Permit II f P5
Building Division g
TIGARD
Check List � Over - The - Counter (OTC) Building Permit °rte
6A
Description of Project: 17
_ GENERAL INFORMATION
Class of Work:* L Floor Areas (sq. ft.): Exterior Wall Construction:
Type of Use:* First floor: N: S:
Type of Construction: Second floor: E: W:
Occupancy Group: Third floor: Openings Protected Y /N ?:
Occupancy Load: '-- Total sq ft.: N: S:
Stories: Note: Combine total floor area E: E:
for
Height: _ all floors above third floor and Roof Construction:
Floor Load: add to the third floor sq. ft. Fire Retardant:
Basement: Basement: Area Separation Rated:
Mezzanine: Garage: Occu. Separation Rated:
REQUIRED ITEMS
Fire sprinkler: YCs Handicap access:
kl )
Smoke detector: Protected corridors:
Fire alarm: 6 Parking spaces ( #):
Notes:
Total Valuation: $ 7 5 + CO
INSPECTIONS FEES DUE
Footing /foundation Firewall $ '(7, 70 Permit Fee
Post /beam structural Smoke detector $ ( IC , ( State Surcharge
Shear wall Misc. inspection $ G . ) Plan Review Fee
Masonry Approach /sidewalk $ 1 - 7 ; C FLS Plan Review Fee
Framing $ Additional Permit Fee
Insulation Sprinkler rough -in $ Additional Plan Review Fee
Gyp board Fire alarm $ Metro Construction Excise Tax
Suspended ceiling Sprinkler final $ School Construction Excise Tax
Final inspection $ Misc. Fee
$ Hourly Rate Fee
$ Hourly Rate State Surcharge
$ Other:
$ (9q ( , 4 Total Fees Due
''OPTIONS:
TYPE OF USE: COM = commercial; CMS = commercial manufactured structure.
CLASS OF WORK: ACS = accessory; ADD = addition; ALT = alteration; FND = foundation; DEM = demo;
FND = foundation; FPS = fire protection system; NEW = new; OTR = other (use for fences, decks, retaining walls,
signs, awnings or canopies); REP = repair.
I: \Building\Forms \OTC - BUP.doc 08/19/08
qd CITY OF TIGARD FIRE PROTECTION SYSTEM PERMIT
NI
COMMUNITY DEVELOPMENT Permit #: FPS2009-00105
k Date Issued: 10/30/2009
TIGARD 13125 SW Hall Blvd., Tigard OR 97223 503.639.4171
Parcel: 2S112DD01400
Jurisdiction: Tigard
Site address: 15686 SW SEQUOIA PKWY
Subdivision: Lot: 0
Project: Courtyard By Marriott
Project Description: Install (5) new fire sprinkler heads.
Owner: FEES
PACIFIC REALTY ASSOCIATES Description Date Amount
PO BOX 58990
SEATTLE, WA 98138 Permit Fee - COM 10/30/2009 $64.54
12% State Surcharge - Building 10/30/2009 $7.74
PHONE:
Contractor:
SIMPLEXGRINNELL LP
6305 SW ROSEWOOD ST.
LAKE OSWEGO, OR 97035
PHONE: 503 - 683 -9000
FAX. 503 - 675 -6521
Type of Use: COM
Class of Work: ALT Type of Const:
Occupancy Grp: Height: ft
Stories:
Commercial Sprinkler System:
Sprinkler Required: Sprinkler Type:
Standpipe Required: Hazard:
Density. Design Area:
K Factor:
Commercial Fire Alarm System:
Fire Alarm Required: Alarm Type:
Pull Station Required: Smoke Detectors Req:
Battery Calcs Provided: Cut Sheets Required:
Total $72.28
Valuations: Required Items and Reports (Conditions)
Sprinkler Valuation: 950
Residential Square Footage:
Fire Alarm Valuation:
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other
applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of
issuance suspended for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon
Utility otification Cen = . Those rules are set forth in OAR 952 - 001 -0010 through OAR 952 - 001 -0100 .1 may obtain a copy of the rules
or di ct questions to OU • • . -fling 503.246.6699 or 1.800.332.2344. _
i
Is ued By: / f Permitte • Signature: �Ijp/
_ ,1. .0 .J . e tritom
CaII 503.639.4175 by 7:00 a.m. for an inspection that b : mess day.
