COMBINATION
OUTDOOR HEATING
AND AIR
CONDITIONING UNIT
EQUIPPED WITH INTERMITTENT IGNITION
RRGG- SERIES
;,_;; ;„ �•--F` Heats with gas, cools with electricity, provides year-
;".�":1? -- :" round heating and cooling from one compact unit.
fy� ` . .
•= a COMPACT because all components are housed in a
single cabinet. The combination unit is completely
wired—with color coded wire—and factory assem-
bled. The units are completely dehydrated, charged
and tested before leaving the factory. Minimum field
work need be done—just connect the ducts, electri-
cal-gas supply and thermostat.
• CERTIFIED PERFORMANCE The design is certified
by the American Gas Association and Canadian Gas
Association for natural and L.P. (propane) gases. All
models carry the Air Conditioning and Refrigeration
Institute seal of certified capacity.
r
RRGG— SERIES
Cooling Capacities 19,000 to 60,000 BTU/HR --
[5.57 to 17.58 kW] c-o.
Heating Input Rates from 50,000 to 150,000 BTU/HR TIE Oieem S 71311'
[14.65 to 43.96 kW] DIFFERENCE /n$1die
\ler J
General Data
_on
0 Air RRNL Series
NOMINAL SIZES 2-5 TONS [7.0-17.6 kW] Nte
Model RRNL-Series B048JK10(E/X) CO6OCK10 CO60DK10 C06OJK10(E/X)
Cooling Performance)
Gross Cooling Capacity Btu[kW] 50,000 114.65] 59,500[17.43] 59,500 117.431 59,500[17.43]
EER/SEER2 11.2/13 10.5/13 10.5/13 10.5/13
Nominal CFM/AHRI Rated CFM[L/sj 1600/1600 1755,/7551 2000/1850[944/873] 2000/1850[944/873] 1900/1850[897/873]
AHRI Net Cooling Capacity Btu[kW] 48,000[14.061 57,500[16.85] 57,500[16.85] 57,500[16.85]
Net Sensible Capacity Btu[kW] 33,990[9.96] 40,460[11.85] 40,460[11.85] 40,460[11.85]
Net Latent Capacity Btu[kW] 14,010[4.1] 17,040[4.99] 17,040[4.99] 17,040[4.99]
Net System Power[kW] 4.28 5.48 5.48 5.48
Heating Performance(Package Gas/Electric)3
Heating Input Btu[kW] 100,000[29.3] 100,000[29.3] 100,000[29.3] 100,000[29.3]
Heating Output Btu[kW] 77,000[22.56] 81,000[23.73] 81,000[23.73] 77,000[22.56]
Temperature Rise Range°F[`C] 45-85 125/47.2] 45-85[25/47.2] 45-85[25-47.2] 45-85[25/47.2]
AFUE(%)4 80 80 80 80
Steady State Efficiency(%) 81 81 81 81
No.Burners 5 5 5 5
No.Stages 1 1 1 1
Gas Connection Pipe Size in.[mm] 0.5[12.7] 0.5[12.7] 0.5[12.7] 0.5[12.7]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating(dB)5 78 78 79 78
Outdoor Coil-Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in.[mm]OD 0.375[9.5] 0.375[9.5] 0.375[9.5] 0.375[9.5]
Face Area sq.ft.[sq.m] 16.23[1.51] 16.23[1.51] 16.23[1.51] 16.23[1.51]
Rows/FPI[FPcm] 2/22[9] 2/22[9] 2/22[9] 2/22[9]
Indoor Coil-Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in.[mm] 0.375[9.5] 0.375[9.5] 0.375[9.5] 0.375[9.51
Face Area sq.ft.[sq.m] 7.39[0.69] 7.39[0.69] 7.39[0.69] 7.39[0.69]
Rows/FPI[FPcm] 2/15[6] 2/15[6] 2/15[6] 2/15[6]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in.[mm] 1/0.75[19.05] 1/0.75[19.05] 1/0.75[19.05] 1/0.75[19.05]
Outdoor Fan-Type Propeller Propeller Propeller Propeller
No.Used/Diameter in.[mm] 1/22[558.8] 1/22[558.8] 1/22[558.8] 1/22[558.8]
Drive Type/No.Speeds Direct/1 Direct/1 Direct/ Direct/1
CFM[Us] 3300[1557] 3300[1557] 3400[1604] 3300[1557]
No.Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan-Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No.Used/Diameter in.[mm] 1/10x9[254x229] 1/12x9[305x2291 1/12x9[305x229] 1/12x9[305x229]
Drive Type/No.Speeds Direct/3 Direct/3 Direct/3 Direct/3
No.Motors 1 1 1 1
Motor HP 3/4 1 1 1
Motor RPM 1075 1075 1075 1075
Motor Frame Size 48 48 48 48
Filter-Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No
(No.)Size Recommended in.[mmj (1)1x24x24[25x610x610] (1)1x24x30 125x610x762] (1)1x24x30[25x610x762] (1)1x24x30[25x610x762]
Refrigerant Charge Oz.[gl 161.2[4570] 172.8[4899] 172.8[4899] 172.8[4899]
Weights MO
Net Weight lbs.[kg] 471 [214] 532[241] 564[256]
Ship Weight lbs.[kg] 511 [232] 577[262] 573[260]
See Page 29 for Notes. [ ]Designates Metric Conversions
INTEGRATED AIR&WATER 15
Unit Dimensions
c
\,..„,./...e p� 157.9 mm\ S
r' X` E •\�\
/� UTSI
D �.
