2010 Oregon Solar Installation Specialty Code
Check List for Prescriptive Installation of Roof-Mounted
PhotoVoltaic Solar Panel System
Property Information
Installation Address: 15745 SW Highland Ct
City: Tigard, OR Zip:97224
Owner's Name: Gary Heintz Date: 4/20/23
Contractor's Name: Green Ridge Solar CCB #: 210450
Design Parameters of the Property/Structure
If"Yes", does not
Flood Hazard Is the installation ❑ Yes qualify for the
Area Located in a flood prescriptive path, follow
plain/flood way? ® No OSSC or ORSC for
design requirements.
Wind Exposure Is the wind exposure ® Yes If"Yes", qualifies for
"C" or less? ❑ No the prescriptive path.
Installations on detached Is the Ground Snow
single/two-family Load 70 psf or less?
dwelling/single/two- If"Yes", qualifies for
family townhomes ® Yes the prescriptive path.
Ground ❑
Snow Load
21
If"Yes", qualifies for
Is the construction
material wood and does Yes
Type of If"Yes", qualifies for
the construction qualify
Construction as "conventional light ❑ No the prescriptive path.
frame" construction?
Is the spacing 24 inches
or less?
Pre-engineered trusses. ® Yes If"Yes", qualifies for
the prescriptive path.
❑ No
Roof framing
members Is the spacing 24 inches
or less?
Nominal lumber. If"Yes", qualifies for
® Yes the prescriptive path.
❑ No
Is the combined weight ® Yes
of the PV modules and If"Yes", qualifies for
racking less than or ❑ No the prescriptive path.
Solar equal to 4.5 psf?
installation Is the solar installation
21
layout in accordance Yes
with Section 305.4(3) of If"Yes", qualifies for
Elthe 2010 Oregon Solar No the prescriptive path.
Code?
❑ Metal
Single layer If roofing material is
Roofing Check the type of ❑ of wood one of the three types
material roofing material shingle/shake checked, qualifies for
Max. two layers the prescriptive path.
® of composition
Connections of
the solar assembly If"Yes", qualifies for
to the roof ❑
❑ Yes If"Yes",
Is the gauge 26 or less? qualifies for
❑ No the prescriptive path.
115 lbs for 60 inch
spacing or less?
If"Yes", qualifies for
❑ Yes the prescriptive path.
❑ No
Minimum Uplift rating
of Clamps? 75 lbs for 48 inches
spacing or less?
If"Yes", qualifies for
❑ Yes the prescriptive path.
❑ No
Attachment of
roof mounted If the spacing falls
solar systems Spacing of clamps? Minimum 24 inches
within 24 inches and 60
directly to inches inches,qualifies for the
Maximum 60 inches
standing seam prescriptive path.
metal panels Width of roofing If the width of the panel
panels? 18 inches or less is less than 18 inches,
inches qualifies for the
prescriptive path.
Minimum #10 at 24
inches o/c?
Size and spacing of If"Yes", qualifies for
fastener? ❑ Yes the prescriptive path.
❑ No
Is the roof decking of
WSP min. 1/2"thickness, ❑ Yes
decking connected to If"Yes", qualifies for
framing members ❑ No the prescriptive path.
w/min. 8d nails @
6"/12"o/c?
Height of the If"Yes", qualifies for
solar modules
•
Submittal Documents required for Prescriptive Installations
Show the location of the PV system in relation to buildings, structures,
property lines, and,as applicable, flood hazard areas.
Site Plan Details must be clear and easy to read.
Minimum size of the plan is 8.5 x 11 inches.
Attach a simple structural plan showing the roof framing(rafter size, type, and
spacing) and PV module system racking attachment.
System must be shown in sufficient detail and clarity to assess whether it
Structural Plan meets the prescriptive construction requirements as listed earlier above in the
matrix.
Minimum size of the plan is 8.5 x 11 inches.
PV Modules
Manufacturer:SEG Solar
Model Number:SEG-400-BMD-HV
Listing Agency:UL
4
C/Bui Iding/Forms/Photovoltaic-Checkl ist02-01-11.docx