Report (6) pco5.6
OFFICE COPY /CO6 s cosc,405. ,A✓
-4111
Honeywell Addressable Fire Alarm Control Panels
SILENT
SA KNIGHT
6808 RECEIVED
Addressable Fire Alarm Control Panel APR 42022
CITY OF TIGARL) • -
The 6808 is an addressable fire alarm control panel(FACP)than.abuiLDING DIVISION
direct replacement for the 5808 FACP.The 6808 can be configured to
achieve a point capacity of 198 points.It has one built-in signaling line
circuit(SLC),which can support 99 System Sensor'(SK)sensors and
99 SK modules or 127 Hochiki"(SD)devices per loop.
A common communications and annunciation link allows up to 17
panels to be connected via copper or fiber optic cable.A designated
panel is configured as the communicator for all panels in the link for
convenient single-point communications.It also has a built-in,dual-
line POTS and IP communicator with additional cellular options
available. 6808
The 6808 system can be enhanced by adding modules such as the The supports a variety of devices,including the
6860 remote annunciator which also has four programmable function 6860,5860,and 6855 remote annunciators,5824
buttons to help automate tasks and reduce time spent at the panel. serial parallel printer interface module(for printing
system reports),the 5496 NAC expander,5895XL
SWIFT"wireless compatibility provides options for wireless detection power module,and SK or SD devices.
through a Class A mesh network.It is ideal for hard-to-wire locations,
buildings where new wiring is not allowed,or to provide an easy install
fire system for new construction projects.SWIFT devices can be
combined with other hard-wired 6808 compatible devices.
The 6808 also has a form-C trouble relay,two programmable form-C
relays,along with powerful features such as drift compensation,pre-
trouble maintenance alert,a built-in sensor test to comply with NFPA 72
calibration testing requirements,and calibration trouble alert.
FEATURES 8 BENEFITS
• Capable of providing • Convenient • 6860 annunciator with • Programmable date • 125 software zones
up to 198 points to field--upgradeable a 4 x 40 large display setting for automatic and 125 output
satisfy smaller firmware and convenient groups for flexible
• Four user-
installation needs . guilt in dual path programmable buttons Daylight Saving Time design options
• Connect up to 17 POTS and IP minimize time spent changes
panels on one site with communications with executing complex or • Jump5tart'' auto
convenient single- optional cellular routine tasks programming reduces
point access using the models available for installation time
• Built in USB interface
SK-NIC Network reliable backup for convenient and
Interface Card. reporting quick programming
Connected panels can
have mixed compatible
FACP models
SIGNAL LINE CIRCUIT(SLC) PROGRAMMING ORDERING INFORMATION
The 6808 St-..0 loop supports multiple The 6808 system offers several options 6808:Addressable Fire Alarm
device types,maintenance alerts,and a to simplify and speed-up programming. Control Panel.(Red cabinet).
built-in sensor test to comply with NFPA JumpStart•auto programming
72 calibration testing requirements. minimizes programming required to start COMPATIBLE ANNUNCIATORS
a new system.The built-in keypad,or the 6860:4x40 LCD remote fire
INDICATOR LIGHTS 6860,5860 or 6855 remote annunciator(4 lines and up to
• General Alarm(Red):Flashes if in annunciators give you on site access to 160 characters)per system;four
alarm;solid when alarm is silenced current system programming. programmable buttons
• Supervisory(Yellow):Flashes if a Programming can also be accomplished 5860:4x20 LCD remote fire
supervisory condition exists;solid using the Windows'-based Honeywell annunciator.5860 is gray;5860R is red
when supervisory is silenced Fire Software Suite(HFSS)program. 6855:4x20 LCD remote fire
• System Troubles(Yellow):Flashes annunciator
SOFTWARE TOOLS
if a trouble condition exists; 5865-3 or 5865-4:LED annunciators
SKST:Silent Knight Selection Tool
solid when trouble is silenced can display up to 30 LEDs(15 red and
provides the installer or design architect 15 yellow).The 5865-4 has key switches
• System Silenced(Yellow): with a Windows'software system for silence and reset,and a system
On when an alarm,trouble or configuration tool to create a detailed Bill trouble LED.
supervisory condition has been of Material(BOM)and battery
silenced but not et cleared 5880:LED/10 module has 40
y calculations.
programmable LED outputs and eight
• System Power(Green):Flashes HFSS:Honeywell Fire Software Suite supervised dry contact inputs which are
for AC failure;solid when provides communication and panel
useful for custom applications.You can
power systems are normal programming,detector status,event use up to eight 5880 modules on one
history and additional data.Requires a USER INTERFACE control panel for maximum flexibility.
PC running Microsoft'Windows. Its compact size allows mounting inside
The 6808 built-in 4 x 20 annunciator
with 80 character LCD display ADDITIONAL INFORMATION the annunciator,or in an accessory
and large easy-to-use tactile Twisted-unshielded pair cabinet.
touchpad can be used for system wire is recommended.