OUTSIDE SIOE
IRETUR ��
2"Is' DUCT � =�.
OPENING. -\
• /
OUTSIDE INSIDE INSIDE�.� \_'•T OK"�fM: \
� 71x• \`
iur mmH ouc / \\
sortor aanvir
/,j{/ INSIDE
I / INSIDE` /
4.1.• (TYP.ALL
1120.7 mm) AA 07
T
INSIDE \ W • BLOWER
\/ INSIDE ACCESS
PANEL
H"
6VSt 'F•aPJ PP\� ',
\ �' JY� EP Gf�
t�
\\ •fe, e`OG,5 �(556rmmI
23116• �4I ' �Je
� fl/P 1155.6 mm) `:i• -
LIQUID PRESSURE SERVICE PORT 'i CONDENSER
SUCTION PRESSURE SERVICE PORT �� M DRAIN
CONNECTION
POWER WIRE ENTRANCE (�/a'119.05 mml NPT)FEMALE
[ ]Designates Metric Conversions CONTROL WIRE K L
ENTRANCE TRANCE N
441 J
-3..f 4.,e:MODEL NU.MBEII 99ref•e -. ».-
"
DIM. 87 ��i7�g �. .- -ma worst
I a .1 - y-,- OIE19 B4E37' �i� n_. $,:•r-,its
'QfE25 - � - •'_ ;; 15E19 - $4r1 '05E37 rNBE43 306649-s:09E61
INCHES - A�111t!`oisor '07N4S'' 87N49 hil. '' , 6•:-•7'815E25 -0¢E31 07E37 19E43 •. 11E49".;1.1E11: - . • MODEL•: 05119'" 05EJ1:-'•_05N37 17E43..z."_ x17649,-!;-.10E61
(mow] .., .5N2r-"•O7E')iI.1T1177i VII-..18E43".::.;: 12E49 . 2E61 : NUMBER 04E25 45014'O6f;17., `i.17N43.``V• ..07N49 10161.•
NEN 09E31:''00137: 8116 3 13E49,%13t31 • ' NFU- -` •-_05E25 r16E31.:QTE37. 19E4.7�u .ttE49 -a1Eb1
'.'17E25 .g?' 10E31's 11F3 12673. 15E411.••15E61 : 'v''.ft7N37 10Ef3 12E49-..-.121:61•
[794] 31/ • 06E25 09E31. .09E37 11E43:. �13E49:1:13E61'
A 31'/4" 14" [794] 311/4" [794] 34'/4" [870; `.87E25 10E31 10E37 ..=12E43'• .15E49- '15E61
B 491/4" (1251] 50" [1270] 511/Ts" (12971 553.15" [1432] -
C 3713/6" [960] 43'/2" [1105] 491/2" )1257] 53" [1473' ACCESSORY MODEL NUMBER
D 131111s" [348] 16445" 421] 21'/,5" ;535] 12+-?/-s" [630]
E 1713/18' (452] 205/e" 5241 22•/e" '5E2] 2617s" [683] Roofcurb full Perimeter RXRA OB20_ RXRA 0821 RXRA DB22 RXRA 0823
F 1511/6" [398] 15"N" 398] 15''11" ;398] 17''/46" [449] Roofcurb-Sloped RXPA-CA20 RXPA-CA21 RXPA-CA22 RXPA-CA23
B 16" [4061 16" 406) 16" [406] 18" [457] Economizer-Modulatin g RXPE-C820 RXPE-C621 RXPE-CB22 RXPE-C823
H 14%2" [356] 167/8" 429] 2ilS" [543] 25'/e" [638] Economizer-2 Position RXPE-CC20 RXPE-CC20 RXPE-CC20 RXPE-CC23
I 181h2" [458] 207h" 530) 221/4" [568] 27W [689] .
