York® Sun TM Pro 3-12.5 Ton ge:14
YORK® Package OCT 16 2023
Single Package R-410A Air Conditioner CITY OF TIGARD
Project Name: Scholls Unit Mo ILDI 1 A3
Quantity: 1 System: ZJ120N18R2B1EAA1A3
Cooling Performance
Total gross capacity 132.4 MBH
Sensible gross capacity 97.2 MBH 111
1 �v
Total net capacity 123.1 MBH
Sensible net capacity 87.9 MBH I ffi:
Efficiency(at ARI) 12.00 EER llf Pi
Integrated eff.(at ARI) 15.00 IEER
Ambient DB temp. 91.8 °F
Entering DB temp. 80.0 °F I
Entering WB temp. 67.0 °F
Leaving DB temp. 57.5 °F
Leaving WB temp. 56.5 °F ib
Leaving air temp dew point 55.90 °F l
Power input(w/o blower) 8.71 kW
Sound power 89 dB(a) i
Refrigerant
Refrigerant type R-410A
Sys1 7 lb 12 oz 10 Ton
Sys2 7 lb 10 oz
Gas Heating Performance • York Sun Pro units are manufactured at an ISO 9001 registered facility and
Entering DB temp. 60 °F each rooftop is completely computer-run tested prior to shipment.
Heating output capacity(Max) 146.0 MBH Unit Features
Supply air 4000 cfm • Two Stage Cooling
Heating input capacity(Max) 180 MBH • 180 MBH Input Aluminized Steel,Two Stage Gas Heat
DB temp. 33.8 F
Air temp.rise 33.8 °F • Full perimeter base rails with built in rigging capabilities
Air
SSE 81.0 % • Unit Cabinet Constructed of Powder Painted Steel,Certified At 750 Hours
Stages 2 Salt Spray Test(ASTM B-117 Standards)
Supply Air Blower Performance • Dry Bulb Low Leak Economizer w/Barometric Relief and Hoods(Bottom or
Supply air 4000 cfm Horizontal End Return Only)with Economizer Fault Detection&Diagnostic
Ext.static pressure 0.6 IWG (Meets ASHRAE 90.1-2013,IECC 2015,California Title 24,AMCA 511).
Addl.Unit Losses(Options/Accessories) 0.58 IWG • Slide-out Blower/3 HP Belt Drive Motor Assembly
Blower speed 1181 rpm • Solid Core Liquid Line Filter Driers
Max BHP of Motor(including service factor) 3.45 HP • Unit Ships with 2"Throwaway Filters
Duct location Bottom
Motor rating 3.00 HP • Replacement Filters:4-(24"x 20").Unit accepts 2"or 4"wide filters.
Actual required BHP 2.94 HP • Single Point Power Connection
Power input 2.74 kW • Through-the-Curb and Through-the-Base Utility Connections
Elevation 203 ft • Short Circuit Current:5kA RMS Symmetrical
Drive type BELT • Return Air Smoke Detector
Requires field-supplied drive true • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin
Electrical Data evaporator coil
Power supply Lk( .3 - • Composite Drain Pan-Front Connection
Unit min circuit ampacity 44.9 A • Tool-free maintenance with features like hinged doors for all-access panels,
Unit max over-current protection 50 A slide-out blower and blower motor tray
Dimensions&Weight BAS Controller
Hgt 51 in Len 89 in Wth 59 in • IntelliSpeed control of the VFD based on stages of cooling.Provides Single
Weight with factory installed options 1285 lb
Clearances Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10.
• Smart Equipment Controller including Discharge Air,Return Air,and Outdoor
Right 12 in Front 48 in Rear 36 in Air Temperature Sensors.
Top 72 in Bottom 0 in Left 36 in Standard Unit Controller: Smart Equipment Control Board
Note: Please refer to the tech guide for listed maximum static pressures • Safety Monitoring-Monitors the High and Low-Pressure Switches,the
�r���CERTIFIED ( i ,����= Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch
CERTIFIED ED ���YYY� ) on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition
Failures,Safety Lockouts and Repeated Limit Switch Trips.
