Specifications • OUP ati-1 June 21, 2004 CITY OF TIG D OREGON McKinstry Company 5400 NE Columbia Boulevard Portland, OR 97218 RE: SHELL FIRE SPRINKLER SYSTEM Project Information Building Permit: BUP2004 -00279 Construction Type: VN Tenant Name: Green Office Occupancy Type: B Address: 11560 SW 67 Avenue Occupant Load: NA Area: NA Stories: 3 Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. FLUSHING The fire service mains shall be completely flushed before connection is made to the sprinkler piping. The flow rate shall not be less than 346.8 gpm. Standard 9 -1, section 8 -2.1 OSSC. HYDROSTATIC TESTING All interior piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for 2 hours. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. Standard 9 -1, section 8 -2.2.1 OSSC. GENERAL 1. A key box shall be installed within 20 feet of the riser room entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 Contact TVF &R for keybox at 503- 612 -7010 2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC 3. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2 OSSC 4. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4 inches from walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC 5. Clearances shall be provided around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2 inches shall be not less than 1 inch. Minimum clearance for pipes 4 inches and larger shall be 2 inches. Standard 9 -1, section 4- 5.4.3.4 6. Monitoring, Section 904.3.1 OSSC. All valves controlling the water supply shall be electrically monitored. 7. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. An approved audible sprinkler flow alarm to alert the occupants shall be provided in the interior of the building in a normally occupied location. 904.3.2 OSSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfu Bria , : lalock, S 'or Plans Examiner HYDRAULIC CALCULATIONS FOR RECEIVED �-- SUN 15 2004 CITY OF TIGARD l c(p0 SR) '7 71 AV UILDING DIVISION ) a j 22) FILE NUMBER: 6W-Ea. DATE: .. /1 / ,/,;04,.. - DESIGN DATA- . OCCUPANCY CLASSIFICATION: 1 604-7' Hazard DENSITY: gpm /sq. ft. AREA OF APPLICATION: r500 sq. ft. COVERAGE PER SPRINKLER: Z Z sq. ft. M4 >- NUMBER OF SPRINKLERS CALCULATED: 14 sprinklers TOTAL SPRINKLER' WATER FLOW REQUIRED: Z,-( � gpm TOTAL WATER REQUIRED (including hose) 34 -i.ia, gpm FLOW & PRESSURE (at base of riser) : ZL ,, ;, gpm @4 psi SPRINKLER ORIFICE SIZE: • // V� inch K= o 5". ( NAME OF CONTRACTOR: f1/IL 1 1 ( -- . DESIGN /LAYOUT BY: ; AUTHORITY HAVING JURISDICTION: 4, U) HYDRAULIC CALC'S PERFORMED BY: 67, • A SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 4 DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE JOB TITLE: THE GREEN BUILDING WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 60.0 45.0 1325.0 58.7 346.8 53.1 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 346.8 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 246.8 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 36.0 K= 5.60 7.8 15.6 5 36.0 K= 5.60 8.6 16.5 10 36.0 K= 5.60 9.5 17.3 15 36.0 K= 5.60 11.5 19.0 20 36.0 K= 5.60 7.2 15.0 25 36.0 K= 5.60 8.0 15.8 30 36.0 K= 5.60 8.8 16.6 35 36.0 K= 5.60 11.9 19.3 40 36.0 K= 5.60 8.2 16.1 45 36.0 K= 5.60 9.2 16.9 50 36.0 K= 5.60 10.1 17.8 55 36.0 K= 5.60 12.1 19.5 60 36.0 K= 5.60 13.5 20.6 65 36.0 K= 5.60 13.9 20.9 100 36.0 - - - - 12.3 - - - 105 36.0 - - - - 12.5 - - - 110 36.0 - - - - 13.0 - - - 115 36.0 - - - - 14.2 - - - 200 35.0 - - - - 12.5 - - - 210 35.0 - - - - 13.2 - - - 215 35.0 - - - - 14.6 - - - TOR 35.0 - - - - 26.2 - - - BOR 1.0 - - - - 43.6 - - - DCOUT -3.0 - - - - 47.6 - - - DCIN -3.0 - - - - 55.6 - - - SOURCE 3.0 SOURCE 53.1 246.8 . . ; SPRINKLER SYSTEM HYDRAULIC ANALYSIS Pave 2 ` DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE JOB TITLE: THE GREEN BUILDING PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 1 15.6 1.049 PL 10.75 PF 0.9 5 36.0 5.6 8.6 16.5 5.8 120 FTG - - -- PE 0.0 1 36.0 5.6 7.8 15.6 0.082 TL 10.75 PV Pipe: 5 32.1 1.380 PL 10.75 PF 0.9 10 36.0 5.6 9.5 17.3 6.9 120 FTG - - -- PE 0.0 5 36.0 5.6 8.6 16.5 0.082 TL 10.75 PV Pipe: 10 49.4 1.380 PL 10.75 PF 2.0 15 36.0 5.6 11.5 19.0 10.6 120 FTG - - -- PE 0.0 10 36.0 5.6 9.5 17.3 0.182 TL 10.75 PV Pipe: 15 68.3 1.610 PL 3.92 PF 0.6 200 35.0 0.0 12.5 0.0 10.8 120 FTG - - -- PE -0.4 15 36.0 5.6 11.5 19.0 0.157 TL 3.92 PV Pipe: 20 15.0 1.049 PL 10.75 PF 0.8 25 36.0 5.6 8.0 15.8 5.6 120 FTG - - -- PE 0.0 20 36.0 5.6 7.2 15.0 0.076 TL 10.75 PV Pipe: 25 30.8 1.380 PL 10.75 PF 0.8 30 36.0 5.6 8.8 16.6 6.6 120 FTG - - -- PE 0.0 25 36.0 5.6 8.0 15.8 0.076 TL 10.75 PV Pipe: 30 47.5 1.380 PL 12.00 PF 3.0 35 36.0 5.6 11.9 19.3 10.2 120 FTG 2E PE 0.0 30 36.0 5.6 8.8 16.6 0.169 TL 18.00 PV Pipe: 35 66.7 1.610 PL 3.92 PF 0.6 105 36.0 0.0 12.5 0.0 10.5 120 FTG - - -- PE 0.0 35 36.0 5.6 11.9 19.3 0.150 TL 3.92 PV Pipe: 40 16.1 1.049 PL 10.75 PF 0.9 45 36.0 5.6 9.2 16.9 6.0 120 FTG - - -- PE 0.0 40 36.0 5.6 8.2 16.1 0.087 TL 10.75 PV Pipe: 45 33.0 1.380 PL 10.75 PF 0.9 50 36.0 5.6 10.1 17.8 7.1 120 FTG - - -- PE 0.0 45 36.0 5.6 9.2 16.9 0.086 TL 