Report (13) ' NAC EOL VOLTAGE g)S ./ / —. 10/ 0
CALCULATION � s�ok s7-
CAPITOL ELECTRIC CO., INC. i ` "" 1 ��
(503) 255-9488 Office
(503)255-1966 Fax
Job Name: Plaza West ( }; 1
Job Address: 9600 SW Oak Street Tigard, OR 97223t
Job Number: �p;i '—Conductor Wire Gauge I 14 I
Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) I 3.07 I
Date: 8/5/2016
Cable Length In Feet(source to end of line) I 191 I
Total Circuit Current I 0.476
Nominal System Voltage I 20.4
Panel Description: Notifier FCPS-24F Minimum Device Voltage I 16 I
Panel No.: NAC 4
Output No.: 4 Point To Point Method EOLv 19.96
Circuit Within Limits ? YES
NAC Devices Mfg By: System Sensor
Load Centering Method EOLv 20.12
Circuit Within Limits ? YES
Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At
No. Rating Current Previous Device Device
Feet)
1 Suite 400 Dental Lab SCR 15cd Stb, Ceiling, Wht 15 0.066 85 20.15
2 Suite 400 Dental Lab SCR 15cd Stb, Ceiling, Wht 15 0.066 25 20.09
3 Suite 400 Dental Lab SCR 15cd Stb, Ceiling, Wht 15 0.066 16 20.05
4 Suite 400 Dental Lab SCR 15cd Stb, Ceiling, Wht 15 0.066 19 20.02
5 Suite 400 Dental Lab PC2R 110cd H/S, Ceiling, Wht, H 110 0.212 46 19.96
6 19.96
7 -- 19.96
8 19.96
9 19.96
10 19.96
11 19.96
12 19.96
13 19.96
14 19.96
15 19.96
16 19.96
17 19.96
18 19.96
19 19.96
20
19.96
Plaza West, NAC 4, EOLv Calc NAC, 4 CKT (20.4V Nominal).xls OUTPUT 4
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503)255-9488 Office, (503) 255-1966 Fax
JOB NAME: Plaza West
ADDRESS: 9600 SW Oak Street Tigard,OR 97223 DATE: 8/5/16
PANEL DESCRIPTION: NAC 4 PREPARED BY:Shane Tercek
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
NAC EXTENDER ,
Notifier FCPS Power Supply 1 0.048 0.048 0.048 0.048
CIRCUIT#1 .� ._u_.F.
Estimated Load 1 ' ,� 1.5 1.500
0.000
0.000
.,._._.__._._._.._:- 0.000
0.000
�. .,,.... 0.000
0.000
r 0.000
��- 0.000
w , r �W* E # r =. e A TOTAL 1.500
CIRCUIT#2 _..
Estimated Load 1 1.5 1.500
0.000
0.000
� ,. 0.000
0.000
0.000
0.000
0.000
0.000
CIRCUIT#3 tx � , .
Estimated Load .1 1.5 1.500
0,000
0.000
[ .1- 0.000
� % 0.000
0.000
0.000
0.000
0.000
_x A TOTAL 1.500
2_,...,._
CIRCUIT#4 Suite 400-Dental Lab
PC2R 110cd H/S,Ceiling,Wht,Hi 1 0.212 0.212
SCR 15cd Stb,Ceiling,Red 4 ":;.; ' 0.066 0.264
- 1- 0.000
- E 0.000
0.000
0.000
0.000
0.000
0.000
, .n...a... ... �;:.,.w'"
TOTAL 0.476
Plaza West, NAC 4, Batt Calc Notifier FCPS-24 NAC Panel (20.4V Nominal).xls Page 1 of 2
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503) 255-9488 Office, (503)255-1966 Fax
JOB NAME: Plaza West
ADDRESS: 9600 SW Oak Street Tigard, OR 97223 DATE: 8/5/2016
PANEL DESCRIPTION: NAC 4 PREPARED BY:Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
AUXILIARY DEVICES '` ` ` .
0.000 0.000
0.000 0.000
0.000 0.000
TOTAL 0.000
STANDBY TOTAL CURRENT: 0.048
STANDBY HOURS: 24
STANDBY AMP HOURS: 1.152 NAC DEVICE CURRENT 4.976
ALARM TOTAL CURRENT: 5.024
ALARM MINUTES: 5
ALARM AMP HOURS: 0.419
TOTAL CALCULATED AMP HOURS 1.571
APPLIED SAFETY FACTOR 1.15
MINIMUM AMP HOURS REQURED 1.806
SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES
Plaza West, NAC 4, Batt Calc Notifier FCPS-24 NAC Panel (20.4V Nominal).xls Page 2 of 2
SYSTEM
SENSOR°
Selectable Output
Notification Devices
SpectrAlert Advance selectable-output horns,strobes,
and horn/strobes are rich with features guaranteed to
cut installation times and maximize profits.
