Permit CITY OF TIGARD - FIRE PROTECTION SYSTEM PERMIT
q
IS ' � COMMUNITY DEVELOPMENT Permit #: FPS2009 -00109
T [GAR D 13125 SW Hall Blvd., Tigard OR 97223 503.639.4171 Date Issued: 11/19/2009
Parcel: 2S 101 DA00101
Jurisdiction: Tigard
Site address: 13190 SW 68TH PKWY 110
Subdivision: TRIANGLE CORPORATE PARK Lot: 3
Project: Business Objects
Project Description: Relocate (5) sprinkler heads.
Owner: FEES
PACIFIC NW PROPERTIES LIMITED PA Description Date Amount
STERN FAMILY LIMITED PARTNERSHIP &, Permit Fee - COM 11/19/2009 $61.85
STERN, HELEN R REV TRUST, 6600 SW 105TH
12% State Surcharge Building 11/19/2009 $7.42
PHONE:
Contractor:
AFP SYSTEMS INC
19435 SW 129TH
TUALATIN, OR 97062
PHONE: 503 - 692 -9284
FAX: 503 - 692 -1186
Type of Use: COM
Class of Work: ALT Type of Const:
Occupancy Grp: Height: ft
Stories:
Commercial Sprinkler System:
Sprinkler Required: Sprinkler Type:
Standpipe Required: Hazard:
Density: Design Area:
K Factor:
Commercial Fire Alarm System:
Fire Alarm Required: Alarm Type:
Pull Station Required: Smoke Detectors Req:
Battery Calcs Provided: Cut Sheets Required:
Total $69.27
Valuations: Required Items and Reports (Conditions)
Sprinkler Valuation: 900
Residential Square Footage:
Fire Alarm Valuation:
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other
applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of
issuance, or if work is suspended for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon
Utility Notif - • -r. Those rules are set forth in OAR 952 - 001 -0010 through OAR 952 - 001 -0100. You may obtain a copy of the rules
or dir- • questions to OU by • 'ng 503.246.6699 or 1.800.332.2344.
Is ued By: ,- 1 / r Permittee Signature: ,
a /
Call 503.639.4175 by 7:00 a.m. for an inspection that business day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
Building Permit Application 1i - DO 90 e
•
Fire Protection System FOR orrlcE USE aN LV . •
R ECEIV
City of Tigard E Recened �� Permit s 0 �
•
y Davy: / 9 a id e9e 9 - aD o
i l l q
13125 SW hall Blvd "Tigard, Olt 97223 NOV 19 2009 Plan Review
1 Phone: 503.639.4171 Fax: 503.598.1960 Date/By: Other Permit:
Re
1 I CiARI) Inspection line: 503.639 4175 / �� D a
DIViSi t Kcadyfliy: See Page 2 for
Internet: wR'tf.tlgard•or.gov V n' GF TiGARD Notified/Method: ad Supplemental )nformelion
BUI LDING _
-
TYPE OF WORK, - REQUIRED DA'L'A :1- AND 2- FAMILYDWELLING
❑ New construction ❑ Demolition -- Penni( fees* are bawd on the value of the work performed.
— Indicate the value (rounded to the nearest dollar) of all
Addition /alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION work indicated on this application.
❑ 1 • and 2-family dwelling g&ommercial /in(lustrial Vahlatiai: S
❑ Accessory building ❑ Multi- tinily Number of bedrooms:
❑ Master builder ❑ Other: Number of bathrooms:
/3/_917 JOl) SI`l'F. INFORMATION AND LOCATION' 4 _ total number of floors:
Job site address_ ±-=) W ( L 5 rn Fwd ■Ai `:;-'1 New dwelling area: square feet
City /State /ZIP: t ,., c„,,1.1 or u ` Garage /carport arca_ square feet
Suite/bldg. /apt. no.: / 10 I Project name: - - -_ Po u , Covered porch area: square feet
Cross street/directions to job site: Deck area: square feet
Other structure arca: square feet
REQUIRED 1)A'TA: COMMERCIAL -USE, CIIE:CKLdST
Subdivision: - -1 Lot no.: Permit fees* are based on the value of the work performed.
fax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
equipment, materials, labor, overhead, and the profit for the
DFSCRI1'1'1ON OF WORK - work indicated on this application.
