Plans (23)[Page Too Large for OCR Processing]
a lp co S ti/ Oak 5 co FP5 Z4 I I- DO 12-Go
.
PLAZA WEST
SUITE 500
9600 SW OAK ST.
TIGARD, OR. 97223
ADDITIONS TO THE EXISTING FIRE
ALARM SYSTEM DATASHEETS &
CALCULATIONS
Prepared by
Fire Systems West, Inc.
600 SE Maritime Avenue Suite 300
Vancouver, WA 98661
(360) 693 -9906
Fire Systems West, Inc I I I I I Designer: Rick Pagel
600 SE Maritme Avenue #300 I I _ I 1 1
Vancouver, WAI98661 I I I I I I I I
(360) 693-9906
http: //www.firesytemswest.com I I I I I
This calculator provides voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering).
Make sure that you know what method is accepted b , and the results do not exceed the limits set by the respective jurisdiction
I I I I Point to Point Method End of Line Method Load Centering Method
Project Name I Plaza West Suite 500 CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS
Job Number I XXXX Date: 110/11/2011 .
Circuit Number ; 4 . I I Totals 1 Voltage Totals Voltage Totals Voltage
Area Covered I Suite 500 I Current Distance Drop Current Distance Drop Current Distance Drop
Nominal System Voltage 20.4 I 0.646 256 0.55 0.646 256 1.015 0.646. 256 0.508
Minimum Device Voltage 16 Wire Ohm's End of Line Voltage 19.85 End of Line Voltage 19.38 End of Line Voltage 19.89
Total Circuit Current 0.646 I Gauge Per 1000 Percent Drop_ 2.69% Percent Drop 4.98% Percent Drop 2.49%
Distance from source to 1st device 10 14 3.07 End of Line and Load Centering Methods use only the wire guage for the first device to source
Wire Gauge for balance of circuit 14 3.07 Standard Wire Resistance in Ohms per 1000 feet.
Voltage 18 =7.77 16 =4.89 14 =3.07 12 =1.98 10 =1.24
f I Current in amps. Distance 18 -14 Awg = Solid Conductors 12 -10 Awg = Stranded Conductors
150a = 150 ma from Notes:
Device I Device Candela Device previous . At Drop from Percent 1. Wire resistance doubled in calcs for two wires.( Pos and Neg)
Number Type Rating Current device Device source Drop
• Device 1 P2R 15cd 0.079 10 20.36 0.040 0.19% 2. P2R 15cd = 0.079
Device 2 SR 15cd 0.066 58 20.16 0.242 1.18%
Device 3 P2R, 15cd 0.079 10 20.13 0.272 1.34% 3. SR 15cd =.066
Device 4 SR . 15cd 0.066 25 20.06 0.337 1.65%
Device 5 SR 15cd 0.066 18 20.02 0.376 1.85%
Device 6 P2R 15cd 0.079 55 19.93 0.474 2.33%
Device 7 P2R 15cd 0.079 32 19.88 0.516 2.53%
Device 8 SR 15cd 0.066 33 19.86 0.543 2.66%
Device 9 SR ' 15cd 0.066 15 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
END 0.000 • 19.85 0.549 2.69%
END 0.000 19.85 0.549 2.69%
Totals I I I 0.646 I 256 I End of Line Voltage 1 19.85
*Th, SYSTEM 1 - . ,
� SE NSOR , :'�'; � 1
Indoor Selectable- Output T_ r
Horns, Strobes, and
Horn Strobes for Wall F . '
v.
Applications a
SpectrAlert* Advance audible visible notification
products are rich with features guaranteed to cut SPECTI lA 1 rt
A D V A N C E
installation times and maximize profits.
Features The SpectrAlert Advance series offers the most versatile and
• Plug -in design with minimal intrusion into the back box easy -to -use line of horns, strobes, and horn strobes in the industry.