10.75 PV Pipe: 50 50.8 1.380 PL 10.75 PF 2.1 55 36.0 5.6 12.1 19.5 10.9 120 FTG - - -- PE 0.0 50 36.0 5.6 10.1 17.8 0.192 TL 10.75 PV Pipe: 55 70.3 1.610 PL 3.92 PF 0.6 210 35.0 0.0 13.2 0.0 11.1 120 FTG - - -- PE -0.4 55 36.0 5.6 12.1 19.5 0.165 TL 3.92 PV Pipe: 60 20.6 1.380 PL 10.75 PF 0.4 65 36.0 5.6 13.9 20.9 4.4 120 FTG - - -- PE 0.0 60 36.0 5.6 13.5 20.6 0.036 TL 10.75 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 3/1/2004F:\PORTLAND\PROJECTS\7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE JOB TITLE: THE GREEN BUILDING PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 65 41.4 1.610 PL 3.92 PF 0.2 215 35.0 0.0 14.6 0.0 6.5 120 FTG - - -- PE -0.4 65 36.0 5.6 13.9 20.9 0.062 TL 3.92 PV Pipe: 200 -68.3 1.610 PL 1.25 PF 0.2 200 35.0 0.0 12.5 0.0 10.8 120 FTG - - -- PE -0.4 100 36.0 0.0 12.3 0.0 0.157 TL 1.25 PV Pipe: 210 70.3 1.610 PL 1.25 PF 0.2 110 36.0 0.0 13.0 0.0 11.1 120 FTG - - -- PE 0.4 210 35.0 0.0 13.2 0.0 0.165 TL 1.25 PV Pipe: 215 41.4 1.610 PL 1.25 PF 0.1 115 36.0 0.0 14.2 0.0 6.5 120 FTG - - -- PE 0.4 215 35.0 0.0 14.6 0.0 0.062 TL 1.25 PV Pipe: 100 68.3 2.635 PL 11.00 PF 0.2 105 36.0 0.0 12.5 0.0 4.0 120 FTG - - -- PE 0.0 100 36.0 0.0 12.3 0.0 0.014 TL 11.00 PV Pipe: 105 135.1 2.635 PL 11.00 PF 0.6 110 36.0 0.0 13.0 0.0 7.9 120 FTG - - -- PE 0.0 105 36.0 0.0 12.5 0.0 0.050 TL 11.00 PV Pipe: 110 205.4 2.635 PL 11.00 PF 1.2 115 36.0 0.0 14.2 0.0 12.1 120 FTG - - -- PE 0.0 110 36.0 0.0 13.0 0.0 0.109 TL 11.00 PV Pipe: 115 246.8 2.635 PL 29.71 PF 11.6 TOR 35.0 0.0 26.2 0.0 14.5 120 FTG 2L2T PE -0.4 115 36.0 0.0 14.2 0.0 0.153 TL 75.71 PV Pipe: TOR 246.8 3.260 PL 34.00 PF 2.6 BOR 1.0 0.0 43.6 0.0 9.5 120 FTG B PE -14.7 TOR 35.0 0.0 26.2 0.0 0.054 TL 48.00 PV Pipe: BOR 246.8 4.240 PL 180.00 PF 2.3 DCOUT -3.0 0.0 47.6 0.0 5.6 150 FTG 4L PE -1.7 BOR 1.0 0.0 43.6 0.0 0.010 TL 228.00 PV Pipe: DCOUT FIXED PRESSURE LOSS DEVICE DCIN -3.0 0.0 55.6 0.0 8.0 psi, 246.8 gpm DCOUT -3.0 0.0 47.6 0.0 Pipe: DCIN 246.8 6.280 PL 30.00 PF 0.1 SOURCE 3.0 SRCE 53.1 (N /A) 2.6 140 FTG GT PE 2.6 DCIN -3.0 0.0 55.6 0.0 0.002 TL 82.00 PV ' SPRINKLER SYSTEM HYDh.AULIC ANALYSIS Page 4 DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE JOB TITLE: THE GREEN BUILDING NOTES: (1) Calculations were performed by the HASS 7.5 computer program under license no. 3806024810 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.008 gpm and a maximum imbalance at any node of 0.189 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14.5 ft /sec at pipe 115. (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD.PIP PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 5.00 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 10.00 10.00 8.00 PAGE: B MATERIAL: THNWL HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 2.635 8.00 17.00 6.00 19.00 10.00 1.00 14.00 14.00 17.00 3.260 10.00 20.00 7.00 22.00 14.00 1.00 18.00 18.00 20.00 PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkV1v BfyVly GatV1v NPTee 6.280 22.00 47.00 14.00 51.00 16.00 5.00 47.00 PAGE: E MATERIAL: PVC150 HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) Ell Tee LngEll ChkV1v BfyVly GatV1v NPTee 4.240 20.00 39.00 12.00 43.00 23.00 4.00 39.00 o , WATER SUPPLY ANALYSIS y 80.0 Static: 60.00 psi Resid: 45.00 psi Flow: 1325.0 gpm O w LEGEND Available pressure 1 58.74 psi „ 346.8 gpm y d 70.0 2 Required pressure x 0 ., 51.13 psi 146.8 gpm [t] A. Source Supply Cure '2] e. Syetem Demand Curve M - G L p A 60.0 �1� W y ro • U G m G H z H L b z E 2 x H ro r 50.0 0 O M P c, LT] to n c O S 40.0 3 s Nx u o ic R H u E 30.0 • > ( M p 20.0 O z s o r i m Ec m m H H 10.0 n m ro u 0.0 13' • z n ro m -14.7 I I I I I I I I 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) G) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 ' DATE: 3/1/2004F: \PORTLAND \PROJECTS \7120 THE GREEN OFFICE BUILDING \FIRE DRAWINGS \GRE. JOB TITLE: THE GREEN BUILDING WATER SUPPLY CURVE 60 * \\ 1 0\ 1 \\\ 1 \\ 55+ \ \\ • 1 X \\ 1 \ \\ 1 \\ 50+ \ \\ \\ 1 \\ 45+ * < -45.0 psi @ 1325 gpm Flow Test Point P 40+ R 1 E 1 S 1 S 35+ U I R I E I 30+ ( 1 P 1 • S 1 I 25+ 1 20+ 15+ 1 I 10+ LEGEND 1 X = Required Water Supply " 53.13 psi @ 346.8 gpm " 5+ 1 0 = Available Water Supply " 58.74 psi @ 346.8 gpm I ' 0 + + - + - - -+ 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) t t - C .iii; Fire & Building Products P. .