Special Inspection
FINAL SUMMARY LETTER
June 9,2021
Job#: T1701930.0
City of Tigard
13125 SW Hall Blvd
Tigard,OR 97223-8199
Attn: Building Division
Re: Project Name: 10BP122-PACTRUST VOLUNTARY SEISMIC UPGRADE-BLDG 4
Address: 16332 SW 72n0 Avenue-Tigard,OR
Permit#: BUP2018-00224 b 6 P 12 3
Per Chapter 17,Section 1704.1.2 of the International Building Code(IBC),we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship,provisions of the State Building Code and Standards,as well as the structural engineer's design changes,approvals and
verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any.type.
Even with diligent construction monitoring and testing, construction defects, aeflciencies or omissions in the contractors work may
exist. II is the contractor's responsibility to perform their work in accordance with the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods.
techniques,sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or welfare.
Information contained herein is not to be reproduced. except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING NC.
Leac
Project Manager
SUmrm
cc: PACTRUST-JOHN WIITALA
CITY OF TIGARD BUILDING DIVISION-WALTER'CHIP'BARNETT
MARVIN&SONS CONSTRUCTION INC-BOB MARVIN
P:1ProjectslGeneraf\20171T17010300106-09-21 Final Letter.doc Updated 11/30/11
Bend Office (541)330-9155
Geotechnical Office (503)601-8250
Carlson Testing, Inc. Eugene Office (541)345-0289
Salem Office (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
June 9,2021
Job#: T1701930.M
City of Tigard
13125 SW Hall Blvd
Tigard,OR 97223-8199
Attn: Building Division
Re: Project Name: 10BP112-PACTRUST VOLUNTARY SEISMIC UPGRADE-BLDG 15
Address: 15870 SW Upper Boones Ferry Road-Tigard,OR
Permit#: BUP2018-00019
oby 112.
Per Chapter 17, Section 1704.1,2 of the International Building Code(IBC),we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
Structural Steel(Shop Only)
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship,provisions of the State Building Code and Standards,as well as the structural engineer's design changes,approvals and
verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce The risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any type.
Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's work may
exist. It is the contractor's responsibility to perform their work in accordance with the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques,sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING INC.
to a Leach
Project Manager
SL/mrm
cc: PACTRUST-JOHN WIITALA
CITY OF TIGARD BUILDING DIVISION-WALTER'CHIP'BARNETT
MHP STRUCTURAL ENGINEERS-ERIC SERKES
MARVIN&SONS CONSTRUCTION INC -BOB MARVIN
P:\Projects\Genera112017\T1701830M\06-09-21 Final Letter.doc Updated 11/30/11
`J t 1 Bend Office (541)330-9155
A1. 50 M MR I Geotechnical Office (503)60I-8250
Carlson Testing, Inc. 4AZ Eugene Office (541)34s-0289
Salem Office (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
November 6, 2018
Job# T 1701930.J
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn Budding Division
Re Project Name PBPA143- Pactrust Voluntary Seismic Upgrade -Building 6
Address 16460 SW 72°'Avenue-Tigard, OR
Permit to BUP2018-00146
Per Chapter 17, Section 1704 1 2 cf the International Building Code(IBC).we have performed special inspection of the following
item(s) per our inspection reports oily
Adhesive Anchors
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship, provisions of the State Building Code and Standards as well as the structural engineer's design changes,approvals and
verbal instructions
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose dunng and after construction. Our services do not constitute a warranty or guarantee of any type.
Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's work may
exist. It is the contractor's responsibility to perform their work in accordance with the approved construction documents
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact Our reports pertain to the material tested/inspected only
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means methods.
techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING INC.