Warranty
• One(1)Year Limited Warranty on the Complete Unit
• Five(5)Year Warranty-Compressors and Electric Heater Elements
• Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger
Information is subject to change without notice.Check local codes. Printed 09/20/2023
OPTIONS: DIMENSIONED AND TOLERENCED PER ANSI YI4.SM.1982 REVISIONS
MATERIAL: 18ga.GALV STEEL REV. ECO# DESCRIPTION DATE APPROVED
INSULATED PANELS (WHERE REQUIRED) Attn: 1 INITIAL DRAWING 3/18/2005 MWG _
1"1.1/2LB DUCT INSULATION (R VALUE 3.85) 2 UPDATED TO HEM CURB 7/26/2022 ES
GASKET PROVIDED WITH CURB
1 1/2"ADDED TO EXISTING CURB O.D. Tag: •
Approval: RETURN
— 48 —
28 ���N� SUPPLY
I ' 1`%
32" _ _ EXISTING CURB LAYOUT ►` ;
INSULATED 57 5/16" /
COVER 3213/16" � �/
44
1 L - /
-y 2015/16" 4%1-
INSULATED yN
21/4 INSULATED
COVER 21/4"
- I COVER
/ f
SUPPLY 49 1/4"
56 7/8" RETURN 59 1/8"
80 5/8" - 50 1/2"
i r .1 F 88 15/16"
5„ I-1 L 1! 1 `z
i 20"
-
L
5" , I ---T
TF- 90 7/16" .-I 4 60 5/8" " ~
THIS DRAWING&THE INFORMATION CONTAINED APPROVALS DATE TRLETILE NAME.
CURB SHOWN IS CDI STANDARD CONFIGURATION CDI RESERVES THE RIGHT TO CHANGE THEREIN IS THE CONFIDENTIAL.PROPRIETARY
INFORMATION OF CRYSTAL DISTRIBUTION INC.. '"", eSaUUderS 7/26/2022
LAYOUT WITHOUT NOTIFICATION.IF CURB IS NEEDED IN A DIFFERENT CONFIGURATION AMAV NOT BE USED ORREPRODUCED 1-3010 5035
WITHOUT THE APPROVAL OF CRYSTAL DISTRIBUTION,INC. °..
CDI MUST BE NOTIFIED PRIOR TO PLACING AN ORDER. ALL RIGHTS RESERVED DIMENSIONS ARE AS FOLLOWS:1.00 In 12S.00 mmI
"VERIFY EXISTING CURB OD .� Contact us APPROXIMATE ECO r.
`VERIFY SUPPLY AND RETURN OPENINGS •ram (4 CURB WEIGHT(LBS.)
OPERATIONAL HEIGHT OF CDI ADAPTER IS 3"LESS THAN OVERALL CURB HEIGHT "NOTE ANY CHANGES �.t..°L. •'i „.t Crn www.cdicurbs.com
SHOWN. "CALL WITH ANY QUESTIONS ^•• or SCALE HEFT"FAX BACK IF DRAWING IS OK AS IS mn -..77 W7.....�.." 1.888.234.7001 1 1 4.72 1:22 I MEET. 1 OF 11
S:\CURBS CURB ADAPTERS\STOCK CURBS HEM\1-3010-5035-HEM\
RECEIVED
O C T 16 2023
CITY OF TIGARD
BUILDING DIVISION
Installation, Operation, and Maintenance
Packaged Rooftop Air Conditioners
PrecedentTM — Gas/Electric
3 to 10 Tons 60 Hz
== 111 ,
itzzi
141414.
•
00,i•
Model Numbers: YSC036G -YSCO6OG YHC072F-YHC102F
Model Numbers: YSC072H -YSC120H YHC120F
Model Numbers: YHC036E -YHC072E YHC037E-YHC067E
Model Numbers: YHC048F-YHCO6OF
ASAFETY WARNING
Only qualified personnel should install and service the equipment.The installation,starting up,and servicing of
heating,ventilating,and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed,adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment,observe all precautions in the literature and on the tags,stickers,and labels that are
attached to the equipment.