Tamper resistant construction With white and red plastic housings, wall and ceiling mounting
• options, and plain and FIRE - printed devices, SpectrAlert Advance can
• Automatic selection of 12- or 24 -volt operation at 15 and 15/75 meet virtually any application requirement.
candela
• Field- selectable candela settings on wall units: 15, 15/75, 30, 75, 95, Like the entire SpectrAlert Advance product line, wall -mount horns,
110, 115, 135, 150, 177, and 185 strobes, and horn strobes include a variety of features that increase
• Horn rated at 88+ dBA at 16 volts their application versatility while simplifying installation. All devices
• Rotary switch for horn tone and three volume selections feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
• Universal mounting plate for wall units costly and time - consuming ground faults.
• Mounting plate shorting spring checks wiring continuity before
device installation To further simplify installation and protect devices from construction
• Electrically Compatible with legacy SpectrAlert devices damage, SpectrAlert Advance utilizes a universal mounting plate
Compatible with MDL sync module with an onboard shorting spring, so installers can test wiring
• continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field - selectable candela settings,
automatic selection of 12- or 24 -volt operation, and a rotary switch
for horn tones with three volume selections.
Agency Listings
T
SIGNALING OD
® MEA
riiii.1
LISTED APPROVED approved 7- 118: 0ndnnr s)
n 125 n- 16s3 mnm s ;runes.
54011 (chimes, ho,n strobes. horns) 3023572 .1/E5452 -05 -E Unme sn4bes)
55512 (suobes) 7135-1653189 Owns. :mes)
SpectrAlert Advance Specifications
Arch Specifications ' , - -
�. _ _ _ General . __ _._
• SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4 -inch octagon back box, or double -gang back
box. Two -wire products shall also mount to a single -gang 2 x 4 x 1' -inch back box. A universal mounting plate shall be used for mounting ceiling and
wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with
the Sync-Circuit" Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.
When used with the Sync-Circuit Module, 12- volt -rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24- volt -rated notification
appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit
from a regulated DC or full -wave rectified unfiltered power supply. Strobes and horn strobes shall have field - selectable candela settings including 15, 15/75, 30,
75, 95, 110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be
wired as a primary- signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at
1 I-Iz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and (JL 464 and shall be approved for fire protective service. The
horn strobe shall be wired as a primary - signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling
appliances, flashing at 1 Hr over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector
system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non - temporal (continuous) pattern. These
options are set by a multiple position switch. On four -wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models
shall operate on a coded or non -coded power supply.
Synchronization Module
The module shall be a System Sensor Sync-Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize
SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a
single pair of wires. The module shall mount to a 4 "/16 x 4 " /16 x 21/4-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z
(class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they
control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32 °F to 120 °F (0 °C to 49 "C)
Humidity Range 10 to 93% non- condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR'
•
Operating Voltage Ranger 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall -Mount Dimensions (including lens) 5.6 L x 4.7 "W x 2.5 - D (142 mm L x 119 mm W x 64 mm D)
Horn Dimensions 5.6'1 x 4.7"W x 1.3°D (142 mm L x 119 mm W x 33 mm D)
Wall -Mount Back Box Skirt Dimensions (BBS -2, BBSW -2) 5.9 - L x 5.0 - W x 2.2 (151 mm L x 128 mm W x 56 mm DI
Wall -Mount Trim Ring Dimensions (sold as a 5 pack) (TR -HS, TRW -HS) 5.7 L x 4.8 "W x 0.35°D (145 torn L x 122 torn W x 9 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non - regulated, time - varying power source that is used on some power supply and panel outputs.
2. P , 5, PC, and SC products will operate at 1 2 V nominal only for 1 S and 15/75 cd.
AVD:mcco
•
UL Current Draw Data
' UL M Strobe Current Draw (mA RMS) . - ' UL Max. Horn Current Draw (mA RMS) - ; . :
_ __ 8_17.5 Volts 16_33 Volts___._ _ _ .__ 8_17.5 Volts__.._j633 Volts _ -
Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR
Standard 15 123 128 66 71 Temporal High 57 55 69 75
Candela Range 15/75 142 148 77 81 - Temporal Medium 44 49 58 69
30 NA NA 94 96 Temporal Low 38 44 44 48
75 NA NA 158 153 Non - temporal High 57 56 69 75
95 NA NA 181 176 Non - temporal Medium 42 50 60 69
110 • NA NA 202 195 Non - temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
High 135 ' NA NA 228 207 Coded Medium 44 51 56 69
Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50
. 177 NA NA 281 251
185 NA NA 286 258
UL Max, Current Draw (mA RMS), 2 -Wire Horn Strobe, Standard Candela Range (15 -115 cd) . - . - '
8 -17:5 Volts . . ' 16-33 Volts
DC Input 15 15/75 15 15/75 '30 75 95 110 115
Temporal High 137 147 - 79 90 .107 • 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non Temporal High 141 152 91 100 116 176 201 221 229
Non Temporal Medium 133 145 75 85 102 163 187 207 216
•
Non Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input .
