Plans BUP2012 - 00130
RECEIVED
JUL 0 3 2012 MILDREN DESIGN GROUP, P.C.
ARCHITECTURE ■ SPACE PLANNING
effyoFTIGARD 7650 S.W. Beveland, Suite 120
PlumbingRequirements General Notes �uII�11�C3DIVISION Tigard; Oregon 97223-8692
Code Analysis (503) 244-0552
BASED ON THE 2010 OREGON STRUCTURAL AND SPECIALTY CODE PER TABLE 29—A A. VERIFY AND CONFIRM ALL DIMENSIONS AND CONDITIONS.
B OCCUPANCY 1:200, 4589 SF = 23 OCC = 11.5 MALE, NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO START
OCCUPANCY AND CONSTRUCTION
11.5 FEMALE OF WORK.
ASSUMED OCCUPANCY: B B. ALL HARDWARE IN ACCORDANCE WITH ANSI 117.1.
NON—SEPARATED USE BETWEEN: N/A REQUIRED PROVIDED (ON FLOOR) C. PROVIDE (1) APPROVED FIRE EXTINGUISHER WITH RATING OF
CONSTRUCTION TYPE: III—B LAVATORIES 1 MALE, 1 FEMALE 2 MALE, 2 FEMALE NOT LESS THAN 2—A: 10B FOR EACH 3,000 SQ.FT. OF FLOOR
WATER CLOSETS 1 MALE, 1 FEMALE 2 MALE, 3 FEMALE AREA TRAVEL FROM ANY PORTION OF BUILDING NOT TO
EXCEED 75'. FIRE EXTINGUISHERS NEED TO BE NEAR EACH
FIRE-RESISTANCE RATING REQUIREMENTS REQUIRED EXIT AND EVERY SEVENTY FIVE FEET ALONG THE
STRUCTURAL FRAME: 0 HRS. PATH OF EGRESS.
EXTERIOR BEARING WALLS: 2 HRS. D. SPRINKLERS ARE EXISTING; A SEPARATE PERMIT WILL BE REQUIRED
EXTERIOR NON-BEARING WALLS: 0 HRS. FOR ANY CHANGES (SEE "DEFERRED SUBMITTALS").
INTERIOR NON-BEARING WALLS: 0 HRS. Deferred Submittals E. ALL FINISHES (IE BASE, ETC.) TO MATCH EXISTING UNLESS
FLOOR CONSTRUCTION: 0 HRS. PLUMBING NOTED OTHERWISE.
HVAC F. PROVIDE 20 CFM OF OUTSIDE AIR PER OCCUPANT AT
FIRE PROTECTION: BUILDING IS EQUIPPED WITH AN AUTOMATIC FIRE PROTECTION SYSTEM AND AUTOMATIC SMOKE ELECTRICAL OFFICE AREA.
LEVEL 4 FINISHED WALLS (NEW) TO RECEIVE (1) COAT PRIMER,
DETECTION THROUGHOUT IN ACCORDANCE WITH OSSC 903.3.1.1 SPRINKLERS G.
VERTICAL EXITS AND PASSAGWAYS EXIT CORRIDORS AND EXITWAYS ROOMS AND ENCLOSED SPACES (2) COATS ACRYLIC LATEX.
FLAME SPREAD INDEX: CLASS C: 76 - 200 CLASS B: 26 - 75 CLASS C: 76 - 200 H. SUSPENDED CEILING IS EXISTING; CONFORMS TO OSSC RULING
SMOKE DEVELOPED INDEX: CLASS C: 0 — 450 CLASS B: 0 — 450 CLASS C. 0 — 450 FOR 2004 OSSC SECTION 1621.1 AND 2007 OSSC (EFFECTIVE
APRIL 1, 2007) SECTION 1613.1, DATED APRIL 20, 2007. 4505
EXITING: 1. VERIFY POWER AND DATA REQUIREMENTS WITH OWNER ;OIEL A. VA UEZ
B OCCUPANCY: COMMON PATH OF EGRESS TRAVEL DISTANCE DOES NOT EXCEED 100'-0" PER OSSC SECTION 1014.3 AND TENANT. Gol
EXIT ACCESS TRAVEL DISTANCE DOES NOT EXCEED 300'-0" PER OSSC SECTION 1016.1 J. FURNISH THREE SILENCERS FOR SINGLE ACTING SINGLE DOORS. '
K. DIMENSIONS THAT ARE NOT MARKED MINIMUM OR MAXIMUM ARE
ABSOLUTE DIMENSIONS. OF O
L. DO NOT PLACE OPPOSING ELECTRICAL OR DATA MUDRINGS WITHIN
SAME CAVITY.