� h6 Customer Service /Sales: Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (414) 570 -5000 / (800) 558 -5236 Fax: (414) 570 -5010 / (800) 877 -1295 Series TY- L — 5 ®6 iGfactor Horizontal Sidewall Sprinklers Quick lies .onse, Standard Coverage General Model/Sprinkler Description Identification The Series TY -FRL, 5.6 K- factor, Hori- Numbers ;. zontal Sidewall Sprinklers are quick response - standard coverage, solder TY3321 - NSW 5.6K, 1 /2 "NPT type spray sprinklers designed for use +. � TY3321 is a redesignation for S1878 „• in light and ordinary hazard, commer- and G8946. vial occupancies such as banks, ho- tels, shopping malls, offices, etc. They �. are designed for installation along a -' wall or the side of a beam and just beneath a smooth ceiling. Horizontal sidewall sprinklers are commonly used Technical instead of pendent or upright sprin- operation klers due to aesthetics or building con- Data struction considerations, where piping The fusible link (heat collector) assem- across the ceiling is not desirable. Approvals bly is comprised of two halves that are UL and C -UL Listed. joined together by a thin layer of solder. WARNINGS FM Approved. When the rated temperature is The Series TY -FRL Sprinklers de- (Refer to Table A for complete approval reached, the solder melts and the two scribed herein must be installed and information.) link halves separate, allowing the maintained in compliance with this sprinkler to operate. document, as well as with the applica- Maximum Working Pressure ble standards of the National Fire Pro- 175 psi (12,1 bar) tection Association, in addition to the Discharge Coefficient Design standards of any other authorities hav- K = 5.6 GPM /psi (80,6 LPM /bar1 /2) C ie ®teioia ing jurisdiction. Failure to do so may impair the integrity of these devices. Temperature Ratings Refer to Table A The 5.6 K- Factor, Series TY FRL Hori- The owner is responsible for maintain- F inishes zontal Sidewall Sprinklers are fin- ing their fire protection system and de- tended for fire protection systems de- vices in proper operating condition. Sprinkler: Refer to Table A signed in accordance with the The installing contractor or sprinkler Physical Characteristics standard installation rules recognized manufacturer should be contacted Frame Bronze by the applicable Listing or Approval relative to any questions. Strut Monel agency (e.g., UL Listing is based on Deflector Bronze NFPA 13 requirements); however, the Hook Monel minimum distance between sprinklers Link Assembly Nickel to prevent cold soldering is 8 feet (2,4 Ejection Spring Inconel m). The Series TY -FRL Horizontal Button Bronze Sidewall Sprinkler must be installed Seal Teflont with a deflector to ceiling distance of 4 t DuPont Registered Trademark to 6 inches (100 to 150 mm). To meet this requirement the centerline of the sprinkler waterway must be located 4- 5/16 to 6 -5/16 inches (110 to 160 mm) below the ceiling. Installation of the Series TY -FRL Horizontal Sidewall Sprinklers in recessed escutcheons will void all manufacturer's warranties, as well as possibly void the sprinkler's Approvals and /or Listings. Page 1 of 4 JANUARY, 2003 YFP140 • • Page 2 of 4 TFP140 � 1 /2" " 1 -5/8' NPT p i�_ � 1 � � � + �(l (41.3 mm) Willi 1 1� 1 ���I WRENCH WRENCH DEFLECTOR* 6 FLANGES RECESS WRENCH 3.5° 3 4 5 2 7 8 1 CNI444444IN AREA CENTERLINE OF SPRINKLER =� ^ �1Z.v1v: WATERWAY "or � qq 5/16' (7,9 mm) _ FIGURE 2 NOMINAL ' W -TYPE 9 SPRINKLER WRENCH 7/16' (11,1 mm) NOMINAL MAKE -IN DEFLECTOR BOSS 2„ WALL (50,8 mm) PLATE SEATING 5/8" 2- 11/16' SURFACE (15,9 mm) (68,3 mm) * Temperature rating is indicated on deflector. ` * Pipe thread connections per ISO 7/1 can be provided on special request. 1 - Frame 3 - Deflector 5 - Link Assembly 7 - Button 2 - Strut 4 - Hook 6 - Ejection Spring 8 - Seal FIGURE 1 QUICK RESPONSE SERIES TY -FRL (TY3321) HORIZONTAL SIDEWALL SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT lel to the ceiling and perpendicular to Installation the back wall surface. The word "TOP" • on the deflector must face upwards The Series TY FRL Sprinklers must be toward the ceiling. installed in accordance with the follow- ing instructions: • Step 2. After installing an escutcheon (as applicable) over the sprinkler pipe NOTES threads and with pipe thread sealant A leak tight 1/2 inch NPT sprinklerjoint applied to the pipe threads, hand should be obtained with a torque of 7 tighten the sprinkler into the sprinkler to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- fitting. mum of 21 ft. lbs. (28,5 Nm) of torque Step 3. Tighten the sprinkler into the may be used to install sprinklers with sprinkler fitting using only the W -Type 1/2 NPT connections. Higher levels of 9 Sprinkler Wrench (Ref. Figure 2). torque may distort the sprinkler inlet With reference to Figure 1, the W -Type and cause leakage or impairment of 9 Sprinkler Wrench is to be applied to the sprinkler. the wrench area. Do not attempt to make -up for insuffi- cient adjustment in the escutcheon plate by under- or over - tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. The Series TY - FRL Horizontal Side - wall Sprinklers must be installed in accordance with the following instruc- tions. Step 1. The Series TY -FRL Horizontal Sidewall Sprinklers must be installed with their centerline of waterway paral- • • TFP94O Page 3 of 4 SPRINKLER FINISH K TYPE TEMP. FRAME NATURAL CHROME RATING COLOR BRASS PLATED CODE 5.6 HORIZONTAL 165 °F /74 °C Unpainted 1/2" SIDEWALL 1, 2, 3 NPT (TY3321) 212 °F /100 °C White NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) for Light or Ordinary Hazard Occupancies as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) for Light or Ordinary Hazard Occupancies