MMD2010-00006 NOTICE OF TYPE I DECISION MINOR MODIFICATION (MMD) 2010-00006 TVF&R ADDITION OF GENERATORS AND RTAC 120 DAYS = 08-10-2010 SECTION I. APPLICATION SUMMARY FILE NAME: TVF&R Addition of Generators and RTAC CASE NO.: Minor Modification (MMD) MMD2010-00006 PROPOSAL: The proposal is to install two emergency generators in a 1,418 sq ft. metal building placed to the west of the main building. The new building will displace 7 standard parking spaces and 544 sift of landscaping. Four trees will be removed and replaced. A security gate will remove approximately 55 sq ft of landscaping. New landscape areas will be installed to provide a net gain of 122 sq. ft. The loading area will be relocated closer to the employee entrance. One double light parking light will be re-located and two security lights will be placed on the west side of the new building. The flagpole area will be re-located to the north side of the property. A new roof top air conditioner will be installed with screening. APPLICANT Tualatin Valley Fire & Rescue AND OWNER: Attn: Gary Wells 20665 SW Blanton Street Aloha, OR 97007 LOCATION: 11945 SW 70`' Ave., WCTM 2S136DC, Tax Lot 04400. ZONING DESIGNATION: C-G: General Commercial District (PD1. The C-G zoning district is designed to accommodate a full range of retail, office and civic uses with a City-wide and even regional trade area. Except where non-conforming, residential uses are limited to single-family residences which are located on the same site as a permitted use. A wide range of uses, including but not limited to adult entertainment, automotive equipment repair and storage, mini-warehouses, utilities, heliports, medical centers, major event entertainment, and gasoline stations, are permitted conditionally. APPLICABLE REVIEW CRITERIA: Community Development Code Chapters 18.360, 18.390, 18.520 and 18.745, 18.765, and 18.790. SECTION II. DECISION Notice is hereby given that the City of Tigard Community Development Director's designee has APPROVED the above request subject to certain conditions of approval. The findings and conclusions on which the decision is based are noted in Section IV. MMD2010-00006 TVF&R Generators and RTAC Decision 041210 Page 1 CONDITIONS OF APPROVAL PRIOR TO THE REQUEST FOR FINAL BUILDING INSPECTION, THE FOLLOWING CONDITIONS SHALL BE SATISFIED 1. Applicant shall request final inspection of this land use permit by the Planning Division prior to requesting final inspection by the Building Division for certificate of occupancy. THIS APPROVAL SHALL BE VALID FOR 18 MONTHS FROM THE EFFECTIVE DATE OF THIS DECISION. SECTION III. BACKGROUND INFORMATION Site Information: The subject parcel is located at 11945 SW 70`" Ave., WCTN1 2S136DC, Tax Lot 04400. The primary building and site were approved under SDR2006-10001 as an office building. The primary building will be occupied by TVF&R for offices and emergency operations center. Proposal Description: The proposal is to install two emergency generators in a 1,418 sq. ft. metal building placed to the west of the main building. The new building will displace 7 standard parking spaces and 544 sq ft of landscaping. Four trees will be removed and replaced. A security gate will remove approximately 55 sq ft of landscaping. New landscape areas will be installed to provide a net gain of 122 sq. ft. The loading area will be relocated closer to the employee entrance. One double light parking light will be re-located and two security lights will be placed on the west side of the new building. The flagpole area will be re- located to the north side of the property. A new roof top air conditioner will be installed with