M. CONTRACTOR TO INSTALL CEILING TILES WITHIN EXISTING CEILING Owner:
GRID (TILES STORED ON SITE) AND RELOCATE LIGHTS,
DIFFUSERS, ETC. AS REQUIRED FOR NEW LAYOUT. Pacific NW
N. ALL ELECTRICAL SWITCHING TO TIE INTO EXISTING BUILDING
SWEEP SYSTEM (SWITCHING ORIGINALLY INSTALLED BY Properties
CAPITOL ELECTRIC). p
0. PROVIDE SOUND ATTENUATION BATT AT ALL NEW INTERIOR
WALLS.
P. PROVIDE PAINT AT NEW WALL LOCATIONS AND WHERE IDENTIFIED
BY KEYNOTE.
Q. CONTRACTOR TO REUSE EXISTING DOORS AND DOORS STORED
ON SITE WHERE POSSIBLE OR NEW DOORS WHEN NECESSARY. 6600 S.W. 105th Avenue
R. CONTRACTOR TO USE CARPET TILE STORED ON SITE AS REQUIRED. Beaverton, Oregon 97005
Project~
Broad River
Expansion
Project
11850 SW 67th Ave-Suite 140
Tigard, Oregon 97223
�� Sheet Title:
Exist m /
Building ��� ' ;\ Area of Work Cover Sheet
11ilu
O 4 CITY OF TIGARD
O Approved..........C.1.................[ �� Revisions:
Conditionally Approved..............[ ]
/ See Letter to:Follow..................[ ]
Attached................ ]
Permit Number, ot
Address: r5 �
Date:
Approved plans
shall be on jots site.
0-T-C
RIdCmIf MILDREN DESIGN GROUP, P.C., 2012, ALL
$newco& RIGHTS RESERVED
AccessibUlty THESE DRAWINGS ARE THE PROPERTY OF(// /� MILDREN DESIGN GROUP, OAND ARE
!!! C l NOT TO BE USED OR REPRODUCED IN ANY
MANNER, EXCEPT WITH THE PRIOR WRITTEN
OFFICECOPY PERMISSION OF MILDREN DESIGN GROUP, P.C.
Key Plan Date: 3 July 2012
No Scale Drawn by: Checked by:
BK DAV
Job Number. 110192
Sheet
Permit Submittal - July 2012 AO
Keynotes
1. EXISTING WALL AND DOOR TO BE REMOVED TYPICAL
2. PROVIDE ALTERNATE PRICE TO REMOVE EXISTING WALLS, .
CLOSET DOORS AND CASEWORK THIS SUITE MILDREN DESIGN GROUP, P.C.
114 3. CENTERLINE WALL/CENTERLINE MULLION TYPICAL
% 4. NEW WALL FLUSH WITH EXISTING FURRING ARCHITECTURE ■ SPACE PLANNING
X4 8 XXX 5. RELOCATED EXISTING FIRE EXTINGUISHER FROM DEMOLISHED
23.13 S.F. � � 7650 S.W. Beveland, Suite 120
/100 = 1 % WALL TO THIS LOCATION Tigard, Oregon 97223-8692
B:EXI TS 1 %
%o (503) 244-0552
/ 4
/ OFFICE
/ 102 102
% X4 B XXX
VESTIBULE 222.7 S.F.
