Loading...
Report 10/31/2008 08:16 5032551966 CAPITOL ELECTRIC PAGE 01 000 Z CA> 8 s 6 .7 FAX COVER SHEET CAPITOL ELECTRIC CO., INC. Date: 10/31/2008 11401 NE MARX STREET PORTLAND, OR 97220 Time: (503) 255 -9488 FAX 255 -1966 Fax #: 503.624.3681 Please deliver the following pages immediately to: Name: Rick Firm: City of Tigard, Building Department From: Dan Wilson RE: Farmers Ins T.I. Fire Alarm ROC Comments: Fire Alarm NFPA -72 Record of Completion for Farmers Insurance T.I. Suite 700 @ 5- Lincoln If you have questions or comments, please call me. Thanks, Dan Wilson 503.262.0411 TOTAL NUMBER OF PAGES, INCLUDING COVER SHEET 5 IF YOU DO NOT RECEIVE ALL PAGES, PLEASE CALL (503) 262 -0411 10/31/2008 08:16 5032551966 CAPITOL ELECTRIC PAGE 02 NFPA -72 Fire Alarm System Record of Completion Date: 10/31/08 City of Tigard Information: Permit No. BUP2008 -00337 Name of protected property: FARMERS INSURANCE TENANT IMPROVEMENT, SUITE 700 Address of protected property: 10200 SW GREENBURG RD TIGARD, OR 97223 Representative of protected property (name /phone): _ Authority having jurisdiction: City of Tigard, Building Services Address/telephone number. 13125 SW Hall Blvd. Tigard, OR 97223 (503) 639.4171 1. Type(s) of System or Service NFPA 72, Chapter 3 -- Local If alarm is transmitted to locations(s) off premises, list where received: NFPA 72, Chapter 3 -- Emergency Voice /Alarm Service Quantity of voice /alarm channels: Single: Multiple: Quantity of speakers installed: Quantity of speaker zones: Quantity of telephones or telephone jacks included in system: NFPA 72, Chapter 5 -- Auxiliary Indicate type of connection: Local energy Shunt Parallel telephone Location of telephone number for receipt of signals: NFPA 72, Alarm: Supervisory: NFPA 72, Chapter 5 -- Proprietary If alarms are retransmitted to public fire service communications centers or others, indicate location and telephone numbers of the organization receiving alarm: Indicate how alarm is retransmitted: X NFPA 72, Chapter 5 -- Remote Station Prime contractor: Central station location: Means of transmission of signals from the protected premises to the central station: McCulloh Multiplex One -way radio Digital alarm communicator Two -way radio Others Means of transmission of alarms to the public fire service communications center: (a) (b) System location: 10/31/2008 08:16 5032551966 CAPITOL ELECTRIC PAGE 03 • Organization name /phone Representative name/Phone Installer Capitol Electric Co. Inc. Dan W. Wilson 503 255 -9488 Supplier Capitol Electric Co. Inc. Dan W. Wilson 503 255 -9488 Service organization Capitol Electric Co. Inc. Dan W. Wilson 503 255 -9488 Location of record (as- built) drawings: Location of owners manuals: Location of test reports: A contract, dated , for test and inspection in accordance with NFPA standard(s) No(s). , dated , is in effect. 2. Record of System Installation Suite 700 Only (Fill out after installations complete and wiring checked for opens, shorts, ground faults, and improper branching, but prior to conducting operational acceptance tests.) This system has been installed in accordance with the NfPA standards as shown below, was inspected by Steve Lines on 10/31/08 , included the devices shown below, and has been in service since 10/31/08 x NFPA 72, Chapters 1 2 3 4 5 6 7 (underline all that apply) x NFPA 70, National Electrical Code, Article 760 x Manufacturer's instructions Other (specify): Signed: Steve Lines Date: 10/31/08 Organization: Capitol Electric Company, Inc. 3. Record of System Operation Suite 700 Only All operational features and functions of this system were tested by Steve Lines on 10/31/08 and found to be operating properly in accordance with the requirements of: x NFPA 72, Chapters 1 2 3 4 5 6 7 (underline all that apply) x NFPA 70, National Electrical Code, Article 760 x Manufacturer's