Specifications (.2 dio ,PvU - 7 -ov j 7 City of Tigard, Oregon o 13125 SW Hall Blvd. m Tigard, OR 97223 Ma"' November 19, 2007 r ® tg iA RE: FIRE SPRINKLER SYSTEM tr, GA R) Project Information Building Permit: BUP2007 -00577 Construction Type: VB Tenant Name: Coral Commons Occupancy Type: R -3 Address: 9360 SW Coral st. Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13) 2002 edition and the State of Oregon Fire Code (OFC) 2007edition. GENERAL 1. Clearances shall be provided around all piping extending through platforms, foundations, walls and floors. The diameter of the hole shall be 2 inches - larger than the penetrating pipe for pipe sizes 1 inch through 3'h inches. The diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger. Sections 9.3.4.1 & 9.3.4.2 NFPA 13. 2. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. Such sprinkler water -flow devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Section 903.4.2 OFC 3. The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. 4. New sprinkler system piping shall be hydrostatically tested at working pressure. 5. Piping shall be protected from freezing as per plans. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. • Respectf I , 1 3-n Nels n, enior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard - or.gov • TTY Relay: 503.684.2772 00 'L' .07--.005 tqco I Fire & Building :.;. Products ` r rapid response' HOME FIRE SPRINKLER SYSTEM Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series LFII Residential Concealed Pendent Sprinklers, Flat Plate 4.9 K-factor General pressures, enabling smaller pipe sizes and water supply requirements. Description The Series LFII (TY3596) has been . designed with heat sensitivity and The Series LFII (TY3596) Residential water distribution characteristics Concealed Pendent Sprinklers are proven to help in the control of residen- decorative, fast response, fusible sol- tial fires and to improve the chance for „- -- Y r der sprinklers designed for use in resi- occupants to escape or be evacuated. ,,, w. ,., ". ",,— �,, dential occupancies such as homes, The Series LFII (TY3596) Residential ' apartments, dormitories, and hotels. Concealed Pendent Sprinklers are The cover plate assembly conceals shipped with a Disposable Protective the sprinkler operating components Cap. The Protective Cap is temporarily above the ceiling. The flat profile of the removed for installation, and then it cover plate provides the optimum aes- can be replaced to help protect the thetically appealing sprinkler design. sprinkler while the ceiling is being in- In addition, the concealed design of stalled or finished. The tip of the Pro - the Series LFII (TY3596) provides 1/2 tective Cap can also be used to mark inch (12,7 mm) vertical adjustment. the center of the ceiling hole into plas- This adjustment reduces the accuracy ter board, ceiling tiles, etc. by gently to which the fixed pipe drops to the pushing the ceiling product against the Technical sprinklers must be cut to help assure Protective Cap. When the ceiling in- a perfect fit installation. stallation is complete the Protective Data Cap is removed and the Cover Plate The Series LFII are to be used in wet Assembly installed. Approvals: pipe residential sprinkler systems for UL and C -UL Listed. one- and two - family dwellings and mo- WARNINGS bile homes per NFPA 13D; wet pipe The Series LFII (TY3596) Residential Maximum Working Pressure: residential sprinkler systems for resi- Concealed Pendent Sprinklers de- 175 psi (12,1 bar) dential occupancies up to and includ- scribed herein must be installed and Discharge Coefficient: ing four stories in height per NFPA maintained in compliance with this K = 4.9 GPM /psi (70,6 LPM /bar / 13R; or, wet pipe sprinkler systems for document, as well as with the applica- Temperature Rating: the residential portions of any occu- ble standards of the National Fire Pro- 160 °F /71 °C Sprinkler rwith pancy per NFPA 13. tection Association, in addition to the 135 °F /57 °C Cover Plate The Series LFII (TY3596) has a 4.9 standards of any other authorities hav- (60,5) K- factor that provides the re- ing jurisdiction. Failure to do so may Vertical Adjustment: quired residential flow rates at reduced impair the performance of these de- 1/2 inch (12,7 mm) vices. Finishes: The owner is responsible for maintain Cover Plate: ing their fire protection system and de- Flat White, Bright White, Chrome, or IMPORTANT vices in proper operating condition. Custom Always refer to Technical Data The installing contractor or sprinkler Sheet TFP700 for the "INSTALLER manufacturer should be contacted Physical Characteristics: WARNING" that provides cautions with any questions. Body Brass with respect to handling and instal- Cap Bronze lation of sprinkler systems and com- /�// Saddle Brass ponents. Improper handling and i � ®�kler� °model Sealing Assembly . . stallation can permanently damage Beryllium Nickel w/ Teflont a sprinkler system or its compo Identification Soldered Link Halves