; :a)- ]_ 0 G Valuation: S �(�O
}- _ Existing building area: `I �;�;) square feet
`, L�\nM — New building arca: )00y square feet
5r PROI'EitTY OWNER ❑ 'TENANT Number of stories:
Name: f j ' v P "1 ie of construction:
—
Address: Occupancy groups:
City /State / /IP: -- -- — _ —„ J Existing_
Phone: ( ) Fax: ( ) New:
APPI ICANT ❑ C:ONIACI' PERSON : NOTIC
Business nani( A Fe - Al} contractors and subcontractors are required to be
i licensed with the Oregon Construction Contractors Board
3 w
Contact name: ,
V _ under ORS 701 and may be required to be licensed in the
Address: 1 4 7 �� ' c - 4J t . jurisdiction in which work is being performed. lithe
City /Slate /ZIP: -i- ,L ,JAI o f� - applicant is exempt from licensing, the following reasons
apply:
Phone: ( S t / 5 ) 6 ° 1 2 41 t 1 Fax:: (L 3) i,, 9 z -1 ( t, i,
E -mail: ,t't - Q . ' ._ Of Sys. cclM • - CONTRACTOR . BUiL DIN(:1'ERMI'1' FEES*
Business name: S �iy G.; tt, __- - - - - - (f'lease,ejer to fee schedule
Permit fee: 6/. F
Address:
- - State surcharge (12% of permit fee): 7 , i/A
City /Slate /7.11': FLS plan review (40% of permit fee): �^
Phone: ( ) Fax: ( ) - (Due upon application) -
Total permit fees: * X /
9.4....._ Amount received:
Authorized S1g11ahlrC
This permit application expires if a permit Is not obtained
Print nannc:
_ 1 within 180 days after it leas been accepted as complete.
r yt.� •,- '� llatc: + Fee methodology set by 7'ri- County Building Industry ` ` _._..... _ Service Board.
r: 9(oi!dingll'enni I s\IlS•1'eimitAprdoc 03/23/06 410.16131(11/07C0>V\4C11)
City of Tigard: Fire Protection Permit Checklist
Page 2 - Supplemental information
Describe work to be done:
1.) 111 New 2.) Modification to sprinkler heads only:
0 Addition F-1-10 heads: No plan review required.
44_ Alteration El 11+ heads: Plan review required.
0 Repair
Number of sprinkler heads: - 3
Additional description of work: p a A cti A L
T )e of S stem Com tete A, B, C orD as a licable :
A.) Commercial Sprinkler
BC \Vet fl . E)ry _
Additional Standpipes
n fo rmation: Hazard Group Li 6 ,4.1-
Density '
Design Area I 5 00
K. Factor
Sprinkler Project Valuation: $
B.) Type 1 - Hood Firc Suppression System
Hood Project Valuation: $
C,) Fire Alarm
Submittal shall Battery Calculations 0 Yes
include: Individual Component 111 Yes
Cut Sheets
Fire Alarm Project Valuation: $
D.) Residential Sprinkler (Stand Alone System)
Square l'ootage: Permit Fee:
0 to 2,000 $187.50
2,001 to 3,600 $232.50
3,601 to 7,200 $292.50
7,201 and greater $381.50
Sprinkler Project Square Footage: sq. ft.
Fire Protection Permit Fees
Project valuation subtotal (see A, 13 & C above): $
Permit fee based on project valuation (see fcc schedule): $
Permit fcc based on square footage (see D above): $
State Surcharge (12% of permit fcc): $
Fl.,S Plan Review (40% of permit fcc): $
TOTAL: $
Ilan review requires a completed application and 2 sets of plans at submittal. Plan review fees are requited at subrnittal.
I: \ Building\ Pennits \ I^PS-PermitApp.doc 0025/08 2
tqco I Fire & Buiiding
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 2.8, 4.2, 4.6' and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
tained when exposed to corrosive at-
G eneral mospheres. Although corrosion resis- Via_ -,,
tant coated sprinklers have passed the � "_ -
Description standard corrosion tests of the appli- '.- • �:
cable approval agencies, the testing is - , -,
The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor- �
5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it 1 tililLik d
dent Sprinklers described in this data is recommended that the end user be i iltri f
sheet are quick response - standard consulted with respect to the suitability
coverage, decorative 3 mm glass bulb of these coatings for any given corro- • h
type spray sprinklers designed for use sive environment. The effects of ambi- %,..-
in light or ordinary hazard, commercial ent temperature, concentration of — -=-
Y
chemicals, and gas /chemical velocity,
occupancies such as banks, hotels, — ""_
p
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be �� r �,Sb Gc G,
plicable, is intended for use in areas exposed. ,
with a finished ceiling. It uses either a An intermediate level versions of the ':,..,---4, - k C.7 c",, two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers - 1 -
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet ,
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- I ; <----
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780
(19,1 mm) of total adjustment from the - . f ,fi"
flush pendent position, or a two -piece WARNINGS e. re 7
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de- �,.