instructions Other (specify): Signed: Steve Lines Date: 10/31/2008 Organization: Capitol Electric Company, Inc. 4. Alarm- Initiating Devices and Circuits Suite 700 Only Quantity and class of initiating device circuits (see NFPA 72, Table 3 -5) Quantity: Style: Class: MANUAL (a) 0 Manual stations Noncoded, activating Transmitters Coded (b) Combination manual fire alarm and guard's tour coded stations. AUTOMATIC Coverage: Complete: Partial: (a) 0 Smoke detectors Ion Photo (b) 0 Duct detectors Ion Photo (c) 0 Heat detectors FT RR FT /RR RC (d) 0 Sprinkler waterflow switches: Transmitters Noncoded, activating (e) Other (list): 10/31/2008 08:16 5032551966 CAPITOL ELECTRIC PAGE 04 • 5. Supervisory Signal- Initiating Devices and Circuits Suite 700 Only GUARD' S TOUR (a) Coded stations (b) Noncoded stations, activating transmitters (c) Compulsory guard tour system comprised of transmitter stations and intermediate stations Note: Combination devices are recorded under 4(b) and 5(a). SPRINKLER SYSTEM (a) Non coded valve supervisory switch at sprinkler riser (b) Non coded valve supervisory switch at sprinkler vault (c) Non coded supervisory air pressure switch at sprinkler riser (d) Site water supply level points Electric fire pump: (e) Fire pump power (f) fire pump running (g) Phase reversal Engine - driven fire pump: (h) Selector in auto position (I) Engine or control panel trouble (j) Fire pump running Engine - driven generator: (k) Selector in auto position (I) Control panel trouble (m) Transfer switches (n) Engine running Other supervisory functions(s) (specify): 6. Alarm Notification Appliances and Circuits Suite 700 Only Quantity and class (see NFPA 72, Table 3 -7) of notification appliance circuits connected to the system: Types and quantities of notification appliances installed: Quantity: 21 Style Y Class: B (a) Bells Inch (b) Speakers (c) 4 Homs (d) Chimes (e) Other: (f) 17 Visual signals Type: ADA SYNCHRONIZED 13 with audible 4 w/o audible (g) Local annunciator 10/31/2008 08:16 5032551966 CAPITOL ELECTRIC PAGE 05 7. Signaling Line Circuits Suite 700 Only Quantity and class (see NFPA 72, Table 3 -6) of signaling line circuits connected to system: Quantity: Style: Class: 8. System Power Supplies (Notification Panel NAC 7.1) (a) Primary (main): NAC 7.1 Nominal voltage: 120 VAC Current rating: 2.5 Amps Overcurrent protection: Type: Circuit Breaker Current rating: 20 Amps Location: FLOOR 7 ELECTRIC ROOM (b) Secondary (standby): X Storage battery: Amp -hour rating: 7 Ah 24 VDC Calculated capacity to drive system, in hours: 2.293 Ah 24 60 Engine - driven generator dedicated to fire alarm system: Location of fuel storage: (c) Emergency or standby system used as backup to primary power supply, instead of using a secondary power supply: Emergency system described in NFPA 70, Article 700 Legally required standby system described in NFPA 70, Article 701 Optional standby system described In NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701 9. System Software (a) Operating system software revision level(s): N/A (b) Application software revision level(s): (c) Revision completed by: N/A (name) (firm) 10. Comments: Dan Wilson Capitol Electric Co., FLS Supervisor (signed) for central station or alarm service company or installation contractor /supplier (title) Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standard(s): This record of completion applies to Suite 700 Only Devices installed conform to NFPA standards. System deviations from the referenced NFPA standard(s) are: NONE Dan Wilson Capitol Electric Co., FLS Supervisor (signed) for central station or alarm service company or installation contractor /supplier (title) Upon completion of the system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction): (signed) representative of the authority having jurisdiction (title) (date)