Loading...
Plans (82) M EC2021 -00869 MECHANICAL SPECIFICATIONS RECEIVED OFFICE COP PART 1 - GENERAL OCT 2 5 2021 SELECT AND SIZE AIR DISTRIBUTION DEVICES IN ACCORDANCE WITH THE VALIDITY OF PERMIT CITY OF TIGARD SCOPE REQUIREMENTS OF EACH APPLICATION. DEVICES, GENERALLY, SHALL PROVIDE THE ISSUANCE OF A PERMIT BUILDING DIVISION UNIFORM, DRAFT-FREE AND QUIET AIR DISTRIBUTION. RIGID FRAMES, COMPATIBLE BASED ON CONSTRUCTION FURNISH, INSTALL, TEST, PLACE INTO OPERATION AND GUARANTEE, COMPLETE, WITH SURFACE OR STRUCTURE. ---- -- - - - - - - ----- DOCUMENTS AND OTHER OPERABLE, AND APPROVED MECHANICAL AND PLUMBING WORK. SECURE AND PAY I - -- FOR ALL MATERIALS, EQUIPMENT, LABOR, SUPERVISION, FEES, TESTS, PERMITS, AND PART 3 - EXECUTION DATA SHALL NOT PREVEf 1T ALL OTHER COSTS REQUIRED. GENERAL O KEYED NOTES THE CODE OFFICIAL FROM S EA REQUIRING THE CORRECTION SCOTT I EDWARDS ARCHITECTURE LLP REGULATIONS IN EFFECT OF ERRORS. OSSC 105.4 PERFORM ALL WORK IN BEST TRADE PRACTICE. ARRANGE FOR GREATEST 1. 6"0 EXHAUST DUCT UP THRU ROOF WITH FACTORY WEATHER CAP, MUST BE 10' MIN nc NATIONAL, STATE, AND CITY CODES, ORDINANCES, ETC., HAVING JURISDICTION. PRACTICAL EASE OF OPERATION AND SERVICE. INSTALL SQUARELY WITH BUILDING FROM ALL FRESH AIR INTAKES. _... -__—_--_-= 2525 E. Burnside St., Portland, OR 97214 RULES AND REQUIREMENTS OF UTILITY SERVING AGENCIES. LINES. PROVIDE RIGID, PERMANENT, LEVEL, BASES AND SUPPORTS. ELIMINATE phone:(503) 226-3617 www.seallp.com VIBRATION AND RATTLING. 2. EXISTING ROOF TOP A/C UNIT TO REMAIN. NO ADDITIONAL FUNDS WILL BE ALLOCATED FOR WORK REQUIRED TO CONFORM TO REGULATIONS AND REQUIREMENTS. FOLLOW THESE SPECIFICATIONS AND MANUFACTURER'S RECOMMENDED INSTALLATION 3. NEW WALL MOUNTED AIR HANDLER. EXISTING i EXISTING PROCEDURES, CONFERENCE ENTRY TECH STORAGE QUALIFICATIONS OF WORKMEN 4. NEW ROOF MOUNTED CONDENSING UNIT. FT-06-1 )PRO COVER AND PROTECT ALL EQUIPMENT AND MATERIALS FROM WEATHER, THEFT, ETC.. i i8fisF5 O iissF \�'NE I USE SUFFICIENT JOURNEYMEN CRAFTSMEN AND COMPETENT SUPERVISORS, TO PLUG OR CAP ALL OPEN ENDS OF INSTALLED PIPING AND DUCTWORK. 