Permit (73) CITY OF TIGARD FIRE PROTECTION SYSTEM PERMIT
C COMMUNITY DEVELOPMENT Permit #: FPS2013 -00029
•T IGARD 13125 SW Hall Blvd., Tigard OR 97223 503.718.2439 Date Issued: 03/05/2013
Parcel: 1 S135BD00100
Jurisdiction: Tigard
Site address: 9600 SW OAK ST 575
Project: Spec Space Subdivision: ASHBROOK FARM Lot: PTS 5 &
Project Description: Add (1) horn strobe
Contractor: SAFE TECHNOLOGY GROUP INC Owner: SUN LIFE ASSURANCE CO OF CANADA
6400 NE HWY 99 SUITE G375 BY NORRIS BEGGS & SIMPSON
VANCOUVER, WA 98665 121 SW MORRISON ST #200
PORTLAND, OR 97204
PHONE: 360 - 699 -2130 PHONE: 503 - 352 -8113
FAX: 360- 719 -1527
FEES
Description Date Amount
•
Specifics: Permit Fee - COM 03/05/2013 $69.92
12% State Surcharge - Building 03/05/2013 $8.39
Type of Use: COM Plan Review - Fire Life Safety - COM 02/28/2013 $27.97
Class of Work: ALT Type of Const: IIB Info Process /Archiving - Lg $2.00 (over 03/05/2013 $2.00
Occupancy Grp: B Height: ft 11x17)
Stories: 5 Houlry Building Rate 03/05/2013 $180.00
Hourly Building 12% State Surcharge 03/05/2013 $21.60
Commercial Sprinkler System:
Sprinkler Required: Sprinkler Type:
Standpipe Required: Hazard:
Density: 0 Design Area: 0
K Factor: 0
Commercial Fire Alarm System:
Fire Alarm Required: Yes Alarm Type: Automatic
Pull Station Required: Smoke Detectors Req:
Battery Calcs Provided: No Cut Sheets Required: No
Total $309.88
Valuations: Required Items and Reports (Conditions)
Sprinkler Valuation: $0.00
Residential Square Footage: 0
Fire Alarm Valuation: $1,200.00
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other
applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of
issuance, or if work is suspended for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon
Utility Notification Center. Those rules are set forth in OAR 952 - 001 -0010 through OAR 952 - 001 -0090. You may obtain a copy of the rules
or direct questions to OUNC by calling 503.232.1987 or 1.800.332.2344.
Issued By: Permittee Signature: An pd5.,„,r
Call 503.639.4175 by 7:00 a.m. for the next available inspection date.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
Building Permit Application
Fire Protection System RECEIVED
FoR cFl lcr uscoN f
a City of Tigard c� Received :2.' (
I N 13125 SW HaII Blvd. Tigard PermitNo.FP5 a013- loO�
, , OR 97223 FEB 2 8 2013 P Revte
°. Phone: 503.718.2439 Fax: 503.598.1 Date/By: i d �"J (,3 Other Permit: �/Z
TIGARD Inspection Line: 503.639.4175 OF TIGARD Date Ready/By: luri ec � SSee Page 2 for
Internet: www.tigard -or.gov BUILDING DIVISION Notified/Method: 2 5 (3 } Supplemental Information
' TYPE OF WORK �� L �� ' / EQUIRED DATA: 1- AND 2- FAMILY DWELLING
❑ New construction ❑ Demolition Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
® Addition/alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION
work indicated on this application.
❑ 1- and 2- family dwelling I ® Commercial /industrial Valuation: S
❑ Accessory building ❑ Multi - family Number of bedrooms:
❑ Master builder ❑ Other: Number of bathrooms:
JOB SITE INFORMATION AND LOCATION Total number of floors:
Job site address: 9600 SW OAK ST New dwelling area: square feet
City /State /ZIP: TIGARD OR 97223 Garage /carport area: square feet
/
Suite/bldg. /apt. no.: 575 Project name: --FF CE Jf D & j . SiCh/ Covered porch area: square feet
Cross street/directions to job site: PLAZA WEST Deck area: square feet
Other structure area: ~ square feet
REQUIRED DATA: COMMERCIAL -USE CHECKLIST
Subdivision: l Lot no.: Permit fees* are based on the value of the work performed.
Tax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
equipment, materials, labor, overhead, and the profit for the
DESCRIPTION OF WORK work indicated on this application.
ADD 1 HORN STROBE Valuation: $51,200.00
Existing building area: square feet
New building area: square feet
• ❑ PROPERTY OWNER ❑ TENANT Number of stories:
Name: Type of construction:
Address: Occupancy groups:
City /State /ZIP: Existing: B
Phone: ( ) Fax: ( )
New: B
® APPLICANT ❑ CONTACT PERSON • • •
NOTICE
Business name: SAFE TECHNOLOGY GROUP INC. All contractors and subcontractors are required to be
Contact name: JASON SWEET licensed with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: 6400 NE HWY 99 SUITE G375 jurisdiction in which work is being performed. If the
City /State /ZIP: VANCOUVER WA 98665 applicant is exempt from licensing, the following reasons
apply:
Phone: (360) 699 -2130 Fax: : (360) 719-1527 ',
E -mail: SALES @SAFETECHNOLOGY.NET
• . CONTRACTOR BUILDING PERMIT FEES* .
