Plans
GENERAL NOTES AERIAL VIEW CODE AND STANDARDS ti4� f ace' - - a, 1.ALL WORK SHALL COMPLY WITH 2O17 OREGON ELECTRIC SPECIALTY CODE(OESC),2019 OREGON STRUCTURAL SPECIALTY CODE,2017 OREGON RESIDENTIAL SPECIALTY CODE,AND ALL STATE AND LOCALr'r ii-i.b :v E N BUILDING AND ELECTRICAL CODES. " 2.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. `� '; 140 Research Way SITE NOTES/OSHA REGULATION ( i srw r,'a .A te 1.A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. l l L'd I.7 i UT 8 0�97 2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM. WWW.BLUERAVENSOLAR.COM 3,THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING ROOF VENTS. . ... CI '4.ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND CONFIDENTIAL-THE INFORMATION THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT jy , THE BUILDING OR STRUCTURE. ,-, HEREIN CONTAINED SHALL NOT BE OFFICE T�T� COPY USED EXC FOR TUE RAVEN OF ANYONE lid!1L{ !i EXCEPT BLUE RAVEN SOLAR NOR SOLAR CONTRACTOR " ^ w : SHALL IT BE DISCLOSED IN WHOLE OR .... ,v.- ,,c, IN PART TO OTHERS 1.MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730. ' �y ;. RECIPIENTS ORGANIZATION,EIXCEPT 2.IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PER IN CONNECTION WITH THE SALE AND THE MANUFACTURER'S INSTALLATION REQUIREMENTS. USE OF THE RESPECTIVE EQUIPMENT, 3.AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF 1 WITHOUT THE WRITTEN PERMISSION STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. OF BLUE RAVEN SOLAR LLC. 4.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO ._ - tt, , LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. 5.CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH AC ," ': N A B C E P SUITABLE SEALING COMPOUND. 74. 41 6.DC WIRING LIMITED TO MODULE FOOTPRINT W/ENPHASE AC SYSTEM. , CERTIFIED 7.ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/SUITABLE WIRING CLIPS. K 8.MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT tU AVAILABLE. Y PV INSTALLATION 9.ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS,AC ` ' PROFESSIONAL PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT COMBINERS,AND . s CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND T LISTED FOR THE APPLICATION PER NEC 690.4(B). Os tt #PV-011719-015866 GurneyScott iiio, 10.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. ' 11.TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS(WHEN PROVIDED) CONTRACTOR: IN ACCORDANCE WITH NEC CODE 110.14(D)ON ALL ELECTRICAL CONNECTIONS. '� BRS FIELD OPS EQUIPMENT LOCATIONS 800-377-4480 :` r � � i 1.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT .i "' A � I r { � WILL BE PROVIDED AS PER SECTION NEC 110.26. �,;r 2.EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS , _ , v� ,' ' � .t - : SPECIFIED BY NEC 690.31(A)AND NEC TABLE 310.15(B). � 3.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC 4� APPLICABLE CODES. 'Q Sealed For Q U 4.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. O Q — ND . ' : ` . ,ExistingRoof& CITY OFTCAT D. : Attachment Only C� PROJECT INFORMATION:T T, cn �' ,4, M RI„ IE\V €D I7I3f CODE C 3 �I LIt"ilV.,D gym. NUMBER OF STORIES: 2 'µme - 345FE . N CONDUIT RUN: Interior Approved: [ ] O Q N W W I�ECOBEE QTY: 0 -: [ ] 1./))/( — N LIGHT BULB QTY: 12 Permit .. tom, (l) Z DREG• n� i ZD?3 - 6� SS E o PV METER: Not Required #: DESIGN CRITERIA SITE SPECIFICATIONS SHEET INDEX 'xr 41,16 2D� ci� W `� �' W w Address: ty�� S `i - .� '' AI. cap- ` 2M5o yy ROOF TYPE(1) INFORMATI011�: E tc #: WIND SPEED: 100 mph CONSTRUCTION V B PVI COVER SHEET O ROOF TYPE: Comp Shin e L{ 2 :(-1' ,e �,, �� I— N Cl) Co FRAMING TYPE: Manuf ed Truss �n Date: 2({ 23 GROUND SNOW LOAD: 25 Ib/ft ZONING: RESIDENTIAL PV2-SITE PLAN ., ..,`, I Cl) T ef) WIND EXPOSURE FACTOR: C PV3 ROOF PLAN M 0 C) C� SHEATHING TYPE: OSB PV4-STRUCTURAL 4/13/23 Q p — j- < Cl ATTACHMENT: SFM Infinity Flashkit SEISMIC DESIGN CATEGORY: D Exp:12/31/23 PV5- ELECTRICAL 3-LINE DIAGRAM RACKING: Unirac SFM Infinity @ 48"OC Portrait/48"OC Landscape SCOPE OF WORK PV6 ELECTRICAL CALCULATIONS DRAWING BY: NUMBER OF ATTACHMENTS: 41 PV7-WARNING LABELS AND LOCATIONS Digitally signed Brendan Fillmore ROOF TYPE(2) INFORMATION (IF APPLICABLE): INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM AND ANY (ALL OTHER SHEETS AS REQUIRED) by John A.Calvert *SEE PV4.2 NECESSARY ADDITIONAL WORK NEEDED FOR INSTALLATION. SS- PRODUCT SPEC. SHEETS Date:2023.04.13 PLOT DATE: 13:38:18-06'00' April 13, 2023 • • , PROJECT NUMBER: SYSTEM TO BE INSTALLED INFORMATION: THE ISSUANCE OF A PERMIT UTILITY COMPANY: 731587 DC SYSTEM SIZE: 6 kW DC BASED ON CONSTRUCTION �a 1 ' �4~ � Portland General Electric (PGE) " .� gar =`,s lts SHEET NAME: AC SYSTEM SIZE:4.35 kW AC DOCUMENTS AND OTHER 5 rp1; t ki MODULE TYPE: (15)QCeIIs Q.PEAK DUO BLK ML-G10+400 DATA SHALL NOT PREVENT Approved plans COVER SHEET THE CODE OFFICIAL FROM PERMIT ISSUER: shall be on job sit?. INVERTER TYPE: Enphase IQ8PLUS-72-2-US �, MONITORING: Enphase IQ Combiner 4 X-IQ-AM1-240-4 REQUIRING THE CORRECT'ON City of Tigard REVISION: PAGE NUMBER: ' '`7 rPRORS. ORSC 105.4 0 PV1 PV SYSTEM SPECIFICATIONS LEGEND TOTAL NUMBER OF MODULES: 15 JUNCTION BOX MODULE MAKE AND MODEL: QCells Q.PEAK DUO BLK ML-G10+400 MODULE WATTAGE: 400W DC r BLUE RAVEN K_MJ UTILITY METER INVERTER MAKE AND MODEL: Enphase IQ8PLUS-72-2-US 1403 N. Research Way INVERTER TYPE: Microinverter(1 Inverter per PV Module) MSP MAIN SERVICE PANEL Orem, UT 84097 INVERTER CURRENT OUTPUT: 1.21A AC 800.377 4480 INVERTER NOMINAL VOLTAGE: 240V AC AC DISCONNECT WWW.BLUERAVENSOLAR.COM INVERTER WATTAGE: 290W AC CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR LOAD CENTER IN PART TO OTHERS OUTSIDE LC RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND A USE OF THE RESPECTIVE EQUIPMENT, .SUB SUBPANEL WITHOUT THE WRITTEN PERMISSION ISE ( OF BLUE RAVEN SOLAR LLC. PV PV METER NABCEP TS TRANSFER SWITCH CERTIFIED PV INSTALLATION ESS SUNPOWER ESS PROFESSIONAL \ Fp I uney #PV-0117C1�9r016S66 w > ElEl � HUB SUNPOWER HUB+ Scott CONTRACTOR: Q El ElI BRS FIELD OPS p I RPO REMOTE POWER OFF 800 377 4480 H re ArffIGl7����L" r El m FIRE SETBACK m Pe ❑ ° I TRENCHING U / 1 Q �M .— �� I PROPERTY LINE p 1 H m I SCALE: 3/32" = 1'-0" a c N CO Sealed For uO < rn N N Existing Roof& p Z a) _c c y N Attachment Only ,,,' 0es14 GtPJ ,,, W .0 a' r w w 0cOO � � 415PE�a' -7 0 H T.61, ORES � o � CY) ao $,yw R DRAWING BY: A. CP1/4 Brendan Fillmore PLOT DATE 4/13/23 April 13, 2023 Exp: 12/31/23 l� 1.AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER PROJECT NUMBER: 2. FOR PRESCRIPTIVE INSTALLATIONS, ROOF ATTACHMENTS 731587 SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OFA ROOF EDGE, SHEET NAME: HIP, EAVE, OR RIDGE (OSSC 3111.3.5.3) SITE PLAN 3. FOR NON-PRESCRIPTIVE INSTALLATIONS, PLANS WILL BE APPROVED AND STAMPED BY LICENCED ENGINEER AND ALL REVISION: PAGE NUMBER: ATTACHMENT SPACING WILL BE AS SHOWN ON PV4. 0 n\ ,2 PV SYSTEM SPECIFICATIONS LEGEND TOTAL NUMBER OF MODULES: 15 MODULE MAKE AND MODEL: QCells Q.PEAK DUO BLK ML-G10+400 JUNCTION BOX MODULE WATTAGE: 400W DC rMJ UTILITY METERBLUE RAVE INVERTER MAKE AND MODEL: Enphase IQ8PLUS-72-2-US4 1403 N. Research Way INVERTER TYPE: Microinverter(1 Inverter per PV Module) MSP MAIN SERVICE PANEL Orem, UT 84097 INVERTER CURRENT OUTPUT: 1.21A AC 800.377.4480 INVERTER NOMINAL VOLTAGE: 240V AC AC DISCONNECT VWVW.BLUERAVENSOLAR.COM INVERTER WATTAGE: 290W AC CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR M P3 SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE MODULES: 2 LC LOAD CENTER RECIPIENTS ORGANIZATION,EXCEPT AZIMUTH: 179 IN CONNECTION WITH THE SALE AND 45 PITCH: USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION TSRF: 93% SUB SUBPANEL OF BLUE RAVEN SOLAR LLC. AREA: 201 ft.' �VJ PV METER NABCEP 1 / TS TRANSFER SWITCH CERTIFIED PV INSTALLATION ® / ESS SUNPOWER ESS PROFESSIONAL tz ® ®a ®¢ Scott Gurney #PV-011719-015866 w / p ; HUB SUNPOWER HUB+ 0 - BRS FIELD OPS _ 1-1. RPO REMOTE POWER OFF / / 1 / J 800 377 4480 ~ FIRE SETBACK z R TRENCHING 0 1(/ • I / D D 1 Z U PROPERTY LINE 0 / I F- Y a I G / SCALE: 3/16" = 1'-0" a M 1' N 4 CO I 1' , N N Lii I MP2 Z < a, NN AC \ M POINT OF INTERCONNECTION #OF MODULES: 6 E re E }' g N 2 AZIMUTH: 269 #nOF1MODULES: 7 IL •c N LV W PITCH: 23 Sealed For —_ ?� L F CB UNDERGROUND SERVICE LINE o AZIMUTH: 89 Existing Roof& 0 O >- N TSRF: 86/o PITCH: 23 Pf t�0c -p AREA: 371 ft.2 Attachment Onlyn. oIN s j M cn u) TSRF: 80% AREA: 541 ft.z �`4 � -. O .� C) U 345REs' VIa .— I— Q0 �, DRAWING BY10 T6OREc Brendan Fillmore • k°16.20 4-. PLOT DATE: CP April 13, 2023 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER PROJECT NUMBER 2. FOR PRESCRIPTIVE INSTALLATIONS, ROOF ATTACHMENTS 731587 4/13/23 SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY Exp:12/31/23 DIRECTION WHERE LOCATED WITHIN 3 FT. OF A ROOF EDGE, SHEET NAME. HIP, EAVE, OR RIDGE (OSSC 3111.3.5.3) 3. FOR NON-PRESCRIPTIVE INSTALLATIONS, PLANS WILL BE ROOF PLAN APPROVED AND STAMPED BY LICENCED ENGINEER AND ALL REVISION PAGE NUMBER: ATTACHMENT SPACING WILL BE AS SHOWN ON PV4. 