Nickel nents and cause the sprinkler to fail Lever Bronze to operate in a fire situation or cause Number Compression Screw Brass it to operate prematurely. SIN TY3596 Deflector Copper or Brass Guide Pin Housing Bronze Page 1 of 4 JANUARY, 2006 TFP442 Page 2 of 4 TFP442 Minimum Flow (b) and _ Maximum Maximum Residual Pressure Coverage Spacing For Horizontal Ceiling Area (a) Ft. (Max. 2 Inch Rise Ft. x Ft. (m) for 12 Inch Run) (mxm) 160 °F /71 °C Sprinkler 12 x 12 12 13 GPM (49,2 LPM) (3,7 x 3,7) (3,7) 7.0 psi (0,48 bar) 14 x 14 14 13 GPM (53,0 LPM) (4,3 x 4,3) (4,3) 7.0 psi (0,48 bar) 16 x 16 16 13 GPM (60,6 LPM) (4,9 x 4,9) (4,9) 7.0 psi (0,48 bar) 18 x 18 18 17 GPM (64,3 LPM) (5,5 x 5,5) (5,5) 12.0 psi (0,83 bar) 20 x 20 20 20 GPM (75,7 LPM) (6,1 x 6,1) (6,1) 16.7 psi (1,15 bar) (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K- factor. Refer to Hydraulic Design Criteria Section for details. TABLE A NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII (TY3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER Guide Pins Stainless Steel NOTE coverage areas being protected by Support Cup Steel When conditions exist that are outside the four sprinklers. Cover Plate Copper the scope of the provided criteria, refer Obstruct To Water Distribution. Retainer Brass to the Residential Sprinkler Design Locat of sprinklers are to be in Cover Plate Ejection Spring Guide TFP490 for the manufacturer's accordance with the obstruction rules Stainless Steel recommendations that may be accept- of NFPA 13 for residential sprinklers. able to the Authority Having Jurisdic- tDuPont Registered Trademark tion. Operational Sensitivity. The sprin- System Type. Only wet pipe systems klers are to be installed relative to the Operation may be utilized. ceiling mounting surface as shown in Figure 3. When exposed to heat from a fire, the Hydraulic Design. The minimum re- Sprinkler Spacing. The minimum p quired sprinkler flow rate for systems Cover Plate, which is normally sol- designed to NFPA 13D or NFPA 13R spacing between sprinklers is 8 feet dered to the Support Cup at three are given in Table A as a function of (2,4 m). The maximum spacing be- points, falls away to expose the Sprin- temperature rating and the maximum tween sprinklers cannot exceed the kler Assembly. At this point the Deflec- allowable coverage areas. The sprin- length of the coverage area (Ref. Ta- tor supported by the Arms drops down kler flow rate is the minimum required ble A) being hydraulically calculated to its operated position. The fusible discharge from each of the total (e.g., maximum 12 feet for a 12 ft. x link of the Sprinkler Assembly is com- number of "design sprinklers" as 12 ft. coverage area, or 20 feet for a 20 prised of two link halves that are sol- specified in NFPA 13D or NFPA 13R, ft. x 20 ft. coverage area). dered together with a thin layer of sol- der. When the rated temperature is For systems designed to NFPA 13, the Installation reached, the solder melts and the two number of design sprinklers is to be link halves separate allowing the sprin- the four most hydraulically demanding kier to activate and flow water. sprinklers. The minimum required dis- Series LFII (TY3596) must be in- charge from each of the four sprinklers stalled in accordance with the follow - is to be the greater of the following: ing instructions: _ Design NOTES • The flow rates given in Table A for Damage to the fusible Link Assembly C NFPA 13D and 13R as a function of during installation can be avoided by temperature rating and the maxi- handling the sprinkler by the support The Series LFII (TY3596) Residential mum allowable coverage area. cup only (i.e., do not apply pressure to Concealed Pendent Sprinklers are UL • A minimum discharge of 0.1 gpm /sq. the fusible link Assembly). and C -UL Listed for installation in ac- ft. over the "design area" comprised A leak tight 1/2 inch NPTsprinklerjoint cordance with the following criteria. of the four most hydraulically de- should be obtained with a torque of 7 manding sprinklers for the actual to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- TFP442 Page 3 of 4 BODY , /` SEALING mum of 21 (fibs. (28,5 Nm) of torque (1/2" NPT) 'L ASSEMBLY is to be used to install sprinklers. ' Higher levels of torque may distort the Jr „, sprinkler inlet with consequent leak - CAP �` age or impairment of the sprinkler. (� / / / ���� SPRINKLER ; I' `;', , i WRENCHING Do not attempt to compensate for in- SADDLE IT = ' ; l AREA sufficient adjustment in the Cover Plate /Retainer Assembly by under- or l is-.1 ` over tightening the Sprinkler. Read 141 just the position of the sprinkler fitting SUPPORT COMPRESSION to suit. CUP WITH j ; r SCREW ROLL FORMED i II Step 1. The sprinkler must only be THREADS i 1 I \ installed in the pendent position and II 1 with the centerline of the sprinkler per - I l �\, �, „ ,,1 ` LEVER pendicular to the mounting surface. GUIDE 1 '�1' I Step 2. Remove the Protective Cap. PIN SOLDER LINK Step 3. With pipe thread