLANGES RECESS
WRENCH
3.5° 3 4 5 2 7 8 1
CNI444444IN
AREA CENTERLINE
OF SPRINKLER
=� ^ �1Z.v1v: WATERWAY
"or
� qq
5/16' (7,9 mm) _ FIGURE 2
NOMINAL ' W -TYPE 9 SPRINKLER
WRENCH
7/16' (11,1 mm)
NOMINAL MAKE -IN
DEFLECTOR
BOSS 2„ WALL
(50,8 mm) PLATE SEATING
5/8" 2- 11/16' SURFACE
(15,9 mm) (68,3 mm)
* Temperature rating is indicated on deflector.
` * Pipe thread connections per ISO 7/1 can be provided on
special request.
1 - Frame 3 - Deflector 5 - Link Assembly 7 - Button
2 - Strut 4 - Hook 6 - Ejection Spring 8 - Seal
FIGURE 1
QUICK RESPONSE
SERIES TY -FRL (TY3321) HORIZONTAL SIDEWALL SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
lel to the ceiling and perpendicular to
Installation the back wall surface. The word "TOP"
• on the deflector must face upwards
The Series TY FRL Sprinklers must be toward the ceiling.
installed in accordance with the follow-
ing instructions: • Step 2. After installing an escutcheon
(as applicable) over the sprinkler pipe
NOTES threads and with pipe thread sealant
A leak tight 1/2 inch NPT sprinklerjoint applied to the pipe threads, hand
should be obtained with a torque of 7 tighten the sprinkler into the sprinkler
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- fitting.
mum of 21 ft. lbs. (28,5 Nm) of torque Step 3. Tighten the sprinkler into the
may be used to install sprinklers with sprinkler fitting using only the W -Type
1/2 NPT connections. Higher levels of 9 Sprinkler Wrench (Ref. Figure 2).
torque may distort the sprinkler inlet With reference to Figure 1, the W -Type
and cause leakage or impairment of 9 Sprinkler Wrench is to be applied to
the sprinkler. the wrench area.
Do not attempt to make -up for insuffi-
cient adjustment in the escutcheon
plate by under- or over - tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY - FRL Horizontal Side -
wall Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. The Series TY -FRL Horizontal
Sidewall Sprinklers must be installed
with their centerline of waterway paral-
•
•
TFP94O Page 3 of 4
SPRINKLER FINISH
K TYPE TEMP. FRAME NATURAL CHROME
RATING COLOR BRASS PLATED
CODE
5.6 HORIZONTAL 165 °F /74 °C Unpainted
1/2" SIDEWALL 1, 2, 3
NPT (TY3321) 212 °F /100 °C White
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) for Light or Ordinary Hazard Occupancies as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) for Light or Ordinary Hazard Occupancies as Quick Response
Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) for Light Hazard Occupancies as Quick Response Sprinklers.
TABLE A
LABORATORY LISTINGS AND APPROVALS
��� �� facturer should be contacted relative to UNDER ANY OTHER LEGAL THE -
any questions. ORY, FOR INCIDENTAL, INDIRECT,
It is recommended hat automatic SPECIAL OR CONSEQUENTIAL
Maintenance ler systems inspected, DAMAGES, INCLUDING BUT NOT
sprink stms t be i
sprinkler
and st ee by inspected,
qualified LIMITED TO LABOR CHARGES, RE-
The Series TY -FRL Sprinklers must be GARDLESS OF WHETHER TYCO
maintained and serviced in accord - Inspection Service. FIRE PRODUCTS WAS INFORMED
ance with the following instructions: ABOUT THE POSSIBILITY OF SUCH
Limited DAMAGES, AND IN NO EVENT
NOTES SHALL TYCO FIRE PRODUCTS' LI-
Before closing a fire protection system Warranty ABILITY EXCEED AN AMOUNT
main control valve for maintenance EQUAL TO THE SALES PRICE.
