SUBMITTAL
Project
CLARIO
Date
Thursday, September 21, 2023
Project Number
23-615
Contact
MILES HOTZ
Notes
PBC190_CLARIO
Table Of Contents
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
7.5-TON 460 FC 3
Unit Report 4
Certified Drawing 5
Performance Summary 9
Guide Specifications 12
Unit Feature Sheet 28
Spec Sheet 29
Packaged Rooftop Builder 1.75 Page 2 of 29
•
7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
7.5-TON 460 FC
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Guide Specification
Unit Feature Sheet
Spec Sheet
Packaged Rooftop Builder 1.75 Page 3 of 29
Unit Report For 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Unit Parameters Dimensions(ft. in.)&Weight(lb.)'""
Unit Model. 48FCDMO8A2A6-0A0A0 Unit Length. 7'4.125"
Unit Size- 08(7.5 Tons) Unit Width. 4' 11.5"
Volts-Phase-Hertz. 460-3-60 Unit Height 3'5.25"
Heating Type. Gas Total Operating Weight: 886 lb
Heat Control. Low Heat
Duct Cfg. Vertical Supply/Vertical Return "` Weights and Dimensions are approximate. Weight does
DX Options. Single Circuit,Two Stage Cooling not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Gas Line Size. 1/2
Condensate Drain Line Size- 3/4
Return Air Filter Type. Throwaway
Return Air Filter Quantity. 4
Return Air Filter Size. 16 x 20 x 2
Selection includes construction throwaway filter into the base fan curve.
Unit Configuration
Standard/Medium Static(EcoBlue)
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
No optional warranties were selected.
Ordering Information
Part Number Description Quantity
48FCDMO8A2A6-OA0A0 Rooftop Unit 1
Field Installed Accessories
CRRFCURB003A01 14-inch Tall Roof Curb 1
Packaged Rooftop Builder 1.75 Page 4 of 29
Certified Drawing for 7.5-TON 460 FC -
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
NOTES: TARS%/CUNENE IS,RE PROPERTY OF CARRI[[A CORPOIMIR
(/ AND 13 DELIVERER UPOR ERE MISS COMMON,RAT 7XE SOIYISSIOR Or TxESE DIMIIIO3 OA ROCUNEA,e
I.D[NENSIOAR ARE lX INCHES DINE NSIONS \� �COR,ENTS OEE NDi eE 01SCSONEO OR USER WITHOUT CARRIER DOES WOr LCEnANCE TART IER(OIMANCE OR
IX[ I ARE IN N[IL INETEM1S. coRrounox•R nnru cRNsnt Acc(nuc[or colula.
2.9 CENTER OF GRAVITY CONNECTION SIZES
3.*DIRECTION OF AIR FLOW A 1 318' [331 DIA FIELD POWER SUPPLY MOLE
1----10-3/8 B 2 1/2' [641 DIA POWER SUPPLY KNOCKOUT
110261
4.—Q 40FALL VIEW DRAWN USING 3RD ANGLE r C 1 3/4' [511 DIA GAUGE ACCESS PLUG
ECONOMIZER H000 .-7 D 7/8' [221 DIA FIELD CONTROL WIRING HOLE
/OPTIONAL/ 3/4.-14 NPT CONDENSATE DRAIN
UNIT COT P 4 e x 20-3/4 E
con TYPE E ALT. [5271 1/2'-14 NPT GAS CONNECTION
arc xae ..r (W 1rI S4 lrE is,/R CONDENSATE f
[1e/11 [esil nest 36-318 311'-14 NPT GAS CONNECTION
NP sro 4R lre s,re DRAIN OPENING
arciwe AIPr [9251
Isis» (f761 I[/esl IN BASEPAN RETURN AIR ! G 2" [511 DIA POWER SUPPLY KNOCK-OUT
WC.N. At" AWI nib IE1011 - .. . .-- .... •- •-1 2. .a
RTr(-RaRR,NeE.rurEFIRa011UN)ALUNi -_ THRU-THE-BASE CHART (FIELD INST)
�
4 THESE HOLES REQUIRED FOR USE WITH ACCY KITS:
12-5/8 '4. CRBTMPWA002A01:GAS THRU CURB
( ��' "2" CRBTMPMR004A01:GAS THRU BASEPAN
RETURN
! AIR HORIZONTAL THREADED
HOLE
CONDUIT SIZE USE O SE SIZES(MAX.1
y �- PI 1/2'
„2' ACC. 7/8'(22.2]
X 24V 7/B'[22.21
10-3l8 Y 1 1l4' 1002,0011 POWER 1 3/1' II/.1]
W a .— —.my, /' =�� [10271
18-1/2 / 28-3/1
FILTER ACCESS PANEL (4691 � SUPPLY
y 2+ I0011 3l/'FPT GAS 1 3/4'[44.41
[TOOL-LESS) �` - /il I • S APIPR Y[955]8 SUPPLY + 10021 PROVIDES 314'APT THRU CURB
C�\ //d AIR HORIZONTAL
FLANGE A FITTING. HOLE SIZE: 2' 150.81
• CONDENSER 'I \\ ./// Y
COIL (421 f 355]11/ 2
INDOOR COIL k THRU-THE-BASE CHART (FIOP)
ACCESS PANEL H ` + + -- . W _ FOR INGSUFOREONLYE PAX•FACTORY OPTION, I.
( SI FITTINGS FOR ONLY X, Y. d Z ARE PROVIDED. +
SEE L —14 I•"'—2%3-1/8 FOR BELOW LISTED MODELS, AFIELD
Ii THRU-THE-BASE `FLUE •
[3561 [801 SUPPLIED 1/2'ADAPTER IS REQUIRED
[2791 CHART HOOD +' BETWEEN BASE PAN FITTING AND GAS VALVE:
�—IX 29-5/8 1 6-1/4— �—25-3/8 /8FCD,S+08,09
[7511 [1001 [1591 [6431
BACK TOP
E STD.
CONDENSER N 2%I-1/4 CONDENSATE 12-518
AIR ——— 2%[1181 [32] DRAIN --[3211—_
[1181 _
I IELD INSTALLED A
ELECTRICAL CONTROL BOX INDOOR BLOWER I III OPTIONAd.
DISCONNECT ACCESS PANEL ACCESS fiC01p®1IIDm
CONDENSER LOCATION 4�
COIL �1I 0 13-7/8 28-3/8 FILIE'
f 353] [7201
OPTIONAL ( OPTIONAL S I SUPPLY AIR
y FACTORY
INSTALLED ' ( ,9,G 3 FACTORY �1 I I OUTSIDE
CONVENIENCE INSTALLED
Irri
OUTLET (. 27-7/8 • DISCONNECT • pp 26 AIR
OUTSIDEAIR ••'II [7091 it
� -_ [6591�
`� 11-,M HANDLE F ANDLE MO
C [2871 6-1/1 7 BAROMETRIC
[9511 f2081 2%6-518 3T 8-3/B 11601 [177] 5-3// RELIEF
59-112 6-5/8 [9401 12141 5-3/4 37-7/8 11461 FLOW
[15101 88-1/8 [1461 19621
[22381 41-I/8
I10651
LET SUP
AIRPLY VERTICAL 4 *RAIR ETURN
VERTICAL
MONT
ITC CLASSIFICATION SHEET DATE SUPERCEDES 48FC 08-12 SINGLE ZONE ELECTRICAL REV
U.S. ECCN:NSR 1 OF 3 03/12/21 - COOLING WITH GAS HEAT 48TN006295 _
Packaged Rooftop Builder 1.75 Page 5 of 29
Certified Drawing for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Ca er)dn Inn RRO TwaP e a a * tl 1WWAcu
n sMIS NOaT6aea
OTRSTD. UNIT CORNER CORNER CORNER CORNER
UNIT OUTDOOR WEIGHT I WEIGHT IAI WEIGHT IB) WEIGHT(CI WEIGHT (DI C.G. CWPoRATIOIY RTIIN COMM.