5. EXISTING GRID, DIFFUSERS, DUCT AND RETURN GRILLS TO REMAIN AS-IS. y ENSURE PROMPT, PROPER, AND SAFE EXECUTION OF WORK. O 2)s'DasKs 4 2PE EXCAVATION AND BACKFILL i ( \ /v DESIGN DRAWINGS I I I ) ACCURATELY GRADE BOTTOM OF TRENCHES TO PROVIDE UNIFORM CONTINUOUS WHITE NOISE CT Oct 20ORE.02021 2 DESIGN DRAWINGS ARE DIAGRAMMATIC AND ONLY DEFINE BASIC FUNCTIONS BEARING AND SUPPORT FOR PIPE. BACKFILL IN SIX INCH (6") MECHANICALLY LEGEND SYSTEM y �P REQUIRED. PROVIDE ALL WORK, MATERIAL, ETC., TO ACCOMPLISH THESE COMPACTED LAYERS, FREE OF ROCKS, WOOD, AND DEBRIS. JETTING IS NOT AN q�tl �O REQUIREMENTS. MINOR DEVIATIONS FROM DESIGN LAYOUT ARE ANTICIPATED AND ACCEPTABLE MEANS OF COMPACTION. ----- gGNEC• ARE A PART OF WORK INCLUDED, HOWEVER, MAKE NO CHANGES THAT ALTER AFP II CHARACTER OF WORK. DO NOT SCALE DESIGN DRAWINGS. ROUGH-IN AND FINAL CONNECTIONS ® NEW 24 X 24 " LAY-IN" CEILING DIFFUSER WITH I RENEWAL DATE: 12/31/2022 MANUAL DAMPER ® BRANCH CONNECTION, II SHOP DRAWINGS THE DRAWINGS INDICATE GENERAL ARRANGEMENTS ONLY. PROVIDE ROUGH-IN AND MATCH EXISTING. FINAL CONNECTIONS FOR FIXTURES AND EQUIPMENT IN ACCORDANCE WITH INDEXED BROCHURE COMPLETELY DESCRIBING MAJOR PRODUCTS AND SYSTEMS (SEVEN HARD BOUND COPIES). MANUFACTURER'S SUGGESTIONS AND PRODUCT REQUIREMENTS. FOR INFORMATION AND COORDINATION ONLY. PROVIDE SUFFICIENT DATA TO DUCTWORK NEW 24 X 24 RETURN GRILLE. MATCH EXISTING EXISTING/—, -- -- - - - e - CONFERE CLEARLY DEFINE THE WORK REQUIRED OF OTHER TRADES FOR PROPER RIGID AND AIRTIGHT. TIGHTLY FITTED JOINTS WITH NO VOIDS. CLOSE MINOR GAPS FI-02-1 HALL HALL INSTALLATION, OPERATION, AND SERVICE OF EQUIPMENT. WITH CANVAS TAPE SET INTO AND SEALED WITH BRUSH APPLIED ADHESIVE, OR WITH — -- 1175'210' F1 0-5-X 105 �OO��CaI"@� 18 SF ,{ SILICONE CAULKING COMPOUND. DO NOT UTILIZE PRESSURE SENSITIVE TAPE. DUCT � "0 SHOP DRAWINGS ARE NOT A FORUM FOR CHANGES IN PROJECT SCOPE OR SEALANT TAPES MUST BE LISTED IN ACCORDANCE WITH UL1818 +54" 100 10"0 NEW 'FLANGE" MOUNTED CEILING DIFFUSER WITH MANUAL DAMPER. MATCH EXISTING 5 00 CF REQUIREMENTS. ® AFF I I I 225 CFM 225 C M BILLING & HELP PART 2 - PRODUCTS THROAT RADIUS OF ELBOWS EQUAL TO DUCT WIDTH OR USE SQUARE ELBOWS WITH TEAM/ EXI NEW TURNING VANES. TRANSITIONS NOT TO EXCEED 4 TO 1 RATIO. EAK TE RAG OFFICE SPACE lu GENERAL SIZES SHOWN ARE NET INSIDE DIMENSIONS. 