work on the fire protection system that Products manufactured by Tyco Fire THE FOREGOING WARRANTY IS
it controls, permission to shut down the Products are warranted solely to the MADE IN LIEU OF ANY AND ALL,
affected fire protection system must be original Buyer for ten (10) years OTHER WARRANTIES EXPRESS OR
obtained from the proper authorities against defects in material and work-
and all personnel who maybe affected manship when paid for and ro erl �MPLIED.INCLUDING WARRANTIES
by this action must be notified. installed and maintained tained under normal OF MERCHANTA AND FIT -
Absence of an escutcheon, which is use and service. This warranty will ex- F OSS FOR A PARTICULAR PUR-
from date of OSE,
used to cover a clearance hole, may pire ten (10) ship-
years P
delay the time to sprinkler operation in ment by Tyco Fire Products. No war -
a fire situation. ranty is given for products or
S Sprinklers that are found to be leaking components manufactured by compa-
P g nies not affiliated by ownership with
or exhibiting visible signs of corrosion Tyco Fire Products or for products and .
must be replaced. components which have been subject
Automatic sprinklers must never be to misuse, improper installation, corro-
painted, plated, coated or otherwise sion, or which have not been installed,
altered after leaving the factory. Modi- maintained, modified or repaired in ac-
fied or over - heated sprinklers must be cordance with applicable Standards of
replaced. the National Fire Protection Associa-
tion, and /or the standards of any other
Care must be exercised to avoid dam- Authorities Having Jurisdiction. Mate -
age to the sprinklers - before, during, rials found by Tyco Fire Products to be
and after installation. Sprinklers dam- defective shall be either repaired or
aged by dropping, striking, wrench replaced, at Tyco Fire Products' sole
twist/slippage, or the like, must be re- option. Tyco Fire Products neither as-
placed. sumes, nor authorizes any person to
The owner is responsible for the in- assume for it, any other obligation in
spection, testing, and maintenance of connection with the sale of products or
their fire protection system and de- parts of products. Tyco Fire Products
vices in compliance with this docu- shall not be responsible for sprinkler
ment, as well as with the applicable system design errors or inaccurate or
standards of the National Fire Protec- incomplete information supplied by
tion Association (e.g., NFPA 25), in Buyer or Buyer's representatives.
addition to the standards of any other IN NO EVENT SHALL TYCO FIRE
authorities having jurisdiction. The in- PRODUCTS BE LIABLE, IN CON -
stalling contractor or sprinkler manu- TRACT, TORT, STRICT LIABILITY OR
•
Page4of4 TFP140
PIN 58 - XXX - X - XXX
I I
TEMPERATURE
RATING
MODEUSIN SPRINKLER
165 165 °F /74 °C
946 5.6K HSW (1/2 "NPT) TY3321
1 NATURAL BRASS 212 212 °F /100 °C
9 CHROME PLATED
•
TABLE B
PART NUMBER SELECTION
SERIES TY -FRL HORIZONTAL SIDEWALL SPRINKLERS
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model /SIN), Quick
Response, 5.6 K- factor, (specify tem-
perature rating), Series TY FRL Hori-
zontal Sidewall Sprinkler with (specify
type of finish), P/N (specify from Table
B).
Sprinkler Wrench:
Specify: W -Type 9 Sprinkler Wrench,
P/N 56- 000 -1 -849.
•
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
. .
_ , .
,, , .
tqco Fire & Building A\
Products
Customer Service /Sales:
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (414) 570 -5000 / (800) 558 -5236
Fax: (414) 570 -5010 / (800) 877 -1295
Series TY -FRB — 2 8, 4.2, 506, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
chemical to which the sprinklers will be
exposed.
