Specifications (3) Ooe ?c--o4
4111
, ,
August 13, 2004
( CflYOFTG ARDI
OREGON
Kamelia Massih
Massih LLC
PO Box 108
Beaverton, OR 97075
RE: NEW OFFICE BUILDING
•
Project Information
Building Permit: BUP2004 -00297 Occupancy Type: B
Tenant Name: Pacific Park Plaza Construction Type: VN
Address: 13000 SW Pacific Highway Occupant Load: NA
Area: 9,901 Sq Ft Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The plans that have been submitted are lacking enough information to perform a
complete plan review. Please see the attached Tri- County Checklist for required information
for a complete submittal.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
If you wish to have a meeting regarding this review, Brian Blalock and I would gladly meet
with you and the design engineer. You can reach Brian at (503) 718 -2436.
Respectfully,
Gary Lampella,
Building Official
c. Brian Blalock, Plans Examination Supervisor
File
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
M6; t I .13 -(-9qr s u(7 z - =�-
Commercial Application Checklist. L = z°
'11'' City of Tigard 201
C,ty of Tigard 13125 SW Hall Blvd., Tigard, OR 97223 : - .
Phone: (503) 639 -4171, Fax: (503) 598 -1960 BUN DING - ,-; t.Jfv1ON
Internet address: www.ci.tigard.or.us
PROJECT `INFORM.. TION '
Project name: et. I (k Date: 6 l2_Z l C 4
Address: 0"0 (j - City: , Aid State: is ZIP:
Scope of work: is S4 g an 0 - A ;
Reference no.: 51> Zo o - co a 1 Map and to - of no.: Z 5 O 2 (ig ( cox jof
Contact person name: , g (� � Company: M ' p LL_
Phone: — _ jo Gl 1 Fax: 6 3 _ (o (1.4 - D S
Cellular phone: G 5 y t4 _ I t� E -mail: triAi l e) S ' inform . aj VYl
• NOTES AND INSTRUCTIONS
in The purpose of this checklist is to help define a complete submittal package for the scope of work. Plan
review will not take place until a complete package is submitted.
® This checklist can be used for all commercial construction projects, including new construction, additions,
alterations and tenant improvements.
in For complex projects, applicants should use the "location" space to note the item's location and page
number from the plans or the specification book.
® It is not necessary to duplicate submittal information, even if it is asked for in multiple sections.
l In the checklist, "Required" means that the applicant must provide this information for plan review.
® In the checklist, "P" means —
• if checked by the applicant — the information is provided for the plan review.
• if checked by the plans reviewer — this information is required for the plan review.
® In the checklist, "NA" means that the information does not apply.
® Choose only those sections of the checklist that apply to your scope of work. Section 1.0, "General Project
Data," must be included with each • ro'ect submitted.
( T _..,: PRE SU BijITTAL = PROCE SS
An applicant may request a pre - submittal meeting with representatives of the jurisdiction in which the project
will be built. The meeting may take place during the conceptual, schematic, or in- progress phase, or when the
applicant has completed plans.
F .., INDEX;; OF :CHECKLIST SECTIONS
1.0 General project data Page 2 7.0 Mechanical data (Types I and II
2.0 Civil data Page 2 kitchen -hood permits) Page 6
3.0 Architectural data Page 3 8.0 Plumbing data Page 7
4.0 Structural data Page 4 9.0 Electrical data Page 8
5.0 Mechanical data (new construction, tenant 10.0 Fire - suppression data Page 9
improvement, gas - piping permits) Page 5 11.0 Fire - detection and fire -alarm data Page 9
6.0 Mechanical data (additional or replacement 12.0 Re -roof installation data Page 10
rooftop - equipment installation permits) Page 6 13.0 Jurisdictional requirements Page 10
This checklist is for building department jurisdictions in Clackamas, Multnomah, and Washington counties.