sealant ap- ELEMENT plied to the pipe threads, and using GUIDE PIN , I the W -Type 18 Wrench shown in Fig - HOUSING ure 2, install and tighten the Sprink- DEFLECTOR ler /Support Cup Assembly into the fit - _ _ L� (OPERATED ling. The W-Type 18 Wrench will DEFLECTOR POSITION) accept a 1/2 inch ratchet drive. SPRINKLER/SUPPORT CUP ASSEMBLY ,c1, \ W�■R� ENCH RECESS - THREAD INTO RETAINER SUPPORT CUP 1 WITH THREAD j . ■ UNTIL MOUNTING J I DIMPLES SURFACE IS \ O O ` 7 • FLUSH WITH ) EJECTION CEILING SPRING PUSH WRENCH — •- INTO ENSURE J-- - - - - -- ENGAGEMENT COVER PLATE/RETAINER WITH SPRINKLER SOLDER COVER WRENCHING AREA TAB ASSEMBLY PLATE FIGURE 1 FIGURE 2 SERIES LFII (TY3596) RESIDENTIAL W -TYPE 18 CONCEALED PENDENT SPRINKLER SPRINKLER WRENCH 2 -1/2° DIA. y SPRINKLER - (63,5 mm) 1/2” (12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING ` / OPERATED _ �� SPRINKLER 1- 7/8 "±1/8" COVER '�'�1 — (47,6 mm PLATE ��' - I I ( 1 3 /8 , " GAP ±3,2 mm) RETAINER , T.,._._._._._...,... 1 7/8" (22,2 mm) I • I COVER- SPRINKLER- MOUNTING 1 -1/8" (28,6 mm) RETAINER SUPPORT CUP 3/18° J SURFACE � .� ASSEMBLY ASSEMBLY (4,8 mm) NV 3 -3/16" DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 SERIES !Ft! (TY3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER INSTALLATION DIMENSIONS / PROTECTIVE CAP /ACTIVATED DEFLECTOR : : Page 4 of 4 TFP442 Step 4. Replace the Protective Cap by painted, plated, coated, or otherwise ucts. TFBP shall not be responsible for pushing it upwards until it bottoms out altered after leaving the factory. Modi- sprinkler system design errors or inac- against the Support Cup. The Protec- fied or over heated sprinklers must be curate or incomplete information sup- - tive Cap helps prevent damage to the replaced. plied by Buyer or Buyer's repre- Deflector and Guide Pins during ceil- sentatives. ing installation and /or during applica Care must be exercised to avoid dam - tion of the finish coating of the ceiling. ation. Sprinklers during, dmageditby instal- dop- contact tort, str F ability or under It may also be used to locate the center of the clearance hole by gently push- ping, striking, wrench twist /slippage, any other legal theory, for incidental, ing the ceiling material against the or the like, must be replaced. indirect, special or consequential dam center point of the Cap. The owner is responsible for the in- ages, including but not limited to labor spection, testing, and maintenance of charges, regardless of whether TFBP NOTE their fire protection system and de- was informed about the possibility of As long as the protective Cap remains vices in compliance with this docu- such damages, and in no event shall TFBP in place, the system is considered to ment, as well as with the applicable liability exceed an amount to t o t be "Out Of Service ". standards of the National Fire Protec- equal the sales price. Step 5, After the ceiling has been com tion Association (e.g., NFPA 25), in The foregoing warranty is made in lieu pleted with the 2 -1/2 inch (63 mm) addition to the standards of any other of any and all other warranties. ex- diameter clearance hole and in prepa- authorities having jurisdiction. The in- press or implied. including warranties ration for installing the Cover Plate As- stalling contractor or sprinkler manu- of merchantability and fitness for a sembly, remove and discard the Pro- facturer should be contacted relative particular purpose tective Cap, and verify that the to any questions. This limited warranty sets forth the ex- Deflector moves up and down freely. NOTE clusive remedy for claims based on If the Sprinkler has been damaged and The owner must assure that the sprin failure of or defect in products, materi the Deflector does not move up and k/ers are not used for hanging of any als or components, whether the claim down freely, replace the entire Sprin- objects and that the sprinklers are only is made in contract, tort, strict liability or any other legal theory. kler assembly. Do not attempt to mod- cleaned by means of gently dusting ify or repair a damaged sprinkler. with a feather duster; otherwise, non- This warranty will apply to the full ex- Step 6. Screw on the Cover Plate As- operation in the event of a fire or inad- tent permitted by law. The invalidity, in sembly until its flange comes in con- vertent operation may result. whole or part, of any portion of this tact with the ceiling. It is recommended that automatic warranty will not affect the remainder. - Do not continue to screw on the Cover sprinkler systems be inspected, Plate Assembly such that it lifts a ceil- tested, and maintained by a qualified Ordering Plate panel out Assembly of such normal position. Inspection Service in accordance with in g local requirements and /or national Procedure If the Cover Plate Assembly cannot be codes. engaged with the Mounting Cup or the When placing an order, indicate the Cover Plate Assembly cannot be en- full product name. Contact your local gaged sufficiently to contact the