A4COMcheck Software Version 4.1.5.3 (
i nftInterior Lighting Compliance Certificate
Project Information BIAP2o21 — OOZgp
Energy Code: 90.1 (2016)Standard
Project Title: Credena Mail Order Pharmacy �376 SVJ DIA ILA ANA C
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
7374 SW Durham Rd Jim Knees Lauren Laskarris
Portland,OR 97224 PKA Architects Mazzetti
6969 SW Hampton St 121 SW Salmon Street,Suite 1000
Portland, OR 97223 Portland, OR 97204
503-968-6800 503-620-3232
Jim@pkaarchitects.com Iaskarris@mazzetti.com
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Common Space Types:Conference/Meeting/Multipurpose 930 1.07 995
2-Hallways 160,170,Main Street(Common Space Types:Corridor/Transition<8 ft 2131 0.66 1406
wide)
3-IT,Boiler(Common Space Types:Electrical/Mechanical) 124 0.43 53
4-Common Space Types:Loading Dock 800 0.43 344
5-Lounge 130,140,Lact(Common Space Types:Lounge/Breakroom) 1490 0.62 924
6-161/2/3/7(Common Space Types:Office-Enclosed):Exempt
7-Patient Support Center(Common Space Types:Office-Open Plan) 4661 0.81 3775
8-Common Space Types:Restrooms 428 0.85 364
9-Manufacturing:Low Bay(<25ft.Floor to Ceiling Height) 7429 0.96 7132
10-Consult(Healthcare Facility:Exam/Treatment) 83 1.68 139
11-Common Space Types:Lobby-General 317 1.00 317
Total Allowed Watts= 15450
Area Category Exemption Qualifications
Connected Watts Total#Watts
Activity Area
Pre-Alt. Repl./Added Pre-Alt. Post-Alt
161/2/3/7(Common Space Types:Office-Enclosed 406 317 10 317.000 308.000
Exemption:Less than 20%connected lighting watts replacement.
Proposed Interior Lighting Power
A B C D E
Fixture ID: Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Common Space Tyoes:Conference/Meeting/Multipurpose(930 salt.)
LED 12:L8:ROUND LED DOWNLIGHT:Other: 1 14 11 154
LED 10:L6-32':FIXED LED COVE LIGHT:Other: 1 1 144 144
Hallways 160,170. Main Street(Common Space Types:Corridor/Transition<8 ft wide 2131 sq.ft.)
LED 17:L13:RELOCATED EXISTING 2X2:Other: 1 9 32 285
LED 1:L1:CYLINDER LED PENDANT:Other: 1 12 11 132
LED 4:L3-5':MONDO LED CIRCLES:Other: 1 1 99 99
Project Title: Credena Mail Order Pharmacy Report date: 11/11/21
Data filename: M:\Portland\Projects\21\215-014-Providence Credena Pharmacy Distribution\03 Page 1 of 6
Disciplines\Elec\Calcs\ComCheck Form\Credena.cck
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Waft.
LED 5:L3-6':MONDO LED CIRCLES:Other: 1 1 116 116
LED 6:L3-8':MONDO LED CIRCLES:Other: 1 1 156 156
LED 7:L4:CURVE DIRECT LED:Other: 1 1 315 315
LED 8:L5:LINEAR DIRECT LED:Other: 1 1 136 136
LED 14:L10:LED LINEAR DIRECT:Other: 1 3 13 39
IT. Boiler(Common Space Types:Electrical/Mechanical 124 sq.ft.)
LED 15:L11:LED LINEAR STRIP:Other: 1 2 20 41
Common Space Types:Loading Dock(800 sq.ft.)
LED 13:L9:LED IP RATED HIGH BAY:Other: 1 4 83 332
Lounge 130.140. Lact(Common Space Types:Lounge/Breakroom 1490 sq.ft.)
LED 1:L1:CYLINDER LED PENDANT:Other: 1 24 11 264
LED 4:L3-5':MONDO LED CIRCLES:Other: 1 3 99 297
LED 5:L3-6':MONDO LED CIRCLES:Other: 1 1 116 116
LED 9:L6-15':FIXED LED COVE LIGHT:Other: 1 1 68 68
LED 12:L8:ROUND LED DOWNLIGHT:Other: 1 2 11 22
LED 16:L12:ROUND LED DOWNLIGHT:Other: 1 8 6 48
161/2/3/7(Common Space Types:Office-Enclosed 406 sat.): Exempt
LED 17:L13:RELOCATED EXISTING 2X2:Other: 1 4 32 127
LED 12:L8:ROUND LED DOWNLIGHT:Other: 1 2 11 22
Patient Support Center(Common Space Types:Office-Open Plan 4661 sq.ft.)
LED 1:L1:CYLINDER LED PENDANT:Other: 1 31 11 341
LED 2:L2:LINEAR DIRECT LED PENDANT:Other: 1 39 19 757
Common Space Types:Restrooms(428 sq.ft.)
LED 11:L7:LED REFLECTION MIRROR:Other: 1 8 18 141
LED 12:L8:ROUND LED DOWNLIGHT:Other: 1 8 11 88
Manufacturing:Low Bay(<25ft. Floor to Ceiling Height)(7429 sq.ft.)
LED 13:L9:LED IP RATED HIGH BAY:Other: 1 40 83 3320
Consult(Healthcare Facility:Exam/Treatment 83 sq.ft.)
LED 12:L8:ROUND LED DOWNLIGHT:Other: 1 2 11 22
Common Space Types:Lobby-General(317 sq.ft.)