ra ( )i v1 i� o „v■ a{- r v.#1
440 -2734 (8/01 /WEB /COM)
is \Dsts \ Forms \COM- AppChecklist.doc 03/15/02
SECTION 10— GENERAL PROJECT .DATA
{
Construction documents Location (sheet number or spec section)
1.1 ® Required No. of sets of plans: New: 1 TI: 2
1.2 ® Required Cover sheet title block
1.3 ® Required Cover sheet vicinity map
1.4 ® Required Cover sheet plan index
1.5 FrP ❑ NA Code summary
1.6 2 ❑ NA Deferred submittal summary
1.7 ❑ P ❑ NA Professional stamp and signature
1.8 L ❑ NA Fire and life- safety plan
1.9 ❑ P ❑ NA Landscape plan
1.10 ❑ P ❑ NA Landscape specifications
Supporting documents Notes
1.20 ❑ P ❑ NA Land -use or planning actions
1.21 ❑ P ❑ NA Required fire -flow calculations
1.22 ❑ ❑ NA Fire- hydrant flow -test report
1.23 'A P ❑ NA Fire department or fire district building survey report
1.24 ❑ P ❑ NA Material safety data sheets (MSDS)
SECTION-" 2 0 ;=–, CIVIL DATA ` ., i... a
Construction documents Location (sheet number or spec section)
2.1 ® Required Site plan
2.2 ® Required Site utility plan
2.3 ® Required Grading plan
2.4 ® Required Erosion - control plan
2.5 ❑ P ❑ NA Utility -vault location and details
Supporting documents Notes
2.20 ❑ P ❑ NA GeotechnicaUsoil engineer report
2.21 ❑ P ❑ NA Storm -water calculations
2.22 ❑ P ❑ NA Site retaining -wall structural calculations
2.23 ❑ P ❑ NA "Assurance of Compliance" with environmental rules ....
440 -2734 (8 /01/WEB /COM) Tri -County Commercial Application Checklist 2
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
is \Dsts \ Forms \COM- AppCheckl ist.doc
L.v
, cSE CT 1O N ,: ` 3 ` 0 ' ,A RC HI T ECT,URA L- ' DAT A ' ,r r _, <
Construction documents Location (sheet number or spec section)
3.1 ® Required Floor plan(s)
3.2 ® Required Transverse and longitudinal cross sections
3.3 ® Required OSSC Chapter 11 accessibility requirements
3.4 ❑ P ❑ NA Interior elevations
3.5 ❑ P ❑ NA Exterior elevations
3.6 ❑ P ❑ NA Roof plans
3.7 ❑ P ❑ NA Exterior wall sections and details
3.8 P ❑ NA Reflected ceiling plan(s) . _ L C ? f j o
3.9 `'Fr P ❑ NA Fire -rated construction details l (
3.10 .X P ❑ NA Energy code compliant construction details and Y� / v cN V1'
specifications n
3.11 IS P ❑ NA Door schedule v .1v 12-n4_ + `" Z
3.12 P ❑ NA Glazing schedule ,..... — .... i.0 .t.... .u.T.,.rt�
3.13 f ] P ❑ NA Furniture plan
Supporting documents Notes
3.20 1Z1 P ❑ NA Energy code compliance forms /calculations
3.21 ❑ P ❑ NA . Material safety data sheets (MSDS)
3.22 ❑ P ❑ NA Hazardous materials inventory statement (HMIS)
3.23 ❑ P ❑ NA Hazardous materials management plan (HMMP)
3.24 F P ❑ NA Written fire and life- safety evacuation plan for area � lV � - g
of rescue assistance V •
3.25 ❑ P ❑ NA Active and passive smoke - control information
c mt 5[>1ecr l 0 G( a h. clzc'-
7 4- r
(MCI U e 5 /e v(( $ ck60(0/
6 Vk r d a. - ,k A (011A
vl
1
��. ehtvi Or . V 5
y
a
- h t1 ®d1 re 5 (d ts4
440 -2734 (8 /01/WEB /COM) Tri-County Commercial Application Checklist 3
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
is \Dsts \Forms \COM- AppCheckl i st.doc
SECTION 4 0 2= ;STRUCTURAL 4 DATA
