HomeMy WebLinkAboutFPS2023-00117 (3) FPS20Z3 60117 1626o s4J VaciVic HwjG12 • RECEIVED tilcu OCT 0 4 7023 Worldwide www.tyco-fire.com CITY OF TIGARD °3u11 niNn nlVlSlnni Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers - Description described herein must be installed F and maintained in compliance with The TYCO Series T FRB,5.6 K-factor, this document, as well as with the u Y Upright (TY313)and Pendent (TY323) applicable standards of the National Sprinklers described in this data sheet Fire Protection Association,in addition . s are quick response,standard coverage, to the standards of any other authori- ' is decorative 3 mm glass bulb-type spray ties having jurisdiction.Failure to do so sprinklers designed for use in light or may impair the performance of these ordinary hazard,commercial occupan- devices. cies such as banks, hotels,and shop- ping malls. The owner is responsible for main- taining their fire protection system The recessed version of the Series and devices in proper operating con- TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac- applicable,is intended for use in areas tor or product manufacturer with any with a finished ceiling. This recessed questions. `: '` pendent sprinkler uses one of the -_ following: Sprinkler • A two-piece Style 15 Recessed r� Escutcheon with recessed adjust- Identification ;r ' t ment up to 5/8 in. (15,9 mm)from .,._ the flush pendent position. Number (SIN) ,,,► 15. • A two-piece Style 20 Recessed TY313. .. . Upright 5.6K,1/2 in.NPT Escutcheon with recessed adjust- TY323. . . .Pendent 5.6K,1/2 in. NPT ment up to 1/2 in. (12,7 mm)from = the flush pendent position. Technical The adjustment provided by the Data Operation Recessed Escutcheon reduces the accuracy to which the fixed pipe drops The glass bulb contains a fluid which to the sprinklers must be cut. Approvals expands when exposed to heat.When Intermediate level versions of Series Refer to Table A the rated temperature is reached, the TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently to shatter the Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to kler guards and shields are described 250 psi(17.2 bar)* activate and water to flow. in Technical Data Sheet TFP780. •The maximum working pressure of 250 psi(17.2 bar) Design only applies to the listing by Underwriters Laborato- ries,Inc.(UL). Discharge Coefficient Criteria IMPORTANT K=5.6 GPM/psi'(80,6 LPM/bar1/2) The TYCO Series TY FRB,5.6 K-factor, Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323) TFP2300 for wamings pertaining to Refer to Table A Sprinklers are intended for fire protec- regulatory and health information. tion systems designed in accordance Finishes Y 9 Always refer to Technical Data with the standard installation rules Sheet TFP700 for the "INSTALLER Sprinkler:Refer to Table B recognized by the applicable Listing or WARNING"that provides cautions Recessed Escutcheon:White Coated, Approval agency(such as, UL Listing with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA lation of sprinkler systems and com- Plated 13, and FM Approval is based on the ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used nents and cause the sprinkler to fail Sealing Assembly...stainless Steel w/TEFLON for recessed pendent installations. to operate in a fire situation or cause Bulb Glass it to Operate prematurely. Compression Screw Bronze Deflector Bronze Page 1 of 4 AUGUST 2018 TFP172 TFP172 , Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON se& ,I=/ . ----------- / 5 =! 