LED 3:L2A:LINEAR DIRECT LED PENDANT:Other: 1 4 13 52
Total Proposed Watts= 7485
Interior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications,and other calculations submitted with this permit application.The proposed interior lighting
systems have been designed to meet the 90.1 (2016)Standard requirements in COMcheck Version 4.1.5.3 and to comply with
any applicable mandatory requirements listed in the Inspection Checklist.
Lauren Laskarris - Electrical Designer ,,{ 'v 11/11/2021
Name-Title Si ature f Date
J
Project Title: Credena Mail Order Pharmacy Report date: 11/11/21
Data filename: M:\Portland\Projects\21\215-014-Providence Credena Pharmacy Distribution\03 Page 2 of 6
Disciplines\Elec\Calcs\ComCheck Form\Credena.cck
eiCOMcheck SoftwareChecklist Version 4.1.5.3
Inspection
Energy Code: 90.1 (2016) Standard
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
&Req.ID
4.2.2, :Plans, specifications,and/or ;❑Complies 'Requirement will be met.
8.4.1.1, ;calculations provide all information ❑Does Not
8.4.1.2, ;with which compliance can be Location on plans/spec:E5.1.01, E6.1.01
8.7 determined for the electrical systems Not Observable
tPR612 'and equipment and document where ❑Not Applicable
;exceptions are claimed. Feeder
;connectors sized in accordance with
,approved plans and branch circuits
sized for maximum drop of 3%.
4.2.2, ;Plans,specifications,and/or DComplies Requirement will be met.
9.4.3,9.7 calculations provide all information ❑Does Not
[PRO with which compliance can be Location on plans/spec: E0.1.02, E4.1.01, E6.1.01
determined for the interior lighting Not Observable
and electrical systems and equipment :❑Not Applicable
and document where exceptions to
the standard are claimed.Information
provided should include interior
;lighting power calculations,wattage of
bulbs and ballasts,transformers and
!control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Credena Mail Order Pharmacy Report date: 11/11/21
Data filename: M:\Portland\Projects\21\215-014-Providence Credena Pharmacy Distribution\03 Page 3 of 6
Disciplines\Elec\Calcs\ComCheck Form\Credena.cck
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
&Req.ID
8.4.2 ;At least 50%of all 125 volt 15-and ;❑Complies ;Requirement will be met.
[EL10]2 20-Amp receptacles are controlled by DDoes Not
:an automatic control device. Location on plans/spec: E3.1.01
❑Not Observable
❑Not Applicable
8.4.3 New buildings have electrical energy ❑Complies Exception: Requirement does not apply.
[EL11]2 use measurement devices installed. ❑Does Not
Where tenant spaces exist,each
tenant is monitored separately. In ❑Not Observable
buildings with a digital control system ❑Not Applicable
;the energy use is transmitted to to
;control system and displayed
;graphically.
9.4.1.1 ;Automatic control requirements ❑Complies Requirement will be met.
[EL?]2` prescribed in Table 9.6.1,for the DDoes Not
appropriate space type,are installed. Location on plans/spec: E0.1.02, E4.1.01
Mandatory lighting controls(labeled Not Observable
❑
:as'REQ')and optional choice controls ❑Not Applicable
(labeled as'ADD1'and 'ADD2')are
implemented.
9.4.1.1 :Independent lighting controls installed ;❑Complies :Requirement will be met.
[EL2]2 ;per approved lighting plans and all ,DDoes Not
manual controls readily accessible and Location on plans/spec: E0.1.02, E4.1.01
;visible to occupants. ❑Not Observable
❑Not Applicable
9.4.1.1f Daylight areas under skylights and ❑Complies Exception:Requirement does not apply.
[EL13]1 roof monitors that have more than DDoes Not
150 W combined input power for
;general lighting are controlled by ❑Not Observable'
photocontrols. ❑Not Applicable
9.4.1.3 Separate lighting control devices for ❑Complies Requirement will be met.
[EL4]1 ;specific uses installed per approved ODoes Not
lighting plans. Location on plans/spec:E0.1.02, E4.1.01
i❑Not Observable
❑Not Applicable
9.6.2 Additional interior lighting power ❑Complies 'Requirement will be met.
[EL8]1 allowed for special functions per the DDoes Not
approved lighting plans and is Location on plans/spec: E0.1.02, E4.1.01
automatically controlled and ❑Not Observable
;separated from general lighting. ;❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Credena Mail Order Pharmacy Report date: 11/11/21
Data filename: M:\Portland\Projects\21\215-014-Providence Credena Pharmacy Distribution\03 Page 4 of 6
Disciplines\Elec\Calcs\ComCheck Form\Credena.cck
Section
# Final Inspection Complies? Comments/Assumptions
&Req.ID
8.7.1 ;Furnished as-built drawings for Requirement will be met.
[FI16]3 ;electric power systems within 30 days DDoes Not
of system acceptance. ❑Not Observable
❑Not Applicable
8.7.2 Furnished O&M instructions for ❑Complies Requirement will be met.
[F117]3 ,systems and equipment to the ODoes Not
building owner or designated
representative. ❑Not Observable;
❑Not Applicable
9.2.2.3 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[FI18]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans,demonstrating proposed watts ❑Not Observable
:are less than or equal to allowed ;❑Not Applicable
watts.
9.4.4 At least 75%of all permanently DComplies Exception:Requirement does not apply.
[F120]1 installed lighting fixtures in dwelling ❑Does Not
units have >= 55 Im/W efficacy or a ❑Not Observable Location on plans/spec:E0.1.02, E4.1.01
>=45 Im/W total luminaire efficacy.
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Credena Mail Order Pharmacy Report date: 11/11/21
Data filename: M:\Portland\Projects\21\215-014-Providence Credena Pharmacy Distribution\03 Page 5 of 6
Disciplines\Elec\Calcs\ComCheck Form\Credena.cck