Correspondence (45) Monday, January 02, 2006 2:27 PM Peter Drake 503 - 654 -4642 3v` p .01 J PETER DRAKE, ARCHITECT I r , 11205 8.E. HOME AVE MILWAUKIE, OR 97222 (5D3) -4642 EmailTodarchOcomcast. net 3 Jan 2006 City Of Tigard Inspector Dan 503 -624 -3681 RE: JohnsonlHall Addition and Remodel at 9095 SW 66 MST 2006 -00130 Dan, I was asked to provide a calculation for the new floor joists that was used in this project. Original plans called out 2x12 #1 or better @ 16" O.C., but owner ended up using 2x12 #2 or better @ 16" O.C. My calculation uses a 40# LL and 15 # DL. You will see that the joists are adequate by 15 %. Please include these calculations with the permit set and sign off the framing inspection. If you need to talk to me directly during the day, l can be reached at the City Of Portland at 823- 7717. Tpank. obi 411 i 11 f eter Ora e,': A i . lea J 1 Architecture Interiors Planning Monday, January 02, 2006 2:27 PM Peter Drake 503 - 654 -4642 p.02 Floor Joist( 98 International One -and Two - Family Dwelling Code (97 NOS) 1 Ver: 5.05 By: Peter Drake, Architect , Peter Drake, Architect on: 12 -31 -2005: 09:51:43 AM Protect: Joanscat - Location: Floor joists Summary: 1.5 IN x 11.25 IN x 16.08 FT Q 16 O.C. / #2 - Douglas Fir -Larch - Dry Use Section Adequate By: 15.1% Controlling Factor: Section Modulus / Depth Required 10.48 In Center Span Deflections: DLO -Center= 0.11 IN Dead Load: LLD- Center= 0.28 IN = L/685 Total l Load: Loaoa : d: TLD- Center= 0.39 IN = U498 To Center Span Left End Reactions (Support A): LL Rxn -A� 429 L8 Dead Load: ea Load: DL_� -A= 161 LB B Total Load: TL-Rxn-A 590 L6 Bearing Length Required (Beam only, Support capacity not checked): BL-A. 0.63 IN Center Span Right End Reactions (Support By LL- Rxn -6= 429 LB Lea Load: DL_�_S= 161 LB Total Load; Dead Load: TL Rxn - B= 590 LB T Bearing Length Required (Beam only, Support capacity not checked): BL -6= 0.63 IN Joist Data: 1.2= 16,08 FT Center Span Length: Floor sheathing applied to top Of Joists -top of joists fully braced. 1 Cd= 00 Live Load Duration Factor. = Live Load Deflect. Criteria: L/ 360 Total Load Deflect. Criteria: Center Span Loading: Uniform Floor Loading: LL-2= 40.0 PSF Dead Load: a Load: DL -2= 15.0 PSF e Total Load: TL -2= 55.0 PSF Total Load Adjusted for Joist Spacing: w T_2= 73 PLF Properties For #2- Douglas Fir -Larch = 900 PSI Bending Stress: FFb 95 PSI Shear Stress: v= 1600000 PSI Modulus of Elasticity: Er-- 625 PSI Stress Perpendicular to Grain: Adjusted Properties Fb'= 1035 PSI Fb' (Tension): Adjustment Factors: Cd =1.00 Cf=1.00 Cr =1.15 '� 95 PSI Fv': Re= Adjustment Factors: Cd =1.00 Design Requirements: M= 2370 FT -t8 Controlling Moment: 8.04 Ft from left support of span 2 (Center Span) Critical moment created by combining all dead loads and live loads on span(s) 2 V= 590 LB controlling Shear, At right support of span 2 (Center Span) Critical shear created by combining all dead Toads and live toads on span(s) 2 Comparisons With Required Sections: S 27.48 IN3 SeGtlon Modulus ( Moment): S= 31.134 INS Area (Shear): Amor: 9.31 IN2 A= 16.88 IN2 Moment of inertia (Deflection): Iraq= 128,61 1N4 1= 177.95 IN4 • l .. . i m i 1 • . . . . . .,.,..,... • Monday, January 02, 2006 2:27 PM Peter Drake 503 -654 -4642 p.03 Floor Joist[ 98 International One -and Two - Family Dwelling Code (97 NDS) ) Ver. 5.05 By: Peter Drake, Architect , Peter Drake, Architect on: 12 -31 -2005 Project: Joanscot - Location: Floor joists Summary: 1.5 IN x 11:25 IN x 16,08 FT 16 O.C. 1 #2 - Douglas Fir -Larch - Dry Use Section Adequate By: 15.1% Controlling Factor: Section Modulus 1 Depth Required 10.48 In _ SHEAR, MOMENT, AND DEFLECTION DIAGRAMS Load combination shown: Controlling . Shear /MomenUDeflection Diagrams 600 • 590 lbs g 0 if 300 • Shear - (lbs) 0 -300 - .• -600 - __590 lbs aQ 16 f( 3000 2370 ft -lbs 8 ft 1500 - Moment (ft-lb) 0 - -- - 4 -1500 - -3000 -.5 -.25 - Deflection (in) 0 - - .25 - . '-.387in 8ft Center Span = 16.08 ft Controlling Load Cases:. Shear: Critical shear created by combining all dead toads and live loads on span(s) 2 Moment: Critical moment created by combining all dead loads and live Toads on span(s) 2 Deflection: Critical deflection created in combining all dead Toads and live toads on span(a) 2 _.. _ _... LOADING DIAGRAM A w �...... Center Span = 16.08 ft Reactions Live Load Dead Load Total Load Uplift Load A 429 Lb 181 LD 590 Lb 0 Lb 8 429 Lb 161 Lb 590 Lb 0 Lb Cant S pan Uniform Loading Live Load Dead Load Total Load