ceil- Limited distributor for availability.. ing, the Sprinkler Fitting must be repo- ��W� sitioned. Warranty Sprinkler Assembly: Products manufactured by Tyco Fire & Series LFII (TY3596), K =4.9, Residen Sere and Building Products (TFBP) are war- tial Concealed Pendent Sprinkler (10) with - ranted solely to the original Buyer for out Cover Plate Assembly, t en P/N 51- 112 -1 -160. Maintenance (0) years against defects in mate- rial and workmanship when paid for Cover Plate Assembly: The Series LFII (TY3596) must be and properly installed and maintained Cover Plate Assembly having a (spec - maintained and serviced in accord- under normal use and service. This ify) finish for the Series LFII (TY3596), ance with the following instructions: warranty will expire ten (10) years K =4.9, Residential Concealed Pen - from date of shipment by TFBP. No dent Sprinkler, P/N (specify). NOTES warranty is given for products or com Absence of a Cover Plate may delay ponents manufactured by companies Chrome P/N 56 -122 -9 -135 the sprinkler operation in a fire situ- not affiliated by ownership with TFBP Off White P/N 56- 122 -0 -135 ation. or for products and components which Bright White P/N 56- 122 -4 -135 have been subject to misuse, improper Flat White P/N 56 -122 -5 -135 Before closing a fire protection system installation. corrosion, or which have White (RAL9010)' P/N 56 -122 -3 -135 . main control valve for maintenance Custom P/N 56- 122 -X -135 protection not been installed, maintained, modi work on it the the fire permission prote tion system em fied or repaired in accordance with ap- *Eastern Hemisphere sales only. which hic the o ntro, fire protection shut plicable Standards of the National Fire d tom must o s obtained from the proper Protection Association, and /or the Sprinkler Wrench: authorities and all personnel who may standards of any other Authoritie p y Having Jurisdiction. Materials found Specify: W -Type 18 Sprinkler Wrench, be affected by this action must be no by TFBP to be defective shall be either P/N 56- 000 -1 -265. tilled. repaired or replaced, at TFBP's sole Sprinklers which are found to be leak- option. TFBP neither assumes, nor ing or exhibiting visible signs of corro- authorizes any person to assume for it, sion must be replaced. any other obligation in connection with Automatic sprinklers must never be the sale of products or parts of prod - TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Attica Fire & Building • Products rr rapid response HOME FIRE SPRINKLER SYSTEM Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Technical %, -: Description Data Tyco Fire & Building Products (TFBP) Sizes Aoh Wm' P4MiCt , BlazeMaster CPVC Pipe and Fittings 3/4" to 3 "fii q y + are designed exclusively for use in wet 4 tx � Sf f T Maximum Working Pressure psi pipe automatic fire sprinkler systems. 175 , •' They are made from a specially devel- p r' " "t ° oped thermoplastic compound com- Approvals , fr ° t posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County, '� ` „em chloride (CPVC) resin and state of the LPCB, MEA, and the City of Los Ange- f s» art additives. TFBP BlazeMaster les. (Refer to IH -1900, Rev. 0, Janu- a CPVC products are easier to install ary 2005 "Installation Instruction & than traditional steel pipe systems, Technical Handbook" for exact list- ` :rs and at the same time, provide superior ing /approval information.) 9 heat resistance and strength as com- Manufacture Source pared to traditional CPVC and PVC U.S.A. piping materials used in the plumbing trade. Various adapters are available Material to connect CPVC pipe to metallic pip- ing. All female pipe thread adapters have brass inserts for durability. • Fittings: ASTM F438 (Sch. 40) and Grooved adapters connect directly to ASTM F439 (Sch. 80), ASTM F1970 grooved end valves and metallic pipe, Color with flexible grooved end couplings. C for WARNING Tyco Fire & Building Products (TFBP) BlazeMaster CPVC Pipe and Fittings described herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities ha v- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ' ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaster® is a registered trademark of Noveon IP Holding Corp. Page 1 of 6 JANUARY, 2006 TFP1915 Page 2 of 6 TFP1915 NOMINAL AVERAGE AVERAGE WEIGHT FT. OF PIPE WEIGHT PER LIFT FILLED WATER WEIGHT SIZE O.D. I.D. lbs. /ft. lbs. /ft. PER LIFT lbs. 3/4° 1.050" 0.874" 0.18 0.44 7875 1339 1" 1.315" 1.101' 0.26 0.67 5040 1320 1 -1/4' 1.660" 1.394" 0.42 1.08 2835 1191 1 -1/2" 1.900° 1.598" 0.54 1.41 2205 1213 2" 2.375" 2.003" 0.84 2.20 1260 1084 2 -1/2" 2.875" 2.423" 1.26 3.26 1215 1531 3" 3.500" 2.952" 1.87 4.83 720 1344 FIGURE 1 — PIPE DIMENSIONS Installation Care and Tyco Fire and Building Products Maintenance (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- The owner is responsible for the fin- ance with IH -1900, Rev. 0, January spection, testing, and maintenance of 2005 "Installation Instruction & Techni- their fire protection system