Specifications (36) NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office c�'+ (503) 255-1966 Fax RECEIVED E® Job Name: Tigard Triangle Commons - Building 1 AUG 2 0 2019 Job Address: 11850 SW 67th Ave Tigard, OR 97223 CITY OF TIGARD Job Number: BUILDING DI\/ISgh'ductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/6/2019 Cable Length In Feet (source to end of line) 468 Total Circuit Current 1.156 Nominal System Voltage 20.4 Panel Description: Silent Knight 5499 Power Supply Minimum Device Voltage 16 Panel No.: NAC 1.1 Output No.: 1 Point To Point Method EOLv 18.47 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 18.74 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 9 7�� /F s � Y �� �✓ v �96 /$ �dy 96�solo v � j: 1 FLOOR 1, CORRIDOR AS-24MCW-FW (75) H/S WHT-M 75 Cd 0.190 45 20.08 2 FLOOR 1, RESTROOM RSS-24MCW-FW (15) STB WHT 15 Cd 0.060 34 19.88 3 FLOOR 1,CORRIDOR AS-24MCW-FW (15) H/S WHT-M 15 Cd 0.074 37 19.67 4 FLOOR 1, CORRIDOR AS-24MCW-FW (15) H/S WHT-M 15 Cd 0.074 96 19.18 5 FLOOR 1, SUITE 100 HSWC (95) H/S-Ceil, White, Hi 95 Cd 0.176 50 18.95 6 FLOOR 1, SUITE 100 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 68 18.71 7 FLOOR 1,SUITE 100 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 28 18.63 8 FLOOR 1, SUITE 100 STWC (15) Stb-Ceil, White 15 Cd 0.061 33 18.56 9 FLOOR 1, SUITE 100 STWC (15) Stb-Ceil, White 15 Cd 0.061 20 18.53 10 FLOOR 1,SUITE 100 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 26 18.49 11 FLOOR 1,SUITE 100 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 31 18.47 12 18.47 13 18.47 14 18.47 15 18.47 16 18.47 17 18.47 18 18.47 19 18.47 20 18.47 Tigard Trianglel, NAC 1.1 EOLv Calc.xls OUTPUT 1 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Triangle Commons Building-1 ADDRESS: 11850 SW 67th Ave Tigard,OR 97223 DATE: 8/6/19 PANEL DESCRIPTION: NAC 1.1 PREPARED BY: Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER Silent Knight 5499 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT#1 Floor 1 sy- 0.000 Wheelock AS-24MCW-FW 75 Cd H/S (M) 1 0.190 0.190 Wheelock AS-24MCW-FW 15 Cd H/S (M) 2 0.074 0.148 Wheelock RSS-24MCW-FW 15 Cd Strobe 1 4-V,17::,711,;;.)11,. 0.060 0.060 Whlk HSWC 95 Cd H/S-Ceiling (H) 1 0.176 0.176 Whlk HSWC 75 Cd H/S-Ceiling (H) 2 0.148 0.296 Whlk HSWC 15 Cd H/S-Ceiling (H) 2 0.082 0.164 Whlk STWC 15 Cd Strobe-Ceiling 2 0.061 0.122 0.000 TOTAL 1.156 CIRCUIT#2 Floor 1 j%%/ 0.000 Wheelock AS-24MCW-FW 110 Cd H/S (M) 0.253 0.000 Wheelock AS-24MCW-FW 75 Cd H/S (M) 1 ;,r% 0.190 0.190 Wheelock AS-24MCW-FW 30 Cd H/S (M) ' I:cf ' "41 0.110 0.000 Wheelock AS-24MCW-FW 15 Cd H/S (M) � 0.074 0.000 Wheelock RSS-24MCW-FW 30 Cd Strobe , �� 0.092 0.000 Wheelock RSS-24MCW-FW 15 Cd Strobe 1 AgNV, v ; 0.060 0.060 Wheelock AS-24MCC-FW 95 Cd H/S (M) 5 jI ,;• 0.269 1.345 Wheelock AS-24MCC-FW 75 Cd H/S (M) 0.201 0.000 <z. TOTAL 1.595 CIRCUIT#3 Floor 1 0.000 Wheelock AS-24MCW-FW 110 Cd H/S (M) 1 0.253 0.253 Wheelock AS-24MCW-FW 75 Cd H/S (M) 2 �l 0.190 0.380 Wheelock AS-24MCW-FW 30 Cd H/S (M) 10.110 0.110 Wheelock AS-24MCW-FW 15 Cd H/S (M) 1 0.074 0.074 Wheelock RSS-24MCW-FW 30 Cd Strobe 2 %/i% ;;, ,/,/ 0.092 0.184 Wheelock RSS-24MCW-FW 15 Cd Strobe 3 -;/'%f'"/ "%! /i 0.060 0.180 Wheelock AH-24-W HORN (M) 3 .,.