Specifications (3) Ooe ?c--o4 4111 , , August 13, 2004 ( CflYOFTG ARDI OREGON Kamelia Massih Massih LLC PO Box 108 Beaverton, OR 97075 RE: NEW OFFICE BUILDING • Project Information Building Permit: BUP2004 -00297 Occupancy Type: B Tenant Name: Pacific Park Plaza Construction Type: VN Address: 13000 SW Pacific Highway Occupant Load: NA Area: 9,901 Sq Ft Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The plans that have been submitted are lacking enough information to perform a complete plan review. Please see the attached Tri- County Checklist for required information for a complete submittal. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. If you wish to have a meeting regarding this review, Brian Blalock and I would gladly meet with you and the design engineer. You can reach Brian at (503) 718 -2436. Respectfully, Gary Lampella, Building Official c. Brian Blalock, Plans Examination Supervisor File 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 M6; t I .13 -(-9qr s u(7 z - =�- Commercial Application Checklist. L = z° '11'' City of Tigard 201 C,ty of Tigard 13125 SW Hall Blvd., Tigard, OR 97223 : - . Phone: (503) 639 -4171, Fax: (503) 598 -1960 BUN DING - ,-; t.Jfv1ON Internet address: www.ci.tigard.or.us PROJECT `INFORM.. TION ' Project name: et. I (k Date: 6 l2_Z l C 4 Address: 0"0 (j - City: , Aid State: is ZIP: Scope of work: is S4 g an 0 - A ; Reference no.: 51> Zo o - co a 1 Map and to - of no.: Z 5 O 2 (ig ( cox jof Contact person name: , g (� � Company: M ' p LL_ Phone: — _ jo Gl 1 Fax: 6 3 _ (o (1.4 - D S Cellular phone: G 5 y t4 _ I t� E -mail: triAi l e) S ' inform . aj VYl • NOTES AND INSTRUCTIONS in The purpose of this checklist is to help define a complete submittal package for the scope of work. Plan review will not take place until a complete package is submitted. ® This checklist can be used for all commercial construction projects, including new construction, additions, alterations and tenant improvements. in For complex projects, applicants should use the "location" space to note the item's location and page number from the plans or the specification book. ® It is not necessary to duplicate submittal information, even if it is asked for in multiple sections. l In the checklist, "Required" means that the applicant must provide this information for plan review. ® In the checklist, "P" means — • if checked by the applicant — the information is provided for the plan review. • if checked by the plans reviewer — this information is required for the plan review. ® In the checklist, "NA" means that the information does not apply. ® Choose only those sections of the checklist that apply to your scope of work. Section 1.0, "General Project Data," must be included with each • ro'ect submitted. ( T _..,: PRE SU BijITTAL = PROCE SS An applicant may request a pre - submittal meeting with representatives of the jurisdiction in which the project will be built. The meeting may take place during the conceptual, schematic, or in- progress phase, or when the applicant has completed plans. F .., INDEX;; OF :CHECKLIST SECTIONS 1.0 General project data Page 2 7.0 Mechanical data (Types I and II 2.0 Civil data Page 2 kitchen -hood permits) Page 6 3.0 Architectural data Page 3 