Plans
_GENERAL NOTES AERIAL VIEW CODE AND STANDARDS ---- 1.ALL WORK SHALL COMPLY WITH 2017 OREGON ELECTRIC SPECIALTY CODE(OESC),2019 OREGON STRUCTURAL SPECIALTY CODE,2017 OREGON RESIDENTIAL SPECIALTY CODE,AND ALL STATE AND LOCAL `, BUILDING AND ELECTRICAL CODES. N 2.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. I S �A f Friend t }A� j 1] C 1TY OF eI , r1 SITE NOTES/OSHA REGULATION 1 1.A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. Orem, UT 84097 2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM. N 800.377.4480 3.THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING ROOF VENTS. �'4 WVVW.BLUERAVENSOLAR.COM 4.ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND ' THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT CONFIDENTIAL-THE INFORMATION THE BUILDING OR STRUCTURE. HEREIN CONTAINED SHALL NOT BE s 4 USED FOR THE BENEFIT OF ANYONE SOLAR CONTRACTOR OFFICE COPY ;, EXCEPT BLUE RAVEN SOLAR NOR # SHALL IT BE DISCLOSED IN WHOLE OR 1.MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730. - h IN PART TO OTHERS OUTSIDE 2.IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PERI. 4' M _` RECIPIENTS ORGANIZATION,EXCEPT THE MANUFACTURER'S INSTALLATION REQUIREMENTS. IN CONNECTION WITH THE SALE AND 3.AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF USE OF THE RESPECTIVE EQUIPMENT, STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE Al-U. WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. 4.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. ,5.CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A SUITABLE SEALING COMPOUND. I. NA---BC E 1-' 13. 6.DC WIRING LIMITED TO MODULE FOOTPRINT W/ENPHASE AC SYSTEM. C Rh 7.ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/SUITABLE WIRING CLIPS. C E 1 I F I E D 8.MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT e —+ AVAILABLE. 9.ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS,AC PV INSTALLATION PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT COMBINERS,AND _ +-1 PROFESSIONAL 111 CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND Scott Gurney FOR THE APPLICATION PER NEC 690.4(B). .›. 1 , #PV-011719-015866 10.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. c- '" 11.TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS(WHEN PROVIDED) - 4 a s CONTRACTOR: IN ACCORDANCE WITH NEC CODE 110.14(D)ON ALL ELECTRICAL CONNECTIONS. * r 1, BRS FIELD OPS EQUIPMENT LOCATIONSOB 800-377-4480 1.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26. ..� a I, .1. 2.EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS w SPECIFIED BY NEC 690.31(A)AND NEC TABLE 310.15(B). ; -- _ C 3.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NECVow# 0 APPLICABLE CODES. t 4.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. w '-' ' Z c Q 0 Q CITY OF TIGARD PROJECT INFOR ATI'N: r` Q IDa � Y NUMBER OF STORIES: I ] • 0 J W LU CONDUIT RUN: Interior ; q 0 E �, c w ECOBEE QTY: 0 Permit# : rin.. ��23 -- OD S. , LIGHT BULB QTY: 0 Address: \D tjL % CO PV METER: Not Required L Suite #: _ DESIGN CRITERIA SITE SPECIFICATIONS SHEET INDEX w w W ROOF TYPE(1)INFORM/ 5ikk Date: ROOF TYPE:Comp m I� t S 23 WIND SPEED: 100 mph CONSTRUCTION-V-B PV1 -COVER SHEET Approved plans o > t u) Lo FRAMING TYPE: Manufactured Truss GROUND SNOW LOAD:40 lb/ft2 ZONING: RESIDENTIAL PV2-SITE PLAN hall be on ob S _ > N y SHEATHING TYPE: OSB WIND EXPOSURE FACTOR: C PV3-ROOF PLAN ) in N 0 V ATTACHMENT: SFM Infinity Flashkit SEISMIC DESIGN CATEGORY: D PV4-STRUCTURAL V Im Q RACKING: Unirac SFM Infinity @ 48"OC Portrait/48"OC Landscape PV5-ELECTRICAL 3-LINE DIAGRAM NUMBER OF ATTACHMENTS:46 SCOPE OF WORK PV6-ELECTRICAL CALCULATIONS DRAWING BY: BELS A ROOF TYPE(2)INFORMATION(IF APPLICABLE): INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM AND ANY PV7 (AVLLOTHERARINSHEETSSASREQURD LOCATIONS Brendan Fillmore ED) *SEE PV4.2 NECESSARY ADDITIONAL WORK NEEDED FOR INSTALLATION. SS-PRODUCT SPEC. SHEETS PLOT DATE April 25, 2023 SYSTEM TO BE INSTALLED INFORMATION: THE ISSUANCE OF A PERMIT .; : UTILITY COMPANY: PROJECT NUMBER: DC SYSTEM SIZE: 8.8 kW DC BASED ON CONSTRUCTION uf Portland General Electric (AGE) 755457 AC SYSTEM SIZE: 6.38 kW AC DOCUMENTS AND OTHER SHEET NAME MODULE TYPE: (22) QCeIIs Q.PEAK DUO BLK ML-G10+400 DATA SHALL NOT PREVENT rti INVERTER TYPE: Enphase IQ8PLUS-72-2-US THE CODE OFFICIAL FROM r'� i . .. PERMIT ISSUER: COVER SHEET 'EQUIRING THE CORRECTION MONITORING: Enphase IQ Combiner 4 X-IQ-AM1-240-4 OF ERRORS. ORSC 105.4 City of Tigard REVISION: PAGE NUMBER 0 PV1 LEGEND . PV SYSTEM SPECIFICATIONS JUNCTION BOX TOTAL NUMBER OF MODULES: 22 FRONT OF HOMEBLUE RAVEN MODULE MAKE AND MODEL: QCells Q.PEAK DUO BLK ML-G10+400 16544 SW FRIENDLY LANE BEAVERTON rM J UTILITY METER MODULE WATTAGE:400W DC ,, 1403 N. Research Way INVERTER MAKE AND MODEL: Enphase IQ8PLUS-72-2-US MSP MAIN SERVICE PANEL Orem, UT 84097 INVERTER TYPE: Microinverter(1 Inverter per PV Module) \INVERTER CURRENT OUTPUT: 1.21A AC \ WWW.BLUERA 800.377.4480 7.4480 AR.COM INVERTER NOMINAL VOLTAGE:240V AC AC DISCONNECT INVERTER WATTAGE: 290W AC CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR LOAD CENTER IN PART TO OTHERS OUTSIDE LC RECIPIENTS ORGANIZATION, CONN CT ON WITH EXCEPT INANDTHE SALE USE OF THE RESPECTIVE EQUIPMENT, SUB SUBPANEL WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. 1St a r__) PVMETER c Ms J TS TRANSFER SWITCH CERTIFIED PV INSTALLATION ESS SUNPOWER ESS PROFESSIONAL Scott Gurney #PV-011719-015866 HUB SUNPOWER HUB+ CONTRACTOR: 0 /// RPO REMOTE POWER OFF BRS HELD OPS �, / 800-377-4480 • 0 FIRE SETBACK WI Ca M fa c �' 0 TRENCHING 0 U D. ® ® CaI Z N o n ® ® ® 1 PROPERTY LINE 0 m I . H op �c ® as ® ® SCALE: 3/32" = 1'-0" .5 c o ch co rn co 00 ea ea ea ea rG —I0 E >, c W W U. cm o N N LE LE Iti Di ,. co .re co LO MM 0 > cn -t V. co � � m N (}n 0 0 V V) - m 40 DRAWING BY: Brendan Fillmore PLOT DATE: April 25, 2023 "'ff+"1:71 ffi 1 :A PROJECT NUMBER: w � � 755457 1.AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER L— -- 2. FOR PRESCRIPTIVE INSTALLATIONS, ROOF ATTACHMENTS SHALL BE SPACED ;. r SHEET NAME: NO GREATER THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. :, °_` SITE PLAN OF A ROOF EDGE, HIP, EAVE, OR RIDGE(OSSC 3111.3.5.3) 3. FOR NON-PRESCRIPTIVE INSTALLATIONS, PLANS WILL BE APPROVED AND REVISION: PAGE NUMBER: STAMPED BY LICENCED ENGINEER AND ALL ATTACHMENT SPACING WILL BE AS 0 p\ /ER SHOWN ON PV4. r V PV SYSTEM SPECIFICATIONS LEGEND TOTAL NUMBER OF MODULES: 22 \ter MODULE MAKE AND MODEL: QCelis Q.PEAK DUO BLK ML-G10+400 • JUNCTION BOX MODULE WATTAGE:400W DC FRONT OF HOME BLUE RAVEN (MD UTILITY METER INVERTER MAKE AND MODEL: Enphase IQ8PLUS-72-2-US INVERTER TYPE: Microinverter(1 Inverter per PV Module) MSP MAIN SERVICE PANEL 1403 N. Research Way.. INVERTER CURRENT OUTPUT: 1.21A AC Orem, UT 84097 INVERTER NOMINAL VOLTAGE:240V 800.377.4480 INVERTER WATTAGE: 290W AC AC AC DISCONNECT VWWV.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION F HEREIN CONTAINED SHALL NOT BE CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR LC LOAD CENTER IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN VVITH THE SALE AND ION CB A SUB SUBPANEL USE OF THETRES RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION AC OF BLUE RAVEN SOLAR LLC. --1 M MSPi 1-IL ' PV METER 1—NIABCEI- PV UNDERGROUND TS TRANSFER SWIT H CERTIFIED G OUND SERVICE LINE C PV INSTALLATION POINT OF INTERCONNECTION ESS SUNPOWER ESS PROFESSIONAL Scott Gurney #PV-011719-015866 ❑ HUB SUNPOWER HUB+ 1 CONTRACTOR: BRS FIELD OPS a A 1' LEI RPO REMOTE POWER OFF 800-377-4480 LfZZZe / FIRE SETBACK ❑ • c o TRENCHING ❑ I Q V o i PROPERTY LINE 0 Z cl N o ❑ FE :,*;1 }, I H m N. Y SCALE: 1/8" = 1'-0" < c a co o r,'': ki1, ;;;1Li aI --1 �� ;el '�� ee Z coC 0 N N f1 E N co � m al 'L0 22 PA r"" r� r� LJ.I LWJ W (u 0 > C° "t (nu) r}, r r}, r' (I) L) 'i > (1) u V 07 - m < c MP1 DRAWING BY: 1 #OF MODULES: 22 AZIMUTH: 180 Brendan Fillmore PITCH: 30 TSRF: 99% PLOT DATE: AREA: 757 ft.2 April 25, 2023 PROJECT NUMBER: 1.AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER 7CJCJ4G7 2. FOR PRESCRIPTIVE INSTALLATIONS, ROOF ATTACHMENTS SHALL BE SPACED NO �J GREATER THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OF A ROOF SHEET NAME: EDGE, HIP, EAVE, OR RIDGE(OSSC 3111.3.5.3) ROOF PLAN 3. FOR NON-PRESCRIPTIVE INSTALLATIONS, PLANS WILL BE APPROVED AND STAMPED BY LICENCED ENGINEER AND ALL ATTACHMENT SPACING WILL BE AS SHOWN ON PV4. REVISION: PAGE NUMBER: 0 PV3 STRUCT URAL INFORMATION: STRUCTURAL NOTES: PV MODULE UNIRAC SFM 2" MICRORAIL UNIRAC SFM 6.5" SPLICE ROOF TYPE(1): 1.AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER �, - ;. '" ROOF TYPE: Comp Shingle SHEATHING TYPE: OSB 2. FOR PRESCRIPTIVE INSTALLATIONS, ROOF ATTACHMENTS _ 1:. BLUE RAVEN SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY FRAMING TYPE: Manufactured Truss NM � FRAMING SIZE: 2x4 @ 24"OC DIRECTION WHERE LOCATED WITHIN 3 FT. OF A ROOF EDGE, U( �II( t, 1403 N. Research Way CEILING JOIST SIZE:2x4 @ 24"OC HIP, EAVE, OR RIDGE(OSSC 3111.3.5.3) y 23" I 48"MAX. LANDSCAPE Orem, UT 84097 3. FOR NON-PRESCRIPTIVE INSTALLATIONS, PLANS WILL BE MAX t 800.37T 84 ATTACHMENT: SFM Infinity Flashkit APPROVED AND STAMPED BY LICENCED ENGINEER AND ALL WVWV.BLUERAV.4480 R.coM RACKING: Unirac SFM Infinity ATTACHMENT SPACING WILL BE AS SHOWN ON PV4. UNIRAC SFM 6.5" SPLICE CONFIDENTIAL-THE @ 48"OC Portrait/48"OC Landscape PV MODULE UNIRAC SFM 2" MICRORAIL HEREINONFICONFIDENTIAL- -THE INFORMATIONSHALL NOT BE USED THE BENEFIT OF ANYONE NUMBER OF ATTACHMENTS:46 None SD FOR THE RAVEN SOLAR NOR I ,.,:� :,::;. .' I SH A N PART T(S)OTO HERS IOUTS DE E OR PV MODULE COUNT: 22 Modules •I:• RECIPIENTS ORGANIZATION,EXCEPT TOTAL ARRAY AREA:448.8 ft2(20.4ft2/panel) , IN CONNECTION WITH THE SALE AND TOTAL ROOF AREA: 2465 18.2%ft2 " USE OF THE RESPECTIVE EQUIPMENT, I' WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. ARRAY/ROOF AREA: 23" 48"MAX. ARRAY WEIGHT: 1,100 lbs lbs/ft2(50 lbs/panel) MAX, PORTRAIT POINT LOAD: LOAD:2.45 ATTACHMENT SPACING- FRONT VIEW NUMBER OF ATTACHMENT POINTS ARE AN ESTIMATE ONLY AND MAY VARY -RACKING ATTACHMENTS TO BE STAGGERED (1%41;:sBC-E-M\D POINT LOAD: 23.91 lbs/attachment `NOTE:LISTED u BASED ON FIELD CONDITIONS.MAXIMUM