screening. SECTION IV. APPLICABLE REVIEW CRITERIA AND FINDINGS COMPLIANCE WITH COMMUNITY DEVELOPMENT CODE SECTIONS: MINOR MODIFICATION OF SITE DEVELOPMENT REVIEW: Section 18.360.050.B contains the following criteria for approval of a request for Minor Modification: Section 18.360.050.B states that the Director shall determine that a major modification will result if one or more of the following changes are proposed. There will be: 1. An increase in dwelling unit density, or lot coverage for residential development; There are no dwelling units on the property. Therefore, this criterion does not apply. 2. A change in the ratio or number of different types of dwellings; There are no dwelling units on the property. Therefore, this criterion does not apply. 3. A change that requires additional on-site parking in accordance with Chapter 18.765. The proposal does not require additional on-site parking. There are 128 parking spaces on the site and 11 will be removed, leaving 117 spaces, 15 more than the 102 required. Therefore, this criterion is satisfied. MMD2010-00006 TVF&R Generators and RTAC Decision 041210 Page 2 4. A change in the type of commercial or industrial structures as defined by the Uniform Building Code; There are no proposed changes in the type of structures. Therefore, this criterion does not apply. 5. An increase in the height of the building(s) by more than 20%; There is no proposed change in building height. Therefore, this criterion does not apply. 6. A change in the type and location of access ways and parking areas where off-site traffic would be affected; The proposal does not change the type or location of access ways or parking areas where off- site traffic would be affected. Therefore, this criterion does not apply. 7. An increase in vehicular traffic to and from the site and the increase can be expected to exceed 100 vehicles per day; The proposal does not increase traffic to and from the site. Therefore, this criterion is satisfied. 8. An increase in the floor area proposed for a nonresidential use by more than 10% excluding expansions under 5,000 square feet; The proposal does not involve an increase in floor area more than 10% and is less than 5,000 sq. ft. Therefore, this criterion is satisfied. 9. A reduction in the area reserved for common space and/or usable open space which reduces the open space area below the minimum required by this code or reduces the open space area by more than 10%; The proposal does not reduce the area reserved for common space or usable open space. Therefore, this criterion does not apply. 10. A reduction of project amenities below the minimum established by this code or by more than 10% where specified in the site plan: a. Recreational facilities; b. Screening; and/or c. Landscaping provisions. The proposal will result in a net gain of 122 sq. ft. of landscaping. This criterion is satisfied. 11. A modification to the conditions imposed at the time of site development review approval which are not the subject of B 1 through 10 above of this subsection. The proposal involves re-locating 4 mitigation trees required in SDR2006-10001 as shown on the approved site plan. Eleven parking spaces will be replaced by the generator enclosure, landscaping and loading space. Net parking requirements exceed the 102 minimum by 15. This criterion is satisfied. FINDING: Based on the analysis above, Staff finds that the criteria for minor modification of a site development have been met. MMD2010-00006 TVF&R Generators and RTAC Decision 041210 Page 3 SECTION V. PROCEDURE AND APPEAL INFORMATION Notice: Notice was posted at City Hall and mailed to: X The applicant and owners