8.0 Plumbing data Page 7 4.0 Structural data Page 4 9.0 Electrical data Page 8 5.0 Mechanical data (new construction, tenant 10.0 Fire - suppression data Page 9 improvement, gas - piping permits) Page 5 11.0 Fire - detection and fire -alarm data Page 9 6.0 Mechanical data (additional or replacement 12.0 Re -roof installation data Page 10 rooftop - equipment installation permits) Page 6 13.0 Jurisdictional requirements Page 10 This checklist is for building department jurisdictions in Clackamas, Multnomah, and Washington counties. ra ( )i v1 i� o „v■ a{- r v.#1 440 -2734 (8/01 /WEB /COM) is \Dsts \ Forms \COM- AppChecklist.doc 03/15/02 SECTION 10— GENERAL PROJECT .DATA { Construction documents Location (sheet number or spec section) 1.1 ® Required No. of sets of plans: New: 1 TI: 2 1.2 ® Required Cover sheet title block 1.3 ® Required Cover sheet vicinity map 1.4 ® Required Cover sheet plan index 1.5 FrP ❑ NA Code summary 1.6 2 ❑ NA Deferred submittal summary 1.7 ❑ P ❑ NA Professional stamp and signature 1.8 L ❑ NA Fire and life- safety plan 1.9 ❑ P ❑ NA Landscape plan 1.10 ❑ P ❑ NA Landscape specifications Supporting documents Notes 1.20 ❑ P ❑ NA Land -use or planning actions 1.21 ❑ P ❑ NA Required fire -flow calculations 1.22 ❑ ❑ NA Fire- hydrant flow -test report 1.23 'A P ❑ NA Fire department or fire district building survey report 1.24 ❑ P ❑ NA Material safety data sheets (MSDS) SECTION-" 2 0 ;=–, CIVIL DATA ` ., i... a Construction documents Location (sheet number or spec section) 2.1 ® Required Site plan 2.2 ® Required Site utility plan 2.3 ® Required Grading plan 2.4 ® Required Erosion - control plan 2.5 ❑ P ❑ NA Utility -vault location and details Supporting documents Notes 2.20 ❑ P ❑ NA GeotechnicaUsoil engineer report 2.21 ❑ P ❑ NA Storm -water calculations 2.22 ❑ P ❑ NA Site retaining -wall structural calculations 2.23 ❑ P ❑ NA "Assurance of Compliance" with environmental rules .... 440 -2734 (8 /01/WEB /COM) Tri -County Commercial Application Checklist 2 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties is \Dsts \ Forms \COM- AppCheckl ist.doc L.v , cSE CT 1O N ,: ` 3 ` 0 ' ,A RC HI T ECT,URA L- ' DAT A ' ,r r _, < Construction documents Location (sheet number or spec section) 3.1 ® Required Floor plan(s) 3.2 ® Required Transverse and longitudinal cross sections 3.3 ® Required OSSC Chapter 11 accessibility requirements 3.4 ❑ P ❑ NA Interior elevations 3.5 ❑ P ❑ NA Exterior elevations 3.6 ❑ P ❑ NA Roof plans 3.7 ❑ P ❑ NA Exterior wall sections and details 3.8 P ❑ NA Reflected ceiling plan(s) . _ L C ? f j o 3.9 `'Fr P ❑ NA Fire -rated construction details l ( 3.10 .X P ❑ NA Energy code compliant construction details and Y� / v cN V1' specifications n 3.11 IS P ❑ NA Door schedule v .1v 12-n4_ + `" Z 3.12 P ❑ NA Glazing schedule ,..... — .... i.0 .t.... .u.T.,.rt� 3.13 f ] P ❑ NA Furniture plan Supporting documents Notes 3.20 1Z1 P ❑ NA Energy code compliance forms /calculations 3.21 ❑ P ❑ NA . Material safety data sheets (MSDS) 3.22 ❑ P ❑ NA Hazardous materials inventory statement (HMIS) 3.23 ❑ P ❑ NA Hazardous materials management plan (HMMP) 3.24 F P ❑ NA Written fire and life- safety evacuation plan for area � lV � - g of rescue assistance V • 3.25 ❑ P ❑ NA Active and