5'x"' NEW CEILING MOUNTED EXHAUST FAN z xt4.75 1655 2 SF NEW AND UNUSED PRODUCTS OF ESTABLISHED AND REPUTABLE AMERICAN SEAL ALL JOINTS OF DUCTWORK ABOVE ROOF WITH GLASS FIBER TAPE EMBEDDED IN EXISTIN MANUFACTURERS. SIMILAR ITEMS SHALL BE OF SAME MANUFACTURER. ROOFING CEMENT. APPLY SECOND COAT OF CEMENT AFTER FIRST HAS SET AND SUPPLY RM 1X12 FINISH WITH TWO COATS OF ALUMINUM ROOFING PAINT. /IN TU1 11958 SW Garden Place COMPLETE AND OPERABLE SYSTEMS, INCLUDE ANY AND ALL ACCESSORIES ��� NEW DUCTWORK 111111®O /IN 5T — 12" SET OSA TO 105 CFM _ REQUIRED FOR PROPER OPERATION AS THOUGH SPECIFICALLY INDICATED. SUCH AS: SHIP-LAP CUT ALL JOINTS IN FIBERGLASS DUCTWORK, USE METAL REINFORCING AT 126 SF Tigard, OR 97223 FILTERS, CONDENSATE DRAINS WITH VENTED TRAPS, RELIEF VALVES, SERVICE VALVES ALL CONNECTIONS, CLOSE WITH THERMAL ACTIVATED TAPE. O AND STOPS, THERMOSTATS, LOW VOLTAGE WIRING, VIBRATION ISOLATORS, AND ITEMS VOLUME DAMPER 1 I — SPECIFICALLY RECOMMENDED BY MANUFACTURER. CONNECT FLEXIBLE DUCTS TO RIGID TRUNK DUCTS WITH FACTORY FABRICATED i "TJ A ° /� n T D T S FITTINGS WITH DAMPER AND SCOOP (WHERE "TAPINS" SERVE SINGLE OUTLETS, AND 0 N1 XI TIN 2 PERFORMANCEE REQUIRED. THESE QUALIFICATIONS ARE IN ADDITION TO KRIBIS REFERENCE A MANUFACTURER'S PRODUCT IS TO ESTABLISH TYPE, QUALITY, AND WHERE TAP-IN DAMPER IS ACCESSIBLE, OUTLET DAMPER MAYBE OMITTED). SECURE O NEW FACTORY PROGRAMMABLE THERMOSTAT SET OSA TO 200 CFM FLEX DUCT WITH PANDUIT CLAMPS, INSTALLED TO FACTORY RECOMMENDED TENSION. 2T 1 ENGINEER(\G, L.L.C. REQUIREMENTSSHOWN ELSEWHERE. I 123 q1 CLUB WAY.9E.102 TEMPE,ARIZONA 85282 5 8X8 P:(6021393-0201 F:16021393-0202 DUCT INSULATION DRAWN BY: 0 CHECKED BY CM JOB NUMBER,21238 AIR CONDITIONING UNITS I I 1 FOR QUESIKJNB REASE CA L..WKROME96 AIR COOLED DIRECT EXPANSION TYPE UNIT WITH REVERSE CYCLE HEATING. WRAP NO VOIDS AND 4" MINIMUM OVERLAP. SECURE WITH WIRES NOT EXCEEDING DECORATIVE WEATHERPROOF CABINET, ENAMEL FINISH. FACTORY PREWIRED 18" SPACING. ENERGY COMPLIANCE PER 2021 OEESC: I INCLUDING CONTROLS, SAFETIES, MOTOR STARTERS, ETC.. BALANCED CENTRIFUGAL HAL 6 MULTI-SPEED SUPPLY AIR BLOWER, ACCESSIBLE FOR LUBRICATION. VERTICAL APPLY INTERNAL DUCT LINER WITH FULL COVERAGE OF ADHESIVE AND SEAL EDGES, 10 RR DISCHARGE CONDENSER FAN. PROVIDE MECHANICAL FASTENERS AT 16" SPACING. PROVIDE CONTINUOUS Z CLIP EQUIPMENT EFFICIENCY: TUEXI TING OVER LEADING EDGE AT AIR CONDITIONING UNIT DISCHARGE. TUI EX THIS PROJECT UTILIZES ONLY EXISTING HVAC EQUIPMENT WHICH IS EXEMPT FROM IECC MINIMUM O RR 10 REFRIGERANT SYSTEM: HERMETIC COMPRESSORS WITH FIVE (5) YEAR WARRANTY. EFFICIENCY REQUIREMENTS. 