Z Affected government agencies Final Decision: A Minor Modification is a Type I procedure. As such, the Director's decision is final on the date it is mailed or otherwise provided to the applicant, whichever occurs first. The Director's decision may not be appealed locally and is the final decision of the Cite. THIS DECISION IS FINAL ON APRIL 12, 2010 AND BECOMES EFFECTIVE ON APRIL 13, 2010. Questions: If you have any questions, please call the City of Tigard Planning Division, Tigard Cit-- Hall, 13125 SW Hall Boulevard, Tigard, Oregon at (503) 639-4171. J1, )6z/ April 12, 2010 APPROVED BY: Darr "Hap" Watkins DATE Assistant Planner MMD2010-00006 TVF&R Generators and RTAC Decision 041210 Page 4 dr ii~ iiuiiiiliL Approved ✓ )nditionally Approved F 3r only the work as described in: J LEGEND PPLPHt1Y UM` ° ! E F'.,'iMIT NO. 101W) See Letter to: Follow D. IAI~E. ro EE ~ o Attach i I L L L L L L L L L L L L L L L L L L X b b Ad r s, ~r tG~ off ~~Am~ I L ~o-~ OF Dal: 12_ v nw N I c L L za _ I_ NK I - I 1 ~ IAA I i I QI ~ II _ c c L L c c II c c L c L L L L L c L I s ,s I,_J DD r rS 1.11 c L LE K IN II IT T ,a I I e I z. I ~~-o- . h I e QYao I I ~_O~ . I L L ~ \ a• I (~~)SECTION N-5 I r-^, IIsTLP s ` _ ~N: o " X t J nsf ~ oo \ c L c° c ra \ - ® 1-22 S 1 T M1- t F - I artan /aT ® U I ~ rNa ~ (A - D c o E EXISTING BUILDING ~ o -41 ~n = u d N APt B YLO L" r- - O > (fi1SECTION E-W SOUTH ELEVATION (~j1SITE PLAN _ aNi L c o rn SULE '=3Gd 7 O m U) D KEY NGTES THIS SHEET c W i ~ N~• u....IK,ATIL•a TEL ~ ~ -4-=- III II` IL j - PNn GENERATOR ENCLOSURE DOOR AND FRAME SCHEDULE O'°-I- NT AAO a o L___ __J - - _ FRAME U t - •'r l ■ r b~ DETAIL RLWARE FIRE OEASTIM6 PLbFr(F MYMWKAI IM RATING NOTES OOasrn!S PEet onKti F~ tr e i yl p 1 • ILa - - - _ - - - - - - M4RK DOOR SIZE MAIL DDDrF!risl, EkveDanTYV.~ HEAD JAMB SILL GROUP LABEL RHL6~1RICK 5L T ~-N ~L O N31 C.•dE •PMLE r / \ _ _ _ _ _ _ _Rt MLY MIEN/SffTA15 OKLL=6 WI✓D IEAL9t I G E~+T.tr. , o.,R„~.,L TD - ELEVATION PERMIT II (2)EAST sXn 5AL RH MKr W cLtr. Pb. DOCUMENLS A11 - I r- ---1= Ar 1° - _ Q - - ~ QDeevATOK ronPaL VLrr~mARp - - - O LI.m VMl SO« •5.M6 CCMG. SRE PLAN I - , - - p 0--@ s DETAILS ~ b b II I :s :c r~ea aat L_-___ _ll___J PnKYer.E c I I ~ i I Auefry, nlcl¢r eerx Q Oosr. uexr Pat may, Deal Deal ores. ~l - O ~.zq /-tea *e uwir wo not ~i wuccelr[~ oenLlsx ffJ I-enllw srsel.w K•n s= _ ll. - _ PHP'a2dIP~NO RO.IO'rt Dw F.6 0°A a i ~ 'ill ~ i v _ - I_. .I - ~ UI~ EA~o~J~wA`~°"w•i~,T°~ r ~n __J. p E,os6 wx lace roRa+NK 0 PLAN-GENERATOR ENCL. WEST ELEVATION HYDRAULIC VERT. PIVOT GATEY' OPa e roLNe -1 V N 1 2 201 ~►11 REVISION City of Tigard, Oregon 13125 SW Hall Blvd. Tigard, OR 97223 March 26, 2010 . ~ 1 Peck Smiley Ettlin Architects Attn: Hans Etthn 4412 SW Corbett Portland, Or 97201 RE: TVF&R Emergency Generators Minor Modification Dear Mr. Ettlin, The City has received your application for Minor Modification (MMD2010-00006) of a Site Development Review (SDR2006-10001). Staff has determined your application to be substantively incomplete. Please respond to the following so your application can be deemed complete and the review process can continue. 1) The installation of an electronically controlled gate creates two individual parking lots, one for the public and one for employees. There should be three ADA parking spaces near the new employee entrance for the 65 spaces in that lot. There should also be three ADA parking spaces in the public lot for the 54 spaces there. The parking ratio in the public lot is 3:1 compact, where only 50% can be compact. Provide a revised parking plan that shows parking compliance. 