passive smoke - control information c mt 5[>1ecr l 0 G( a h. clzc'- 7 4- r (MCI U e 5 /e v(( $ ck60(0/ 6 Vk r d a. - ,k A (011A vl 1 ��. ehtvi Or . V 5 y a - h t1 ®d1 re 5 (d ts4 440 -2734 (8 /01/WEB /COM) Tri-County Commercial Application Checklist 3 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties is \Dsts \Forms \COM- AppCheckl i st.doc SECTION 4 0 2= ;STRUCTURAL 4 DATA Construction documents Location (sheet number or spec section) 4.1 ® Required Structural cover sheet 4.2 ❑ P ❑ NA Foundation plan 4.3 ❑ P ❑ NA Under -slab mechanical plan 4.4 ❑ P ❑ NA Under -slab electrical plan 4.5 ❑ P ❑ NA Under -slab plumbing plan 4.6 P ❑ NA Floor framing plan 4.7 M P ❑ NA Roof framing plan 4.8 P ❑ NA Structural elevations 4.9 ! P ❑ NA Structural details and cross sections 4.10 ❑ P ❑ NA Standpipe information 4.11 ❑ P ❑ NA Special inspector /structural observation matrix Supporting documents Notes _ 4.20 ❑ P ❑ NA Geotechnical/soil engineer report 4.21 ❑ P ❑ NA Site - specific seismic hazard report 4.22 ❑ P ❑ NA Design narrative 4.23 ❑ P ❑ NA Structural calculations 440 -2734 (8/01/WEB /COM) Tri- County Commercial Application Checklist 4 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties 1. \DstsWorms \COM-AppChecklist.doc f 7 - Zzy)q -66 2_ C ,SECr` �ON_'S0 „ -,. MECHANICAL; DATA ( \Tew< cons true ion, 'tenant'. Improvement, gas piping permits)° Construction documents Location (sheet number or spec section) 5.1 ® Required Floor plan 5.2 ® Required Equipment schedule 5.3 ❑ P ❑ NA Site plan 5.4 ❑ P ❑ NA Under -slab mechanical plan 5.5 ❑ P ❑ NA Roof plan 5.6 ❑ P ❑ NA Fuel gas piping plan 5.7 ❑ P ❑ NA HVAC equipment and duct plan(s) 5.8 ❑ P ❑ NA Roof access details 5.9 ❑ P ❑ NA Duct smoke detector plans 5.10 ❑ P ❑ NA Fire /smoke damper locations 5.11 ❑ P ❑ NA Smoke control plan 5.12 ❑ P ❑ NA Outside air (OSA) table 5.13 ❑ P ❑ NA Refrigeration equipment and piping plan 5.14 ❑ P ❑ NA Kitchen equipment plan 5.15 ❑ P ❑ NA Type I and/or Type II kitchen hood plan (see Section 7.0 — Mechanical Data) 5.16 ❑ P ❑ NA Fume /vapor hood plan 5.17 ❑ P ❑ NA Process piping/product and/or exhaust - conveying duct plan 5.18 ❑ P ❑ NA Fire -rated construction details 5.19 ❑ P ❑ NA Equipment hanger /fastener details Supporting documents Notes 5.20 ® Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 5.21 El P ❑ NA Equipment manufacturers' catalog "cut sheets" or specifications 5.22 ❑ P ❑ NA Outside air (OSA) calculations 5.23 ❑ P ❑ NA Smoke- control calculations 5.24 ❑ P ❑ NA Combustion air calculations 5.25 ❑ P ❑ NA Fuel gas piping sizing calculations 5.26 ❑ P ❑ NA Make -up air calculations 5.27 ❑ P ❑ NA Energy code compliance forms 5.28 ❑ P ❑ NA Boiler information 440 -2734 (8 /01/WEB /COM) Tri -County Commercial Application Checklist 5 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties i : \ Dsts \Forms \CO M- AppCheckl i st.doc SECTIONr.6 0. , MECHANICAL' DATA` Additional,or.,re lacement roofto installation , permitsjo�� Construction documents Location (sheet number or spec section) 6.1 Z Required Roof plan 6.2 ❑ P ❑ NA Roof framing plan 6.3 ❑ P ❑ NA Fuel gas piping plan 6.4 ❑ P ❑ NA Roof access details Supporting documents Notes 6.20 ® Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 6.21 ❑ P ❑ NA Equipment manufacturers' catalog "cut sheets" or specifications 6.22 ❑ P ❑ NA Fuel gas piping sizing calculations 6.23 ❑ P ❑ NA Energy code compliance forms SECTION . 