Descr iption An intermediate level versions of the 1 . ,
pt ® ®� Series TY -FRB Pendent Sprinklers are
The Series TY -FRB, 2.8, 4.2, 5.6, and
detailed in Technical Data Sheet ° 1 1 •
s, i;,
8.0 K- factor, Upright and Pendent TFP356, and Sprinkler Guards are de- f
tailed in Technical Data Sheet TFP780 x; tit
Sprinklers described in this data sheet
are quick response - standard cover - "`
age, decorative 3 mm glass bulb type WARNINGS
spray sprinklers designed for use in The Series TY -FRB Sprinklers de-
light or ordinary hazard, commercial scribed herein must be installed and
maintained in compliance with this - •"'•••,•:,.;:.,_ ; :..:=•-'
,. �..:..Y -` e _
occupancies such as banks, hotels, document, as well as with the applica-
shopping malls, etc. ble standards of the National Fire Pro -
The recessed version of the Series tection Association, in addition to the
TY -FRB Pendent Sprinkler, where ap- standards of any other authorities hav
plicable, is intended for use in areas ing jurisdiction. Failure to do so may
with a finished ceiling. It uses either a impair the integrity of these devices. s two -piece Style 10 (1/2 inch NPT) or , '' ! " ,
Style 40 (3/4 inch NPT) Recessed Es- The owner is responsible for maintain- t
-� '
cutcheon with 1/2 inch (12,7 mm) of ing their fire protection system and de- ,. i t
recessed adjustment or u to 3/4 inch vices in proper operating condition. ' `
(19,1 mm) of total adjustment from the The installing contractor or sprinkler I'
flush pendent position, or a two -piece manufacturer should be contacted
Style 20 (1/2 inch NPT) or Style 30 (3/4 relative to any questions. •..' .,T
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust- '
ment or up to 1/2 inch (12,7 mm) of Model/Sprinkler ng Pressure
k
Maximum Working total adjustment from the flush pen- Ma Ma psi (12,1 k
dent position.The adjustment provided Identification )
by the Recessed Escutcheon reduces Discharge Coefficient
the accuracy to which the fixed pipe Numbers K = 2.8 GPM /psi / (40,3 LPM /bar
drops to the sprinklers must be cut. K = 4.2 GPM /psi / (60,5 LPM /bar /
Corrosion resistant coatings, where TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /bar /
applicable, are utilized to extend the TY1231 - Pendent 2.8K, 1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar /
life • of copper alloy sprinklers beyond TY2131 - Upright 4.2K, 1/2 "NPT Temperature Ratings
that which would otherwise be ob- TY2231 - Pendent 4.2K, 1/2 "NPT Refer to Table A and B
tained when exposed to corrosive at- TY3131 - Upright 5.6K, 1/2 "NPT Finishes •
mospheres. Although corrosion resis- -- �TY3231 - Pendent 5.6K, 1/2 "NPT Sprinkler: Refer to Table A and B
tant coated sprinklers have passed the TY4131 - Upright 8.0K, 3/4 "NPT P
standard corrosion tests of the appli- TY4231 - Pendent 8.0K, 3/4 "NPT Recessed Escutcheon: White Coated, x
cable approval agencies, the testing is Chrome Plated, or Brass Plated E
czi
not representative of all possible cor- Technical v
rosive atmospheres. Consequently, it Physical Characteristics i°
is recommended that the end user be Data Frame Bronze
consulted with respect to the suitability Button Brass /Copper E
of these coatings for any given corro- Approvals Sealing Assembly 0
sive environment. The effects of ambi- Beryllium Nickel w/Teflont a
UL and C -UL Listed. Bulb Glass )
eat temperature, concentration of FM, LPCB, and NYC Approved.