5T 2 O COPPER PIPING THROUGHOUT, INCLUDE SERVICE AND CHARGING VALVES, FILTER AIR DISTRIBUTION DEVICES DRYER, HIGH-LOW PRESSURE CONTROLS, REFRIGERANT ACCUMULATOR, AND CONTROLS: 6"0 INSTALL TIGHTLY AND SQUARE WITH BUILDING LINES. VERIFY EXACT POSITIONING OF BILLING 6• CRANKCASE HEATER. ANY NEW THERMOSTAT MUST BE 7 DAY SOLID STATE PROGRAMMABLE THERMOSTAT PER IECC 11 6" CFM Ec ALL DEVICES WITH ARCHITECTURAL DRAWINGS AND NOTES, FLANGED DEVICES SHALL C403.4.2 THROUGH C403.4.2.3. T-STAT MUST BE CAPABLE OF OFF-HOUR AND SET-BACK (25)8'DESKS TOILET EXHAUST FANS 1 0 BE SEALED AIR TIGHT WITH SPONGE RUBBER GASKETS. ADJUST BLADES AND CONTROL, AUTOMATIC SHUT DOWN AND AUTMOATIC STARTUP CONTROL. IF T-STAT DOES NOT — e DAMPERS FOR PROPER AIR DISTRIBUTION AND FLOW. REQUIRE MANUAL CHANGEOVER FROM THE HEATING AND COOLING MODES, IT RESTRICTS SET POINT CEILING MOUNTED, CENTRIFUGAL DIRECT-DRIVE. STATICALLY AND DYNAMICALLY BALANCED. FURNISH WITH OVERLOAD PROTECTION, DISCONNECT, BACKDRAFT COMMISSIONING OVERLAP O N DAMPER. ACOUSTIC LINED HOUSINGS IN UNITS OVER 100 CFM. DUCT AND PLENUM INSULATION AND SEALING VERIFY PROPER POWER TO ELECTRIC MOTORS AND CONTROLS. TEST AND ADJUST ALL NEW SUPPLY AND RETURN AIR DUCTS AND PLENUMS SHALL BE INSULATED WITH A MINIMUM ATO 200 CFM R DUCTWORK CONTROLS AND SYSTEMS AND CONFIRM PROPER OPERATION. OF R-6 INSULATION WHERE LOCATED IN UNCONDITIONED SPACES AND A MINIMUM OF R8 WHERE I AN INDEPENDENT AABC OR NEBB CERTIFIED CONTRACTOR SHALL BALANCE AIR LOCATED OUTSIDE THE BUILDING. WHEN LOCATED INSIDE THE BUILDING ENVELOPE, THE DUCT OR GALVANIZED STEEL. MATERIAL GAGES, JOINTS, SUPPORTS AND BRACING IN LA COMPLIANCE WITH MECHANICAL CODE AND SMACNA RECOMMENDATIONS. DISTRIBUTION TO VALUES LISTED ON DRAWINGS, A FINAL COPY OF THE TEST AND PLENUM SHALL BE SEPARATED FROM THE BUILDING EXTERIOR OR UNCONDITIONED SPACE BY A BALANCE REPORT SHALL BE PROVIDED TO THE ENGINEER UPON COMPLETION OF THE MINIMUM OF R-12 INSULATION. TUt EF REPORT. A PROJECT SHALL NOT BE CONSIDERED IN COMPLIANCE WITH THE PLANS 1 0 2T O 1 FLEXIBLE DUCT FOR AIR CONDITIONING TERMINAL BRANCHES: 1" THICK FIBERGLASS ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS AND CONNECTIONS IN DUCTWORK SHALL BE DUCT SUPPORTED OVER SPRING STEEL WIRE HELIX. WOVEN FIBERGLASS MESH LINER AND SPECIFICATIONS UNTIL SUCH A REPORT HAS BEEN PROVIDED TO