as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) for Light Hazard Occupancies as Quick Response Sprinklers. TABLE A LABORATORY LISTINGS AND APPROVALS ��� �� facturer should be contacted relative to UNDER ANY OTHER LEGAL THE - any questions. ORY, FOR INCIDENTAL, INDIRECT, It is recommended hat automatic SPECIAL OR CONSEQUENTIAL Maintenance ler systems inspected, DAMAGES, INCLUDING BUT NOT sprink stms t be i sprinkler and st ee by inspected, qualified LIMITED TO LABOR CHARGES, RE- The Series TY -FRL Sprinklers must be GARDLESS OF WHETHER TYCO maintained and serviced in accord - Inspection Service. FIRE PRODUCTS WAS INFORMED ance with the following instructions: ABOUT THE POSSIBILITY OF SUCH Limited DAMAGES, AND IN NO EVENT NOTES SHALL TYCO FIRE PRODUCTS' LI- Before closing a fire protection system Warranty ABILITY EXCEED AN AMOUNT main control valve for maintenance EQUAL TO THE SALES PRICE. work on the fire protection system that Products manufactured by Tyco Fire THE FOREGOING WARRANTY IS it controls, permission to shut down the Products are warranted solely to the MADE IN LIEU OF ANY AND ALL, affected fire protection system must be original Buyer for ten (10) years OTHER WARRANTIES EXPRESS OR obtained from the proper authorities against defects in material and work- and all personnel who maybe affected manship when paid for and ro erl �MPLIED.INCLUDING WARRANTIES by this action must be notified. installed and maintained tained under normal OF MERCHANTA AND FIT - Absence of an escutcheon, which is use and service. This warranty will ex- F OSS FOR A PARTICULAR PUR- from date of OSE, used to cover a clearance hole, may pire ten (10) ship- years P delay the time to sprinkler operation in ment by Tyco Fire Products. No war - a fire situation. ranty is given for products or S Sprinklers that are found to be leaking components manufactured by compa- P g nies not affiliated by ownership with or exhibiting visible signs of corrosion Tyco Fire Products or for products and . must be replaced. components which have been subject Automatic sprinklers must never be to misuse, improper installation, corro- painted, plated, coated or otherwise sion, or which have not been installed, altered after leaving the factory. Modi- maintained, modified or repaired in ac- fied or over - heated sprinklers must be cordance with applicable Standards of replaced. the National Fire Protection Associa- tion, and /or the standards of any other Care must be exercised to avoid dam- Authorities Having Jurisdiction. Mate - age to the sprinklers - before, during, rials found by Tyco Fire Products to be and after installation. Sprinklers dam- defective shall be either repaired or aged by dropping, striking, wrench replaced, at Tyco Fire Products' sole twist/slippage, or the like, must be re- option. Tyco Fire Products neither as- placed. sumes, nor authorizes any person to The owner is responsible for the in- assume for it, any other obligation in spection, testing, and maintenance of connection with the sale of products or their fire protection system and de- parts of products. Tyco Fire Products vices in compliance with this docu- shall not be responsible for sprinkler ment, as well as with the applicable system design errors or inaccurate or standards of the National Fire Protec- incomplete information supplied by tion Association (e.g., NFPA 25), in Buyer or Buyer's representatives. addition to the standards of any other IN NO EVENT SHALL TYCO FIRE authorities having jurisdiction. The in- PRODUCTS BE LIABLE, IN CON - stalling contractor or sprinkler manu- TRACT, TORT, STRICT LIABILITY OR • Page4of4 TFP140 PIN 58 - XXX - X - XXX I I TEMPERATURE RATING MODEUSIN SPRINKLER 165 165 °F /74 °C 946 5.6K HSW (1/2 "NPT) TY3321 1 NATURAL BRASS 212 212 °F /100 °C 9 CHROME PLATED • TABLE B PART NUMBER SELECTION SERIES TY -FRL HORIZONTAL SIDEWALL SPRINKLERS Ordering Procedure When placing an order, indicate the full product name. Refer to the Price List for complete listing of Part Numbers. Contact your local distributor for avail- ability. Sprinkler Assemblies with NPT Thread Connections: Specify: (Specify Model /SIN), Quick Response, 5.6 K- factor, (specify tem- perature rating), Series TY FRL Hori- zontal Sidewall Sprinkler with (specify type of finish), P/N (specify from Table B). Sprinkler Wrench: Specify: W -Type 9 Sprinkler Wrench, P/N 56- 000 -1 -849. • TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 . . _ , . ,, , . tqco Fire & Building A\ Products Customer Service /Sales: Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (414) 570 -5000 / (800) 558 -5236 Fax: (414) 570 -5010 / (800) 877 -1295 Series TY -FRB — 2 8, 4.2, 506, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General chemical to which the sprinklers will be exposed. Descr iption An intermediate level versions of the 1 . , pt ® ®� Series TY -FRB Pendent Sprinklers are The Series TY -FRB, 2.8, 4.2, 5.6, and detailed in Technical Data Sheet ° 1 1 • s, i;, 8.0 K- factor, Upright and Pendent TFP356, and Sprinkler Guards are de- f tailed in