Construction documents Location (sheet number or spec section)
4.1 ® Required Structural cover sheet
4.2 ❑ P ❑ NA Foundation plan
4.3 ❑ P ❑ NA Under -slab mechanical plan
4.4 ❑ P ❑ NA Under -slab electrical plan
4.5 ❑ P ❑ NA Under -slab plumbing plan
4.6 P ❑ NA Floor framing plan
4.7 M P ❑ NA Roof framing plan
4.8 P ❑ NA Structural elevations
4.9 ! P ❑ NA Structural details and cross sections
4.10 ❑ P ❑ NA Standpipe information
4.11 ❑ P ❑ NA Special inspector /structural observation matrix
Supporting documents Notes _
4.20 ❑ P ❑ NA Geotechnical/soil engineer report
4.21 ❑ P ❑ NA Site - specific seismic hazard report
4.22 ❑ P ❑ NA Design narrative
4.23 ❑ P ❑ NA Structural calculations
440 -2734 (8/01/WEB /COM) Tri- County Commercial Application Checklist 4
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
1. \DstsWorms \COM-AppChecklist.doc
f 7
- Zzy)q -66 2_ C
,SECr` �ON_'S0 „ -,. MECHANICAL; DATA ( \Tew< cons true ion, 'tenant'. Improvement, gas piping permits)°
Construction documents Location (sheet number or spec section)
5.1 ® Required Floor plan
5.2 ® Required Equipment schedule
5.3 ❑ P ❑ NA Site plan
5.4 ❑ P ❑ NA Under -slab mechanical plan
5.5 ❑ P ❑ NA Roof plan
5.6 ❑ P ❑ NA Fuel gas piping plan
5.7 ❑ P ❑ NA HVAC equipment and duct plan(s)
5.8 ❑ P ❑ NA Roof access details
5.9 ❑ P ❑ NA Duct smoke detector plans
5.10 ❑ P ❑ NA Fire /smoke damper locations
5.11 ❑ P ❑ NA Smoke control plan
5.12 ❑ P ❑ NA Outside air (OSA) table
5.13 ❑ P ❑ NA Refrigeration equipment and piping plan
5.14 ❑ P ❑ NA Kitchen equipment plan
5.15 ❑ P ❑ NA Type I and/or Type II kitchen hood plan
(see Section 7.0 — Mechanical Data)
5.16 ❑ P ❑ NA Fume /vapor hood plan
5.17 ❑ P ❑ NA Process piping/product and/or exhaust - conveying
duct plan
5.18 ❑ P ❑ NA Fire -rated construction details
5.19 ❑ P ❑ NA Equipment hanger /fastener details
Supporting documents Notes
5.20 ® Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
5.21 El P ❑ NA Equipment manufacturers' catalog "cut sheets"
or specifications
5.22 ❑ P ❑ NA Outside air (OSA) calculations
5.23 ❑ P ❑ NA Smoke- control calculations
5.24 ❑ P ❑ NA Combustion air calculations
5.25 ❑ P ❑ NA Fuel gas piping sizing calculations
5.26 ❑ P ❑ NA Make -up air calculations
5.27 ❑ P ❑ NA Energy code compliance forms
5.28 ❑ P ❑ NA Boiler information
440 -2734 (8 /01/WEB /COM) Tri -County Commercial Application Checklist 5
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
i : \ Dsts \Forms \CO M- AppCheckl i st.doc
SECTIONr.6 0. , MECHANICAL' DATA` Additional,or.,re lacement roofto installation , permitsjo�� Construction documents Location (sheet number or spec section)
6.1 Z Required Roof plan
6.2 ❑ P ❑ NA Roof framing plan
6.3 ❑ P ❑ NA Fuel gas piping plan
6.4 ❑ P ❑ NA Roof access details
Supporting documents Notes
6.20 ® Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
6.21 ❑ P ❑ NA Equipment manufacturers' catalog "cut sheets"
or specifications
6.22 ❑ P ❑ NA Fuel gas piping sizing calculations
6.23 ❑ P ❑ NA Energy code compliance forms
SECTION . 7 0, ; MECHANICAL DATA- (Type ? I 'and Ta pe,II'. kitchen hood p emit t's) E