ATTACHMENT SPACING TO BE FOLLOWED PER SCALE: 3/4"= 1'-0" CERTIFIED ENGINEER OF RECORD SPECIFICATIONS. U N I RAC SFM INFINITY UNIRAC SFM MICRORAIL/SPLICE PV INSTALLATION v� PROFESSIONAL PV MODULE Scott Gurney � - #PV 011719-ION 015866 QCELLS Q.PEAK DUO BLK ML-G10+400 O 'Aldk PORTRAIT CONTRACTOR: PV MODULE �_ BRS FIELD OPS ®� UNIRAC SFM SLIDER �� - 800-377-4480 III OR ROOF STRUCTURE (E) ROOF MODULE Q" SHEATHING -�' —� WIDTH O vim- .. U FLASHING �— _ _ a) Q O v ' (1) 5/16"STAINLESS STEEL LAG BOLT LANDSCAPE 0 m co ci WITH 2-1/2" MIN. EMBEDMENT = �' v a0 AND FLAT WASHER —I 2Y2'MIN. EMBED. / t _ • MODULE 3I0 < c 00 c° 1 _�� ��� WIDTH 1 CG J _ . ao co co e O E >, c W LJ.1 LL ca v o N N MIDDLE/TOP STANDOFF DETAIL ATTACHMENT SPACING- SIDE VIEW z co a c N N RE D SCALE: 1/2"= 1'-0" W O co I= W W 112 gc� o HH SCALE: 3"= 1'-0" � QCELLS Q.PEAK DUO BLK ML-G10+400 O N co,_ PV MODULE N cs co_ `10) V VV) - 0 < UNIRAC SFM TRIMRAIL FLASHING DRAWING BY: Iv Ei Brendan Fillmore UNIRAC SFM SLIDER AND (E) ROOF PLOT DATE: TRIMRAIL ROOF ATTACHMENT "�i SHEATHING April 25, 2023 PROJECT NUMBER: (1) 5/16"STAINLESS STEEL LAG BOLT 755457 WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER 2X" MIN.;EMBED. SHEET NAME: e STRUCTURAL REVISION: PAGE NUMBER B BOTTOM STANDOFF DETAIL (E) BUILDING STRUCTURE 0 PV4 SCALE: 3"= 1-0" (1) 8 AWG THHN/THWN-2,CU.,BLACK(L1) 26.6 A AC (2) 10 AWGTHHN/THWN-2,CU.,BLACK(L1) MAX 13.3 A AC (1) 10 AWG THHN/THWN-2,CU.,BLACK(L1) MAX 13.3 A AC (1) 12-2 TC-ER,THHN/THWN-2,CU. MAX 13.3 A AC .1 C (1) 8 AWG THHN/THWN-2,CU.,RED(L2) 240 V AC (2) 10 AWG THHN/THWN-2,CU.,RED(L 2) 240 V AC J (1) 8 AWG THHN/THWN-2,CU.,WHITE(N) 3 (1) 10 AWGTHHN/THWN-2,CU.,GREEN(EGC) (1) 10 AWG THHN/THWN-2,CU.,RED(L2) 240 V AC (1) 6 AWG BARE,CU(EGC) 240 V AC 2 (1) 10 AWG THHN/THWN-2,CU.,GREEN(EGC) 1NILLIegr' (1) 10 AWGTHHNJTHWN-2,CU.,GREEN(EGC) OR 10 2 UF-B W/G(OR NM-B THHN/THWN-2,SOLID CU. (1) 3/4 INCH EMT EXTERIOR (1) 3/4 INCH EMT EXTERIOR (1) 3/4 INCH EMT(Not Required for UF-B or NM-B Cable) INTERIOR EXTERIOR BLUE RAVEN 1403 N. Research Way Orem, UT 84097 800.377.4480 DESIGNER NOTES: WVWV.BLUERAVENSOLAR.COM ELECTRICAL NOTES: CONFIDENTIAL-THE INFORMATION LOAD SIDE BREAKER IN MSP.INTERIOR POI ALL CONDUIT TO BE RAN AT LEAST 7/6 IN.ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. HEREIN CONTAINED SHALL NOT BE USED FOR AC DISCONNECT TO BE LOCATED WITHIN 10 FEET OF THE UTILITY METER. THE BENEFITN EXCEPT BLUE RAVEN OF ANYONE EN SOLAR NOR SHALL PIT BET DISCLOSEDS IN WHOLE OR (22)QCeIIs Q.PEAK DUO BLK ML-G10+400 RECIPIENTS ORGANIZATION,EXCEPTI (E)225A MAIN SERVICE PANEL ENPHASE IQ COMBINER 4 UL 1703 COMPLIANT IN CONNECTION WITH THE SALE AND (E)200A/2P MAIN BREAKER (SOLARLOAD ONLY) (22) Enphase IQ8PLUS-72-2-US USE OF THE RESPECTIVE EQUIPMENT, 4"x4"x4"PVC JB-1 EZ SOLAR OF BLUE RAVEN SOLAR LLC. UL 1741 COMPLIANT WITHOUT THE WRITTEN PERMISSION PV AC DISCONNECT (E)200A/2P NON-FUSED JUNCTION BOX JUNCTION BOX 111M.172.M. :Al — LOCKABLE,VISIBLE OPEN (N)20A/2P L, ^ JB Li n �B-1 �� /� / `\_\ (1)CIRCUIT OF //NABCEP soa,zaov,2-POLE c `� _ 11 MODULES EGC �EGT�.1 ) (E)LOADS =PV BREAKER TO BE LOCATED NVOY _ AT OPPOSITE END OF BUSSING 15A/2P xY Y CERTIFIED 4.1. FROM MAIN BREAKER V (� (N)35a/2P "/// "ll PV INSTALLATfON ������ � �� � � (N)20A/2P �� ��©: JB-1 (1)CIRCUIT OF PROFESSIONAL ___ EGC • � ♦ EGC � r L2 L2 EGC 4 EGC . EGC' \ � 11 MODULES $CO$GUfOey f #PV-011719-015866 G I 120/2aovac N ® ® __--i 3 2 1 CONTRACTOR: 60HZ 1 PHASE TO UTILITY BRS FIELD OPS GRID 800-377-4480 I 0 V (E)GROUNDING Y , k,.,' Z co p — ELECTRODE(S) �^" " "- I m N. ti •`' y = at co. co IX J CO c0 O ccoo -c o N N Z m c rnci) N N ID i WC O 0 g2 W CU " W ILI m c `` II— W 't ,' ,�AA 'r A; .( X; $ 11 DRAWING BY: 1-/-tri, �F k: '' r 'ff _ ` Brendan Fillmore ' ,. . I , ¢.J . ,k i E, b pi; d' a i � PLOT DATE: tO INTERCONNECTION NOTES '` "" April 25, 2023 705.12(8)(3)THE FOLLOWING METHOD(S) SHALL BE USED TO EI. x ,., ,# I z `f PROJECT NUMBER: DETERMINE THE RATINGS OF BUSBARS: (2)WHERE TWO SOURCES, 4 ;£" ONE A PRIMARY POWER SOURCE AND THE OTHER ANOTHER POWER , „ 755457 SOURCE,ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT SHEET NAME: CONTAINS LOADS, THE SUM OF 125 PERCENT OF THE #' :` , . ELECTRICAL POWER-SOURCE(S)OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUS BAR SHALL NOT r, `.-" REVISION: PAGE NUMBER: EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR. UTILITY COMPANY: Portland General Electric (PGE) PERMIT ISSUER: City of Tigard0 PV5 MODULE SPECIFICATIONS CLCells Q.PEAK DUO BLK ML-G10+400 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(STC) 400 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC MODULE VOC 45.3 V DC STATE Oregon JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 16.6 A AC MODULE VMP 37.13 V DC CITY Beaverton CONDUCTOR(TC-ER,COPPER(90°C))= 12 AWG BLUE RAVEN MODULE IMP 10.77 A DC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING= 30 A MODULE ISC 11.14 A DC ASHRAE EXTREME LOW TEMP(°C) -6 AMB.TEMP.AMP.CORRECTION= 0.91 36 ADJUSTED AMP.= 27.3 > 16.6 1403 N. Research Way VOC CORRECTION -0.27%/°C ASHRAE 2%AVG.HIGH TEMP(°C) Orem, UT 84097 VMP CORRECTION -0.34%/°C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC 800.377.4480 SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(1SC X1.25)= 16.6 A AC WVWVBLUERAVENSOLAR.COM ADJ.MODULE VOC @ ASHRAE LOW TEMP 49.1 V DC NUMBER OF MODULES PER MPPT 11 11 CONDUCTOR(UF-B,COPPER(60°C))= 10 AWG CONFIDENTIAL-THE INFORMATION CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE ADJ.MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 31.7 V DC DC POWER RATING PER CIRCUIT(STC) 4400 4400 USED IN FOR THE INED H ANYONE TOTAL MODULE NUMBER 22 CONDUIT FILL DEBATE= 1 EXCEPT BLUE RAVEN SOLAR NOR AMB.TEMP.AMP.CORRECTION= 0.91 SHALL IT BE DISCLOSED IN WHOLE OR MICROINVERTER SPECIFICATIONS Enphase ICL8+Microinverters STC RATING OF ARRAY 880U IN PART TO OTHERS OUTSIDE POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP; 13.3 13.3 ADJUSTED AMP.= 27.3 > 16.6 RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 16.6375 16.6375 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC USE OF THE RESPECTIVE EQUIPMENT, COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 16.6 A AC WITH OUT OF BLUE THERAVEN SOLAR LLITTEN PERMISSION C. MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 CONDUCTOR(UF-B,COPPER(60°C))= 10 AWG MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB.ARRAY AC CURRENT(IMP) 26.6 MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 6380W AC CONDUCTOR RATING= 30 A CONDUIT FILL DERATE= 0.8 NABCEP AC OVERCURRENT PROTECTION 20 A .91=CORRECTION0 AMP.TEMP. MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. JRISE(V) VEN D(V) %VRISE AMB. ADJUSTED AMP. 2 .91 > 16.6 CERTIFIED CEC WEIGHTED EFFICIENCY 97% VRISE SEC.1(MICRO TO JBOX) 39.6 12 Cu. 1.76 241.76 0.73% N T LAAIO VRISE SEC.2(JBOX TO COMBINER BOX) 45 10 Cu. 1.52 241.52 0.63% COMBINER BOX TO INVERTER RATED AMPS= 26.6 A AC PV INSTALLATION 1 AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 5 8 Cu. 0.21 240.21 0.09% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1,25)= 33.28 A AC Scott Gurney SIO NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 3.49 243.49 1.45% CONDUCTOR(THWN-2,COPPER(75°C TERM.))= 8 AWG #PV-011719-015866 NOMINAL OPERATING AC FREQUENCY 47-68HZAC CONDUCTOR RATING= 50 A MAXIMUM AC POWER 24000NDUIT FILL DEBATE= 1 CONTRACTOR: VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL{NEC 690.54) BRS FIELD O R: MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 26.6 A AC AMB.TEMP.AMP.CORRECTION= 0.91 800-377-4480 MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 45.5 > 33.3 0 N GROUNDING NOTES WIRING&CONDUIT NOTES Z O Cu _ 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. CO co USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE Q a) OO co INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). 2 CO D CD CO USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED �+ THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF 0 E C Ill N PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. Z C 0 0 N N SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. C - L COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND Ia C LL Q CC 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS CC G 4 . PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.46]. REQUIRED. G > O N CO laa 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE 0 > (n 0 } } 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE > CO CO7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE _ a)a) v v V 0 MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(B)(3)(C)]. 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV RESISTANT,AND UL V (/) 2 ) Q 0 GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.0. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/fHWN-2 INSULATED, 90°C RATED, EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. DRAWING BY: 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN 11. 4-WIRE DELTA CONNECTED ET AND UV RESISTANT,RATED FOR 600V EXPOSED. SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE: 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC April 25, 2023 GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) PROJECT NUMBER: 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED:PHASE A OR L1-BLACK,PHASE B OR L2-RED, ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY 755457 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THW W N/THN-2 AND MAY BE USED INSIDE CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] °°USE-2 IS AVAILABLE AS UV WHITE REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. SHEET NAME: 18.IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING ELEC CALCS MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.15]. 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER: 0 PV6 STANDARD LABELS ADDITIONAL LABELS \re' LABEL 1 BLUE RAVEN FOR PV SYSTEM DISCONNECTING MEANS WHERE THE LINE AND LOAD TERMINALS MAY BE ENERGIZED IN THE LABEL 3 ELECTRIC SHOCK HAZARD OPEN POSITION. DUAL POWER SUPPLY IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL 1403 N. Research Way TERMINALS ON THE LINE AND [2017 NEC 690.13(B)] ANYWHERE THAT IS POWERED BY BOTH THE UTILITY Orem, UT 84097 [2020 NEC 690.13(B)] AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PAN LOAD SIDES MAY BE ENERGIZED EL SOURCES:UTILITY GRID AND AND SUBPANELS.