Technical Data Sheet TFP780 x; tit Sprinklers described in this data sheet are quick response - standard cover - "` age, decorative 3 mm glass bulb type WARNINGS spray sprinklers designed for use in The Series TY -FRB Sprinklers de- light or ordinary hazard, commercial scribed herein must be installed and maintained in compliance with this - •"'•••,•:,.;:.,_ ; :..:=•-' ,. �..:..Y -` e _ occupancies such as banks, hotels, document, as well as with the applica- shopping malls, etc. ble standards of the National Fire Pro - The recessed version of the Series tection Association, in addition to the TY -FRB Pendent Sprinkler, where ap- standards of any other authorities hav plicable, is intended for use in areas ing jurisdiction. Failure to do so may with a finished ceiling. It uses either a impair the integrity of these devices. s two -piece Style 10 (1/2 inch NPT) or , '' ! " , Style 40 (3/4 inch NPT) Recessed Es- The owner is responsible for maintain- t -� ' cutcheon with 1/2 inch (12,7 mm) of ing their fire protection system and de- ,. i t recessed adjustment or u to 3/4 inch vices in proper operating condition. ' ` (19,1 mm) of total adjustment from the The installing contractor or sprinkler I' flush pendent position, or a two -piece manufacturer should be contacted Style 20 (1/2 inch NPT) or Style 30 (3/4 relative to any questions. •..' .,T inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of recessed adjust- ' ment or up to 1/2 inch (12,7 mm) of Model/Sprinkler ng Pressure k Maximum Working total adjustment from the flush pen- Ma Ma psi (12,1 k dent position.The adjustment provided Identification ) by the Recessed Escutcheon reduces Discharge Coefficient the accuracy to which the fixed pipe Numbers K = 2.8 GPM /psi / (40,3 LPM /bar drops to the sprinklers must be cut. K = 4.2 GPM /psi / (60,5 LPM /bar / Corrosion resistant coatings, where TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /bar / applicable, are utilized to extend the TY1231 - Pendent 2.8K, 1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar / life • of copper alloy sprinklers beyond TY2131 - Upright 4.2K, 1/2 "NPT Temperature Ratings that which would otherwise be ob- TY2231 - Pendent 4.2K, 1/2 "NPT Refer to Table A and B tained when exposed to corrosive at- TY3131 - Upright 5.6K, 1/2 "NPT Finishes • mospheres. Although corrosion resis- -- �TY3231 - Pendent 5.6K, 1/2 "NPT Sprinkler: Refer to Table A and B tant coated sprinklers have passed the TY4131 - Upright 8.0K, 3/4 "NPT P standard corrosion tests of the appli- TY4231 - Pendent 8.0K, 3/4 "NPT Recessed Escutcheon: White Coated, x cable approval agencies, the testing is Chrome Plated, or Brass Plated E czi not representative of all possible cor- Technical v rosive atmospheres. Consequently, it Physical Characteristics i° is recommended that the end user be Data Frame Bronze consulted with respect to the suitability Button Brass /Copper E of these coatings for any given corro- Approvals Sealing Assembly 0 sive environment. The effects of ambi- Beryllium Nickel w/Teflont a UL and C -UL Listed. Bulb Glass ) eat temperature, concentration of FM, LPCB, and NYC Approved. chemicals, and gas /chemical velocity, ( RefertoTableAforcompleteapproval Compression Screw Bronze E should be considered, as a minimum, information includin corrosion resis Deflector Copper /Bronze a along with the corrosive nature of the tant status.) g Bushing (K =2.8) Bronze rn • Page 1 of 8 APRIL, 2003 TFP171 Page 2 of 8 TFP171 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2„ ** NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR i \ —_—__..— �° 7 /16 " te r 5 2 -1/4" 1 r ._,_._. � (11 I 4 (57,2 mm) A vs NO NAL I I r AK E -IN 2 1- 9116" � ' %/ ! (55 6 / mm) 1 e � _ 3 (39,7 mm) WRENCH FLATS = —__ � � 1 7 SSP DEFLECTOR* — 2-7/8" (73,0 mm) DIA. 1/2" NPT ** 1 PENDENT RECESSED PEN NT UPRIGHT CROSS SECTION 1 - Frame . 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compressio 7 - Bushing orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE S /ES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8.K-FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or20 PLATE SEATING 1/2 ** NOMINAL RECESSED SSU` SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR • 6 1 � } ,� �7/1 ) i 5 2- 3/16" mm (55 ,6 mm) ' di �J��� I N NAI 4 1 L - - �, 1 MA -IN L 1-1/2" r 1 2- 3/16" � 2 (38,1 mm) �' WREN 1 (55,6 mm) �r 1 -- . - -- ° F. S — i 3 SSP DEFLECTOR* — 2-7/8" (73,0 • DIA. 1/2" NPT ** PENDENT RECESS • PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Co , •ression orifice seat on frame. crew * * Pipe thread connections per ISO 7/1 can be provided on special request. • FIGURE 2 QUICK RESPON E SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT TFP171 Page 3 of 8 • ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2„ * * NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR • 7 /16" � 5 2- 3/16" 1 111r== (11,1 m (55,6 mm) II .