'/ X4 01 XXX /100 = 3
100.73 S.F. B:EXITS 1 Wall Legend
E /100 –
�" EXIT 0FI
104 ® 112 EXISTING WALL TO REMAIN
X413 XXX
1 MACHINE RM. `I \ 125.54 S.F. C - - _ _ _ EXISTING WALL TO BE REMOVED
J E 103 OFFICE /100ITS 1 113 FFICE
3%" METAL STUDS WITH % " GYPSUM
113
111 I X4 B X XX BOARD
'\ X4 B X XX �`� 185.29 S.F.
125.54 S.F.
WOMEN d TRAINING \ /100 = 2
112 /100 = 2
O -10-4T- ��' B:EXITS 1
DW X4 B X XX 104, B:EXITS 1
MEN 405.77 S.F.
--- • /20 = 21110 OFFICE
o E B:EXITS 1 � ��-, NC) 109 X4 B XXX p�°c
°` 126.62 S.F. , Room Symbol Le end 4505
1 FE 'ti \ O 10Q = 2 °' J L .A. VA EZ
/
OPEN OFFICE B:EXITS 1
ROOM NAME GON
103
X4 B X XX 5 ����� OFFICE ROOM NUMBER
790.78 S.F. �ti ROOM AREA LOAD 44B�R
O/100 = 8 1 .] / ROOM FINISH
B:EXITS 1 .-�'. joFACTOR B9
107 XXX/100: 2-�_NUMBER OF
11aI�. 108 OFFICE \'j. B: 2 E ITS OCCUPANTS
Str X408 X XX � � NUMBER OF Owner:
129.71 S.F. ��, OCCUPANCY GROUP PER EXITS PROVIDED Pacific NW/100 = 2 IBC TABLE 1004.1.2/NUMBER
" '�GoMM 106 B:EXITS 1
3 105 , OFFICE Properties
109
q X4 B X XX
� � \ ,C _ 2
2 127.5 S.F.
-`. . r A2
/100 = 2
B:EXITS 1 Finish Schedule
3 ROOM NAME 6600 S.W. 105th Avenue
OFFICE FIOOr Flnlsh — A4BB9 Beaverton, Oregon 97005
107
,. X4 B X XX A. EXPOSED CONCRETE SLAB
132.95 S.F. B. CARPET
�2 OFFICE /100 = 2 C. SHEET VINYL Project:
106 B:EXITS 1 D. VINYL COMPOSITION TILE
OFFICE X4 B X XX E. SLATE TILE Broad River
105 132.32 S.F.
/100 = 2 X. EXISTING TO REMAIN
X4 B X XX B:EXITS 1
134.27 S.F. Base Expansion
/100 = 2
B:EXITS 1 0. NO BASE Project
4. 4" RUBBER BASE
X. EXISTING TO REMAIN
Wail Finish
A. EXPOSED CONCRETE
11850 SW 67th Ave-Suite 140 B. GYPSUM BOARD AND PAINT Tigard, Oregon 97223
C. 4' PLASTIC WAINSCOT WITH STAINLESS STEEL
TRIM AT EDGES, W.R. GYPSUM BOARD AND PAINT
ABOVE. TYPICAL AT ELEVATED WALLS ONLY. Sheet Title-
FloorFloor
I lan X. EXISTING TO REMAIN Floor Plan
4,589 SF OFFICE CeilingFinish
0 2 4 8 16 46 TOTAL OCCUPANTS
A. EXPOSED ROOF STRUCTURE
B. SUSPENDED ACOUSTICAL - TEE BAR
C. GYPSUM BOARD AND PAINT
Door Schedule Door Types X. EXISTING TO REMAIN
Celhng height
MARK NOMINAL SIZE FRAME DOOR HARDWARE REMARKS 8 8'-0"
WIDTH HEIGHT THICK. MAT'L FINISH MAT'L FINISH TYPE GROUP
9. 9'-0"
102 3'-0" 8'-0" 1-3/4" MTL FF Sc ST B 1 12. 12'-0"
103 3'-0" 8'-0" 1-3/4" MTL FF SC ST B 2
104A 3'-0" 8'-0" 1-3/4" MTL FF SC ST B 3 X. EXISTING TO REMAIN
10413 3'-0" 8'-0" 1-3/4" MTL FF SC ST B 2 Revisions:
105 3'-0" 8'-0" 1-3/4" MTL I FF Sc ST A 1