and de- cal Handbook ". vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and /or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls, permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible formoni- • Loring proprietary and /or central sta- tion alarms. TFP1915 Page 3 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE -OUT SCHD. WEIGHT TYPE NUMBER (T /O) (Ib.) TEE 80000 3/4' 5/8" 40 0.11 i„' T/O 80001 1' 11/16' 40 0.19 �/ J 80002 1 -1/4" 7/8' 40 0.26 M INN 80003 1 -1/2' 1 -1/16° 80 0.51 -ER. 80004 2' 1.3/8" 80 0.90 TIO ■■ T/O 80005 2 -1/2' 1 -9/16' 80 1.59 80006 3' 1- 13/16" 80 2.41 X xYxZ X Y Z 80132 3/4'x3/4" x 1" 3/4" 3/4° 5/8' 40 0.14 80133 1' x 3/4' x 3/4' 9/16' 9/16° 3/4" 40 0.14 80134 1' x 3/4' x 1' 3/4" 11/16° 3/4" 40 0.17 80260 1' x 1' x 3/4" 5/8" 5/8" 13/16° 40 0.16 80135 1 -1/4' x 1'x3/4' 5/8' 5/8" 15/16" 40 0.21 80136 1 -1/4' x 1° x 1" 3/4° 3/4° 15/16" 40 0.22 80137 1 -1/4" x 1" x 1 -1/4" 15/16' 15/16" 7/8" 40 0.26 REDUCING TEE 80261 1-1/4" x 1.1/4' x 3/4" 5/8' 5/8° 7/8" 40 0.23 80262 1 -1/4" x 1 -1/4" x 1' 3/4' 3/4' 7/8" 40 0.26 Z 80138 1 -1/4" x 1 -1/4" x 1 -1/2" 1" 1" 1' 80 0.43 T/O �„� 80140 1 -1/2' x 1.1/4' x 3/4' 9/16' 9/16' 1° 80 0.36 ■i i� i 80141 1 -1/2° x 1 -1/4' x 1' 9/16" 9/16° 1 -1/16° 80 0.38 . 80263 1 -1/2" x 1 -1/2 "x3/4' 9/16° 9/16° 1' 80 0.36 X 11111111111M Y 80264 1 -1/2' x 1 -1/2' x 1" 9/16" 9/16' 1 -1/16° 80 0.38 J � � I ' - � 80275 1 -1/2" x 1 -1/2' x 1 -1/4" 7/8" 7/8" 1' 80 0.45 T/O •• T/O 80265 2' x 2" x3/4" 3/4" 3/4' 1 -3/8' 80 0.61 80266 2' x 2' x 1" 7/8' 7/8° 1 -3/8' 80 0.66 80274 2' x 2' x 1 -1/4" 1 -1/16° 1.1/16° 1 -3/8' 80 0.74 80267 2" x 2' x 1 -1/2' 1 -1/8' 1 -1/8' 1 -3/8" 80 0.78 80271 2 -1/2' x 2 -1/2" x 1' 1 -9/16" 1-9/16" 1 -9/16' 80 1.43 80272 2 -1/2' x 2 -1/2' x 1 -1/4' 1 -9/16" 1 -9/16° 1-9/16" 80 1.46 80273 2.1/2" x 2 -1/2' x 1 -1/2' 1.9/16' 1 -9/16' 1 -9/16° 80 1.48 80276 2 -1/2" x 2 -1/2' x 2° 1 -9/16" 1 -9/16' 1 -9/16" 80 1.50 80270 3' x 3" x 1 -1/2" 1- 13/16' 1- 13/16' 1-13/16" 80 2.28 80268 3' x 3' x 2' 1- 13/16" 1- 13/16" 1 -3/4' 8D 2.25 80269 3' x3 "x2 -1/2" 1- 13/16' 1- 13/16" 1- 13/16' 80 2.44 CROSS & REDUCING CROSS 80009 3/4" 9/16" 40 0.13 80010 1' 11/16° 40 0.23 0„ T/0 80011 1 -1/4' 15/16" 40 0.34 ., 80012 1 -1/2' 1 -1/16' 80 0.67 .1111.. 80013 2' 1.5/16' 80 1.00 >j - 80014 2 -1/2" 1 -9/16' 80 1.91 II ..II T/O 80008 3" 1- 13/16' 80 2.89 T/O ■■ T/O 80015 1' x 1' x 3/4" x 3/4" 7/8' 40 0.28 90° ELBOW & 80025 3/4' 5/8" 40 0.09 REDUCING ELBOW 80026 1' 3/4' 40 0.14 80027 1-1/4' 7/8' 40 0.21 X 80028 1 -1/2" 1 -1/16" 80 0.40 /.,j T/O 80029 2' 1 -5/16' 80 0.79 - 80030 2 -1/2" 1 -9/16° BO 1.14 VIE. 80031 3° 1- 13/16" 80 1.82 ♦♦� Y X x Y X Y ' T/0 - 80032 1' x 3/4" 11/16' 13/16° 40 0.16 FIGURE 2 - FITTING DIMENSIONS (Part 1 of 4) Page 4 of 6 TFP1915 FITTING PART NOMINAL SIZE NOMINAL TAKE -OUT SCHD. WEIGHT TYPE NUMBER (T /O) (Ib.) 45° ELBOW 80050 3/4° 3/8' 40 0.08 T/O 80051 1' 3/8' 40 0.11 �� 80052 1 -1/4' 3/4° 40 0.20 4"_ 80053 1 -1/2' 1/2' 80 0.31 T/O � 80054 2' 3/4' 80 0.56 � 1 i rA __, 80055 2 -1/2' 13/16' 80 0.89 80056 3' 1' 80 1.19 80075 3/4° 1/8" 40 0.07 COUPLING & 80076 1' 1 /8" 40 0.11 REDUCING COUPLING 80077 1 -1/4' 3/16' 40 0.12 "'."' 80078 1 -1/2' 3/16' 80 0.25 80079 2' 3/16' 80 0.38 80080 2 -1/2' 1/4' 80 0.67 I- T/O 80081 3' 3/16' 80 0.91 80220 1' x 3/4' 1/8" 40 0.08 80200 1' x 3/4" 7/16' 40 0.04 80201 1- 1/4'x3/4' 1/2' 40 0.11 80202 1 -1/4' x 1' 5/16' 40 0.12 80203 1-1/2' x 3/4' 5/8' 80 0.16 80204 1 -1/2' x 1' 1/2' 80 0.14 REDUCER BUSHING 80205 1.1/2' x 1.1/4' 3/8' 80 0.17 80206 2' x 3/4" 13/16' 80 0.27 80207 2'x 1' 11/16' 80 0.26 80208 2' x 1.1/4' 9/16' 80 0.24 80209 2' x 1.1/2' 7/16' 80 0.19 -1 - T/O 80215 2 -1/2" x 1' 15/16' 80 0.42 80214 2 -1/2' x 1 -1/4' 13/16' 80 0.45 80213 2 -1/2' x 1 -1/2' 11/16' 80 0.46 80211 2 -1/2' x 2' 5/8' 80 0.29 80210 3' x 2' 3/4' 80 0.72 80212 3' x 2 -1/2' 1/2' 80 0.47 CAP 80100 3/4' 5/16' 40 0.04 80101 1' 3/8' 40 0.06 80102 1 -1/4' 7/16' 40 0.10 80103 1 -1/2' 11/16' 80 0.20 80104 2" 5/8' 80 0.31 T/0 80105 2.1/2' 7/8' 80 0.58 80106 3' 1' 80 0.88 GROOVED T/O PIPE O.D. COUPLING ADAPTER 80160 1 -1/4' x 1.1/4' Groove 2 -5/16' 1 -1/4' (1.660') 40 0.78 80161 1 -1/2' x 1 -1/2' Groove 2-5/16" 1.1/2' (1.900') 80 0.95 PIPE 80162 2' x 2' Groove 2.5/16' 2' (2.375') 80 1.42 O.D. 80163 2.1/2' x 2.1/2' Groove 2.5/16' 2 -1/2' (2.875') 80 2.28 80164 3' x 3' Groove 2.1/4' 3' (3.500') 80 3.00 - T /O--I 80169 2.1/2' x 76,1 mm Groove 2 -5/16" 76,1 mm (3.000') 80 2.28 FIGURE 2 - FITTING DIMENSIONS (Part 2 of 4) TFP1915 Page 5 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE -OUT SCHD. WEIGHT TYPE NUMBER (T /O) (Ib.) ° SPRINKLER HEAD ADAPTER _ _ 80175E 3/4' x 1/2" NPT 7/16" 80 0.20 . �P'IIIII' 80176E 1' x 1/2' NPT 7/16' 80 0.22 F,,, 80175WL 3/4' x 1/2' NPT 7/16' 40 0.16 '���I! .1 80179 1'x3/4' NPT 13/16" 40 0.43 T/O SPRINKLER HEAD ADAPTER -Ay:4z`, 80175W 3/4' x 1/2' NPT 1/2' 40 0.19 Y 80176W 1' x 1/2' NPT 1/2' 40 0.18 ..li: - T/O SPRINKLER HEAD ADAPTER (SPIGOT) _ ���. 