0 PV3 STRUCTURAL INFORMATION: STRUCTURAL NOTES: PV MODULE UNIRAC SFM 2"MICRORAIL UNIRAC SFM 6.5"SPLICE ROOF TYPE(1): ROOF TYPE: Comp Shingle 1.AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER SHEATHING TYPE: OSB 2. FOR PRESCRIPTIVE INSTALLATIONS, ROOF ATTACHMENTSBLUE RAVEN FRAMING TYPE: Manufactured Truss SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY FRAMING SIZE: 2x4© 24"OC DIRECTION WHERE LOCATED WITHIN 3 FT. OF A ROOF EDGE, 'I M CEILING JOIST SIZE: 2x4 @ 24"OC HIP, EAVE, OR RIDGE (OSSC 3111.3.5.3) 23" IA 1403 N. Research Way 3. FOR NON-PRESCRIPTIVE INSTALLATIONS, PLANS WILL BE i MAX. ~ 48" MAX.-- ___-- LANDSCAPE Orem, UT 84097 ATTACHMENT: SFM Infinity Flashkit APPROVED AND STAMPED BY LICENCED ENGINEER AND ALL 800.377.4480 RACKING: Unirac SFM Infinity ATTACHMENT SPACING WILL BE AS SHOWN ON PV4. WWW.BLUERAVENSOLAR.COM @ 48"OC Portrait/48"OC Landscape PV MODULE UNIRAC SFM 2"MICRORAIL UNIRAC SFM 6.5"SPLICE CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE NUMBER OF ATTACHMENTS: 41 USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR PV MODULE COUNT: 15 Modules '� _' I I SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE TOTAL ARRAY AREA: 306.0 ft2(20.4ft2/panel) RECIPIENTS ORGANIZATION,EXCEPT TOTAL ROOF AREA: 1342 ft2 IN CONNECTION WITH THE SALE AND ARRAY/ROOF AREA: 22.8% uN " N " WITHOUT THE WRITTENEPERMI SS ON ARRAY WEIGHT: 750 lbs(50 lbs/panel) 23" OF BLUE RAVEN SOLAR LLC. DISTRIBUTED LOAD: 2.45 lbs/ft2 MAX. 48"MAX. y PORTRAIT POINT LOAD: 18.29 lbs/attachment `NOTE.LISTED NUMBER OF ATTACHMENT POINTS ARE AN ESTIMATE ONLY AND MAY VARY 0 ATTACHMENT SPACING- FRONT VIEW BASED ON FIELD CONDITIONS.MAXIMUM ATTACHMENT SPACING TO BE FOLLOWED PER -RACKING ATTACHMENTS TO BE STAGGERED NABCEP ENGINEER OF RECORD SPECIFICATIONS. SCALE: 3/4"= 1'-0" CERTIFIED UNIRAC SFM INFINITY UNIRAC SFM MICRORAIL/SPLICE O PV INSTALLATION PV MODULE PROFESSIONAL QCELLS Q.PEAK DUO BLK ML-G10+400 Scott Gurney #PV-011719-015866 PV MODULE 11 PORTRAIT CONTRACTOR: BRS FIELD OPS '0717 UNIRAC SFM SLIDER • ROOF STRUCTURE 800-377 4480 • i• (E) ROOF MODULE 'OZ SHEATHING --+--' _ — WIDTH — FLASHING ' —_ O w� (1)5/16"STAINLESS STEEL LAG BOLT � T ! 0 '--- Q WITH 2-1/2" MIN. EMBEDMENT LANDSCAPE Z O � 8 AND FLAT WASHER 21/2" MIN. EMBED. �, u"I23° F' _� _ ' MODULE- LO a Cr) _�' L- WIDTH te a) N (fl MIDDLE/TOP STANDOFF DETAIL ATTACHMENT SPACING- SIDE VIEW Z N N SCALE: 3" = 1'-0" (E) BUILDING STRUCTURE D SCALE: 1/2"= 1'-0" ct E O M m MI .(13 ca W W QCELLS Q.PEAK DUO BLK ML-G10+400 2 — L H' I— PV MODULE O N M 12 N u) V) 5,�, co Sealed For V p° , H Q im UNIRAC SFM TRIMRAIL f +? s Existing Roof& FLASHING In PRap Attachment Only GIN ,•, DRAWING BY UNIRAC SFM SLIDER AND C.1 Brendan Fillmore TRIMRAIL ROOF ATTACHMENT '�-_ (E) ROOF 4 345PE i fir' SHEATHING PLOT DATE: I '46 April 13, 2023 (1)5/16"STAINLESS STEEL LAG BOLT L � ' �i/, 'ice Irrg�OREGi N, N. PROJECT NUMBER: WITH 2-1/2"AND FLAT WASHERMIN. EMBEDMENT '741 16 i\-1N 731587 1I12. MM BED. C SHEET NAME: 1_ 4/13/23STRUCTURAL B BOTTOM STANDOFF DETAIL Exp: 12/31/23 REVISION: PAGE NUMBER: SCALE: 3" = 1'-0" (E) BUILDING STRUCTURE 0 PV4 III 14 AWE TH iN/7H"a4N-?_CU,RACK 1111 18 2 A ACC 12) 10 AWG TIIHNIIHWN-,?,CU,BLACK(LI) MAX 9,7 A AC (1) tO AWG 1HHN/THWN,2,Cu.,SLACK 1;1il MAX 9,7 A AC °I I) 12 2 Tr-€R,THHN(THWN 2,,CU MAX 9.7 A AC • +� (11 10 AWG FHUN/THWN-2,CU,.RED I L2) 240 V AC y(2) 74 AW N/TH4"A-2.CU_,RED'It 2I .240 V AC )It 10.AWG THH.-h4f1HWN•2,CU..RED till 240 V AC (73 6 AWG BARE.CU(EGC..1 240 V AC .l (' ' 10AWG 7H?iNj1HWN-t,CU.,Y�.''Hi1E IN) all 10 AWG III N,(1HVd -7,C.LI,GRE1N If ) I1.) 10 AWG fk?H x�f1'riwN-2,CL+.Q7E-EN I ECsC.i . 1(11 10Atit4THP/NJ7I+t4N-2.(U..GREEw(1Gc) OR to-10 -tw,GiORNNt-8 ,71-11,`t114WN•.4SO1,10CU. (1I 4 INCH EMT EXIERtOR (1) 3/4 INCH{.,MI E%ICRIOR (1) .1/4 INLEt EMT(Not Require t tot ti7--11 or NM-8 Cibir1 IN ILICOR R EX1fRit}R BLUE E N 1403 N. Research Way Orem, UT 84097 800.377.4480 W W W.BLUERAVENSOLAR.COM DESIGNER NOTES: ELECTRICAL NOTES: CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE LOAD SIDE BREAKER IN MSP.THIN AND ALLOCATED BREAKERS TO MAKE SPAVE FOR PV. ALL CONDUIT TO BE RAN AT LEAST 7/8 IN.ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. USED FOR THE BENEFIT OF ANYONE AC DISCONNECT TO BE LOCATED WITHIN 10 FEET OF THE UTILITY METER, EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE (15)QCelis Q.PEAK DUO BLK ML-G10+400 RECIPIENTS ORGANIZATION,EXCEPT ENPHASE IQ COMBINER 4 UL 1703 COMPLIANT IN CONNECTION WITH THE SALE AND (E)200A MAIN SERVICE PANEL X-IQ-AM1-240-4 (15) Enphase IQ8PLUS-72-2-US USE OF THE RESPECTIVE EQUIPMENT, (E)200A/2P MAIN BREAKER (SOLAR LOAD ONLY) UL 1741 COMPLIANT WITHOUT THE WRITTEN PERMISSION 4"x4"x4"PVC JB-1 EZ SOLAR OF BLUE RAVEN SOLAR LLC. PV AC DISCONNECT JUNCTION BOX JUNCTION BOX (E)200A/2P NON-FUSED L �10-_ LOCKABLE,VISIBLE OPEN (N)20i1\„2P u uu , s L ' 30A,240V,2-POLE '~� `� n JB EGC IN JB-1 �—� (1)CIRCUIT OF NABCEP (E ENVOY r -f 8 MODULES 'PV BREAKER TO BE LOCATED CERTIFIED AT OPPOSITE END OF BUSSING L 15A/2P ❑ ❑ FROM MAIN BREAKER 2 1 PV INSTALLATION (N)25A/2P N ❑ ❑ L, o� LZ _ (N)20Al2P Li L, n JB-1 L, n (1)CIRCUIT OF PROFESSIONAL ❑ L2 r EGC _■ EGC• E E2 L2 \'`�—— Scott Gurney 7 r EGC EGC fir} EGC _ 7 MODULES #PV-01 1 71 9-01 5866 120/24O VAC 15 __ V V CONTRACTOR: 60HZ0fjj BRS FIELD OPS 1 PHASE TO UTILITY 800-377-4480 GRID —_ III —_J I I I C.) I Q Z (E)GROUNDING 0 0 ELECTRODE(S) ...,,,,,,,,:-Traweik,-;T,?•-•.-• M :" grate - U. < rn N N n - - Z V) V) ( g I4 W (6 5 N I— H „ .._ : — �Y - !,, ** 1111 1., 0 0 ° u) u) 7 ^ �.. s I- c+ (0 2 V) V) O V >t-"t1 04 `A 17A "8 C1 I , e 1 a i DRAWINGL BY: P �*1 t71 `_ Brendan Fillmore PLOT DATE: -rc ryrrc .,G" tl v. 4 . ; 41Ai 6 ,,I . '_ . _ . April 13, 2023 . INTERCONNECTION NOTES PROJECT NUMBER: 705.12(B)(3)THE FOLLOWING METHOD(S)SHALL BE USED TO # • 731587 DETERMINE THE RATINGS OF BUSBARS: (2)WHERE TWO SOURCES, ONE A PRIMARY POWER SOURCE AND THE OTHER ANOTHER POWER SOURCE, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT :: --1 SHEET NAME: CONTAINS LOADS, THE SUM OF 125 PERCENT OF THE ) , - rELECTRICAL • POWER-SOURCE(S)OUTPUT CIRCUIT CURRENT AND THE RATING OF , # ; ` � ;-, y ( ,i ',r k It ,.E �. ,' -� ., •• REVISION: PAGE NUMBER: THE OVERCURRENT DEVICE PROTECTING THE BUS BAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR. UTILITY COMPANY: Portland General Electric (PGE) PERMIT ISSUER: City of Tigard 0 PV5 MODULE SPECIFICATIONS QCells Q.PEAK DUO BLK ML-G10+400 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(STC} 400 W 1 TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX,SHORT CI RCUI I CURRRENT(ISC)= 9.7 A AC MODULE VOC 45.3 V DC STATE Oregon JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 12.1 A AC MODULE VMP 37.13 V DC CITY Tigard CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG MODULE IMP 10,77 A DC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING 30 A BLUE RAVE MODULE ISC 11,14 A DC ASHRAE EXTREME LOW TEMP('C) -6 AMB.TEMP.AMP.CORRECTION= 0.91 VOC CORRECTION -0.27 %f C ASHRAE 2%AVG.HIGH TEMP( C) 36 ADJUSTED AMP.= 27.3 > 12.1 1403 N. Research Way VMP CORRECTION •0.34 %PC 1 JUNCTION BOX TO MAX_SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC Orem, UT 84097 SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT{ISC X1.25}= 12.1 A AC 800.377.4480 W W W.B L U E RAV E N SOLAR.CO M ADJ_MODULE VOC @ ASHRAE LOW TEMP 49.1 V DC NUMBER OF MODULES PER MPPT 8 7 CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG CONFIDENTIAL-THE INFORMATION ADJ.MODULE VMP @ ASHRAE Z`IC AVG.HIGH TEMP 31,7 V DC DC POWER RATING PER CIRCUIT(STC) 3200 2800 CONDUCTOR RATING 30 A HEREIN CONTAINED SHALL NOT BE _.�,_. -�.,..W__ _.__„ . _._.____ ,.....- - ___,._...... .,.__ . ..w�.. __. -___ USED FOR THE BENEFIT OF ANYONE TOTAL MODULE NUMBER 15 CONDUIT FILL DEBATE= 1 EXCEPT BLUE RAVEN SOLAR NOR MICROINVERTER SPECIFICATIONS En hase IQ8+Mtcromverters STC RATING OF ARRAY 6000 AMB_TEMP.AMP.CORRECTION= 0,91 SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE POWER POINT TRACKING(MPPT)MIN/MAX 30 , 58 V DC AC CURRENT -, MAX POWER POINT(IMP 9.7 8.5 ADJUSTED AMP.= 27.3 > 12.1 RECIPIENTS ORGANIZATION,EXCEPT MAXIMUM INPUT VOLTAGE 60 V DC MAX,CURRENT(IMP X 1,25) 12.1 10,5875 JUNCTION BOX TO MAX,SHORT CIRCUIT CURRRENT(ISC)= 9,7 A AC ISC OH THE SALE AND USE OFF TH THEE R RES WITH EQUIPMENT, MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 12.1 A AC WITHOUT THE WRITTEN PERMISSION MAXIMUM USABLE DC INPUT POWER 440 W MAX,COMB,ARRAY AC CURRENT(IMP) 18.2OF BLUE RAVEN SOLAR LLC. CONDUCTOR(UF-B,COPPER{60'C))= 10 AWG MAXIMUM OUTPUT CURRENT 1.21 A AC MAX ARRAY AC POWER 4350W AC CONDUCTOR RATING= 30 A AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 0,8 NABCEP MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. /RISE(V) VEND(V) %VRISE AMB,TEMP.AMP.CORRECTION= 0.91 CERTIFIED ICEC WEIGHTED EFFICIENCY 97'3%3 VRISE SEC_1(MICRO TO JBOX) 28.8 12 Cu_ 0.93 240.93 0.39% ADJUSTED AMP.= 21.84 > 11.1 • VRISE SEC.2(JBOX TO COMBINER BOX) 55 10 Cu., 1.35 241,35 0.56% COMBINER BOX TO INVERTER RATED AMPS= 18.2 A AC PV INSTALLATION AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC,3(COMBINER BOX TO POI) 5 10 Cu, 0,23 240.23 0.109E MAIN PV OCPD(15) MAX,CURRENT(RATED AMPS X1.25) 22.69 A AC PROFESSIONAL NOMINAL OPERATING AC VOLTAGE 240 V AC I TOTAL VRISE 2.51 242,51 1.05% CONDUCTOR(THWN-2,COPPER(75'C TERM.)) 10 AWG Scott Gurney #PV-011719-015866 NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 3S A MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690,54) CONDUIT FILL DERATE= 1 CONTRACTOR: MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 18.2 A AC AMB.TEMP.AMP.CORRECTION= 0,91 BRS FIELD OPS MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 VAC ADJUSTED AMP,= 31,85 > 22.7 800 377 4480 0 GROUNDING NOTES WIRING &CONDUIT NOTES Z Q U 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1 ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE O 0 PROVIDED. PER [NEC 690.47], THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE INADEQUATE, OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). 