106 3'-0" 8'-0" 1-3/4" MTL FF SC ST A 1
107 3'-0" 8'-0" 1-3/4" MTL FF Sc ST A 1 \ \
108 3'-0" 8'-0" 1-3/4" MTL FF SC ST A . 1
109 3'-0" 8'-0" 1-3/4" MTL FF SC ST A 1 N Legend
110 3'-0" 8'-0" 1-3/4" MTL FF SC ST A 1
111 3'-0" 8'-0" 1-3/4" MTL FF SC ST A 1 3'X8' TEMPERED REtIrE FIRE EXTINGUISHER
112 3'-0" 8'-0" 11-3/4"1 MTL FF SC ST A 1
113 3'-0" 8'-0" 1-3/4" MTL FF SC ST B 1 A B loo NEW DOOR
LEGEND Door Hardware EXISTING DOOR TO REMAIN
CL CLEAR
FF FACTORY FINISH GROUP 1
GL GLASS 2 PAIR BUTTS STANLEY 652 FBB179 4/2 X 4Y MILDREN DESIGN GROUP, P.c., zoiz, ALL
1 1 RIGHTS RESERVED
SC SOLID CORE 1 LOCKSET SCHLAGE 626 SPARTA ND50PD THESE DRAWINGS ARE THE PROPERTY OF
ST STAIN MILD1 STOP IVES 630 407Y NOT TO BE UEN SED GN GORU REPRODUCED AND IN ANY
MANNER, EXCEPT WITH THE PRIOR WRITTEN
PERMISSION OF MILDREN DESIGN GROUP, P.C.
GROUP 2
2 PAIR BUTTS STANLEY 652 FBB179 4% X 4% Date: 3 July 2012
1 LATCHSET SCHLAGE 626 SPARTA NDI OS Drawn by: Checked by:
1 CLOSER LCN 4041
1 STOP IVES 630 407% BK DAV
GROUP 3 Job Number: 110192
2 PAIR BUTTS STANLEY 652 FBB179 4% X 4% Sheet
1 LOCKSET SCHLAGE 626 SPARTA ND70PD
1 CLOSER LCN 4041
1 STOP IVES 630 407, Permit Submittal - Jul 2012 Al
v
Electrical Symbols Keynotes
1. EXISTING SUSPENDED CEILING AND LIGHTS
EXISTING FLUORESCENT LIGHT FIXTURE 2. EXISTING CEILING OUTLET3. REPAIR GRID AS REQUIRED WHERE BROKEN AT REMOVED
WALLS; PROVIDE NEW CEILING TILE AS NEEDED - SHOWN MILDREN DESIGN GROUP, P.C.
EXISTING FLUORESCENT LIGHT FIXTURE TO BE REMOVED OR RELOCATED SHADED ARCHITECTURE ■ SPACE PLANNING
4. REMOVE EXISTING WALL MOUNTED CARD READER AND/OR 7650 S.W. Beveland, Suite 120
RELOCATED EXISTING FLUORESCENT LIGHT FIXTURE KEY PAD, REPLACE WITH BLANK COVER PLATE (STYLE AND Tigard, Oregon 97223-8692
COLOR TO BE SELECTED BY OWNER)
(503) 244-0552
EXISTING EXIT SIGN ON BATTERY BACKUP TO REMAIN
NEW LIGHT SWITCH, MATCH EXISTING COVERPLATE COLOR
N
NEW 3-WAY LIGHT SWITCH, MATCH EXISTING COVERPLATE
N 3 COLOR
" @= EXISTING DUPLEX OUTLET
W EXISTING QUADPLEX OUTLET
N
A EXISTING DATA OULET
D EXISTING DUPLEX AND DATA FLOOR OUTLETS
EXISTING DUPLEX OUTLET TO BE REMOVED
EXISTING QUADPLEX OUTLET TO BE REMOVED
. EXISTING DATA OUTLET TO BE REMOVED
1 �N NEW DUPLEX OUTLET C� 00-
DN NEW DATA OUTLET WITH PULL STRING 4505
> 0, 0 GON
3
OF
Owner:
Pacific NW
Properties
3
6600 S.W. 105th Avenue
Beaverton, Oregon 97005
Reflected Ceiling Plan
Project:
0 2 4 8 16 Broad River
0
Expansion
Project
V a.
