Loading...
Specifications MEc2a23-a6 g35 OFFICE COPY 1560 1) t m nv-th %t• Sheet 1 Butler Job No. 27-0923-127 Project Kyuramen Date 10/1/23 Consultin , Inc. Client Kaly Construction&Design Subject Cover Page By MEB STRUCTURAL CALCULATIONS RECEIVED Kyuramen Tenant Improvement OCT 0 4 2023 Vent Hood & Architectural Features CITY OF TIGARD 7500 SW Dartmouth Street Suite 150 BUILDING DIVISION Tigard, Oregon for Kaly Design & Construction _Qv, PRO 5�;G Fssi 14855 \ REGJJ E . BV I EXPIRES 12-31-2023 October 1, 2023 These structural calculations are for the supoport of 3 vent hoods and anchoring of interior architectural features for Kyuramen in the building located at 7500 SW Dartmouth Street in Tigard, Oregon. All new structural components were designed in accordance with the 2022 Oregon Structural Specialty Code. The weight of the added components is small compared to the overall building weight and will have no significant impact on the overall building framing, foundation or lateral loading. Butler Job No. 27-0923-127 Project Kyuramen Sheet 2 Date 9/29/23 Consulting, Inc. Client Katy Construction&Design Subject Vent Hood By MEB Vent Hoods Vent Hood 1 1,003 lb Customer Side Vent Hood 2 476 lb Prep Side - Left Vent Hood 3 898 lb Prep Side - Right Hang from added ceiling joists between partition walls • �••N N m u com Vent i Vent Hood 2 � Hood 3 Vent _ , _ Hood1 B3 Beam B1 B2 B3 Span = 9.50 ft 9.50 ft 19.00 ft OH = - ft - ft - ft P1 = 119.0 lb VH3 224.5 lb VH2 250.8 lb VH2 X- P1 = 5.00 ft 5.00 ft 6.50 ft P2 = - lb - lb 250.8 lb X- P1 = - ft - ft 18.33 ft R1 = 56.4 lb 106.3 lb 173.8 lb R2 = 62.6 lb 118.2 lb 327.7 lb Section 800S200-33 800S200-33 (2)800S200-33 MMax 281.8 ft-lb 531.7 ft-lb 1,129 ft-lb fb = 2,576 psi 4,860 psi 5,161 psi OX = 0.026 in 0.050 in 0.210 in = 2L/1.086 Use 800S200-33 Use 800S200-33 Use (2) 800S200-33 Butler Job No. 27-0923-127 Project Kyuramen Sheet 3 Date 10/1/23 Consulting, Inc. Client Kaly Construction&Design Subject Seismic Anchorage By MEB Seismic Anchorage Seismic Loading FP = 0.4 pSnsW (1 + 2z/h) Rp/IP aP = 1.00 RP = 2.50 Ip = 1.00 0 , , per USGS Seismci Hazard Map for SS = 0.94 Lat 45.4530°, Long 122.7537° SOS = 0.770 h = 22.00 ft Vent Hoods Vent Hood 1 Vent Hood 2 Vent Hood 3 W = 1,003 lb 476 lb 898 ;b z = 8.67 ft 8.67 ft 8.67 ft RT°p-' 0.7FP = 155 lb 73 lb 138 lb RTOP = 30.5 lb 14.5 lb 27.3 lb o RBOt = 46.9 lb 22.2 lb 42.0 lb EN`" �- V MMax = 406.2 ft-lb 192.7 ft-lb 363.6 ft-lb RB°t _ bo 00 Section 550S162-43 550S162-43 550S162-43 fb = 7,157 psi OK 3,396 psi OK 6,408 psi OK Japanese Torii Decoration Designed by others Design attachment to wall Component Section Length Unit Wt 1 Qty Weight j Height Wt x Ht i Curved Top Boards14x12 15.5 9.57 2 297 10.29 3,053 Top Beams 8x14 12.21 24.6 1 1 300 9.56 2,871 Mid-Beam 8x8 10.5 13.7 ! 