Construction documents Location (sheet number or spec section)
7.1 ® Required Site plan
7.2 ® Required Floor plan(s)
7.3 ® Required Kitchen equipment plan
7.4 ® Required Kitchen equipment and hood elevations
7.5 ❑ P ❑ NA Roof plan
7.6 ❑ P ❑ NA Cross sections through hoods, ducts and shafts
7.7 ❑ P ❑ NA Fire -rated construction details
7.8 ❑ P ❑ NA Fire suppression details
Supporting documents Notes
7.20 ® Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
7.21 ® Required Make -up air calculations
7.22 ❑ P ❑ NA Equipment manufacturers' catalog "cut sheets"
or specifications
7.23 ❑ P ❑ NA Hood/grease extractor listing documentation
7.24 ❑ P ❑ NA Hood/grease duct sizing calculations
7.25 ❑ P ❑ NA Fire suppression information
440 -2734 (8 /0l/WEB /COM) Tri- County Commercial Application Checklist 6
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
\Dsts\Forms \CO M- AppCheckl ist.doc
th 1 1/9' '212,6
_ l
��EC1"�ON'8 0 tiPLUA�IBING�pDATA
Construction documents Location (sheet number or spec section)
8.1 ® Required Floor plan(s)
8.2 ® Required Piping and material schedule
8.3 ® Required Equipment layout plan
8.4 ® Required Fixture schedule
8.5 ❑ P ❑ NA Site utility plan
8.6 ❑ P ❑ NA Building cross section
8.7 ❑ P ❑ NA Rise diagram
8.8 ❑ P ❑ NA Roof plan
8.9 ❑ P ❑ NA Back flow prevention location
8.10 ❑ P ❑ NA Irrigation plan
8.11 ❑ P ❑ NA Fire -rated construction details
8.12 ❑ P ❑ NA Under -slab plumbing plan
Supporting documents Notes
8.20 0 Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
8.21 ❑ P ❑ NA Equipment manufacturers' catalog "cut sheets"
or specifications
8.22 ❑ P ❑ NA Utility maintenance agreements
8.23 ❑ P ❑ NA Water supply calculations
8.24 ❑ P ❑ NA Sanitary system calculations
8.25 ❑ P ❑ NA Irrigation demand calculations
8.26 ❑ P ❑ NA Roof drain and storm water calculations
440 -2734 (8 /01 /WEB /COM) Tri -County Commercial Application Checklist 7
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
1: \Dsts \Forms \COM- AppCheckl i st.doc
SECTION: 9'0 W '- 'ELECTRICAL °`DATA "
; ... .,a
Construction documents Location (sheet number or spec section)
9.1 ® Required No. of sets of plans: 2
9.2 ® Required Floor plan(s)
9.3 ® Required Electrical load calculations
9.4 ® Required One line diagram
9.5 ® Required Feeder riser diagram
9.6 ® Required Available fault current information
9.7 ® Required Panel schedule(s)
9.8 ❑ P ❑ NA Site electrical plan
9.9 ❑ P El NA Fire -rated construction details
9.10 ❑ P El NA Lighting plan
9.11 ❑ P ❑ NA Emergency power system and emergency lighting plan
9.12 El P ❑ NA Under -slab electrical plan
Supporting documents Notes
9.20 ® Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
9.21 ❑ P ❑ NA Energy code compliance forms and calculations
for lighting
9.22 ❑ P ❑ NA Emergency power system specifications
9.23 ❑ P ❑ NA Feeder riser information
9.24 El P ❑ NA Lighting equipment manufacturers' catalog
"cut sheets" or specifications
440 -2734 (8 /OI/WEB /COM) Tri-County Commercial Application Checklist 8
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