2) As I read your plan, the landscape removal total is 656 sq. ft. and the replacement is 334 sq. ft., leaving a net loss of 322 sq. ft. The total landscaping of 11,595 sq. ft. with 322 sq. ft. net loss brings the project below the minimum required 11,433 sq. ft. (11,273 sq. ft. net). Provide revised plans that meet the minimum landscaping standard. 3) The project will displace 4 trees. Provide a current landscape plan that shows the re-location of these trees. 4) Provide plans that show the re-location of the parking lot lighting and how it will provide adequate coverage. If you have questions, please call me at 503-718-2440 or e-mail me at ha 2 a,tiP~ard-ongov. /S' cerJ~ely G; Darrel " ap~" Watkins Assistant Planner CC: TVF&R, Gary Wells Land Use File MMD2010-00006 MMD2010-00006 TVF&R Generators, Gate & A/C 032610 Page 1 Phone: 503.639.4171 Fax: 503.684.7297 www.tigard-or.gov TTY Relay: 503.684.2772 City of Tigard Minor Modification - Type I Application GENERAL INFORMATION In addition, the Director must find that the proposed Property Address/Location(s): change is in compliance with all applicable requirements of 7704" , Ole- Title 18 of the Tigard Development Code. To complete 1 this review, the Applicant's proposal must include a Tax Map & Tax Lot #(s): / S 3 6 DG O 4f DO discussion indicating how the site expansion/change will 22 2LS16r continue to comply with the maximum setback, building Site Size: 1 • height, parking, and landscaping standards. Other r requirements of this title such as clear vision, solid waste Applicant*: storage, non-conforming situations, signs, and tree Address: ZO& SW L AN removal may also be applicable depending on the type and City/State: A_W tfg " Or- Zip: 7 007 location of the proposed modifications. Primary Contact: &A" W aW Phone: 503 G+2.0331 Fax: 543 E-Mail: 64r-i . W&O 0 TVP9 .GIW Property Owner/Deed Holder(s)*: REQUIRED SUBMITTAL ELEMENTS (Attach list if more than one) i -V"fo, (Applications will not be accepted without the Address: -206615- SW 614WTV N Phone: 03'(044 following required submittal elements) City/State: AUCi 4R- Zip: 913 f Application Form [,~],im/ Owner's Signature /Written Authorization * When the owner and the applicant are different people, the I~ Title Transfer Instrument or Deed applicant must be the purchaser of record or a lessee in Site Plan (4 Large Plans & One - Reduced to 8'/:" x 11 possession with written authorization from the owner or an agent of the owner. The owner(s) must sign this application Applicant's Statement/Narrative (4 copies) in the space provided on the back of this form or submit a LN' Filing Fee $579.00 written authorization with this application. Minor Modifications: Minor Modifications are processed for permitted uses and conditional uses. To review a modification as a Minor Modification, the Director must first find that the expansion or change does not invoke one or more of the criteria discussed within Section 18.360.050(B) - Site Development FOR STAFF USE ONLY Review or Section 18.330.020(B)(2) - Conditional Use. If the modification exceeds the maximum allowed under any one or Case No.(s): rl M 2 J I t7 - uC~,~i, more of the criteria, a Major Modification review is required. Major Modifications are processed in the same manner as a Other Case No.