Plans
JAN-22°2010 12:28PM FROM- T-328 P.001/002 F-530
i vL--- vv i tee` , .ter
(UNLESS OTHERWISE SPECIFIED) I(':lrJ!00 lg
PGE FACILITIES IN GREEN ARE TO BE REMOVED
- - - - INSTALL I-0350 AL-TX SECONDARY IN I OF 3-3" PVC
CONDUITS, PROVIDED lIz INSTALLED BY CUSTOMER
CONSTRUCTION NOTES: SFR-N
I. CUSTOMER TO PROVIDE ALL TRENCHING AND BACKFILLING. TRENCH TO BE
36 INCHES DEEP AND 24 INCHES WIDE, MEASURED FROM FINAL GRADE.
2. CONDUIT (IF NECESSARY) WILL BE GRAY, SCHEDULE 40, ELECTRICAL GRADE,
PVC CONDUIT WITH NYLON PULL STRINGS (MIN. 500 LBS. TEST).
PGE TO DETERMINE THE SIZE AND NUMBER OF CONDUITS REQUIRED.
MAINTAIN 12 VERTICAL INCHES AND 24 HORIZONTAL INCHES CLEARANCE BETWEEN
GAS AND OTHER UTILITIES. ALL ELBOWS TO BE 36 INCH (MIN) RADIUS.
ALL SENDS MUST BE FACTORY MADE. CONDUIT RUNS LONGER THAN 150 FEET
OR WITH MORE THAN 270 DEGREES OF BENDS MUST USE RIGID STEEL ELBOWS,
OR PGE APPROVED FIBERGLASS AND MUST OF APPROVED BY PGE PRIOR TO
INSTALLATION BY CUSTOMER.
3. CUSTOMER RESPONSIBLE FOR ROAD CROSSINGS. USE ONLY GRAY, SCHEDULE 40,
ELECTRICAL GRADE, PVC CONDUIT WITH NYLON PULL STRINGS (MIN. 500 LBS. TEST).
4. SINGLE PRIMARY INSTALLATIONS-CONDUIT TO EXTEND A MINIMUM OF 10' FROM
TRANSFORMER PAD.
5. ALL PGE TRANSFORMERS TO BE INSTALLED B FEET (MIN) FROM ANY COMBUSTIBLE
WR CHECKLIST BUILDING AND 4 FEET (MIN) FROM ANY FIRE HYDRANT. PGE TRANSFORMERS MUST
BE WITHIN 15 FEET OF A DRIVEABLE AREA. ALWAYS MAINTAIN 10 FEET CLEARANCE
ITEM NO YES IN FRONT OF ALL TRANSFORMERS.
HOLEDIGGER X 6. CUSTOMER TRENCH AND ELBOW CONFIGURATIONS MUST BE INSPECTED BY PGE PRIOR
BOOM X TO BACKFILLING. PLEASE CALL 503-T36-5450 TWO DAYS PRIOR TO INSPECTION.
SACKHOE X 7. DESIGN 15 BASED ON STANDARD UNDERGROUND EQUIPMENT. NON-STANDARD UNDGERGROUND
EQUIPMENT MAY BE AN OPTION AT AN ADDITIONAL COST TO THE CUSTOMER.
PGE TRENCH X
LOCATES X AS-BUILT VERIFICATION This document accurately
STAKING X & NESC VROLATI®NS CORREC TED represents FIELD ccnstructlon.
FLAGGING X
TREETRIM X Foreman: e:
LANDSCAPE X SDC
X lEngine ar: Date;
EASEMENT
PERMITS X Designer: Date:
CUTSHEET X www.PortlondGeneral.com www.PortlandGenerol.biz www.EarthAdvantege,com
TRANSMISSION JOB NO. DATE SECTION(S) SCALE
SHUTDOWN X 526270 01/31/2008 C21-02A P=60'
CUSTOMER CIRCUIT SIZE
SHUTDOWN X TIGARD 13336 IIx17
CONTACT P~~ TITLE
C
CON RICHARD LUNDSTROM
PH$ LOCATION
DATE 6861 SUN COMMERCIAL ST, TIGARD; WASH CO
TIME WILSONVILLE DESCRIPTION SHEET
DOOR HANGER X LINE CREW CENTER INSTALL LJG SVC
DESIGN BY PHONE (503) DRAWN BY I OF I
JUG CIR. VER. X 9480 SIB BOECKMAN RD MILO STARR 570m4414 K,RUTHERFORD
WILSONVILLE, OR 97070
® PORTt_AND GENERAL ELECTRIC CO.- ALL RIGHTS RESERVED
2°2010 12:28PM FROM-
T°326 P.0021002 F°530
c-.; IC.ZCI~
1.17% KR
19, 36 - AIC 1-210 AL-TX
G.0/240V
800A ERM CAN I -350 A X-0
S 4-200AM METERS 2-3°5P E
5861
~i ~o ~C `o r~ PGA __-,--INSTALL 3" POLE CONDUIT UNIT
0996445~~ WITH 12" BRACKETS & WEATHERHEA
1-142
00501 E10T
1996-30 PL02544 PGE
O1 8-
0 18/
P1~02544
01818- q~s POLE #02544
00460/ PLL02544
C 75 44
B 10 3584
9 GU6fOM6126a 61.3K
A99 I 6U6t0MER5o 25KW
LOAD TYPE CONNECTED DIVERSITY ESTIM
KW FACTOR DEM
LIGHTING 13.2 0.9 II..
RECEPTACLES 0.1
WATER HEATING 2 0.2 2
ELECTRIC HEAT 0.75
REFRIGERATION / AC 10.5 0.75 7.1
MOTORS
MISC 10 0.3
--1 TOTAL CON LOAD 34.7
TOTAL EST. DEMAND
1F 1c ti~
~ Coo ti~
~ w
B SITE CALL BEFORE YOU DIG: OREGON LAW REGUIRES YOU TO REQUEST UTILI'
THOMAS cu1OE LOCATION 48 HOURS PRIOR TO EXCAVATION. FOR LOCATES CALL THE OREGO
UTILITY NOT(FiCAT(ON CENTER AT 503-246-•6659 OR 1-500°332-2344.
6 -F.41 q/ Z TONSAACKFILLLRPIGE WILL NOT INSTALL WIRE UNTIL DTRENCH IIS INSPECTION 10% BACKFIPLIEI
MC DONALD SERVICE COORDINATOR
l.. VICINIT AP 503-736-5450