(NEC 705.12(8)(3)] 800.377.4480 IN THE OPEN POSITION PV SOLAR ELECTRIC SYSTEM VWVW.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE LABEL 2 USED FOR THE BENEFIT OF ANYONE PHOTOVOLTAIC SYSTEM SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR A AC DISCONNECT A THE DISCONNECTING MEANS AS A POWER SOURCE IN PART TO OTHERS OUTSIDE AND WITH THE RATED AC OUTPUT CURRENT AND THE NOMINAL OPERATING AC VOLTAGE. RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND RATED AC OUTPUT CURRENT 26.62 A 2017 NEC 690.54][ USE OF THE RESPECTIVE EQUIPMENT, (2020 NEC 690.54] WITHOUT THE WRITTEN PERMISSION NOMINAL OPERATING AC VOLTAGE 240�/ OF BLUE RAVEN SOLAR LLc. LABEL 3 NABCEP A IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL ANYWHERE THAT IS POWERED BY BOTH THE UTILITY CERTIFIED DUAL POWER SUPPLY AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL AND SUBPANELS. LABEL 10 PV INSTALLATION SOURCES:UTILITY GRID AND [200NEC 705.12(B)(3)] A PERMANENT PLAQUE OR DIRECTORY TO BE PROFESSIONAL (20220 NEC 705.12(B)(3)J PV SOLAR ELECTRIC SYSTEM LOCATED AT MAIN SERVICE EQUIPMENT DENOTING Scott Gurney POWER TO THIS BUILDING IS ALSO SUPPLIED THE LOCATION OF THE RAPID SHUTDOWN SYSTEM #PV-011719-015866 FROM A ROOF MOUNTED SOLAR ARRAY.SOLAR DISCONNECTING MEANS IF SOLAR ARRAY RAPID SHUTDOWN DISCONNECTING SWITCH IS NOT CONTRACTOR: LABEL 4 ARRAY RAPID SHUTDOWN DISCONNECT IS GROUPED AND WITHIN LINE OF SITE OF MAIN AAPPLY TO THE DISTRIBUTION EQUIPMENT ADJACENT LOCATED OUTSIDE NEXT TO THE UTILITY METER. SERVICE DISCONNECTING MEANS. BRS FIELD OPS TO THE BACK-FED BREAKER FROM THE POWER [2017 NEC 705.10AND 690.56(C)(1)(a)] 800-377-4480 (2o20NEC 705.10AND 69o.ss(C)J POWER SOURCE OUTPUT CONNECTION SOURCE. DO NOT RELOCATE [2017 NEC 705.12(8)(2)(3)(b)J (2020 NEC 705.12(B)(3)(2)] THIS OVERCURRENT LABEL 11 c DEVICE 0 A" PERMANENT PLAQUE OR DIRECTORY TO BE LOCATED AT AC COMBINER PANEL. a) Q U PHOTOVOLTAIC SYSTEM [2017 NEC 110.21(B)] Z COMBINER PANEL [2020 NEC 110.21(B)] 0 m DO NOT ADD LOADS Q a) o °p - M co. ce J � � SUBPANEL Z t}Eo N N UTILITY MAIN (IF INTERCONNECTION AC PV PV COMBINER c co Cl) METER SERVICE PANEL IS MADE HERE) DISCONNECT METER BOX W N li 0 2 2 SOLAR PV SYSTEM EQUIPPEDLABEL 6 O O O O O O p co 22 y BUILDINGS WITH PV SYSTEMS SHALL HAVE A N ; N cos_ WITH RAPID SHUTDOWN PERMANENT LABEL LOCATED AT EACH SERVICE (E) O (It) O O i 1.0 EQUIPMENT LOCATION TO WHICH THE PV SYSTEMS TURN RAPID SHUTDOWN ARE CONNECTED OR AT AN APPROVED READILY (n m Q 0 SWITCH TO THE 0 0 O IF BREAKER "OFF'POSITION TO sawe.Ecrwc VISIBLE LOCATION AND SHALL INDICATE THE LOCATION 4 SHUT DOWN PV SYSTEM wv _s_, OF RAPID SHUTDOWN INITIATION DEVICES. IS USED O 0DRAWING BY: AND REDUCE SHOCK HAZARDEnli (2017 NEC 690.56(C)(1)(a)J IN THE ARRAY (2020NEC 690.56(C„ c..) Brendan Fillmore (iII1) OR PLACARD PLOT DATE: RAPID SHUTDOWN SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT SWITCH FOR April 25, 2023 SWITCH (2017 NEC 690.56(C)(3)] -0 SOLAR PV SYSTEM (2020 NEC 690.56(C)(2)J -0 PROJECT NUMBER: 755457 LABELING NOTES SHEET NAME: 1)LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL LABELS 2)LABELING REQUIREMENTS BASED ON THE 2017&2020 NEC CODE,OSHA STANDARD 19010.145,ANSIZ535. REPRESENTATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED 3)MATERIAL BASED ON THE REQUIREMENTS OF THE AHJ. REVISION: PAGE NUMBER: 4)LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND SHALL NOT BE MAY VARY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON 3 LINE HANDWRITTEN[NEC 110.211 DIAGRAM. 3 LINE DIAGRAM ON PV5 TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. 0 PV7 ,,,...,.,..,, 4,„,„. ,,,,,,,,,,,,,,„., BLUE RAVEN .",,•,,. .,,,,, , ,,...,,,-... ,,,,,,4, LAI< DUO BLK ML-G10+ SERIES : :q,.,..,:,,, C),PEAK DUO BLK ... . ..,......,.. 1403 N.Research Way , ..::,],.... •Mechanical Specification Orem,UT 84097 7IET(ann. hiL_Gio+ SERIES ocells Format 740in k 41.1in 1.26 in(including frame) (1879mm-1045mm-32 mini - t - 800.377.4480 Weight 48 5 lbs(72.014g) i I 1.•Grar.,poen•0.N.,16 F., Ira i VWVW.BLUERAVENSOLAR.COM Front Cover 0.13 in(32 rnm)thermally pre stressed glass s'Ellar ILXI II, F,TI,4- I CONFIDENTIAL-THE INFORMATION with anti-reflection technology 1978396 nee HEREIN CONTAINED SHALL NOT BE 390-410Wp I 132 Cells Back Cover Transparent composite film with black grid 0 I USED FOTRB TL HE BENEFIT OF ANYONE EXCEPUE RAVEN SOLAR NOR 20.9% Maximum Module Efficiency Frame Black anodised aluminium SHALL IT BE DISCLOSED IN WHOLE OR Cell 6,.22 rnonocrystalline 0.ANTUM solar half cells i.....-11 +1.10,8elo+al IN PART TO OTHERS OUTSIDE Junction box 2.09-3,98 in•1.26-2.36 in-0.59-0.71in RECIPIENTS ORGANIZATION,EXCEPT ' I 1:14111 9 0.1.01,41 I.4 11. IN CONNECTION WITH THE SALE AND (53-101mm-3)-60mm.15-18mm).IP67,with bypass diodes , USE OF THE RESPECTIVE EQUIPMENT, Cable 4 mrn:!Solar cable:1-9 a 72,04in(1830 mm).171 z 72.04 In(1830 mml - ; i i . l . ' WITHOUT THE WRITTEN PERMISSION Connector Staubli MCI:1%8 OF BLUE RAVEN SOLAR LLC. MODEL aPEAK DUO 81...K.td1L-G10+I t r....,I--(7--- Dare-, •Electrical Characteristics ,.. POWER CLASS 390 395 '., ., 405 410 MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS,STC(POWER TOLERANCE.5W7-0W) .-..-•.•--: ..-- EIS TC," 135TC' -•.:-",---.',... Bil-C' F1.51C' BST C' CERTIFIED Power at MPP' Poi, [W] 390 426.6 395 432.1 ':".40.0';.; 437.5 405 443.0 410 448.5 1.1 Breaking the 20%efficiency barrier In II CLAN TUM DUO Z Technology with zero gap cell layout Short Circuit Cumant' ,.-, Open Circuit Voltage' I, [A] ..-, .,..-...- 11.01 12.05 11.04 11013 ',-,.70,0-r.. 1211 ,,,....-_,,....E 1110 12.15 1113 12.18 V, M 45.49 45.65 45.52 45.68 ,.„4R.fle,. 45.72 4559 4575 45.62 45.78 PV INSTALLATION PROFESSIONAL boosts module efficiency up to 20.9%. '.:. Current at PAPP i ,„ [A] 10.39 11.37 10.45 11.43 ff0f),:i: 1149 10.56 11.55 10.61 11.61 i Scott Gurney Voltage at MPP V.- M 37.54 37.53 37.81 37.81 :311;09%,,,-, 38.0 Et 3836 38.35 38.63 38.62 #PV-011719-015866 ....„,.....„..„.„.„ Efficiency' n [94] 219.9 2201 a 20.6 2 20.9 2 A reliable investment etfacialltY of P.p,and I,70%t 10%•Brfaciality given for rear side irradiation on top of STC(front side)•According to IEC 60904-1-2according to IEC 647904-3 CONTRACTOR: Inclusive 25-year product warranty and 25-year linear l Measurement tolerances P.....-t 3%;1,,Vs,±5%at SIC,1000W/rn','at BSTC 1000Wirirl+9 k 135 Wm',9=70%,25 t 2'C.AM ES according to IEC 60904-3 BRS FIELD OPS Warwasty performance warranty'. MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS,NMOT' 385-498-6700 Power at MPP Fs., [W] 292.6 296.3 .:,.*10,,,, 303.8 307.6 - Short Circuit Current iw [A] 8,87 8.89 '-;?:-*?''.! 8.94 8.97 Enduring high performance F.: 0 n Circuit Voltage Pe V. [V] 42.90 42.93 .41Z96, 42.99 43.03 Long-term yield securtty with Anti LeTID Technology, tr Current at fiPP 1,.,,,r [A] 816 8.21 8.31 8.36 Anti PID Technology 2 and Hot-Spot Protect. Voltage at MPP Vex, [V] 35,86 36.10 : 3.. 36.57 36130 'Measurement tolerances P,t 3%;I,:Vs„,t 5%at STC:1000 Wirn,25 t 2`C...AM 1.5 according to IEC 60904,3•'1300 Wim,,NMOT.spectrum AM 1,5 -0C114131 PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE Extreme weather rating certified tor • -.... Al least 98%of nominal power TM,...,......",......- &ing frst year.Thereafter mais high snow snow(5400 Pa)and wind loads(4000 Pa). ',': -:',, 0.5%degradation per year.Ite cr. 1 c) .,, , least 93.5%of marina)power . , .. uP to 10 years.tat least 86%ol ' .. . „ .. nominal power up to 25 yews, Innovative all-weather technology z..;--..., ,.,-,.---. :.-.- ---:-... .--,:,,...,..,...:.... NI date within measurement ci a. -.:, il tolerances.Full warranties In Optima!yields,whatever the weather with excellent low-light ,, ,,. ..••....,;•.. ... •.,,,-.,„.. ...-.-..„ ,i,.... lOi li:- ,....,.- •• ,,;-:---•• ,. •:-.:••.--•-..--•.,- accordance wall the warranty and temperature behaviour 'S$ eo''')-•- •-',-!''• •,,----•-•:;,•:" l• !'--l-'•• '•' terms of the Ocells sates .2 P. . . '0 01, ,l, 73 organisation of your respectn'e 200 WO WO as WO 2, FEAllE CP wtry. 3 2 The most thorough testing programme in the industry 'Standard terms of guarantee loi the 5 PS companies iwith the highest production capacity in 2021 fgebruus 2021) TEMPERATURE COEFFICIENTS Typital module too knout,-urvdel kw in-edema coodtiona in caoparison to STC cond ton(25'C,1000 Wine). '-i:t A ), Ocells Is the first solar module manufacturer to pass the Temperature Coefficient of Isc a [%1K1 +0.04 Temperature Coefficient of 1/, 13 1%?Kl -0_27 most comprehensive quality programme in the industry.The 09,5 4 3 1 .. . Temperature Coefficient of P v [1:IN -0.34 Nominal Module Operating Ternperature NMOT pi] new"Quality Controlled PV"of the independent certification (43±3°c> 5 Institute TUV Rheinland. •Properties for System Design Maximum System Voltage Vm M 1000(tEc0000(u LI PV module classification Class II 'See dale%heel ori Fee l'Or further inkErntelio, Maximum Series Fuse Rating IA DC] 20 Fire Rating based on ANSI/IL 61730 TYPE 2 'APT test conditions accordmii to IEC/TS 62804-112015,methoe A(-1500 V_96h) Max.Design Load,Push/Pur Orbs/It'l 75(3600PM/55(2560 Pre Permitted Module Temperature -40"1,up to+185lF ?,, Marc.Test Load,Push/Pull' [lbstiF", 113(5400 Pall 84(4000 Pa) °ri C`mitinu°111 DutY (..-40't up to-485`C) 'See Installation Manual •Qualifications and Certificates UL 61730,CE-compliera, u Ouslay Controlled PV-TOV Rheinland_ 41 '-'l -- .-- IEC 61216:2016,1K 61730:2016, ..ft U.S.Patent Na.9,893.215(sofa,coils). A. C E . - . g Kw... C LI '.........• A a i,,,The ideal solu - r ...-,tion for I Fl +,El- SHEET NAME: ,......„. 41-.7; Fz:t Rooftop arrays on xi......".% ., (N ) 1 i' •?.,. SPEC SHEETS fl residential buildings WasavowEr+von valeamoNNIMENIIPIENMEINEwm 1 REVISION: PAGE NUMBER: in Qcells pursues minimizing paper output consideration of the global environment. 