(s}: Zlv new Site Development Review or Conditional Use Permit. Receipt No.: - ~ Applicant's Statement: Date: 7 The applicant's statement must include a summary of the proposed changes. Criteria in either 18.360.050(B) or Application Accepted By: 18.330.020(B)(2) must be addressed with a detailed response Date Determined Complete: l to each criterion. Failure to provide the information needed Revised: 16-Oct-09 to process the application would be reason to consider an is\cur 1n\masters\1and use a lications\minor modification a .dots application incomplete and delay review of the proposal. City of Tigard 13125 SW Hall Blvd., Tigard, OR 97223 503-639-4171 www.tigard-or.gov Page 1 of 2 To consider an application complete, you will need to submit ALL of the REQUIRED SUBMITTAL ELEMENTS as described on the front of this application in the "Required Submittal Elements" box. (Detailed Submittal Requirement Information sheets can be obtained, upon request, for all types of Land Use Applications.) THE APPLICANT(S) SHALL CERTIFY THAT: ♦ The above request does not violate any deed restrictions that may be attached to or imposed upon the subject property. ♦ If the application is granted, the applicant will exercise the rights granted in accordance with the terms and subject to all the conditions and limitations of the approval. ♦ All of the above statements and the statements in the site plan, attachments, and exhibits transmitted herewith, are true; and the applicants so acknowledge that any permit issued, based on this application, and may be revoked if it is found that any such statements are false. ♦ The applicant has read the entire contents of the application, including the policies and criteria, and understands the requirements for approving or denying the application. SIGNATURES of each owner of the subject property. DATED this day of , 20 i Owner' ignature Owner's Signature G~ r ~ ~e~ls Owner's Signature Owner's Signature Owner's Signature Owner's Signature City of Tigard 13125 SW Hall Blvd., Tigard, OR 97223 503-639-4171 www.tigard-or.gov Page 2 of 2 CITY OF TIGARD RECEIPT 13125 SW Hall Blvd., Tigard OR 97223 503.639.4171 Receipt Number: 177282 - 03/2212010 CASE NO. FEE DESCRIPTION REVENUE ACCOUNT NUMBER PAID MMD2010-00006 Minor Modification to an Approved Plan 1003100-43116 $504.00 MMD2010-00006 Minor Modification to an Approved Plan - 1003100-43117 $75.00 LRP Total: $579.00 PAYMENT METHOD CHECK # CC AUTH. CODE ACCT ID CASHIER ID RECEIPT DATE RECEIPT AMT Credit Card 03568C KPEERMAN 03/22/2010 $579.00 Payor: Hans O. Ettlin Total Payments: $579.00 Balance Due: $0.00 Page 1 of 1 EI PECK SMILEY ETTLINAV architects f JTY M i n o r M o d if i c a t i o n f o.r~, 11 935 SW 70th 'S W r i t t e n N a r r a t i v e RE: Land Use File MMD2010-0006 TVF&R CBOC REVISION Revised 4 April, 2010 Tualatin Valley Fire and Rescue purchased this site and building to be their Command and Business Operations Center (CBOC). The use is public facility/commercial office. The facility is currently being seismically upgraded to Type IV Essential Facilities structural standards. Part of the upgrade is the future installation of two ground mounted diesel generators and a rooftop unit to make the facility independently operable in a seismic or other catastrophic event. The two generators and its related above ground fuel tank will be located in a screened enclosure west of the existing structure in the middle of the west parking lot. Seven parking spaces will be lost but the facility has adequate minimum parking without these spaces. There are 128 total existing spaces, with 117 remaining after the enclosure is built. The minimum number of spaces required is 102. The enclosure will have pre-finished metal siding of a dark bronze color and have a 26'-0" x 65'-0" footprint (1,690 SF). The total lot coverage percentage will not change as the location is already paved. The Cummins generators will have sound rated enclosures to dampen the motor noise. The enclosure shall reduce the sound level of the generator set while operating at full rated load