6808 COMPATIBLE DEVICES AND
operation,programming and The 6808 also has 13 preset notification ACCESSORIES
maintenance.It has five LEDs for cadence patterns See the data sheets listed below for a
complete listing of the SK,SD or SWIFT
alarm,supervisory,system trouble,
(including ANSI 3.41). devices.
system silenced and system power. 53623:SK Devices Data Sheet
AGENCY LISTINGS AND APPROVALS J3624:SD Devices Data Sheet
System operations include silencing NPFA 13,NFPA 15,NFPA 16,NFPA 70,
350614,350616&350618:SWIFT
alarms and troubles,resetting alarms NFPA 72:Central station;remote wireless devices
and the display of alarm troubles and Signaling;Local Protective Signaling For a complete and current listing of
memory.The system's non-volatile Systems;Auxiliary Protected Premises compatible devices and accessories,visit
www.silentknight.com.
event history buffer stores 1,000 Unit;Water Deluge releasing service. Important:You cannot mix SK and SD
events for viewing from the built- Suitable for automatic,manual, devices in the same fire alarm system.
in or remote annunciator.System waterflow,sprinkler supervisory(DACT
operations can be initiated with a non-coded)signaling services
mechanical firefighter's key or a • UL Listed:S2766
valid 4-to 7-digit operator's code.
• CSFM:7165-0559:0502
• FONY:COA#6246
• FM approved
Page 2 of 4—351608:B 9/26/2018
SK COMPATIBLE ADDRESSABLE B200S-LF(-IV,-WH):Low-Frequency WS K-WGI:Wireless Gateway
DEVICES intelligent sounder base WSK-PHOTO:Wireless Photoelectric smoke
SK-ACCLIMATE:Multi criteria B200S-LF:Low-frequency intelligent detector
photoelectric smoke detector with thermal sounder base WSK-PHOTO-T:Wireless Multi-criteria
135°F fixed temperature B224RB(-IV,-WH):Relay base photoelectric smoke detector with thermal
SK-BEAM:Reflected beam smoke detector B224RB: Relay base detection(135°F fixed temperature)and
without test feature• B224g1(_IV,-WH):Isohtor base B5.1..OW 4°base
SK-BEAM-T:Reflected beam smoke g22461: Isolator base WSK-HEAT:Wireless Heat,(135°F fixed
detector with test feature temperature)and B510W 4"base
SK-CONTROL:Supervised control module SD COMPATIBLE ADDRESSABLE WSK-HEAT-ROR:Wireless heat,ROR
SK-CONTROL-6:Six circuit supervised DEVICES (135°F fixed temperature)and B510W 4"
control module SD505-6AB:Addressable 6°base base
SK-DUCT:Photoelectric duct smoke SD505-6IB:Addressable 6"short circuit WSK-MONITOR:Wireless monitor module
detector with extended air speed range isolator base WSK-RELAY:Wireless relay module
SK-FIRE-CO:Four criteria fire and carbon SD505-6RB:Addressable 6"relay base W-USB:SWIFT Tools USB transceiver used
monoxide detector SD505-6SB:Addressable 6'sounder base for communication with SWIFT devices
SK-HEAT:Fixed thermal detector(135°F) SD500-AIM:Addressable input module
SK-HEAT-W:Fixed thermal detector (switch input) SBUS ACCESSORIES
(135°F),white SD500-ANM:Addressable notification 5496:A 6 amp notification power expander
SK-HEAT-ROR:Fixed rate of rise detector module with four power-limited notification
(135°F) appliance circuit outputs.SD500-ARM: Addressable relay module
SK-HEAT-ROR-W:Fixed rate of rise SD505-DTS-K: Remote test switch and 5883:Relay Interface.Provides 10 Form C
detector(135°F),white LED indicator for the SD505-DUCTR relays.
SK-HEAT-HT:Fixed high temperature 5824:Serial/Parallel Printer Interface
SD505-DUCT:Addressable Duct Smoke
thermal detector(190°F)
Detector. Module for printer connection.
SK-HEAT-HT-W:Fixed high temperature 5895XL:Power Supply with six Flexput°
thermal detector(190°F),white SD505-DUCT
usin Addressable Duct circuits,and two Form C relays.Max.16 per
Detector housing with relay base.
SK-ISO:Fault isolator module system.
SD505-HEAT:Absolute temperature heat
SK-MINIMON:Mini monitor module detector.Trip point range from 5815RMK:Remote mounting kit.