COIL TYPE LBS. NO. LBS. KG. LBS. KG. LBS. NO. LBS. K6. X Y 2
48FC-1408 RTPF 781 357 181 82 150 68 207 94 249 113 40 110161 34 1/2(8761 19 3/8 14921
48FC-409 RTPF 868 394 197 89 100 73 229 104 282 128 39 1/2 110031 35(8891 18 5/8 14731
48FC-N12 RTPF 878 398 213 97 175 80 221 100 268 121 39 7/8 110131 33 1/4 18411 18 1/2 14701
RTPT-ROUND TUBE.PLATE FIN(COPPER/ALUMI
RPA STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING. ..J__
FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
BACK WITH _
CORNER A CORNER B ECONOMIZER
I BACK 1
_--� WITHOUT •
///�^ \ I ECONOMIZER ECONOMIZER HOOD
��//� �� I (OPTIONAL/
�`111\
•
II n11II a: 1(( //wit;i.
�;; y l� •
•��' —I LEFT , Li RIGHT
IIh
X
CORNER D CORNER C
TOP 88-1/4 - FRONT
fil. . O I NOTE:
1. FOR ALL MINIMUM CLEARANCES LOCAL CODES OR JURISDICTIONS MAY PREVAIL.
CLEMANCE
II
2 SLRU N COIGJICT1VE BARfl@i IIONC°N3UC71VE BAIRRER G.EARAME
® I ® FRONT 48 I1219mm1 36 [91dmm] 18 [457mm]
_ _ LET 46 E1219mm] 42 I1067mm1 16 C457mm]
S'_- �=�— -et- BACK N/O ECM 48 (1219mm) 02 [1067mm1 18 I457mm1
BACK W/ECON 36 E914mm1 36 1914mm1 18 C457mm]
FRONT RIGHT 36 [914mm1 36 1914mm] 18 I457mm]
TOP 72 [1829mm] 72 [18291101 72 [1829mm1
ITC CLASSIFICATION SHEET DATE SUPERCEDES 48FC 08-12 SINGLE ZONE ELECTRICAL REV
U.S. ECCN:NSR 2 OF 3 03/12/21 - COOLING WITH GAS HEAT d87M006295 -
Packaged Rooftop Builder 1.75 Page 6 of 29
Certified Drawing for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Cwr.I WT REY T TP.S Stl •]ON iV AV5 dTI AAY MOYOA
.... g1'S tiTT[Y9CCSOSEYW TXOY ARI ACCEPTANCE
OF CYYIAACT.
' n 2-114
571
2%1-7/8 !Milk
\ 148] niT _ \�
/,.. -. 84-1/8 - II_�4�F ll.—
.� ,1 • 121561 11.141�_
�� -� (INSIDE THE BASE RAIL 6 SHIRT)
\ , • 2X 7/8 24 2
\ O L [21] 151]
24 1-3/8
1357
� . 2X [25] F•—
Q O / nisi iezil
DETAIL B
AT 2 PLCS
\ • / 53-7I8
[13701
(INSIDE THE BASE RAILS)
\\ ® 952-III
\ . -, O ,- [571 /
\` 2%2 AM." [IB78
151] �RI P.
immmurimnipplai
■ I4818
INSIDE BASERAIL DIMENSIONS I20] I 7/8
[241
BOTTOM
2%1-1/2
/
71
3-1/4
1821 21 11001
DETAIL C
AT 2 PLCS
FIELD INSTALLEI
ELECTRICAL DISCONNECT
LOCATION
FILTER ACCESS PANEL I CONTROL BOX INDOOR BLOWER
(TOOL-LESS) CONDENSER CONDENSER O 111"'
ACCESS PANEL ACCESS PANELCOIL COILOOINDOOR COILI ii
ACCESS PANELQ
•
2-311I601 / 1-3/4
BACK UTT 2-3/ , SEE DETAIL B SEE DETAIL CJ I 1441
TIP CURB TIP CURB
WIDTH WI DTX
7-3/4 73-1/4 7-I/8
1191] 118601 11821
FRONT
ITC CLASSIFICATION SHEET DATE SUPERCEDES 48FC 08-12 SINGLE ZONE ELECTRICAL REV
COOLING WITH GAS HEAT 48TM006295 _
U.S. ECCN: NSR 3 OF 3 03112121 -
Packaged Rooftop Builder 1.75
Page 7 of 29
Certified Drawing for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
8 I 7
6
6 4 I 3 2 7
ROOF CURB A 1.ROO POWER"RING CONTROL WRNG ACCESSORY CONVBIIENCE
ACCEBBORYR I.ROOFCURB ACCESSORY IS SLAPPED 0ISASSEMB.ED. CONNECTOR PKO.ACC. OAS CONNECTION TYPE GAB FTTNG FITTING COMM' OUTLET WIG CONNECTOR
2.INSULATED PANELS:25.411)1NK POLYURETHANE FOAM,44.5[IJHI i DENSITY.
14.CRRFCURSCOSAOI 1 1 3•CIMENSIOHBN[I APE NMB.UMETERS. CRBTMPWR002A01 TMRU THE CURB
4.ROOFCURB:tI GAGE STEEL,
24„ 5.ATTACH DUCTWORK TO CURB.(FLANGES OF DUCT REST ON CURB). 34'(18I NPT 11M'[31.7]NET 1?[12.71 APT VC 112.71 NPT
CRRFCURBOO4A01 PM I,E_ CE CLEARANCE 4 FEET ON EACH SIDE. CRSTMPWRCO4AS+ THRU THE BOTTOM
7, DIRECTION OF AIR FLOW.
I.CONNECTOR PACKAGE CRBTMPMM052Ao1 IS FOR THRLATHECURB GAS TYPE
PACKAGE CRBTMPW*234A01 IS FOR THRUM/SECTION TYPE GAS CONNECTIONS.
D
1 441 ,
144.s1
531?
[135I.I) / T
L-1A0'
6391' - 50.0] (34N' / p5A1
— [7s3.51 12Io.01 (774.7)
r271P SI
I I I I I�2I nAn 12-1?[31T3[WDE ,
T INSULATED DECK PANELS
P15H0'12RA]WDE `.
INSULATED DECK PANEL ��
0 13N
L.3NM (uAI
(10I.0I g 1 0N' �..
_ 144A] �I SECTOR liCN 910E
L, GAS SERVICE PLATE
IITNIRU TIE CURB 15131 •
.........
PINCE
—32EHE' 2'I30® F ! I •- NOTE
(327.1] 51 YP REQUIRASSEMBLED) I Mt1
[207I.3)
_..
T �I (SEE NOTES ...„
I /�\\
1
1 sew
1513NM I RETURN AB3 23,MI' :
pol el 1 SUPPLYNaR oPENx+o (ses s) VIEW"B" �
1I W'�l CORNER DETAIL
7YP
1 3M' -31 17/72' —� 101IA2 G51 1
[44.51 poi [3I2A) (SUPPLED BATH CURB) A
L(FIELD SUPPLIED)
II a&1 1
DUG TYPICAL(4)SIDES 1067
(FIELD SUPPLIED) 7NE' 4'2'
(11j CURTER FLASHINGlimo] \
(FIELD SUPPLIED)
No FELT SEE VIEW'S"'
(FIELD SUPPLIED)
R• siwP CERTIFIED DRAWING
wE RA ! ��o OF1Ho MATERIAL
PRODUCTION M
MI I ORNR1D RElFAEE LEVEL
la
\ �- (FIELD SUPPLIED) TIRO WEE UNLEEE.37NO#S5 EPECEEU ANartrryra.nr
a1ENSKES MR N VMS
PR6NLIR)N�� TOLERANCE!ON:
A I / • _ +DEC 2DEC 3 OEI _...ENO u.+� I E.� ...., i
METES.