to a maximum of 66 dBA at any location 7 meters from the generator set in a free field environment. The enclosure will also increase the noise dampening effect. The enclosure will displace 544 square feet of landscaping. TVF&R is adding 680 square feet of new landscaping, resulting in a surplus area of 136 square feet more than the existing SF which exceeds the required minimum. The existing trees will be relocated to the new landscape areas (see attached revised plan). Part of the site security will include a vertical pivoting gate on the north side of the building isolating the westerly parking lot from public access. The gate is made of painted black aluminum and matches the existing ornamental fencing on the site. The gate is 25'-0" wide and 8'-0" high. The security gate will be in an open position during normal business hours Monday through Friday. The gate will only be lowered at night for security of stored TVF&R staff vehicles. No staff is required to park there for their normal business operations and only staff vehicles being stored on site overnight will located in the secure area. The public is allowed to park there during normal business hours. The existing parking lot illumination will be maintained on the west side of the west parking lot with the addition of two additional lighting fixtures on the west face of the generator enclosure. The fixtures will be indirect wall mounted wall packs with 100 watt metal halide lamps with no light spillage or glare to the adjacent properties. (Fixture cut attached) The roof will receive a second 30 ton air handler which will be fully screened with a unit mounted screen system. The screen system will match the existing screen system on the existing air handling unit and be by Cityscapes. The unit is 7'-10" wide x 4'-10" high x 24'-0" long. There is one 5 foot long section that is 7'-10" high. This second unit is required for operational redundancy and backup for emergency operations. One internal parking lot light will be removed and replaced to provide even internal light coverage with no light spillage to adjacent properties. Hans Ettlin, PSE Architects For TVF&R 4412 SW Corbett, Portland, OR 97201 tel 503.248.9170 fax 503.248.0223 www.psearchs.com I AFTER RECORDING RETURN TO: Jordan Schrader Ramis PC Wa certit,r TRUE and IXACT copy bf the Two Centerpointe Dr Ste 600 recorded V~~ 3~ 200 Lake Oswego OR 97035 as (46796-38157 - KMB) Dwk Pago PACards CCd County O~ QQ~WPAIR This space is reserved for recorder's use. STATUTORY WARRANTY DEED Dartmouth Square, LLC, an Oregon limited liability company ("Grantor"), conveys and warrants to Tualatin Valley Fire & Rescue, A Rural Fire Protection District ("Grantee"), the real property described on Exhibit A attached hereto and incorporated herein ("Property"), free of encumbrances except as specifically set forth on Exhibit B attached hereto and incorporated herein. The true consideration for the conveyance is $8,200,000.00. A. At the time of delivery of the Deed, Grantor is seized of the estate in the Property that Grantor purports to convey and Grantor has good right to convey the same. B. Grantor warrants and will defend the title to the Property against all persons who may lawfully claim the same. C. BEFORE SIGNING OR ACCEPTING THIS INSTRUMENT, THE PERSON TRANSFERRING FEE TITLE SHOULD INQUIRE ABOUT THE PERSON'S RIGHTS, IF ANY, UNDER ORS 195.300, 195.301 AND 195.305 TO 195.336 AND SECTIONS 5 TO 11, CHAPTER 424, OREGON LAWS 2007. THIS INSTRUMENT DOES NOT ALLOW USE OF THE PROPERTY DESCRIBED IN THIS INSTRUMENT IN VIOLATION OF APPLICABLE LAND USE LAWS AND REGULATIONS. BEFORE SIGNING OR ACCEPTING THIS INSTRUMENT, THE