J 177/6 [443] 213/6" 543] 26'/6" [664] 303/4" [772] Concentric Diffuser
K 151/" [394] 197/6' 494] 24'/4" [616] 281h" [724] and Grille RXRN-B014 RXRN-B015 RXRN-B015 RXRN-B1.116
l 283/46" [719] 293/6" 741] 305h6" [770) 323/4' [832] Pressure Relief Damper — — — RXRP-A23
M 101A" [260] 101/4" 260] 10'14" [261] 135/6" [338] - ~
N 33/46- [87] 37h6" [87] 33/4' [95] 53/45' [132] Manual Fresh Air Damper RXRF-EA20 RXRF-EA21 RXRF-EA22 RXRF-FA23
T 48'/4" [1226] 49" [1245] 50'/6' [1272] 543/" [1381] Rectangular to Round
W 364/1" [929] 42'/4" [1073] 48'/4" 11226] 563/4" [14411 Transitions RXMC-A01 RXMC-A02 RXMC-A03 RXMC-A04
X 13/4" (35] 1318" [35) 13/" [35] 13/" [351 Downflow Filter Package' RXRY-B20 RXRY-B21 RXRY-822 RXRY-B23
4 'Filters are included.
48ES—A
Comfort' 13 SEER Single—Packaged Air Conditioner
and Gas Furnace System with Puron® (R-410A) CCarrie�
Refrigerant
Single and Three Phase turn to the experts
2 to 5 Nominal Tons (Sizes 24-60)
Product Data
Innovative Unit Base Design
tl at �>j1 On the inside a high-tech composite material will not rust and
( J, incorporates a sloped drain pan which improves drainage and helps
inhibit mold,algae and bacterial growth.On the outside metal base
,,1•114114 44\
11 rails provide added stability as well as easier handling and rigging.
=`===_ Convertible duct configuration
\ 1_=_____ Unit is designed for use in either downflow or horizontal
applications. Each unit is converted from horizontal to downflow
and includes horizontal duct covers. Downflow operation is
provided in the field to allow vertical ductwork connections. The
basepan seals on the bottom openings to ensure a positive seal in
the vertical airflow mode.
Efficient operation High-efficiency design offers SEER
0. — o (Seasonal Energy Efficiency Ratios) of up to 13.5 and AFUE
(Annual Fuel Utilization Efficiency)ratings as high as 80.4%.
III..
` c�/ t' Energy-saving,direct spark ignition saves gas by operating only
when the room thermostat calls for heating. Standard units are
O furnished with natural gas controls. A low-cost field installed kit
Ii for propane conversion is available for all units.
A09034 48ESN units are dedicated Low NOx units designed for
Fig.1- Unit 48ES-A California installations. These models meet the California
maximum oxides of nitrogen (NOx) emissions requirement of 40
nanograms/joule or less as shipped from the factory and MUST be
Single-Packaged Products with Energy-Saving Features and installed in California Air Quality Management Districts and
Puron®refrigerant. wherever a Low NOx rule exists.
• Up to 13.5 SEER Durable, dependable components Compressors are designed
• Up to 80.4%AFUE for high efficiency.Each compressor is hermetically sealed against
• Factory-Installed TXV contamination to help promote longer life and dependable
• ECM Motor-Standard operation. Each compressor also has vibration isolation to provide
• Direct Spark Ignition
quieter operation.All compressors have internal high pressure and
• Low Sound Levels overcurrent protection.
Monoport inshot burners produce precise air-to-gas mixture,
• Dehumidification Feature which provides for clean and efficient combustion. The large
FEATURES/BENEFITS monoport on the inshot(or injection type)burners seldom, if ever,
One-piece heating and cooling units with low sound levels, easy requires cleaning.All gas furnace components are accessible in one
installation,low maintenance,and dependable performance. compartment.