A. A- A. 3= na 'Ownvm° incoarcc.NE-snonretmet
/ PESIVIRATEN NUMBER
E
SUPPLE AR RETURN AE INSULATION - 1020120 CURB ASY,ROOF
(FIELD SUPPLIED) - EwEERHO MX LIFEE:1uarB (00I414)
\\ ENgEERINGREOURELENB . -- _ E@ ORAFIEIN SM. REV
j \ V RUC WAS I 7A•,47 WAS 4'2+3/1Sl1 T-005,Y-002 SWIM CIEI Ew SOHJ405012
C 1E GA WAS 15 GA,1513HB'WAS 1515HS NAIL 402/13 MAC 10878YB ME!]11f:• MMC 12NIIW- - D WERT E OF C
FIELD SUPPLIED WAS WITH CURB EURFKi FRIER Ii6PURCN ISOEL MIIFANAIUEE ORM MS DMMNRW EGOS GE1MRd1
REV WINKS RECORD WTI EF GERI APO ECM RO - PURCH N/A
UNCONTROLLED WHEN PRINTED
Packaged Rooftop Builder 1.75 Page 8 of 29
Performance Summary For 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Part Number:48FCDMO8A2A6-0A0A0
ARI EER. 11.20
IEER. 15.0
Base Unit Dimensions
Unit Length- 88.1 in
Unit Width. 59.5 in
Unit Height. 41.3 in
Operating Weight
Base Unit Weight. 743 lb
Accessories
14-inch Tall Roof Curb. 143 lb
Total Operating Weight. 886 lb
Unit
Unit Voltage-Phase-Hertz 460-3-60
Air Discharge. Vertical
Fan Drive Type. Vane Axial
Actual Airflow. 3000 CFM
Site Altitude. 39 ft
Cooling Performance
Condenser Entering Air DB. 90.0 F
Evaporator Entering Air DB. 78.0 F
Evaporator Entering Air WB- 64.4 F
Entering Air Enthalpy. 29.49 BTU/lb
Evaporator Leaving Air DB. 56.8 F
Evaporator Leaving Air WB. 54.6 F
Evaporator Leaving Air Enthalpy. 22.91 BTU/lb
Gross Cooling Capacity. 88.67 MBH
Gross Sensible Capacity- 68.33 MBH
Compressor Power Input 5.87 kW
Coil Bypass Factor 0.157
Mixed Air
Outdoor Air Airflow 420 CFM
Outdoor Air DB. 90.0 F
Outdoor Air WB• 67.0 F
Outdoor Air Htg.Temp. 22.0 F
Return Air DB. 76.0 F
Return Air WB' 64.0 F
Return Air Htg.Temp• 70.0 F
Heating Performance
Heating Airflow. 3000 CFM
Entering Air Temp. 63.3 F
Leaving Air Temp' 95.1 F
Gas Heating Input Capacity. 125.0 MBH
Gas Heating Output Capacity' 103.0 MBH
Temperature Rise- 31.8 F
Supply Fan
External Static Pressure. 0.50 in wg
Fan RPM. 1449
Fan Power 1.11 BHP
NOTE- Selected IFM RPM Range: 1040-2000
Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated.
Packaged Rooftop Builder 1.75 Page 9 of 29
Performance Summary For 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Electrical Data
Voltage Range- 414-506
Compressor#1 RLA. 6.1
Compressor#1 LRA- 60
Compressor#2 RLA. 6.1
Compressor#2 LRA- 60
Indoor Fan Motor Type- MED
Indoor Fan Motor FLA(Total). 3
Combustion Fan Motor FLA(ea)- 0.25
Power Supply MCA. 19
Power Supply MOCP(Fuse or HACR). 20
Disconnect Size FLA. 19
Disconnect Size LRA- 128
Electrical Convenience Outlet. None
Outdoor Fan[Qty/FLA(ea)]. 2/0.8
Control Panel SCCR:5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 85.3 82.0 85.6
125 Hz 81.1 76.0 84.7
250 Hz 74.2 69.1 80.5
500 Hz 71.3 64.0 76.0
1000 Hz 72.5 64.1 72.4
2000 Hz 68.0 57.7 68.0
4000 Hz 63.1 50.7 62.8
8000 Hz 54.1 46.2 59.3
A-Weighted 76.3 68.6 79.0
Advanced Acoustics
0Ank
IS 0
'3
4 i ,® g
s
Advanced Accoustics Parameters
1. Unit height above ground. 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground. 5.7 ft
4. Height of obstruction- 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
Packaged Rooftop Builder 1.75 Page 10 of 29
•
Performance Summary For 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Octave Band Center Freq.Hz 63 125 250 500 1k 2k 4k 8k Overall
A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space,an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
FanCurve
20 \ 1EOCRPMll
14oQZPMI 18IRRA 2 O:RPM
\IXCRANI 220CITIVI\
15 \ \ \
100CRPM \ \ \
N _ \ \ \ \ 3.006
y 11)
N
a
U 80JF2PA4 \ \
05 607FPM 200BFP-
1.50BI P
QO 05 10 15 20 25 30 35 40
AirfloW(CFM-thousands)
RPM=1449BHP=1.11 Maxim unRPM=2200MaximumBHP=3.00
SC-SystemCurveRP-RatedPoint
Packaged Rooftop Builder 1.75 Page 11 of 29
•
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Packaged Rooftop Builder 1.75 Page 12 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Note about this specification:
This specification is in the"Masterformat"as published by the Construction Specification Institute. Please feel free to copy this specification directly into
your building spec.
Cooling Only/Electric Heat Packaged Rooftop
HVAC GuideSpecifications
Size Range:7.5to 15 Nominal Tons
Carrier Model Number. 50FC*08-16
(230680)Schedulesfor Decentralized HVAC Equipment
(23 0680.13)Decentralized Unitary HVAC Equipment Schedule:
(2306 80.13.A.)Rooftop unit(RTU)schedule:
1. Schedule is perthe project specification requirements.
(230716)HVAC equipment insulation
(23 0716.13)Decentralized,Rooftop Units:
(230716.13.A.)Evaporatorfan compartment:
2 Interiorcabinetsurfaces shall be insulated with a minimum 1/2 in. thick,minimum 1 1/2 lb density, flexiblefiberglass
insulation bonded with a phenolic binder,neoprene coated on theairside.
2 Insulation and adhesive shall meet NFPA 90A requirements forflame spread and smoke generation.
(230716.13.B.)Electric Heat Compartment:
3 Aluminum foil-facedfiberglass insulation shall be used.
3 Insulation and adhesive shall meet NFPA 90A requirements forflame spread and smoke generation.
(230913)Instrumentation and control devices for HVAC
(230913.23)Sensors and Transmitters:
(2 3 0913.23.A.)Thermostats:
4. Thermostat must
a energize both"W"and"G'when calling for heat.
b. have capability to energize 1 or2 stages of cooling,and 2 d ifferent stages of heating.
c. include capability for occupancy scheduling.
(230923)Direct Digital Control system for HVAC
(230923.13)Decentralized,Rooftop Units:
(23 0923.13.A.)SystemVu TM intelligent integrated Direct Digital Control(DDC)shall provide:
1. Integrated unit operation for comfort cooling,heating ventilation as well as all monitoring,recording and reporting
capabilities. Controller shall also provide diagnostics and alarms of abnormal unit operation through the controller.
Controller shall have an intuitive user display and be able to be used in a standabne operation or via building automation
system(BAS).
2 Quick Unit Status LEDs of: RUN—meaning all systems are go, ALERT—thatindicatesthere is currently a non-critical
issue with the unit, like filters need to be replaced and FAULT—that indicates the unit has a critical issue and will possibly
Packaged Rooftop Builder 1.75 Page 13 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
shutdown.
3 Six large navigation keys foreasyaccess.Navigation keys shall consist of:TEST, BACK,ENTER,and MENU along with
UP and DOWN arrows.