This permit card shall be kept in a conspicuous place on the job s' - until completion of the project.
Approved plans are required on the job site at the time of each inspection.
Building Permit Application
Fire Protection System FOR OFFICE USE ONLY
¢� '� Received
III q City of Tigard q � Date /B : ed . , O Q 9 A Permit No.: ,� rte.„ 000/46S 13125 SW Hall Blvd., Tigard, OR 972 r� , Plan Review
Phone: 503.639.4171 Fax: 503.598.1160 Date /B : Other Permit:
Inspection Line: 503.639.4175 (, ^'" "� %fl ' Date Ready /By: luris: El See Page 2 for
T I GARD G v O N otified /Method: Supplemental Information
Internet: www.tigard- or.gov PP
TYPE OF T;OARL1
'NG DIVISION REQUIRED DATA: 1- AND 2- FAMILY DWELLING
❑ New construction ❑ Demolition Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
2 /alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION work indicated on this application.
Valuation: $
❑ 1- and 2- family dwelling Commercial /industrial
❑ Accessory building 0 Multi- family Number of bedrooms:
❑ Master builder ❑ Other: Number of bathrooms:
154018 4 JOB SITE INFORMATION AND LOCATION Total number of floors:
Job site address: .� " � t , W . ertu.G�Gi PG2 ,ekL New dwelling area: square feet
5
City /State /ZIP: T 4 , 6AI 97 -Z q Garage /carport area: square feet
Suite/bldg. /apt. no.: d Project name: mitigiiemazirro►I.„ Covered porch area: square feet
Cross street /directions to job site:
I_ f _,� eek area: square feet
i Other structure area: square feet
REQUIRED DATA: COMMERCIAL -USE CHECKLIST
Subdivision: Lot no.: Permit fees* are based on the value of the work performed.
Tax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
equipment, materials, labor, overhead, and the profit for the
•
DESCRIPTION OF WORK work indicated on this anplication.
Valuation: If 9s 0 ``
I / _TtiAttal ..c pre-6J S,icL .k' 0Ars 1 tki...5 fC 1
LIA S,t.lipt f r �A) . <47/FY S `� Existing building area: square feet
U0 Lf New building area: square feet i q 93
❑ PROPERTY OWNER ❑ TENANT Number of stories:
Name: Type of construction:
Address: Occupancy groups: 41,1/4 Ko atArol
City /State /ZIP: Existing:
Phone: ( ) Fax: ( ) New:
rizr APPLICANT ❑ CONTACT PERSON NOTICE
Business name: i All contractors and subcontractors are required to be
A / licensed with the Oregon Construction Contractors Board
Contact name:
Jo LA ' friyi . under ORS 701 and may be required to be licensed in the
Address: h3OS S. iJ • i o S ti.Jod 51. jurisdiction in which work is being performed. If the
City /State /ZIP: L OS t „)e, l 4 p applicant is exempt from licensing, the following reasons
,} - l 9 70 3S apply:
Phone: (,,ro3) 653 . .9000 Fax:: ( )
E -mail: jovokei so43 Si m.9(exefft i,1 , 11 . ?VIA .
CONTRA TOR BUILDING PERMIT FEES*
Lei , (Please refer to fee schedule)
Business name:
5Ultw (? I�Z.X �� r A .(/tej Permit fee:
Address:
State surcharge (12% of permit fee):
City /State /ZIP: o
FLS plan review (40% of permit fee):
Phone: ( ) Fax: ( ) (Due upon application.)
CCB lic.: /tf T 3. 1 Total permit fees:
Authorized signs re: � . (/‘_/,_. Amount received: 7Z Ag
This permit application expires if a permit is not obtained
Print name: Date: q . oq within 180 days after it has been accepted as complete.
�J IA. Q S�� 1 0 , z , * Fee methodology set by Tri- County Building Industry
Service Board.
I: \Building \Permits \FPS - PermitApp.doc 10/01/09 440-4613T(1 I /02/COM/WEB)
City of Tigard: Fire Protection Permit Checklist
Page 2 - Supplemental Information
Describe work to be done:
1.) ❑ New 2.) Modification to sprinkler heads only.