'CC CO ,[ USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3 ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE CO " I. co 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4. UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. 0 > ~ N N SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE 0) 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. - Cl) ._. Mn COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE-CONDUCTOR CABLE LISTED AND C C 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS a) 0 c c PARTS OR MODULE FRAMES ACCORDING TO[NEC 690 46]. REQUIRED. EI.I • 0 I.I.I W 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE 2 E 'S L I` I� 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O (I) O Cl) Ms. MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE ~ Mn Co MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],8[NEC 310.15(B)(3)(C)]. N �+ 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV RESISTANT.AND UL = 0 V V GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP () o r- I- Q Q 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED. 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY: EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE: 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) April 13, 2023 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK, PHASE B OR L2-RED, PROJECT NUMBER: ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND *USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWWTHWN-2 AND MAY BE USED INSIDE 731587 CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] **USE-2 IS AVAILABLE AS UV WHITE REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME: FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250 118(10)]. DISCONNECTING MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.15]. EL EC C A 1 l�/1LliCS 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC L l� 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER: 0 PV6 STANDARD LABELS ADDITIONAL LABELS LABEL 1 : LUE RAVEN FOR PV SYSTEM DISCONNECTING MEANS WHERE THE LINE AND LOAD TERMINALS MAY BE ENERGIZED IN THE LABEL 3 ELECTRIC SHOCK HAZARD OPEN POSITION. DUAL POWER SUPPLY IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL 1403 N. Research Way [2017 NEC 690.13(B)] ANYWHERE THAT IS POWERED BY BOTH THE UTILITY Orem, UT 84097 TERMINALS ON THE LINE AND [2020 NEC 690.13(B)] AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL LOAD SIDES MAY BE ENERGIZED SOURCES:UTILITY GRID AND AND SUBPANELS.{NEC 705.12(B)(3)] 800.377.4480 OPEN POSITION PV SOLAR ELECTRIC SYSTEM IN THEW W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE LABEL 2 USED FOR THE BENEFIT OF ANYONE PHOTOVOLTAIC SYSTEM SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT EXCEPT BLUE RAVEN S NOR SHALL IT BE DISCLOSED INN WHOLE OR THE DISCONNECTING MEANS AS A POWER SOURCE IN PART TO OTHERS OUTSIDE A AC DISCONNECT A AND WITH THE RATED AC OUTPUT CURRENT AND THE RECIPIENTS ORGANIZATION,EXCEPT NOMINAL OPERATING AC VOLTAGE IN CONNECTION WITH THE SALE AND RATED AC OUTPUT CURRENT 18.15 A [2017 NEC 690.54] USE OF THE RESPECTIVE EQUIPMENT, [2020 NEC 690.54] WITHOUT THE WRITTEN PERMISSION NOMINAL OPERATING AC VOLTAGE OF BLUE RAVEN SOLAR LLC. LABEL 3 NAB CEP ® IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL CERTIFIED ANYWHERE THAT IS POWERED BY BOTH THE UTILITY DUAL POWER SUPPLY AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL AND SUBPANELS. LABEL 10 PV INSTALLATION SOURCES: UTILITY GRID AND [2017 NEC 705.12(B)(3)] ® PERMANENT PLAQUE OR DIRECTORY TO BE PROFESSIONAL [2020 NEC 705.12(8)(3)J LOCATED AT MAIN SERVICE EQUIPMENT DENOTING Scott Gurney PV SOLAR ELECTRIC SYSTEM POWER TO THIS BUILDING IS ALSO SUPPLIED THE LOCATION OF THE RAPID SHUTDOWN SYSTEM #PV-011 71 9-01 5866 FROM A ROOF MOUNTED SOLAR ARRAY.SOLAR DISCONNECTING MEANS IF SOLAR ARRAY RAPID SHUTDOWN DISCONNECTING SWITCH IS NOT CONTRACTOR: LABEL 4 ARRAY RAPID SHUTDOWN DISCONNECT IS GROUPED AND WITHIN LINE OF SITE OF MAIN BRS FIELD OPS ® APPLY TO THE DISTRIBUTION EQUIPMENT ADJACENT LOCATED OUTSIDE NEXT TO THE UTILITY METER. SERVICE DISCONNECTING MEANS. TO THE BACK-FED BREAKER FROM THE POWER [2017 NEC 705.10 AND 690.56(C)(1)(a)] 800-377-4480 POWER SOURCE OUTPUT CONNECTION SOURCE. [2020 NEC 705.1 o AND 690 56(C)] DO NOT RELOCATE [2017 NEC 705.12(B)(2)(3)(b)] [2020 NEC 705.12(13)(3)(2)] THIS OVERCURRENT LABEL 11 DEVICE A PERMANENT PLAQUE OR DIRECTORY TO BE 0 LOCATED AT AC COMBINER PANEL. Q PHOTOVOLTAIC SYSTEM [2017NEC 110 21(B)] ZO gni° COMBINER PANEL [2020 NEC 110.21(8)] - DO NOT ADD LOADS chi - co d' to 0 > N W W U- Q6- NN UTILITY MAIN (IF S ERCONNELIQN AC PV PV COMBINER Z cn U) Cl) METER SERVICE PANEL IS MADE HERE) DISCONNECT METER BOX ce E 0 2 g W .(13p W W SOLAR PV SYSTEM EQUIPPED LABEL 6 E O E O E CD 0 ° >- } BUILDINGS WITH PV SYSTEMS SHALL HAVE A (- Q) (� 2 N (/) WITH RAPID SHUTDOWN PERMANENT LABEL LOCATED AT EACH SERVICE O c -i: O O ED = o " c) U U EQUIPMENT LOCATION TO WHICH THE PV SYSTEMS 0 Q N— H Q Q TURN RAPID SHUTDOWN ARE CONNECTED OR AT AN APPROVED READILY SWITCH TO THE VISIBLE LOCATION AND SHALL INDICATE THE LOCATION C-,)IF BREAKER O 0 11 "OFF" PV SYSTEM uaaecm�c. DRAWING BY: SHUTDOWN s OF RAPID SHUTDOWN INITIATION DEVICES. IS USED AND REDUCE 2017 NEC 690.56 C 1 a ISN CK THE EMI ( ( )()()] 8 Brendan Fillmore IN THE ARRAY (2020 NEC 690.56(C)] LABEL 7 OR PLACARD PLOT DATE: 3 RAPID SHUTDOWN SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT April 13, 2023 SWITCH FOR SWITCH -0 SOLAR PV SYSTEM [2020NEC690.56(C)(2] -0 PROJECT NUMBER: 731587 LABELING NOTES SHEET NAME: 1)LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL LABELS 2)LABELING REQUIREMENTS BASED ON THE 2017&2020 NEC CODE,OSHA STANDARD 19010.145,ANSIZ535. REPRESENTATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED 3)MATERIAL BASED ON THE REQUIREMENTS OF THE AHJ. REVISION: PAGE NUMBER: 4)LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND SHALL NOT BE MAY VARY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON 3 LINE 0 PV7 HANDWRITTEN[NEC 110.21] DIAGRAM. 3 LINE DIAGRAM ON PV5 TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. powered by 1 '.,--..Cr, '^ .+' a 3r) 1403 N.Research Way Q.ANTUM DUO/ �"" 4cinx41.1in81 26min_ludegframe) - orem,UT84os7 (1879 mm x 1045.,nm x 32 mm) s u° mm, 800.377.4480 ,sight 48.5l bs(2z.0 kg) _- `-' _ ___ __ I I f WWW.BLUERAVENSOLAR.COM ront Cover 0131r(3. min)-hermely prestressed glass with �~ arti-reflection technology ° 1BC1° CONFIDENTIAL-THE INFORMATION „mp Back =4er Composite film HEREIN CONTAINED SHALL NOT BE Frarr,0, _ ._ Black anodized al-minum _ USED FOR THE BENEFIT OF ANYONE 6 x 22 monocrystalline Q ANTUM solar half cells�� s EXCEPT BLUE RAVEN SOLAR NOR u c ion Box 2.09-3.98 in x 1.26-2.36in x 0.59-071in'� SHALL IT BE DISCLOSED IN WHOLE OR (53-101m c x 32-60mm x15-18 mm)IP6"with bypass diodes °mm> IN PART TO OTHERS OUTSIDE ,able 4mm2Solar able(+)>492i,(1250mm:,O>-49-2in(1250aa) n RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND ;Connector S'aabll MC4.IP68 I - ._I_�__ USE OF THE RESPECTIVE EQUIPMENT, °sE, t zasmm, WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. Q.PEAK DUO BLK ML-G10+ , COontrolledPV �C AR r < ,T 39 POWER CLASS 385 390 395 400 _�� 405 385-405 TUVRhelnland - Mar. PM A EAT --- STCCdr. L,NB,3, NEPTOL iCE 5W � ____ E P a - ERTIFIED . °�'1ern '' www.mv.com _ e- [W] 385 390 395 400 405 CERTIFIED ID 1111232516 ENDURING HIGH ? ' 4l1104 07 U 114 uv NR '+Volt.°.. V,. J 45.19 .. 45.23 40. 40 3J 45.34 PERFORMANCE °p EUPD RESEARCH --- '----- --- --.-- _ PV INSTALLATION 1n. +'urren 3a- _ iA] 10.59 1065 1n71 10 7 �0.83- TOP BRAND PV J .-. -I' --. __,_ ,,.,,.. __ 3 PROFESSIONAL YYWW��� mat P V:� iVl 36-36 �� • �g .�662 .- 6.88 371 V01Scott Gurney Eunoac 1 ___.. .._ �1 (%] 19.6 >199 20.1 >204 ... y 0.6 assErn°rEnNn'e MINIS. Ail aEv,OPMA E,aT l,.,PMA; D ''a TING C ONS NM r .. #P - 719-015866 USA 2021 ' WarrantyQ CELLS S werarM�w, NI] 28ec 25296 2895 0 1 308.a ,a ertur,° °anti g _._7 9.oc CONTRACTOR: _aer. _ait Ivj __ -42.62 - 42-65_.__ 4269 42 42.76 BRS FIELD OPS _n.. BREAKING'THE 20%EFF:CiENC"BARRIER i arrant r. ..I _ ;Ai 8.35 - 8.41 6.46 .851 8.57 111LL8.1 .._. - .__. i. _ ._....._ _..... ._ ._ ._. _ _5 498 6700 Q.ANTUM DUO Z Technology with zero gap cell layout Rage a >t ? V,,, tvj 34.59 34.81 3 a 35.25 5.46 boosts module efficiency up to 20.9%. 'Measurement tolerances Pm„±3%,Ise,Voc 5%at STC:1000 W/m'25+2°C,AM 1.5 according to IEC 60904 3.