1 144 6.875 989 Posts 12x12 ! 10.25 32.1 2 658 5.125 ' 3,373 Total 1 1,399 7.35 110,286 Trib Wt = 699 lb RTOD z = 7.35 ft 0.7FP = 80 lb � � Brace @ ea post CVo l■� `4 V RTop = 13.4 lb it n I. RBOt = 26.8 lb RB, . MMax = 197.0 ft-lb Stud 550S162-43 fb = 3,471 psi OK Sheet 4 Butler Job No. 27-0923-127 Project Seismic Anchorage Date 10/1/23 Consultin , Inc. Client Kaly Construction&Design Subject Vent Hood By MEB Seismic Anchorage (Cont) Honeycomb Seating Enclosure Framing designed by others Design attachment to floor Component i Section Length ' Unit Wt j Qty Weight i Height Wt x Ht (ft) (plf) _ � - I (lb) 1 ft-lb Upper Steel Frame C4x7.25 23.94 7.25 2 347 9.52 3,305 Upper Joists 2x4 21.21 1.3 8 221 11.5 2,537 Upper Cover 1/2" P/W 9.28 2 ! 1 1 19 12.9 239 Upper Rear Cover 1'/2" P/W 43.1 j 2 1 86 9.52 821 Lower Steel Frame C4x7.25 17 7.25 4 I 493 3.52 1,735 Lower Joists 2x4 17 1.3 12 265 2.92 774 Lower Cover Joists;2x4 3.375 1.3 12 53 6.19 326 Lower Cover 1/2" P/W 16.17 2 1 I 32 6.4 207 Lower Rear Cover 11/2" P/W 42.24 2 1 1 84 3.04 257 Lower Floor Joists 2x4 17 1.3 12 265 0.15 40 Lower Floor Covert/2" P/W 16.17 2 1 32 0.33 11 Total 1 1 1 1,898 5.40 10,251 Int.Cover 12x4 Deck 8.82 7.25 1 ! 4 6.375 28 Int. Floor Frame C4x7.25 3.21 7.25 ! 4 93 9.73 906 Int Floor Joists 2x4 3.21 1.3 11 46 2.92 134 Int. Floor 1/2" P/W 15.38 2 1 31 3.17 i 98 Int. Rear Cover 12x12 41.86 2 1 84 5.92 496 Stairs 2x Treads 13.52 8 1 108 1.59 171 Railing 2x 20.55 4 2 164 4.13 678_ Total Interior ! 530 4.73 2,511 , Ends Interior Trib Wt = 949 lb 1,214 lb z = 5.40 ft 5.26 ft W FP (Ult) = 174 lb (Ult) 221 lb (Ult) MOT = 5,126 ft-lb 6,381 ft-lb V X = 2.67 ft-lb 2.67 ft-lb ROL = 474.4 ft-lb 607.0 ft-lb RBot RE = 1,920 lb 2,390 lb X R 1.1 D + E = 2,442 psi OK 3,058 psi OK R R R 0.9D - E = (1,493) psi OK (1,844) psi OK Use (2) 1/2" x 4" screw anchors See Simpson Anchor designer printout in appendix SIMPSON Anchor Designer TM Company: Butler Consulting,Inc. Date: 10/1/2023 Engineer: Mark Butler Page: 1/5 S Software Project: Kyuramem Version 3.2.2309.2 Address: 12501 SE Scott Screek Lane Phone: (503)970-23256 E-mail: mark@bciengineering.com 1.Project information Customer company: Kaly Design&Construction Project description:Tenant Improvement Customer contact name:Ken Yu Location:7500 SW Dartmouth Street,Tigard,Oregon Customer e-mail: Fastening description:Anchorage to floor Comment:Anchorage of honeycomb seating enclosure 2.Input Data&Anchor Parameters General Base Material Design method:ACl 318-19 Concrete: Normal-weight Units: Imperial units Concrete thickness,h(inch):5.00 State:Cracked Anchor Information: Compressive strength;fe(psi):3000 Anchor type:Concrete screw 4)c,v: 1.0 Material:Carbon Steel Reinforcement condition:Supplementary reinforcement not present Diameter(inch):0.500 Supplemental edge