(Please refer to fee schedule)
Business name: SAFE TECHNOLOGY GROUP INC.
Permit fee:
Address: 6400 NE HWY 99 SUITE G375
City /State /ZIP: VANCOUVER WA 98665 State surcharge (12% of permit fee):
FLS plan review (40% of permit fee):
Phone: (360) 699-2130 , Fax: (360) 719 -1527 (Due upon application.)
a ,�
CCB lic.: 173731 ✓' I I< Total permit fees:
Authorized signature: ,� {C� Amount received:
,/ This permit application expires if a permit is not obtained
Print name: JASON SWEE Date: 2 -27 -13 within 180 days after it has been accepted as complete.
* Fee methodology set by Tri -County Building Industry
Service Board.
1: \ Building \Perm its \FPS- PermitApp, doc 02 /01/11 440- 4613T(I I /02/COM/WEB)
City of Tigard: Fire Protection Permit Checklist
Page 2 - Supplemental Information
Describe work to be done:
1.) ❑ New 2.) Modification to sprinkler heads only:
❑ Addition ❑ 1 -10 heads: No plan review required.
❑ Alteration ❑ 11+ heads: Plan review required.
❑ Repair
Number of sprinkler heads: _
Additional description of work:
T J. a of S stem Com • lete A, B, C or D as a . s licable :
A.) Commercial Sprinkler
❑ Wet ❑ Dry
Additional Standpipes
Information: Hazard Group
Density
Design Area
K. Factor
Sprinkler Project Valuation: $
B.) Type I - Hood Fire Suppression System
Hood Project Valuation: $
C.) Fire Alarm
Submittal shall Battery Calculations ❑ Yes
include: Individual Component ❑ Yes
Cut Sheets
Fire Alarm Project Valuation: $ 1200
D.) Residential Sprinkler (Stand Alone System)
Square Footage: Permit Fee:
0 to 2,000 $198.75
2,001 to 3,600 $246.45
3,601 to 7,200 $310.05
7,201 and greater $404.39
Sprinkler Project Square Footage: sq. ft.
Fire Protection Permit Fees
Project valuation subtotal (see A, B & C above): $
Permit fee based on project valuation (see fee schedule): $
Permit fee based on square footage (see D above): $
State Surcharge (12% of permit fee): $
FLS Plan Review (40% of permit fee): $
TOTAL: $
Plan review requires a completed application and 2 sets of plans at submittal. Plan review fees are required at submittal.
z: \SAFE \ Forms \Use these forms \Permit Apps \ Tigard \FPS- Pcrmiulpp.doc 02/01/112
S 2013- 00 sED 2c ?
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 -
FIRE ALARM SYSTEM
RECORD OF COMPLETION
I
Name of protected property: P GL Z. cit U? S 5 0 0 1 I L S 7S_
Address: 9 (0 0 u 5 t.l./ 011 %s\' /-
Representative of protected property (name/phone):
Authority having jurisdiction: � ,�"1 !A k I ivk
Address/telephone number: /31 O 2 S J 5 vu 1-6111"
Organization name/phone Representative name/phone
Installer Safe Technology Group 360- 699 -2130
Supplier Safe Technology Group 360 -699 -2130
Service organization Safe Technology Group 360- 699 -2130
Location of record (as- built) drawings: FACP
Location of operation and maintenance manuals: FACP
Location of test reports: Central Station
A contract for test and inspection in accordance with NFPA standard(s)
Contract No(s): Effective date: Expiration date:
System Software
(a) Operating system (executive) software revision level(s):
(b) Site - specific software revision date:
(c) Revision completed by:
(name) (firm)
1. Type(s) of System or Service
NFPA 72, Chapter 6 — Local
If alarm is transmitted to location(s) off premises, list where received:
NFPA 72, Chapter 8 — Remote Station
Telephone numbers of the organization receiving alarm:
Alarm:
Supervisory:
Trouble:
If alarms are retransmitted to public fire service communications centers or others, indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
NFPA 72, Chapter 8 — Proprietary
Telephone numbers of the organization receiving alarm:
Alarm:
Supervisory:
Trouble:
If alarms are retransmitted to public fire service communications centers or others, indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
K NFPA 72, Chapter 8 — Central Station
Prime contractor:
Central station location:
(NFPA 72, 1 of 4)
FIGURE 4.5.2.1 Record of Completion.
2002 Edition
72 - NATIONAL FIRE ALARM CODE
Means of transmission of signals from the protected premises to the central station:
McCulloh Multiplex One -way radio
X Digital alarm communicator Two -way radio Others
Means of transmission of alarms to the public fire service communications center:
(a)
(b)
System location:
NFPA 72, Chapter 9 — Auxiliary
Indicate type of connection: Local energy Shunt Parallel telephone
Location of telephone number for receipt of signals:
2. Record of System Installation
(Fill out after installation is complete and wiring is checked for opens, shorts, ground faults, and improper branching,
but prior to conducting operational acceptance tests.)