chemicals, and gas /chemical velocity, ( RefertoTableAforcompleteapproval Compression Screw Bronze E
should be considered, as a minimum, information includin corrosion resis Deflector Copper /Bronze a
along with the corrosive nature of the tant status.) g Bushing (K =2.8) Bronze rn
•
Page 1 of 8 APRIL, 2003 TFP171
Page 2 of 8 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2„ ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
i \ —_—__..— �° 7 /16 " te r 5
2 -1/4" 1 r ._,_._. � (11 I 4
(57,2 mm) A vs NO NAL I I r AK E -IN 2
1- 9116" � ' %/ ! (55 6 / mm) 1 e � _ 3
(39,7 mm) WRENCH
FLATS = —__ � � 1
7
SSP DEFLECTOR* — 2-7/8" (73,0 mm) DIA. 1/2" NPT ** 1
PENDENT RECESSED PEN NT UPRIGHT CROSS SECTION
1 - Frame . 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compressio 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE S /ES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8.K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or20
PLATE SEATING 1/2 ** NOMINAL RECESSED SSU`
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
• 6
1 �
} ,� �7/1 ) i 5
2- 3/16" mm
(55 ,6 mm) ' di �J��� I N NAI 4
1 L - - �, 1 MA -IN
L
1-1/2" r 1 2- 3/16" � 2
(38,1 mm) �' WREN 1 (55,6 mm) �r 1 -- . - -- ° F. S — i 3
SSP DEFLECTOR* — 2-7/8" (73,0 • DIA. 1/2" NPT **
PENDENT RECESS • PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Co , •ression orifice seat on frame.
crew * * Pipe thread connections per ISO 7/1 can be provided on
special request.
•
FIGURE 2
QUICK RESPON E SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
TFP171 Page 3 of 8 •
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2„ * * NOMINAL RECESSED SSU*
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR •
7 /16" � 5
2- 3/16" 1 111r== (11,1 m
(55,6 mm) II .� 14� � NOMINAL Ali 4
� ` MAKE -I � V
1-1/2" I �r_f 1 2 3/16" ibip 3
2
(38,1 mm) WRENCH 1 (55,6 mm) � , � ` - FLATS �
SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. - 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING 3/4 ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
/
'i'i- --- �,-t1Y ,"TT, %'TT 6*
1 i 12,. l3% 5
2- 5/16" + �� (12,7 m I
(58,7 mm) i t1 ���r NOS L I 4
FIO ��, SAKE -IN 1110 WRENCH 2-1/4" v le 2
1 9/16"
(39,7 mm) II FLATCH (57,2 mm) 3
SSP DEFLECTOR - 2 -7/8" (73,0 ms• CIA. - --- 3/4" NPT **
. PENDENT RECESS a PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - 8 • 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 ompression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Operation Design NFPA 13, and FM Approval is based
I" on the requirements of FM's Loss Pre -
The glass Bulb contains a fluid which Criteria vention Data Sheets ). Only the Style
expands when exposed to heat. When 10, 20, 30, or 40 Recessed Escutch-
the rated temperature is reached, the The Series TY -FRB Pendent and Up - eon, as applicable, is to be used for
fluid expands sufficiently to shatter the right Sprinklers are intended for fire recessed pendent installations.
glass Bulb, allowing the sprinkler to protection systems designed in ac-
activate and water to flow. cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Page 4 of 8 TFP171
SPRINKLER FINISH (See Note 7) Installation
K TYPE TEMP. BULB NATURAL CHROME WHITE***
LIQUID BRASS PLATED POLYESTER The Series TY -FRB Sprinklers must be
• - installed in accordance with the follow -
135°F/57°C Orange ing instructions:
PENDENT 155 °F /68 °C Red
(TY1231) 1, 2, 3, 5 NOTES
and 175 °F/79 °C Yellow Do not install any bulb type sprinkler if
UPRIGHT 200 °F /93 °C Green the bulb is cracked or there is a loss of
(TY1131) liquid from the bulb. With the sprinkler
2 . 8 286 °F /141 °C Blue held horizontally, a small air bubble
1/2" should be present. The diameter of the
NPT 135 °F /57 °C Orange air bubble is approximately 1/16 inch
RECESSED 155 °F /68 °C Red • (1,6 mm) for the 135 °F /57 °C to 3/32
PENDENT inch (2,4 mm) for the 286 °F /141 °C
(TY2231)' 175 °F /79 °C - low temperature ratings.