7/16" I \ \ i I Num NOMINAL 2" 4 MAKE IN (50,8 min) 1 i to (50,8min) (34,9 mm) %kr ENCH 1 t 1I FLATS 1 - - 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 min)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Installation Step 2. With pipe-thread sealant L� applied to the pipe threads, hand- RENCH RECESS The TYCO Series TY FRB,5.6 K-factor, tighten the sprinkler into the sprinkler W Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the END"A") dance with this section. sprinkler fitting using only the W-Type -� General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FIGURE 2 Do not install any bulb-type sprin- erence to Figure 1,apply the W-Type 6 Sprinkler Wrench to the wrench flats. W-TYPE 6 kler if the bulb is cracked or there is Torque sprinklers 7 to 14 lb-ft (9,5 to SPRINKLER WRENCH a loss of liquid from the bulb.With the sprinkler held horizontally, a small air 19,0 N•m). bubble should be present. The diam- Recessed Pendent Sprinklers WRENCH eter of the air bubble is approximately The Series TY FRB Recessed Pendent RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor- 3/32 in.(2,4 mm)for the 286°F(141°C) dance with the following instructions. /��� temperature ratings. Step A. After installing the Style 15 �� A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the should be obtained by applying a sprinkler threads,and with pipe-thread minimum to maximum torque of 7 to sealant applied to the pipe threads, 14f lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the `�� of torque can distort the sprinkler Inlet sprinkler fitting. with consequent leakage or impairment Step B.Tighten the sprinkler into the IN ENSURE PUSH WRENCH of the sprinkler. sprinkler fitting using only the W-Type TODo not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure ENGAGEMENT insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WITH SPRINKLER eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench WRENCHING AREA the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m). W-TYPE7 RECESSED Upright and Pendent Sprinklers Step C. After ceiling installation and SPRINKLER WRENCH The Series TY-FRB Upright and finishing,slide on the Style 15 or Style Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB in accordance with the following Sprinkler and push the Closure over the instructions. Mounting Plate until its flange comes in Step 1.Install Pendent sprinklers in the contact with the ceiling. pendent position.Install upright sprin- klers in the upright position. TFP172 Page 3 of 4 Care and 2-7/8" DIA. Maintenance (73,0 mm) 2-1/4"DIA. The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm) Upright (TY313) and Pendent (TY323) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. + \ - FLUSH Before closing a fire protection system 3/8±5/16" ,,III main control valve for maintenance (9,5t7,9 mm) 11I 1 '/ work on the fire protection system } / Illi, 1/8„ that it controls, obtain permission to shut down the affected fire protection MOUNTING J systems from the proper authorities SURFACE (3,2 mm) and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 affected by this action. mm) TY-FRB PLATE 3/4"(19,1 mm) Absence of the outer piece of an FIGURE 4 a clearance hole, can deulay escutcheon, whichis to cover SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) operation in a fire situation.lay sprinkler WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 1 The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only - 2-7/8" DIA. - cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER 2-1/4" DIA. _ vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16t1/4" leaking or exhibiting visible signs of (7,9t6,4 mm) 1/2"(12,7 mm) corrosion must be replaced. + m FLUSH Automatic sprinklers must never be 11�``Ljik 1 I . ,7, painted, plated, coated, or other-wise altered after leaving the factory. t / Modified sprinklers must be replaced. MOUNTING 1/8" J Sprinklers that have been exposed to SURFACE (3,2 mm) corrosive products of combustion,but have not operated,should be replaced - - 1 if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON klers damaged by dropping, striking, wrench twist/slippage,or the like,must Limited Recessed Escutcheon be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch- kler that has a cracked bulb or that has eon