Steveh W Leach
Project Manager
SWUks
cc Pactrust-John Wiitala
MHP Structural Engineers-Eric 8erkes
Marvin& sons Construction Inc-Bob Marvin
P\ProectsGeneral'F;n.al letter Forms\New Final Letter Tempiates`:City of Tigard doc Updated 11I30111
Bend Office (541)330-9155
Gentechnlcal Office (503)601.8250
Carlson Testing, Inc. Eugene
gomee (541)345-0289
(503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
June 9,2021
Job#: 71701930.T
City of Tigard
13125 SW Hall Blvd
Tigard,OR 97223-8199
Attn: Building Division
Re: Project Name: OBP3-PACTRUST VOLUNTARY SEISMIC UPGRADE-BUILDING A
Address: 15951-15999 SW 724O Avenue-Tigard,OR
Permit#: BUP2020-00249 3 o b P 219
Per Chapter 17,Section 1704.1.2 of the International Building Code(IBC),we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship,provisions of the State Building Code and Standards,as well as the structural engineer's design changes,approvals and
verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any type.
Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's work may
exist. it is the contractor's responsibility to perform their work in accordance with the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques,sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING INC.
7 St lea
Project Manager
SUmrm
cc: PACTRUST-JOHN WIITALA
CITY OF TIGARD BUILDING DIVISION-WALTER'CHIP'BARNETT
MARVIN&SONS CONSTRUCTION INC-BOB MARVIN
P\Projects\Genera1120i71T1701930T\06-09.21 Final Letter.doc Updated 11/30/11
Date April 19, 2018
Job z. T1701930 H
Page 2 of 2
CTI s services did not include responsibilities related to determining, supervising, implementing or controlling the means,
methods, techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to
health. safety or welfare.
Information contained herein is riot to be reproduced, except in full, without prior authorization from this office. If there are
further questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING INC
vi
-Ste n W L eh—
Project Manager
SWUjng
cc Pactrust -John Wiitala IOMNMAPACTRUST,Cc$
Clackamas Co Building Codes Division 6ioSEaVICEPco CLACKAMAS Ok US
MHP Structrual Engineers - Eric Berkey E6EBr[Sp$lPSE•CE
Marvin & Sons Construction Inc- Bob Marvin MARVINAND50N5a(UNLA51 NET
Bend Office (541)330-9155
Geotechnicd Office (503)601-8250
Carlson Testing, Inc. Salem Office
(541)345-0209
Salem Office (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
June 9,2021
Job#. T1701930.0
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn: Building Division
Re: Project Name. PBC190- PACTRUST VOLUNTARY SEISMIC UPGRADE- SUITE 900
Address: 7204 SW Durham Road-Tigard,OR
Permit#i: 8UP2017-00218
Per Chapter 17,Section 1704,1.2 of the International Building Code(IBC),we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship,provisions of the State Building Code and Standards,as well as the structural engineer's design changes,approvals and
verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any type.
Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's work may
exist. It is the contractor's responsibility to perform their work in accordance with the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact. Our reports pertain to the material tested/inspected only
CTI's services did not include responsibilities related to determining, supervising implementing or controlling the means, methods,
techniques,sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office,
Respectfully submitted,
CARLSON TEST NG INC.
t eLe h
Project Manager
SUmrm
cc: PACTRUST-JOHN WIITALA
CITY OF TIGARD BUILDING DIVISION-WALTER'CHIP'BARNETT
MHP STRUCTURAL ENGINEERS -ERIC BERKES
P 1ProjectstGenerati2017\T1701930D\06.09-21 Final Letter.doc Updated 11/30/11
trf3P11S
J M M � Bend Office (,541)330-9155
Ei r- PA- 5 Geotechnical Office (503)6U1-f1250
Carlson Testing, Inc.Inc � Z Eugene Office (541)345-0289
Salem Office (503)589.1252
Tigard Off-ice (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
November 6, 2018
Job# T 1701930.J
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn Building Division
Re. Project Name. PBPA143- Pactrust Voluntary Seismic Upgrade-Budding 6
Address 16480 SW 72""Avenue-Tigard, OR
Permit 4t BUP2018-00146
Per Chapter 17.Section 1704 1.2 of the International Building Code(IBC),we have performed special inspection of the following
item(s) per our inspection reports only
Adhesive Anchors
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders end applicable
workmanship, provisions of the State Building Code and Standards as well as the structural engineer's design changes,approvals and
verbal instructions
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects.
deficiencies or omissions that arose dunng and after construction Our services do not constitute a warranty or guarantee of any type
Even with diligent construction monitonng and testing, construction defects. deficiencies or omissions in the contractor's work may
exist. It is the contractor's responsibility to perform their work in accordance with the approved construction documents
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact Our reports pertain to the material tested/inspected only
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to health, safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted.