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
• Temporal Low 129 151 76 86 101 160 184 194 201
Non- Temporal High 142 161 103 112 126 181 203 221 229
Non- Temporal Medium 134 155 85 95 110 166 189 208 216
Non- Temporal Low 132 154 80 90 105 161 184 202 211
UL Max. Current Draw (mA RMS) 2 -Wire Horn Strobe, High Candela Range (135 -185 cd) .
16 -33 Volts 16 -33 Volts
DC Input 135 150 177 185 FWR Input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non - Temporal High 255 270 303 309 Non Temporal High 233 248 275 281
Non - Temporal Medium 242 2.59 293 2.99 Non - Temporal Medium 219 232 262 2.67
Non - Temporal Low 238 254 291 295 Non - Temporal Low 214 229 256 262
. Horn Tones and Sound O Data
• Horn and Horn Strobe Output (dBA) , . '. .
8 -17.5 - 16-33 24 -Volt Nominal
. Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR
• 1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal I.ow 71 73 76 76 83 80 94 89
4 Non- Temporal High 82 82 88 88 93 92 100 100
5 Non - Temporal Medium 78 78 85 85 90 90 98 98
6 Non- Temporal Low 75 75 81 81 88 84 96 92
7' Culled High 82 82 88 88 93 92 101 101
8' Coded Medium 78 78 85 85 90 90 97 98
9t Coded Low 75. 75 81 81 88 85 96 92
'Settings 7, 8, and 9 are not available on 2 -wire horn strobes.
AVD500000
SpectrAlert Advance Dimensions
4.7" .2.5 " - -- , 5:05" 2:231 — --
_■••■. eal NW POW ' .
1■ � a
5.6" 5.98
1111
m a C
•
I
0 a : C
Wall -mount horn strobes Wall back box skirt
•
SpectrAlert Advance Ordering Information
Model Description >;. Model Description
Wall Horn Strobes Horns
P2R`t 2 -Wire Horn Strobe, Standard cd', Red HR Horn, Red
P2RH" 2 -Wire Horn Strobe, High cd, Red I.IW Horn, White
P2• 2 -Wire Horn Strobe, Standard cd, White ' Accessories
P2WH" 2 -Wire Horn Strobe, High cd, White BBS -2 Back Box Skirt, Wall, Red
P4R' 4 -Wire Horn Strobe. Standard cd, Red BBSW -2 Back Box Skirt, Wall, White
P4RH 4 -Wire Horn Strobe, High cd, Red TR -HS Trim Ring, Wall, Red
P4W 4 -Wire Horn Strobe, Standard cd, White TRW -HS Trim Ring, Wall White
Wall Strobes
• SR"t Strobe, Standard cd, Red
. SRN" Strobe, High cd, Red
SW' Strobe, Standard cd, White
SWH• Strobe, High cd, White ,
Notes:
• Add • - P'to model number for plain housing (no 'FIRE' marking on cover), e.g.. P2R -P.
t Add "-SP' to model number for •FUEGO" marking on cover, e.g., P2R -SP.
.1r cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings.-High cd" refers to strobes that include 135, 150. 177, and 185 candela settings.
,� SYSTEM 62011 system sensor.
11 3825 Ohio Avenue • St. Charles, IL 60174 Products�neat�ss ttochange rtar�.v„ns„tem� soced„r,
�_ SENSOR' Phone: 800- SENSOR2 • Fax: 630-377-6495 ""•"t°oduct infermahon.inducing the latest venial d""s data sheet
Avostne00 •6n1 .`7807
•
•