Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE
The TYCO Series TY-FRB Sprinklers r
Description described herein must be installed .
and maintained in compliance with
The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the
Upright (TY313) and Pendent (TY323) applicable standards of the National 'P
Sprinklers described in this data sheet Fire Protection Association,in addition •ik , .,5x .,
! j
are quick response,standard coverage, to the standards of any other authori-
decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so Mill
sprinklers designed for use in light or may impair the performance of these \
ordinary hazard,commercial occupan- devices. i.._
cies such as banks, hotels, and shop-
ping malls. The owner is responsible for main-
taining their fire protection system
The recessed version of the Series and devices in proper operating con-
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac-
applicable,is intended for use in areas tor or product manufacturer with any
with a finished ceiling. This recessed questions.
pendent sprinkler uses one of the
following. Sprinkler
• A two-piece Style 15 Recessed 4, � >#
Escutcheon with recessed adjust- Identification
ment up to 5/8 in. (15,9 mm) from
the flush pendent position. Number (SIN)
• A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPT
Escutcheon with recessed adjust- t`'`
ment up to 1/2 in. (12,7 mm) rom TY323. . . .Pendent 5.6K, 1/2 in. NPT T " _..
the flush pendent position. Technical
The adjustment provided by the Data Operation
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops The glass bulb contains a fluid which
to the sprinklers must be cut. Approvals expands when exposed to heat.When
Intermediate level versions of Series Refer to Table A the rated temperature is reached, the
TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently t to sprinklshatterer
the
Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to
kler guards and shields are described 250 psi(17.2 bar)' activate and water to flow.
in Technical Data Sheet TFP78O. 'The maximum working pressure of 250 psi(17.2 bar) Design
only applies to the listing by Underwriters Laborato-
ries,Inc.(UL).
Discharge Coefficient Criteria
IMPORTANT K=5.6 GPM/psis(80,6 LPM/bard) The TYCO Series TY-FRB,5.6 K-factor,
Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323)
TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec-
regulatory and health information. tion systems designed in accordance
Always refer to Technical Data Finishes with the standard installation rules
y Sprinkler:Refer to Table B
Sheet TFP700 for the "INSTALLER recognized by the applicable Listing or
WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing
with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA
lation of sprinkler systems and com- Plated 13, and FM Approval is based on the
ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention
installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style
a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used
vents and cause the sprinkler to fall Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations.
to operate in a fire situation or cause Bulb Glass
it to operate prematurely. compression Screw Bronze
Deflector Bronze
Page 1 of 4 AUGUST 2018 TFP172
TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request.
2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
.•777l7EGrGH. } \
/
5 1 7/16"
(11,1 mm)
4 — NOMINAL 2" ��
MAKE-IN (50,8 mm) 1 __irr j\ /
2' V 0, 2" 1-3/8"
(50,8 mm) (34,9 mm)
3 WRENCH
11 FLATS 1
1 }
1/2" NPT** DEFLECTOR* �— 2-7/8"(73,0 mm)DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting.
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A') dance with this section. sprinkler fitting using only the W-Type
General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
FlGURE 2 Do not install any bulb-type sprin- erence to Figure 1,apply the W-Type 6
W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH a loss of liquid from the bulb. With the Torque sprinklers 7 to 14 lb-ft (9,5 to
sprinkler held horizontally, a small air 19,0 N•m).
bubble should be present. The diam- Recessed Pendent Sprinklers
WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent
RECESS 1/16 in.(1,6 mm)forthe 135°F(57°C)and Sprinklers must be installed in accor-
3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions.
-jr it
�, temperature ratings. Step A. After installing the Style 15
A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the
should be obtained by applying a sprinkler threads,and with pipe-thread
minimum to maximum torque of 7 to sealant applied to the pipe threads,
LI
14 lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the
of torque can distort the sprinkler Inlet sprinkler fitting.
with consequent leakage or impairmentPUS Step B. Tighten the sprinkler into the
IN TO WRENCH of the sprinkler. sprinkler fitting using only the W-Type
N ENSURE Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
ENGAGEMENT insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WITH SPRINKLER eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench
WRENCHING AREA the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m).
W-TYPE7 RECESSED
Upright and Pendent Sprinklers Step C. After ceiling installation and
SPRINKLER WRENCH
The Series TY-FRB Upright and finishing, slide on the Style 15 or Style
Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB
in accordance with the following Sprinkler and push the Closure over the
instructions. Mounting Plate until its flange comes in
Step 1.Install Pendent sprinklers in the contact with the ceiling.
pendent position. Install upright sprin-
klers in the upright position.