THE ENGINEER. SECURELY FASTENED AND SEALED WITH WELDS, GASKETS, MASTICS, OR TAPES. TAPES AND AND FIBERGLASS REINFORCED METALIZED OUTER JACKET. UL-181CLASS 1 AND MASTICS USED TO SEAL DUCTWORK SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL NFPA ( ) BEFORE ACCEPTANCE AND FINAL PAYMENT, IT SHALL BE DEMONSTRATED THAT ALL 181A OR 1818. DUCT CONNECTIONS TO FLANGES OF AIR DISTRIBUTION SYSTEM EQUIPMENT SHALL INS AND 90B. APPARATUS IS FUNCTIONING PROPERLY AND EFFICIENTLY. THE CONTRACTOR SHALL BE SEALED AND MECHANICALLY FASTENED. UNLISTED DUCT TAPE IS NOT PERMITTED AS A MAKE A THOROUGH TEST OF EACH SUPPLY, RETURN, AND EXHAUST SYSTEMS TO DUCT INSULATION ASSURE THAT EACH DIFFUSER AND REGISTER HAS THE PROPER QUANTITY OF AIR IN SEALANT ON ANY METAL DUCTS. I;IHELP ACCORDANCE WITH AABC OR NEBB. DUCTWORKINSULATIONINSULATION VALUES SET FORTH BY THE IECC SHALL SUPERCEDE ANY OTHER L — J (5)5'01 ■ 1 1/2" THICK BY 0.5 PCF FIBERGLASS WITH VAPOR BARRIER BLANKET ON METALLIC - — — — AIR CONDITIONING SUPPLY AND RETURN DUCTWORK BELOW ROOF. 1" THICK THE TEST AND BALANCE CONTRACTOR HAS THE RIGHT TO COMMUNICATE ANY SPECIFICATIONS (INCLUDING MECHANICAL SPECIFICATIONS). NEOPRENE COATED DUCT LINER ON DUCTWORK ABOVE ROOF. INFORMATION TO THE MECHANICAL ENGINEER. -- GRILLES, REGISTERS, AND DIFFUSERS UPON REQUEST OF OWNER, AND AT HIS CONVENIENCE, PROVIDE SUFFICIENT SET OSA TO 105 CFM _v OFFICE COPY QUALIFIED PERSONNEL AND TIME, TO INSTRUCT OWNER OR HIS REPRESENTATIVE IN �•T• X17riL�1Di DIFFUSERS: RECTANGULAR MULTIPLE CONE FIXED PATTERN TYPE (FACE PATTERN THE SAFE AND PROPER OPERATION OF SYSTEMS PROVIDED. HELP TEAM 5 FOR CODE COMPLtA1�tCB SELECTED TO SUIT AIR PATTERN REQUIRED). REMOVABLE CORE/OPPOSED BLADED 114 � VOLUME CONTROL/ENAMEL FINISH. AIR BALANCE REPORT MUST BE PROVIDED TO BUILDING INSPECTOR PRIOR TO OR (39)TDESKS ,Apppmve& [ J I DURING THE FINAL BUILDING INSPECTION. OTC$ I FILTER GRILLES: FIXED PIN-SET BARS A7 APPROXIMATELY 400, WITH HINGED FACE. PROVIDE COPIES OF ALL OPERATION AND MAINTENANCE MANUALS TO OWNER ALUMINUM OR ENAMELED STEEL. " remit AND/OR BUILDING REPRESENTATIVE. TU1 � � 6T OSA VENTILATION CALCULATIONS _ Suite#: _ BASED ON 2019 OMSC TABLE 403.3.1.1 O $�Ij Date-. - `S OUTDOOR AIR RATE IN BREATHING ZONE=RPPZ+RAAZ IMC 2018 403.3.1.1 -403.3.1.3 I �I ' E zow FTS OCC/1080 FTS P Rp R A E RESTROOMS INTERMITTENTLY- 3 