4. Full back lit user display with 4 line by 30 character text capabilities.Display menu shall be designed to provide guided
major menus and sub menus main menus provided below:
a Shutdown Unit
b. Run Status
c Settings
d. Alerts/Faults
e Service
f. Inputs
g. Outputs
h. USB
5 The capability forstandabne operation with conventional thermostat/sensor or use with building automation systems(BAS)
of Carrier i-Vu®, BACnet MS/PT and Carrier Comfort Network® (CCN)systems. No special modules or boards are
required forthese capabilities.Has the capability to work with Equipment Touch TM and System Touch TM devices and ZS
Sensors.
6 The ability to read refrigerant pressures at display or via BAS network of;Discharge Pressure and Suction Pressure.The
need fortraditional refrigerant gages is not required.
7. USB Data Port for flash drive interaction.This will allow the transfer of data for uploads,downloads,perform software
upgrades,back-up and restore data and filetransferdata such as component numberof starts and run hours.
8 Reverse Rotation Protection of compressors if field three phasewiring is misapplied.
9 Provide Service Capabilities of:
b. Auto run test
c Manual run test
d. Component run hours and starts
e Commissioning reports
a Data logging
f. Alarm history
10. Economizer control and diagnostics.Set up economizer operation,receive feedback from actuator. Also meets the most
recent Califomia Title 24,ASHRAE 90.1 and I ECC Fault Detection and Diagnostic(FDD)requirements.
11. Unit cooling operation down to40°F(4°C)[0°F(-18°C)forsize 14 models].
12 Controller shall have easy access connections around the controller perimeter area and consist of Mate-N-Lok,terminal
block and RJ style modularjack connections.
13 365 day real time clock,20 holiday schedules along with occupied and unoccupied scheduling.
14. Auto-Recognition foreasy installation and commissioning of devices like economers,space sensors,etc.
15. A 5°F temperature difference between cooling and heating set points to meet the latestASHRAE 90.1 Energy Standard.
16. Contain return airsensor,supply airsensor and outdoor airsensor to help monitor and provide data for the unit comfort
operation,diagnosticand alarms.
17. Use of Carrier'sfield accessory hand-held Navigator TM display,Equipment Touch and System Touch devices.
Packaged Rooftop Builder 1.75 Page 14 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
18. Units with the factory-installed Humidi-MiZer®system option are capable of providing multiple modes of improved
dehumidification as a variation of the normal cooling cycle.
19. Supply Air Tempering control operates the gas or electric heat to maintain a minimum supply airtemperature during
conditions where very cold outdoor aircauses the supply airtemperature to fall below the configured Supply Air
Tempering Setpoint.This occurs during periods where DCV is active and increasing the amount of outdoor air or incases
where the system is operating at very low airflow and the calculated economizer position has increased to maintain a
constant ventilation rate.
20. Demand limiting inSystemVuTM is achieved through set point expansion.The systems heating and cooling set points are
expanded in steps or levels.The degree to which the set points may be expanded is defined by the 6 demand level offsets
and the2 commanded demand limit levels.
21. 3-year limited partwarranty.
(230933)Electric and Electronic Control System for HVAC
(23 09 33.13)Decentralized,Rooftop Units:
(230933.13.A.)General:
1. Shall be complete with self-contained low-voltage control circuit protected by aresettable circuit breaker on the 24—v
transformerside.Transformer shall have75VAcapability.
2 Shall utilize color-coded wiring.
a Shall include a Unit Control Board to conveniently and safely provide connection points for vital control functions such as:
smoke detectors,phase monitor,economizer,thermostat, DDC control options, and low and high pressure switches.
Controller shall also provide an intuitive means to adjust the indoor fan speed through a simple switch and pot adjustment
design.
4 Unit shall include a minimum of one 8-pin screwterminal connection board forconnection of control wiring.
(230933.13.B.)Safeties:
2 Compressor over-temperature,over-current.High internal pressuredifferential.
a Low pressureswitch.
a Low pressure switch shall use different color wire than the high pressure switch.The purpose is to assist the installer
and service technician to correctly wire and ortroubleshootthe rooftop unit.
4. High pressureswitch.
b. High pressure switch shall use different color wire than the low pressure switch.The purpose is to assist the installer
and service technician to correctly wire and ortroubleshootthe rooftop unit.
5 Mixed air auto re-set temperature switch
c. When return airtemperatures get the critical point that can cause compressor reliability issues,this switch will shut
down compression only until the temperature raise accordingly.Switch opens at 60°F(16°C)and closes at 65°F
(18°C).
5 Automatic reset,motorthermal overload protector.
(23 09 93)Seq uence of Operations for HVAC Controls
(230993.13)Decentralized,Rooftop Units:
(230993.13.A.)INSERT SEQUENCE OF OPERATION
(234013)Panel Air Filters
(234013.13)Decentralized,Rooftop Units:
(23 4013.13.A.)Standard filter section:
Packaged Rooftop Builder 1.75 Page 15 of 29
•
• Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By:
09:12AM
1. Shall consist of factory installed,low velocity,disposable 2 in.thick fiberglassfilters of commercially available sizes.
4 Unit shall use only one filter size.Multiple sizes are not acceptable.
5 Filters shall be accessible through a naccess panel with "no-tool"removal as described in the unit cabinet section of this
specification(238119.13.G).
(238119)Self-Contained AirConditioners
(23 8119.13)Small-Capacity Self-Contained Air Conditioners:
(238119.13.A.)General:
2 Outdoor,rooftop mounted,electrically controlled,heating and cooling unit utilizing fully hermetic scroll compressors for
cooling duty and optional electric heat for heating duty.
5 Factory assembled,single-piece heating and cooling rooftop unit.Contained within the unit enclosure shall be all factory
wiring,piping,controls,and special features required prior to field start-up.
6 Unitshall use Purone(R-410A)refrigerant.
6 Unitshall be installed in accordance with the manufacturer's instructions.
6 Unit must be selected and installed in compliance with local,state,and federal codes.
(238119.13.B.)QualityAssurance:
3 Unit meetsASHRAE 90.1 minimum efficiency requirements.
6 Unitshall be rated in accordance with AHRI Standards 340/360.
7. Unit shall be designed to conform toASHRAE 15.
7. Unit shall be UL-tested and certified in accordance with ANSI Z21.47 Standards and UL-listed and certified under
Canadian standards as atotal packageforsafety requirements.
7. Insulation and adhesive shall meet NFPA 90A requirementsforflame spread and smoke generation.
6 Unit casing shall be capable of withstanding 500 hoursalt spray exposure perASTM B117(scribed specimen).
8 Unit shall be desig ned in accordance with ISO 9001,and shall be manufactured in a facility registered by ISO 9001:2015.
9 Roof curb shall be desig ned to conform to NRCA Standards.
10 Unit shall be subjected to a completely automated run test on the assembly line.The data foreach unit will be stored at the
factory,and must be available upon request.
11. Unit shall be designed in accordance with UL Standard 60335-2-40,including tested to withstand rain.
12 Unitshall be constructed to prevent intrusion of snow and tested to prevent snow intrusion into the control box up to 40
13 Unit shake tested to assurance level 1,ASTM D4169 to ensure shipping reliability.
(238119.13.C.)Delivery,Storage,and Handling:
4 Unit shall be stored and handled per manufacturer's recommendations.
7. Lifted by crane requires either shipping top panel or spreader bars.
8 Unit shall only be stored or positioned in the upright position.
(238119.13.D.)Project Conditions:
5 As specified in the contract.
(238119.13.E.)Operating Characteristics:
6 Unitshall be capable of starting and running at 125°F(52°C)ambientoutdoortemperatureexcept 14 size models that are
capable of starting and running at 120°F(49°C),meeting maximum load criteria of AHRI Standard 340/360 at±10%
Packaged Rooftop Builder 1.75 Page 16 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
voltage.
8 Compressor with standard controls shall be capable of operation down to 40°F(4°C) [0°F(-18°C) for size 14 models],
ambient outdoor temperatures.Accessory winter start kit is necessary if mechanically cooling at ambient temperatures down
to 25°F(-4°C)or 0°F(-18°C).