�800W/rn,NMOT,spectrum AM 15 O CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE _- THE MOST THOROUGH TESTING PROGRAMME IN THE NrDUSTRY v° Q CELLS is the first solar module manufacturer to pass the most comprehen- ,,- °, At least 9a%of nominal power during , -- p first year.Thereafter max.0.5% sive quality programme in the industry:The new"Quality Controlled PV"of degradation per year.At(east 93.5% °, nominal power up to 10 years.At the independent certification institute TUV Rheinland. least 86%of nominal power up to `' ' >, ' 25 years. INNOVATIVE A_;_ VSE,2T-. EP.TECH%0 OGY - Al:',I .e3., l data within measurement tolerant- '` Optimal yields,whatever the weather with excellent = ,.?, ,:1 F es.Full warranties In accordance withlow-light andtem eraturebehavior. r) no moo , the warranty terms of the OCEts '°° °° °° p sales organisation of your respective ,o country. �, r` �� _ 1' n,r a 6,, a Typical module performance under low irradiance conditions in ENDURING HIGH _RIEOR IA50E comparison to STC conditions(25°C,1000W/rn) L. Long-term yield security with Anti LID Technology,Anti PID �,- TEMPERATURE COEFFICIENTS 0 Technology',Hot-Spot Protect and Traceable Quality Tra.QT" __ - --- o - ,n. =ureCoef . a [%/K] ,.... +0.04 Temper.,._ ,efficient�.L. 13 i%/Kl_._ 0.27 Ter,-,I, snareCoef, ,:.n e�,...,., High-tech aluminum alto frame,certified for PROPER I Ssniper; NMOT g v t.l`1cATHER RATING Nov--1 ( (43-3'C) EXTREME` _ _ ['Fj109,5.4_.,.__._.__..._ FOR SYSTEM DESIGN high snow(5400 Pa)and wind loads(4000 Pa). -- -__ z-:- m S/sr.... "-age V,,; [V) 1000(EC)/1000(UL) PV vo,. .:ass r,,...s- Gass ii a ,=ua,s.at�rrg .H DC] 20 Rating :,ANSI U1 ''- TYPE m A RELIABLE INVESTMENT _ ___ __ Max De .,ad Pus- Ilc ift=j 'u6 0 Pa)/55r266J?a) itted'rr -..per ,._. 40 F up to 185"F o Inclusive 25-year product warranty and 25-year or ,, 40 c u -t.a,rt Ibs/ft- 113 54001oe/B4,4t,00 Pa; p linear performance warranty2. __ o d C) o s See Installation Manual __._- -_..,_._..-. __._.___ ____ _...__.._ ..._..___ a a ssay 12 3,, ea^ 'APT test conditions according to IEC/TS 62804-L2015,method A(4500 V,96h) _ ��- _ no_ocv CEO_ „o_oc, See data sheet on rear for further information1-8 U QUALIFICATIONS AND CERTIFICATES PACKAGING INFORMATION e >av3o CE pI m. Wes" s ® DRAWING BY: us°,r T �.. d IJ o o ' s EC 612152016 IEC 617302016, _ _. THE IDEAL SOLUTION FOR: Patent No S8ss21s(solar Dells) $0® ( E 0 4 20rpm 165 24 24 Fc ft c a y n C US ` ♦ eaginF 1940mm 1100mm 1220mm 751kg pallets pallets modules EvEp PLOT DATE: 60 Note:Installation instructions must be followed.See the installation and operating manual or contact our technical service department for further information on approved installation and use of this product Engineered in Germany cE I IC Hanwhe O CELLS America Inc PROJECT NUMBER: el 400 Spes m a Center i ,',Su.e:400Irvine.CA 92618 USA I TEL ri 949 748 59 96 I EMA ndu ri;-fa5gcallsccP-.I WEB n,wmq-oegsas SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: NU V V BLUE RAVEN A �,,, EN PHA►S E, DATA SHEET IQ8 and IQ8+ Microinverters 1403 N.Research Way Orem,UT 84097 INPUT DATA IDCI 108-60-2-US 108PLUS-72-2-US 800.377.4480 Commonly used module pairings' W 235-350 235-440 WWW.BLUERAVENSOLAR.COM all 1 Ni el Module compatibility 60-cell/120 half-cell 60-cell/120 half-cell,66-cell/132 half-cell and 72-cell/144 CONFIDENTIAL-THE INFORMATION �'�'• half-cell HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE MPPT voltage range V 27-37 29-45 EXCEPT BLUE RAVEN SOLAR NOR Operating range V 25-48 25-58 SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE Min/max start voltage v 30/48 30/58 RECIPIENTS ORGANIZATION,EXCEPT WITH THE SALE AND Max input DC voltage v 50 60 USE OF THETION RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Max DC current'[module!so] A 15 OF BLUE RAVEN SOLAR LLC. .a.. }r Overvoltage class DC port II i`A r'a DC port backfeed current mA 0 It at li PV array configuration 1x1 Ungrounded array;No additional DC side protection required;AC side protection requires max 20A per branch circuit NAB C. E I--- ) ~` CERTIFIED 1 OUTPUT DATAIACI 06-60-2-U8 QBPLUS-72-2-US Peak output power VA 245 300 PV INSTALLATION Max continuous output power VA 240 290 PROFESSIONAL Nominal(L-L)voltage/range' v 240/211-264 Scott Gurney Max continuous output current A 1.0 1.21 #PV-011 71 9-01 5866 I08 and I08+ Microinverters Nominal frequency Hz 60 CONTRACTOR: Easy to install Extended frequency range Hz 50-68 BRS FIELD OPS Our newest I08 Microinverters are the industry's first microgrid-forming,software- • Lightweight and compact with AC short circuit fault current over 2 385-498-6700 defined microinverters with split-phase power conversion capability to convert DC plug-n-play connectors 3 cycles Arms power to AC power efficiently.The brain of the semiconductor-based microinverter Power Line Communication Max units per 20 A(L-L)branch circuit` 16 13 •is our proprietary application-specific integrated circuit(ASIC)which enables the (PLC)between components Total harmonic distortion <5% microinverter to operate in grid-tied or off-grid modes.This chip is built in advanced 55nm technology with high speed digital logic and has super-fast response times • Faster installation with simple Overvoltage class AC port III to changing loads and grid events,alleviating constraints on battery sizing for home two-wire cabling AC port backfeed current mA 30 energy systems. Power factor setting 1.0 High productivity and reliability Grid-tied power factor(adjustable) 0.85 leading-0.85 lagging _` • Produce power even when the Peak efficiency i 97.5 97.6 rASM, Enphase grid is down' fi' CEC weighted efficiency W 97 97 • More than one million cumulative i!..,; ' Night-time power consumption mW 60 -llgil hours of testing ywarear lrantyd MECHANICAL DATA A • Class II double-insulated Ambient temperature range -40°C to+60°C(-40°F to+140°F) Part of the Enphase Energy System.IQ8 Series IQ8 Series Microinverters redefine reliability enclosure Microinverters integrate with the Enphase IQ Battery, standards with more than one million cumulativeRelative humidity range 4%to 100%(condensing) high- Enphase IQ Gateway.and the Enphase AOptimized for the latest y p pp monitoring hours of power-on testing,enabling anindustry- DC Connector type MC4 and analysis software. leading limited warranty of up to 25 years. powered PV moues Dimensions(HxWxD) 212 mm(8.3")x 175 mm(6.9")x 30.2 mm(1.2") Microgrid-forming Weight 1.08 kg(2.38 Ibs) Complies with the latest Cooling Natural convection-no fans advanced grid support" Ap proved for wet locations Yes CERTIFIED • Remote automatic updates for Pollution degree PD3 DRAWING BY: the latest grid requirements Enclosure Class II double-insulated,corrosion resistant polymeric enclosure Connect PV modules quickly and easily to IQ8 Series IQ8 Series Microinverters are UL Listed as •Microinverters using the included Q-DCC-2 adapter PV Rapid Shut Down Equipment and conform with Configurable to support a wide Environ.category/UV exposure rating NEMA Type 6/outdoor cable with plug-n-play MC4 connectors. various regulations,when installed according to range of grid profiles COMPLIANCE PLOT DATE: manufacturer's instructions. • Meets CA Rule 21(UL 1741-SA) CA Rule 21(UL 1741-SA).UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B.ICES-0003 Class B,CAN/CSA-C22.2 NO.107.1-01 requirements Certifications This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014,NEC 2017.and NEC 2020 section 690.12 and C22.1-2018 Rule 64-218 Rapid Shutdown of PV Systems,for AC and DC conductors,when installed according to PROJECT NUMBER: ©2022 Enphase Energy.All rights reserved.Enphase.the Enphase logo,108 Microinverters,and other *Only when installed with IQ System Controller 2, manufacturer's instructions. names are trademarks of Enphase Energy,Inc.Data subject to change. meets UL 1741. (t)No enforced DC/AC ratio.See the compatibility calculator at https://link.enphase.com/module-compatibility **IQ8 and IQBPIus supports split phase,240V (2)Maximum continuous input DC current is 10.6A(3)Nominal voltage range can be extended beyond nominal if required IQ8SP-DS-0002-01-EN-US-2022-03-17 installations only. by the utility.(4)Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. IQ8SP-DS-0002-01-EN-US-2022-03-17 SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ____ SS BLUE IQ Combiner 4/4C RAVEN MODEL NUMBER 1403 N.Research Way Orem,UT 84097 800.377.4480 WWW.BLUERAVENSOLAR.COM DENTIAL-THE INFORMATION it! t:rtiti C.'.t' ,: E.; f: ` -`;' ( ; HEREIN ICONTAINEDSHALLNOTBE Q Combiner 4 4 USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR ACCESSORIES AND REPLACEMENT PARTS' __..` r SHALL IN PART TTOOTOHERSIN OUTSIDE OR a:,.:.„ ,v a'; ,'. }. RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITH OUT T THE WRITTEN PERMISSION OF LUE RAVEN SOLAR LLC. o" r3re. t t NAB CEP CSMr' t.tIttt /„.t':k') CERTIFIED E ., PV INSTALLATION PROFESSIONAL p - ". , _ _,,,. ,• ,,; Scott Gurney rd},,r s.., .. #PV-011719-015866 ELECTRICAL SPECIPtCATt NS CONTRACTOR: c' :. ir;,: BRS FIELD OPS I 3 ..s .: I � J as 385-498-6700 . °:t::E' Lts `. Ir7: .r .}itr}•e .! `".;. `alirS+.t .. •r -i,r:- .. 32 212 e„§``- t +r,y, •.�U. ..",. t ap , t,4,x (tt :t,::.f:.,, .2. ,� , I 1 f ' r MECHAN€CAL.DATA. .. X'),}AM.1. Xk 4)-.4M'-24:11 .tr t t 2 t ! !+r I t. ot.tO }. 2,11's'' n° 4r,.1"1.'11/11 1 _ .•ideti-"=E _.._ 'a(%`": ._t'{;St ..r..-i_'#3• _:, -.: .. : •# ..:1� fi:< r,:''t .r:" _.`� to �..,2. I sar INTERNE/ CONNECTION OPT6INS 'i ICAMI 24'�,4.K1i - , COMPLIANCE (1) t-t-o-f,tt ., t•r e ia +<1, „2 LISTED ,`;g'z§.'1 Imoredtizt"3L1S tl.tisms ,.i 3 Pr y E PHAS . xr E SHEET NAME: 1;, 1 ; SPEC SHEETS REVISION: PAGE NUMBER: 0 SS • BLUE R AVE N 1403 N.Research Way Orem,UT 84097 WIRING DIAGRAMS 800.377.4480 1NWW.BLUERAVENSOLAR.COM 6.75 FUSIBLE NOT FUSIBLE CONFIDENTIAL-THE INFORMATION [172] HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR - _ 2$ !