is \ Dsts\Forrns \CO M - AppCheckl i st.doc
. r c - ( �c) 7 7
§EC 9ON `100 FIRE, SUPPRESSION: DATA
Construction documents Location (sheet number or spec section)
10.1 ® Required Floor plan(s)
10.2 Z Required Sprinkler piping plan(s)
10.3 ❑ P ❑ NA Site plan
10.4 ❑ P ❑ NA Standpipe information
10.5 ❑ P ❑ NA Back flow prevention information
10.6 ❑ P ❑ NA Reflected ceiling plan(s)
10.7 ❑ P ❑ NA Transverse and longitudinal cross sections
10.8 ❑ P ❑ NA Fire -rated construction details
10.9 ❑ P ❑ NA Specialty fire suppression system plans
and list of systems
Supporting documents Notes
10.20 ® Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
10.21 ® Required Equipment manufacturers' catalog "cut sheets"
10.22 ❑ P ❑ NA Hydraulic calculations
10.23 ❑ P ❑ NA Specialty fire suppression system information
SECTION 1 1 0 FIRE DETECTION 'AND ALARM DATA
Construction documents Location (sheet number or spec section)
11.1 ZRequired Floor plan(s)
11.2 ❑ P ❑ NA Site plan
11.3 ❑ P ❑ NA Reflected ceiling plan(s)
11.4 ❑ P ❑ NA Transverse and longitudinal cross sections
11.5 ❑ P ❑ NA Wiring schematic
11.6 ❑ P ❑ NA Elevator recall information
11.7 ❑ P ❑ NA Operational matrix
11.8 ❑ P ❑ NA Fire -rated construction details
11.9 ❑ P ❑ NA Standard electrical notes
Supporting documents Notes
11.20 ® Required Structural calculations for vertical loads and lateral
loads for equipment weighing over 400 pounds
11.21 ® Required Equipment manufacturers' catalog "cut sheets"
11.22 ® Required Installer certification information
11.23 ❑ P ❑ NA Battery calculations
11.24 ❑ P ❑ NA Sample fire alarm log book
11.25 ❑ P ❑ NA Emergency power system specifications
11.26 ❑ P ❑ NA Monitoring station information
1 1.27 ❑ P ❑ NA Voltage drop calculations
440 -2734 (8 /01/WEB /COM) Tri-County Commercial Application Checklist 9
For use in building department jurisdictions in Clackamas, Multnomah, and Washington Counties
is \Dsts\Forms \COM- AppCheckl ist.doc
SECTION 12.0 {= RERO0 IhrSTALLATION DATA- N !
Construction documents Location (sheet number or spec section)
12.1 ® Required Site plan or building location map
12.2 ® Required . - Occupancy classification
12.3 ® Required Type of construction
12.4 ® Required Minimum roof class required
12.5 ® Required Class of roofing to be installed
12.6 ® Required Roof plan
12.7 r P ❑ NA Parapet and scupper cross section(s)
Supporting documents Notes
12.20 ® Required Pre -re -roof inspection report
12.21 ® Required Roofing system listing information
12.22 ® Required Roofing manufacturer's catalog "cut sheets"
12.23 ❑ P ❑ NA Structural calculations
12.25 ❑ P ❑ NA Structural engineer's report
SECTION, 13 0';= 4 L1RISDICTIQNAL SPECIFIC REQUIREMENTS r, > t
Construction documents Item Location (sheet number or spec section)
13.1 ❑ P ❑ NA ❑ Required
13.2 ❑ P ❑ NA ❑ Required
13.3 ❑ P ❑ NA ❑ Required
13.4 ❑ P ❑ NA ❑ Required
13.5 ❑ P ❑ NA ❑ Required
13.6 ❑ P ❑ NA ❑ Required
13.7 ❑ P ❑ NA ❑ Required
13.8 ❑ P ❑ NA ❑ Required
13.9 ❑ P ❑ NA ❑ Required
13.10 ❑ P ❑ NA ❑ Required
440 -2734 (8 /01/WEB /COM) Tri-County Commercial Application Checklist 10