Puron Environmentally Sound Refrigerant is Carrier's unique Tub-tubular" heat exchangers are constructed of aluminized
refrigerant designed to help protect the environment. Puron is an steel for corrosion resistance and optimum heat transfer for
HFC refrigerant which does not contain chlorine that can harm the improved efficiency.The tubular design permits hot gases to make
ozone layer. Puron refrigerant is in service in millions of systems, multiple passes across the path of the supply air.
proving highly reliable,environmentally sound performance. In addition,dimples located on the heat exchanger walls force the
Easy Installation hot gases to stay in close contact with the walls, improving heat
Factory-assembled package is a compact, fully self-contained, transfer.
combination gas heating/electric cooling unit that is prewired, ECM Motor is standard on all 48ES-A models.
pre-piped, and pre-charged for minimum installation expense. Direct-drive PSC (Permanent Split Capacitor) condenser-fan
These units are available in a variety of standard and optional motors are designed to help reduce energy consumption and
heating/ cooling size combinations with voltage options to meet provide for cooing operation down to 40°F (4.4°C) outdoor
residential and light commercial requirements. Units are temperature. Motormaster® H low ambient kit is available as a
• lightweight and install easily on a rooftop or at ground level.The field-installed accessory.
high tech composite base eliminates rust problems associated with Thermostatic Expansion Valve - A hard shutoff, balance port
ground level applications. TXV maintains a constant superheat at the evaporator exit(cooling
cycle)resulting in higher overall system efficiency.
1
AHRI* CAPACITIES
New vnt Cr
Cooling Capacities and Efficiencies
UNIT 48ES-A NOMINAL TONS STANDARD CFM NET COOLING EER", SEERt
CAPACITIES(Btuh)
24 2 800 23,000 11.0 13.2
30 2-1/2 1000 28,400 11.2 13.5
36 3 1200 34,400 11.0 13.0
42 3-1/2 1400 40,500 11.2 13.2
48 _ 4 1600 46,500 _ 11.2 13.2
--3 60 5 1750 57,000 11.0 13.4
LEGEND Notes:
dB-Sound Levels(decibels) 1. Ratings are net values,reflecting the effects of circulating fan heat.
db-Dry Bulb Ratings are based on:
SEER-Seasonal Energy Efficiency Ratio Cooling Standard:80°F(26.7°C)db,67°F wb(19.4°C)indoor entering-air
wb-Wet Bulb temperature and 95°F db(35°C)outdoor entering-air temperature.
COP-Coefficient of Performance 2. Before purchasing this appliance,read important energy cost and effi-
*Air Conditioning,Heating&Refrigeration Institute. ciency information available from your retailer.
< **At"A conditions-80°F(26.7°C)indoor db/67°F(19.4°C)indoor wb&
I 95°F(35°C) outdoor db.
Cr, 1-Rated in accordance with U.S.Government DOE Department of Energy)
Ill
o, test procedures and/or AHRI Standards 210/240.
Gas Heating Capacities and Efficiencies
UNIT 48ES-A HEATING INPUT(Btuh) OUTPUT CAPACITY TEMPERATURE RISE AFUE(%)
(Btuh) RANGE°F(°C)
3004 40,000 32,000 (16.7-33.3) 80.0
24060 - 48,000 - - 80.0
30060 48,000 25-55 80.0
36060 48,000 (13.9-30.6) 80.0
42060 47,000 78.5
36090 72,000 79.3
42090 73,000 35-65 80.4
48090 90000 73,000 (19.4-36.1) 80.4
60090 73,000 80.4
48115 30-60
60115 115,000 93,000 (16.7-33.3)
80.3
• 60130 30,000 103,000 (19.4-36.1) 78.9
LEGEND J
AFUE-Annual Fuel Utilization Efficiency
NOTE:Before purchasing this appliance,read important energy cost and efficiency information available from your retailer.