Figure 5 200 °F /93 °' Green 1, 2, 5
A leak tight 1/2 inch NPT sprinkler joint
13 ' /57 °C Orange should be obtained with a torque of 7
RECESSED 155 °F /68 °C Red to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi -
PENDE. mum of 21 ft. lbs. (28,5 Nm) of torque
(TY ° 1)" 175 °F /79 °C Yellow may be used to install sprinklers with
• . igure 6 200 °F /93 °C Green 1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
135°F/57°C Orange tained with a torque of 10 to 20 ft.lbs.
PENDENT 155 °F168 °C Red (13,4 to 26,8 Nm). A maximum of 30
(TY2231) ft.lbs. (40,7 Nm) of torque is to be used
and 175 °F /79 °C Yellow to install sprinklers with 3/4 NPT con -
UPRIGHT nections. Higher levels of torque may
200 °F /93 °C Green distort the sprinkler inlet and cause
4.2 (TY3131) leakage or impairment of the sprinkler.
286 °F /141 °C Blue 1 2 9 P P
1/2" Do not attempt to make - up for insuffi
NPT 135 °F /57 °C Or. • se
RECESSED cient adjustment in the escutcheon
155 °F /68 °C Red
PENDENT plate by under- or over - tightening the
(TY2231)' 175° •°C Yellow sprinkler. Readjust the position of the
Figure 7 sprinkler fitting to suit.
9 40 °F /93 °C Green
The Series TY -FRB Pendent and Up-
135°F/57°C Orange right Sprinklers must be installed in
R ■ SSED 155 °F /68 °C Red accordance with the following instruc-
• ENDENT tions.
(TY2231)** 175 °F /79 °C Yellow Step 1. Pendent sprinklers are to be
Figure 8 200 °F /93 °C Green installed in the pendent position, and
upright sprinklers are to be installed in
NOTES: the upright position.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step 2. With pipe thread sealant a
plied 2
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C - UL) as Quick Response S thread
Sprinklers. p the pipe d hand tighten
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin the sprinkler into the sprinkler fitting.
klers. Step 3. Tighten the sprinkler into the
5. Approved by the City of New York under MEA 354 -01 -E. sprinkler fitting using only the W - Type
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- 6 Sprinkler Wrench (Ref. Figure 13).
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. - Figures 1, 2, 3, an
to d
F
' Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Re- 4, the With reference en 6 o F igurer Wrench is d
Installed cessed lith y as applicable. be applied to the sprinkler wrench
" Installed ied with Style 20 (1 /2
ith Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Re- flats. pp p
cessed Escutcheon, as applicable.
"' Frame and Deflector only. Listings and approvals apply to all colors (Special Order).
N /A: Not Available The Series TY -FRB Recessed Pen-
dent Sprinklers must be installed in
TABLE A accordance with the following instruc-
LABORATORY LISTINGS AND APPROVALS tions.
2.8 AND 4.2 K- FACTOR SPRINKLERS Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
•
•
•
TFP171 Page5of8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL CHROME WHITE *" LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131)
286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)' 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
135 °F /57 °C Orange •
RECESSED 155 °F /68 °C Red
� PENDENT 1,2,3,4,5 1,2,4,5 N/A
(TY3231)" 175 °F /79 °C Yellow
Figure 10 200F/93°C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231) 1, 2, 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6
UPRIGHT 200 °F /93 °C Green
8 0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)' 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow
135 °F /57 °C 4 range
RECESSED
155° •8 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY42 175 °F /79 °C Yellow
_ • • ure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB) as Quick Response Sprinklers; however, the LPC does not rate the thermal
sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53 -428- 3377).
7. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
• Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
• Installed with Style 10.(1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
"' Frame and Deflector only. Listings and approvals apply to all colors (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
sprinkler fitting using only the W -Type Step C. After the ceiling has been in- ,
7 Recessed Sprinkler Wrench (Ref. stalled or the finish coat has been ap-
Figure 14). With reference to Figure 1, plied, slide on the Style 10, 20, 30, or
2, 3, and 4, the W -Type 7 Recessed 40 Closure over the Series TY -FRB
Sprinkler Wrench is to be applied to Sprinkler and push the Closure over
the sprinkler wrench flats. the Mounting Plate until its flange
comes in contact with the ceiling.
t
ti ,
Page 6 of 8 TFP171
2 -7/8" DIA. 2 -7/8" DIA.
