Loading...
Report FPS2023 —000// BMANHESTER AFFICE COPY Td_C HNOI O_ICG Y SYSTEMS EQUIPMENT SUBMITTAL for RECEIVED JM 3 0 2022 TIGARD SENIOR HOUSING IIY OF TIGARD 8803 SW OMARA ST, TIGARD, OR 97223 ?lJll_.DING DIVISION Fire Detection and Alarm System submitted by GB Manchester Inc CCB 202097 MODEL # DESCRIPTION MFG iO1000RD FIRE ALARM CONTROL PANEL W/ DIALER EST PS12180 BATTERY, 12V/18AH (FACP) Power Sonic RLCD-CR LCD ANNUNCIATOR, RED EST BPS10A BOOSTER POWER SUPPLY, 10A EST PS12100H BATTERY, 12V/10.0AH Power Sonic SIGA-CC1S SYNC CONTROL MODULE EST SIGA-OSD OPTICAL SMOKE DETECTOR AND BASE EST SIGA-HFD HEAT DETECTOR, 135° FIXED EST SIGA-278 PULL STATION EST SIGA-CT1 SINGLE INPUT MODULE EST SIGA-CT2 DUAL INPUT MODULE EST SIGA-CR RELAY CONTROL MODULE EST SIGA-CRH RELAY MODULE, HIGH POWER EST G4AVWF HORN-STROBE,WALL, WHITE EST G4VWF STROBE, WALL,WHITE EST GCAVWF HORN-STROBE, CEILING, WHITE EST GCVWF STROBE, CEILING,WHITE EST GCF-VMH STROBE, CEILING, WHITE, HIGH CANDELA EST WG4WF-HVMC HORN-STROBE,WALL/CEIL., WHITE, WP EST G4LFWF-H HORN (520HZ)WALL,WHITE EST 7707P-88-ULP-M RADIO COMMUNICATOR AES BW-DOCBOX DOCUMENT CABINET MIER 6000 NE 88th St, Vancouver, WA. 98665 Portland 503.287.1112 Vancouver 360.816.0484 Toll Free 877.816.0484 Small Building Fire alarm Solutions E3wARDs MR =NMI Intelligent Fire - . �i� sir o mom pm 0°0 Alarm Systems -a> i064, i01000 FDNY ..�ono COA 6227 vvva° i HAnDa 7165-1657. (W4sugs 0244 83000 Overview Features EDWARDS brand intelligent life safety systems offer the power • Auto-programming reduces installation time of high-end intelligent processing in configurations that deliver • Supports Signature Series intelligent modules and detectors uncomplicated solutions for small to mid-sized applications.With • Combines the Signature intelligent releasing module with intelligent detection,electronic addressing,automatic device mapping,optional Ethernet®connectivity, and a full line of easily Signature multisensor detectors for reliable fire suppression configured option cards and modules,these flexible systems offer • Electronic addressing with automatic device mapping versatility that benefits building owners and contractors alike. • Optional Ethernet port(SA-ETH)for central station monitoring service The i064 provides one Class A or Class B intelligent device loop ^programming,diagnostics and a variety of system reports. that supports up to 64 device addresses,and two Class B Notifi- • Two programmable switches with LEDs and custom labeling cation Appliance Circuits(NACs). Optional Class A device wiring is • Supports Genesis horn silence over two wires,and UL available with the use of a module. 1971-compliant strobe synchronization The i01000 provides one Class A or Class B intelligent device • Optional multi-protocol Field Server Bridge for interface loop that supports up to 250 device addresses. Loop controller to 3rd party Building Management Systems. modules may be added in combination to expand total system • Ground fault detection by module capacity in 250-point increments to up to 1,000 device addresses. • Supports up to eight serial annunciators, (LCD, LED-only, The i01000 panel includes four NACs that may be wired for either and graphic interface) Class A or Class B operation. • Can use existing wiring for most retrofit applications The RZI16-2 module adds even more capacity to i0 installations • Upload/download remotely or locally by adding up to 16 conventional device circuits and two additional • Optional USB module for local printing or programming using notification appliance circuits.This makes them an ideal retrofit the configuration utility on a technician's laptop. solution that can accommodate new intelligent detectors,as well as existing conventional devices. • Two-level maintenance alert reporting • Pre-alarm and alarm verification by point iO Series supports a wide range of high-end features, including: • Supports 10-Year Carbon Monoxide detectors • Adjustable detector sensitivity • 4 x 20 character backlit LCD display • R-Series remote annunciators • Optional earthquake hardening:seismic Importance Factor 1.5 • SIGA-REL Releasing Modules • Standalone operation • Fully integrated CO detection using Signature Series detectors with or without audible signaling • Alarm