_ SHALL IT BE DISCLOSED IN WHOLE OR MIM [7] - Q Q IN PART TO OTHERS OUTSIDE ' I/ I/ RECIPIENTS ORGANIZATION,EXCEPT IN (3 HOLES) A C ` 7 CONNECTION WITH THE SALE AND II -- II b( b( USEWITHOUT OF THE RESPECTIVE EQUIPMENT, i,` THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. II . i OHS/NI--O 6.00 [�9] B - 4 NABCEP [152 ] 4ii ? ?? CERTIFIED l g/ A,B,C D ye • KNOCKOUTS PV INSTALLATION s ^ PROFESSIONAL . I O--I S/N 1--0 Scott Gurney o #PV-011719-015866 A TERMINAL LUGS* CONTRACTOR:4.50 KNOCKOUTS 4.60 [114] [117] BRS FIELD OPS AMPERES MAX. WIRE MIN. WIRE TYPE # 6 AWG # 12 AWG AL 385 498 6700 30 # 6 AWG # 14 AWG CU 7.50 [191] ') KNOCKOUTS SYMBOL A B C D 0 A,B,C IIII CONDUIT SIZE .50 .75 1 1.25 KNOCKOUTS ,_1 V'V ,--. IT O !( )1 0 LI NEMA TYPE 3R ILLUSTRATED DUAL DIMENSIONS: INCHES A,B,C,D MILLIMETERS KNOCKOUTS HORSEPOWER RATINGS CATALOG VOTAGE WIRING 120VAC 240VAC NUMBER RATINGS DIAG. STD. MAX. STD. MAX. 10 10 10 30 10 30 D211NRB•■ 240VAC A 1/2 2 1 1/2 — 3 — NOTES: D221NRB 240VAC A — — 1 1/2 3* 3 7 1/2* FINISH — GRAY BAKED ENAMEL ELECTRODEPOSI11ED OVER CLEANED PHOSPHATIZED STEEL. D321NRB 240VAC B — — 1 UL LISTED — FILE E-2875 1/2 3 3 7 1/2 ALL NEUTRALS — INSULATED GROUNDABLE DU221RB 240VAC C — — — — 3 — DRAWING BY: SUITABLE FOR USE AS SERVICE EQUIPMENT DU321RB 240VAC D — — — — 3 7 1/2 TOP OF NEMA TYPE 3R SWITCHES HAVE PROVISIONS FOR MAXIMUM 2 1/2" BOLT—ON HUB. SHORT CIRCUIT CURRENT RATINGS: • 10,000 AMPERES. PLOT DATE: 10,000 AMPERES WHEN USED WITH OR PROTECTED BY CLASS H OR K FUSES. GENERAL DUTY SAFETY SWITCHES El SQUARE D 100,000 AMPERES WITH CLASS R FUSES. VISIBLE BLADE TYPE * FOR CORNER GROUNDED DELTA SYSTEMS. • PLUG FUSES 30 AMPERE * LUGS SUITABLE FOR 60'C OR 75' CONDUCTORS. ENCLOSURE — NEMA TYPE 3R RAINPROOF by Schneider Electric PROJECT NUMBER: DWG# 1 852 O. FEBRUARY 2014 REF DWG #1852 SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ____ S S RSTC Enterprises, Inc. (7: 2214 Heimstead Road VEN Eau Claire, WI 54703 L A K 1403 N Research Way Orem,UT 84097 715-830-9997 FLASHED PV ROOF-MOUNT MBINE*�pi �y 800.377.4480 R/I EN LO URE WWW.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE Outdoor Photovoltaic Enclosures 0799 Series EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT Composition/Cedar Roof System , IN CONNECTION WITH THE SALE AND t' USE OF THE RESPECTIVE EQUIPMENT, ETL listed and labeled 4 a• WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. Report # 3171411 PRT-002 Revised May, 2018 NABCEP • UL50 Type 3R, 11 Edition Electrical equipment enclosures CERTIFIED • CSA C22.2 No. 290 Nema Type 3R • Conforms to UL 1741 Standard PV INSTALLATION PROFESSIONAL Scott Gurney #PV-01 1 71 9-01 5866 0799 Series Includes: CONTRACTOR: 0799 - 2 Wire size 2/0-14 SolaDeck0799-25 ., BRS FIELD OPS 385-498-6700 0799 - 5 Wire size 14-6 0799 - D Wire size 14-8 � Models available in Grey, Black or Stainless Steel Basic Specifications Material options: • Powder coated, 18 gauge galvanized 90 steel (1,100 hours salt spray) • Stainless steel SolaDeck 0799-5G Process - Seamless draw (stamped) Flashing - 15.25" x 17.25" Height - 3" Cavity - 255 Cubic inches Base Plate: DRAWING BY • Fastened to base using toggle fastening system _ � r Y • 5 roof deck knockouts - PLOT DATE: • Knockout sizes: (3) .5", (1) .75" and (1) 1" • 8", 35mm slotted din rail • Ground Block PROJECT NUMBER: Passthrough and combiner kits are available for either SolaDeck0799-DG ' g SHEET NAME AC or DC applications. SPEC SHEET REVISION: PAGE NUMBER: -- SS .„,,:,..,,:.... .....,,,.,.. 1 BLUE RAVEN S F M F - .:: u N I a .. . .. RAC 1403 N.Research Wa Y Orem,UT 84097 BETTER SOLAR STARTS HERE 8 00.377.4480 W W W.BLUERAVENERAVENSOLAR.COM 1 4 CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR 3 2 «� SHALL IT BE DISCLOSED IN WHOLE OR U f IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, /t& II* � /iTh SYSTEM OVERVIEW 20% FEWER ATTACHMENTS WIT OF BLUE RAVEN SOLAR MICSION PART NAME DESCN N Save time and money on every project:SFM INFINITY requires fewer 1 attachments than rail systems. NABCEP 2 INSTALLS PER DAY II TRIMRAIL Structural front[rim provides aesthetic and aligns modules. CERTIFIED Make two installs per day your new standard.SFM INFINITY has fewer © PV INSTALLATION roof attachments.one tool installation,and pre assembled components TRIMRAIL SPLICE Connects and electrically bonds sections of TRIMRAIL. . .; .�,�.:. , , --. 4 m.3<_. .. PROFESSIONAL MI ' ' #PV-011t719-015866 to get you off the roof 40 to faster, �� TRIMRAIL FLASHKIT Attaches TRIMRAIL to roof.Available for comp shingle or tile, `'"I ..__� l" _ ' ' II CONTRACTOR: HOMEO 0 SFM INFINITY 15 Attachments BRS FIELD OPS ' e _ MODULE CLIPS 1111r385-498-6700 Secure modules to TRIMRAIL. IMICRORAIL Connects rlod,des to SLIDERS Provides post-install array leveling. .. BETTER AESTHETICS �a . Install the system with the aesthetics preferred by homeowners. 111 ' SPLICE Connects and supports modules.Provides oast-westbonding. m- ii . with integrated front trim,trim end caps.dark components,and ATTACHED SPLICE also available recessed hardware, III 11111111.- SLIDER FLASHKIT Roof attachment and flashing.Available for comp shingle and tile. RAIL 20 Attachments MAXIMUM POWER DENSITY 30% LOGISTICS SAVINGS Easily mix module orientations to achieve optimal power density without incurring the increased bill of materials,labor,and BONDING AND ACCESSORIES With feeler SKUs and compact components,SFM INFINITY is easier to attachments required by rail. stock,easier to transport,and easier to lift to the roof.Plus,make more PART NAME - - pESCRIPT efficient use of your vehicle fleet. IVTRIMRAIL ENDCAPS Covers ends at TRIMRAIL for refined aesthetic. l le TRIMRAIL BONDING CLAMP Eleetrically bonds TRIMRAIL and modules 034 Pig; 0 IV N/S BONDING CLAMP Electrically bonds rom of modules DRAWING BY: PLOT DATE: SFI NF1 IITY REY LUTI NIZES RHCFT0P SOLAR -W-ITH BE-NEFITS ACROSS YOUR -G SINESS PROJECT NUMBER: -- FROM [DESIGN- AND LOGISTICS, THROUGH ARRAY INSTALLATION AND -SERVICE. SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: SS OM : UN --„,,..„.„,„ ,..,,,. „..,, BLUE RAVEN .. .1 : sFivi FSRAME SYSTEM BONDING a GROUNDING i --,::::: - -,' N. . MICRDRAIL I GUIDE ; PAGE 14030rem,UT 84097Jay 800.377.4480 VVWW.BLUERAVENSOLAR.COM CONF.._._... DENTIAL-THE MATION j............._____,- _._ ., . .,.,__.. _,_._.,,_ .____ S T_.,.-- -_- _._F L-._ . i_ ---_ __,__.__-.._ ___ F — _._ 1 _ HEREIN CONTAINED SHALL NOT BE Trrriir_T j E I q w �j _ USED FOR THE BENEFIT OF ANYONE ma ���� ; EXCEPT BLUE RAVEN SOLAR NOR �� f '_ S . SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND F USE OF THE RESPECTIVE EQUIPMENT, !_ WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. E 0.4'' ' T f -7-I _1, CERTIFIED =_ _ PV INSTALLATION PROFESSIONAL i Li T [ Scott Gurney .,...—,......==„0.,.,„..... ..____________,____ -_______ __ -- ._ #PV-01 1 71 9-01 5866 I� - ' E-W BONDING PATH. CONTRACTOR: __I_ E-W module to module bonding is accomplished BRS FIELD OPS __E_ with 2 pre-installed bonding pins which engage 385-498-6700 '-11 - on the secure side of the MicrorailTM and splice. 1 de T "__ i _ - I i , i F__T. _ a 1 3 I ---�- i Star Washer is 4 - .: WEEBLUG Single Use Only ' Single Use Only Alternate method N-S BONDING PATH: TERMINAL TORQUE, N-S module to module bonding is Install Conductor and accomplished with bonding clamp with 2 integral torque to the following: TERMINAL TORQUE, TERMINAL TORQUE, bonding pins. (refer also to alternate method) 4-6 AWG: 35in-Ibs Install Conductor and Install Conductor and 8 AWG: 25 in-lbs torque to the following: torque to the following: 10-14 AWG: 20 in-lbs 4-14 AWG: 35in-Ibs 6-14 AWG: 7ft-Ibs leDRAWING BY: LUG DET` " _Fi TORQUE INFO LUG i _°_ IOW:WE, E IN LUG U L IL & fOR UE m Ilsco Lay-In Lug (GBL-4DBT) Ilsco Flange Lug (SGB-4) Wiley WEEBLug (6.7) `:i 0.,0 PLOT DATE • 10-32 mounting hardware • 1/4" mounting hardware • 1/4" mounting hardware 'J • Torque = 5 ft-lb • Torque = 75 in-lb • Torque = 10 ft-lb — Alternate method PROJECT NUMBER: • AWG 4-14-Solid or Stranded • AWG 4-14-Solid or Stranded • AWG 6-14-Solid or Stranded i TRIMRAIL BONDING PATH: NOTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION Trimrail to module bonding is accomplished with SHEET NAME System bonding is accomplished through modules.System grounding accomplished by attaching bonding clamp with integral bonding pin and SPEC SHEET a ground lug to any module at a Location on the module specified by the module manufacturer. bonding T-bolt. (refer also to alternate method) REVISION: PAGE NUMBER: ---- S S 1 1 1 CODE COMPLIANCE NOTES 1 BLUE RAVEN IIII 1r 1 PAGE t4 O em,UT 8409vay 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION SYSTEM LEVEL FIRE CLASSIFICATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR The system fire class rating requires installation in the manner specified in the performance is inherent in the SFM design,and no additional mitigation measures SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE SUNFRAME MICRORAIL (SFM) Installation Guide.SFM has been classified to are required.The fire classification rating is valid for any roof pitch.There is no RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND the system level fire portion of UL 1703. This UL 1703 classification has