>�s , 0.043 0.129 0.000 'r ivs�'.' ✓ iz � TOTAL 1.310 CIRCUIT#4 Floor 1 0.000 Wheelock AS-24MCW-FW 110 Cd H/S (M) ' 4q�> 0.253 0.000 Wheelock AS-24MCW-FW 75 Cd H/S (M) 2 0.190 0.380 Wheelock AS-24MCW-FW 30 Cd H/S (M) 1 0.110 0.110 �j Wheelock AS-24MCW-FW 15 Cd H/S (M) 2 ,/%///,'; 0.074 0.148 Wheelock RSS-24MCW-FW 30 Cd Strobe 1 0.092 0.092 Wheelock RSS-24MCW-FW 15 Cd Strobe 2 ''+ 0.060 0.120 Wheelock AS-24MCC-FW 95 Cd H/S (M) 2 ;;;// 0.269 0.538 Wheelock AS-24MCC-FW 75 Cd H/S (M) 1 0.201 0.201 'S TOTAL 1.589 Tigard Trianglel, NAC 1.1 Batt Calc.xls Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Triangle Commons Building-1 ADDRESS: 11850 SW 67th Ave Tigard, OR 97223 DATE: 8/6/19 PANEL DESCRIPTION: NAC 1.1 PREPARED BY: Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES "a, F... St% .,F,., /%/��', 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: 0.075 STANDBY HOURS: 24 STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 5.650 ALARM TOTAL CURRENT: 5.825 ALARM MINUTES: 5 ALARM AMP HOURS: 0.485 TOTAL CALCULATED AMP HOURS 2.285 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 2.743 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES Tigard Trianglel, NAC 1.1 Batt Calc.xls Page 2 of 2 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Triangle Commons - Building 1 Job Address: 11850 SW 67th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/6/2019 Cable Length In Feet (source to end of line) 272 Total Circuit Current 0.938 Nominal System Voltage 20.4 Panel Description: Silent Knight 5499 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.1 Output No.: 1 Point To Point Method EOLv 19.56 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 19.62 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) �z::r..o' %a_ �-... .r e��'se;y a r�ay.,..tior�' ;s�"'•a_ r i_:�r,e r:s,.� .-,� C� �,y r z -xs ar�aa9�y,��a:. �i d� s � a h �' /r/. i�%/ .z��. �0.:�'o'y V/'6 6 s'lc✓�: '' .. L�r�' ,9 ,s ,<y cycy •,tv�4 y 4�yiy�_ �W.- -',yam y y aM-c s'r', /fir. 1 FLOOR 2 AS-24MCC-FW (75) H/S WHT-H 75 Cd 0.221 57 20.07 2 FLOOR 2 HSW (75) H/S-Wall, White, Hi 75 Cd 0.148 27 19.95 3 FLOOR 2 HSWC (30) H/S-Ceil, White, Hi 30 Cd 0.102 45 19.80 4 FLOOR 2 HSW (75) H/S-Wall, White, Hi 75 Cd 0.148 31 19.71 5 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 38 19.63 6 FLOOR 2 HSWC (115) H/S-Ceil, White, Hi 115 Cd 0.197 41 19.57 7 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 33 19.56 8 19.56 9 19.56 10 19.56 11 19.56 12 • 19.56 13 19.56 14 19.56 15 19.56 16 19.56 17 19.56 18 19.56 19 19.56 20 19.56 Tigard Trianglel, NAC 2.1-1 EOLv Calc.xls OUTPUT 1 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Triangle Commons - Building 1 Job Address: 11850 SW 67th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/6/2019 