JAN-22-2010 i2:28PM!'- FROM- T°329 P. 001/002 F°530
(UNLESS OTHERWISE SPECIFIED) ~LAC~
PGE FACILITIES IN GREEN ARE TO BE REMOVED
- - ° INSTALL 1-'0350 AL-TX SECONDARY IN I OF 3-3" PVC
CONDUITS, PROVIDED & INSTALLED BY CUSTOMER
CONSTRUCTION NOTES: SFR-N
I. CUSTOMER TO PROVIDE ALL TRENCHING AND BACKFILLING. TRENCH TO BE
36 INCHES DEEP AND 24 INCHES WIDE, MEASURED FROM FINAL GRADE.
2. CONDUIT (IF NECESSARY) WILL BE GRAY, SCHEDULE 40, ELECTRICAL GRADE,
PVC CONDUIT WITH NYLON PULL STRINGS (MIN. 500 LBS. TEST).
PGE TO DETERMINE THE SIZE AND NUMBER OF CONDUITS REQUIRED.
MAINTAIN 12 VERTICAL INCHES AND 24 HORIZONTAL INCHES CLEARANCE BETWEEN
GAS AND OTHER UTILITIES. ALL ELBOWS TO BE 36 INCH (MIN) RADIUS.
ALL BENDS MUST BE FACTORY MADE. CONDUIT RUNS LONGER THAN 150 FEET
OR WITH MORE THAN 270 DEGREES OF BENDS MUST USE RIGID STEEL ELBOWS,
OR PGE APPROVED FIBERGLASS AND MUST BE APPROVED BY PGE PRIOR TO
INSTALLATION BY CUSTOMER.
3. CUSTOMER RESPONSIBLE FOR ROAD CROSSINGS. USE ONLY GRAY, SCHEDULE 40,
ELECTRICAL GRADE, PVC CONDUIT WITH NYLON PULL STRINGS (MIN. 500 LBS. TEST).
4. SINGLE PRIMARY INSTALLATIONS-CONDUIT TO EXTEND A MINIMUM OF 10' FRAM
TRANSFORMER PAD.
Ip'
n CHECKLIST 5. ALL PGE TRANSFORMERS TO BE INSTALLED 8 FEET (MIN) FROM ANY COMBUSTIBLE
tYR BUILDING AND 4 FEET (MIN) FROM ANY FIRE HYDRANT. PGE TRANSFORMERS MUST
BE WITHIN 15 FEET OF A DRIVEABLE AREA. ALWAYS MAINTAIN 10 FEET CLEARANCE
ITEM NO YES IN FRONT OF ALL TRANSFORMERS.
HOLEDIGGER X 6. CUSTOMER TRENCH AND ELBOW CONFIGURATIONS MUST BE INSPECTED BY PGE PRIOR
BOOM X TO BACKFILLING. PLEASE CALL 503-T36-5450 TWO DAYS PRIOR TO INSPECTION.
BACKHOE X 7. DESIGN IS BASED ON STANDARD UNDERGROUND EQUIPMENT. NON-STANDARD UNDGERGROUND
EQUIPMENT MAY BE AN OPTION AT AN ADDITIONAL COST TO THE CUSTOMER.
PGE TRENCH X
LOCATES X AS-BUILT VERIFICATOO N This document CCCUrately
STAKING X represents FIELD ccnsrructlon.
° FLAGGING X & CORRECTED
TREETRIM X Foreman: Defe:
LANDSCAPE X SDC
EASEMENT X Engineer: Date-,
PERMITS X Designee': Date:
CUTSHEET X www.PortlandGeneral.com www.PortlandGeneral.biz www.EarthAdvantage.com
TRANSMISSION 108 N0. DATE SECTION(S) SCALE
1HUTDOWN( X 526270 01/31/2008 C21- 12A 1"=60'
CUSTOMER CIRCUIT SIZE
SHUTDOWN X /PP TIGARD 13336 IIx17
CONTACT TITLE
PH$ RICHARD LUNDSTROM
LOCATION
DATE 8861 SW COMMERCIAL ST, TIGARD, WASH CO
TIME WILS17PIVILLE DESCRIPTION SHEET
DOOR HANGER X LINE CREW CENTER INSTALL lJG SVC
DESIGN BY PHONE (5031 DRAWN BY I OF 1
UG CIR. VER. 9480 SW BOECKMAN RD MILO STARR 570-4414 K.RUTHERFORD
WILSONVILLE, OR 97070
0 PORTLAND GENERAL ELECTRIC CO, ° ALL RIGHTS RESERVED
,2®2010 12:28PM FROM-
T-328 P.002/002 F-530
1.17% KR
19,36 A1,C 1-210 AL-TX
_0/240V
800A ERM CAN 1-350 A X-0
S 4-200AM METERS 2-3"SP E
u 0'
00 r r.6, g1~~ 8 $ 61 ~
02544, _,,--INSTALL 3" POLE CONDUIT UNIT
996-45~ ti's WITH 12" BRACKETS & WEATHERHEA
s~x T`~ 1~0~
1 ° 142
00501 F10T 3-3"
1996-30 PL02544 J'rFr ,
PGE
01 1 S/
PI~02544
01816-°s POLE 402584
PL02544
C 75 44
8 10 3584
9 Gu6fomKo 0 6 I .31C
A00 I 6U6t0M6K5o 25KW
LOAD TYPE CONNECTED DIVERSITY ESTIM
KW FACTOR DEM
LIGHTING 13.2 0.9 IL.
RECEPTACLES 0.1
WATER HEATING 12 0.2 2
ELECTRIC HEAT 0.75
REFRIGERATION / AC 10.5 0.75 7.1
MOTORS
misc --lo 0.3
J
.mJ
TOTAL CON LOAD 39.7
Q OTAL EST. DEMAND
P~ ~o
8 SITE CALL BEFORE YOU DIG: OREGON LAW REQUIRES YOU TO REOUEST UTILI'
THOl9A5 GUIDE C~1 LOCATION 49 HOURS PRIOR TO EXCAVATION, FOR LOCATES CALL THE OREGO
UTILITY NOTIFICATION CENTER AT 503-286-6692 OR 1-600-332-2344.
655-F4 Z TO BAACKFILL, PIGS WILL COGRO)NATOR FOR
INSTALL WIRE TRENCH TRENCH 15 1007 SACKFL LIEI
I ° I C DONALD \ N SERVICE COORC~INATOR
~~C{(~{T AP 503~~3+a~s45o