been required minimum or maximum height limitation above the roof deck to maintain USEOFTHERESPECTINEEQUIPMENT, WITHOUT THE WRITTEN PERMISSION incorporated into the UL 2703 product certification. SFM has achieved Class A, the Class A, B & C fire rating for SFM.SUNFRAME MICRORAILTMcomponents shall OF BLUE RAVEN SOLARLLC. B & C system Level performance for low slope & steep sloped roofs when used be mounted over a fire resistant roof covering rated for the application. in conjunction with type 1 and type 2 modules.Class A, B & C system level fire NABCEP CERTIFIED Module Type i Roof Slope System Level Fire Rating Microrail Direction Module Orientation Mitigation Required PV INSTALLATION AL Type 1 and Type 2 I Steep Slope & Low Slope I Class A, B & C East-West ' Landscape OR Portrait 5 None Required Scott Gurney #PV-011719-015866 CONTRACTOR: BRS FIELD OPS UL2703 TEST MODULES 385 498 6700 See pages 22 and 23 for a list of modules that were electrically and mechanically tested or qualified with the SUNFRAME MICRORAIL (SFM) components outlined within this Installation Guide. • Maximum Area of Module = 27.76 sqft • UL2703 Design Load Ratings: a) Downward Pressure - 113 PSF/ 5400 Pa b) Upward Pressure - 50 PSF / 2400 Pa c) Down-Slope Load - 21.6 PSF/ 1034 Pa • Tested Loads: a) Downward Pressure - 170 PSF/ 8000 Pa b) Upward Pressure - 75 PSF / 3500 Pa c) Down-Slope Load - 32.4 PSF / 1550 Pa • Maximum Span = 6ft DRAWING BY: • Use with a maximum over current protection device OCPD of 30A • System conforms to UL Std 2703, certified to LTR AE-001-2012 PLOT DATE: • Rated for a design load of 2400 Pa / 5400 Pa with 24 inch span • PV modules may have a reduced load rating, independent of the SFM load rating. Please consult the PV module manufacturer's installation guide for more information PROJECT NUMBER: • Down-Slope design load rating of 30 PSF/ 1400 Pa for module areas of 22.3 sq ft or less SHEET NAME SPEC SHEET REVISION: PAGE NUMBER: V V : LLIE RAVEN i i sri : sFm ,,, , , . . . . , _ . ,,.. ,:, .,..,., . : ,.., ■ • , . xkT. IL - 1 . 1 PAGE 14 Orem,UT 84097yay 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION 1 HEREIN CONTAINED SHALL NOT BE Manufacture Module Model/Series Manufacture Module Model/Series EXCEPT BLUEUSEDBENEFIT RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR ._._.._ ...._,.. IN PART TO OTHERS OUTSIDE Aleo P-Series Eco Solargy Orion 1000&Apollo 1000 LGxxxN2T-A4 RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND ET Solar ET-M672BHxxxTW LGxxx(A1C/E1C/E1K/N1C/N1K/N2T/N2W/ USE OF THE RESPECTIVE EQUIPMENT, DNA-120 ( )BF/MF 26 WITHOUT THE WRITTEN PERMISSION Aptos Freedom Forever FF MP BBB 370 Q1C/01K/S1C/S2W) A5 OF BLUE RAVEN SOLAR LLc. DNA-144-(BF/MF)26 xxx FreeVolt Mono PERC LG N2T B5 LGxxxN1 K-B6 NABCEP CHSM6612P,CHSM6612P/HV,CHSM6612M, GCL GCL-P6 &GCL M6 Series LGxxx(A1C/M1C/M1K/N1C/N1K/Q1C/Q1K/ , CERTIFIED Astronergy CHSM6612M/HV,CHSM6610M (BL)(BF)/(HF), Hansol TD-AN3,TD AN4, LG Electronics OAC/QAK) A6 PV INSTALLATION CHSM72M-HC UB-AN1,UD-AN1 ; LGxxx(N1C/N1K/N2T/N2W)-E6 PROFESSIONAL AXN6M610T,AXN6P610T, 36M,60M,60P,72M & 72P Series, LGxxx N1C/N1K/N2W/S1C/S2 Scott Gurney Auxin ( �/-G4 #PV-011 71 9-01 6866 AXN6M612T&AXN6P612T Heliene 144HC M6 Monofacial/Bifacial Series, LGxxxN 2T-J5 CONTRACTOR: ,35mm 60 rem AXlblack ium 144HC M10 SL Bifacial p ( ) LGxxx(N1K/N1W/N2T/N2W)-L5 BRS FIELD OPS AXI power 60(35mm), HT60-156(M)(NDV)(-F), LGxxx(N1C/Q1C/Q1K)-N5 385-498-6700 HT Solar Axitec AXlpower 72 (40mm), HT 72-156(M/P) LGxxx(N1C/N1K/N2W/Q1C/Q1K)-V5 remium 60 35mm, � AXI P ( ) KG MG,TG,RI,RG,TI,MI,HI & KI Series 1 LR4-60(HIB/HIH/HPB/HPH)-xxxM Hyundai AXlpremium 72 (40mm). HIA-SxxxHG LR4-72(HIH/HPH)-xxxM BVM6610, ITEK IT,iT-HE & IT-SE Series . LR6-60(BP/HBD/HIBD)-xxxM (30mm) Boviet BVM6612 _._._.__ ,...,._. _.,.-,,._____.____. _�-.. LR6-60(BK)(PE)(HPB)(HPH)-xxxM (35mm) Japan Solar JPS-60&JPS-72 Series BYD P6K& MHK-36 Series LONGi LR6-60(BK)(PE)(PB)(PH)-xxxM (40mm) JAP6 60-xxx,JAM6-60-xxx/SI,JAM6 K-60/ O LR6 72(BP)(HBD)(HIBD) xxxM (30mm) CS1(H/K/U/Y)-MS xxx,JAP6 k-72-xxx/4BB,JAP72SYY-xxx/ZZ, ( V)( )( )( )( )( ) CS3(K/L/U),CS3K-MB-AG,CS3K-(MS/P) O LR6 72 H BK PE PH PB HPH xxxM JAP6(k)-60-xxx/4BB,JAP6OSYY-xxx/ZZ, (35mm) Canadian Solar CS3N-MS,CS3U-MB-AG,CS3U-(MS/P),CS3W JA Solar JAM6(k)-72-xxx/ZZ,JAM72SYY-xxx/ZZ, ; LR6-72(BK)(HV)(PE)(PB)(PH)-xxxM (40mm) CSSA-M,CS6(K/U),CS6K-(M/P),CS6K-MS CS6P-(M/P),CS6U-(M/P),CS6V-M,CS6X-P JAM6(k) 60 xxx/ZZ,JAM605YY xxx/ZZ Mission Solar Energy MSE Series i.YY:01,02,03,09,10 Centrosolar America C-Series& E-Series ii.ZZ:SC,PR,BP,HiT,IB,MW,MR Mitsubishi MJE & MLE Series CT2xxMxx-01,CT2xxPxx-01, CertainTeed CTxxxMxx-02,CTxxxM-03, JKM &JKMS Series Neo Solar Power Co. D6M & D6P Series CTxxxMxx-04,CTxxxHC11-04 Jinko Eagle JKMxxXM DRAWING BY: Dehui DH-60M JKMxxxM 72HL V Kyocera KU Series PLOT DATE: PROJECT NUMBER • Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx" • Items in parenthesis are those that may or may not be present in a compatible module's model ID • Slashes "I"between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME: • Please see the SFM UL2703 Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET • SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section, page 12 for further information REVISION: PAGE NUMBER NU : V V I1 ,5,,..„,,t„..,.;.„..,,,,:2,,,,,,,..... 1 1 :7.7, . .. ,;.,,,, • au : li yS. 'I t 1 0 , 1 I 1 1 PAGE 1403 N Research Orem,UT 84097yay 800.377.4480 W W W.BLUERAVENSOLAR.COM ,. _. ..---_--.._ , _... -__-..- _--_.-- --.-._- CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE Manufacture Module Model/Series Manufacture 1 Module Model/Series Manufacture , Module Model/Series U EXCEPT EPTBLLUEUE R REAVVENT OF ANYONE EN SOLAR NOR 1 ' SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE EVPVxxx(H/K/PK), TwinPeak Series A-Series A400-BLK,SPR-MAX3-XXX-R, RECIPIENTS ORGANIZATION,EXCEPT SunPower IN CONNECTION WITH THE SALE AND VBHNxxxSA15 & SA16, TwinPeak 2 Series X-Series,E-Series & P-Series USE OF THE RESPECTIVE EQUIPMENT, ....._.-.-- _._.._._ ..--- WITHOUT THE WRITTEN PERMISSION VBHNxxxSA17&SA18, ' TwinPeak 2 BLK2 Series Suntech STP,STPXXXS B60/Wnhb OF BLUE RAVEN SOLAR LLC. REC(cont.) Panasonic VBHNxxxSA17(E/G) & SA18E, TwinPeak 2S(M)72(XV) TP572,TP596,TP654,TP660, VBHNxxxKA01 & KA03 & KA04, TwinPeak 3 Series(38mm) Talesun NABCEP TP672,Hipor M,Smart VBHNxxxZA01,VBHNxxxZA02, TP4(Black ) ___ --_-- -- - sc,scB,sc6l,scBz CERTIFIED VBHNxxxZA03 VBHNxxxZA04 Renesola Vitrus2 Series & 156 Series Tesla PV INSTALLATION _____.__ ,......._ ._ _._._ ., . _.._.. . __ ...___„ .. TxxxH,TxxxS Peimar SGxxxM (FB/BF) Risen RSM72-6(MDG)(M),RSM60 6 PROFESSIONAL P 1. Scott Gurney _ A05 PD05 DD05 DE06,DD06 PE06 Phono Solar PS-60,PS-72 SEG Solar SEG-xxx-BMD-HV Trina PD14,PE14,DD14,DE09.05,DE14,DE15, #PV-011719-015866 Prism Solar P72 Series ' S-Energy SN72 & SN60 Series(40mm) i PE15H CONTRACTOR: _.. . BRS FIELD OPS Plus,Pro,Peak,G3,G4,G5,G6(+),G7,G8(+) Seraphim SEG-6 &SRP-6 Series UP-MxxxP(-B), 385-498-6700 Upsolar Pro,Peak L-G2,L-G4,L-G5,L-G6,L-G7 Sharp NU-SA& NU-SC Series UP-MxxxM(-B) O.PEAK DUO BLK-G6+ SLA, SLG,BC Series & SlLxxx(BL/NL/NT/HL/ D7MxxxH7A,D7(M/K)xxxH8A Q.PEAK DUO BLK-G6+/TS Silfab ,FAMxxxE7G-BB URE FAKxxx(C8G/E8G),ML/BK/NX/NU/HC) ( ) O.PEAK DUO(BLK + 0.Cells ( ) G8 FAMxxxE8G(-BB) Solarever USA SE-166*83-xxxM-120N , Q.PEAK DUOL-G8.3/BFF Eldora, i PowerXT-xxxR-(AC/PD/BD) Q.PEAK DUO(BLK) ML-G9(+) Vikram Solivo, Solaria PowerXT-xxxC-PD Q.PEAK DUO XL-G9/G9.2/G9.3 PowerXT xxxR PM (AC) ' Somera O.PEAK DUO(BLK) ML-G10(+) _.--.--..--._-._-- -.-- Sunmodule Protect, Waaree 1 AC&Adiya Series 0 PEAK DUO XL-G(10/10.2/10.3/10.c/10.d) SolarWorld Sunmodule Plus Winaico WST&WSP Series _._-. -.- _.. ' Alpha (72)(Black)(Pure) N-Peak(Black) SS-M-360 to 390 Series, Yingli YGE &YLM Series SS-M-390 to 400 Series, ZN Shine ZXM6-72 ZXM6-NH144-166_2094 N-Peak 2 (Black) REC Sonali SS-M-440 to 460 Series, PEAK Energy Series SS-M-430 to 460 BiFacial Series, PEAK Energy BLK2 Series SS 230-265 PEAK Energy 72 Series SunEdison F-Series,R-Series & FLEX FXS Series DRAWING BY Suniva MV Series & Optimus Series PLOT DATE: PROJECT NUMBER: • Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx" • Items in parenthesis are those that may or may not be present in a compatible module's model ID • Slashes "/" between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME • Please see the SFM UL2703 Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET • SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section, page 12 for further information REVISION: PAGE NUMBER: ---- S S Intertek AUTHORIZATION TO MARK intertcAk AUTHORIZATION TO MARK BLUE RAVEN Total ate red. Total Oriente Assured 1403 N.Research Way Orem,UT 84097 This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) 800.377.4480 Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing WWW.BLUER4VENsoLAR.coM Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION HEREIN SHALL NOT BE Report. Report. USED FORO THE ABENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be SHALL IT BE DISCLOSED IN WHOLE OR applied only Apply lied at the location of the PartyAuthorized To A I Mark. applied onlyat the location of the PartyAuthorized To Apply Mark. PART TO G OUTSIDE pp pp y RECIPIENTS ORGAA NIZANIZA TION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Applicant: Unirac, Inc