with(specify*)finish,P/N(specify"`) lost liquid from its bulb. (Ref. Installa- Warrant tion Section.) Specify: Style 20 Recessed Escutch- For warranty terms and conditions,visit eon with(specify*)finish,P/N(specify*) The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770 inspection,testing,and maintenance of their fire protection system and devices with this document, as Ordering Sprinkler Wrench in complianceSpecify: W-Type 6 Sprinkler Wrench, well as with the applicable standards Procedure P/N 56-000-6-387 of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001 the standards of any other authorities ability.When placing an order,indicate having jurisdiction.Contact the install- the full product name and Part Number ing contractor or product manufacturer (p/N). with any questions. Automatic sprinkler systems are rec- Sprinkler Assemblies with NPT ommended to be inspected, tested, Spread ConnectionsSeTY or and maintained by a qualified Inspec- Specify:n (specify)es Sprinkler,Upright IN tion Service in accordance with local Pendent p SIN requirements and/or national codes. (specify), mK era5.6, Quick Response, (specify)temperature rating, (specify) finish,P/N(specify,refer to Table A). TFP172 Page 4 of 4 SPRINKLER FINISH(See Note 7) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERe FACTOR COLOR BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6 PENDENT(TY323) 200°F(93°C) Green 5.6 286°F(141°C) Blue 1/2 in.NPT 135°F(57°C) Orange RECESSED PENDENT 155°F(68°C) Red 1,2,3,4 (TY323) 175°F(79°C) Yellow Figures 4a and 5b 200°F(93°C) Green Notes: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable. b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable. c. Frame and Deflector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/Na77 — XXX — X — XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C) 371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C) POLYESTER Notes: 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) a. Use suffix"I"for ISO 7-1 connection;for example, POLYESTER 77-370-4-175-I 5 JET BLACK(RAL9005) 200 200°F(93°C) POLYESTER 9 CHROME PLATED 286 286°F(141°C) Notes: a. Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION / �/ 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 {. C 2018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date end are subject to change without notice. Jo 1 neon ��),�i NATIONAL FIRE PROTECTION ASSOCIATION aid NFPA are registered trademarks of National Fire Protection Association: Controls TEFION is a registered trademark of DuPont FLexHead® Flexible Sprinkler Hose Solutions 1"1.%t() ASC,.. Engineered Solutions Fig. 20XXT Standard Tall Hose Specifications — t` Assembly Length r . _ .. 24 in 36 in 48 in �, - 60 in 72 in " d ` ?. nay s,'� " ''t+ e �Y ���� , $� � � � ' �` Outlet Drop Size(NPT per ASME B1.20.1) i' �, ° 1/2 NPS(DN15) 3/a NPS(DN20) �' �r � s� w �a r ¢ f� Inlet Pipe Size(NPT per ASME Bt20.1) � k t ii $ a te W ' ( ) 1 NPS DN25 Pressure Rating coos O UL: 175 psi(1,205 kPa) LenD APPROVED FM:175 psi(1,205 kPa) Minimum Bend Radius Fig.20XXT cULus&FM Approved Brackets UL: 3.0 in(76.2 mm) Bracket cULus Listed FM Approved FlexHead Historical FM:8.0 in(203.2 mm) Fig#&Size Model Number BKT-MPO ✓ ✓ MP024BKT2 Ambient Temperature 300°F(145°C)Max BKT-MPT ✓ ✓ MPT24BKT1 Material BKT-ADO,16 in ✓ ✓ AD016BKT3 304 Stainless Steel BKT-ADO,24 in ✓ ✓ AD024BKT3 Features BKT-ADO,30 in ✓ ADO3OBKT3 • 100%Leak Tested Fully Welded Design BKT-ADO,48 in ✓ ADO486KT3 • Pre-Installed Sprinkler Head option BKT-UH03 V UHO-3 available upon request • Compliant with NFPA 13,13R,&13D BKT-TZ ✓ SPO6TZBKT2 • For Wet,Dry,and Pre-Action Notes:Flexhead Historical Model Numbers may be used to verify cULus Listings&FM Approvals. Sprinkler Systems Ordering Specify figure number,length,outlet size, outlet drop length,and description. 