ON command manually activates alarm condition • Form C contacts for alarm and trouble, Form A for supervisory Page 1 of 8 E85001-0135 Issue 2.0 Application Perfect for retrofits EDWARDS iO Series life safety systems are powerful intelligent EDWARDS i0 Series control panels are particularly well-suited to solutions for small to mid-sized buildings.Advanced Intelligent retrofit applications.All connections are made over standard wiring technology delivers the benefits of flexible system installation, -no shielded cable required.This means that in most situations while clean and easy-to-operate user interfaces make panel existing wiring can be used to upgrade a legacy control panel to operation and system maintenance quick and intuitive. 10 technology without the expense or disruption of rewiring the entire building.10 control panels also support the ingenious The smart choice RZ116-2 Zone Module,which adds up to 16 conventional circuits Signature Series electronic addressing eliminates the tedium of and two NACs.This combination easily accommodates new setting dipswitches,and automatic device mapping ensures that intelligent detection alongside existing conventional circuits, each device resides on the system at its correct location.Mean- making it an superior solution in the retrofit market. while,innovative programming allows the designer to customize the system to precisely suit the needs of the building owner. Scalable IP and Cellular Communications Optional SA-ETH module supports IP connection to a central sta- Reliability you can count on tion's Sur-Gard receiver,meeting one of the methods of communi- The inherent fault-tolerant characteristics of Analog/Addressable cation allowed by NFPA 72 as of the 2013 Edition.Several popular Technology boosts the reliability of EDWARDS fire alarm systems. third-party IP/Cellular communicators have been tested with the 10 When combined with i0 Series smoke and heat detectors,these control panels and are compatibility listed to UL864.The IP/Cellular systems deliver a level of dependability not previously available for communicators meet NFPA72 2013 edition requirements for sole small to mid-sized applications.All EDWARDS systems are built to or secondary transmission paths.Using IP/Cellular communicators exacting reliability benchmarks. can reduce the cost of ownership by eliminating POTS lines.Please see the 10 control panel compatibility documentation part number Clear-cut remote annunciation 3102353-EN for a full list of compatible communicators. . Remote annunciation is a strong suit of the i0 Series fire alarm systems. Up to eight annunciators can be installed on a single Signals with a difference system.Compatible annunciators include a range of LED and i0 system NACs are configurable to fully support the advanced LCD models that provide zone or point annunciation,as well as signaling technology of EDWARDS Genesis and Enhanced Integ- common control capabilities.i0 control panels also supports rity notification appliances.These devices offer precision synchro- graphic annunciation with optional RA Graphic Annunciator nization of strobes to UL 1971 standards.For Genesis devices, interface modules.Each interface provides common control enabling this feature allows horns to be silenced while strobes on and 32 LEDs. the same two-wire circuit continue to flash until the panel is reset. Flexibility built right in A complete line of accessories Two fully-programmable front panel switch/LED combinations Provide i0 Series life safety systems are supported by a complete line of an added me.sure of flexibility.Their slide-in labels take the mystery analog/addressable detectors,modules and related equipment. out of custom applications,and present a clean finished appearance. Consult the Ordering Information section for details. Programming and remote diagnostics Dimensions systems are simpleto set up,yet i i0 Series life safety '2' 'I `D EDWARDS ��..,i oa di . hu+l offer advanced programming features that put these small building _ i T— • •O O O •0 f0 panels into a class of their own.The auto programming feature t quickly gets the panel operational using factory default settings. O o Basic zone and point settings can be programmed through the front panel interface,so the