Manufacturer: Redacted information Applicant: Unirac, Inc Manufacturer: Redacted information OF BLUE RAVEN SOLAR LLC. Address: 1411 Broadway Blvd NE Address: 1411 Broadway Blvd NE NABCEP Albuquerque, NM 87102 Albuquerque, NM 87102 Country: USA Country: USA CERTIFIED PV INSTALLATION Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL Report Issuing Office: Intertek Testing Services NA, Inc. Lake Forest, CA Report Issuing Office: Intertek Testing Services NA, Inc. Lake Forest, CA Scott Gurney Control Number: 5003705 Authorized by: + Control Number: 5014989 Authorized by: eiwelhimailarthttf #PV-011719-015866 for L. Matthew Snyder, Certification Manager for L. Matthew Snyder, Certification Manager CONTRACTOR: BRS FIELD OPS 385-498-6700 C US C W Intertek Intertek This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.lntertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights, IL 60005 545 East Algonquin Road,Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices,and Ground Lugs for Use with Flat- Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] Standard(s): PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 DRAWING BY: Brand Name: Unirac Brand Name: Unirac Models: Unirac SFM Models: Unirac SFM PLOT DATE: PROJECT NUMBER: SHEET NAME: ATM for Report 102393982LAX-002 Page 1 of 4 ATM Issued:27-Oct-2022 ATM for Report 102393982LAX-002 Page 2 of 4 ATM Issued:27-Oct-2022 SPEC SHEET ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory REVISION: PAGE NUMBER: SS '- Intertek AUTHORIZATION TO MARK int rte AUTHORIZATION TO MARK BLUE Total Quality.Assured. Total Quanty.Assurett. 1403 N.Research Way Orem,UT 84097 This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) 800.377.4480 Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing WWW.BLUERAVENsoLAR.coM Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION HEREIN SHALL NOT BE Report. Report. USED FORONTAINED THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be SHALL IT BE DISCLOSED IN WHOLE OR applied only Apply pponlylocation of the Party Apply RECIPIENTS ORGA lied at the location of the PartyAuthorized To A I Mark. applied at the Authorized To Mark. IN PART TO GANERS OUTSIDE NIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Applicant: Unirac, Inc Manufacturer: Redacted information Applicant: Unirac, Inc Manufacturer: Redacted information OF BLUE RAVEN SOLAR LLC. Address: 1411 Broadway Blvd NE Address: 1411 Broadway Blvd NE NABCEP Albuquerque, NM 87102 Albuquerque, NM 87102 Country: USA Country: USA CERTIFIED PV INSTALLATION Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL Report Issuing Office: Intertek Testing Services NA, Inc., La - Forest, CA Report Issuing Office: Intertek Testing Services NA, Inc., Lake��� Forest, CA Scott Gurney . Control Number: 5019851 Authorized by: r Control Number: 5021866 Authorized by: for L. Matthew Snyder, Certification Manager for L. Matthew Snyder, Certification Manager #PV-01 1 71 9-01 5 866 Manager CONTRACTOR: BRS FIELD OPS 385-498-6700 Ill COLS C' US Intertek Intertek This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights, IL 60005 545 East Algonquin Road,Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Standard s ; Flat- Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] ( ) Standard(s): PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 DRAWING BY: Brand Name: Unirac Brand Name: Unirac Models: Unirac SFM Models: Unirac SFM PLOT DATE: PROJECT NUMBER: SHEET NAME ATM for Report 102393982LAX-002 Page 3 of 4 ATM Issued:27-Oct-2022 ATM for Report 102393982LAX-002 Page 4 of 4 ATM Issued:27-Oct-2022 SPEC SHEET ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory REVISION: PAGE NUMBER: __ _ SS intertek inter t � Listing Constructional Data Report (CDR) Listing Constructional Data Report (CDR) BLUE RAVEN Total Quality.Assured. Total Quality.Assured. 1403 N.Research Way Orem,UT 84 7 �„ 09 e1 P.rl atReferen . ... �1 . .. .... �ate,cress 800.377.4480 ,iiRe6ortNuinber;102393982LAX-002 Original 11-Apr-2016 I Revised: 5-Oct-2022 (T I}t 102393982LAX-002 I Original 11-Apr-2016 I Revised: 5-Oct-2022 WWW.BLUERAVENSOLAR.COM lrltl CONFIDENTIAL-THE INFORMATION Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use HEREIN CONTAINED SHALL NOT BE with Flat-Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] USED FOR THE BENEFIT OF ANYONE Stattdrdts} EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR PV Module and Panel Racking Mounting System and Accessories [CSA TI L No.A-40:2020] IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, Applicant Unirac, Inc Manufactttrer2 WITHOUT THE WRITTEN PERMISSION ' :;? OF BLUE RAVEN SOLAR LLC. 1411 Broadway Blvd NE Address Albuquerque, NM 87102 address NABCEP Country USA Country Klaus Nicolaedis CERTIFIED Gong Todd Ganshaw Contact PV INSTALLATION 505-462-2190 PROFESSIONAL ° 505-843-1418 one Scott Gurney #PV-011719-015 866 Q:,'i ..... PAX ......; NA EA➢C: ,.._ klaus.nicolaedis@unirac.com CONTRACTOR: Ett ma! BRS FIELD OPS toddg@unirac.com 385-498-6700 Manufacturer3 Manufacturer4 Address.....;: Address Chun Countrjr Contact Contact Phone Phone . ... mail Etrla E il Manufacturer 5:; Address DRAWING BY: Country .. Contact PLOT DATE: Phone . FAX ''. PROJECT NUMBER: Page 1_of 138 Page 2 of 138 This report=s for the exclusive use of totertetr's Client and rs provided purl+ tt to the agreement between !Mertes(and its Client Intertek s reaPereibsity and This rSHEET NAME: t%arpih any limited to the terms and Gor'r'Uons c4 the toepon sS lot the exoluSrve usec tnierteit`S Client and provtdec9 fxrrsts.�sit to the agrmprrtn Iniertert oral,tS CIr#nt Int#rCC1c' rerrrgr+y 6 tya9reerr,eeit tnlertek assures no habttrly' any party. outer than to the Crent in accOrdana<e with the l r ty are limited to the terms and conn$4,ons of the agreement Intertek assumes no habrldty to any party. 4�threr than to the Chant in acoedancer with to a reerrreni,for any loss.eq�errse Or damage occasioned by the use of the report Only the Chant a authorized to pormt cc or distribciion of tt report and agreement for any loss,expense or damage occasioned by the use of the report Only the Client rs authorized to permit co prig or distribution of the report and SPEC SHEET then only rra its entrety Any use of the tntertek name or one of its markS for the sale or advert lament Of th tested material. product or sere,ce rt7;agt test be then only it its entree,/ Any use of the tetertek name Or one Of its marks for the sale o+advertisement of the tested material. product or Service moat first be ap ror d in enbrg by tnterttek.The observations and test results-n this report are relevant only to the sample tested This report by reset1 does not imply that the approved in writing by tntertek-The observations and test results:n this report are relevant only to the sample tested This report by itself does rot imply that the matesrat product,or service:s or has ever been under an Intertek eertincatxtart program motorist product,or service s or has ever been under an tnt eertt'icaeori program REVISION: PAGE NUMBER: ---- SS Report No. 102393982LAX-002 Page 3 of 138 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 4 of 138 Issued: 11-Apr-2016 Unirac, Inc Revised: 5-Oct-2022 Unirac, Inc Revised: 5-Oct-2022 E RAVEN roduc scn do Puct ° Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Models , Unirac SFM Brand larva .. :Unirac M iet�� NA 1403 N. ,UT840 Way Orem 897 800.377.4480 w 'r'llii : The product covered by this report is the Sun Frame Micro Rail roof mounted Photovoltaic ww.BLUERAVENSOLAR.COM Rack Mounting System. This system is designed to provide bonding and grounding to Fuse Rating: 30A CONFIDENTIAL-THE INFORMATION photovoltaic modules. The mountingsystem employs anodized or mill finish aluminum brackets HEREIN CONTAINED SHALL NOT BE y USED FOR THE BENEFIT OF ANYONE that are roof mounted using the slider, outlined in section 4 of this report. There are no rails j 'Module Orientation: Portrait or Landscape EXCEPT BLUE RAVEN SOLAR NOR within this product,whereas the 3"Micro Rail, Floating Splice, and 9"Attached Splice Maximum Module Size: 17.98 ft2 SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE electrically bond the modules together forming the path to ground. UL2703 Design Load Rating: 33 PSF Downward, 33 PSF Upward, 10 PSF Down-Slope RECIPIENTS ORGANIZATION,EXCEPT Tested Loads-50 psf/2400Pa Downward, 50psf/2400Pa Uplift, 15psf/720Pa Down Slope IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, The Micro Rails are installed onto the module frame by using a stainless steel bolt anodized Trina TSM-255PD05.08 and Sunpower SPR-E20-327 used for Mechanical Loading WITHOUT THE WRITTEN PERMISSION with black oxide with a stainless type 300 bonding pin,torqued to 20 ft-lbs, retaining the OF BLUE RAVEN SOLAR LLC. modules to the bracket. The bonding pin of the Micro Rail when bolted and torqued, penetrate Increased size ML test: miligiEiiiir.iiiiMaximum Module Size: 22.3 ft2 il the anodized coating of the photovoltaic module frame (at bottom flange)to contact the metal, (N:-1A-13CEP creating a bonded connection from module to module. UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 30 PSF Down-Slope C�eptt°n LG355S2W-A5 CERTIFIED The grounding of the entire system is intended to be in accordance with the latest edition of the used for Mechanical