9istallation' ilstruction.mum be Endowed Conrad our leclriod send.le+forever Er/korner).on approved irenalbeina of this prodaot ElanwEE El'CEEES A.2,42,A PM1,...400 Swart".Coro.Drirc,suito 1400,toriiie,CA 92.691,us A 1 TEL+I 040 748 0900 i WOOL tiqc, qcoOs.corn t WEE orww.riceltsconi ocells o ss NNW" BLUE RAVEN ENPHASE. DATA SHEET IQ8 and I08+ Microinverters -'t 1403 N.Research Way IOU DATA IO Orem,UT84097 FDA-AD-2-US 1USPLUS-72-2-US Commonly used module pairings' w 235-350 800.377.4480 ill 235-440 VW WV.BLUERAVENSOLAR.COM it.i— , Module compatibility 60-cell/120 half-cell 60-cell/120 half-cell,66-cell/132 half-cell and 72-cell/144 CONFIDENTIAL-THE INFORMATION PI 111 half-cell HEREIN CONTAINED SHALL NOT BE MPPT voltage range v 27-37 29-45 USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR Operating range v 25-48 25-58 SHALL IT BE DISCLOSED IN WHOLE OR Min/max start voltage v 30/48 IN PART TO OTHERS OUTSIDE 30/58 RECIPIENTS ORGANIZATION,EXCEPT Max input DC voltage v 50 60 IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, Max DC current'[module Ise] A 15 WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. ioa� Overvoltage class DC port II OB DC port backfeed current mA 0 PV array configuration 1x1 Ungrounded array;No additional DC side protection required;AC side protection requires max 20A per branch circuit X A E7 C E P !Mr !!� OUTPUT DATA CERTIFIED 108-60-2-US IGBPLUS-72-E-US Peak output power VA 245 300 Max continuous output power VA 240 290 PV INSTALLATION Nominal(L-L)voltage/range' v 240/211-264 PROFESSIONAL Scott Gurney Max continuous output current A 1.0 1.21 #PV-011719-015866 IQ8 and IQ8+ Microinverters Nominal frequency Hz 60 Easy to install CONTRACTOR: Extended frequency range Hz 50-68 Our newest I08 Microinverters are the industry's first microgrid-forming,software- • Lightweight and com act with BRS FIELD OPS P 3 short circuit fault current over 2 385-498-6700 defined microinverters with split phase power conversion capability to convert DC plug-n-play connectors 3 cycles Arms power to AC power efficiently.The brain of the semiconductor-based microinverter • is our proprietary application-specific integrated circuit(ASIC)which enables the Power Line Communication Max units per 20 A(L-L)branch circuit' is 13 microinverter to operate in grid-tied or off-grid modes.This chip is built in advanced (PLC)between components Total harmonic distortion <5% 55nm technology with high speed digital logic and has super-fast response times • Faster installation with simple Overvoltage class AC port Ill to changing loads and grid events,alleviating constraints on battery sizing for home two-wire cabling AC port backfeed current mA 30 energy systems. Power factor setting 1.0 High productivity and reliability Grid-tied power factor(adjustable) I • Produce power even when the 0.85leading-0.85lagging Ease Peak efficiency % 97.5grid is down• 9zs CECweightedefficiency X 97More than one million cumulative Night-time power consumption mw year limited hours of testing 60 warranty • Class II double-insulated MECHANICAL DATA Part of the Enphase Energy System,108 Series 108 Series Microinverters redefine reliability enclosure Ambient temperature range -40°C to+60°C(-40°F to+140°F) Microinverters integrate with the Enphase IQ Battery, standards with more than one million cumulative Relative humidity range 4%to 100%(condensing)• Optimized for the latest high- Enphase IQ Gateway,and the Enphase App monitoring hours of power-on testing,enabling an industry- and analysis software. leading limited warranty of up to 25 years. powered PV modules DC Connector type MC4 Dimensions(HxWxD) 212 mm(8.3")x175 mm(6.9")x 30.2 mm(1.2") Microgrid-forming Weight 1.08 kg(2.38 Ibs) ilOr C) T • Complies with the latest Cooling Natural convection-no fans advanced grid support" Approved for wet locations CERTIFIED Yes • Remote automatic updates for Pollution degree PD3 the latest grid requirements DRAWING BY: Connect PV modules quickly and easily to IQ8 Series IQ8 Series Microinverters are UL Listed as Enclosure Class II double-insulated,corrosion resistant polymeric enclosure •Microinverters using the included Q-DCC-2 adapter PV Rapid Shut Down Equipment and conform with Configurable to Support a Wld@ Environ.category/UV exposure rating NEMA Type 6/outdoor cable with plug-n-play MC4 connectors. various regulations,when installed according to range of grid profiles manufacturer's instructions. COMPLIANCE • Meets CA Rule 21(UL 1741-SA) PLOT DATE: requirements CA Rule 21(UL 1741-SA),UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B,ICES-0003 Class B,CAN/CSA-C22.2 NO.107.1-01 Certifications This o is aapd tDown imd ofomth ,N 2 , Ec 690.12pr and C22.1-2018ULListed Rules PV 64-2R18 i RapidShu ShutdownDoEqu ofp PVent Systemsanc n,forr ACs with and DC NEC conductors2014EC,when 017 installedandNC according2020se tion to PROJECT NUMBER: ©2022 Enphase Energy.All rights reserved.Enphase,the Enphase logo,I08 Microinverters,and other 'Only when installed with IQ System Controller 2, manufacturer's instructions. names are trademarks of Enphase Energy,Inc.Data subject to change. meets UL 1741. (1)No enforced DC/AC ratio.See the compatibility calculator at httpsJ/link.enphase.com/module-compatibility "108 and IQ8PIus supports split phase,240V (2)Maximum continuous input DC current is 10.6A(3)Nominal voltage range can be extended beyond nominal if required IQ8SP-DS-0002-01-EN-US-2022-03-17 installations only. by the utility.(4)Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. IQ8SP-DS-0002-01-EN-US-2022-03-17 SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: VV BLUE RAVEN IQ Combiner 4/4C ,,:::-;! /..n.it Dttlta 1403 N.Research Way Sheet i Enphase NetworkingMODEL NUMBER Orem,UT 84097 I4Combiner 4 IQ Combiner 4 with IQ Gatewayprhlted chcutt rd for integrated revenue grade PV production metering(ANSI01 tR-5.%) X-IQ-AM1-240-4 and consumptionmonitocing(t2.5%).includes a silvet solar shieldlo match the lO �and#O +stem Controller 2 and to 800.377.4480 4O-AA11-340-4(IEE€1547:2010 deflect heat WWW.BLUERAVENSOLAR.COM IQ Combiner 4C IQ Combiner 4C with IQ Gateway printed circuit board for integrated revenue grade PV production metering(ANSI C12.20±0.5%) CONFIDENTIAL-THE INFORMATION X-IQ-AM1-240-4C and consumption monitoring(±2.5%).Includes Mobile Connect cellular modem(CELLMODEM-M1-06-SP-05),a plug-and-play HEREIN CONTAINED SHALL NOT BE The IQ Combiner f}/t�C with (Q Gateway and X2-IQ-AM1-240-4C(IEEE 1547:2018) industrial-grade nds,w modem therei adequsystems upta60mirviceiertheinstallati nae rea the US,cludesCanada,Mexico rshielPuert Rico,and the USED FOR THE BENEFIT OF ANYONE I/1 Combiner US Virgin Islands,where is adequate cellular service in the installation area.)includes a silver solar shield to match the EXCEPT BLUE RAVEN SOLAR NOR l`�6# integrated I_TE-M1 cell modem (included IQ Battery and IC System Controller and to deflect heat. SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE ACCESSORIES AND REPLACEMENT PARTS (not included,order separately) RECIPIENTS ORGANIZATION,EXCEPT Only With IQ Combiner 4C) consolidates 106,1Q7,and!QB.(Donotmix106/7Microinverters with 108) IN CONNECTION WITH THE SALE AND Supported microinverters THE RESPECTIVE EQUIPMENT, interconnection equipment into a single Communications Kit USE OFT THE WRITTEN PERMISSION COMMS-CELLMODEM-M1-06 -Includes COMMS-KIT-01 and CELLMODEM-M1-06-SP-05 with 5-year Sprint data plan OF BLUE RAVEN SOLAR MIS. enclosure. It streamlines IQ Mlcrolnverters and CELLMODEM-M1-06-SP-05 -4G based LTE-Ml cellular modem with 5-year Sprint data plan CELLMODEM-M1-06-AT-05 -4G based LTE-M1 cellular modem with 5-year AT&T data plan / storage Installations b rovIdlrl a Consistent, Supports EatonBR210,BR215,BR220,BR230,8R240,BR250,and8R260circuitbreakers. X:1A-BCED g p g Circuit Breakers Circuit breaker,2 pole,lOA,Eaton BR210 r EPYPHASE pre wired solution for residential applications. BRK-15A-2-240V0V BRK-15A-2-240V Circuit breaker,2 pole,WA,Eaton BR210 It offers up#o four 2 pole input Circui#s and BRK-20A-2P-240V2 Circuit breaker,2 pole,20A,Eaton BR220 CERTIFIED BRK-15A-2P-240V-B Circuit breaker,2 pole,15A,Eaton BR2158 with hold down kit support Eaton BR series bulbar assembly BRK-20A-2P-240V-B Circuit breaker,2 pole,20A,Eaton 8R2208 with hold down kit support XA-SOLARSHIELD-ES Replacement solar shield for 1Q Combiner 4/4C PV INSTALLATION ,t XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 4/4C(required for EPLC-01) PROFESSIONAL y Scott Gurney ff wrc x _ __ X-IQ-NA-HD-125A Hold-down kit for Eaton circuit breaker with screws #PV-011719-015866 ,r a A air of 200A split core current transformers Consumption monitoring CT p CONTRACTOR: � (CT-200-SPLIT/CT-200-CLAMP) ' Smart ELECTRICAL SPECIFICATIONS BRS FIELD OPS • Includes IQ Gatewayfor communication and control Continuous duty 385-498-6700 Rating • Includes Mobile Connect cellular modem System voltage 120/240VAC,60 Hz t u (CELLMODEM-M1-06-SP-05),included only with 125A Eaton BR series busbar rating 1 IQ Combiner 4C f.- • Includes solar shield to match Enphase IQ Battery Max.continuous current rating 65A Max.continuous current rating(input from PV/storage) 64A f r aesthetics and deflect heat Supports Wi-Fi,Ethernet,or cellular connectivity Max.fuse/circuit rating(output) 90A s • Optional AC receptacle available for PLC bridge Branch circuits(solar and/or storage) Up to four2-pole Eaton BR series Distributed Generation(DG)breakers only(not included) 1 F • Provides production metering and consumption Max.total branch circuit breaker rating(input) 80A of distributed generation/95A with IQ Gateway breaker included ): monitoring IQ Gateway breaker 10A or i5A rating GEtSiemens/Eatonincluded t, Production metering CT 200A solid core pre-installed and wired to IQ Gateway 1- Simple MECHANICAL DATA t Dimensions(WxHxD) 37.5 cm x 49.5 cm x 16.8 cm(14.75 in x 19.5 in x 6.63 in).Height is 53,5 ern(21.06 in)with mounting brackets. X-IQ AM1-240-4C �i • Mounts on single stud with centered brackets 7.5 kg(16.5Ibs) t, • Supports bottom,back and side conduit entry weight X2 IQ AM1-240 QC(IEEE 1547:2018) -40°C to+46°C(-40°F to 115°F t '. Allows up to four 2-pole branch circuits for 244VAC Ambient temperature range 115°F) f - plug-in breakers(not included) Cooling Natural convection,plus heat shield 80A total PV or storage branch circuits Enclosure environmental rating Outdoor,NRTL-certified,NEMA type 3R,polycarbonate construction Wire sizes • 20A to 50A breaker inputs:14 to 4 AWG copper conductors t, 60A breaker branch input:4 to 1/0 AWG copper conductors • Main lug combined output:10 to 2/0 AWG copper conductors 1 Reliable • Neutral and ground:14 to 1/0 copper conductors Durable NRTi-certified NEMA type 3R enclosure •Always follow local code requirements for conductor sizing. Five-year limited warranty Altitude Up to 3,000 meters(9,842 feet) Two years labor reimbursement program coverage INTERNET CONNECTION OPTIONS included for both the IQ Combiner SKU's Integrated Wi-FI IEEE802.11b/g/n • UL listed Cellular CELLMODEM M1-06-SP-OS,CELLMODEM-M1-06-AT-05(4G based LTE-M1 cellular modem).Note that an Mobile Connect X IQ AM1240 4 • X2-IQ-AM1-240-4 and X2-IQ-AM1-240-4C comply with cellular modem is required for all Enphase Energy System installations. X2-IQ-AM1-240-4(IEEE 1547:2018) IEEE 1547:2018(UL 1741-SB,3rd Ed.) Ethernet Optional,IEEE 802.3,CatsE(or Cat6)UTP Ethernet cable(not included) COMPLIANCE Compliance,IQ Combiner CA Rule 21(UL 1741-SA) IEEE 1547:2018-UL 1741-SB,3rd Ed.