inch NPT) Recessed Escutcheon with scribed herein must be installed and --4"_: "
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this •
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro -
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hav- Model/Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT
with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2 "NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT
Sheet TFP700 for the 'INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT
with respect to handling and instal- TY4831- Upright 8.0K, 1/2 "NPT
lation of sprinkler systems and com- TY4931- Pendent 8.0K, 1/2 "NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171
Page 2 of 10 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE' 1 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE
1/2" T MAKE-IN ESCUTCHEON DEFLECTOR
6
�= fir i - 1 - 1 - 1
:,Trr�,ITtr
E
;
�f 5
2 -114" 7/16„
f (11,1 mm) I 4
(57,2 mm) - - I NOMINAL I I
1 MAKE -IN � 2
1 -9/16" r_r �" "A
I (556/mm) J' V 3
(39,7 mm) WRENCH :� ill jr.
t ill
Air /%1!ti \\ FLATS f
41golif 1
SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. - 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NP MAKE-IN ESCUTCHEON DEFLECTOR
6
i ..--..
h
i �'r
7/16" 5
2- 3/16" m� } MI- (11,1 mm)
i (55,6 mm) . = � �� - I NOMINAMAKE -IN L ' 4
7�
1 -1/2" r� 2- 3/16" �o 2
(38,1 mm) I ill WRENCH (55,6 mm) V 'o. . FLATS 3
I i 1
SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 1/2" NPT i
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 /NCH NPT
TFP171 Page 3 of 10
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE 1/2 MAKE-IN ESCUTCHEON DEFLECTOR
NPT
6
r 7/16" !ter 5
2- 3/16 " ( 11,1 mm)
(55,6 mm)
��� N OMINAL I (38,1 /2" I I ! 2-3/16" . .!D 2
(55,6 mm)
111 - - • FLATS — _ 3
1
SSP DEFLECTOR* f— 2 -7/8" (73,0 mm) DIA. - 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING NOMINAL RECESSED
SURFACE \ NPT MAKE -IN ESCUTCHEON DEFLECTOR
6
t — ..........—
_ 1/2.. Ins 5
�
2- 5/16" } If : (12,7 mm)
(58,7 mm) I�O NOMINAL i I 4
�
1-9/16" r= 014 MAKE -IN
2 -1/4" u'2
(39,7 mm) I Ir L�- WRENCH (57,2 mm) IVI
9 �'r 3
• III -- • FLATS I 7
SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 3/4" NPT f
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Page 4 of 10 TFP171
•7116" (11,1 rnm)
1/2" NOMINAL SSU
NPT MAKE -IN DEFLECTOR
1=5; 5
2 -1/4" } 2- 3/16"
(57,2 mm) 0 = , 1 I (55,6 mm) ; 4
1-9/16" WRENCH r�r V 2
(39,7 mm) FLATS
I -- -- 3
SSP
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 5
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K- FACTOR, 1/2 INCH NPT
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C -UL Listed. fluid expands sufficiently to shatter the
FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A and B for complete activate and water to flow.
approval information including corro-
sion resistant status.) Design
Maximum Working Pressure
Refer to Table C. Criteria
Discharge Coefficient
K = 2.8 GPM /psi / (40,3 LPM /bar1 /2) The Series TY -FRB Pendent and Up-
K = 4.2 GPM /psi / (60,5 LPM /bar1 /2) right Sprinklers are intended for fire
K = 5.6 GPM /psi / (80,6 LPM /bar1/2) protection systems designed in ac-
K = 8.0 GPM /psil/ (115,2 LPM /bar1/2) cordance with the standard installation
rules recognized by the applicable
Temperature Ratings Listing or Approval agency (e.g., UL
Refer to Table A and B Listing is based on the requirements of
Finishes NFPA 13, and FM Approval is based
Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre -
Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style
Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Physical Characteristics c
Frame Bronze E
Button Brass /Copper 0
Sealing Assembly
Beryllium Nickel w /Teflont
Bulb Glass a) a �
Compression Screw Bronze m
Deflector Copper /Bronze 0
Bushing (K =2.8) Bronze
'2
a
in
4—
TFP171 Page 5 of 10
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL CHROME WHITE***
LIQUID BRASS PLATED POLYESTER
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY1231) ) 175 °F /79 °C Yellow 1, 2, 3, 5
UPRIGHT 200F/93°C Green
2.8 (TY1131)
286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY1231)* 175F/79°C Yellow
Figure 6 200 °F /93 °C Green 1, 2, 5
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY1231) ** 175 °F /79 °C Yellow
Figure 7 200F/93°C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY2231)
and 175 °F /79 °C Yellow
UPRIGHT 200F/93°C Green
4.2 (TY2131)
286 °F /141 °C Blue 1 2
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)* 175F/79°C Yellow
Figure 8 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED
155F/68°C Red
PENDENT
(TY2231) ** 175F/79°C Yellow
Figure 9 20OF/93°C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354 -01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin-
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
