Report Oct, 2. 2008 3:47PM No. 3410 P. 2
nsTaNVEY'' All Activity Report
Security Solution: / , - 06 2
Page 1 of 2
Activity from 10/01/08 to 10/02/08 with open /close activity.
1116824909
GREENBURG SPACE CENTER
11105 SW GREENBURG RD
TIGARD, OR 97223
503 - 624 -2052
Date Day Panel Zone Event/Comment/Area
10/01/08 02:01 Wed AT ALARM
PERIODIC TEST REPORT
AUTO TEST
10/01/08 02:02 Wed AT ALARM
PERIODIC TEST REPORT
AUTO TEST
10/01/08 14:29 Wed 4 ALARM
WATER FLOW
RISER #2
10/01/08 14:29 Wed ALARM ACK
PIX: 1
10/01/08 14:29 Wed FIRE
TUALATIN FIRE 5035201357
10/01/08 14:29 Wed SYS COMM
USER
10/01/08 14 :29 Wed SYS COMM
LINDA MUNOZ
10/01/08 14:29 Wed IN TEST MO
000:02:30 ALL ZONES
10/01/08 14:29 Wed CALL RES
ANSWER
10/01/08 14:30 Wed COMMENT
DID NOT COMPLETE DISPATCH
10/01/08 14:30 Wed COMMENT
PER LOG
10/01/08 14:30 Wed 4 RESTORE
WATER FLOW
RISER #2
10/01/08 14:30 Wed OUST ERROR
FALSE FIRE
10/01/08 14:30 Wed CALL RES
ANSWERING MACHINE
10/01/08 14:30 Wed CALL RES
LEFT MESSAGE
10/01/08 Wed 2 ALARM
WATER FLOW
RISER #1
10/01/08 14:32 Wed 2 RESTORE
WATER FLOW
RISER #1
10/01/08 14:33 Wed 2 ALARM
WATER FLOW
RISER #1
10/02/08 18 :37
Oct. 2. 2008 3:47PM j ,, No. 3410 P. 3
1 )0(7b 0 - ) 0 (X)
e
Page 2of2
Date Day Panel Zone Event/Comment/Area
10/01/08 14:33 Wed 2 RESTORE
WATER FLOW
RISER #1
10/01/08 14:34 Wed 3 ALARM
FIRE SUPERVISORY
RISER #1
10/01/08 14:34 Wed 3 RESTORE
FIRE SUPERVISORY
RISER #1
10/01/08 14 :34 Wed 5 ALARM
FIRE SUPERVISORY
RISER #2
10/01/08 14:34 Wed 5 RESTORE
FIRE SUPERVISORY
RISER #2
10/01/08 14:35 Wed 7 ALARM
FIRE SUPERVISORY
MAIN VALVE
10/01/08 14:35 Wed 7 RESTORE
FIRE SUPERVISORY
MAIN VALVE
10/01/08 14:35 Wed 8 ALARM
FIRE SUPERVISORY
MAIN VALVE
10/01/08 14:35 Wed 8 RESTORE
FIRE SUPERVISORY
MAIN VALVE
10/01/08 14:36 Wed 6 ALARM
PULL STATION
FACP
10/01/08 14:36 Wed 6 RESTORE
PULL STATION
FACP
10/01/08 14:38 Wed 1 ALARM
SMOKE
FACP SMOKE
10/01/08 14:39 Wed 1 RESTORE
SMOKE
FACP SMOKE
10/01/08 14:39 Wed TMSG TROUBLE
SYSTEM SHUTDOWN
TROUBLE MESSAGE
10/01/08 14:40 Wed TMSG RESTORE
SYSTEM SHUTDOWN
TROUBLE MESSAGE
10/01/08 17:02 Wed OUT OF TES
ALL ZONES
10/02/08 02:01 Thu AT ALARM
PERIODIC TEST REPORT
AUTO TEST
10/02/08 02:02 Thu AT ALARM
PERIODIC TEST REPORT
AUTO TEST
10/02/08 15:35 Thu QUALITY
REPORT FAXED e mailed to the cam melody
10/02/08 18:37
Conventional Monitored Fire Alarm System - Record of Completion
CMFA -ROC blank.doc
Protected Premise: Owner's Rep & Phone:
Greenburg Space Center The Robison Family Trust
11125 SW Greenburg Road
Tigard, OR 97223
1. Type(s) of System or Service:
Local (per NFPA 72, Chapter 3)
Remote Supervising Station (per NFPA 72, Chapter 4)
Monitoring Provided By: Stanley Convergent Security Solutions, Inc.
Phone (for testing):
Number of Phone Lines: '2.