80177L 3/4° x 1/2' NPT 1/2' 40 0.16 MG 80178 1' x 1/2' NPT 9/16" 40 0.20 �.'"I1:::' 80180 1" x 3/4° NPT 7/8' 40 0.40 -1 T/O FEMALE ADAPTER - AKIIIIII ,... ,\N 80142 3/4" x 3/4' NPT 13/16" 40 0.41 80145 1' x 1° NPT 7/8' 40 0.63 80146 1 -1/4' x 1.1/4' NPT 1-1/8" 40 1.03 80147 1 -1/2° x 1 -1/2' NPT 1 -3/8' 80 1.42 80148 2' x 2' NPT 1- 11116' 80 2.66 - -T /O MALE ADAPTER ■iii Al, 80157 3/4" x 3/4" NPT 1 -5/16' 40 0.33 80158 1' x 1' NPT 1-3/8" 40 0.56 m = -T /O X xYxZ X Y Z SPRINKLER HEAD ADAPTER TEE 80250 3/4" x 3/4' x 1/2' NPT 9/16' 9/16' 1" 40 0.22 Z 80251 1' x 1' x 1/2' NPT 11/16' 11/16' 1-3/16" 40 0.29 ;_•� T/O 80249 1" x 1" x 1" NPT 15/16' 15/16" 1 -9/16' 40 0.73 �`) 80256 1 -1/4° x 1° x 1/2' NPT 7/16' 9/16' 1 -5/16' 40 0.30 - 80252 1.1/4' x 1-1/4" x 1/2" NPT 7/16' 7/16' 1.5/16' 40 0.31 X -ME_ Y 80257 1 -1/2' x 1.1/4' x 1/2' NPT 1/2" 11/16" 1 -7/16' 80 0.43 ■ -I ��� 80254 1.1/2' x 1.1/2' x 1/2" NPT 1/2' 1/2" 1 -7/16' 80 0.46 T/O •• T/O 80258 2' x 1 -1/2' x 1/2' NPT 1/2" 5/8' 1- 11/16' 80 0.56 80253 2' x 2' x 1/2' NPT 1/2" 1/2' 1- 11/16' 80 0.62 FIGURE 2 - FITTING DIMENSIONS (Part 3 of 4) . . Page 6 of 6 TFP1915 FITTING PART NOMINAL SIZE NOMINAL TAKE -OUT SCHD. WEIGHT TYPE NUMBER (T /O) (Ib.) BACK -TO -BACK TEE X x Y x Z X Y, Z X I 0 T/O Y )11il'IPLIIIIII 80459 1" x 1/2' NPT x 1/2' NPT 5/8" 1 -5/16" 40 0.48 111111 z 80460 1' x 1/2" NPT x 1/2' NPT 5/8' 1 -3/16' 40 0.46 T/O T/O BACK -TO -BACK CROSS X x Y x Z x W X, Y Z, W x 1"1 T/O IIIIIIitir ililil Illwal�•1111 w 80462 1' x 1" x 1/2' NPT x 1/2" NPT 5/8' 1.3/16" 40 0.46 W;'zr. 80463 1' x 1" x 1/2° NPT x 1/2" NPT 5/8" 1-5/16" 40 0.47 T/O i111 �� T/O T/O SPRINKLER HEAD X x Y X Y ADAPTER 90° ELBOW Y ; T/O IrI �.1 80199 3/4' x 1/2' NPT 9/16' 1' 40 0.20 SIM x 80198 1' x 1/2' NPT 3/4' 1 -1/4' 40 0.26 80196 1'x3/4' NPT 1 -1/16' 1- 7/16' 40 0.26 T/O FIGURE 2 — FITTING DIMENSIONS (Part 4 of 4) LLimit by TFBP to be defective shall be either of merchantability and fitness for a par- repaired or replaced, at TFBP's sole titular purpose, WarraWarra option. TFBP neither assumes, nor This limited warranty sets forth the ex- nty authorizes any person to assume for it, clusive remedy for claims based on any other obligation in connection with f ailure of or defect in products, materi- Products manufactured by Tyco Fire & the sale of products or parts of prod- p Building Products (TFBP) are war- ucts. TFBP shall not be responsible for als or components, whether the claim ranted solely to the original Buyer for sprinkler system design errors or inac- is made in contract, tort, strict liability or any other legal theory. ten (10) years against defects in mate- curate or incomplete information sup rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex- and properly installed and maintained sentatives. tent permitted by law. The invalidity, in under normal use and service. This In no event shall TFBP be liable, in whole or part, of any portion of this warranty will expire ten (10) years warranty will not affect the remainder. from date of shipment by TFBP. No contract, tort, strict liability or under • warranty is given for products or com any other legal theory, for incidental, ponents manufactured by companies indirect, special or consequential dam not affiliated by ownership with TFBP ages, including but not limited to labor - or for products and components which charges, regardless of whether TFBP have been subject to misuse, improper was informed about the possibility of installation, corrosion, or which have such damages, and in no event shall not been installed, maintained, modi- TFBP's liability exceed an amount fied or repaired in accordance with ap equal to the sales price. plicable Standards of the National Fire The foregoing warranty is made in lieu Protection Association, and /or the of any and all other warranties. ex- standards of any other Authorities press or implied. including warranties Having Jurisdiction. Materials found TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Back to Application Guide TEXTRON SPECIFICATIONS H anger M a t e ® Threaded Rod EZG660 & EZG670 HangerMate Anchors Anchoring System Application Material: EZG660 & EZG670 Anchors Wood Specification: 5/16" threaded shank diameter, one -piece anchor with head drilled high -low, waxed threads, Type 17 point and end - drilled 3 /8 l 1 t t "�i twin -lead threads head to accept 3/8 -16 threaded rod components threaded rod ♦� components '1)J��h, FM Approvals and UL Listings: �) Both styles cULus Listed for pipe up to 3 -1/2" diameter EZG660 • �rt and FM approved for pipe up to 4" -1/4 length • Head Style: ' 1 3/4" high, 9/16" diameter head end - drilled and tapped to �� accept 3/8 " -16 threaded components � /�� EZG670 0�� )�)� � Drive Hex Size: 3" length ) ''\ 1/2" across flats Features & Benefits Shank Length: • End-drilled and tapped for attaching 3/8 -16 EZG660: 2 threaded components to wood EZG670: 3" • Solid, one piece cold formed part; head cannot spin off or unscrew from body Shank Threads: • Type 17 point cuts threads into wood and wax 5/16 " - 14 high - low threads (waxed) coating reduces installation torque Point Type: Type 17 (waxed) with shank slot Performance Values for EZG360 & EZG670 Anchors Material & Heat Treat Average Ultimate Pull-Out Value (lbs) Carbon steel (AISI C 10B21); no heat treat Douglas Fir Southern Pine Hem Fir 2487 2162 1768 Finish: Zinc plated per ASTM B633 Type 11 Class 12 Installation Tools: • HangerMate drive socket: EZE215 with safety set feature; automatically disengages when anchor is seated • Recommended power tool: Contractor -grade screw gun; 12 volt min. cordless or 6 amp. corded tool • In most applications, a pre - drilled hole is not needed. In exceptionally hard wood, drill hole only to minimum size required. 