system is up and running in no time. t O 0 O For more advanced system configuration and correlation groups °' • r•O w programming, i0 Series systems interface to a PC running com- ® _ e I O IC) pebble i0-CU software.This option offers full system configuration ® 1 in the familiar Windows®operating environment.Connection is made to a laptop through the panel's optional RS-232 communi- _ cations port,which can also be used to connect a system printer >e 1409.1 D9,1 Among the many innovative features of 10 Series control panels (1)surface Mounting Holes (3)Backbox 'o0o Attached is the optional network card.This module provides a standard 10/100 Base T Ethernet®network connection that permits access (2)Semi-flush mounting Holes (4)Backbox with door and trim kit attached. to the control panel from any remote location with the correct Panel dimensions,in(cm) communications protocols.The connection can be used to .._- download to the panel from the i0-CU,or upload and view Model D,' D2 r u3 04 J 0 i Da D7 a8 i D9 280 3.85 9.0 22D ; 15.75 F 7025 1 4.4 28.2 27 system reports using the i0-CU, lam p1.1i P s) pm 1.tem , -' film (no) l (e 21.5 3.85 i 7.5 155 1425 10.25 i 4.5 21.7 2.7 Available system reports include:Correlation groups.Device io94 (s1.6) 155) (19.Q 1 PGA j t , PA L1.4) (5.5.1) (0.8:1 details,Device maintenance,History,Internal status,System •Add 1-1/2 in.(3.81 alto D1 and D5 dmmaious far trim Idi The trim kit configuration,System status,Walk test,Dialer,and CO runtime. provides 0.75 inches(1.9 an)of trim to the top,bottom,and sides of the bedmox. E85001-0135 Page 2 of 8 Issue 2.0 4 System Layout io1000 ii Any combination of two single-or dual Signature loop modules . AV Standard Loop:250 points(one expansion slot) i0-SDC2 Expander, Loop 1 of 2: 250 points Up to 125 sensors and 125 modules per loop (one expansion N„ _ii t trfS,— -- — l —a—,, 'sz i ♦ • ,-eve '..ii% >I l:.xi, , I a< I , iO-SDC2 Expander, Loop 2 of 2: 250 points ,up to 20,000 feet of wiring per bop I 1 i , it 5 IS ff. Ili- kziT;:4 ' T Optional 10 A or 6.5 A Booster c «:o ate.^ C Ethernet(SA-ETH)" 1 -_ iiii la DACT/Dialer(SA-DAC1) �— Up to eight remote annunciators RS-232(SA-232 or SA-USB)" Sixteen Conventional IDCs, Relays:Two Form C,one Form A two additional NAGS with RZI16-2 module Each 101000 panel has room for up to two Signature loop controller modules in any combination of single or dual 250-device loops. i01000 loops support 125 detectors and 125 modules. Panel Layout 'C.,1 8 n ",s 3,.. --s----- �R1__ 110 ' yr"-�.-i -'° .444.-4' i064 2 �1 �M aplitx -.� �! 7 i' or r e 1 QQ r ( x f C� off1L 1' ) tt -F a t rt L7«Y t CO cl%;" Loop supports up to 64 intelligent devices of any 9t0 + ' , 4 ...-'M�FIat. 1_ 10 Up to 20,000 feet of wiring. -:-Uik --11 5L (. '" 12 Optional 10 A or 6.5 A Booster Power Supply 3111). G3 _ ---- I -- ----- - — - el— — —■e r3 __e -_ .. 1 Transformer 2 Main AC wiring block&fuse holder 3 RS-232 card connector(J3) Ethernet(SA-EfHy .-----' 4 Dialer card connection(J8) 5 Ethernet card connector(J 1) DACT/Dialer(SA-DACT) D 6 Main circuit board RS-232(SA-232 or SA-USB)" 7 Panel backbox enclosure 8 Operator interface Relays:Two Form C,one Form A Sixteen Conventional IDCs, 9 SLC card connector(J7) two additional NACs with 10 Class A card connector(J2) Each i064 panel ships with one Signature loop RZI16-2 module 11 Tie wrap mounts tabatsexpander controller that supports 64 devices of any type. 12 connector(J6) 13 S Standby batteries This panel's device capacity cannot be expanded. 'SA-ETH supports:(1)remote connectivity for diagnostics&programming,(2)Central station monitoring to Sur-Gard IP Receivers. "'RS-232 supports:(1)Printer,(2)Programming Interface,(3)Use of Field Server Bridge(SA-FSB)for 3rd party Building Management Systems interface. Page 3 of 8 E85001-0135 Issue 2.0 Wiring & Configuration Signature device loop Auxiliary&smoke power outputs(TB3) T63 The system provides one Signature device loop circuit with a total The control panel provides two auxiliary power capacity of 125 detectors and 125 module addresses.The loop outputs that can be used for powering ancillary 0=-No circuit is supervised for opens, shorts,and grounds. equipment such as remote annunciators and two (1) 0 wire smoke detectors. Aux 2 can be software �INC Circuit 101000 i064 selected to operate continuously.The circuit is specifications supervised for shorts and grounds. Device loops One Class B or A One Class B or A loop, (� NO loop,supporting 125 supporting 64 devices of Circuit specifications 0 four load a'kind. Circuit voltage 21.9 to 28.3 V modules.Expandable to ' range NC detectors and 125 %...._ r __-_--- -- --.