(X2-IQ-AM1-240-4 and X2-IQ-AM1-240-4C) ; (13 CAN/CSA C22.2 No.107.1,Title 47 CFR,Part 15,Class B,ICES 003 Production metering:ANSI C12.20 accuracy class 0.5(PV production) LISTED N H S Consumption metering:accuracy class 2.5 E 1 Y��I l�J E, Compliance,IQ Gateway UL 60601-1/CANCSA 22.2 No.61010 1 SHEET NAME: To learn more about Enphase offerings,visit enphase.com 2022 Enphase Energy.Ail rights reserved.Enphase,the Enphase Ingo,IQ Combiner 414C,and other names are trademarks of IQ C 4 4C DS 0103 EN US 12 24-2D22 Enphase Energy,Inc.Data subject to change IQ-C 4-4C DS 0103 EN US 12-24 2022 SPEC SHEETS REVISION: PAGE NUMBER: 0 SS BLUE RAVEN 1403 N.Research Way Orem,UT 84097 800.377.4480 WIRING DIAGRAMS WWW.BLUERAVENSOLAR.COM 1 7.25 .28 DIA CONFIDENTIAL-THE INFORMATION Ir [184] [7] NOT FUSIBLE HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE — _ (3 HOLES) !' EXCEPT BLUE RAVEN SOLAR NOR IMMEMINEVAIII SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE it 01 I Q O O RECIPIENTS ORGANIZATION,EXCEPT I I I IN CONNECTION WITH THE SALE AND i:_' II Iii ♦ A 1 B /[ /[ USE OF THE RESPECTIVE EQUIPMENT, b I I WITHOUT THE WRITTEN PERMISSION O O O OF BLUE RAVEN SOLAR LLC. 1�� 6.00 9.63 [152] I ° [245] I ABCEP I I�J TERMINAL LUGS$ CERTIFIE D A,B,C AMPERES MAX. WIRE MIN. WIRE TYPE „=,;, KNOCKOUTS PV INSTALLATION -;, v=" 60 2 AWG #10 AWG AL I #2 AWG #14 AWG Cu PROFESSIONAL A,B,C Scott Gurney o — #PV-011719-015866 KNOCKOUTS 4.50KNOCKOUTS CONTRACTOR: [9BRS FIELD OPS [114] L_3.[95] SYMBOL A B C D 385-498-6700 CONDUIT SIZE .50 .75 1 1.25 7.75 NEMA TYPE 3R [197] 1 U A,B,C 0 KNOCKOUTS DUAL DIMENSIONS: INCHES A,B,C,D MILUMETERS KNOCKOUTS HORSEPOWER RATINGS CATALOG WIRING 240VAC NUMBER VOLTAGE RATINGS DIAG. MAX. 10 30 DU222RB 240VAC A 10 — DRAWING BY: NOTES: DU322R8 240VAC B 10 15 FINISH — GRAY BAKED ENAMEL UL LISTED — FILE E-2875 SUITABLE FOR USE AS SERVICE EQUIPMENT TOP OF NEMA TYPE 3R SWITCHES HAVE PROVISIONS FOR MAXIMUM 2 1/2" BOLT—ON HUB. SQUARE DATE: SHORT CIRCUIT CURRENT RATINGS: GENERAL DUTY SAFETY SWITCHES SORE D 10,000 AMPERES WHEN USED WITH OR PROTECTED BY CLASS H OR K FUSES VISIBLE BLADE TYPEEi 100,000 AMPERES WHEN USED WITH OR PROTECTED BY CLASS R FUSES. 60 AMPERE Schneider Electric $ LUGS SUITABLE FOR 60'C OR 75'C COPPER OR ALUMINUM CONDUCTORS. ENCLOSURE — NEMA TYPE 3R RAINPROOF PROJECT NUMBER: oG/ 1861 DECEMBER 2004 REF DWG #1861 SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: SS NoNoe. RSTC Enterprises, Inc. (W; BLUE RAVEN 2214 Heimstead Road � K 1403 N.Research Way Eau Claire, WI 54 703 A DfN UT arch 715-830-9997 FLASHED PV ROOF-MOUNT 800 377 4480 COMBINER/ENCLOSURES W WVV.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR Outdoor Photovoltaic Enclosures 0799 Series SHALLITBEDISCLOSEDIN VVHOLE OLARNOOR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND Composition/Cedar Roof System USE OF THE RESPECTIVE EQUIPMENT, ivy.r' WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. ETL listed and labeled Report#3171411 PRT-002 Revised May, 2018 ,-,- NABCEP • UL50 Type 3R, 11 Edition Electrical equipment enclosures o r CERTIFIED • CSA C22.2 No. 290 Nema Type 3Rfyw PV INSTALLATION • Conforms to UL 1741 Standard PROFESSIONAL VI :". Scott Gurney,,° ' #PV-011719-015866 0799 Series Includes: CONTRACTOR: a` BRS FIELD OPS Sola Deck 0799-25 0799 -2 Wire size 2/0-14 385-498-6700 0799 -5 Wire size 14-6 0799 - D Wire size 14-8 Models available in Grey,Black or Stainless Steel Basic Specifications Material options: • Powder coated, 18 gauge galvanized 90 steel (1,100 hours salt spray) • Stainless steel Sole Deck 0799-5G Process - Seamless draw (stamped) Flashing - 15.25" x 17.25" Height- 3" Cavity - 255 Cubic inches DRAWING BY: Base Plate: • Fastened to base using toggle fastening system ®. PLOT DATE • 5 roof deck knockouts . • Knockout sizes: (3) .5", (1) .75" and (1) 1" • 8", 35mm slotted din rail PROJECT NUMBER: • Ground Block 1 SHEET NAME Passthrough and combiner kits are available for either Sole Deck0799-DG SPEC SHEET AC or DC applications. REVISION: PAGE NUMBER: ---- S S NtitiN/F- SFM INFINITY BLUE RAVEN ry �°""� �, � �� 1403 N.Research Way .;. � „r.,�� .�. BETTER SOLAR STARTS HERE Ore .UT84097 m ,,,�c".,, .. ., .,..,, . 5 800.377.4480 1 ., tWAN.BLUERAVENSOLAR.COM / ,,, "'" CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR OLE E IlL21 03_ ( SHA IN ART L IT BETN TO OTHERS ISCLOSED LOUTS DE OR RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, SYSTEM OVERVIEW 20% FEWER ATTACHMENTS WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. 41. PART NAME DESCRIPTION Save time and money on every project:SFM INFINITY requires fewer 1 i attachments than rail systems. XJA-BC-E1- 3 2 INSTALLS PER DAY TRIMRAIL Structural front trim provides aesthetic and aligns modules. CERTIFIED Make two installs per day your new standard.SFM INFINITY has fewer I : mr5-, �,is ti� PV INSTALLATION roof attachments,one tool installation,and pre assembled components TRIMRAIL SPLICE Connects and electrically bonds sections of TRIMRAIL. �r s� : .a., X , , PROFESSIONAL �w any,, ; f Scott Gurney to get you off the roof 40%faster. III S. 1 z r " � fk' 1111611, ''1.'� y , 6y ? �,, g3 9 : . #PV-011 71 9-01 5866 TRIMRAIL FLASHKIT Attaches TRIMRAIL to roof.Available for comp shingle or tile, 4 %% >. s Qi Oir F HOMEOWNERS II SFM , ! lir SFM INFINITY 15 Attachments BRS FIELD OPS MODULE CLIPS Secure modules to TRIMRAIL. 385-498-6700 ---,4id"„,,,e,,„,.f/ -*..,.m , c;' F . " ,: 1131 MICRORAIL Connects modules to SLIDERS.Provides post-install array leveling. r- �' p �n, i BETTER AESTHETICS g I 1 tip I f Install the system with the aesthetics preferred by homeowners, SPLICE Connects and supports modules.Provides east west bonding. with integrated front trim,trim end caps,dark components,and If SPLICE also available. recessed hardware. II SLIDER FLASHKIT Roof attachment and flashing.Available for comp shingle and tile. RAIL 20 Attachments MAXIMUM POWER DENSITY Easily mix module orientations to achieve optimal power density 30% LOGISTICS SAVINGS without incurring the increased bill of materials,labor,and BONDING AND ACCESSORIES With fewer SKUs and compact components,SFM INFINITY is easier to attachments required by rail. stock,easier to transport,and easier to lift to the roof.Plus,make more PART NAME DESCRIPTION efficient use of your vehicle fleet. , r 4 ," r 4/ lirTRIMRAIL ENDCAPS Covers ends of TRIMRAIL for refined aesthetic. W�.. - rr¢ - TRIMRAIL BONDING CLAMP �,��' Electrically bonds TRIMRAIL and modules 4 Pg4 P1/4 t' - . A.f3/,-4 -Ai „ , if N/S BONDING CLAMP Electrically bonds rows of modules lb . • fi DRAWING BY: PLOT DATE: SFM INFINITY REVOLUTIONIZES ROOFTOP SOLAR WITH BENEFITS ACROSS YOUR BUS INESS FROM DESIGN AND LOGISTICS, THROUGH ARRAY INSTALLATION AND SERVICE. PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: SS 14,1,, . 1 BLUE RAVEN 1GROUNDING ! .. AME1 14 Oem,UT 84097 N Research Way 0 INSTALLATION GUIDE 1 PAG E us 1MICRORAILTM WVWV.BLUERAV ENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE - 1 _MIN_1M1 111 11�__111M4 I I _11. -_ Il- 11 ■ USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL FOR DISCLOSED IN WHOLE OR ( IN PART TO OTHERS OUTSIDE ( I RECIPIENTS ORGANIZATION,EXCEPT U IN CONNECTION WITH THE SALE AND ( ( ' USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. NAgCEP M - 110..140 -*' I CERTIFIED I PV INSTALLATION I PROFESSIONAL gdillillikilbt- Scott Gumey #PV-011719-015866 ►-. �''— 'T MI E-W BONDING PATH: CONTRACTOR: I E-W module to module bonding is accomplished BRS FIELD OPS I with 2 pre-installed bonding pins which engage 385-498-6700 1 I on the secure side of the MicrorailTM and splice. I \ rI I I ( i I i I i i i I I I I I I i i I I I I I I 40 Star Washer is WEEBLUG Single Use Only Single Use Only c,›ternate method N-S BONDING PATH: TERMINAL TORQUE, N-S module to module bonding is Install Conductor and accomplished :It: bonding clamp with 2 integral torque to the following: TERMINAL TORQUE, TERMINAL TORQUE, bonding pins. r also to alternate method) 4-6 AWG: 35in-lbs Install Conductor and Install Conductor and 8 AWG: 25 in-las torque to the following: torque to the following: 10-14 AWG:20 in-lbs 4-14 AWG: 35in-lbs 6-14 AWG:7ft-lbs DRAWING BY: DETAIL & TORQUE INFO LUG DETAIL & TORQUE INFO LUG DETAIL & TORQUE INFO -? LUG Q Ilsco Lay-In Lug (GBL-4DBT) Ilsco Flange Lug (SGB-4) Wiley WEEBLug (6.7) (`� PLOT DATE°� • 1 4" mountin hardware• - untin hardware 1/4 mounting hardware / 9 � � , �� 10 32 mounting Alternate method • Torque = 5 ft-lb • Torque = 75 in-lb • Torque = 10 ft-lb e '''•-, PROJECT NUMBER • AWG 4-14-Solid or Stranded • AWG 4-14-Solid or Stranded • AWG 6-14-Solid or Stranded TRIMRAIL BONDING PATH: NOTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION Trimrail to module bonding is accomplished with SHEET NAME: System bonding is accomplished through modules.System grounding accomplished by attaching bonding clamp with integral bonding pin and SPEC SHEET bonding T-bolt. (refer also to alternate method) REVISION: PAGE NUMBER a ground lug to any module at a location on the module