� 14� � NOMINAL Ali 4 � ` MAKE -I � V 1-1/2" I �r_f 1 2 3/16" ibip 3 2 (38,1 mm) WRENCH 1 (55,6 mm) � , � ` - FLATS � SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. - 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING 3/4 ** NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR / 'i'i- --- �,-t1Y ,"TT, %'TT 6* 1 i 12,. l3% 5 2- 5/16" + �� (12,7 m I (58,7 mm) i t1 ���r NOS L I 4 FIO ��, SAKE -IN 1110 WRENCH 2-1/4" v le 2 1 9/16" (39,7 mm) II FLATCH (57,2 mm) 3 SSP DEFLECTOR - 2 -7/8" (73,0 ms• CIA. - --- 3/4" NPT ** . PENDENT RECESS a PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - 8 • 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 ompression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT Listing is based on the requirements of Operation Design NFPA 13, and FM Approval is based I" on the requirements of FM's Loss Pre - The glass Bulb contains a fluid which Criteria vention Data Sheets ). Only the Style expands when exposed to heat. When 10, 20, 30, or 40 Recessed Escutch- the rated temperature is reached, the The Series TY -FRB Pendent and Up - eon, as applicable, is to be used for fluid expands sufficiently to shatter the right Sprinklers are intended for fire recessed pendent installations. glass Bulb, allowing the sprinkler to protection systems designed in ac- activate and water to flow. cordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Page 4 of 8 TFP171 SPRINKLER FINISH (See Note 7) Installation K TYPE TEMP. BULB NATURAL CHROME WHITE*** LIQUID BRASS PLATED POLYESTER The Series TY -FRB Sprinklers must be • - installed in accordance with the follow - 135°F/57°C Orange ing instructions: PENDENT 155 °F /68 °C Red (TY1231) 1, 2, 3, 5 NOTES and 175 °F/79 °C Yellow Do not install any bulb type sprinkler if UPRIGHT 200 °F /93 °C Green the bulb is cracked or there is a loss of (TY1131) liquid from the bulb. With the sprinkler 2 . 8 286 °F /141 °C Blue held horizontally, a small air bubble 1/2" should be present. The diameter of the NPT 135 °F /57 °C Orange air bubble is approximately 1/16 inch RECESSED 155 °F /68 °C Red • (1,6 mm) for the 135 °F /57 °C to 3/32 PENDENT inch (2,4 mm) for the 286 °F /141 °C (TY2231)' 175 °F /79 °C - low temperature ratings. Figure 5 200 °F /93 °' Green 1, 2, 5 A leak tight 1/2 inch NPT sprinkler joint 13 ' /57 °C Orange should be obtained with a torque of 7 RECESSED 155 °F /68 °C Red to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi - PENDE. mum of 21 ft. lbs. (28,5 Nm) of torque (TY ° 1)" 175 °F /79 °C Yellow may be used to install sprinklers with • . igure 6 200 °F /93 °C Green 1/2 NPT connections. A leak tight 3/4 inch NPT sprinkler joint should be ob- 135°F/57°C Orange tained with a torque of 10 to 20 ft.lbs. PENDENT 155 °F168 °C Red (13,4 to 26,8 Nm). A maximum of 30 (TY2231) ft.lbs. (40,7 Nm) of torque is to be used and 175 °F /79 °C Yellow to install sprinklers with 3/4 NPT con - UPRIGHT nections. Higher levels of torque may 200 °F /93 °C Green distort the sprinkler inlet and cause 4.2 (TY3131) leakage or impairment of the sprinkler. 286 °F /141 °C Blue 1 2 9 P P 1/2" Do not attempt to make - up for insuffi NPT 135 °F /57 °C Or. • se RECESSED cient adjustment in the escutcheon 155 °F /68 °C Red PENDENT plate by under- or over - tightening the (TY2231)' 175° •°C Yellow sprinkler. Readjust the position of the Figure 7 sprinkler fitting to suit. 9 40 °F /93 °C Green The Series TY -FRB Pendent and Up- 135°F/57°C Orange right Sprinklers must be installed in R ■ SSED 155 °F /68 °C Red accordance with the following instruc- • ENDENT tions. (TY2231)** 175 °F /79 °C Yellow Step 1. Pendent sprinklers are to be Figure 8 200 °F /93 °C Green installed in the pendent position, and upright sprinklers are to be installed in NOTES: the upright position. 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step 2. With pipe thread sealant a plied 2 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C - UL) as Quick Response S thread Sprinklers. p the pipe d hand tighten 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin the sprinkler into the sprinkler fitting. klers. Step 3. Tighten the sprinkler into the 5. Approved by the City of New York under MEA 354 -01 -E. sprinkler fitting using only the W - Type 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- 6 Sprinkler Wrench (Ref. Figure 13). klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. - Figures 1, 2, 3, an to d F ' Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Re- 4, the With reference en 6 o F igurer Wrench is d Installed cessed lith y as applicable. be applied to the sprinkler wrench " Installed ied with Style 20 (1 /2 ith Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Re- flats. pp p cessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to all colors (Special Order). N /A: Not Available The Series TY -FRB Recessed Pen- dent Sprinklers must be installed in TABLE A accordance with the following instruc- LABORATORY LISTINGS AND APPROVALS tions. 2.8 AND 4.2 K- FACTOR SPRINKLERS Step A. After installing the Style 10. 