January 2021 RT-SVX21AC-EN
t ,
Dimensions and Weights
Unit Clearances necessary to assure adequate serviceability,cataloged
unit capacity,and peak operating efficiency.
Figure 1,p. 18 illustrates the minimum operating and Providing less than the recommended clearances may
service clearances for either a single or multiple unit result in condenser coil starvation, "short-circuiting"of
installation.These clearances are the minimum distances exhaust and economizer airflows,or recirculation of hot
condenser air.
Figure 1. Typical installation clearances for single and multiple unit applications
Side by Side _/i
Note 2 End to End
Note 2,3
All
7,0^ 1829 MM '1 %11111114
' 2134 MM \ �e
ll 1
Notes:
1.For horizontal discharge unit,
this measurement is reduced to
1'6"(457 MM)to minimize duct
extensions.
\3,0„ Atopo.
2.When equippedirelief
with economizer 914 MM
or taro nu relief damper,clearance \ 121distance is to be measured fromprotruding hood instead of base. 111114,..,..11L0
.., MM
3.Clearance Is the same if any unit
is rotated 180°. Note 1
4.Addition clearance required when Single Unit \3'0"
barometric damper or economizer 914 MM
is installed. 3'0"
914MM
\\, t
Note 4 \ • \ /
41 .,.,
41
At'
„I J 411111111,.'
\121/2" 12.. \163/4"
�„ 318\ /,305 MM 426 M\
232 MM
YSC036-060G&YHC036,YHC037E Units YSC072-120H,YHC048-120F,YHC047-067E Units
18 RT-SVX21 AC-E N
t
Dimensions and Weights
WARNING Figure 2. Corner weights
Center of Gravity
Heavy Objects! I. Length
Failure to follow instructions below or properly lift unit A - — B
could result in unit dropping and possibly crushing Center
operator/technician which could result in death or Gravity G
serious injury,and equipment or property-only damage. W dth
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted.Each of the
cables(chains or slings),hooks,and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables(chains or slings)may
not be of the same length.Adjust as necessary for even
unit lift.
D C
Center of Gravity
AWARNING
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping
and possibly crushing operator/technician which could
result in death or serious injury,and equipment or
property-only damage.Test lift unit approximately 24
inches to verify proper center of gravity lift point.To
avoid dropping of unit,reposition lifting point if unit is
not level.
Table 3. Maximum unit and corner weights(Ibs)and center of gravity dimensions(in.)-gas/electric models
Maximum Model
Unit Weights(a) Corner Weights(b) Center of Gravity(in.)
Tons Model No. Shipping Net A B C D Length Width
3 YSC036G 577 472 193 178 45 55 33 9
4 YSC048G 598 492 205 183 46 58 33 9
5 YSCO6OG 627 522 214 193 52 63 33 10
6 YSC072H 805 710 222 217 121 150 41 22
7.5 YSCO9OH 925 832 253 225 169 185 42 23
7.5 YSC092H 990 847 265 249 173 160 46 21
8.5 YSC102H 1028 927 300 242 203 182 47 22
10 YSC120H 1156 1058 345 242 258 213 41 23
3 YHC036E 607 532 165 137 95 134 31 19
4 YHC048E 858 763 238 200 148 176 40 23
4 YHC048F 806 711 226 199 144 143 44 22
5 YHC060E 917 822 261 218 156 187 40 22
5 YHCO6OF 850 755 239 214 152 151 44 21
6 YHC072E 1025 927 296 198 205 228 41 24
6 YHC072F 965 822 250 245 174 153 47 21
6 YHC074F 1114 1016 334 231 248 202 41 23
7.5 YHC092F 1124 1026 340 233 249 204 41 23
8.5 YHC102F 1133 1035 341 236 253 205 49 23
1.0 YMC120fi 1453 m 1259' 356 371 289 242 54 27
(a)Weights are approximate.
(b)Corner weights are given for information only.
RT-SVX21 AC-E N 19