specified by the module manufacturer. __-- SS , • : NIsFim FRAME BLUE RAV. ,,EN „.., IIIII ' UI III MICRORAILTMINSTALLATION1403 N.Research Way PAGE Orem,UT84097 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION SYSTEM LEVEL ARE CLASSIFICATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE The system fire class rating requires installation in the manners specified in the EXCEPT BLUE RAVEN SOLAR NOR p performance is inherent in the SFM design,and no additional mitigation measures SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE SUNFRAME MICRORAIL(SFM) Installation Guide.SFM has been classified to are required.The fire classification rating is valid for any roof pitch.There is no RECIPIENTS ORGANIZATION,EXCEPT the system level fire portion of UL 1703. This UL 1703 classification has been required minimum or maximum height limitation above the roof deck to maintain IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, incorporated into the UL 2703 product certification. SFM has achieved Class A, the Class A, B & C fire rating for SFM.SUNFRAME MICRORAILTM components shall WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. B & C system level performance for low slope & steep sloped roofs when used be mounted over a fire resistant roof covering rated for the application. in conjunction with type 1 and type 2 modules. Class A, B & C system level fire NABCEP CERTIFIED Module Type Roof Slope System Level Fire Rating Microrail Direction Module Orientation Mitigation Required PV INSTALLATION PROFESSIONAL Type 1 and Type 2 Steep Slope & Low Slope Class A, B & C East-West Landscape OR Portrait None Required Scott Gurney #PV-011719-015866 CONTRACTOR: UL2703 TEST MODULES BRS FIELD OPS 385-498-6700 See pages 22 and 23 for a list of modules that were electrically and mechanically tested or qualified with the SUNFRAME MICRORAIL (SFM) components outlined within this Installation Guide. • Maximum Area of Module = 27.76 sqft • UL2703 Design Load Ratings: a) Downward Pressure - 113 PSF/ 5400 Pa b) Upward Pressure - 50 PSF / 2400 Pa c) Down-Slope Load - 21.6 PSF/ 1034 Pa • Tested Loads: a) Downward Pressure - 170 PSF/ 8000 Pa b) Upward Pressure - 75 PSF/ 3500 Pa c) Down-Slope Load - 32.4 PSF/ 1550 Pa • Maximum Span = 6ft • Use with a maximum over current protection device OCPD of 30A DRAWING BY: • System conforms to UL Std 2703, certified to LTR AE-001-2012 • Rated for a design load of 2400 Pa / 5400 Pa with 24 inch span PLOT DATE: • PV modules may have a reduced Load rating, independent of the SFM load rating. Please consult the PV module manufacturer's installation guide for more information PROJECT NUMBER: • Down-Slope design load rating of 30 PSF/ 1400 Pa for module areas of 22.3 sq ft or less SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ____ SS , 1 11TESTED / CERTIFIED MODULE LIST ' LUE RAVEN u su :us : FRAME7V� Orem,UT 8409 U s ' MICRORAILTM O Il INSTALLATION GUIDE : PAGE 14800.377.4480 VVVWV.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE Manufacture Module Model/Series Manufacture Module Model/Series Manufacture Module Model/Series EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE xN2T-A4 RECIPIENTS EXCEPT Aleo P-Series Eco Solargy Orion 1000 &Apollo 1000 LGxx CONNECTION ORGANIZATION,Z THE SALE AND LGxxx A1C/E1C/E1K/N1C/N1K/N2T/N2W/ USE OF THE RESPECTIVE EQUIPMENT, ET Solar ET M6726HxxxTW ( WITHOUT THE WRITTEN PERMISSION DNA-120-(BF/MF)26 Q1C/Q1K/S1C/S2W)-A5 OF BLUE RAVEN SOLAR LLC. Aptos Freedom Forever FF-MP-BBB-370 DNA-144-(BF/MF)26 LGxxxN2T-B5 FreeVolt Mono PERC LGxxxN1K-B6 NABCEP CHSM6612P,CHSM6612P/HV,CHSM6612M, GCL GCL-P6 &GCL-M6 Series LGxxx(A1C/M1C/M1K/N1C/N1K/Q1C/Q1K/ CERTIFIED Astronergy CHSM6612M/HV,CHSM6610M (BL)(BF)/(HF), TD AN3,TD AN4,Hansol LG Electronics QAC/QAK)-A6 PV INSTALLATION CHSM72M-HC UB-AN1,UD-AN1 LGxxx(N1C/N1K/N2T/N2W) E6 PROFESSIONAL Scott Gurney AXN6M61OT,AXN6P610T, 36M,60M,60P,72M & 72P Series, LGxxx(N1C/N1K/N2W/S1C/S2W)-G4 #PV-011719-015866 Auxin 144HC M6 MonofaciaV Bifacial Series, LGxxxN2T JS AXN6M612T&AXN6P612T HelieneCONTRACTOR: AXlblackpremium 60(35mm), 144HC M10 SL Bifacial LGxxx(N1K/N1W/N2T/N2W)-L5 BRS FIELD OPS HT60-156(M)(NDV)(-F), LGxxx(N1C/Q1C/Q1K)-N5 385-498-6700 AXlpower 60(35mm), HT Solar Axitec AXlpower 72 (40mm), HT 72-156(M/P) LGxxx(N1C/N1K/N2W/Q1C/Q1K)-V5 AXlpremium 60 (35mm), KG,MG,TG,RI,RG,TI,MI,HI & KI Series LR4-60(HIB/HIH/HPB/HPH)-xxxM Hyundai H IHHPH xxxM AXlpremium 72 (40mm). HiA-SxxxHG LR4 72( / ) BVM6610, ITEK iT,iT-HE & iT-SE Series LR6-60(BP/HBD/HIBD)-xxxM (30mm) Boviet BVM6612 LR6-60(BK)(PE)(HPB)(HPH)-xxxM (35mm) Japan Solar JPS-60 &JPS-72 Series LONGi LR6-60(BK)(PE)(PB)(PH)-xxxM (40mm) BYD P6K& MHK-36 Series JAP6 60-xxx,JAM6-60-xxx/SI,JAM6(K)-60/ LR6-72(BP)(HBD)(H I BD)-xxxM (30mm) CS1(H/K/U/Y)-M S xxx,JAP6(k)-72-xxx/4BB,JAP72SYY-xxx/ZZ, LR6-72(HV)(BK)(PE)(PH)(PB)(H PH)-xxxM CS3(K/L/U),CS3K MB AG,CS3K-(MS/P) JAP6(k)-60-xxx/4BB,JAP6OSYY-xxx/ZZ, (35mm) Canadian Solar CS3N-MS,CS3U MB AG,CS3U-(MS/P),CS3W JA Solar JAM6(k)-72-xxx/ZZ,JAM72SYY-xxx/ZZ, LR6-72(BK)(HV)(PE)(PB)(PH)-xxxM (40mm) CSSA M,CS6(K/U),CS6K(M/P),CS6K-MS JAM6(k)-60-xxx/ZZ,JAM6OSYY-xxx/ZZ. CS6P-(M/P),CS6U-(M/P),CS6V-M,CS6X-P Mission Solar Energy MSE Series i.YY:01,02,03,09,10 Centrosolar America C-Series & E-Series ii.ZZ:SC,PR,BP,HiT,IB,MW,MR Mitsubishi MJE & MLE Series CT2xxMxx-01,CT2xxPxx-01, 1KM &JKMS Series Neo Solar Power Co. D6M & D6P Series CertainTeed CTxxxMxx-02,CTxxxM-03, DRAWING BY: linko Eagle JKMxxxM CTxxxMxx-04,CTxxxHC11-04 JKMxxxM-72HL-V Dehui DH-60M PLOT DATE: Kyocera KU Series PROJECT NUMBER: • Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx" • Items in parenthesis are those that may or may not be present in a compatible module's model ID • Slashes "/"between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME: • Please see the SFM UL2703 Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET • SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section,page 12 for further information REVISION: PAGE NUMBER: ---- S S , . . Ner 1 1 SUN ; ' 1 IlaFRAMEBLUE RAVEN LIST ! :, ,,,_,.,,, 1 Ol MICRORAILTMINSTALLATION 1403 ResearchWay GUIDE PAGE N.Qf a 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE Manufacture Module Model/Series Manufacture Module Model/Series Manufacture Module Model/Series USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE EVPVxxx(H/K/PK), TwinPeak Series A-Series A400-BLK,SPR MAX3 XXX R, RECIPIENTS ORGANIZATION,EXCEPT SunPower VBHNxxxSA15 & SA16, TwinPeak 2 Series IN CONNECTION WITH THE SALE AND X-Series,E-Series & P-Series USE ECE , VWITHOUTOFTHE THERESP WRITTEN TIVE PERMISSIONEQUIPMNT BHNxxxSA17& SA18, TwinPeak 2 BLK2 Series Suntech STP,STPXXXS-B60/Wnhb OF BLUE RAVEN SOLAR LLC. REC(cont.) Panasonic VBHNXXXSA17(E/G) & SA18E, TwinPeak 2S(M)72(XV) TP572,TP596,TP654,TP660, VBHNxxxKA01 & KA03 & KA04, TwinPeak 3 Series(38mm) Talesun -IA TP672,Hipor M,Smart VBHNxxxZA01,VBHNxxxZA02, TP4(Black) SC,SC B,SC B1,SC B2 CERTIFIED VBHNxxxZA03,VBHNxxxZA04 Renesola Vitrus2 Series & 156 Series Testa TXXXH,TXXXS PV INSTALLATION Peimar SGxxxM (FB/BF) Risen RSM72-6(MDG)(M),RSM60 6 PA05,PD05,DD05,DE06,DD06,PE06, PROFESSIONAL Scott Gurney ono Solar PS-60,PS-72 SEG Solar SEG-xxx-BMD-HV Trina PD14,PE14,DD14,DE09.05,DE14,DE15, #PV-011719-015866 Prism Solar P72 Series S-Energy SN72 & SN60 Series(40mm) PE15H CONTRACTOR: Plus,Pro,Peak,G3,G4,G5,G6(+),G7,G8(+) Seraphim SEG-6 & SRP-6 Series BRS FIELD OPS UP MxxxP(B), 385-498-6700 Upsolar Pro,Peak L-G2,L-G4,L-G5,L-G6,L-G7 Sharp NU-SA& NU-SC Series UP-MxxxM(-B) Q.PEAK DUO BLK-G6+ SLA, SLG,BC Series & SILxxx(BL/NL/NT/HL/ D7MxxxH7A,D7(M/K)xxxH8A Q.PEAK DUO BLK-G6+/TS Silfab ML/BK/NX/NU/HC) URE FAKxxx(C8G/E8G),FAMxxxE7G-BB Q.Cells Q.PEAK DUO(BLK)-G8(+) Solarever USA SE 166'83 xxxM 120N FAMxxxEBG(-BB) Q.PEAK DUO L-G8.3/BFF . Q.PEAK DUO(BLK)ML-G9(+) PowerXT-xxxR-(AC/PD/BD) Eldora, Solaria PowerXT-xxxC-PD Vikram Solivo, Q.PEAK DUO XL-G9/G9.2/G9.3 Q.PEAK DUO(BLK)ML G10(+) PowerXT-xxxR-PM (AC) Somera Sunmodule Protect, Waaree AC &Adiya Series Q.PEAK DUO XL-G(10/10.2/10.3/10.c/10.d) SolarWorld Sunmodule Plus Winaico WST&WSP Series Alpha(72)(Black)(Pure) N-Peak(Black) SS-M-360 to 390 Series, Yingli YGE &YLM Series N-Peak 2 (Black) SS-M-390 to 400 Series, ZN Shine ZXM6-72, ZXM6-NH144-166_2094 REC Sonali SS-M-440 to 460 Series, PEAK Energy Series PEAK Energy BLK2 Series SS-M-430 to 460 BiFacial Series, PEAK Energy 72 Series SS 230 265 SunEdison F-Series,R-Series & FLEX FXS Series DRAWING BY: Suniva MV Series & Optimus Series PLOT DATE: PROJECT NUMBER: • Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx" • Items in parenthesis are those that may or may not be present in a compatible module's model ID • Slashes "/"between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME: • Please see the SFM UL2703 Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET • SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section,page 12 for further information REVISION: PAGE NUMBER: ---- SS B intertek AUTHORIZATION TO MARK intertek AUTHORIZATION TO MARK LUE RAVEN ,, Total Quality.Assured. 