1. The loads indicated obove are average ultimate values achieved under laboratory conditions and appropriate safety factors should be applied for design purposes. 2. NFPA (National Fire Protection Assoc.) minimum fastening requirements are five times the weight of a 15 ft section of water - filled pipe plus 250 lbs. This is 1475 lbs. for 4" pipe. 3. All test values were obtained using 3/8 -16 rod. When 1 /4 -20 rod is used, the strength of the rod may be feu than the pull-out values of the anchors. For more information, .contact 4. Loads were determined by testing products in the orientation for which they were Textron Fastening Systems • 1.800.435.7213 designed to be used. End - drilled parts were pulled in line with the anchor's axis while cross - drilled parts were tested with the force perpendicular to the axis. e-mail: info@ds.textron.com HangerMate® is a registered trademark of Textron Inc. Back to Application Guide -1 2 N Fastening Systems S P E C I F I C A T I O N S HangerMate® Threaded Rod EZH665 HangerMate Anchors Anchoring System Application Material: EZH665 Anchors Wood Specification: 0 .) 5/16" threaded shank diameter, one-piece anchor with twin -lead threads high -low, waxed threads, Type 17 point and cross - drilled ,) head to accept 3/8 " -16 threaded rod components head ,1) � �1 ��J FM Approvals and UL Listings: cross-drilled to p accept t 91)) �M,, • cULus Listed for pipe up to 3-1/2" diameter 3/8 -16 threaded rod Head Style: components 3/4" high, 9/16" diameter head cross - drilled and tapped to accept 3/8 " -16 threaded components Features & Benefits Drive Hex Size: • Cross - drilled and tapped for attaching 3/8 -16 1/2" across flats threaded components to wood • Solid, one piece cold formed part; head cannot spin Shank Length: off or unscrew from body 2 • Type 17 point cuts threads into wood and wax coating reduces installation torque Shank Threads: 5/16" high - low threads (waxed) Point Type: Performance Values for EZH665 Anchor Type 17 (waxed) with shank slot • Average Ultimate Pull -Out Value (Ibs) Material & Heat Treat Douglas Fir Southern Pine Hem Fir Carbon steel (AISI C10B21); no heat treat 1801 1460 1451 Finish: Zinc plated per ASTM B633 Type 11 Class 12 Installation Tools: • HangerMate drive socket: EZE215 with safety set feature; automatically disengages when anchor is seated • Recommended power tool: Contractor -grade screw gun; 12 volt min. cordless or 6 amp. corded tool • In most applications, a pre - drilled hole is not needed. In exceptionally hard wood, drill hole only to minimum size required. 1. The loads indicated above are average ultimate values ochieved under laboratory conditions and appropriate safety factors should be applied for design purposes. 2. NFPA (National Fire Protection Assoc.) minimum fastening requirements are five times the weight of a 15 It section of water - filled pipe plus 250 lbs. This is 1475 lbs. for 4" pipe. 3. All test values were obtained using 3/8 - 16 rod. When 1/4-20 rod is used, the strength of the rod may be less than the pull -out values of the anchors. For more information, contact 4. foods were determined by testing products in the orientation for which they we Textron Fastening Systems • 1.800.435.7213 designed to be used. End - drilled parts were pulled in line with the anchors axis while cross - drilled parts were tested with the force perpendicular to the axis. e-mail: info @tfs.textron.com HangerMate® is a registered trademark of Textron Inc. F„ 4 , ,,4 "^'.%�� *3' .k' R A k k ". ''.fib 4, -14 :. .'F' i 7if�, k° k`f.,.if�,... ' f �t" ''t k!° ' ' S J 7� =M c, :. ® n, � w B '-4.4-,', .ice.^- �r x t:V V 4 ;.1 y „ , 41 .a o- � � �' i'F`^ 'Ma" � � '`� &`�` , 4 1. a� - "' a �' r k,` xr t 1 zr �� :.. r .. ' '' I ., x . 7 1 _ ;- vwwv tolco corn ^,!$P i brand f111�BCO �" .. £ e x _ �i� . Z. o * ' . rx�aa s ` y. ,' R � 1 5 / 2 4 0 01., M1 e rr ., :.. ., . .., - ..,..,..�, - A, ..1 3 e t .. , „�.