(73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" (12,7 mm)
5/8±1 /4" 1 /2 ±1 /8"
(15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF
(57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER ' PLATE
FITTING FITTING
1/8" 1/8"
��' (3,2 mm) - �i (3,2 mm) r e r
\ �, SURFACE 1
MOUNTING
SURFACE rir'!1�i .4/.9 �
•
CLOSURE
CLOSURE SERIES
1 -5/16° (33,3 mm) SERIES 1 -5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm)
FIGURE 5 FIGURE 6
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8" DIA.
(73,0 mm) 3/4° (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm)
5/8 ±1 /4"
(15,9 ±6,4 mm) 2 -1/4" DIA. y 1/4° (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
�� (3,2 mm) 1,.
I (3,2 mm)
il�lli 11�11
I ,.�;. � 1 1 \ , A
MOUNTING Il, i
MOUNTING
\ � , SURFACE �.
■
SURFACE ------ - - - - -- -- - --
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
• WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may and after installation. Sprinklers dam-
C are and delay the time to sprinkler operation in aged by dropping, striking, wrench
w �
a fire situation. twist/slippage, or the like, must be re-
M aintenance Sprinklers that are found to be leaking placed. Also, replace any sprinkler that
exhibiting visible signs of corrosion has a cracked bulb or that has lost
or ex
The Series TY -FRB Sprinklers must be liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec-
painted, plated, coated or otherwise ommended to be initially performed for
NOTES altered after leaving the factory. Modi- corrosion resistant coated sprinklers,
Before closing a fire protection system fied sprinklers must be replaced. after the installation has been com-
main control valve for maintenance Sprinklers that have been exposed to pleted, to verify the integrity of the cor-
work on the fire protection system that corrosive products of combustion, but rosion resistant coating. Thereafter,
it controls, permission to shut down the have not operated, should be replaced annual inspections per NFPA 25
affected fire protection system must be if they cannot be completely cleaned should suffice; however, instead of in-
obtained from the proper authorities by wiping the sprinkler with a cloth or specting from the floor level, a random
and all personnel who maybe affected by brushing it with a soft bristle brush. sampling of close -up visual random
by this action must be notified. Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
' N
TFP171 Page 7 of 8
2 -7/8" DIA. 2 -7/8" DIA.
5/8x1/4"
(73,0 mm) 3/4" (19,1 mm) 1/2x1/8" (73,0 mm) 1/2" (12,7 mm)
(15,9±6,4 mm) 2-1/4" /4' DIA. y 1/4" (6,4 mm) (12,7x3,2 mm) r 2 -1/4" DIA. 1/4" (6,4 mm)
• FACE OF (57,2 mm) MOUNTING FACE OF . (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
��' (3,2 mm) �� (3,2 mm)
ir. M-e • •••
1
; , � r }
J M OUNTING ,
MOUNTING } SURFACE I _
SURFACE ='r ,
CLOSURE SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm)
CLOSURE TY -FRB
TY -FRB 3/4" (19,1 mm) 1" (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. _ 2 -7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2' (12,7 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (12;7x3,2 mm) 2 -1/4° DIA. 1/4" (6,4 mm)
(57,2 mm) MOUNTING
FACE OF (57,2 mm) MOUNTING FACE OF
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8'
(3,2 mm) u (3,2 mm)
min.- -.ma •
■
AEI it rie 1 \ = =mi U
' . } MOUNTING MOUNTING SURFACE i
SURFACE Al .
CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm)
TY -FRB 13/16' (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE '11 FIGURE 12
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may c RECESS
be affected by the corrosive conditions \
present.