1403 N.Research Way Total Quality.Assured. Total UT 84097 800.377.4480 This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) y�yyyy.BLUERAV.4480 R.COM Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing CONFIDENTIAL-THE INFORMATION Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing HEREIN CONTAINED SHALL NOT BE Report. Report. USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be IN PART TO OTHERS ouTSIDE applied only at the location of the Party Authorized To Apply Mark. applied only at the location of the Party Authorized To Apply Mark. RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Applicant: Unirac, Inc Manufacturer: Redacted information Applicant: Unirac, Inc Manufacturer: Redacted information OF BLUE RAVEN SOLAR LLC. 1411 Broadway Blvd NE NABCEP 1411 Broadway Blvd NE Address: Address: Albuquerque, NM 87102 Albuquerque, NM 87102 CERTIFIED Country: USA Country: USA PV INSTALLATION Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL Report IssuingOffice: Intertek Testing Services NA, Inc. Lake Forest, CA /� Scott Gurney Report Issuing Office: Intertek Testing Services NA, Inc. Lake Forest, CA, p ���U_- 1 A-__CA, #PV-011719-015866 Control Number: 5003705 Authorized by: ©©JJ Control Number: 5014989 Authorized by: GVY�.i.Ul for L. Matthew Snyder, Certification Manager for L. Matthew Snyder, Certification Manager CONTRACTOR: BRS FIELD OPS 385-498-6700 (BP C US C US Intertek Intertek This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number. nt to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are Thism Authorization terms to and conditionso i for the f the exclusive use of Intertek Client and is provided anyyrpae 9 Intertek assumes no liabilityto party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by limited use of isAuthorization of the agreement. re the otheis li id o Marh. agr the Client is this ued to permit copyingMarordistributionfteru of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is t nly d to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted 9 first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights,IL 60005 545 East Algonquin Road,Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices,and Ground Lugs for Use with Flat- Mounting Systems,Mounting Devices,Clamping/Retention Devices,and Ground Lugs for Use with Flat- Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] DRAWING BY: Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Brand Name: Unirac Brand Name: Unirac Models: Unirac SFM Models: Unirac SFM PLOT DATE: PROJECT NUMBER: SHEET NAME: ATM Issued:27 Oct 2022 ATM for Report 102393982LAX-002 Page 2 of 4 ATM Issued:27-Oct-2022 SPEC SHEET ATM for Report 102393982LAX-002 Page 1 of 4 ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory REVISION: PAGE NUMBER:NU V s . . Nei' Intertek AUTHORIZATION TO MARK Intertek AUTHORIZATION TO MARK BLUE RAVEN Dial Quality.Assured Total Quality.Assured. rn T1403 N.Research Way Orem,UT 84097 This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) 800.377.4480 Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing vwuw.BLUERAVENsoLAR.coM Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION Report. Report. HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be ExcEPr BLUE RAVEN sr WHOLESHALL OR applied only at the location of the Party Authorized To Apply Mark. applied only at the location of the Party Authorized To Apply Mark. IN PART To OTHERS E RECIPIENTS ORGANIZATION,ION,EX EXCEPT IN CONNECTION WITH THE SALE AND Applicant: Unirac, Inc Manufacturer: Redacted information USE OF THE RESPECTIVE EQUIPMENT, Applicant: Unirac, Inc Manufacturer: Redacted information WITHOUT VV SO PERMISSION OF BLUEUE RAVEN EN SOLAR LLC. Address: 1411 Broadway Blvd NE 1411 Broadway Blvd NE Albuquerque, NM 87102 Address: Albuquerque, NM 87102 NABCEP\ Country: USA Country: USA CERTIFIED Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PV INSTALLATION Report Issuing Office: Intertek Testing Services NA, Inc., La Forest, CA 1 Report Issuing Office: Intertek Testing Services NA, Inc., Lake Forest, CA PROFESSIONAL �� Scott Gurney Number: 5019851 Authorized by: Control Number: 5021866 Authorized by: #Pv-olnls-ols8ss for L. Matthew Snyder, Certification Manager for L. atthew Snyder, Certification Manager CONTRACTOR: BRS FIELD OPS 385-498-6700 C US C ous Intertek Intertek. This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement limited to the terms and conditions of the agreement.Intertek assumes no liabilityto g P gin accordanceden with the and itsm nt,for Intertek's,responsibility and liability c are any party,other than to the Client in accordance with the agreement,for anyloss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in the agreement,for anyloss,expense or by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark isodamage occasioned is by the use of this Authorization to Mark.Only gr the Clintent isthis authorizedthrito permit non t copying or distribution of the Authorization Intertek to Mark and then only in its entirety. the Use of Intertek's product on service vic Is restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement o first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with then of the tested material, must first be enproved not o h Intertek.Initial Faroctory n quality co Assessments and Followl up Services are for the e purpose of ionsiassuring his appropriatespec usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights, IL 60005 545 East Algonquin Road,Arlington Heights,IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems,Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021 Standard(s): l PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:20201 PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 DRAWING BY: Brand Name: Unirac Brand Name: Unirac Models: Unirac SFM Models: Unirac SFM PLOT DATE: PROJECT NUMBER: SHEET NAME: ATM for Report 102393982LAX-002 Page 3 of 4 ATM Issued:27-Oct-2022 ATM for Report 102393982LAX-002 Page 4 of 4 ATM Issued:27-Oct-2022 SPEC SHEET ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory REVISION: PAGE NUMBER: ____ SS 'Illiogii''. �t��tek in' tertek � Listing Constructional Data Report (CDR) Listing Constructional Data Report (CDR) BLUE RAVEN N Total Quality.Assured. Total Quality.Assured. `� ; i"'- 1403 N.Research Way Orem,UT 84097 ,-,f u r= ',,,, . f. N -» „. am . ; r.{ . ,. :..S43 800.377.4480 M rIRevised: 5-Oct-2022 WWW.BLUERAVENSOLAR.COM .. r Revised: 5-Oct-2022 , ".;.irk ¢ ,;, ;<. 102393982LAX-002 Original 11-Apr-2016:F a°,t r,.. 102393982LAX-002 Original 11-Apr-2016 i ` ,, CONFIDENTIAL- HEREIN CONTAINED INFORMATION NOT BE ; , Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use USED FOR THE BENEFIT OF ANYONE ` ` with Flat-Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] IN CONNECTION WITH THE SALE AND I USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION a OF BLUE RAVEN SOLAR MIS , : t,. Unirac, Inc -. ., . 1411 Broadway Blvd NE 'gig Albuquerque, NM 87102BCEP ItrIgiggRtiteily, r CERTIFIED , r µ4 USA i 'i.; Klaus Nicolaedis g «f PV INSTALLATION `.' Todd Ganshaw PROFESSIONAL 'J:. E Gurney 505-462-2190 ,i' Scott#PV-011719-015866e 505-843-1418 NA CONTRACTOR: f ,��� "�; BRS FIELD OPS . , klaus.nicolaedis@unirac.com -4V,4 u ..t't toddg@unirac.com ¢ 'p., (',:, 385-498-6700 rsz s u:, iceett x,t it ..z,,, eta-.?<r4 ` �. "',�k'�.rrxt�; �� yr ,�a 4 3f X4rt'C" R -,f � i": f�y ', '.:,^^F s t6R$ k$d; g'uv,4x'" .Za ' f3 ", DRAWING BY: i I. ,'G PLOT DATE: ,,'kit"•' PROJECT NUMBER: :1mA, Yh ; Page 1 of 138 Page 2 of 138 SHEET NAME: This repot s end is for the ch*sive use of Iritsr1elle Client s is provided pursuant Io the between Intoned and its Client. tntartek's resporteitaity and This report is for the exclusive use of t sr.Nts Cesnt end is provided pub to the�eement between Intertek and its Gent tntertett's r sperrabicty and WOW am limited to the terms and oemctmns of the egresmsnt. Inteneic assumes no liability to array party.other than to the Caere in aocorderce with the kebi ty are limited to the towns and conditions of the agreement tnfertSfc assumes no liability to any party.other than to the Clem in accordance with ad sgrserfroot for sorry lose:es enee or demape occosiorocid by the use of this sport OrtrY the Chant is eut hortxed to permit copylict or distribution of tbia report and agreement for every loss,income or damage occasioned by the use of this report Only the cat is authorized to Permit copying or dlsbitiutton of dge recoil and SPEC SHEET then only in its*Mesh My use of the intereek name or one of its mirKs for the sate or aherbswlint of the tasted malarial,product or service must first be then orgy in its entirety.My use of the Wendt ruerne or ono of its manes for the sate or advertisement of the WWI material,product or**MOO must first be approve{in writing by Oaten*-The cbeeivations and test reectts in this report are relevant only to the sample tested This report by itself dose not irrety that the approved in wining by intermit.The ceriervetto s and lest rebate in this report we relevant only to the sample tested.The report by itself does not impiry that the REVISION: PAGE NUMBER: met inet.product.Or service is or has ever been under an Nortek certificationprogram. notarial.produce,or service is or has ever been under en lrrtertek cendicaticri program C • V^ Report No. 102393982LAX-002 Page 3 of 138 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 4 of 138 Issued: 11-Apr-2016 Unirac, Inc \le' Revised: 5-Oct-2022 Unirac, Inc Revised: 5-Oct-2022 • •. .. BLUE E RAVEN �t :� � �?$J c.� ;P_#4,..4+ M� ' 2-f1, r r ��7, a !t y"�r' ." ' �SiW�� � 7 „r t 74; r't,"." ? 4"{fr ,ft ` ; s' Photovoltaic MountingSystem, Sun Frame Microrail Installation Guide, PUB2022SEP28 1.-;�.�. f. w Unirac SFM €„ 1 J,! , Unirac r 1403 N.Research Way 1 NA Orem,UT 84097 41 The product covered by this report is the Sun Frame Micro Rail roof mounted Photovoltaic 600.377.4480 W V W V.B L U E RAV E N S O LAR.C O M Rack Mounting System. This system is designed to provide bonding and grounding to Fuse Ratin40 g: 30A CONFIDENTIAL-THE INFORMATION photovoltaic modules. The mounting system employs anodized or mill finish aluminum bracketsifli HEREIN CONTAINED SHALL NOT BE that are roof mounted using the slider, outlined in section 4 of this report.There are no rails Module Orientation: Portrait or Landscape USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR within this product, whereas the 3"Micro Rail, Floating Splice, and 9"Attached Splice ,, Maximum Module Size: 17.98 ft2 SHALL IT BE DISCLOSED IN WHOLE OR electrically bond the modules together forming the path to ground. UL2703 Design Load Rating: 33 PSF Downward, 33 PSF Upward, 10 PSF Down-Slope IN PART TO OTHERS OUTSIDE PRECIPIENTS ORGANIZATION,EXCEPT Tested Loads-50 psf/2400Pa Downward, 50psf/2400Pa Uplift, 15psf/720Pa Down Slope IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, The Micro Rails are installed onto the module frame by using a stainless steel bolt anodized it*VP. ' .. Trina TSM-255PD05.08 and Sunpower SPR-E20-327 used for Mechanical Loading WITHOUT THE WRITTEN PERMISSION with black oxide with a stainless type 300 bonding pin, torqued to 20 ft-lbs, retaining the ' `' OF BLUE RAVEN SOLAR LLC. modules to the bracket. The bonding pin of the Micro Rail when bolted