CARLSON TESTING INC.
Steven W Leach
Project Manager
SWUks
cc: Pactrust-John Wiitala
MHP Structural Engineers-Eric Berkes
Marvin& sons Construction Inc-Bob Marvin
P\Pro ects\General1Frnat letter FormstNew Final Letter Templates\C iy of Tigard doc Updated 11/30(11
Bend Office (541)330-9155
Geotechnical Office (503)601-8250
Carlson Testing, Inc. Eugene Office (541)345-0189
Salem Office (503)589-1152
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
June 9, 2021
Job#: T1701930.P
City of Tigard
13125 SW Hat Blvd
Tigard,OR 97223-8199
Attn: Building Division
Re: Project Name: OBP1 -PACTRUST VOLUNTARY SEISMIC UPGRADE-BLDG 1
Address: 16120 SW 72n4 Avenue-Tigard.OR
Permit#: BUP2017-00202
Per Chapter 17,Section 1704.1.2 of the International Building Code(IBC),we have performed special inspection of the following
items)per our inspection reports only:
Adhesive Anchors
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship, provisions of the State Building Code and Standards,as well as the structural engineer's design changes,approvals and
verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any type.
Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's work may
exist. It is the contractor's responsibility to perform their work in accordance with the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact. Our reports pertain to the material tested/inspected only
CTl's services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques,sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING INC.
eLe
reject Manager
SLimrrn
cc: PACTRUST-JOHN WIITALA
CITY OF TIGARD BUILDING DIVISION-WALTER'CHIP'BARNETT
MARVIN&SONS CONSTRUCTION INC -BOB MARVIN
P.Projects\Generalt20171T1701930Pi06-09-21 Final Letter.cuc Updated 11/30/11
Bend Office (541)330-9155
c:eotechnical Office (503)601-8250
Carlson Testing, Inc. Salem
Office
(541)345-0289
Salem UlTiee (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
June 9,2021
Job#: T1701930
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn: Building Division
Re; Project Name: 1OBP128-PACTRUST VOLUNTARY SEISMIC UPGRADE- BUILDING 18
Address: 16100 SW 72nd Avenue-Tigard, OR
Permit#: BUP2017-00122
Per Chapter 17,Section 1704.1.2 of the International Building Code(IBC),we have performed special inspection of the following
item(s)per our inspection reports only;
Adhesive Anchors
Structural Steel(Shop Only)
All requested inspections and tests were performed and reported according to the requirements of project documents and to the best of
our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and applicable
workmanship, provisions of the State Building Code and Standards,as well as the structural engineers design changes.approvals and
verbal instructions.
:Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any type.
Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's work may
exist. It is the contractor's responsibility to perform their work in accordance with the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by members
of its profession in the same locale. Statements made in our reports are based on technical judgments and should not be construed to
be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques,sequences or procedures of the construction or evaluating or reporting job conditions related to health, safety or welfare,
Information contained herein is not to be reproduced, except in full, without prior authonzation from this office. If there are further
questions regaroing this matter please Do not hesitate to contact tnls ofce.