20, 30, or 40 Mounting Plate, as appli- cable, over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprin- kler into the sprinkler fitting. Step B. Tighten the sprinkler into the • • • TFP171 Page5of8 SPRINKLER FINISH (See Note 7) K TYPE TEMP. BULB NATURAL CHROME WHITE *" LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)' 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green 135 °F /57 °C Orange • RECESSED 155 °F /68 °C Red � PENDENT 1,2,3,4,5 1,2,4,5 N/A (TY3231)" 175 °F /79 °C Yellow Figure 10 200F/93°C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) 1, 2, 5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6 UPRIGHT 200 °F /93 °C Green 8 0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135 °F /57 °C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)' 175 °F /79 °C Red Figure 11 200 °F /93 °C Yellow 135 °F /57 °C 4 range RECESSED 155° •8 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY42 175 °F /79 °C Yellow _ • • ure 12 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB) as Quick Response Sprinklers; however, the LPC does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53 -428- 3377). 7. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as • Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. • Installed with Style 10.(1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. • Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to all colors (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS sprinkler fitting using only the W -Type Step C. After the ceiling has been in- , 7 Recessed Sprinkler Wrench (Ref. stalled or the finish coat has been ap- Figure 14). With reference to Figure 1, plied, slide on the Style 10, 20, 30, or 2, 3, and 4, the W -Type 7 Recessed 40 Closure over the Series TY -FRB Sprinkler Wrench is to be applied to Sprinkler and push the Closure over the sprinkler wrench flats. the Mounting Plate until its flange comes in contact with the ceiling. t ti , Page 6 of 8 TFP171 2 -7/8" DIA. 2 -7/8" DIA. (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" (12,7 mm) 5/8±1 /4" 1 /2 ±1 /8" (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER ' PLATE FITTING FITTING 1/8" 1/8" ��' (3,2 mm) - �i (3,2 mm) r e r \ �, SURFACE 1 MOUNTING SURFACE rir'!1�i .4/.9 � • CLOSURE CLOSURE SERIES 1 -5/16° (33,3 mm) SERIES 1 -5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8" DIA. (73,0 mm) 3/4° (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm) 5/8 ±1 /4" (15,9 ±6,4 mm) 2 -1/4" DIA. y 1/4° (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" �� (3,2 mm) 1,. I (3,2 mm) il�lli 11�11 I ,.�;. � 1 1 \ , A MOUNTING Il, i MOUNTING \ � , SURFACE �. ■ SURFACE ------ - - - - -- -- - -- CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT • WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT used to cover a clearance hole, may and after installation. Sprinklers dam- C are and delay the time to sprinkler operation in aged by dropping, striking, wrench w � a fire situation. twist/slippage, or the like, must be re- M aintenance Sprinklers that are found to be leaking placed. Also, replace any sprinkler that exhibiting visible signs of corrosion has a cracked bulb or that has lost or ex The Series TY -FRB Sprinklers must be liquid from its bulb. (Ref. Installation maintained and serviced in accord- must be replaced. Section). ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec- painted, plated, coated or otherwise ommended to be initially performed for NOTES altered after leaving the factory. Modi- corrosion resistant coated sprinklers, Before closing a fire protection system fied sprinklers must be replaced. after the installation has been com- main control valve for maintenance Sprinklers that have been exposed to pleted, to verify the integrity of the cor- work on the fire protection system that corrosive products of combustion, but rosion resistant coating. Thereafter, it controls, permission to shut down the have not operated, should be replaced annual inspections per NFPA 25 affected fire protection system must be if they cannot be completely cleaned should suffice; however, instead of in- obtained from the proper authorities by wiping the sprinkler with a cloth or specting from the floor level, a random and all personnel who maybe affected by brushing it with a soft bristle brush. sampling of close -up visual random by this action must be notified. Care must be exercised to avoid dam- tions should be made, so as to better Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- ' N TFP171 Page 7 of 8 2 -7/8" DIA. 2 -7/8" DIA. 5/8x1/4" (73,0 mm) 3/4" (19,1 mm) 1/2x1/8" (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 2-1/4" /4' DIA. y 1/4" (6,4 mm) (12,7x3,2 mm) r 2 -1/4" DIA. 1/4" (6,4 mm) • FACE OF (57,2 mm) MOUNTING FACE OF . (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" ��' (3,2 mm) �� (3,2 mm) ir. M-e • ••• 1 ; , � r } J M OUNTING , MOUNTING } SURFACE I _ SURFACE ='r , CLOSURE SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm) CLOSURE TY -FRB TY -FRB 3/4" (19,1 mm) 1" (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. _ 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2' (12,7 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (12;7x3,2 mm) 2 -1/4° DIA. 1/4" (6,4 mm) (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING FACE OF SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8' (3,2 mm) u (3,2 mm) min.