Page 6 of 10 TFP171
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200F/93°C Green
5.6 (TY3131)
286F/141°C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175 °F /79 °C Yellow
Figure 10 200 °F /93 °C Green
135F/57°C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY3231) ** 175 °F /79 °C Yellow
Figure 11 200 °F /93 °C Green
135F/57°C Orange
PENDENT 155F/68°C Red
(TY4231)
1, 2, 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286F/141°C Blue
3/4"
NPT 135F/57°C Green
RECESSED 155F/68°C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 12 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231) ** 175 °F /79 °C Yellow
Figure 13 200F/93°C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
TY4931
1/2" ( /2" and 175 °F /79 °C Yellow 1, 2, 4, 5, 6 1, 2, 5
NPT UPRIGHT 200F/93°C Green
(TY4831)
286 °F /141 °C Blue
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31- 53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
TFP171 Page 7 of 10
• SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT
NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT(TY3131) OR
1/2" RECESSED PENDENT 175 PSI (12,1 BAR)
NPT (TY3231)
(SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A
8.0 PENDENT(TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting.
Installation (13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used Step 3. Tighten the sprinkler into the
The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con- sprinkler fitting using only the W -Type
be installed in accordance with the fol- nections. Higher levels of torque may 6 Sprinkler Wrench (Ref. Figure 14).
lowing instructions: distort the sprinkler inlet and cause With reference to Figures 1, 2, 3, 4,
leakage or impairment of the sprinkler. and 5, the W-Type 6 Sprinkler Wrench
NOTES is to be applied to the sprinkler wrench
Do not install any bulb type sprinkler if Do not attempt to make -up for insuffi- flats.
the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY -FRB Recessed Pen -
liquid from the bulb. With the sprinkler plate by under- or over - tightening the dent Sprinklers must be installed in
held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc-
should be present. The diameter of the sprinkler fitting to suit. tions.
air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10.
(1,6 mm) for the 135 °F /57 °C to 3/32 right Sprinklers must be installed in 20, 30, or 40 Mounting Plate, as appli-
inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and
temperature ratings. tions. with pipe thread sealant applied to the
A leak tight 1/2 inch NPT sprinkler joint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin
should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting.
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the
mum of 21 . ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type
may be used to install sprinklers with Step 2. With pipe t sealant ap- 7 Recessed Sprinkler Wrench (Ref.
ep e
1/2 NPT connections. A leak tight 3/4 St ht Figure 15). With reference to Figure 1,
inch NPT sprinkler joint should be ob- plied 2 the pipe a th ea, hand tighten 2, 3, and 4, the W -Type 7 Recessed
Page 8 of 10 TFP171
2 -7/8" DIA. . 2 -7/8" DIA.
5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" (12,7 mm)
(15,9 ±6,4 mm) 2.1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm)
2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
�� ' (3,2 mm) i •!'i (3,2 mm)
11-l lfli �-*
•
s . f MOUNTING VIP
MOUNTING . SURFACE � .
SURFACE iil• /f.1l��
CLOSURE SERIES 1-5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1- 1/16" (27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8" DIA.
5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm)
(15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8"
•�' (3,2 mm) •� ' (3,2 mm)
•
i ----------,--- 1 iM MrAl X _ r_ r _i_ '
\ � f MOUNTING �:' MOUNTING SURFACE •. . -•
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY-FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi-
the sprinkler wrench flats. it controls, permission to shut down the fied sprinklers must be replaced.
affected fire protection system must be Sprinklers that have been exposed to
Step C. After the ceiling has been in-
stalled or the finish coat has been ap- obtained from the proper authorities corrosive products of combustion, but
plied, slide on the Style 10, 20, 30, or and all personnel who maybe affected have not operated, should be replaced
40 Closure over the Series TY -FRB by th action must be notified if they cannot be completely cleaned
Sprinkler and push the Closure over The owner must assure that the sprin- by wiping the sprinkler with a cloth or
the Mounting Plate until its flange klers are not used for hanging of any by brushing it with a soft bristle brush.
comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam -
the event of fire or inadvertent opera- age to the sprinklers - before, during,
Care and tion may result. and after installation. Sprinklers dam -
Absence of an escutcheon, which is aged by dropping, striking, wrench
Maint enance to cover a clearance hole, may twist/slippage, or the like, must be re-
1a®ntenance placed. Also, replace any sprinkler
delay the time to sprinkler operation in that has a cracked bulb or that has lost
The Series TY -FRB Sprinklers must a fire situation. liquid from its bulb. (Ref. Installation
be maintained and serviced in accord- Sprinklers that are found to be leaking Section).
ance with the following instructions: or exhibiting visible signs of corrosion
must be replaced. Frequent visual inspections are rec
NOTES ommended to be initially performed for
Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers,
main control valve for maintenance painted, plated, coated or otherwise after the installation has been com-
TFP171 Page 9 of 10
2 -7/8" DIA. . DIA -
5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
(15,9 ±6,4 mm) 2 -1/4" DIA. y 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. y 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
IT (3,2 mm) �� (3,2 mm) rr ,
ii ria f � � \ 1
IP MOUNTING _ MOU SURFACE SURFACE - ' ' 1 -
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. _ 2-7/8" DIA. -
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm)
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) F 2 -1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) MOUNTING FACE OF (57,2 mm)
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
r�Il (3,2 mm) i Eli ��. 3,2
1 \ AI
��
U
,�, 1 MOUNTING �I�
MOUNTING SURFACE
SURFACE . '
CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor- WRENCH
rosion resistant coating. Thereafter, RECESS
annual inspections per NFPA 25 /
should suffice; however, instead of in- WRENCH RECESS
specting from the floor level, a random (END "A" USED FOR
sampling of close -up visual inspec- 1/2 " NPT MODELS)
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the wo ,
corrosion resistant coatin as it ma WRENCH RECESS
g ' y (END "8" USED FOR PUSH WRENCH
be affected by the corrosive conditions 3 /4" NPT MODELS) IN TO ENSURE
present. ENGAGEMENT
The owner is responsible for the in- FIGURE 14 WITH SPRINKLER
p WRENCHING AREA
spection, testing, and maintenance of W -TYPE 6 SPRINKLER
their fire protection system and de- WRENCH FIGURE 15
vices in compliance with this docu- W -TYPE 7 RECESSED
ment, as well as with the applicable facturer should be contacted relative SPRINKLER WRENCH
standards of the National Fire Protec- to any questions.
tion Association (e.g., NFPA 25), in Inspection Service in accordance with
addition to the standards of any other It is recommended that automatic local requirements and /or national
authorities having jurisdiction. The in- sprinkler systems be inspected, codes.
stalling contractor or sprinkler manu- tested, and maintained by a qualified
Page 10 of 10 TFP171
P/N 57- XXX -X -XXX
TEMPERATURE
MODEL/SIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175F/79°C
341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only.
360 8.0K UPRIGHT (1/2 "NPT) TY4831'
361 8.0K PENDENT (1/2 "NPT) TY4931*
TABLE D
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
LimitLimit no event shall TFBP be liable, in
ed contract, tort, strict liability or under Ordering
any other legal theory, for incidental,
Warranty indirect, special or consequential dam- Procedure
ages, including but not limited to labor
Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the
Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price
ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num-
ten (10) years against defects in mate- TFBP's liability exceed an amount bers.
rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail -
and properly installed and maintained
under normal use and service. This The foregoing warranty is made in lieu ability.
warranty will expire ten (10) years of any and all other warranties. ex-
from date of shipment by TFBP. No press or implied. including warranties Sprinkler Assemblies with NPT
warranty is given for products or com- of merchantability and fitness for a par- Thread Connections:
ponents manufactured by companies ticular purpose. Specify: (Specify Model /SIN), Quick
Response, (specify K- factor), (specify
not affiliated by ownership with TFBP This limited warranty sets forth the ex- temperature rating), Series TY -FRB
or for products and components which clusive remedy for claims based on (specify Pendent or Upright) Sprinkler
have been subject to misuse, improper failure of or defect in products, materi- with (specify type of finish or coating),
installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D).
not been installed, maintained, modi- is made in contract, tort, strict liability
fied or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon:
plicable Standards of the National Fire eci , , Re
Protection Association, and /or the erm by y ' This warranty will apply to the full ex- S P fY Style Y ( 10 20, 30 or 40 )
tent permitted b law. The invalidity, in cessed Escutcheon with (specify *) fin -
standards of any other Authorities p
whole or p art, of an y portion of this
Having Jurisdiction. Materials found s ish, P/N (specify*).
by TFBP to be defective shall be either warranty will not affect the remainder.
repaired or replaced, at TFBP's sole * Refer to Technical Data Sheet TFP770.
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56- 000 -6 -387.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56- 850 -4 -001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446