Respectfully submitted,
CARLSON TESTI G INC.
eac
Project Manager
SL/mrm
cc: PACTRUST-JOHN W IITALA
CITY OF TIGARD BUILDING DIVISION-WALTER'CHIP'BARNETT
MHP STRUCTURAL ENGINEERS -ERIC BERKES
P:1Projects\Genera112017\T1 70 1 930106-09.21 Final Letter.doc Updated 11/30/11
Bend Office (541)330-9155
Geetechnical Office (503)6014250
Carlson Testing, ugene Office (541)345-0284
Inc.• Salem Office (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
Date: August 31,2017
Job#: T1701930.A
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn: Building Division
Re: Project Name: 10BP126-PacTrust Voluntary Seismic Upgrade-Building 14
Address: 16100 SW 72id Ave-Tigard, OR
Permit#: BUP2017-00222& BUP2017-00197
Per Chapter 17, Section 1704.1.2 of the International Building Code(IBC), we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
The non-compliance (NC) items recorded for each of the above inspection categories, as listed on the non-compliance report,
have been either repaired and re-inspected by CTI for compliance or reviewed and accepted by the engineer of record for the
project in the"As-Built Condition'or through an RFI
The issuance of this final report is based on the engineer's acceptance of the NC items not specifically re-inspected by CTI. CTI
did not provide any additional review or re-inspection of those items beyond the inspections that initially generated each of these
individual items on the non-compliance list. The engineer of record has provided the acceptance of the non-compliance items
and as-built conditions.
All requested inspections and tests were performed and reported according to the requirements of project documents and to the
best of our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and
applicable workmanship, provisions of the State Building Code and Standards, as well as the structural engineer's design
changes, approvals and verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any
type. Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's
work may exist. It is the contractor's responsibility to perform their work in accordance with the approved construction
documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by
members of its profession in the same locale. Statements made in our reports are based on technical judgments and should not
be construed to be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
ens services did not include responsibilities related to determining,supervising, implementing or controlling the means, methods,
techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or
welfare.
Information contained herein is not to be reproduced. except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,))
CARLSON-+STING INC
erbn W. lAchi
Project Manager
SWL/jng
cc: PacTrust-John Wiitala JosivvapAc.TRUST cow
City of Tigard Building Division-Walter'Chip' Barnett EMAIY.ED
MNP Structural Engineers-Eric Berkes ERFRKFStAMHPSE.COM
Marvin&Sons Construction Inc-Bob Marvin MARVINANDSONS@COMCAST.NET
P:\Projects\Genera112017\T1701930A10H-31.17 Final letter rioc Updated 11/30/11
Bend Office (541)330-9155
Geatechnical Office (503)601-8250
Carlson Testing Inc. Eugene Of (541)345-0289
Salem Office
(503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
Date: June 19, 2018
Job#: T1701930,G
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn: Building Division
Re: Project Name: 10BP126-PacTrust Voluntary Seismic Upgrade- Building 7
Address: 16500 SW 72nd Ave-Tigard, OR
Permit#: BUP2017-00316
Per Chapter 17, Section 1704.1.2 of the International Building Code(IBC), we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
The non-compliance (NC) items recorded for each of the above inspection categories, as listed on the non-compliance report,
have been either repaired and re-inspected by CTI for compliance or reviewed and accepted by the engineer of record for the
project in the'As-Built Condition' or through an RFI
The issuance of this final report is based on the engineer's acceptance of the NC items not specifically re-inspected by CTI. CTI
did not provide any additional review or re-inspection of those items beyond the inspections that initially generated each of these
individual items on the non-compliance list. The engineer of record has provided the acceptance of the non-Compliance items
and as-built conditions.