9. Unit shall discharge supply airvertically or horizontally as shown on contract drawings.
8 Unit shall be factory configured for vertical supply and return configurations.
a Unit shall be field convertible from vertical to horizontal airflow on all models. No special kit required except on 16 size
models that requires a Supply Duct Kit field installation for horizontal airflow.
7. Unit shall be capable of mixed operation:vertical supply with horizontal return or horizontal supply with vertical return.
(238119.13.F.)Electrical Requirements:
7. Main powersupplyvoltage,phase,and frequency must match those required by the manufacturer.
(238119.13.G.)Unit Cabinet:
8 Unit cabinet shall be constructed of galvanized steel,and shall be bonderized and coated with a prepainted baked enamel
finish on all externally exposed surfaces.
9. Unit cabinet exterior paint shall be: film thickness, (dry)0.003 in.minimum,gloss(per ASTM D523,60°F/16°C):60,
Hardness:H-2H Pencil hardness.
10. Evaporator fan compartment interior cabinet insulation shall conform to AH RI Standards 340/360 minimum exteriorsweat
criteria. Interior surfaces shall be insulated with a minimum 1/2 in. thick, 1 lb density, flexible fiberglass insulation,
neoprene coated on theairside.Aluminum foil-facedfiberglass insulation shall be used in the heat compartment.
9. Base of unit shall have a minimum of four locations forthru-the-base gas and electrical connections(factory-installed or
field-installed),standard.
9. Base Rail:
a Unit shall have base rails on a minimum of2 sides.
b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging.
c. Holes shall be provided in the base rail for moving the rooftop by fork truck.
d. Base rail shall be a minimum of 16 gage thickness.
a Condensatepanandconnections:
b. Shall be a sloped condensate d rain pan made of a corrosion resistant material.
c Shall comply with ASHRAE Standard 62.
d. Shall use a 3/4 in. 14 NPT drain connection,possible either through the bottom or side of the drain pan.Connection
shall be made per manufacturer's recommendations.
9 Top panel:
c Shall be a single piece top panel on 08-14 models and two piece on 16 size models.
10. Electrical Connections:
d. All unit powerwi ring shall enter un it cabinet at a single,factory prepared,knockout location.
d. Thru-the-base capability.
1) Standard unit shall have athru the-base electrical location(s)using a raised,embossed portion ofthe unit basepan.
2) Optional,factory approved,watertight connection method must be usedforthru-the-base electrical connections.
3) No basepan penetration,otherthan those authorized bythe manufacturer,is permitted.
11. Ccmponentaccesspanels(standard):
Packaged Rooftop Builder 1.75 Page 17 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By:
09:12AM
a Cabinet panels shall be easily removable forservicing.
b. Unit shall have one factory installed,tool-less,removable,filter access panel.
c. Panels covering control box,indoor fan,indoor fan motor,gas components(where applicable),and compressors shall
have molded composite handles.
e Handlesshall be UV modified,composite.They shall be permanently attached,and recessed intothe panel.
e Screws on the vertical portion of all removable access panel shall engage into heat resistant,molded composite collars.
f. Collars shall be removable and easily replaceable using manufacturer recommended parts.
(23 8119.13.H.)Coils:
1. Standard Aluminum Fin-Copper Tube Coils:
a Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to seamless
intemallygrooved copper tubes with all joints brazed.
c Evaporator coils shall be leaktested to 150 psig,pressure tested to 450 psig,and qualified to UL 1995 burst test at
1775psig.
d. Condenser coils shall be leaktested to 150 psig,pressure tested to 650 psig,and qualified to UL 1995 burst test at
1980 psig.
2 Optional Pre-coated aluminum-fin condensercoils:
b. Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments.
b. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between
thealuminumfin andcoppertube.
a Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.
f. Corrosion durability of fin stock shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM
B117-90.
f. Corrosion durability of fin stock shall be confirmed through testing to have no visible corrosion after 48 hour
immersion in a room temperature solution of 5%salt,1%acetic acid.
g. Fin stock coating shall pass 2000 hours of the following:one week exposure in the prohesion chamber followed by one
week of accelerated ultraviolet light testing.Prohesion chamber the solution shall contain 3.5%sodium chloride and
0.35%ammonium sulfate.The exposure cycle is one hour of salt fog application at ambient followed by one hour
drying at 95°F(35°C).
3 Optional Copper-fin evaporatorand condenser coils:
c Shall be constructed of copperfins mechanically bonded tocoppertubes and coppertube sheets.
c Galvanized steeltubesheets shall not beacceptable.
c A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential forgalvanic
corrosion between coil and pan.
4. Optional E-coated aluminum fin evaporatorand condensercoils:
d. Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridging
betweenfins.
d. Coating processshall ensurecompletecoil encapsulation oftubes,finsand headers.
d. Color shall be high gloss black with gloss perASTM D523-89.
d. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges.
g. Superior hardness characteristics of 2H per ASTM D3363-92A and cross-hatch adhesion of4B-5B per ASTM D3359-
93.
Packaged Rooftop Builder 1.75 Page 18 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
h. Impact resistance shall be up to 160 in.-lb(ASTM D2794-93).
g. Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively(ASTM D2247-92
and ASTM D870-92).
h. Corrosion durability shall be confirmed through testing to be no less than 1000 hours salt spray perASTM B117-90.
(238119.13.1.)Refrigerant Components:
1. Refrigerantcircuitshall include the following control,safety,and maintenance features:
a Thermostatic Expansion Valve (TXV)shall help provide optimum performance across the entire operating range.Shall
contain removablepowerelementtoallowchange out of power element and bulb without removing the valve body.
e Refrigerant filter drier—Solid core design.
e Service gage connections on suction and discharge lines.
e Pressure gage access through a speciallydesigned access portin thetop panel ofthe unit.
2 Compressors:
b. Unit shall use two tandem scroll compressors on single independent refrigeration circuit.
b. Units shall have single circuitand two stage cooling and contain two dualstage compressors.
f. Evaporator coils shall be a full active design to help better control comfort latent removal.
f. Compressor motors shall be cooled by refrigerant gas passing through motorwindings.
h. Compressors shall be internally protected from high dischargetemperatureconditions.
i. Compressors shall be protected from an over-temperature andoveramperage conditions by an internal, motor
overload device.
h. Compressor shall befactory mounted on rubber grommets.
i. Compressor motors shall have internal line break thermal,current overload and high pressure differential protection.
i. Crankcase heaters shall not be required for normal operating range,unless required by compressor manufacturer due to
refrigerant charge limits.
j. Compressors shall bea two stage cooling capacity design.
(2381 19.13.J.)RetumAirFilterSection:
1. Filters access is specified in the un it cabinet section of th is specification.
2 Filters shall be held in place by a pivoting filtertray,facilitating easy removal and installation.
3 Shall consist of factory installed,low velocity,throw-away 2 in.thick fiberglass filters.
4. Filters shall be standard,commercially available sizes.
5 Only one size filter per unit is allowed.
(238119.13.K.)Evaporator Fan and Motorwith EcoBlueTM Technology:
2 Direct Drive Evaporator fan motor:
a Shall bea ECM motordesign.
b. Shall have permanently lubricated bearings.
c. Shall have inherent automatic-resetthermal overload protection.
d. Shall have slow ramp up to speed capabilities.
e Shall require no fan/motor belts for operation,adjustments and or initial fan speed set up.
j. Fan DC voltage set up on Unit Control Board can eliminate the need of removal of bloweraccess door,required on
Packaged Rooftop Builder 1.75 Page 19 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
conventional belt drive systems.
i. Shall be internally protected from electrical phase reversal and loss.