� ...r . ,�. t. rte Fig. 98 - Rod Stiffener t- l :; Size Range — Secures 3/8" thru 7/8" hanger rod Material — Carbon Steel Function — Secures channel to hanger rod for vertical seismic bracing. %- Finish — Electro Galvanized ` w ' ! rs. ' ��"• t, li1lr Note — Available in HDG finish or Stainless Steel materials. `r , ; r Order By — Figure number j 1 I ; A /j Fig. 99 - All Thread Rod Cut to Length Size Range — Secures 3/8" thru 7/8" rod in ��/ Dimensions • Weights 1" increments `` � / /` Rod Max. Rec. Load Lbs. Material — Carbon Steel (t((l/ Size For Service Temps 650 °F 750 °F Maximum Temperature — 750 °F t`(( Finish — Plain ���� 3/8 610 540 1/2 1130 1010 Note — Available in Electro- Galvanized and �l(( �� 5/8 1810 1610 HDG finish or Stainless Steel materials. "�t(�� 3/4 2710 2420 Order By — Figure number, rod diameter, rod ``t( 7/8 3770 3360 length and finish Fig. 100 - All Thread Rod Full Lengths Size Range — Secures 3/8" thru 7/8" rod in 10' lengths Material — Carbon Steel Maximum Temperature — 750 °F Finish — Plain f ��, - !� Note — Available in Electro- Galvanized and „ 'I j- HDG finish or Stainless Steel materials. ''�i. Order By — Figure number, rod diameter '!�:' -3., and finish (r Dimensions • Weights ' 4r._ Max Rec. Load Lbs. Rod For Service Temps Approx. �( j Size 650 °F 750 °F Wt./100 " 1/4 240 215 12 . 3/8 610 540 29 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 ' 4960 4420 222 1' 4 8000 7140 360 1 11630 10370 510 6 Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92879 • Ph 909.737.5599 • Fax. 909.737,0330 ji Customer Service • 800 786 5266 www.tolco.com SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 11/2/2007 C: \HASS78 \CEDAR RIDGE HOMES.SDF JOB TITLE: CEDAR RIDGE HOMES WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 89.0 40.0 1444.0 88.9 42.9 64.9 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 42.9 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 42.9 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 9.6 K= 4.90 9.2 14.8 2 9.6 K= 4.90 9.5 15.1 Al 9.6 - - - - 10.4 - - - A2 9.6 - - - - 14.0 - - - 3 18.8 K= 4.90 7.0 13.0 A3 18.8 - - - - 9.2 - - - A4 9.6 - - - - 13.7 - - - TOR 9.6 - - - - 16.5 - - - BOR 3.6 - - - - 19.9 - - - METER -1.0 - - - - 39.1 - - - UG -1.0 - - - - 39.6 - - - SOURCE -1.0 SOURCE 64.9 42.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 . DATE: 11/2/2007 C: \HASS78 \CEDAR RIDGE HOMES.SDF JOB TITLE: CEDAR RIDGE HOMES PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 1 -14.8 0.884 PL 8.00 PF 1.3 1 9.6 4.9 9.2 14.8 7.8 150 FTG T PE 0.0 Al 9.6 0.0 10.4' 0.0 0.114 TL 11.00 PV Pipe: 2 -15.1 0.884 PL 5.00 PF 0.9 2 9.6 4.9 9.5 15.1 7.9 150 FTG T PE 0.0 Al 9.6 0.0 10.4 0.0 0.117 TL 8.00 PV Pipe: 3 -29.9 1.109 PL 18.75 PF 3.6 Al 9.6 0.0 10.4 0.0 9.9 150 FTG E PE 0.0 A2 9.6 0.0 14.0 0.0 0.138 TL 25.75 PV Pipe: 4 -13.0 0.884 PL 14.00 PF 2.1 3 18.8 4.9 7.0 13.0 6.8 150 FTG ET PE 0.0 A3 18.8 0.0 9.2 0.0 0.089 TL 24.00 PV Pipe: 5 -13.0 1.109 PL 9.25 PF 0.5 A3 18.8 0.0 9.2 0.0 4.3 150 FTG E PE 4.0 A4 9.6 0.0 13.7 0.0 0.030 TL 16.25 PV Pipe: 6 -13.0 1.109 PL 3.08 PF 0.3 A4 9.6 0.0 13.7 0.0 4.3 150 FTG E PE 0.0 A2 9.6 0.0 14.0 0.0 0.030 TL 10.08 PV Pipe: 7 -42.9 1.109 PL 2.33 PF 2.5 A2 9.6 0.0 14.0 0.0 14.2 150 FTG E PE 0.0 TOR 9.6 0.0 16.5 0.0 0.269 TL 9.33 PV Pipe: 8 -42.9 1.109 PL 2.00 PF 0.8 TOR 9.6 0.0 16.5 0.0 14.2 150 FTG C PE 2.6 BOR 3.6 0.0 19.9 0.0 0.269 TL 3.00 PV Pipe: 9 -42.9 1.109 PL 50.00 PF 17.2 BOR 3.6 0.0 19.9 0.0 14.2 150 FTG 2E PE 2.0 . METER -1.0 0.0 39.1 0.0 0.269 TL 64.00 PV Pipe: 10 FIXED PRESSURE LOSS DEVICE UG -1.0 0.0 39.6 0.0 0.5 psi, 42.9 gpm METER -1.0 0.0 39.1 0.0 Pipe: 11 -42.9 1.000 PL 50.00 PF 25.3 UG -1.0 0.0 39.6 0.0 17.5 140 FTG - - -- PE 0.0 SOURCE -1.0 SRCE 64.9 (N /A) 0.506 TL 50.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 : DATE: 11/2/2007 C: \HASS78 \CEDAR RIDGE HOMES.SDF JOB TITLE: CEDAR RIDGE HOMES • NOTES: (1) Calculations were performed by the HASS 7.8 computer program under license no. 27010344 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.075 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 17.5 ft /sec at pipe 11. (4) PIPE FITTINGS TABLE Pipe Table Name: CASCADE.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 5.00 PAGE: E MATERIAL: PVC150 HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G Ell Tee LngEll ChkV1v BfyVly GatVly 0.884 7.00 3.00 1.00 1.00 1.00 1.00 1.109 7.00 5.00 1.00 1.00 1.00 1.00 c o � td 1-3 WATER SUPPLY ANALYSIS y 100.0 Static: 89.00 psi Resid: 40.00 psi Flow: 1444.0 gpm y,� LEGEND r •• N Available pressure 1 N 1 88.93 psi @ 42.9 gpm t'i o Required pressure 2 64.94 psi @ 42.9 gpm G 80 A. Source Supply Curve A B. System Demand Curve U 0 ( to ro G x H E 2 Z x 1 r m tid P 60.0 7d R cr S '- S z U x E 40.0 • n ( � H p > s m > t 20.0 CO F< �Er) n H Mm H 0.0 B 0 ti ro M 0 -14.7 I I } 1 + 1 1 d ` 400 600 800 1000 1200 1400 1600 1800 2000 'A FLOW (GPM) • • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 = DATE: 11/2/2007 C: \HASS78 \CEDAR RIDGE HOMES.SDF JOB TITLE: CEDAR RIDGE HOMES WATER SUPPLY CURVE 96+ *\ 880 \ I \\ \ \\ 80+ \ \\ \ \ 72+ \\ \\ \ P 64X \\ R 1 \ E 1 \\ S 1 \ S 56+ \ U I \\ R I E 1 \\ 48+ ( 1 \\ P I S I I 40+ * < -40.0 psi @ 1444 gpm Flow Test Point 32+ 24+ 16+ LEGEND 1 X = Required Water Supply 64.94 psi @ 42.9 gpm 8+ 1 0 = Available Water Supply " 88.93 psi 8 42.9 gpm 1 0 + + - +--- + - - - -+ + + + + + +