A-Weighted Sound Power Level (dBA)
UNIT 48ES-A STANDARD TYPICAL OCTAVE BAND SPECTRUM(dBA without tone adjustment)
RATING dBA 125 250 300 1000 2000 4000 8000
24---30 78 66.0 66.0 70.5 71.5 67.5 62.5 58.5
30---30/50 75 66.0 6:15 68.0 68.5 67.5 61.5 55.0
36---30/50/60 75 84.0 63.5 68.0 70.5 64.5 81.0 61.0
42 30/50/60 77 67.0 V.0 69.5 70.5 68.0 65.5 61.0
48---30/50/60 78 71.5 68.5 73.0 71.5 68.0 64.0 57.0
60---30/50/60 78 74.5 66.5 70.0 70.0 66.5 64.0 57.0
* Tested in accordance with AHRI Standard 70(not ltaied'n
4
PHYSICAL DATA (CONT) Nawt 0 N. r-r k
UNIT SIZE 48090 48115 48190 80090 80118 80190
NOMINAL CAPACITY(ton) 4 4 4 5 5 _ 5
NOMINAL HEATING INPUT(Btu/ht) 90,000 115,000 130,000 90,000 115,000 130,000
SHIPPING WEIGHT**lb - 428 428 - 428 450 450 - 450
SHIPPING WEIGHT**kg 194 194 194 204 204 204
COMPRESSORS Scroll
Quantity
REFRIGERANT(R-410A)
Quantity lb 8.4 8.4 8.4 10.0 10.0 10.0
Quantity(kg.) 2.9 2.9 2.9 4.5 4.5 4Z
REFRIGERANT METERING DEVICE TXV
OUTDOOR COIL
Rows...Fils/in. 1..21 1..21 1...21 2...21 2...21 2...21
Face Area(sq ft) 15.5 15.5 15.5 15.5 15.5 15.5
OUTDOOR FAN
Nominal Cfm 4000 4000 4000 3200 3200 3200
Diameter in. 26 26 26 26 26 26
Diameter(mm) 660.4 660.4 660.4 660.4 660.4 660.4
Q Motor Hp(Rpm) 1/5(810) 1/5(810) 1/5(810) 1/5(810) 1/5(810) 1/5(810)
I INDOOR COIL
0 Rows...Fins/in. 3...17 3...17 3...17 3...17 3...17 3...17
W Face Area(sq ft) 4.7 4.7 4.7 5.7 5.7 5.7
V00 INDOOR BLOWER -
Nominal Cooling Airflow(Cfm) 1600 1800 1600 1750 1750 1750
Size in. 11x10 11x10 11x10 11x10 11x10 11x10
Size(mm) 279.4x254 279.4x254 279.4x254 279.4x254 279.4x254 279.4x254
Motor HP(RPM) 1.0(1075) 1.0(1075) 1.0(1075) 1.0(1040) 1.0(1040) 1.0(1040)
FURNACE SECTION*
Burner Orifice No.
Natural Gas Qty...Drill Size(Factory Installed) 3..28 3...33 3...31 3...38 3...33 3...31
Propane Gas 3...53 3...51 3...49 3...53 3...51 3...49
HIGH-PRESSURE SWITCH 650+/-15
(psig)Cut-out Reset(Auto) 420+/-25
LOSS-OF-CHARGE/LOW-PRESSURE 20+/-5
SWITCH(Liquid Line)(psig)cut-out Reset 45+/-10
(auto)
RETURN-AIR FILTERS Throwaway ft in. 24x36x1
(mm) 610x914x25
*Based on altitude of 0 to 2000 ft(0-610 m).
t Required fitter sizes shown are based on the larger of the AHRI(Air Conditioning,Heating and Refrigeration Institute)rated cooling airflow or the heating
airflow velocity of 300 ft/minute for throwaway type.Air fitter pressure drop for non-standard filters must not exceed 0.08 IN.W.C.
$if using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
"For 460 volt units,add 14 lbs(6.35 kg)to the shipping weight.