Loading test. PV INSTALLATION National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar Mounting configuration: Four mountings on each long side of panel with the longest span of 24" PROFESSIONAL 'Photovoltaic Systems or the Canadian Electrical Code, CSA C22.1 Part 1 in accordance to the UL2703 Design Load Rating: 46.9 PSF Downward,40 PSF Upward, 10 PSF Down-Slope Scott Gurney revision in effect in the jurisdiction in which the project resides.Any local electrical codes must LG395N2W-A5, #PV-011719-015866 be adhered in addition to the national electrical codes. The Grounding Lug is secured to the LG360S2W-A5 and LG355S2W-A5 used for used for Mechanical Loading test. photovoltaic module,torqued in accordance with the installation manual provided in this Mounting configuration: Six mountings for two modules used with the maximum span of 74.5" CONTRACTOR: document. IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 50psf/2400Pa Uplift BRS FIELD OPS 385 498 6700 Other optional grounding includes the use of the Enphase UL2703 certified grounding system, atings R , Mechanical Load test to add FlashLoc Slider and Trim Assemblies to UL2703 and IEC 61646 which requires a minimum of 2 micro-inverters mounted to the same rail, and using the same Certifications, & Increase SFM System UL2703 Module Size: engage cable. Maximum Module Size: 27.76 ft2 UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 21.6 PSF Down-Slope Jinko Eagle 72HM G5 used for Mechanical Loading test. Mounting configuration: Four mountings on each long side of panel with the longest span of 24" Mamzimum module size: 21.86 ft2 IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 75psf/3600Pa Uplift SunPower model SPR-A430-COM-MLSD used for Mechanical Loading Fire Class Resistance Rating: -Class A for Steep Slope Applications when using Type 1 Modules. Can be installed at any interstitial gap. Installations must include Trim Rail. -Class A for Steep Slope Applications when using Type 2 Modules. Can be installed at any interstitial gap. Installations must include Trim Rail. -Class A Fire Rated for Low Slope applications with Type 1 or 2 listed photovoltaic modules. This system was evaluated with a 5"gap between the bottom of the module and the roof's I surface See section 7.0 illustractions# 1, 1 a and lb for a complete list of PV modules evaluated with DRAWING BY: these racking systems Other.Ratings .. NA PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory _--- ^ _ .Report No. 102393982LAX-002 Page 42 of 138 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 43 of 138 Issued: 11-Apr-2016 Unirac, Inc Revised: 5-Oct-2022 Unirac, Inc Revised: 5-Oct-2022 . .., „. . . . . . . „ BLUE RAVEN 7,01Nstr:01.00* -:!::-.:!:,:.::,,!5: ,.,; (,':::;!;!! ,,g,: :,';---.,,,,1:!,,,,,,„:,.:--,,„-,E,:,,,:::,„-.-:;,„:-:.T:,-,,-,.:-.-.,,,,-,,, ,,i,,„.-„...::::-,,:- . -. .,-,,,-,,,,,,,.....,:,,,-5,.:-:i::::,.::.,-,,,,,1-,-,i, ,,,J!!,...; :,,,: ,,,,,:,,,,,-,,, :.::,-:,,,:-.,:',,:.-:,,:,,.,,;,,-1 11"144"rati:40*-;', '...:0': ','''..:':',-,',',,:'::-.,"Y':-: ::,H.--2,-- '-;':',-Y:,,,:,---,,,,,--, ,,-,:,',-y-.,5',--:::„ ,.:: ,::::,-.;-,, '.,, ,,,--,,',,-:,,Ki,:.,F,,, ,,,H,,,::,-,,,,-,,: ,1 Illustration 1 -Approved PV Modules Illustration 1a -Approved PV Modules Continue 1403 N Research Way Orem,UT 84097 800.377.4480 Sanufat.tum Modute MatIM/Sees Manufacture. Module Made I Setift Masurfacture Moduta Menet"Tante% Manufacture Moduta Monat( rat VVWVV.BLUERAVENSOLAR.COM AMe , 4*.eitt.ti Ks,,.S01,41 44 cil,U.MU 4!...AO.,h L,:C.3}U I(A.XX Ni r A4 fai.A'"VAiA i:1-4,41mPiat, CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE r t °Ail At ,r MilliKt* :t.*TA LIA.A4Aitmti1aitEA/N1CZNIAi8424,442wi. VSMNAtim SA iti&5A16, USED FOR THE BENEFIT OF ANYONE AT IttrrA 1:11 OM,7-ii i;`,', 1,et,t4om f c,r,T.,,,,,-, Fr 4' BBB 3M AAtii„is-JAI AT, VHT,NA.A.A%Aki'.,AA 334 336', EXCEPT BLUE RAVEN SOLAR NOR, !NA 144 la akat 1,4" SHALL IT BE DISCLOSED IN WHOLE OR i)6)6660 Morg-7,Pt Ri: 1 hlota61,11271 W; P.44,4 444,.kr Vfilahatx,M4111,A,TM,A ,AI'IT IN PART TO OTHERS OUTSIDE 1.-10,m,ttr,tt5"tr‘wrttit:trtirti.t torttletra m (Fa (FF.FAFF,rr„,FFCF_55.6 5.,),,,, Umm;t4t*HA vliati,,x‘otyittili. 4 Atkiitn,4,KACat RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND AVM-4101,T, -t H‘Alf,-6;„MAI taa Ma;Mim 1 Al,1M,Atatill A 1, 1.M.AN k I:t)ANA 10xxx4A11;Mill:;,4.1K,IN5r,e7jy...,0411,:,, "i81,4NatxxiAL4L'4.gt1?3ixxxi.Ai33', USE OF THE RESPECTIVE EQUIPMENT, 9 ITITYA I.10',AA TIM'A i4i:4 A,N4, ..,iii AN' V.1 Ell°!,2,c,,±0, Q6.61QA6)6.6 61-6101/21.s.67,611 6 SittaNs)))),66131 WITHOUT THE WRITTEN PERMISSION LGtmrt-triltirtt',Kerr,:f.65),),/60,i-A OF BLUE RAVEN SOLAR LLC. 0?'4,5t.16107,aaa ta6h4,1"1 OT 3hht hOlh,tl't"P,Mai 1.,72P st,,,„- i' ,a14, 9,444M 0 tjA4'I AAN6M6127 4 A.M,AliPalt T Hayera? "?.?tttit"?4,6 MtmititA,th"ttala",-,il Stale?", tht4aahtlt4tNIC'NJW,,`SISla,nal.f,4 Pr"TTATA rir44pie,F iM, at`EAM 1c)6)10 SL F)06.560)) 1.5,65..546,5)5 thaahl tah40 Pti Se6f) (Nr-I-A-BC-EF"\\ LCA'imaNIAINIWAii'MNPAI I a AMAAA'm 6.0 i:35eamt 156 iI,111, Hi;Aar Plat,Pi,V,PtaAt a (A,C.-5,4640E5 I, I Chtit-ANIC?tilt7011,i1 air,kytait AAAAtram i't 4Ormat ii FT%72 l',..160,tirl CERTIFIED A4,athltata?"93 3 -q, Kt,,mr, rrFRI,44,:,,IT AI I,1.1 ..K.l'ahara ',...(1*%.v IN1AtiNtA,11421Atr4K.,;cilk:vi 0 MAAmit., PFAA.,71,),IC)al 1),:-t-,e, Foovvr.F.,,F FF Ftcw:., RA e,c,liliFLI444.11T11,4*.Pii: 1.,..M. PV INSTALLATION B100167 4 leli. i 0 ITV ,T.,T ME itt,11 SI"ierie33 344 72,3,31H.HP11),33=30.3 PROFESSIONAL R441 4,,t PLAY, ",,10 rtitAil LA,1=1 aaalattitt, LAA firF11 PAK 1", , . a:1cep,Hi10(,a1Bia,t mAoAltAaii OMtalilt (.0,)P65I6'16AK6 P`DaUlaOt 1,i,H.L, i 5.,,'Wt,F1 11,A Scott Gurney WO ,, laP F 40 13;KPtHiTttHPI A aAM #PV-011719-015 866 Al.%(.4,)x.'„:4:.itaMfr6P.xce,,,,,.1,10,1610:1 fill' '..ONO Lna datia.8.AATitAra-pr-H) ...m,40,..,,q csi4/....,w.1..,.,...,. S 5N ' *VA !AFT,A1 PT,xxorANIIAP , ,'," fie ,' 4'1:HXjtH,H' xM , : 'AK Tht)Ai 9„1,9 001 CONTRACTOR:C *Vltt7V MEN ,"NP Q.PE:Ak DkfiCt!:1J1),,;M't-•G1C71".1 BRS FIELD OPS ..,kil,,ka'i 64)OA A',4SH bk,,a,,,YY x V.-Y.:'/,' i.Rfr 72iii141145;;IP1)(PHiPiTHIA;161.,ax:cM 4-At'ulo40r,ACAlit (!,,/,N3 AM,1;11,1 444 AC,CM.11 ithiSePl;_C'','"W 385-498-6700 65, u PEP335 MO AL QV:06U illt)5.05.0 601.0 0)kA.,..4, :A=M6(f.i.)2 .,;',...:".,,,,,M,'2V,,,r ...,.':2.. 'ti.,r,,,A.) y... ,./ I',f,(KAI,("It‘h.::KAT,,Nftlf 7.1'1 KS-OK i'43 A*ATTT TtrAST3SY, .::.4,72. Adr,11.1 IT'11(MA:A')(P4rei IAD 12.ttit11i,tiA,i1.1M"What'll?*s CM 14,„r”rni i -'4.,4.,PI MAit 1,M,tt,1 ii‘Aii SI ii-haakvi, 14/,1 at'0,:.03,09,10 r.,4 Pe A ijite.,II i en),)00),Li4 4411e4 4 4 ;Aim A,1.iiiiiimet 4/ Sia1iiM.,ep,H.,r,43,kw,mp „5,60,6066),',U41'666560, 6654 566666 :!,4-i*.lis.i‘.0.1,,,AT REA. 14,tAuta,7,1,, MTh 6,65'06 55-56hri- PLAN Enerq,-,",,,,t?Tt, AM,t.i.ALMS tia,,ta at,...Miat ati atAxAM in, 44:AA Miettiliti BLK 2&ellen r.aat-?att 4 v Oa tit?4 caltalt Cataltalt(,.. et m A Lit,,P'..C.prit. k 1.,,,,xm,o,cat,a`,1.xxa.4 a a 04 PraX f Tunny;:72 6.6,61)5 )666..6.061 ,i'l 44 V 10660.0 645060,61 ky‘wer.) I'. ',.,t,,, DRAWING BY: PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1-Jul-2022)Mandatory ED 16.3 15(1-Jul-2022)Mandatory S S r Report No. 102393982LAX-002 Page 44 of 138 Issued: 11-Apr-2016 Unirac, Inc Revised: 5-Oct-2022 : LUE RAVEN 11.0'Illustrations :.. i. :. :. Illustration lb-Approved PV Modules Continue 1403 N.Research Way Orem,UT 84097 Plartufacturit Modute r4odet f Salts $44.1.0411,tre Modulo 44tt f Seties 800.377.4480 W W W.BLUERAVENSOLAR.COM < ro,foPr4k Seth^< .... A KeKefi,4{4P 6LSS.51 +.M.AX;..A?;x{g, S;c-+Uwrx CONFIDENTIAL-THE INFORMATION 'vxset'tak.Z 5r.t=t• S',KKK',F. S nt„Ka A r.44#rrr•: HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE T.,r44...k ?Et ni fer=r:o A&Knefn w tr.Kt IA.A.K's liKt, KAK SEC:Cool l EXCEPT BLUE RAVEN SOLAR NOR 'Cd..anfkr,tM 2�.M;"lx`^'t T i,Y 1.4,.•31o..MESA.1"Piyt-J. SHALL IT BE DISCLOSED IN WHOLE OR .'n±trs't.44 1 AArrn t f t!t trim. ti Ta c autsr. ,tptr=Ar SKI.;_'! IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,Tp4 EX EPT'stati.k SC SC 5 `t 6 r,t.0 IN CONNECT ON WITH THE SALE LAND F"trnraot V t&A, &of-Kw*A 1"a'.Aorirft r`4±;td Tnx3tl,!AA'S USE OF THE RESPECTIVE EQUIPMENT, nets t?4mt s'}to sY�tEdt.l(" '.S; 1r,�}5. .. WITHOUT THE WRITTEN PERMISSION >R .."gtc' nG41-,tsc Y ,W.,2,!,,uI 06- OF BLUE RAVEN SOLAR LLC. SEC-S.f(af SEC arx CC4D 544 rfoj it II,Pill,tIC}3d.I.'t; +Kii„, t'tIX ArVA. 4 re-re, vN: P.SNKr'rr er.(4€t`mati8 01-..1‘.,Ki .364 .&SEP 6 SefKK. lir M.x.gt.11,_ NABCEP Lr. ,.41 5:t=44' Cta, 4 -,..4 4;44rr�:.4 4 x ti,..34. " i 1,1, D7M...-t,S_ t;0,1A,Kxx;tsk4 CERTIFIED M .6x»rAA."Al 1-410 IRE AK,K,I..:d&A._Ica_if&AA,,xvar.eef PV INSTALLATION �,I.r4'.K tt�. ~%t.:r t,',Ji 444C :1€rr� ;a .xxr ��t� �, , PROFESSIONAL ,.ndnr3'. Scott Gurney cotnrvr Fti°^§rr+4.7•xr.xC tr!?' V`tar4 'i"'° #PV-011719-015866 f.,u„,,t,i t..Kfrxr CAM rA:: v.,1::vz:e CONTRACTOR: SKA)0`V-K-z ld BRS FIELD OPS s..;:#36 ro.. 0,St.-t>w� ��� r; n_,r. tS vt,.kr aerr.�: 385-498-6700 444,Kt *.-3t.:•.ro>C'S"t t,44, ,'44'.,q;rtr 1555 t, :We.,,`W..4.4 1r,6 3Fsy.4 ',ev..7-1._ 'S.t,g 4,0.t.s 4at1$.,+C$. yy,.Cl 4C11 co$4,141 5ef-40431. .rT,r,._ ,,0 tilt,', ed,d,vratt , k....t,et,it.OrrK, Cf,44X54444..r_rr~. w,.o M S Ker ct h 6 Alrfr t:e,fr.'_"."±tz'.t. DRAWING BY: PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1-Jul-2022)Mandatory SS