❑ Addition 1 -10 heads: No plan review required.
1 ( Alteration ❑ 11+ heads: Plan review required.
❑ Repair
Number of sprinkler heads: .5
Additional description of work
Type of System (Complete A, B, C or D as applicable):
A.) Commercial Sprinkler
[e" Wet ❑ Dry
Additional Standpipes
Information: Hazard Group Liclk
Density m 6
Design Area ( Q 5
K. Factor 5; 6
Sprinkler Project Valuation: $ q 50. o
B.) Type I - Hood Fire Suppression System
Hood Project Valuation: $
C.) Fire Alarm
Submittal shall Battery Calculations ❑ Yes
include: Individual Component El Yes
Cut Sheets
Fire Alarm Project Valuation: $
D.) Residential Sprinkler (Stand Alone System)
Square Footage: Permit Fee:
0 to 2,000 $198.75
2,001 to 3,600 $246.45
3,601 to 7,200 $310.05
7,201 and greater $404.39
Sprinkler Project Square Footage: sq. ft.
Fire Protection Permit Fees
Project valuation subtotal (see A, B & C above): $
Permit fee based on project valuation (see fee schedule): $
Permit fee based on square footage (see D above): $
State Surcharge (12% of permit fee): $
FLS Plan Review (40% of permit fee): $
TOTAL: $
Plan review requires a completed application and 2 sets of plans at submittal. Plan review fees are required at submittal.
http: / /www.tigard- or.gov /city hall /departments /cd/docs /FPS- PermitApp.doc 10 /O1 /23
tqc.., I Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -F ® 22, 4.2, 506, and 8.0 K®factor
Us right, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
tained when exposed to corrosive at-
eneral mospheres. Although corrosion resis-
tant coated sprinklers have passed the
Description standard corrosion tests of the appli- d '
cable approval agencies, the testing is E
The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible car-
5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it I *` ;w
dent Sprinklers described in this data is recommended that the end user be
sheet are quick response - standard r �� '-
q P consulted with respect to the suitability
coverage, decorative 3 mm glass bulb of these coatings for any given corro-
type spray sprinklers designed for use sive environment. The effects of ambi-
in light or ordinary hazard, commercial ent temperature concentration of
Y , 3 "
occupancies such as banks, hotels,
p chemicals, and gas /chemical velocity,
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the
two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet i x ' '•
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de-
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780
(19,1 mm) of total adjustment from the
flush pendent position, or a two -piece WARNINGS
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de-
inch NPT) Recessed Escutcheon with scribed herein must be installed and -`
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro -
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hay- Model/Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT
with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2 "NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 314 "NPT
with respect to handling and instal- TY4831- Upright 8.0K, 1/2 "NPT
lation of sprinkler systems and com- TY4931- Pendent 8.0K, 1/2 "NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171
Page 2 of 10 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON DEFECTOR
fIlMrr = m _ a - 1 - mil
— — i !� ° 5
��1'' �
2 -1/4" } � (11, 7/16"
1 1 m mm) 1 4
(57,2 mm) ��� � 1 i I iI NMAKE -IN 4 OMINAL I I
1 , 2
1-9/16" �� I� 71 � ` � 2- 3/16 " 7 3
(39,7 mm) WRENCH ! (55,6 mm) � \ r
/ i
FLATS --- P., f 1
.4v-r.or-la III
limif SSP DEFLECTOR — 2 -7/8" (73,0 mm) DIA. 1 1/2" NPT f 7
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NP MAKE-IN ESCUTCHEON
DEFLECTOR
6
.-
�= W s = � Oly
i
rr 7/16" ';
2- 3/16" 1
} �1''�� (11,1 mm)
��I ∎ � A��
1111 I NOMINAL ;
■ (55,6 mm) 4
f 1 MAK -IN
2- 3/16"
1-1/2" 1I i i ' `�� 1 V#-,* 1 2
(38,1 mm) I WRENCH 1 (55,6 mm)p
. F LATS 3
SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
TFP171 Page 3 of 10
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NFT MAKE -IN ESCUTCHEON DEFLECTOR
f = _ 5
1== ii
IN ( 7 116" )
2- 3/16" � � � 11,1 mm
(55,6 mm) 1 A = � ���- NOMINAL ; 4
7�1 MAKE -IN
1 -1 /2" I II'
(38,1 mm) ` �, 2- 3/16" ,�� it
WRENCH I (55,6 mm) 1
1 _ � - �� � � _. FLATS 3
SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING NOMINAL RECESSED
SURFACE NP MAKE-IN ESCUTCHEON
T DEFLECTOR
6
1/2" ' 0 ' S
2- 5/16 ' \ ■--, � �� (12,7 mm)
(58,7 mm) �� - 4
NOMINAL ;
1 - MAKE -IN
1 9/16" IV �If ` ) i 1i.7 b 2
(39,7 mm) WRENCH (57,2 mm 7 1 ii 7 y � 6 W 3
SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. 3/4" NPT f
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. -
Screw
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Page 4 of 10 TFP171
7/16" (11,1 mm)
1!2" NOMINAL SSU *
NPT MAKE -IN DEFLECTOR
t .._--
6
r = ' t 5
��
2 -1/4" 2 -3/1 I
(57,2 mm) I =i' I (55,6 6 mm) I ' 4
1-9/16" i WRENCH ��� Ff 1 2
�■■•
(39,7 mm) FLATS
l - .! - -- - - 1
SSP *
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 5
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K- FACTOR, 1/2 INCH NPT
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C -UL Listed. fluid expands sufficiently to shatter the
FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A and B for complete activate and water to flow.
approval information including corro-
sion resistant status.) Design
Maximum Working Pressure
Refer to Table C. Criteria
Discharge Coefficient
K = 2.8 GPM /psi (40,3 LPM /bar1/2) The Series TY -FRB Pendent and Up-
K = 4.2 GPM /psi (60,5 LPM /bar1 /2) right Sprinklers are intended for fire
K = 5.6 GPM /psi (80,6 LPM /bar1/2) protection systems designed in ac-
K = 8.0 GPM /psi (115,2 LPM /barli2) cordance with the standard installation
rules recognized by the applicable
Temperature Ratings Listing or Approval agency (e.g., UL
Refer to Table A and B Listing is based on the requirements of
Finishes NFPA 13, and FM Approval is based
Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre -
Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style
Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Physical Characteristics 8
Frame Bronze E
Button Brass /Copper m
Sealing Assembly 1-
Beryllium Nickel w/Teflont
a'
Bulb Glass iv
Compression Screw Bronze .6
Deflector Copper /Bronze
cc
Bushing (K =2.8) Bronze
0
0
0
4—
TFP171 Page 5 of 10
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL CHROME WHITE***
LIQUID BRASS PLATED POLYESTER
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY1231) 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
2.8 (n1131) 286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY1231)* 175F/79°C Yellow
Figure 6 200 °F /93 °C Green 1, 2, 5
135 °F /57 °C Orange
RECESSED
155F/68°C Red
PENDENT
(TY1231)** 175 °F /79 °C Yellow
Figure 7 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY2231)
and 175F/79°C Yellow
UPRIGHT 200F/93°C Green
4.2 (TY2131)
286 °F /141 °C Blue 1 2
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)* 175 °F /79 °C Yellow
Figure 8 200F/93°C Green
135 °F /57 °C Orange
RECESSED
155F/68°C Red
PENDENT
(TY2231) ** 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354 -01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin-
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
Page 6 of 10 TFP171
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE *** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135F/57°C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1,2,3,4,5,6,7 1,2,3,5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131)
286F/141°C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175 °F /79 °C Yellow
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY3231) ** 175 °F /79 °C Yellow
Figure 11 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231) 1, 2, 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155F/68°C Orange
•
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 12 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231) ** 175 °F /79 °C Yellow
Figure 13 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
8.0 (TY4931) 1, 2, 5
1/2" and 175 °F /79 °C Yellow 1, 2, 4, 5, 6
NPT UPRIGHT 200 °F /93 °C Green
(TY4831)
28&F/141°C Blue
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
TFP171 Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT
NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" RECESSED PENDENT 175 PSI (12,1 BAR)
NPT (TY3231) N/A
(SEE NOTE 1)
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
®® tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting.
Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the
ft.lbs. (40,7 Nm) of torque is to be used sprinkler fitting using only the W -Type
The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con -
6 Sprinkler Wrench (Ref. Figure 14).
be installed in accordance with the fol- nections. Higher levels of torque may With reference to Figures 1, 2, 3, 4,
lowing instructions: distort the sprinkler inlet and cause and 5, the W -Type 6 Sprinkler Wrench
leakage or impairment of the sprinkler. is to be applied to the sprinkler wrench
NOTES Do not attempt to make -up for insuffi- flats.
Do not install any bulb type sprinkler if cient adjustment in the escutcheon The Series TY -FRB Recessed Pen -
the bulb is cracked or there is a loss of
plate by under- or over - tightening the dent Sprinklers must be installed in
liquid from the bulb. With the sprinkler sprinkler. Readjust the position of the accordance with the following instruc-
held horizontally, a small air bubble
should be present. The diameter of the sprinkler fitting to suit. tions.
air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10.
(1,6 mm) for the 135 °F /57 °C to 3/32 right Sprinklers must be installed in 20, 30, or 40 Mounting Plate, as appli-
inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and
temperature ratings. tions. with pipe thread sealant applied to the
A leak tight 1/2 inch NPT sprinkler joint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin-
should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting.
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the
mum of 21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type
may be used to install sprinklers with S 2. Wi pipe thread sealant ap 7 Recessed Sprinkler Wrench (Ref.
1/2 NPT connections. A leak tight 3/4 Figure 15). With reference to Figure 1,
inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighte 2, 3, and 4, the W -Type 7 Recessed
Page 8 of 10 TFP171
2 -7/8" DIA. 2 -7/8" DIA.
5181114" (73,0 mm) 3/4" (19,1 mm) 1/211/8" (73,0 mm) 1/2" (12,7 mm)
(15,916,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,713,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
�� •�' (3,2 mm) •�. ( 3,2 mm)
-----------
ltll,� r -ili iii"
lim /il M =lii%r 1 _ - 1 ` 111
f MOUNTING
MOUNTING �: SURFACE .
SURFACE w, - .1�. �%r - l"\ \. '
CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1-1/16" (27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8" DIA.
51811/4" (73,0 mm) 3/4" (19,1 mm) 1/211/8" (73,0 mm) 1/2" (12,7 mm)
(15,916,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,113,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
-1 •�' (3,2 mm) •� (3,2 mm)
,il�lli r �, iii" ,
frA _ - i, _-� 1 v U 1��
MOUNTING
MOUNTING �: SURFACE II SURFACE -- - -
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi-
the sprinkler wrench flats. it controls, permission to shut down the fied sprinklers must be replaced.
Step C. After the ceiling has been in- affected fire protection system must be Sprinklers that have been exposed to
stalled or the finish coat has been ap- obta from the proper authorities corrosive products of combustion, but
plied, slide on the Style 10, 20, 30, or and all personnel who maybe affected have not operated, should be replaced
40 Closure over the Series TY -FRB by th action must be notified if they cannot be completely cleaned
Sprinkler and push the Closure over The owner must assure that the sprin- by wi the sprinkler with a cloth or
the Mounting Plate until its flange klers are not used for hanging of any by brush i t w a soft bristle brush.
comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam-
the event of a fire or inadvertent opera- age to the sprinklers - before, during,
Care and tion may result. and after installation. Sprinklers dam -
Absence of an escutcheon, which is aged by dropping, striking, wrench
used to cover a clearance hole, may twist/slippage, or the like, must be re-
Maintenance delay the time to sprinkler operation in placed. Also, replace any sprinkler
The Series TY -FRB Sprinklers must a fire situation. that has a cracked bulb or that has lost
P liquid from its bulb. (Ref. Installation
tallation
be maintained and serviced in accord- Sprinklers that are found to be leaking Section).
ance with the following instructions: or exhibiting visible signs of corrosion
must be replaced. Frequent visual inspections are rec-
NOTES ommended to be initially performed for
Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers,
main control valve for maintenance painted, plated, coated or otherwise after the installation has been com-
TFP171 Page 9 of 10
2 -7/8" DIA. 2 -7/8" DIA.