Means of Transmission: y c t
Alarm Codes: Co..nac —'c. "�S>
This system was designed by, and equipment supplied by:
Northwest Fire suppression, Inc., 15385 SW Beaverton Creek Court
Beaverton, OR 97006 Phone: 503 - 644 -7720
Location of "as built" drawings, owner's manual, test reports, and maintenance
records:
A contract for test and inspection in accordance with NFPA 72, 7 -3.2:
(check one) is in effect.
X. Owner has declined test and inspection contract at this time.
Comments: 7r,L•g, c■S
(record of completion — page 2) Z.C. .) v V `-. cf
2. Record of System Installation:
(Lead installing technician or electrician to complete prior to acceptance testing)
This system has been installed in accordance with the National Electric Code, and
meets all requirements of Article 760 as a Power Limited Fire Alarm system.
After all device installation was complete (except control equipment final
terminations), all initiation, signal and control circuit wiring was tested and found to
be free of opens, shorts and ground faults.
The entire system was installed per the AHJ approved plans, and complete, accurate
"as built" notations have been provided to Northwest Fire Suppression, Inc.
Exceptions:
Installing Contractor 6\ W�S-c
Responsible Journeyman ^Z)t1/4 License # t-l L
Signatur �-- v — Date 5 -D
3. Record of System Operation:
(Responsible testing technician to complete prior to acceptance testing)
All operational functions and features of this system were tested and found to be
working properly in accordance with the approved plans, per NFPA 70, National
Electric Code, Article 760, per NFPA 72, Chapters 1, 3, 4, 5, 6 and 7, and per the
manufacturer's instructions.
I have reviewed the "as built" drawings and find that they are accurate and complete.
Exceptions:
Certifying Contractor 1.1-cW FS; toa
Responsible Technician �p\a License # 1{3c\ LF,
Signature tea, T�,_ � Date 1- - -f -OS
(record of completion —page 3) p 24' 0 5 - oc �J �
4. Alarm Initiating Devices (indicate quantities)
Manual Stations
Ionization Smoke Detectors
\ Photoelectric Smoke Detectors
Photoelectric Duct Detectors
Other Smoke / Flame Detectors, type
Fixed Temperature Heat Detectors
Fixed Temperature Heat / Rate of Rise Detectors
Rate Anticipated or Compensated Heat Detectors
Feet of Linear Heat Detector
Z Sprinkler Waterflow Switches
Other Initiating Devices (i.e. satellite panels, hood systems, etc.)
List them:
5. Supervisory Signal Initiating Devices (indicate quantities)
Sprinkler Valve Tamper Switches
Sprinkler Low Air Pressure Switches
Other Supervisory Switches (i.e. fire pump, water supply, generator, etc.)
List them:
'Z — ° Z3 - 7
(record of completion — page 4)
6. Alarm Notification Appliances and Circuits (quantities)
Notification Circuits (Zones)
Horn / Strobes Strobes (only) Horns (only)
Bells Other (list them) Annunciators
7. Signaling Line Circuits (Addressable Systems Only)
Quantity: N/A Style: N/A
8. System Power Supplies
Fire Alarm Control Panel:
Primary (Main): Nominal Voltage 120 VAC Breaker Current Rating: 'Amps
Is this a dedicated branch circuit, with the disconnect means mechanically
protected, and with a red marking (per NFPA 72, 1- 5.2.5.2)? Yes or No y
Breaker Location:a..�
Secondary (Standby):
Sealed Lead Acid Batteries, 12 Amp Hrs. Providing (24, 60 or 90) 60 Hrs.
Or
Emergency Standby System (U.P.S.): (check as applies) NA
Per National Electric Code, Article 700
Per National Electric Code, Article 701
Per National Electric Code, Article 702 (plus Article 700 or 701)
Notification Expansion Panels: NA
Primary (Main): Nominal Voltage 120 VAC Breaker Current Rating: _ Amps
Is this a dedicated branch circuit, with the disconnect means mechanically
protected, and with a red marking (per NFPA 72, 1- 5.2.5.2)? Yes or No
Breaker Location(s):
Secondary (Standby):
Sealed Lead Acid Batteries, Amp Hrs. Providing (24, 60 or 90) Hrs.
(record of completion —page 5) LOLA � ' (--J ZJ�
9. System Software
Operating System Software Revision Level (on IC): N/A
Application Software Revision Level: N/A
Revision Completed (Installed) By: N/A
Company: N/A
10. Comments
System Deviations From the Referenced NFPA Standards (list if any):
11. Acceptance Testing Statements
Commissioning Technician:
I have tested and witnessed satisfactory performance of all system devices and control
functions, and/or have noted any exceptions on this Record of Completion.
Date l -- ZS -
Local Authority (or Authorities) Having Jurisdiction:
This system has been inspected and is accepted for the jurisdiction I represent.
Name ' Representing C T K---(i
Comments: 4 1004 t )C -; (/v ` a-G 0
Signed Date \ OA A -I S.
Name Representing
Comments:
Signed Date