SK-MONITOR:Monitor module 135°F-150°F(0°C-37°C). Dimensions:10 3/8"W x 10-3/16"H x 3"D
SK-MONITOR-2:Dual input monitor SD500-LIM:Addressable Line isolator COMMUNICATION OPTIONS
module module
SK-MON-10:10 input monitor module SD500-MIM:Addressable Mini input CELL-CAB Cellular communicator,
monitor module(switch input) metal enclosure with lock/key*
SK-PHOTO:Photoelectric smoke detector p CELL-MOD:Cellular communicator,plastic
SK-PHOTO-W:Photoelectric smoke SD505-PHOTO:Photoelectric smoke *
detector,white
detector enclosure
SK-PHOTO-T:Photoelectric smoke detector
SD500-PS/-PSDA:Addressable Single or *Sole path,powered by panel.
with thermal(135°F fixed temperature) dual action putt station IPGSM-4G:Dual path fire alarm
SD500-SDM:Addressable smoke detector communicator,cellular and/or IP(primary or
SK-PHOTO-T-W:Photoelectric smoke backup,selectable)
• detector with thermal(135°F fixed module
temperature),white SK-IP-2:Remote reporting via the Internet.
SK-PHOTOR:Photoelectric detector with AUDIBLE/VISIBLE DEVICES Requires a VisorAlarm''receiver at the central
remote test capability These AV devices are all 2-wire.Color:"R" station
SK-PHOTO-R-W:Photoelectric detector indicates red;"W"denotes white.For a MISC.ACCESSORIES
with remote test capability,white complete listing of Silent Knight AV devices
SK-NIC:Network Interface Card.Provides a
SK-PULL-SA:Addressable single action go to www.sitentknightcom. common communications link for the 6808.
pull station CHSRL/CHSWL:Wall chime/strobe
SK-PULL-DA:Addressable dual actionpull SK-NIC-KIT:Installation Accessory Kit
CHSCRL/CHSCWL:Ceiling chime/strobe SK-FML:Fiber-Optic Multi Mode,
station CHRL/CHWL:Wall chime
transmitter and receiver
SK-RELAY:Addressable relay module HRL/HWL:Wall horn
SK-RELAY-6:Addressable Six relaycontrol SK-FSL:Fiber Optic Single Mode
P2RL/P2WL:Wall horn/strobe RBB:Remote battery box accessory cabinet
module PC2RL/PC2WL:Ceiling horn/strobe for batteries that are too large to fit in the
SK-RELAYMON-2:Addressable Dual SRL/SWL:Wall strobe FACP cabinet.Dimensions:16"W x 10"H x
relay/monitor module
SK ZONE:Addressable zone interface SCRL/SCWL:Ceiling strobe 6"D(406mm W x2_54mm H x 152mm DI
' module SPSCRL/SPSCWL:Ceiling speaker/strobe SK-SCK:Seismic Compliance Kit used to
SK-ZONE-6:Six zone interface module SPSRL/SPSWL:Wall speaker/strobe securely fasten batteries to the fire panel.
B300-6(-IV):6"base for SK--W Series SPRL/SPWL:Wait speaker
B210LP:6"mounting base SPCRL/SPCWL:Ceiling speaker
B501(-BL,-IV,-WHITE):4°flangeless base
6501:4"Flangeless mounting base SWIFT WIRELESS DEVICES
8200S(-IV,-WH):Intelligent sounder base SWIFT is only compatible with System
B200S:Intelligent sounder base Sensor(SK)devices.It is not compatible
with Hochiki(SD)devices.
Page 3 of 4— 351608:8 9/26/2018
•
6808 Technical. Specifications
PHYSICAL NOTIFICATION APPLIANCE CIRCUITS(NACs) Flexpute,Honeywell",
Overall Dimensions:.16.36"W x 26.37"H x 3.91"D Four programmable circuits which can be JumpStart",Silent Knight',
programmed individually as: SWIFT'',and System
Shipping Weight:32 lbs. Sensor*are registered
Color:Red NACs:3A @ 27.4VDC per circuit,power-limited trademarks of Honeywell
(with a maximum current of 6A) International Inc.
ENVIRONMENTAL Auxiliary Power Circuits:3A @ 27.4VDC per circuit,
Hochiki*is a registered
Operating Temperature:32°F to 120°F (0°C to power--limited trademark of Hochiki
49°C) Corporation.Microsoft'
Humidity:0 to 93%relative humidity(non- Supports Class B(Style 4)and Class A(Style 6 or 7) and Windows`are
condensing) configuration for the SI...0 registered trademarks of
Microsoft Corporation.
ELECTRICAL WIRING:See the product manual for wiring details This document is not
6808 Primary AC:120 VAC 60Hz,3,3A Total intended to be used for
Accessory Load:6A G 27.4VDC power-limited installation purposes.We
StandbyCurrent:190mA try to keep our product
information up-to
Alarm Current:250mA date and accurate.We
Battery Charging Capacity:7 to 35AH cannot cover all specific
Battery Size:7A1-I to 18AH max.allowed in control applications or anticipate
all requirements.Ail
panel cabinet.Larger capacity batteries can be
specificationsare subject
housed in RBB accessory cabinet. to change without notice.
For Technical Support,call
800-446-6444.
Honeywell Silent Knight Honeywell
12 Clintonville Road .
Northford,CT 06472 SILENT`
351608 18 109/18
r 2018 Honeywell International Inc. t:HT
800 328 0103