i� VPX6
11850 SW 67th Ave-Suite 140
Tigard, Oregon 97223
I
4
X6 WHERE TOP OF WALL TO STRUCTURE (1) 20 GA. 35/8" NOMINAL METAL Sheet Title:
o
2 ABOVE IS LESS THAN 5'-9" PROVIDE STUD BRACING TO STRUCTURE Ref lected
o (1) BRACE AT 8'-0" O/C TO ONE WITH (2) #8 SHEET METAL
IN
SIDE ONLY, STAGGER SIDES. WHERE SCREWS AT EACH END; PROVIDE Ceiling Plan
DOUBLE STUD BRACE WHEN MULLION
px6 DISTANCE IS GREATER THAN 5'-9", DISTANCE TO STRUCTURE ABOVE
" Details PROVIDE BRACES EACH DIRECTION AT and Details
IS GREATER THAN 5 -9". BRACING
�px6 x. 450 8'-0" 0/C TO BE PROVIDED WHERE DISTANCE
BETWEEN PERPENDICULAR
px6 INTERSECTING WALLS OR
HORIZONTAL BRACING BETWEEN
'4
WALLS EXCEEDS 8'-0" (DO NOT SEALANT TAPE
EXTEND BRACING INTO EXPOSED
2 STRUCTURE AREAS) Revisions:
qP px 6 L 1 Y2" x 912" x 16 GA x
�x6 (3J dr 3" WITH� (/4 1[8 SCREWS(3)dr l � Yt SUSPENDED CEILING Mir ALUMINUM BRAKE SHAPE
EACH SIDE TO MATCH EXISTING SYSTEM
ATTACH STUD TRACK CASING BEAD USG 200-A
�px6
(3)dr
TO BRACING THROUGH 5/8" GYPSUM BOARD EACH SIDE
OVERSIZED HOLE IN SECURE TO STUDS WITH TYPE 'S' INTERIOR OFFICE WALL
GRID SCREWS AT 5" - 7" 0/C
3Y2" SOUND 24" 0/C STUD CHART:
ATTENUATION BATT •362 S 125-18 TO 9'-11"
• 362 S 137-33 TO 17'-6"
• 400 S 162-33 TO 19'-10"
4" RUBBER BASE •600 S 162-33 TO 27'-7"
TYPICAL SEE A/E FOR ALTERNATE
SIZES MILDREN DESIGN GROUP, P.C., 2012, ALL
X4 POWER-ACTUATED FASTENERS: RIGHTS RESERVED
xaTHESE AWINGS ARE TE POPERTY
• 0.145" 0 x %" MIN. EMBED MILDREN DDESIGN GROUPHP.CR AND AREF
X4 AT 12" 0/C, WALL TO 22'-0" NOT TO BE USED OR REPRODUCED IN ANY
0.145" X " MIN. EMBED MANNER,PERMISSION OF MILDREN DESIGN GROUEXCEPT WITH THE PRIOR P, P.C..
AT 6" 0/C, WALL TALLER
THAN 22'-0"
Date: 3 July 2012
('1 Wall to Suspended Ceiling2 Wall at Mullion Drawn by: Checked by:
��23'=1'-0" A2 3"=1'-0" BK DAV
1a1d-r8 1i1b
Power Plan Job Number: 110192
Sheet
0 2 4, 8 16