Report (2) Fe5 2023-0O U 6 • . t OFFICE COPY RECEIVED 120t Pu-horntzo OCT Worldwide ri eomwww•tyco--firecyCOo Co CITY OF TIGARD BUILDING DIVISION Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers r Description described herein must be installed . and maintained in compliance with The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the Upright (TY313) and Pendent (TY323) applicable standards of the National 'P Sprinklers described in this data sheet Fire Protection Association,in addition •ik , .,5x ., ! j are quick response,standard coverage, to the standards of any other authori- decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so Mill sprinklers designed for use in light or may impair the performance of these \ ordinary hazard,commercial occupan- devices. i.._ cies such as banks, hotels, and shop- ping malls. The owner is responsible for main- taining their fire protection system The recessed version of the Series and devices in proper operating con- TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac- applicable,is intended for use in areas tor or product manufacturer with any with a finished ceiling. This recessed questions. pendent sprinkler uses one of the following. Sprinkler • A two-piece Style 15 Recessed 4, � ># Escutcheon with recessed adjust- Identification ment up to 5/8 in. (15,9 mm) from the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPT Escutcheon with recessed adjust- t`'` ment up to 1/2 in. (12,7 mm) rom TY323. . . .Pendent 5.6K, 1/2 in. NPT T " _.. the flush pendent position. Technical The adjustment provided by the Data Operation Recessed Escutcheon reduces the accuracy to which the fixed pipe drops The glass bulb contains a fluid which to the sprinklers must be cut. Approvals expands when exposed to heat.When Intermediate level versions of Series Refer to Table A the rated temperature is reached, the TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently t to sprinklshatterer the Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to kler guards and shields are described 250 psi(17.2 bar)' activate and water to flow. in Technical Data Sheet TFP78O. 'The maximum working pressure of 250 psi(17.2 bar) Design only applies to the listing by Underwriters Laborato- ries,Inc.(UL). Discharge Coefficient Criteria IMPORTANT K=5.6 GPM/psis(80,6 LPM/bard) The TYCO Series TY-FRB,5.6 K-factor, Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323) TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec- regulatory and health information. tion systems designed in accordance Always refer to Technical Data Finishes with the standard installation rules y Sprinkler:Refer to Table B Sheet TFP700 for the "INSTALLER recognized by the applicable Listing or WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA lation of sprinkler systems and com- Plated 13, and FM Approval is based on the ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used vents and cause the sprinkler to fall Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations. to operate in a fire situation or cause Bulb Glass it to operate prematurely. compression Screw Bronze Deflector Bronze Page 1 of 4 AUGUST 2018 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON .•777l7EGrGH. } \ / 5 1 7/16" (11,1 mm) 4 — NOMINAL 2" �� MAKE-IN (50,8 mm) 1 __irr j\ / 2' V 0, 2" 1-3/8" (50,8 mm) (34,9 mm) 3 WRENCH 11 FLATS 1 1 } 1/2" NPT** DEFLECTOR* �— 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Installation Step 2. With pipe-thread sealant applied to the pipe threads, hand- The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the END"A') dance with this section. sprinkler fitting using only the W-Type General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FlGURE 2 Do not install any bulb-type sprin- erence to Figure 1,apply the W-Type 6 W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH a loss of liquid from the bulb. With the Torque sprinklers 7 to 14 lb-ft (9,5 to sprinkler held horizontally, a small air 19,0 N•m). bubble should be present. The diam- Recessed Pendent Sprinklers WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent RECESS 1/16 in.(1,6 mm)forthe 135°F(57°C)and Sprinklers must be installed in accor- 3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions. -jr it �, temperature ratings. Step A. After installing the Style 15 A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the should be obtained by applying a sprinkler threads,and with pipe-thread minimum to maximum torque of 7 to sealant applied to the pipe threads, LI 14 lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the of torque can distort the sprinkler Inlet sprinkler fitting. with consequent leakage or impairmentPUS Step B. Tighten the sprinkler into the IN TO WRENCH of the sprinkler. sprinkler fitting using only the W-Type N ENSURE Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure ENGAGEMENT insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WITH SPRINKLER eon Plate by under-or over-tightening W-Type 7 Recessed Sprinkler Wrench WRENCHING AREA the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m). W-TYPE7 RECESSED Upright and Pendent Sprinklers Step C. After ceiling installation and SPRINKLER WRENCH The Series TY-FRB Upright and finishing, slide on the Style 15 or Style Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB in accordance with the following Sprinkler and push the Closure over the instructions. Mounting Plate until its flange comes in Step 1.Install Pendent sprinklers in the contact with the ceiling. pendent position. Install upright sprin- klers in the upright position.