2 EvaporatorFan:
b. Shall be easily set with dedicated selection switch and adjustment pot on unit control board or through SystemVuTM
controller.
b. Shall provide two stage cooling capacity control,the indoor fan speed is automatically controlled to meet the code-
compliant<66%low fan speed and 100%at full fan speed operation.
d. Blowerfan shall be a Vane Axial fan design with 75%less moving parts than a conventional belt drive system.
e Shall be constructed of a cast aluminum statorand high impact composite material on stator,rotorand air inlet casing.
f. Shall be a patented/pending design with a corrosion resistant material and dynamically balanced.
k Shall have slow ramp up to speed capabilities to help reduce sound and comfort issues typically associated with single
speed beltdrive systems.
j. Shall be a slide out design with removal of a few support brackets.
3 Shall include an easilyaccessible Unit Control Board to conveniently and safely provide connection points for vital control
functions such as:smoke detectors,phase monitor,gas controller,economizer,thermostat, DDC control options,and low,
high and mixed airtemperature switches.Controller shall also provide an intuitive means to adjust the indoor fan speed
through a simple switch and pot adjustment design.
(238119.13.L.)Condenser Fans and Motors:
1. Condenserfan motors:
a Shall be a totally enclosed motor.
c Shall use permanently lubricated bearings.
c. Shall have inherent thermal overload protection with an automatic resetfeature.
f. Shall use a shaft-down design on all sizes.
2 CondenserFans:
b. Shall bea direct-driven propellertypefan.
b. Shall have galvalum blades riveted to steel spider that have corrosion-resistant properties and shall be dynamically
balanced.
(238119.13.M.)Special Features Options and Accessories:
1. Integrated EconoMi$er® IV,EconoMi$er2,and EconoMi$er X Low Leak rate models.(EconoMi$er IV is only available as
afield-installed accessory—this design only allows single speed fan operation.)
a Integrated,gear driven opposing modulating blade design type capable of simultaneous economizer and compressor
operation.
c Independent modules for vertical or horizontal return configuration shall be available.Vertical return modules shall be
available as a factory installed option.
d. Damper blades shall be galvanized steel with compositegears.Plastic or composite blades on intake or return shall not
beacceptable.
g. Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or humidity are
belowset-points.
g. Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for positive air
stream control.
I. Standard leak rate shall be equipped with dampers notto exceed 2%leakage at 1 in.wg pressure differential.
Packaged Rooftop Builder 1.75 Page 20 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
k Economizer controlleron EconoMi$er IV models shall be Honeywell W7212thatpro-vides:
1) Combined minimum and DCV maximum damper position potentiometers with compressor staging relay.
2) Functions with solid-stateanalog enthalpy or dry bulb changeover control sensing.
3) Contain LED indicates for:when free cooling is available,when module is in DCVmode,when exhaust fan contact
isclosed.
j. Economizer controlleron EconoMi$erX models shall be the Honeywell VV7220that provides:
2) 2-line LCD interface screen for setup,configuration and troubleshooting.
3) On-board Fault Detection and Diagnostics (FDD)that senses and alerts when the economizer is not operating
properly,per California Title 24,ASHRAE 90.1 and IECC.
4) Sensor failure loss of communication identification.
4) Automatic sensordetection.
5) Capabilities for use with multiple-speed orsingle speed indoorfan systems.
6) Utilize digital sensors:Dry bulb and Enthalpy.
j. Economizer controller on EconoMi$er 2 models with SystemVu TM controls shall be a 4 to 20mA design controlled
directly by the controller.SystemVu controller meets California Title 24,ASHRAE 90.1 and IECC Fault Detection
and Diagnostic(FDD)requirements.
k Shall be capable of introducing up to 100%outdoor air.
k Shall be equipped with a barometric reliefdampercapable of relieving up to 100%return air and contain seals that
meetASHRAE90.1 requirements.
I. Shall be designed to close damper(s)during loss-of--power situations with spring return built into motor.
m Dry bulb outdoor airtemperaturesensorshall be provided as standard.Enthalpy sensor is also available on factory
installed only.Outdoor airsensorsetpoint shall beadjustable and shall range from 40°F to 100°F(4°C to 38°C).
Additional sensoroptions shall be available as accessories.
n. The economizer controller shall also provide control ofan accessory powerexhaust unit function.Factory set at 100%,
with a range of 0%to 100%.
o. The economizer shall maintain minimum airflow into the building during occupied period and provide design
ventilation rate forfull occupancy.
p. Dampers shall be completely closed when the unit is in the unoccupied mode.
q. Economizer controller shall accept a 2 to 10 vdc CO2 sensor input for IAQ/DCVcontrol. In this mode,dampers shall
modulate the outdoor air damperto provide ventilation based on the sensor input.
r. Compressor lockout temperature on W7220 control is adjustable from—45°F to 80°F(-43°C to 27°C),set at a factory
default of 32°F(0°C).W7212 control opens at 35°F(2°C)and closes at50°F(10°C).
a Actuator shall be direct coupled to economizer gear.No linkage arms orcontrol rods shall be acceptable.
t. Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan
contact is closed.
2 Integrated EconoMi$er62,and EconoMi$erX Ultra Low Leak rate models.
a Integrated,gear driven opposing modulating blade design type capable of simultaneous economizer and compressor
operation.
b. Independent modules for vertical or horizontal return configuration shall beavailable.Vertical return modules shall be
available as afactory-installed option.
c. Damperblades shall be galvanized steel with compositegears.Plastic orcomposite blades on intake or return shall not
Packaged Rooftop Builder 1.75 Page 21 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By:
09:12AM
beacceptable.
d. Shall include all hardware and controls to provide free cooling with outdoor airwhen temperature and/or humidity are
belowsetpoints.
e Shall beequipped with gear driven dampers for both the outdoor ventilation air and the return air for positive air
stream control.
f. Ultra Low Leak design meets California Title 24 section 140.4 and ASHRAE 90.1 requirements for 4 cfm persq ft on
theoutsideairdampersand 10 cfm persq fton the return dampers.
I. Economizer controller onEconoMi$erX models shall be the Honeywell W7220 that provides:
1) 2-line LCD interface screen for setup,configuration andtroubleshooting.
2) On-board Fault Detection and Diagnostics (FDD)that senses and alerts when the economizer is not operating
properly,per California Title 24,ASHRAE 90.1 and IECC.
3) Sensorfailure loss of communication identification.
4) Automaticsensordetection.
5) Capabilitiesforusewith multiple-speed indoorfan systems.
6) Utilize digital sensors:Dry bulb and Enthalpy.
k Economizer controller on EconoMi$er 2 models with SystemVu TM controls shall be a 4-20mA design controlled
directly by the controller.SystemVu controller meets California Title 24,ASHRAE 90.1 and IECC Fault Detection
and Diagnostic(FDD)requirements.
k Shall be capable of introducing up to 100%outdoor air.
I. Shall beequipped with a barometric reliefdampercapable of relieving up to 100%return air and contain seals that
meetASHRAE90.1 requirements.
I. Shall be designed to close damper(s)during loss-of-power situations with spring return built into motor.
m Dry bulb outdoor airtemperature sensor shall be provided as standard.Enthalpysensor is also available on factory
installed only.Outdoor airsensorsetpoint shall beadjustable and shall range from 40°F to 100°F (4°C to 38°C).
Additional sensoroptions shall be available as accessories.
n. The economizer controller shall also provide control ofan accessory power exhaust unit function.Factory set at 100%,
with a range of 0%to 100%.
o. The economizer shall maintain minimum airflow into the building during occupied period and provide design
ventilation rate forfull occupancy.
p. Dampers shall be completely closed when the unit is in the unoccupied mode.
q. Economizer controller shall accept a 2 to 10 vdc CO2 sensor input for IAQ/DCVcontrol. In this mode,dampers shall
modulatetheoutdoorairdamperto provide ventilation based on the sensor input.
r. Compressor lockouttemperature on W7220 control is adjustable from-45°F to 80°F(-43°C to 27°C),set at a factory
default of 32°F(0°C).W7212 control opens at 35°F(2°C)and closes at50°F(10°C).
s. Actuator shall be direct coupled to economizer gear.No linkage arms orcontrol rods shall be acceptable.
t. Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan
contact is closed.