Cable Length In Feet (source to end of line) 336 Total Circuit Current 0.842 Nominal System Voltage 20.4 Panel Description: Silent Knight 5499 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.1 Output No.: 2 Point To Point Method EOLv 19.32 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 19.53 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) e y may# day Q aq� 1 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 55 20.12 2 FLOOR 2 STWC (30) Stb-Ceil, White 30 Cd 0.085 29 19.98 3 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 41 19.81 4 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 34 19.68 5 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 23 19.60 6 FLOOR 2 HSWC (30) H/S-Ceil, White, Hi 30 Cd 0.102 28 19.52 7 FLOOR 2 HSWC (150) H/S-Ceil, White, Hi 150 Cd 0.242 57 19.38 8 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 69 19.32 9 19.32 10 19.32 11 19.32 12 19.32 13 19.32 14 19.32 15 19.32 16 19.32 17 19.32 18 19.32 19 19.32 20 19.32 Tigard Trianglel, NAC 2.1-1 EOLv Calc.xls OUTPUT 2 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Triangle Commons - Building 1 Job Address: 11850 SW 67th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/6/2019 Cable Length In Feet (source to end of line) 360 Total Circuit Current 1.137 Nominal System Voltage 20.4 Panel Description: Silent Knight 5499 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.1 Output No.: 3 Point To Point Method EOLv 18.90 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 19.14 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) yt 3.a y s G y a 1 may' y`11 s'�'y�r 9 Wab t r. a 1 FLOOR 2 RSS-24MCW-FW (15) STB WHT 15 Cd 0.060 28 20.20 2 FLOOR 2 RSS-24MCW-FW (15) STB WHT 15 Cd 0.060 18 20.09 3 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 36 19.86 4 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 40 19.65 5 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 67 19.35 6 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 59 19.14 7 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 35 19.05 8 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 28 18.99 9 FLOOR 2 HSWC (177) H/S-Ceil, White, Hi 177 Cd 0.282 49 18.90 10 18.90 11 18.90 12 18.90 13 18.90 14 18.90 15 18.90 16 18.90 17 18.90 18 18.90 19 18.90 20 18.90 Tigard Trianglel, NAC 2.1-1 EOLv Calc.xls OUTPUT 3 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Tigard Triangle Commons - Building 1 Job Address: 11850 SW 67th Ave Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/6/2019 Cable Length In Feet (source to end of line) 344 Total Circuit Current 0.777 Nominal System Voltage 20.4 Panel Description: Silent Knight 5499 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.1 Output No.: 4 Point To Point Method EOLv 19.46 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 19.58 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 FLOOR 2 RSS-24MCW-FW (15) STB WHT 15 Cd 0.060 40 20 21 2 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 