reinforcement:Not applicable Nominal Embedment depth(inch):3.250 Reinforcement provided at corners:No Effective Embedment depth,hef(inch):2.350 Ignore concrete breakout in tension:No Code report:ICC-ES ESR-2713 Ignore concrete breakout in shear:No Anchor category: 1 Ignore 6do requirement:Not applicable Anchor ductility:No Build-up grout pad:No hmm(inch):5.00 cac(inch):3.56 Base Plate Cm;,,(inch): 1.75 Length x Width x Thickness(inch):3.00 x 7.00 x 0.25 Smin(inch):3.00 Recommended Anchor Anchor Name:Titen HD®-1/2"0 Titen HD,hnom:3.25"(83mm) Code Report:ICC-ES ESR-2713 VA 11 \ \ Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com SIMPSON Anchor DesignerTM Company: Butler Consulting,Inc. Date: 10/1/2023 Engineer: Mark Butler Page: 2/5 S Software Project: Kyuramem -�" Version 3.2.2309.2 Address: 12501 SE Scott Screek Lane Phone: (503)970-23256 E-mail: mark@bciengineering.com Load and Geometry Load factor source:ACl 318 Section 5.3 Load combination: not set Seismic design:Yes Anchors subjected to sustained tension:Not applicable Ductility section for tension: 17.10.5.2 not applicable Ductility section for shear: 17.10.6.2 not applicable f!o factor:not set Apply entire shear load at front row:Yes Anchors only resisting wind and/or seismic loads:No Strength level loads: N.[lb]: 1844 Vuax[lb]:205 Vuay[lb]:0 M.[ft-lb]:0 Muy[ft-lb]:0 Muz[ft-lb]:0 <Figure 1> � ems `�- 41, 205 w Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for piausibwty. Svnpson Strong-Tie Company Inc, 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com SIMPSON Anchor DesignerTM Company:Engineer: M ButlearkrButler Consulting,Inc. Date: 10/1/2023 Page: 3/5 Strong-Tie Software Project: Kyuramem Version 3.2.2309.2 Address: 12501 SE Scott Screek Lane Phone: (503)970-23256 E-mail: mark@bciengineering.com <Figure 2> ter; ^� g _,,,,„„_.....„,,,,,,,,,,,,,,,„.„,,,---4-,4*,,*,,,,r':4A„,-;,-;04,i,-Str.:„TV,;7-7;,,'-, --Als-,---M;R:;;;VAlkt. —-- .,-,---,.-1,,,..1,-- 1,-,V.,,e-c-A,z i,e1,,,,,,Kg P"-:'-'-' ,/,:VIt4.-1-,,,-,,,, ,zig.,w.,,W V21-4..to t.,-.4,44-ar,7;,,, ,--,-,Ittp 8 ,:,„„ ke`c.f,,;#4,,''',r j't:',3! ,t1.4,,,r,—, :e4.:t;.4 rtmir.,zia„,,,,,,,,i,,,43--.*:.A„,:rig---,44,7t,-,7,,4-4-4,-..„-_-:,,,,,,f7.1,-,N, 8 `- ? p t a'� e r 00 CO P. Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 wwwstrongtie.com SIMPSON Anchor Designer TM Company: Butler Consulting,Inc. Date: 10/1/2023 Engineer: Mark Butler Page: 4/5 S+ " Software Project: Kyuramem Version 3.2.2309.2 Address: 12501 SE Scott Screek Lane Phone: (503)970-23256 E-mail: mark@bciengineering.com 3.Resulting Anchor Forces Anchor Tension load. Shear load x, Shear load y, Shear load combined, Nua(lb) V.