1(:)1 FLEXHEAD An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: Approved Address: Approved as noted Contractor: Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: FH-3.22 page 1 FP-SUB-20XXT-Standard-Tall-Hose-v0120220331 FlexHead®Flexible Sprinkler Hose Solutions rill114111'. Engineered Solutions Fig. 20XXT Standard Tall Hose Fig.20XXT cULus Listing per UL 2443&FM Approval(Listing)per FM 1637 Equivalent Length Max#of 90°Bends Outlet Asembly FM Drop Length UL k=5.6 k=8.0 k=11.2 k=14.0 k=16.8 UL FM In ft/m ft/m ft/m ft/m ft/m ft/m 11 18.4 7.7 7.6 24 - - 3 1 3.4 5.6 2.3 2.3 16 26.6 11.5 11.5 36 - - 3 2 4.9 8.1 3.5 3.5 1/2 NPS 24 30.3 15.3 15.4 DN15 48 7.3 9.2 4.6 4.7 - - 4 3 60 29 35.8 19.1 19.3 - - 4 4 8.8 10.9 5.8 5.9 35 45.6 23.0 23.2 72 - - 4 4 10.7 13.9 7.0 7.1 12 7.3 5.9 14.7 7.1 - 243 1 3.7 2.2 1.8 4.5 2.2 18 21.5 10.4 21.8 10.9 - 363 2 5.5 6.5 3.1 6.6 3.3 3/4 NPS 48 -23 30.5 14.9 29.0 14.8 4 3 DN20 7.0 9.3 4.5 8.8 4.5 29 39.5 19.4 36.1 18.7 60 8.8 - 12.0 5.9 11.0 5.7 4 4 72 32 48.5 24.0 43.2 22.6 4 4 9.8 14 7.3 13.1 6.9 1 Equivalent Length of NPS 1(DN25)Sch 40 Pipe. 2 Equivalent Lengths listed above assume the maximum number of 90°bends. 3 A 90°bend can be achieved with two 45°bends or three 30°bends. 4. UL Equivalent Lengths are listed for installation with sprinklers with a maximum k-factor of 16.8. 5 FM Equivalent Lengths listed above include the Friction Loss of the Sprinkler. 6.UL Listed for"Limited Flexibility" FH-322 page 2 FP-SUB-20XXT-Standard-Tall-Hose-v0120220331 : 16C ., Engineered Solutions Fig. 20XXT Standard Tall Hose --------A-----1 — X —V\----1 r B - ,gim&\//<7,‘ .4 s/k22 ,&,/ .1e. ' N N, /4 ws 7, .,/,N,p,-.4 ..\../ 3.. 4,,&‘. 4.-7.— /</,.,,, /\/>f&Xe <4;:g /<,,'; „v/‘4.;&.•..d,/,k,, ,e,, Fig.20XXT cULus Listing per UL 2443&FM Approval(Listing)per FM 1637 Asembly True Length(L) Braid Length(X) Inlet Nipple Length(A) Outlet Drop Length(B) FlexHead Historical Length Model Number in in mm in mm in mm in mm 1/2 NPS Outlet 3/4 NPS Outlet 24 24 610 15 381 20241-50 2024T-75 36 36 914 37 940 2036T-50 20361-75 48 48 1219 39 991 3.0 76.2 6.3 160.0 20481-50 2048T-75 60 60 1524 51 1295 2O60T-50 20601-75 72 72 1829 63 1600 2072T-50 20721-75 0 FLEXHEAD. Art ASC Engineered Solution FH-3.22 page 3 FP-SUB-20XXT-Standard-Tall-Hose-v0120220331 - /6C.' ' to) Engineered Solutions Fig. 20XXT Standard Tall Hose Installation Instructions Connection to the Branch 1. Apply pipe sealant or tape to the NPT thread. 2. Install into branch outlet.Tighten the assembly by placing the pipe wrench on the pipe nipple section. 3. Note:Only place the pipe wrench on the unthreaded portion of the inlet nipple. Connection to the Sprinkler Head 1. Installation of the sprinkler head into the outlet drop shall be per the sprinkler manufacturer's installation instructions. Connection to the Bracket 1. Installation of the hose to the bracket shall be per the bracket's installation instructions.The bracket shall be listed for installation with the 20XXT.See Page 1 for Listed and Approved brackets. Bending the Hose 1. The hose may be bent to ensure the inlet nipple and outlet drop are in the desired locations. 2. The hose should never be bent to a radius less than minimum listed bend radius.The bend radius is defined to the center of the hose. 3. The hose must have at least one 90°bend.A 90°bend can be achieved with two 45°bends or three 30°bends. 4. For best performance,the bends in the hose should be as large and smooth as possible. General Installation Notes 1. Never apply a wrench to the braided hose. 2. The Fig 20XXT may be installed in any direction from the branch. 3. If installing a sprinkler to a bracket after installation,it is best practice to prevent twisting of the bracket and hose by holding the outlet drop with a wrench. 