PERSON ACQUIRING FEE TITLE TO THE PROPERTY SHOULD CHECK WITH THE APPROPRIATE CITY OR COUNTY PLANNING DEPARTMENT TO VERIFY THAT THE UNIT OF LAND BEING TRANSFERRED IS A LAWFULLY ESTABLISHED LOT OR PARCEL, AS DEFINED IN ORS 92.010 OR 215.010, TO VERIFY THE APPROVED USES OF THE LOT OR PARCEL, TO DETERMINE ANY LIMITS ON LAWSUITS AGAINST FARMING OR FOREST PRACTICES, AS Page I - STATUTORY WARRANTY DEED 46796-38157168658.docWBG/612512009 DEFINED IN ORS 30.930, AND TO INQUIRE ABOUT THE RIGHTS OF NEIGHBORING PROPERTY OWNERS, IF ANY, UNDER ORS 195.300, 195.301 AND 195.305 TO 195.336 AND SECTIONS 5 TO It, CHAPTER 424, OREGON LAWS 2007, Dated this M- day of June, 2009. GRANTOR ACCEPTED BY: DARTMOUTH S A E, LLC, an Oregon TUALATIN VALLEY FIRE & RESCUE, A limited liab' f ny Rural Fire Protection District e. By: By6~ Its: 2z a Its: ' T STATE OF OREGON ) ss. . County of ) Persort4Ily ppear d before me this day of June, 2009, the above-named , who, being duly sworn, did say that he is a 0A0 k1 ~ of Dartmouth Squ LLC, an Oregon limited liability company", an tthat said instrument was signed on ehalf of said company, and acknowledged said instrument to be his voluntary act and d. OFFICIAL SEAL KARLEEN M HUGGINS \ 111 P C F ORE O tmy NOTARY PUBUC•OREGON TAR COMMISSION N0.397575 MY Com ission ExPires: 16124 tl"t COMMISSION EXPIRES OCTOBER 20, 2009 STATE OF OREGON ) 6al-ah ) ss. County of ) P sonal ly appeared before me this day of June, 2009, the above-named nwho, being duly sworn, did say that he is a hytSianj C of Tualatin Valley Fire & Rescue, A Rural Fire Protection District, and that said instrument was signed on _ehalf of said district, and acknowledged said instrument to be his voluntary act a deed. OFFIGIAL SEAL KARLEEN M HUGGINS Pf NOTARY PUBLIC•OREGON COMMISSION No 397575 G COMMISSION EXPIRES OCTOBER 20, 2009 TAR BL C FOR ORE My Commission Expires: Page 2 - STATUTORY WARRANTY DEED 46796-38157I68658.dbe HBG1625-'2009 i Exhibit A Legal Description Parcel I: The following described property situated in the City of Tigard, County of Washington and State of Oregon, to wit: Lots 30, 31 and 32, FRUITLAND ACRES, except those portions of said Lots 30 and 31, conveyed by A. H. Tower and Bertha Tower to Earl Oney and Marianne Oney on April 10, 1947, and recorded in Book 274,,Page 353, Deed Records, of Washington County, Oregon, on May 21, 1947 and more particularly described as follows: Beginning at the intersection of the North line of Lot 30, FRUITLAND ACRES, with the East line of the County Road along the West side of said FRUITLAND ACRES, according to the duly recorded map and plat thereof, thence South on and along the East line of said county road 100 feet to a point on the West line of Lot 31, FRUITLAND ACRES; thence East parallel with the North line of said Lot 30 a distance of 200 feet; thence North parallel with the East line of said county road to the North line of said Lot 30 to a point 200 feet East of the point of beginning; thence West a distance of 200 feet East to the point of beginning. And also excepting a portion of Lots 30 and 31, FRUITLAND ACRES, in the County of Washington and State of Oregon, more particularly described as follows: Beginning at the Northeast corner of said Lot 30; thence West along the North line of said lot a distance of 225 feet to a point; thence South parallel with the East line of said Lots 30 and 31 a distance of 100 feet to a point; thence East parallel with the said North line 225 feet to a point on the East line of said Lot 31; thence North along the East line of Lots 30 and 31 a distance of 100 feet to the point of beginning. And also excepting from said Lots 31 and 