All requested inspections and tests were performed and reported according to the requirements of project documents and to the
best of our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and
applicable workmanship, provisions of the State Building Code and Standards, as well as the structural engineer's design
changes, approvals and verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any
type. Even with diligent construction monitoring and testing, construction defects, deficiencies or omissions in the contractor's
work may exist. It is the contractor's responsibility to perform their work in accordance with the approved construction
documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by
members of its profession in the same locale. Statements made in our reports are based on technical judgments and should not
be construed to be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
ctra services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to health,safety or
welfare,
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
C9RLSON. INGzC,
W. Lea
Project Manager
SW L/jng
cc: PacTrust- John Wiitala )oi,NWOPACTRUST.004
City of Tigard Building Division-Walter'Chip' Barnett MAILED
MHP Structural Engineers -Eric Berkes EBERKESAMHPSE.COM
Marvin& Sons Construction Inc- Bob Marvin MARV1NANOS0NSSCOMCAST.NET
P\Projects1Genera1120171T1701930G\06-19-18 Final Leiter doc Updated 11/30/11
Bend Office (541)330-9155
Geotechnical Office (503)601-8250
Carlson Testing Inc SalOffice
Eugene
Office (541)345-0289
• Salem Office (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
Date: June 19, 2018
Job#: T1701930.1
City of Tigard
13125 SW Hail Blvd
Tigard, OR 97223-8199
Attn: Building Division
Re: Project Name: 10BP126- PacTrust Voluntary Seismic Upgrade-Building 3
Address: 16300 SW 72n0 Ave-Tigard,OR
Permit#: BUP2018-00018
Per Chapter 17, Section 1704.1.2 of the International Building Code(IBC),we have performed special inspection of the following
item(s)per our inspection reports only:
Adhesive Anchors
The non-compliance (NC) items recorded for each of the above inspection categories, as listed on the non-compliance report,
have been either repaired and re-inspected by CTI for compliance or reviewed and accepted by the engineer of record for the
project in the`As-Built Condition'or through an RFI.
The issuance of this final report is based on the engineer's acceptance of the NC items not specifically re-inspected by CTI. CTI
did not provide any additional review or re-inspection of those items beyond the inspections that initially generated each of these
individual items on the non-compliance list. The engineer of record has provided the acceptance of the non-compliance items
and as-built conditions.
All requested inspections and tests were performed and reported according to the requirements of project documents and to the
best of our knowledge, the work was in conformance with the approved plans and specifications, approved change orders and
applicable workmanship, provisions of the State Building Code and Standards, as well as the structural engineer's design
changes, approvals and verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction defects,
deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or guarantee of any
type. Even with diligent construction monitoring and testing, construction defects. deficiencies or omissions in the contractors
work may exist. It is the contractor's responsibility to perform their work in accordance with the approved construction
documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar circumstances by
members of Its profession in the same locale. Statements made in our reports are based on technical judgments and should not
be construed to be conclusive representations of fact. Our reports pertain to the material tested/inspected only.
CTrs services did not include responsibilities related to determining, supervising, implementing or controlling the means, methods,
techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to health, safety or
welfare.
Information contained herein is not to be reproduced, except in full,without prior authorization from this office. If there are further
questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted
- STIN NC.
nW. L chi
Project Manager
SW L/jng
cc: PacTrust-John Wiitala )OHNWePACTRUST.COM
City of Tigard Building Division-Walter 'Chip' Barnett MAILED
MHP Structural Engineers-Eric Berkes EBERKES@MHPSE.00M
Marvin& Sons Construction Inc-Bob Marvin MARVTNANOSONSaCOMCAST.NET
P 1ProjectslGeneral120171T17019301\06-19-18 Final letter.doc Updated 11/30/11
Bend Office (541)330-9155
Ceotechnical Office (503)601-8250
Carlson Testing, Inc. Eugene Office (541)345-0289
Salem Office (503)589-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
Date. January 10, 2019
Job#: T1701930.K
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223-8199
Attn: Building Division
Re: Project Name: PBPA143—Pactrust Voluntary Seismic, Upgrade— Building 2
Address: 16200 SW 72nd Avenue—Tigard, OR
Permit#: BUP2018-00161
Per Chapter 17, Section 1704.1.2 of the International Building Code(IBC), we have performed special inspection of the
following item(s)per our inspection reports only:
Adhesive Anchors
Structural Steel(Shop Only)
All requested inspections and tests were performed and reported according to the requirements of project documents and
to the best of our knowledge, the work was in conformance with the approved plans and specifications, approved change
orders and applicable workmanship, provisions of the State Building Code and Standards, as well as the structural
engineer's design changes, approvals and verbal instructions.
Our construction inspection and testing services were provided and intended to help reduce the risk of construction
defects, deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or
guarantee of any type. Even with diligent construction monitoring and testing, construction defects, deficiencies or
omissions in the contractor's work may exist. It is the contractor's responsibility to perform their work in accordance with
the approved construction documents.