0 FLEXHEAD An ASC Engineered Solution FH-322 page 4 FP-SUB-20XXT-Standard-Tall-Hose-v0120220331 EMPFladbleVrinkter Hose Solubons Engineered Solutions Multiport Open Hub Bracket Fig. BKT-MPO Product Specifications 13r.1cke_t t eucilt 24 in t iate rial Carbon Steel-Galvanized r��i>lic tie3ns Suspended Ceilings per ASTM C635&C636 Wood Framing-Gypsum or Dry Wall '1 Steel Framing-Gypsum or Dry Wall tp F t tl urts Open hub design for ease of installation Bracket hub set for Center-of-Tile installation out of the box. Wide body prevents rotation and ensures stability 0 Bracket hub may be installed at quarter 1eID APPROVED and mid points along the bracket Fig.BKT MPO cull us l fh Listed Hoses CH It riuc Hose Figure# cULus Listed FM Approved Specify figure number&description 20XXT ✓ ✓ 20XXET ✓ FLEXHEAD 20XXE ✓ _ ✓ ✓ An ASC Engineered Solution 20XXSF 20XXSF-CS ✓ 20XXSF-SLT ✓ 20XXSF-CS-SLT ✓ 20XXH ✓ ✓ 20XXHE ✓ ✓ 20XXI ✓ 20XX-DPS ✓ 20XX-DPS-DT ✓ Note:Brackets are only UL Listed and FM AApproved when installed with FlexHead brackets listed above. PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: 0 Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: FH page 1 FP-SUB-BKT-MPO-v01 20220418 - nexage - kiermosesokido Engineered Solutions Multiport Open Hub Bracket Fig. BKT-MPO Applications rit 011illint .,_.._ .._.,_ ,._..._ .._ .._ — ...._.._ W. F".411 -1. 111.01 if! Millia 4 "IlliMir--7-11Millimi" .1.111"..131111111111111111111111111111111111114 Mid Point Installation Quarter Point Installation , - 7 -. 1 - -1- i' 1 7— i 1 I — ::_7J —1 1 r d...— — ___-- - --------- I [.. , -- L---... L - 16"On-Center Wood Frame Installation 16"On-Center Steel Frame Installation F FLEXHEAD. An ASC Engineered Solution FH page 2 FP-SUB-BKT-MPO-v01 20220418 FLEXHBD® Spinkler Hosed n 4441%/ Engineered Solutions Multiport Open Hub Bracket Fig. BKT-MPO /l >, � r + 9 + � o ( 4 � ) L ( 1 + I I I I I I I I + - A - Y I , , � H � � Z } L - Fir,.BKT MPO Dimensions&Mode[Number L W H A Y Z FlexHead Historical In/mm In/mm in/mm in/mm in/mm in/mm Model Number 24 6.00 3.14 16.0 1.13 0.75 MP0246KT2 610 152.4 79.7 406.4 28,7 19.1 F FLEXHEAD An ASC Engineered Solution FH page 3 FP-SUB-BKT-MPO-v0120220418 • 144400. ASC Engineered Solutions Multiport Open Hub Bracket Fig. BKT-MPO ,ilsi I I It.ton i ;, Ia Determine the location of the sprinkler above the suspended ceiling tile. Position the bracket legs and hub in the desired location on suspended ceiling T-bar. Note:The hub and self-drilling mounting screws are in the true center of the bracket. • . Install one bracket leg at a time,applying a downward pressure on the bracket leg and T-bar. ' R&M1: • Install the self-drilling mounting screw into the suspended ceiling T-bar using the tamperproof head drive provided.Repeat on both sides of the bracket. i lj/I ,uiT4: _ ,1i � t, .. �" �'tl �,l , i ,'... I Determine the location of the sprinkler between the wood frames or steel studs. Adjust the position of the bracket hub to the desired position if necessary.The hub may be placed on the top or bottom of the bracket body. • Install two(2)screws into each structural stud(wood or steel).Four(4)screws total per bracket. Wood Frames:'/4-20 Self Tapping Screw k Steel Frames:1/4-20 Self Tapping Screw riin(-t FIoxibh S(>�inhler Hc�s�: Open the hinge door on the bracket hub by rotating the locking shaft 1/4 turn. 2 Slide the flexible hose drop into the hub. Close the hinge door and re-lock the locking shaft with a 1/4 turn. i Ensure the flexible hose drop is straight and not applying a substantial moment on the bracket which may cause sprinkler misalignment. `' Adjust the flexible hose drop to the desired height and tighten the set screw hand-tight plus a 3/4 turn(130 in-lbs). ,ArIp ctin;. tfie Pin I- t Hui? I Loosen the mounting screws holding the hub to the bracket body. Slide the hub along the bracket body to the desired position and tighten the mounting screws. t�crre���n ld,,I� Installation&maintenance of FlexHead products shall be in accordance with applicable local and federal codes (E.g.NFPA13,NFPA13R,NFPA13D,NFPA25,FM Datasheets,IBC). FLEXHEAD. An ASC Engineered Solution FH page 4 FP-SU8-8KT-MPO-v01 20220418