WOUR X 70 CFM PER WGUR - = 210 CFM EXHAUST REQUIRED 1 P _ SET OSA TO 200 CFM CORRIDOR- 355 SQ.FT. X 0.06 CFM/SQ.F`E - 21 CFM OSA REQUIRED I STORAGE- 550 SQ.FT. X 0.12 CFAN SQ.FT. - - = 68 CFM OSA REQUIRED � I � I CONFERENCE ROOM- 650 SQ.FT. I IODOX 50 = 33 X 5 + 0.05 X 650 0.8 = 255 CFM OSA REQUIRED _ I ____ _________________________ 1 _____ _____ OFFICE-4400 SQ.FT. / 1000 X 5 = 22 X 5 + 0.06 X 4400 0.8 = 468 OFM OSA REC)URED _. ; ____--_-__ _____________________ __-_ T I CU1 MECHANICAL VENTILATION REWIRED: 810 CFM IMCN18403.3.1.1 RA-AREAOUTDDORRATE W-PEOPLEOWDOORRATE PZ-ZONEPOPIAATIONAZ-ZOFEROORARFA 3T ERVER NOTE: EXISTING LEC Drawing: VENTILATION SYSTEMS SHALL BE BALANCED BY AN APPROVED METHOD. A BALANCE REPORT SHALL VERIFY THAT THE VENTILATION SYSTEM IS I 0 CAPABLE OF SUPPLYING AIRFLOW RATES REQUIRED. A COPY OF THE AIR-BALANCE REPORT MUST BE PROVIDED TO THE MECHANICAL I CONFERENCE I 13 6'"14' MECHANICAL PLAN INSPECTOR FOR FINAL INSPECTION APPROVAL THIS REPORT SHALL BE SEALED,DATED AND WET SIGNED BY A PROFESSIONAL ENGINEER. 84 SF THERE IS AN ADDITIONAL FEE FOR ENGINEER OF RECORD TO WITNESS AND SEAL THIS REPORT j +54" 15'x23' +55"AFF AFF 345 SF AH1 ® 3T .: I MR.SLIM INDOOR UNIT SCHEDULE - BUILDING 1 +12"AFF I MITSUBISHI MODEL# TAG LOCATION TYPE BTU COOLING REMARKS INDOOR WEIGHT Job No: 21065 AH 1 rr ROOM 212 WALL MOUNTED 36,000 MSY-GL36NA-U1 30 LBS. SEE NOTES BELOW. MATCHES CU 1 I© Date: 10/19/2021 I ; 1 NOTES* EXHAUST FAN SCHEDULE Drawn By: - 1. COORDINATE WITH ELECTRICAL CONTRACTOR FOR ELECTRICAL INFORMATION PRIOR TO ORDERING EQUIPMENT. � 1 2. PROVIDE FACTORY CONDENSATE PUMP -MITSUBISHI S13100 MANUF. I OPER. REMARKS �—j� Checked By: - MR.SLIM CONDENSING UNIT SCHEDULE - 24.6 SEER TAG MODEL# rvPe CFM ESP BDD WATTS SONES DRIVE WT. — -------------- ---------------------- I cooK luf Sheet No: TAG SERVES ROOM g�COOLING MITSUBISHI MODEL# OUTDOOR UNIT NOTES: GC-144 CEILING 100 0.25 YES 73 2.0 DIRECT 16 LBS. PROVIDE SEPARATE WALL SWITCH MECHANICAL PLAN CONDENSING WEIGHT CU-1 R ROOM 212 36,000 MUY13L36NA-U1 130 LBS. 1. COORDINATE WITH ELECTRICAL CONTRACTOR AND ELECTRICAL DRAWINGS FOR ELECTRICAL INFORMATION PRIOR TO ORDERING EQUIPMENT SCALE: 3/16" = V.0" M 1 ■ 1 2. PROVIDE WITH FAN SPEED CONTROLLER TO MATCH CFM AND ESP 1. COORDINATE WITH ELECTRICAL CONTRACTOR FOR ELECTRICAL INFORMATION PRIOR TO ORDERING EQUIPMENT.