32 the following described property: Beginning at a point on the South line of Section 36, Township 1 South, Range 1 West, of the Willamette Meridian at the Southwest corner of Lot 32, FRUITLAND ACRES, a subdivision of record in Washington County, Oregon and running thence, North 89°38' East 200.00 feet along the South line of said Lot 32 to an iron rod; thence North 115.13 feet, parallel with the West line of Lots 32 and 31, said FRUITLAND ACRES, to an iron pipe at the Southeast corner of that certain tract of land conveyed by Deed to Earl Oney, et ux, and recorded in Book 274, Page 353, Washington County Deed Records; thence South 89°38' West 200.00 feet along the South line of said Oney Tract to an iron rod at the Southwest corner thereof, a point on the West line of Lot 31, said FRUITLAND ACRES; thence South along the West line of said Lot 31 and Lot 32, 115.13 feet to the place of beginning. Parcel II: Page 1 - EXHIBIT A 46796-38157 168658.docWBG 6'as-znnv Beginning at the Northeast corner of said Lot 30; thence West along the North line of said lot a distance of 225 feet to a point; thence South parallel with the East line of said Lots 30 and 31 a:y distance of 100 feet to a point; thence East parallel with the said North line 225 feet to a point on the East line of said Lot 31; thence North along the East line of Lots 30 and 31 a distance of 100 feet to the point of beginning. EXCEPTING FROM PARCELS I AND II ABOVE those portions described in Dedication Deed Recorded June 22, 2007 as Recorder's Fee No. 2007-069253, Washington County Deed Records. Page 2 - EXHIBIT A 46796-38157 168658.d0CWBG1&2517009 I Exhibit B Encumbrances 1. Agreement for Purchase of Meter and Payment of System Development Charge, including the terms and provisions thereof, Between: Tualatin Valley Water District and Dartmouth Square, LLC Recorded: March 21, 2008, Recorder's No. 2008-024942 Page 1 - EXHIBIT B' 46796-3815716865E.doc'.N8G'6'7r2009 s3 § 1 I RF OI I ~ ~ ' I I I II I L--= 8 I - - 797 I a I I o®eee ®°eee D I Iol I I p EEC K IIL Na~ O V} 5 M 1 111.1 E 711 I I ° C~ c A T o p I I~ a 94-1 .j ILE u~ I p U J I I - - - w I a ~ o\- t (2)SOUTH ELEVATION (,)GENERATOR ENCLOSURE o , t~ _ t•d , tK t'd EXISTING BUILDING - L N p O > C ~ A N f m O L,SITE PLAN (1) 2 ~IZ~ c IA W SOALE 201T EC F- ~1WEST ELEVATION '0°' A11 t~.td KEY NOTES -E T C cc b CC ' Q D O Nan lMU¢'.Ir1ac r[Yr3t E - e.e -rt>~ - OE.VSnws PMCINS NffA O - c I I I I I I I I D O O eiasn,w na rANC i6ea+ATtal Ibea.AraKl b a nrt ru AO.W9lf L I I I I 1 I SECTION r.~SECTION ~ ~ r ° =Kr ,/1' . ,'4 1/1• . t'd Q Erbsn~atcm,cAL 9trswE uN° ~ Q Nsr brvlre Sov.coNSTnucnoN D.~ce~ wm NE.m+ DOCUMENTS B O~ eea+"-sa a,cw5 ~NJ mltx aK M. SITE PLAN w ~.w wonNb 1'( I O VP~ s.~ r+¢ rrwc cw cac. vro. [ AILS r;"\HYDRAULIC VERT. PIVOT GATE JI OAT _ p 0_.__ 0 4 ~ o t, I O ~ CD y II NOTES : m D D n C 1. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT. 03 O • 0 O n ( N CD 93 7/8" CD O C 1 Cn cD OPTIONAL LOW ~ n / 30 TON PLAN VIEW AMBIENT DAMPER C N y LIFTING POINTS X N - r --i O 4 O D 94 3/16" 87 1 /4" 811/16" 0 58 5/16" 57 5/16" G Q ~ O 3 ~88 7/8" - { 3 22 1/4 1 3/8" DRAIN HOLES C 1" NPT-F CONDENSATE 90 3/8" (BOTH SIDE) 93 7/8" C t DRAIN (BOTH SIDE) 130 5/16" 30 TON FRONT VIEW VJ 162 3/8" 289 3/8" Q d 30 TON LEFT SIDE VIEW 7 1 1/8" CONDUIT 6 1/16" SUPPLY D.C CONTROL CIRCUIT 1 1/8" CONDUIT A.C CONTROL CIRCUIT r~ O 41 /8" CONN. THRU p < BASE FOR POWER SUPPLY CV 1 1/8" CONDUIT AC & 67" DC CONTROL CIRCUIT 8 3/8" 403/8" RETURN 7318 8 11/16" 5L 13/16• - - l "il -91/2" 7 Q C lb 5 13/16" 78 7/8" 13 11/16" W CD 15 11!16" N p 199 1/8" 23 3/16" 18 1/16" A p 19 9/16" NO N 30 TON PLAN VIEW OF UNIT O