7 0, ; MECHANICAL DATA- (Type ? I 'and Ta pe,II'. kitchen hood p emit t's) E Construction documents Location (sheet number or spec section) 7.1 ® Required Site plan 7.2 ® Required Floor plan(s) 7.3 ® Required Kitchen equipment plan 7.4 ® Required Kitchen equipment and hood elevations 7.5 ❑ P ❑ NA Roof plan 7.6 ❑ P ❑ NA Cross sections through hoods, ducts and shafts 7.7 ❑ P ❑ NA Fire -rated construction details 7.8 ❑ P ❑ NA Fire suppression details Supporting documents Notes 7.20 ® Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 7.21 ® Required Make -up air calculations 7.22 ❑ P ❑ NA Equipment manufacturers' catalog "cut sheets" or specifications 7.23 ❑ P ❑ NA Hood/grease extractor listing documentation 7.24 ❑ P ❑ NA Hood/grease duct sizing calculations 7.25 ❑ P ❑ NA Fire suppression information 440 -2734 (8 /0l/WEB /COM) Tri- County Commercial Application Checklist 6 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties \Dsts\Forms \CO M- AppCheckl ist.doc th 1 1/9' '212,6 _ l ��EC1"�ON'8 0 tiPLUA�IBING�pDATA Construction documents Location (sheet number or spec section) 8.1 ® Required Floor plan(s) 8.2 ® Required Piping and material schedule 8.3 ® Required Equipment layout plan 8.4 ® Required Fixture schedule 8.5 ❑ P ❑ NA Site utility plan 8.6 ❑ P ❑ NA Building cross section 8.7 ❑ P ❑ NA Rise diagram 8.8 ❑ P ❑ NA Roof plan 8.9 ❑ P ❑ NA Back flow prevention location 8.10 ❑ P ❑ NA Irrigation plan 8.11 ❑ P ❑ NA Fire -rated construction details 8.12 ❑ P ❑ NA Under -slab plumbing plan Supporting documents Notes 8.20 0 Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 8.21 ❑ P ❑ NA Equipment manufacturers' catalog "cut sheets" or specifications 8.22 ❑ P ❑ NA Utility maintenance agreements 8.23 ❑ P ❑ NA Water supply calculations 8.24 ❑ P ❑ NA Sanitary system calculations 8.25 ❑ P ❑ NA Irrigation demand calculations 8.26 ❑ P ❑ NA Roof drain and storm water calculations 440 -2734 (8 /01 /WEB /COM) Tri -County Commercial Application Checklist 7 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties 1: \Dsts \Forms \COM- AppCheckl i st.doc SECTION: 9'0 W '- 'ELECTRICAL °`DATA " ; ... .,a Construction documents Location (sheet number or spec section) 9.1 ® Required No. of sets of plans: 2 9.2 ® Required Floor plan(s) 9.3 ® Required Electrical load calculations 9.4 ® Required One line diagram 9.5 ® Required Feeder riser diagram 9.6 ® Required Available fault current information 9.7 ® Required Panel schedule(s) 9.8 ❑ P ❑ NA Site electrical plan 9.9 ❑ P El NA Fire -rated construction details 9.10 ❑ P El NA Lighting plan 9.11 ❑ P ❑ NA Emergency power system and emergency lighting plan 9.12 El P ❑ NA Under -slab electrical plan Supporting documents Notes 9.20 ® Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 9.21 ❑ P ❑ NA Energy code compliance forms and calculations for lighting 9.22 ❑ P ❑ NA Emergency power system specifications 9.23 ❑ P ❑ NA Feeder riser information 9.24 El P ❑ NA Lighting equipment manufacturers' catalog "cut sheets" or specifications 440 -2734 (8 /OI/WEB /COM) Tri-County Commercial Application Checklist 