3 Two-Position Damper(field-installed only):
a Damper shall be a Two-Position Damper.Dampertravel shall be from the full closed position to the field adjustable%-
open set-point.
b. Dampershall include adjustable dampertravel from 25%to 100%(full open).
c Dampershall include single ordual blade,geardriven dampers and actuator motor.
Packaged Rooftop Builder 1.75 Page 22 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By:
09:12AM
d. Actuatorshall be direct coupled to dampergear.No linkage arms or control rods shall be acceptable.
e Damper will admit up to 100%outdoor air for applicable rooftop units.
f. Dampershall close upon indoor(evaporator)fan shutoff and/or loss of power.
m The damperactuatorshall plug into the rooftop unit'swiring harness plug.No hard wiring shall be required.
I. Outside air hood shall include aluminum water entrainmentfilter.
4 Manual damper(field-installed only):
b. Manual damper package shall consist of damper, air inlet screen,and rain hood which can be preset to admit up to
25%or 50%outdoor air for year round ventilation.
5 Humidi-MiZerAdaptive Dehumidification System:
c. The Humidi-MiZer® Adaptive Dehumidification System shall be factory installed and shall provide greater
dehumidification of the occupied space by two modes of dehumidification operations in addition to its normal design
cooling mode:
1) Subcooling mode further sub cools the hot liquid refrigerant leaving the condenser coil when both temperature and
humidity in thespaceare not satisfied.
2) Hot gas reheat mode shall mix a portion of the hot gas from the discharge of the compressor with the hot liquid
refrigerant leaving the condenser coil to create a two-phase heat transfer in the system,resulting in a neutral leaving
airtemperaturewhen only humidity in the space is not satisfied.
3) Includes lowambient controller.
6 LowAmbient Control Package:
a Controller shall control coil head pressure by condenser fan speed modulation or condenser fan cycling and wind
baffles.
b. Shall consist of solid-state control and condenser coil temperature sensor to maintain condensing temperature between
90°F(32°C)and 110°F(43°C)at outdoor ambient temperatures down to 0°F(-18°C).
7. CondenserCoil Hail Guard Assembly:
b. Shall protect against damage from hail.
c. Shall be either hood style or louvered.
8 Unit-Mounted,Non-Fused Disconnect Switch(Available on 7.5 to 12.5 ton units with MOCPs of 80amps orless,or 15 ton
units with MOCPs of 100 amps or less):
c. Switch shall be factory installed,internally mounted.
d. National Electric Code(NEC)and UL approved non-fused switch shall provide unit power shutoff.
c. Shall be accessible from outside the unit.
d. Shall provide local shutdown and lockout capability.
e Sized only for the unit as ordered from the fac-tory.Does not accommodate field-installed devices.
9. Convenience Outlet:
d. Poweredconvenienceoutlet
1) Outlet shall be powered from main line powerto the rooftop unit.
2) Outlet shall be powered from line side or load side of disconnect by installing contractor,as required by code. If
outlet is powered from load side of disconnect, unit electrical ratings shall be UL certified and rated foradditional
outletamperage.
3) Outlet shall befactory-installed and internally mounted with easily accessible 115-vfemale receptacle.
Packaged Rooftop Builder 1.75 Page 23 of 29
•
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
4) Outlet shall include 15 amp GFI receptacleswith independent fuse protection.
5) Voltage required to operate convenience outlet shall be provided by a factory installed step-down transformer.
6) Outlet shall be accessible from outsidethe unit.
7) Outlet shall include afield installed"Wet in Use"cover.
b. Factory-Installed Non-Poweredconvenienceoutlet.
2) Outlet shall be powered from a separate 115/120v power sou rce.
2) Atransformershall not be included.
4) Outlet shall befactory-installed and internally mounted with easily accessible 115-vfemale receptacle.
5) Outlet shall include 15 amp GFI receptacles with independent fuse protection.
6) Outlet shall be accessible from outsidethe unit.
7) Outlet shall include afield installed"Wet in Use"cover.
c Field-Installed Non-Powered conven ience outlet.
3) Outlet shall be powered from a separate 115/120v power source.
3) Atransformershall not be included.
3) Outlet shall be field-in stalled and internally mounted with easily accessible 115-v female receptacle.
6) Outlet shall include 20 amp GFI receptacles.This kit provides a flexible installation method which allows code
compliance for height requirements of the GFCI outlet from the finished roof surface as well as the capability to
relocate the outletto a more convenient location.
7) Outlet shall be accessible from outsidethe unit.
8) Outlet shall include a field installed"Wet in Use"cover.
10. Thru-the-Base Connectors:
a Kits shall provide connectors to permit gas and electrical connections to be brought to the unit through the unit
basepan.
b. Minimum offour connection locations per unit.
11. Supply Duct Cover(size 16 only):
b. Required when field converting the factory standard vertical duct supply to horizontal duct supply configuration.One
required per unit.
12 Propeller Power Exhaust:
c. Power exhaust shall be used in conjunction with an integrated economizer.
c Independent modules for vertical or horizontal return conflgurations shall beavailable.
c Horizontal power exhaust shall be mounted in return ductwork.
d. Power exhaust shall be controlled by economizer co ntrolleroperation.Exhaust fans shall be energized when dampers
open past the 0to 1 00%adjustable setpointon the econom¢ercontrol.
1a Roof Curbs(Vertical):
d. Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the exhaust air
without supply aircontamination.
d. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weig ht.
d. Permits installation and securing of ductwork to curb priorto mounting unit on the curb.
Packaged Rooftop Builder 1.75 Page 24 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By:
09:12AM
14. OutdoorAir Enthalpy Sensor:
e The outdoor air enthalpy sensor shall be used to provide single enthalpy control.When used in conjunction with a
return air enthalpy sensor,the unit will provide differential enthalpy control.The sensor allows the unit to determine if
outside air is suitable for free cooling.
15. Retum Ai r Enthalpy Sensor:
f. The return air enthalpy sensor shall be used in conjunction with an outdoor a i r enthalpy sensor to provide differential
enthalpycontrol.
16. Indoor Air Quality(CO2)Sensor:
g. Shall be able to provide demand ventilation indoor air quality(IAQ)control.
a The IAQ sensor shall be available in duct mount,wall mount,or wall mount with LED display.The setpoint shall have
adjustment capability.
17. Smoke detectors(factory-installed only):
h. Shall beafour-wire controller and detector.
f. Shall be environmental compensated with differential sensing for reliable,stable,and drift-free sensitivity.
a Shall use magnet-activated test/reset sensorswitches.
e Shall havetool-less connection terminal access.
a Shall have a recessed momentary switch fortesting and resetting the detector.
f. Controllershall include:
1) One set of normally open alarm initiation contacts for connection to an initiating device circuit on a fire alarm
control panel.
2) Two Form-C auxiliary alarm relays for interface with rooftop unit or other equipment.
3) One Form-C supervision(trouble)relay to control the operation ofthe Trouble LED on a remote test/reset station.
4) Capable of direct connection totwo individual detector mod ules.
5) Can be wired to up to 14 other duct smoke detectors for multiple fan shutdown applications.
18. Winter Start Kit:
a Shall contain a bypass device around the low pressure switch.
b. Shall be required when mechanical cooling is required down to 25°F(-4°C).
c. Shall not be required to operate on an economizer when below an outdoor ambient of40°F(4°C).
19. Time Guard:
b. Shall prevent compressor short-cycling by providing a 5 minute delay(±2 minutes)before restarting a compressor after
shutdown for any reason.
c. One device shall be required per compressor.
20. Disconnect Switch Bracket(size 16 only):
c. Provides a pre-engineered and sized mounting bracket for applications requiring a unit mounted fused and non fused
disconnect of greaterthan 100 amps.Bracketassures that no damage will occur to coils when mounting with screws
and otherfasteners.
