JAN 22-2010 12:28PM FROM- T-328 P.001/002 F-530
(UNLESS OTHERWISE SPECIFIED)
IC~c~?1C
PGE FACILITIES IN GREEN ARE TO HE REMOVED
- - - - - - _ - INSTALL 1-0350 AL-TX SECONDARY IN I OF 3-3" PVC
CONDUITS, PROVIDED & INSTALLED BY CUSTOMER
J A,a 2 2 L;3413
n 'D
.~t 01 ON
_1 k, iok
CONSTRUCTION NOTES: SFR-N
1. CUSTOMER TO PROVIDE ALL TRENCHING AND BACKFILLING. TRENCH TO BE
36 INCHES DEEP AND 24 INCHES WIDE, MEASURED FROM FINAL GRADE.
2. CONDUIT (IF NECESSARY) WILL BE GRAY, SCHEDULE 40, ELECTRICAL GRADE,
PVC CONDUIT WITH NYLON PULL STRINGS (MIN. 500 LBS. TEST).
PGE TO DETERMINE THE SIZE AND NUMBER OF CONDUITS REQUIRED.
MAINTAIN 2 VERTICAL INCHES AND 24 HORIZONTAL INCHES CLEARANCE BETWEEN
GAS AND OTHER UTILITIES. ALL ELBOWS TO BE 36 INCH (MIN) RADIUS.
ALL SENDS MUST BE FACTORY MADE. CONDUIT RUNS LONGER THAN 150 FEET
OR WITH MORE THAN 270 DEGREES OF BENDS MUST USE RICID STEEL ELBOWS,
OR PGE APPROVED FIBERGLASS AND MUST BE APPROVED BY PGE PRIOR TO
INSTALLATION BY CUSTOMER.
3. CUSTOMER RESPONSIBLE FOR ROAD CROSSINGS. USE ONLY GRAY, SCHEDULE 40.
ELECTRICAL GRADE, PVC CONDUIT WITH NYLON PULL STRINGS (MIN. 500 LBS. TEST).
4. SINGLE PRIMARY INSTALLATIONS-CONDUIT TO EXTEND A MINIMUM OF 10' FROM
TRANSFORMER PAD.
WR CHECKLIST s. ALL PGE TRANSFORMERS TO BE INSTALLED a FEET IMIN) FROM ANY COMBUSTIBLE
BUILDING AND 4 FEET (MIN) FROM ANY FIRE HYDRANT. POE TRANSFORMERS MUST
BE WITHIN 15 FEET OF A DRIVEABLE AREA. ALWAYS MAINTAIN 10 FEET CLEARANCE
ITEM NO YES IN FRONT OF ALL TRANSFORMERS.
HOLEDIGGER X 6. CUSTOMER TRENCH AND ELBOW CONFIGURATIONS MUST BE INSPECTED BY PGE PRIOR
BOOM X TO BACKFILLING. PLEASE CALL $03-736-5450 TWO DAYS PRIOR TO INSPECTION.
SACKHOE X 7. DESIGN 15 BASED ON STANDARD UNDERGROUND EQUIPMENT.NDN-STANDARO UNDGERGROUND
EQUIPMENT MAY BE AN OPTION AT AN ADDITIONAL COST TO THE CUSTOMER.
PGE TRENCH X
LOCATES X AS-BUILT VERIFICATION This document accurately
_ STAKING X & NESC VIOLATIONS CORRECTED represents FIELD construction.
FLAGGING X
TREETRIM X Foreman: Date:
LANDSCAPE X SDC
EASEMENT X Engineer: Date:
PERMITS X Designer: Date:
CUTSHEET X www.PartlondGeneral.com www.PortlandGeneral.biz www.EarthAdvantage.com
TRANSMISSION 1011 NO, DATE SECTI INIS) SCALE
SHUTDOWN x 526270 01/31/x008 C21-02A V=60'
CUSTOMER CIRCUIT SIZE
SHUTDOWN X TIGARD - 13336 IIxl7
CONTACT PGY TITLE
PHn RICHARD LUNDSTROM
LOCATION
DATE 8861 SW COMMERCIAL ST. TIGARD; WASH CO
TIME WILSONVILLE DESCRIPTION SHEET
DOOR HANGERR X LINE CREW CENTER INSTALL UG SVC
DESIGN BY PHONE (503) DRAWN BY I OF (
UG CIR. VER. X 9480 SW BOECKMAN RD MILO STARR 570-4414 K.RUTHERFORD
WILSONVILLE, OR 97070
® PORTLAND GENERAL ELECTRIC CO. -ALL RIGHTS RESERVED
f
2.2010 12:28PM FROM-
T-328 P-002/002 F-530
1,17% KR
19,36 AIC 1-210 AL-TX
c.0/240V
800A ERM CAN 1-350 A X-D
S 4-200AM METERS 2-3°SP E
/y Of
f•6 y~ 8861
~0 e-
D2544 ,''L PGA _,,-INSTALL 3" POLE CONDUIT UNIT
996-45 % WITH 12" HRACKETS & WEATHERHEA
f r a
°q f~ 'CIL
1-142
5 F10T
PG3E
1996 PL02544 rrFrr r,-` ,f ti j
1 0 020O
PL 9~
01618- 9C's 9C POLE 402544
00460/
PL02544 s'p
C 75 44
B 10 3584
9 61.16t0MOR5r 61.9K
APO i CLIW ER8l 25KW
LOAD TYPE CONNECTED DIVERSITY ESTIM
KW FACTOR DEM
LIGHTING 13.2 0.9 ll.-
RECEPTACLES 0.1
WATER HEATING 12 0.2 2
ELECTRIC HEAT 0.75
REFRIGERATION / AC 10.5 0.75 7.1
MOTORS
MISC 10 0.3
J
G TOTAL CON LOAD 34,7
OTAL EST. DEMAND
PG CO, N~
'y w
B SITE CALL BEFORE YOU DIG: OREGON LAW REQUIRES YOU TO REQUEST UTILI'
LOCATION 4e HOURS PRIOR TO EXCAVATION. FOR LOCATES CALL THE OREG0
UTILITY NOTIFICAT10N CENT10% AT 503-246-MSS OR 1-800-332-2344.
655'F4 ll~/ z CONTACT SERVICE WILL NOT COORDFOR INATOR MIRE UNTIL OTCRENCH TlS I10OE ®ACKFILLLE
MC DONALD \ N SERVICE COORDINATOR
VICINIT AP 503-736•-5450