(73,0 mm) 3/4" (19,1 mm) 1/212,7 mm
(73,0 mm) "
518±1/4" ( ) _ 1/2±1/8" (12,7 mm)
(15,9±6,4 mm) 2.1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" I 1/8"
A
�� ∎i� — f MOUNTING 1 101 MOUNTING , , 1 SURFACE
SURFACE i , _I_.,-
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. _ 2 -7/8" DIA. -
5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) MOUNTING FACE OF (57,2 mm)
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
illi `. .1II (3,2 mm) " (3,2 mm)
Al A 1 2/11 re
I I . %, '
Al , 1
, i ' MOUNTING VIV 1
MOUNTING SURFACE
SURFACE . • r
CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1- 1/16" (27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor- G WRENCH
rosion resistant coating. Thereafter, RECESS
annual inspections per NFPA 25
should suffice; however, instead of in- WRENCH RECESS sielF"..
specting from the floor level, a random (END "A" USED FOR fj
sampling of close -up visual inspec- 1/2" NPT MODELS) tions should be made, so as to better —...d
determine the exact sprinkler condi- S '
tion and the long term integrity of the .........•
corrosion resistant coating, may as it ma WRENCH RECESS be affected by the corrosive conditions (END "B" USED FOR PUSH WRENCH IN TO ENSURE
3/4" NPT MODELS)
present. ENGAGEMENT
The owner is responsible for the In FIGURE 14 WITH SPRINKLER WRENCHING AREA
spection, testing, and maintenance of W -TYPE 6 SPRINKLER
their fire protection system and de- WRENCH FIGURE 15
vices in compliance with this docu- W -TYPE 7 RECESSED
ment, as well as with the applicable SPRINKLER WRENCH
standards of the National Fire Protec facturer should be contacted relative
tion Association (e.g., NFPA 25), in to any questions.
addition to the standards of any other It is recommended that automatic Inspection Service n ts and d /or /or nati an with
local l requirements
authorities having jurisdiction. The in- sprinkler systems be inspected, national
codes.
stalling contractor or sprinkler manu- tested, and maintained by a qualified
•
Page 10 of 10 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEL /SIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only.
360 8.0K UPRIGHT (1/2 "NPT) TY4831*
361 8.0K PENDENT (1/2 "NPT) TY4931*
TABLE D
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
In no event shall TFBP be liable, in Ordering
Limited contract, tort, strict liability or under
any other legal theory, for incidental, ldam- Procedure
Warranty indirect, special or consequential dam-
ages, including but not limited to labor
Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the
Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price
ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num-
ten (10) years against defects in mate- TFBP's liability exceed an amount bers.
rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail -
and properly installed and maintained
under normal use and service. This The foregoing warranty is made in lieu ability.
warranty will expire ten (10) years of any and all other warranties. ex
from date of shipment by TFBP. No press or implied. including warranties Sprinkler Assemblies with NPT
warranty is given for products or com- of merchantability and fitness for a par- Thread Connections:
ponents manufactured by companies ticular purpose. Specify: (Specify Model /SIN), Quick
not affiliated by ownership with TFBP This limited warranty sets forth the ex-
Response, ( specify K-factor), ( specif
or for products and components which Y temperature
(specify en rating), Series pri FRB
P p clusive remedy for claims based on (specify Pendent or Upright) Sprinkler
have been subject to misuse, improper failure of or defect in products, materi- with (specify type of finish or coating),
installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D).
not been installed, maintained, modi- is made in contract, tort, strict liability
fied or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon:
plicable Standards of the National Fire 20
Protection Association, and /or the This warranty will apply to the full ex- Specify: Style Y ( 10, 40) Re
standards of any other Authorities tent permitted by law. The invalidity, in cessed Escutcheon with 30, or 40 th (specify) fin -
Having Jurisdiction. Materials found whole or part, of any portion of this ish, P/N (specify *).
by TFBP to be defective shall be either warranty will not affect the remainder. • Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56- 000 -6 -387.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56- 850 -4 -001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446