8 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties is \ Dsts\Forrns \CO M - AppCheckl i st.doc . r c - ( �c) 7 7 §EC 9ON `100 FIRE, SUPPRESSION: DATA Construction documents Location (sheet number or spec section) 10.1 ® Required Floor plan(s) 10.2 Z Required Sprinkler piping plan(s) 10.3 ❑ P ❑ NA Site plan 10.4 ❑ P ❑ NA Standpipe information 10.5 ❑ P ❑ NA Back flow prevention information 10.6 ❑ P ❑ NA Reflected ceiling plan(s) 10.7 ❑ P ❑ NA Transverse and longitudinal cross sections 10.8 ❑ P ❑ NA Fire -rated construction details 10.9 ❑ P ❑ NA Specialty fire suppression system plans and list of systems Supporting documents Notes 10.20 ® Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 10.21 ® Required Equipment manufacturers' catalog "cut sheets" 10.22 ❑ P ❑ NA Hydraulic calculations 10.23 ❑ P ❑ NA Specialty fire suppression system information SECTION 1 1 0 FIRE DETECTION 'AND ALARM DATA Construction documents Location (sheet number or spec section) 11.1 ZRequired Floor plan(s) 11.2 ❑ P ❑ NA Site plan 11.3 ❑ P ❑ NA Reflected ceiling plan(s) 11.4 ❑ P ❑ NA Transverse and longitudinal cross sections 11.5 ❑ P ❑ NA Wiring schematic 11.6 ❑ P ❑ NA Elevator recall information 11.7 ❑ P ❑ NA Operational matrix 11.8 ❑ P ❑ NA Fire -rated construction details 11.9 ❑ P ❑ NA Standard electrical notes Supporting documents Notes 11.20 ® Required Structural calculations for vertical loads and lateral loads for equipment weighing over 400 pounds 11.21 ® Required Equipment manufacturers' catalog "cut sheets" 11.22 ® Required Installer certification information 11.23 ❑ P ❑ NA Battery calculations 11.24 ❑ P ❑ NA Sample fire alarm log book 11.25 ❑ P ❑ NA Emergency power system specifications 11.26 ❑ P ❑ NA Monitoring station information 1 1.27 ❑ P ❑ NA Voltage drop calculations 440 -2734 (8 /01/WEB /COM) Tri-County Commercial Application Checklist 9 For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties is \Dsts\Forms \COM- AppCheckl ist.doc SECTION 12.0 {= RERO0 IhrSTALLATION DATA- N ! Construction documents Location (sheet number or spec section) 12.1 ® Required Site plan or building location map 12.2 ® Required . - Occupancy classification 12.3 ® Required Type of construction 12.4 ® Required Minimum roof class required 12.5 ® Required Class of roofing to be installed 12.6 ® Required Roof plan 12.7 r P ❑ NA Parapet and scupper cross section(s) Supporting documents Notes 12.20 ® Required Pre -re -roof inspection report 12.21 ® Required Roofing system listing information 12.22 ® Required Roofing manufacturer's catalog "cut sheets" 12.23 ❑ P ❑ NA Structural calculations 12.25 ❑ P ❑ NA Structural engineer's report SECTION, 13 0';= 4 L1RISDICTIQNAL SPECIFIC REQUIREMENTS r, > t Construction documents Item Location (sheet number or spec section) 13.1 ❑ P ❑ NA ❑ Required 13.2 ❑ P ❑ NA ❑ Required 13.3 ❑ P ❑ NA ❑ Required 13.4 ❑ P ❑ NA ❑ Required 13.5 ❑ P ❑ NA ❑ Required 13.6 ❑ P ❑ NA ❑ Required 13.7 ❑ P ❑ NA ❑ Required 13.8 ❑ P ❑ NA ❑ Required 13.9 ❑ P ❑ NA ❑ Required 13.10 ❑ P ❑ NA ❑ Required 440 -2734 (8 /01/WEB /COM) Tri-County Commercial Application Checklist 10 For use in building department jurisdictions in Clackamas, Multnomah; and Washington Counties is \Dsts \Forms \COM- AppChecklist eloc