This system has been installed in accordance with the NFPA standards as shown below, was inspected by
on , includes the devices shown
in 5 and 6, and has been in service since
X NFPA 72, Chapters 1 2 3 7 l$ >$ 10 11 (circle all that apply)
K NFPA 70, National Electrical Code, Article 760
K Manufacturer's instructions
Other (specify):
Signed: /h01 Date: 3/4// 3
Organization: Saf e c ogy Group
3. Record of System Operation
Documentation in accordance with Inspection Testing Form, Figure 10.6.2.3, is attached
All operational features and functions of this system were tested by date
and found to be operating properly in accordance with the requirements of:
X NFPA 72, Chapters 1 2 3 4 5 6 7 8 9 g) 11 (circle all that apply)
X NFPA 70, National Electrical Code, Article 760
X Manufacturer's instructions
Other (specify):
Signed: Date: 3 /6//j
Organization: Safe ethnology Group
4. Signaling Line Circuits
Quantity and class of signaling line circuits connected to system (see NFPA 72, Table 6.6.1):
Quantity: Style: Class:
(NFPA 72, 2 of 4)
FIGURE 4.5.2.1 Continued
2002 Edition
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 -
5. Alarm- Initiating Devices and Circuits
Quantity and class of initiating device circuits (see NFPA 72, Table 6.5):
• Quantity: Style: Class:
MANUAL
(a) Manual stations Noncoded Transmitters Coded Addressable
(b) Combination manual fire alarm and guard's tour coded stations
AUTOMATIC
Coverage: Complete K Partial
Selective Nonrequired
(a) Smoke detectors Ion Photo Addressable
(b) Duct detectors Ion Photo Addressable
(c) Heat detectors FT RR FT/RR RC Addressable
(d) Sprinkler waterflow indicators: Transmitters Noncoded Coded Addressable
(e) The alarm verification feature is disabled or enabled , changed from seconds to seconds.
(f) Other (list):
6. Supervisory Signal Initiating Devices and Circuits (use blanks to indicate quantity of devices)
GUARD'S TOUR
(a) Coded stations
(b) Noncoded stations
(c) Compulsory guard's tour system comprised of transmitter stations and intermediate stations
Note: Combination devices are recorded under 5(b), Manual, and 6(a), Guard's Tour.
SPRINKLER SYSTEM
Check if provided
(a) Valve supervisory switches
(b) Building temperature points
(c) Site water temperature points
(d) Site water supply level points
Electric fire pump:
(e) Fire pump power
(f) Fire pump running
(g) Phase reversal
Engine -driven fire pump:
(h) Selector in auto position
(i) Engine or control panel trouble
(j) Fire pump running
ENGINE- DRIVEN GENERATOR:
(a) Selector in auto position
(b) Control panel trouble
(c) Transfer switches
(d) Engine running
Other supervisory function(s) (specify):
(NFPA 72, 3 of 4)
FIGURE 4.5.2.1 Continued
2002 Edition
72 -34 NATIONAL FIRE ALARM CODE
7. Annunciator(s)
Number: Type: Location:
8. Alarm Notification Appliances and Circuits
NFPA 72, Chapter 6 — Emergency Voice/Alarm Service
Quantity of voice /alarm channels: Single: Multiple:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in system:
Quantity and the class of notification appliance circuits connected to system (see NFPA 72, Table 6.7):
Quantity: Style: Class:
Types and quantities of notification appliances installed:
(a) Bells With Visible
(b) Speakers With Visible
(c) Horns With Visible f
(d) Chimes With Visible
(e) Other: With Visible
(f) Visible appliances without audible:
9. System Power Supplies
(a) Fire Alarm Control Panel: Nominal voltage: 120VAC Current rating:
Overcurrent protection: Type: Breaker Current rating: 20A
Location:
(b) Secondary (standby):
Storage battery: 2 Amp -hour rating:
Calculated capacity to drive system, in hours: 24
Engine -driven generator dedicated to fire alarm system:
Location of fuel storage:
(c) Emergency system used as backup to primary power supply:
Emergency system described in NFPA 70, Article 700:
10. Comments
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standard(s):
System deviations from the referenced NFPA standard(s) are:
(signed) for installs • cont (title) ( a te)
(signed) for alarm service company (title) (date)
(signed) for central station (title) (date)
Upon completign if th . sys : • (s) satisfactory test(s) witnessed (if required by the authority ha jng ju 'sdiction):
N ' _ ,� ►/ ��5 Lker 3 Il j I3
(signed) representa ve having jurisdiction title) ( ( ate)
• 'ec,fr ( ((J-- (NFPA 72, 4 of 4)
FIGURE 4.5.2.1 Continued
2002 Edition