63 19.93 3 FLOOR 2 HSWC (15) H/S-Ceil, White, Hi 15 Cd 0.082 22 19.85 4 FLOOR 2 STWC (75) Stb-Ceil, White 75 Cd 0.135 30 19.74 5 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 34 19.66 6 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 36 19.58 7 FLOOR 2 HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 77 19.48 8 FLOOR 2 STWC (15) Stb-Ceil, White 15 Cd 0.061 42 19.46 9 19.46 10 19.46 11 19.46 12 19.46 13 19.46 14 19.46 15 19.46 16 19.46 17 19.46 18 19.46 19 19.46 20 19.46 Tigard Trianglel, NAC 2.1-1 EOLv Calc.xls OUTPUT 4 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Triangle Commons Building-1 ADDRESS: 11850 SW 67th Ave Tigard,OR 97223 DATE: 8/6/19 PANEL DESCRIPTION: NAC 2.1 PREPARED BY: Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER 7 Silent Knight 5499 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT#1 Floor 2 e / 0.000 "' '� 0.221 0.221 Wheelock AS-24MCC-FW 75 Cd H/S (H) 1 �� �:�,��f i�;s% Whlk HSW 75 Cd H/S-Wall (H) 2 / F y ' ' � // 0.148 0.296 Whlk HSWC 115 Cd H/S-Ceiling (H) 1 /% 0.197 0.197 Whlk HSWC 30 Cd H/S-Ceiling (H) 1 0.102 0.102 Whlk STWC 15 Cd Strobe-Ceiling 2 0.061 0.122 0.000 0.000 0.000 , TOTAL 0.938 CIRCUIT#2 Floor 2 '.. �� ..,. 0.000 Whlk HSWC 150 Cd H/S-Ceiling (H) 1 /, 0.242 0.242 io Whlk HSWC 75 Cd H/S-Ceiling (H) 1 ,// 0.148 0.148 Whlk HSWC 30 Cd H/S-Ceiling (H) 1 0.102 0.102 WhlkHSWC 15 Cd HIS Ceiling (H) 1 ;. 0.082 0.082 Whlk STWC 30 Cd Strobe-Ceiling 1 / 0.085 0.085 Whlk STWC 15 Cd Strobe-Ceiling 3 y %%i 0.061 0.183 :jrZWItt: 0.000 0.000 TOTAL 0.842 CIRCUIT#3 Floor 2 T 0.000 Wheelock RSS-24MCW-FW 15 Cd Strobe 2 274, 0.060 0.120 Whlk HSWC 177 Cd H/S-Ceiling (H) 1 0.282 0.282 Whlk HSWC 75 Cd H/S-Ceiling (H) 4 0.148 0.592 Whlk HSWC 15 Cd H/S-Ceiling (H) 1 0.082 0.082 Whlk STWC 15 Cd Strobe-Ceiling 1 0.061 0.061 0.000 0.000 0.000 i % TOTAL 1.137 CIRCUIT#4 Floor 2 , �,,'; , 1 0.000 Wheelock RSS-24MCW-FW 15 Cd Strobe 1 /-- 0.060 0.060 Whlk HSWC 75 Cd H/S-Ceiling (H) 2 ' Al 0.148 0.296 Whlk HSWC 15 Cd H/S-Ceiling (H) 2 ',_, ??. ? 0.082 0.164 Whlk STWC 75 Cd Strobe-Ceiling 1 141', 0.135 0.135 Whlk STWC 15 Cd Strobe-Ceiling 2 %g` ve,w. ,.."4b20.1-: 0.061 0.122 .:n a f !/%�//f/,��1,,�,s�,,,� �`,/sem, .�-�, .��:� �;„„ 0.000 0.000 o.000 ��, ' /��� imiTOTAL 0.777 Tigard Trianglel, NAC 2.1 Batt Calc.xls Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503) 255-1966 Fax JOB NAME: Tigard Triangle Commons Building-1 ADDRESS: 11850 SW 67th Ave Tigard,OR 97223 DATE: 8/6/19 PANEL DESCRIPTION: NAC 2.1 PREPARED BY: Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES 0ay,.. :' 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: 0.075 STANDBY HOURS: 24 STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 3.694 ALARM TOTAL CURRENT: 3.869 ALARM MINUTES: 5 ALARM AMP HOURS: 0.322 TOTAL CALCULATED AMP HOURS 2.122 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 2.547 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES Tigard Triangle1, NAC 2.1 Batt Calc.xls Page 2 of 2