SPECTR lert
The SpectrAlert Advance series of notification appliances is Features
designed to simplify your installations,with features such as:plug in plug-in design
designs,instant feedback messages to ensure correct installation of
individual devices,and eleven field-selectable candela settings for •Same mounting plate for wall-and ceiling-mount units
wall and ceiling strobes and horn/strobes. •Shorting spring on mounting plate for continuity check before
installation
More specifically,when installing Advance products,first attach a •Captive mounting screw
universal mounting plate to a four-inch square,four-inch octagon or
double-gang junction box.The two-wire mounting plate attaches to •Tamper resistance capability
a single-gang junction box, •Field selectable candela settings on wall and ceiling units:15,15/75,
30,75,95,110,115,135,150,177,185
Then,connect the notification appliance circuit wiring to the SEMS
terminals on the mounting plate. •Automatic selection of 12 or 24 volt operation at 15 and 15/75
candela
Finally,attach the horn,strobe or horn/strobe to the mounting plate Outdoor wall and ceiling products
by inserting the product's tabs in the mounting plate's grooves.The
device will rotate into position,locking the product's pins into the Outdoor products rated from—40°to 151°F
mounting plate's terminals.The device will temporarily hold in place •Minimal intrusion into the back box
with a catch until it is secured with a captured mounting screw. •Horn rated at 88+dbA at 16 volts
SpectrAlert Advance products allow you to choose:
•12 or 24 volts •Rotary switch for tone selection
•At 24 volts, 15,15/75,30,75,95, 110,115,135,150,177 or 185 •3 horn volume settings
candela by way of rear-mounted slide switch and front viewing
window •Electrically compatible with existing SpectrAlert products
•Horn tones and volume by way of rotary switch
The SpectrAlert Advance series includes outdoor notification Agency Listings
appliances.Outdoor strobes and horn/strobes(two wire and four
wire)are available for wall or ceiling.Outdoor horns are available for SIGNALING
MEA 7125-1653:186(indoor strobes)
wall only.All System Sensor outdoor products are rated between ® Q 7,25.1653187(outdoors1'obey)
7125-1653188(horn/strobes)
minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or LISTED APPROVED approved ''-
7125-1653 7125-1653:189(horns)
dry applications. 54011 3023572 MEA452-05-E
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance horns,strobes and horn/strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box or double-gang back box.
Two-wire products shall also mount to a single-gang 2 x 4 x 1k-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.
The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with the Sync•Circuit-
Module
ync•CircuitModule accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the
Sync•Circuit Module,12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts;24-volt rated notification appliance circuit
outputs shall operate between 17 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated
DC,or full-wave rectified,unfiltered power supply.Strobes and horn/strobes shall have field-selectable candela settings including 15,15/75,30,75,95,110,115,
135,150,177,185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be
wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at
1Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Horn/Strobe Combination
The horn/strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.
The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances,flashing at 1Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated
lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal(continuous)
pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on
horn/strobe models shall operate on a coded or non-coded power supply.
Outdoor Products
SpectrAlert Advance outdoor horns,strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151
degrees Fahrenheit.The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three-fourths inch conduit
entries.
Synchronization Module
The module shall be a System Sensor Sync•Circuit listed to UL 464 and shall be approved for fire protective service.The module shall synchronize
SpectrAlert strobes at 1Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn/strobe models over a
single pair of wires.The module shall mount to a 4516x 45X6 x 21§-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class
A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they
control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
K Series Operating Temperature -40°F to 151°F(-40°C to 66°C)
Humidity Range 10 to 93%non-condensing(indoor products)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWRI
Operating Voltage Rangel 8 to 17.5 V(12V nominal)or 16 to 33 V(24 nominal)
Input terminal wire gauge 12 to 18 AWG
Ceiling mount dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high)
Wall mount dimensions(including lens) 5.6"L x 4.71W x 2.5"D(142 mm L x 119 mm W x 64 mm D)
Horn dimensions 5.61 x 4,7'W x 1.3"D(142 mm L x 119 mm Wx33 mm D)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time varying power source that is used on some power supply and panel outputs.
2.P,5,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
A05-0395-002