- -.ma • ■ AEI it rie 1 \ = =mi U ' . } MOUNTING MOUNTING SURFACE i SURFACE Al . CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) TY -FRB 13/16' (20,6 mm) TY -FRB 1 -1/16' (27,0 mm) FIGURE '11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may c RECESS be affected by the corrosive conditions \ present. WRENCH RECESS r) The owner is responsible for the in- (END "A" USED FOR n spection, testing, and maintenance of 1/2" NPT MODELS) / > their fire protection system and de- ) u � vices in compliance with this docu- `� ment, as well as with the applicable .-�' standards of the National Fire Protec- WRENCH RECESS PUSH WRENCH tion Association (e.g., NFPA 25), in (END "B" USED FOR IN TO ENSURE addition to the standards of any other 3/4" NPT MODELS) ENGAGEMENT authorities having jurisdiction. The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA facturershould be contacted relative to W -TYPE 6 SPRINKLER any questions. WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected, W -TYPE 7 RECESSED tested, and maintained by a qualified SPRINKLER WRENCH Inspection Service. • N e Page 8 of 8 TFP171 P/N 57 - XXX - X - XXX I I TEMPERATURE MODEUSIN RATING SPRINKLER 330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1/2 "NPT) TY1231 1' NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1/2 "NPT) TY2231 9 CHROME PLATED 200 200 °F /93 °C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 7 LEAD COATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.OK PENDENT (3/4 "NPT) TY4231 TABLE C PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS . ORY, FOR INCIDENTAL, INDIRECT, cutcheon with (specify finish), P/N Limited SPECIAL OR CONSEQUENTIAL (specify). DAMAGES, INCLUDING BUT NOT Warranty LIMITED TO LABOR CHARGES, RE- 1/2" (15 mm) GARDLESS OF WHETHER TYCO Style 10 Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED Chrome Plated P/N 56- 701 -9 -010 Y Y 1/2" (15 mm) Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10 original Buyer for ten (10) years DAMAGES, AND IN NO EVENT White Color against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- Coated P/N 56- 701 -4 -010 manship when paid for and properly ABILITY EXCEED AN AMOUNT 1/2" (15 mm) Style 10 installed and maintained under normal EQUAL TO THE SALES PRICE. Brass Plated P/N 56- 701 -2 -010 use and service. This warranty will ex THE FOREGOING WARRANTY IS 1/z (15 mm) pire ten (10) years from date of ship- Style 20 ment by Tyco Fire Products. No war- M ADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56- 705 -9 -010 rant is given for products or OTHER WARRANTIES EXPRESS OR 1/2" (15mm) Style 20 components manufactured by compa- IMPLIED. WARRANTIES White Color Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Coated P/N 56- 705 -4 -010 Tyco Fire Products or for products and N ESS FOR A PARTICULAR PUR- 1/2" (15 mm) components which have been subject POSE. Style 20 installation, corro- Brass Plated P/N 56- 705 -2 -010 to misuse, improper 3/4" (20 mm) sion, or which have not been installed, Style 30 maintained, modified or repaired in ac- Ordering Chrome Plated P/N 56- 705 -9 -011 cordance with applicable Standards of ,,p 3/4" (20 mm) the National Fire Protection Associa- Procedure Style 30 White Color tion, and /or the standards of any other Coated P/N 56- 705 -4 -011 Authorities Having Jurisdiction. Mate - When placing an order, indicate the full 3/4" (20 mm) rials found by Tyco Fire Products to be roduct name. Refer to the Price List Style 30 defective shall be either repaired or p Brass Plated P/N 56- 705 -2 -011 P for complete listing of Part Numbers. 3/4" (2o mm) ' replaced, at Tyco Fire Products sole , style 40 option. Tyco Fire Products neither as- Contact your local distributor for avail- Chrome Plated P/N 56- 700 -9 -010 '\ sumes, nor authorizes any person to ability. 3/4" (20 mm) ■ assume for it, any other obligation in Style a c olor \ Sprinkler Assemblies with NPT connection with the sale of products or P Coated P/N 56- 700 -4 -010 parts of products. Tyco Fire Products Thread Connections: 3 /4" (20 mm) shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick Style 40 system design errors or inaccurate or Response, (specify K- factor), (specify Brass Plated P/N 56- 700 -2 -010 incomplete information supplied by temperature rating), Series TY -FRB Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler Sprinkler Wrench: with (specify type of finish or coating), Specify: W -Type 6 Sprinkler Wrench, IN NO EVENT SHALL TYCO FIRE P/N (specify from Table C). P/N 56- 000 -6 -387. PRODUCTS BE LIABLE, IN CON- TRACT, TORT, STRICT LIABILITY OR Recessed Escutcheon: Specify: W -Type 7 Sprinkler Wrench, UNDER ANY OTHER LEGAL THE Specify: Style (specify) Recessed Es- P/N 56- 850 -4 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446