CTI has provided its professional services with the degree of care and skill currently exercised under similar
circumstances by members of its profession in the same locale. Statements made in our reports are based on technical
judgments and should not be construed to be conclusive representations of fact. Our reports pertain to the material
tested/inspected only.
CTI's services did not include responsibilities related to determining, supervising, implementing or controlling the means,
methods, techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to
health, safety or welfare.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are
further questions regarding this matter please do not hesitate to contact this office,
Respectfully submitted,
CARD TESTI INC.
7
ven W. each
Project Manager
SWUjng
cc: PACTRUST-JOHN WIITALA
CITY OF TIGARD BUILDING DIVISION-WALTER 'CHIP'BARNETT
MHP STRUCTURAL ENGINEERS -ERIC BERKES
MARVIN&SONS CONSTRUCTION INC -BOB MARVIN
P.iProjects\Genera1120171T1701930K101-10-19 Final Letter.doc Updated 11/30/11
August 2, 2018
Job#: T1803886
Page 2 of 2
CTI's services did not include responsibilities related to determining supervising, implementing or controlling the means,
methods, techniques, sequences or procedures of the construction or evaluating or reporting job conditions related to
health. safety or welfare
Information contained herein is not to be reproduced, except in full, without prior authorization from this office. If there are
further questions regarding this matter please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING INC.
Jd
Stev4n W Lech
Project Manager
SLlks
cc. Columbia Tech Center LLC c!o Pactrust-Leslie Louis
Abbott Construction -Jason Bragg
MHP Structural Engineers - Eric Berkes
Rend Office (541)330-9155
Geotcchnicat Office (503)601-8250
Carlson Testing, Inc. Eugene Office (541)345-0289
Salem Office (503)5,89-1252
Tigard Office (503)684-3460
Special Inspection
FINAL SUMMARY LETTER
August 2, 2018
Job# T1803886
City of Tigard
13125 SW Hail Blvd
Tigard. OR 97223-8199
Attn Building Division
Re Project Name PCC211 -Pactrust Voluntary Seismic Upgrade
Address 15755 SW Sequoia Parkway-Tigard, OR
Permit# BUP2017-00201
Per Chapter 17, Section 1704.1.2 of the International Building Code (IBC), we have performed special inspection of the
following item(s) per our inspection reports only'
Installation of Adhesive Anchors
Any non-compliance (NC) items recorded for each of the above inspection categories. as listed on the non-compliance
report, have been either repaired and re-inspected by CTI for compliance or reviewed and accepted by the engineer of
record for the project in the"As-Built Condition' or through an RFI.
The issuance of this final report is based on the engineer's acceptance of the NC items not specifically re-inspected by
CTI If CTI did not provide additional review or re-inspection of those items beyond the inspections that initially generated
each of the non-compliance items, then the engineer of record has provided acceptance of the non-compliance items and
as-built conditions
All requested inspections and tests were performed and reported according to the requirements of project documents and
to the best of our knowledge, the work was in conformance with the approved plans and specifications, approved change
orders and applicable workmanship, provisions of the State Building Code and Standards, as well as the structural
engineer's design changes, approvals and verbal instructions
Our construction inspection and testing services were provided and intended to help reduce the risk of construction
defects, deficiencies or omissions that arose during and after construction. Our services do not constitute a warranty or
guarantee of any type. Even with diligent construction monitoring and testing, construction defects, deficiencies or
omissions in the contractor's work may exist. It is the contractor's responsibility to perform their work in accordance with
the approved construction documents
CTI has provided its professional services with the degree of care and skill currently exercised under similar
circumstances by members of its profession in the same locale. Statements made in our reports are based on technical
judgments and should not be construed to be conclusive representations of fact Our reports pertain to the material
tested/inspected only
P 1Proiects\Generai\Final Letter Forms\Ne*Final Letter Templates\City of Tigard doc Updated 11/30111