(Ib) Vuay(Ib) 4(Vuax)2+(Vuay)z(Ib) 1 777.6 86.3 0.0 86.3 2 1066.3 118.7 0.0 118.7 Sum 1843.9 205.0 0.0 205.0 Maximum concrete compression strain(%o):0.00 <Figure 3> Maximum concrete compression stress(psi):0 Resultant tension force(Ib): 1844 Resultant compression force(Ib):0 Eccentricity of resultant tension forces in x-axis,e';o(inch):0.37 I Eccentricity of resultant tension forces in y-axis,e'Ny(inch):0.00 Eccentricity of resultant shear forces in x-axis,e'vx(inch):0.38 0 1 Y 2 Eccentricity of resultant shear forces in y-axis,e'vy(inch):0.00 4.Steel Strength of Anchor in Tension(Sec.17.6.1) Nse(Ib) 0 ONsa(Ib) 20130 0.65 13085 5.Concrete Breakout Strength of Anchor in Tension(Sec.17.6.21 Nb=kola''/cherl 5(Eq.17.6.2.2.1) kc Ra f c(psi) her(in) Nb(Ib) 17.0 1.00 3000 2.350 3354 0 t 75 (A•• rA- T • ` ej,N`f'nW Ae Sec.17 5.1 2& 17.6 2.1a).75�P.Cbs- �� ,��, ,goo)�ec.;a w,N. -q. y ANc(in2) ANce(in2) Ca,min(in) Y'ec,N c Wed,N Y'c,N Y'cp,N Nb(lb) ¢ 0.750Ncbg(Ib) 83.19 49.70 - 0.905 1.000 1.00 1.000 3354 0.65 2476 8.Steel Strength of Anchor in Shear(Sec.17.7.1) Vsa(Ib) Ogout 0 tbgroutbVsa(Ib) 4790 1.0 0.60 2874 10,Concrete Pryout Strength of Anchor in Shear(Sec.17=7.31 gVcpg=OkcpNcbg=Okcp(ANc/ANco)Wec,NY'ed,NY'c,N'I'cp,NNb(Sec. 17.5.1.2&Eq.17.7.3.1b) kcp ANC(in2) ANco(in2) Y'ec,N Wed,N y'c,N iF'cp,N Nb(Ib) 0 0Vcpg(Ib) 1.0 83.19 49.70 0.904 1.000 1.000 1.000 3354 0.70 3552 11.Results input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com SIMPSON Anchor Designer TM Company: Butler Consulting,Inc. Date: 10/1/2023 Engineer: Mark Butler Page: 5/5 .0 4 Software Project: Kyuramem Version 3.2.2309.2 Address: 12501 SE Scott Screek Lane • Phone: (503)970-23256 E-mail: mark@bciengineering.com Interaction of Tensile and Shear Forces(Sec.17.8) Tension Factored Load.N.(Ib) Design Strength,oNn(Ib) Ratio Status Steel 1066 13085 0.08 Pass Concrete breakout 1844 2476 0.74 Pass(Governs) Shear Factored Load,V.(Ib) Design Strength,oVn(Ib) Ratio Status Steel 119 2874 0.04 Pass Pryout 205 3552 0.06 Pass(Governs) Interaction check Nua/ONn Vua/OVn Combined Ratio Permissible Status Sec. 17.8.1 0.74 0.00 74.5% 1.0 Pass 1/2"Q Titen HD,hnom:3.25"(83mm)meets the selected design criteria. 12.Warnings -Per designer input,the tensile component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor tensile force associated with the same load combination.Therefore the ductility requirements of ACI 318 17.10.5.2 for tension need not be satisfied—designer to verify. -Per designer input,the shear component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor shear force associated with the same load combination.Therefore the ductility requirements of ACI 318 17.10.6.2 for shear need not be satisfied—designer to verify. -Designer must exercise own judgement to determine if this design is suitable. -Refer to manufacturer's product literature for hole cleaning and installation instructions. Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com