6
f
48ES-A
C
13.15/71 11.15/11 LMl7 ELECTRICAL UNIT WT, UNIT NE1441 I4(30 CENTER or GRAVITY 1N/NN
1361,07 1354,01 _ CNARACTE RIXT1CS tO 46 'A• X v 2 •4
/8E3(-IN)0421060/0967131570 206/230-1, 208(230-3.60 411 186.5 44.3/4 1137 )2.13/16 571.4 16 151,2 11-116 435.0
3.7/11 13-9/14 46E3(•/N)6421060/016760 460.3-60 425 1021 44.3/4 1137 22.13/16 579,4 16 457.2 11-118 435.D Q
187431 13/1.51 16(31-/N1A461090/115/130)13/570 206/230-1, 206/230.3.60 119 190.2 16.3/1 1187 22.17/11 5T l.1 16 157,2 17-310 441.7
illr 18[31-IN1A/61090/115!7!0)10 460-3.60 433 191.5 44.3/4 1187 22.13/16 576.4 16 451.2 11-3/6 441.3
2.13/11 RETURN SUPPLY 4815/-)NIA{0(090/115/1)0)13/370 2061231.1, 208/230-3-60• X200.1 46•311 1187 22.13116 379.1 16 157.2 11.518 441.7
171.11 ® 44051-IN1A{01090/175/13071D 490.3.10 ®201.5 44-3/4 1187 22.13/14 571.4 16 457.2 77-5/8 147.7 rn
qss - rte' UNITS VOLTAGE ,1,
CORNEA WEIGHT L3/AC !w
AM OPTIONAL j / l OPTIONAL 4/ES1•/N1442(06D/090)(3/S10 208/235 41.7_28.0 82.2 37,3 123.4 54.0 143.9/5.5 OY(
f101.s :- AIR 481544 _ r SUPPLY 11 14[31-/N)A421001/200)10 460 61.2 28.0 62.2 37.3 112.1 60.1 118.1 81.8
lY OPENING / L ENIMG 11 46(81•//4)44610101115/131113/510 206/230 62.9 20.1,63.8 16.1 125.8.57.1 141.7 61.1 Z
, \, Il 48(51-//4)4461090/115/130140 460 82.9 21,6 63.0 38.1 134.6 61.2 151,1 64.8 Cl)U q//i�i \\\,\,` II 46131-/NIA60(0P0/f 13/130117/510 208/230 56.2 30.0 66.2 40.1 132.1 40.1 154.4 70.1 V�
�s'r /BEd)-IN)A601190/115/111110 160 _16.2 30.0 482 40.1 141.1 61.2 151.1 12.1 1
II j'!n r�l/%
ARROW MECHANICAL CONTRACTORS, INC.
10330 S.W. TUALATIN RD.
TUALATIN, OREGON 97062
PHONE: (503)692-1565
FAX: (503)691-1879
DESIGN OF HVAC BASE UNITS CONNECTION
TO MANUFACTURED ROOF CURB
DESIGN CRITERIA:
• SEISMIC USE GROUP: I OR II
• SEISMIC DESIGN CATEGORY: D,E, OR F
• HEAVIEST UNIT TOTAL WEIGHT: WP = 1600#
TOTAL LATERAL FORCE (USING ASCE 7-02 9.6.1.3)
F, _ 0.4apSDSWPIP 1+2 z
Fp RP(1.4) h
ap =1.0
SDS =1.0(max)
WP = 1600#
IP = 1.0
RP=2.5
z = UNIT ATTACHMENT POINT IN STRUCTURE ABOVE BASE
h =ROOF HEIGHT ABOVE BASE
z
—=1.0 FOR ROOF TOP HVAC UNITS
h
Fp _ (0.4)(1.0)(1.0)(1600)(1.0) (1+2(1.0))
2.5 (1.4)
Fp =549#
CHECK,
FpMnv = 0.3 SDS WPIP4
Fpm =(0.3)(1.0)(1600)(1.0)1 44 =343# <549# OK
USE 549#
ARROW MECHANICAL CONTRACTORS, INC.
10330 S.W. TUALATIN RD.
TUALATIN, OREGON 97062
PHONE: (503)692-1565
FAX: (503)691-1879
OVERTURNING ON UNITS:
_ 3.5'
1.5' MIN.
MIN.
4. Wp= 1600ff
Fp=549#
G.C.
2.0'
MAX.
L
END VIEW HVAC UNIT
DIMENSION REQUIREMENTS
MOT =(Fp)(Vert.Dist.to Center of Gravity)_(549)(2.0)=1098 FT-LBS
MR=(Wp)(Reduction for Load Combination)(Least Horiz.Dist.to Center of Gravity)=(1600)(0.9X1.5)=2160 FT-LBS
MR>MOT .'.TENSION AND UPLIFT CONNECTION NOT REQUIRED DESIGN FOR SHEAR ONLY.
r i (4)#10 SCREWS BASE UNIT(20 GA)
\ AT LOCATIONS SHOWN
A A
-I (4)#10 SCREWS
� M.;. I
L VY , INACCESSIBLE 16 GA CURB
AREA, CONDENSER
COIL END
PLAN VIEW DETAIL A-A
SCREW DESIGN: 4" �
r 44-AN
549 ,r�"� �~ E�` 611\
V(ACTUAL) _ = 137#/SCREW 11 '23
4 SCREWS
V(ALLOWABLE)=177#/SCREW IN 20 GA MATERIAL(REF :ER -4943P) 4i" C GO
177#>137# OK ti ��. .y�us,�. ����
..,,.tY �ii�la��rr%'✓
USE (4) #10 SCREWS