22 HingedAccess Panels:
d. Shall provide easy accessthrough integrated quartertum latches.
d. Shall be on major panels of:filter,control box,fan motor,and compressor.
Packaged Rooftop Builder 1.75 Page 25 of 29
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
22 Condensate overflow switch:
e This sensor and related controller monitors thecondensate level in the drain pan and shuts down compression
operation when overflow conditions occur.It includes:
1) Indicator light—solid red(morethan 10seconds on water contact—compressors disabled), blinking red(sensor
dis-connected).
2) 10second delay to break—eliminates nuisance trips from splashing orwaves in pan(sensorneeds 10seconds of
constantwatercontact before tripping).
3) Disablesthe compressors operation when condensate plug is detected,but still allows fans to run for Economizer.
23. 4 in.MERV-13 Return Air filters:
a Factory option to upgrade standard unit filters to 4 in. MERV-13 filters.Filter media is secu rely fasted inside the filter
frame on all four sides.
24. 4 in.filter rack kit:
b. The 4 in.filter rack accessory kit is designed to hold 4 in.MERV-8 or MERV-13 filters.Filters not included in kit.
25. 2 in.MERV-13 Return Air filters:
c. Accessory kit to field upgrade standard unit filters to 2 in.MERV-13filters.
26. 2 in.MERV-8 Return Air filters:
d. Accessory kitto field upgrade standard unit filtersto2 in.MERV-8filters.
27. Phase Monitor Control:
e Shall monitorthe sequence ofthree phase electrical system to providea phase reversal protection.
b. Shall monitor thethree p hese voltage inputsto provide a phase loss protection forthe three phase device.
c. Will work on either a Delta or Wye power connection.
28. Horn/StrobeAnnunciator.
f. Provides an audible/visual signaling device for use with factory-installed option or field installed accessory smoke
detectors.
1) Requires installation of a field-supplied 24-vtransformersuitable for4.2 VA(AC)or 3.0 VA(DC)perhom/strobe
accessory.
2) Requires field-supplied electrical box,North American 1-gang box,2 in.(51 mm)x4 in.(102 mm).
3) Shall haveaclearcolored lens.
29. Electric Heat:
a Heating Section:
1) Heaterelement open coil resistance wire,nickel-chrome alloy,0.29 inches inside diameter,strung through ceramic
insulators mounted on metal frame.Coil ends are staked and welded to terminal screw slots.
3) Heaterassemblies are provided with integral fusing for protection of internal heater circuits not exceeding 48amps
each.Auto reset thermo limit controls,magnetic heater contactors(24 v coil)and terminal block all mounted in
electric heater control box(minimum 18 ga galvanized steel)attachedtoendofheaterassembly.
30. UV-C ultraviolet lamp kit:
a High-output,lowtemperature ultraviolet lamp accessory.It includes:
1) 36 in.lamp,interlock switch,mounting brackets,necessary wires,wire ties,screws and labels to field install kit in
unit return air plenum.
4) Separatededicated 115vpowersourcerequired.
Packaged Rooftop Builder 1.75 Page 26 of 29
•
Guide Specification for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
4) UV-C kit can not be used on units with Humidi-MiZersystem.
31. High Short Circuit Current Rating(SCCR)protection:
a Factory-installed option provides high short circuit current protection to each compressor,plus all indoorand out+door
fan motors of 10 kA against high potential fault current situations.(Standard unit comes with 5 kA rating.)
b. This option is not available with factory installed Non-Fused Disconnect, Humidi-MiZersystem, Low Ambient
controls,Phase loss monitor/protection and 575Voltmodels.
Packaged Rooftop Builder 1.75 Page 27 of 29
r
Unit Feature Sheet for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By:
09:12AM
Car'rter
6
0
W tithe r er 48 F wteth.sobhie teciictotogy
.PACKAGED.ROOFTOP GAS.HEATINGIELECTRIC COOLING UNITS—
15.0 JEER 7.5,.8'5-10,12.5,15_TONS
• STANDARD FEATURES-INCLUDE:
•Rated ph accordanceviie/MID,Standards 340/360
•Pisan(R-410A),HFC refrigerant
•Two-stage•cooling,capacity coetrol oh all models
•lEFJYs of Wei",EER aup io 112'
•Exceeds current DOE rEER efficiencies white.-'meeting DOE's new
steogent2023lEEit etlelency requirements
-- ' •2023 DOE,ASHRAE 90 i had itECC.IEEE energy compgine
•Nov Diret:F Eeoeluefm Technology indoor fan syslem'uses'
Vane Joliet fan design and electronically commutated motor indoor
so6lU@,_"f:technology • fan,motor also deivets staged Air Volume(SA11)fan speed control:;
TJ oorinarve composBe:Qorrfensate Perrin accerdanee'irrith AS1.40a
62-Standard,sloping data;side or center drain
•UVre�Brant metering system on all models
410 • Standard coaling operating range up JOIST(52`C),except 14 si4'e
l models with 115 F(46'Cj and doom to 40`F(-4°C),except 14size
.� .. S f models wi h O F(18"9'41Aw Ambient controlsgallows coating operation.
downtooF(=1s'C) .
C!M, �1.;'E •Ere-panled tenor panels and pfiner-coaled interior panels tested to
500 hours;salt spray.proteetron .
•blew tint C9001Board with intuitive tpahic**Pate 4crPislmOnf
•Exclusive 19C solid state conhn'for on-board diagnostcs:with LED
•Induced draft gas•heat combustion desgn
•Redundant One valveswith up to two stages of keeling
WEATHERMAKER@ SERIES o.,,tol.preettheiliigh Plisahrei inched airternperatureswitchproteclion
48FC units are single packaged gat'heating,.eleChlc MAINTENANCE FEATURES:
carti•ng unitsthatare pre-wired and charged with Puron •Acogsspanelswtheasygriphandles
(R-410)refrigerant;The units are factory tested:in both • Innovative easy stadsg,no-ship scram oh unit access pans"
heating and coofeeg modes..All models use two stage •Two-inch disposable return air fifers'and Too(-less tiier access door
cooling capacity control with a iltti.wive evaporator coil •New side aft-vane Axial evaporator-fan system has:no fani bells:
and new Ecobluen4 direct drive ECM Indoor fart system per,blower shaft iilowerbearings
INSTALLATION FEATURES:
•Thru-the lomPa entrycaDai y
Single Pit 9ns and electric connections.
Fed•Fed persneter;base rail with built-in rigging adapters and fork slots
F.ieldconvertiibleholmvertical1 horizontal airflow,16sizerequiresa
Approved and certified by: special supply duct cover kit: ..
STANDARD WARRA•NTY:
AlusZtoC€PiIf:EO. • 10-yearhealei er-15•yearstatatess.steel option.
5=yearcornprassor
he.maw iwws•sme. 3-tear S 4e-Thi u"
nuwnMzru.■ 1-
US 1,74 • Many optional upgrades also available
1.11Z IIIpoya•iocv r
ow*.atna.wpmair
`M. OPTIONS.INCLUDE BItT ARE NOT LIMITED TO:
• Intelligent SystemVu Meleramicating controls
•:Supply"and Return Air Benton Detectors,high static motors
• Louveredtiondenser tint[guards
•Disconnect switch ahOgOrivarsence Outlet options
Stainless Steel:tient exchanger option
ForaebripletafistofoptionsarideccessonesreaeitoProdugtData • Comostonr stantcoicoafing:
• MERV-13.4°Return AirFiters.
•'Patented Humidi-MiZer'adaptive dehumidification system-
•.Hinged access panels
•'Integrated econon ger.system.Low and Ultra tow Leak versions
• Phase*Abe and condensate of erirnm protection
Packaged Rooftop Builder 1.75 Page 28 of 29
Spec Sheet for 7.5-TON 460 FC
Project: CLARIO 09/29/2023
Prepared By: 09:12AM
Packaged Rooftop Builder 1.75 Page 29 of 29