and torqued, penetrate Increased size ML test: the anodized coating of the photovoltaic module frame(at bottom flange)to contact the metal, Maximum Module Size:22.3 ft2 NABCEP _ t� creating a bonded connection from module to module. UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 30 PSF Down-Slope LG355S2W-A5 CERTIFIED ,,,,4#4,-,.."0,4 Ko.,,,,w,-;11s-ot The grounding of the entire system is intended to be in accordance with the latest edition of the used for Mechanical Loading test. • .1 National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar Mounting configuration: Four mountings on each long side of panel with the longest span of 24" PV INSTALLATION Photovoltaic Systems or the Canadian Electrical Code, CSA C22.1 Part 1 in accordance to the UL2703 Design Load Rating:46.9 PSF Downward, 40 PSF Upward, 10 PSF Down-Slope PROFESSIONAL { Scott Gurney revision •in effect in the jurisdiction in which the project resides.Any local electrical codes must LG395N2W-A5, #PV-01 1 71 9-01 5866 sY be adhered in addition to the national electrical codes. The Grounding Lug is secured to the s, LG360S2W-A5 and LG355S2W-A5 used for used for Mechanical Loading test. photovoltaic module,torqued in accordance with the installation manual provided in this Mounting configuration: Six mountings for two modules used with the maximum span of 74.5" CONTRACTOR: document. IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 50psf/2400Pa Uplift BRS FIELD OPS y 385-498-6700 x Other optional grounding includes the use of the Enphase UL2703 certified grounding system, '. s . ., ` . t" Mechanical Load test to add FlashLoc Slider and Trim Assemblies to UL2703 and IEC 61646 which requires a minimum of 2 micro-inverters mounted to the same rail, and using the same 3s2' Certifications, & Increase SFM System UL2703 Module Size: . engage cable. ` fro, s Maximum Module Size: 27.76 ft2 * UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 21.6 PSF Down-Slope ` �/ Jinko Eagle 72HM G5 used for Mechanical Loading test. ,� ` Mounting configuration: Four mountings on each long side of panel with the longest span of 24" -, Mamzimum module size:21.86 ft2 4 IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 75psf/3600Pa Uplift SunPower model SPR-A430-COM-MLSD used for Mechanical Loading N s � �P« 4 ,�. = ' Fire Class Resistance Rating: n ffi. -Class A for Steep Slope Applications when using Type 1 Modules. Can be installed at any � , interstitial gap. Installations must include Trim Rail. �,o. - '° -Class A for SteepSlope Applications when usingType 2 Modules. Can be installed at any f t P PP YP =1 � interstitial gap. Installations must include Trim Rail. -Class A Fire Rated for Low Slope applications with Type 1 or 2 listed photovoltaic modules. This system was evaluated with a 5"gap between the bottom of the module and the roof's ,,., surface .,y' .1 See section 7.0 illustractions#1, la and lb fora complete list of PV modules evaluated with DRAWING BY:these racking systems ;' ,„1„, ' �x NA PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory __—_ SS Report No. 102393982LAX-002 Page 42 of 138 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 43 of 138 Issued: 11-Apr-2016 Unirac, Inc Revised: 5-Oct-2022 Unirac, Inc Revised: 5 Oct 2022BLUE RAVEN , r. m.. . �; ,✓',. ,rl' r .,,F.r: ,_.... e .4. r-@.'.p..; , {', ,- , e': :F..•... i#,. .'{ ,;.,,„., ;;.e', r,-. {',a,,,.,, . ,,.4 .'�• ....,. ,,,: t ,.. {r .": { {,.,. t" .O':.,%, J.: i,{5 � ,u..sr r.✓s%,�.-- ,::✓r.r-, fSl,.,r.J.,..,a.,F� >., ., "x' fsr % -,d*4 �F o,„-.. ,, r,�> %rr.,�',�^{'�, ,,��;.� r,^;'u ,y r/{�, ,;,, ,r',�;.!{ s{{'.,, !; ;+� f ,,,, ,...?t„r,�.�{,+��,,:�ss." ��{� :�{`�%-v.:,,�.'....:i�!'„2f...., 8." "r,. �r 1 �:{ {{'r:� �`'9°`�,.%f ',%,;,^'""p���{�, {�'^���r�r "�„„?`i �! f-'rF�a!s%,✓,��% .�'��,,.���,�..a:,�t.'.�`iu�.:,�F, �- ,.. -��f r .,,.r >�;;� �_ ...-�t�� ,. , � . '�'� ��{� ,ice.A�:�,tiJr..,r,.{.,,.�.�-.-.-.��.,,;{� �'� u.�,i {r��,v�`.. {,�,,. �� ,-{,.,:.,� {`{'.a,:{, ,r�..�x _, :.... ,. Illustration 1 -Approved PV Modules Illustration 1 a-Approved PV Modules Continue 1403 N.Research Way Orem,UT 84097 �...N ,..,_. r 800.377.4480 Manufacture Module Model./Series Manufacture Module Model!Series Manufacture Module Model 15eries Manufacture Module Model/S es WUNN.BLUERAVENSOLAR.COM Alec, P-Series Era Solar y Brian 1000&Apollo 1000 xxx 1 1KMN JN2WJ HNxxxSA15&SA LG N2T-A4 EVPVx x{N/X/PK}, CONFIDENTIAL THE INFORMATION HEREIN CONTAINED SHALL NOT BE LGxxx(A1C/E1CIE K/NiCJN 2T VS 16 USED FOR THE BENEFIT OF ANYONE ET ET M6726HxxxTW xxxOR DNA-120-tBFJMF}26 Freedom __ Qi 2W) S SA17&SA18, Forever FF MP-B86 370 CJQ1KJSiCJS A VBHNSHALL ITBE DISCLOSED WHOLE EXCEPT AntosIN DNA-144-(BFJMF)26 LGxxxN2T-BS Panasonic VBHNxxx5A11tEJG)&5A18E, IN PART TO OTHERS OUTSIDE FreeVolt Mono PERC RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH LGxxxN1K-66 HNxxxKA01&KAO3&KA04, THE SALE AND CHSM6612P,CH5M6612PJHV.CNSM6612M GCL GCL-P6&GCL-M6 Series --- 6 LGxxx(A1CJM1CJMt1KINiCINiKJQiCJQiKI VBHNxxxZA01,&KA03&KA0 USE OF THE RESPECTIVE EQUIPMENT, Astronergy CHSM6612M/NV,CNSM6610M(BL){BF)/(HF), TO-AN 3,TD-AId4, VBHNxxXZA03,VBHNxxxZA04 WITOUTT BLUE RAVEN SOLHE WRITTEN AR R MISSION Nansol LG Electronics QACJQAK}-A6OF CM5M72M-HC UB-AN1,UD-AN1 LGxxx(N1C/N1K/N2TJN2W)-Eb pelmar SGxxxM{FBIBF} AXN6M610T,AXN6P6101, 36M,60M,60P,72M&72P Series, ; AuxinLGxxx(N1CjN1K/N2W/SiCI52W}-G4 PhonaSolar PS-60,P5 72 NABCEP AXN6M612T&AXN6P612T Helene 144HC MS Mnnafacia((8ifacial Series, LGxxxN2T-15 _. -. AXiotackpremium 60(35mm), _._ .,... 144HC Mi0 SLBrfaciat 5 , _,__.. „ .._..__ _.. _ ) Prism Solar P72 Series LGxx x(N i K/N S WJ N 2T JN 2 Wp L AXIpawer 60(35mm), tf 60-156{h17( t F). LG nc(NICIQICIC?1K)-Ns Plus.Pro.Peak,G3,Cam,65,G6(+),G7 G8{+ CERTIFIED HT Solar Pro,Peak L-G2,L-G4,L-G5,L-Gb,L-G7 HT 72 1561MIP) Miter AXipower 72(40mm), LGxxx(N10E111KJN2W/Q1CIQ1K)-V5 I PEAK DUO BL AXlpremium60(15mm), KG,MG,TG,RI,RG,TI,Mi,HI&KISeries € _-----__ .___--- . ._.----..-.---. .r ._-----...___,_.,-�.._._ ..,... _.._ _.. -.- Q K-G6+ PV INSTALLATION Hyundai - LR4-SO(H18JHiHJfiPBJHPH)-xxxM QPEAK DUO BLK-G6+ITS AXiprem+um 72(40mm). Hu1-SxxxHG HIHPH)-xxxM PROFESSIONAL QPEAK DUO(BLK)-Gs(+) LR4.72tH1Scott Gurney BVM5610, ITEK T IT-HE&3T SE Series LR6.60(BP/HBD/HIBD)-xxxM(30mm) Q-Cells Soviet . .,.___,_...-.._..._, ,. _._...__.._._. _ ..-.,,_.._..,_. ,.._ _.-,..,.._. # Q..PEAKDUO L-G8.3/BFF = #PV-011719-015866 8VM6612 Japan Solar JPS-60&iP5-72 Series LR6-60(8K)(PE)04P6)(HPH)-xxxM(35mm) QPEAK DUO{BLK}ML-G9{+) BYD P6K&MMK-36 Series -- .._.-.. ,. M- LONG LR6-60(8K)(PEXP8)(PH)-xxxM(40mm) 1 I(H 1AP660-xxx,1A6-60-xxx/Sk,JAM6(K)-60I QPEAK DUO XL-GS/G9.2/69,3 CONTRACTOR: C51(HJKJUIY)-MS xxx,IAP6(k}-72-xxx/46B,)AP72SWxxx/ZZ, LR6-72(BP)(HBD)(HIBD)-xxxM(30mm) Q-PEAK DUO(BLK)ML-G10(+) BRS FIELD OPS C53(KJIIU),C53K-M8-AG,C53K-(MS/P} iAP6(k)-60-xxx/488,1AP60SW-xxxfZ, LR6-72(HV)(BK)(PE)(PH}(P8)(HPH)-xxxM QPEAK DUO XL-G(1O/10.2/10,3I10.c/1O d} 385-498-6700 Canadian Solar C53N-M5,CS3U-MB-AG.CS3U(MSiP).CS3W lA5olar JAM6(k)-72-xx,r/22,JAM 725W-xxx/Z2, (35mm) CSSA-M,CS6(K/U),tS6K-(M/P),CS6K-MS Alpha(72)(Black)(Pure) :IAM6(k)-60-60 -xxx/Z2. ! LR6.72(8K)(HV)(PE)(PB)(PH)xxxM(40mm) CS6P-(M/P).CS611-(M/P)-CS6V-M.CS6X-P N-Peak(Black) + i,W:01,02,03.09,10 Mission Solar Energy MSE Series CentmsotarAmenca C-Series&E-Series ii.ZZ�SC,PR,BP,HIT,IS,MW,MR .,_.._.,�. .- -.-.. ,-..,._ REC ---. .- -.--. .__.. �_-----.. ........... ...�..v.._._... ..-..-..., Mitsubishi Mk&MLE Series I N-Peak PEAK Energy ck)Series C't2xxMxx-Oi,CT2xxPxx-03, -. .. '-" 1KM&1KMS Series PEAK Energy BLK2 Series CertainTeed CTxxxMxx-02,CTxxxM-03, , i,nko EagleJKMxxeM Neo Solar Power Co DEM&DSP Series " PEAK Energy 72 Series ---_-..---_.-_ .....---- CTxxxMXx-o4,CTxxxHC11-04 ± --..-...._. _.._-_-_ .a --.- -,-- .IKMxXXM-72HL-V '....__ ___,.-,. ,.._...,__.„. Dahill DH•150M Kyocera ,KU Series DRAWING BY: PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1Ju1-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory __ S S • Report No. 102393982LAX-002 Page 44 of 138 Issued: 11-Apr-2016Nir' Unirac, Inc Revised: 5-Oct-2022 � . . ' '` .ff � o '.r.vlv.r f f%t'e 'lo ; ! r ,.- ' ' o� r ,ai�f,,� ,� ` � rr�.�,:' � �� E RAVEN Er , x,.F u, '..�:� r �i` ,, i„ f? f„ ; `/§' r texclv � �f it, r:`f,"l�; 01,/ �* Illustration 1 b-Approved PV Modules Continue >y 1403 N.Research Way Orem,UT 84097 Manufacture Module Model/Series Manufacture Module Model/Series 800.377.4480 TwinNak Series A-Series A400-BLK,SPR-MAX3-XXX-R, W W W.BLUERAVENSOLAR.COM SunPawer CONFIDENTIAL-THE INFORMATION TwinPeak 2 Series X-Series,E-Series&P-Series TwinPeak 2 BLK2 Series Suntech HEREIN CONTAINED SHALL NOT BE REC(cant) STP STPXXXS $60/Wnrih USED FOR THE BENEFIT OF ANYONE TwinPeak 25(M)72(XV) EXCEPT BLUE RAVEN SOLAR NOR TwinPeak 3 Series(38mm) Talesun TPS72,TP596,TP654,TP660, SHALL IT BE DISCLOSED IN WHOLE OR TP672,Hipor M,SmartIN PART TO OTHERS OUTSIDE TP4{Black} SC,SC B,SC 81,SC 82 RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND Renesola Vitrus2 Series&156 Series Testa TxxxH,Txxx5 Risen RSM72-6 {M}, Series 6 USE OF THE RESPECTIVE EQUIPMENT, FAGS,P005,0005,DCOG,DD06,PC06, WITHOUT THE WRITTEN PERMISSION 5EG Solar I SEG xxx BMD HV 7rina P©24,PE14,0014,DE09.05,OE14,DE15, OF BLUE RAVEN SOLAR LLC. 5-Energy 5N72&SN60 Series(40mm) PE15H Seraphim SEG-6&SRP-6 Series Upsolat UP-MxxxP(-$), , NAECEP Sharp NU-SA&NU-SC Series UP-MxxxM(B) Silfab SLA., SIG,BC Series&SIlxxx(BLJNLJNT/HLJ D7MxxxH7A,D7(M/K}xxxH8A CERTIFIED ML/BKJNXJNU/HC) URE FAKxxx(C8G/E8G),FAMxxxE7G-B13 Salarever USA SE-166.83-xxxM•120N FAMxxxE8G(-BB) PV INSTALLATION PoweDa-xxxR-(AC/PD/80) Eldora, PROFESSIONAL Solaria ; PowerXT-xxxC-PO Vikram Saliva, Scott Gurney PowerXT-main-PM{AC) Somers #PV-011719-015866 - SotarWortd Sunmodute P,uted Waaree AC&Adiya Series CONTRACTOR: Sunmadule Plus Wins it() ' WST&WSP Series BRS FIELD OPS SS-M-360 to 390 Series, Vinyli VGE&YLM Series 1 385-498-6700 SS-M-390 to 400 Series, ZN Shine ZXM6-72,ZXM6-NH144-166_2094 Sonati SS-M•440 to 460 Series, SS-M-430 to 460 BiFaciat Series, 5S 230-265 SunEdison F-Series,R-Series&FLEX FXS Series Suniva 1 MV Series&Optimus Series - DRAWING BY: PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1-Jul-2022)Mandatory SS