WRENCH RECESS r)
The owner is responsible for the in- (END "A" USED FOR n
spection, testing, and maintenance of 1/2" NPT MODELS) / >
their fire protection system and de- ) u �
vices in compliance with this docu- `�
ment, as well as with the applicable .-�'
standards of the National Fire Protec- WRENCH RECESS PUSH WRENCH
tion Association (e.g., NFPA 25), in (END "B" USED FOR IN TO ENSURE
addition to the standards of any other 3/4" NPT MODELS) ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
facturershould be contacted relative to W -TYPE 6 SPRINKLER
any questions. WRENCH
It is recommended that automatic FIGURE 14
sprinkler systems be inspected, W -TYPE 7 RECESSED
tested, and maintained by a qualified SPRINKLER WRENCH
Inspection Service.
• N e
Page 8 of 8 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1' NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1/2 "NPT) TY2231 9 CHROME PLATED 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 7 LEAD COATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.OK PENDENT (3/4 "NPT) TY4231
TABLE C
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
. ORY, FOR INCIDENTAL, INDIRECT, cutcheon with (specify finish), P/N
Limited SPECIAL OR CONSEQUENTIAL (specify).
DAMAGES, INCLUDING BUT NOT
Warranty LIMITED TO LABOR CHARGES, RE- 1/2" (15 mm)
GARDLESS OF WHETHER TYCO Style 10
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED Chrome Plated P/N 56- 701 -9 -010
Y Y 1/2" (15 mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT White Color
against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- Coated P/N 56- 701 -4 -010
manship when paid for and properly ABILITY EXCEED AN AMOUNT 1/2" (15 mm)
Style 10
installed and maintained under normal EQUAL TO THE SALES PRICE. Brass Plated P/N 56- 701 -2 -010
use and service. This warranty will ex THE FOREGOING WARRANTY IS 1/z (15 mm)
pire ten (10) years from date of ship- Style 20
ment by Tyco Fire Products. No war- M ADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56- 705 -9 -010
rant is given for products or OTHER WARRANTIES EXPRESS OR 1/2" (15mm) Style 20
components manufactured by compa- IMPLIED. WARRANTIES White Color
Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Coated P/N 56- 705 -4 -010
Tyco Fire Products or for products and N ESS FOR A PARTICULAR PUR- 1/2" (15 mm)
components which have been subject POSE. Style 20
installation, corro- Brass Plated P/N 56- 705 -2 -010
to misuse, improper
3/4" (20 mm)
sion, or which have not been installed, Style 30
maintained, modified or repaired in ac- Ordering Chrome Plated P/N 56- 705 -9 -011
cordance with applicable Standards of ,,p 3/4" (20 mm)
the National Fire Protection Associa- Procedure Style 30
White Color
tion, and /or the standards of any other
Coated P/N 56- 705 -4 -011
Authorities Having Jurisdiction. Mate - When placing an order, indicate the full 3/4" (20 mm)
rials found by Tyco Fire Products to be roduct name. Refer to the Price List Style 30
defective shall be either repaired or p Brass Plated P/N 56- 705 -2 -011
P for complete listing of Part Numbers. 3/4" (2o mm)
' replaced, at Tyco Fire Products sole ,
style 40
option. Tyco Fire Products neither as- Contact your local distributor for avail- Chrome Plated P/N 56- 700 -9 -010
'\ sumes, nor authorizes any person to ability. 3/4" (20 mm)
■ assume for it, any other obligation in Style a c olor
\ Sprinkler Assemblies with NPT
connection with the sale of products or P Coated P/N 56- 700 -4 -010
parts of products. Tyco Fire Products Thread Connections: 3 /4" (20 mm)
shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick Style 40
system design errors or inaccurate or Response, (specify K- factor), (specify Brass Plated P/N 56- 700 -2 -010
incomplete information supplied by temperature rating), Series TY -FRB
Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler Sprinkler Wrench:
with (specify type of finish or coating), Specify: W -Type 6 Sprinkler Wrench,
IN NO EVENT SHALL TYCO FIRE P/N (specify from Table C). P/N 56- 000 -6 -387.