- -- Resettable circuit 24 VDC nominal at 500 mA _. (3) -t __. NO Communication Maximum 20 V peak-to-peak ower 2 line voltage i Continuous circuit 24 VDC nominal at 500 mA. Circuit current 0.5 A max (Aux power 1) Use this circuit for powering Circuit 660 total,0.5 pF,max two-wire smoke detectors. ImpedanceNote:Any current above 0.5 amp connected to both Aux Isoletora.. _. .. 64 maximum_. _-._ _-_- - 1 and 2 will reduce the total available NAC power by that 0 Signal Supported on a system-wide basis(all device loops) amount. Synchronization when using a SIGA-CC1S or SIGA-MCC1S nodule (1)Trouble and Genesis or Enhanced Integrity notification ap Alarm,trouble,and supervisory relay(TB3) (2)Supervisory pliances. The trouble relay is normally-open,held closed, (3) um.awiring Coss Awing and opens on any trouble event or when the (4)Smoke/Aux panel is de-energized.The supervisory relay is Loop+sec.&- Data u.. Loop+�c -® normally-open,and closes on any supervisory event.The alarm relay changes over on any Loop 1 FRI -@ + Loup 1 PRI -® 1,`e. - alarm event. +� Loop Loop + Loop Loop Loopy avIw devise Loop MO a aL1N °iNn °e Relay specifications Alarm Trouble Supervisory Type Form C Form A Notification appliance circuits(TB2) Voltage , 24 VDC at 1 A resistive 24 VDC at 1 A resistive 101000 control panels come equipped with four notification ap- Relay circuits can only be connected to power-limited sources. pliance circuits. i064 control panels come with two NACs.Each circuit can be individually configured for continuous,temporal, synchronized, and coded output. Annunciator loop(TB4) Specifications i01000 1064 The control panel provides a connection for up to eight serially Circuit Type 4 Classor 2 B or 2 Class A 2 Class B or 2 Class A driven and supervised remote annunciators. with SA-CLAmodule dule Voltage __ Circuit specifications --- � - 24 VFWR Current 8.0 A total,2.5 A max. 3.75 Kirin!,2.5 A mau. Device loops Class B(Style Y)or Gass A(Style Z) per circuit at 120/230 per circuit at 120/230 Circuit voltage 2.55 V VAC 60 Hz. VAC 60 Hz. Circuit current 30 mA max 5.0 A total,2.5 A max. . 3.0 A total,2.5 A max. Circuit Up to 8 annunciators or 4000 feet per circuit at 230 VAC per circuit at 230 VAC impedance _. .___ __-___—.___ 50 Hz. 50 Hz. - __--- Impedance 26 0 total,0.3.5 pF max .__ . _---EOLR 15 K 0,%W Class B Class A Synchronization 1_ Supported system-wide .._.__... Channel1 Channel Channel Channel + — + — + — + — loss CkaBwiring ' I 1-12 Awinnq + a + I0I0I0I®l T� Anlwndafor 01- NAG1 NAC1. .�'■e,1l 0 NAG1+ Anntridabx 0 uAtx -- 0 + + I 0C111(+)IN ®CH7(+)IN 0 NAM. a�:��a[1 O,C—" 4 ®cH1()w �q1(—)IN >es 0 Nap- 0 -- t9 CH2(+)M SCH2(+)IN 0 "Ace' MI91131I 0 + tg[k12(—)IN )ail(—)IN 0 NAu 1111,11113[w R 0 + 0 1i8 TBB Marking indicates output signal polarity when the circuit is active.Polarity reverses when the circuit is not active.Wire notification appliances a000dtgty.Notification appliance polarity shown in active state. E85001 -0135 Page 4 of 8 Issue 2.0 Option Cards EDWARDS 10 Series panels are supported by a complete line RZ116-2 Remote Zone Interface Module of modules and related equipment that enhance performance ....... ......... and extend system capabilities. Option cards plug directly into • . • the control panel main circuit board or are connected to it with a ribbon cable.After installation,terminals remain accessible.The . . cabinet provides ample room for wire routing,keeping wiring neat I at all times. . . . Single and Dual Loop Controller Cards The RZI18-2 Addressable Remote Zone Interface Module is an The i0-SDC1 is a single loop controller card that can be used with addressable device that provides connections for sixteen Class B the iO64 as a replacement for the standard 64-point loop,or with the i01000 as a 250-point expansion module. Initiating Device Circuits and two Class B Supervised Output Circuits.The inputs and outputs can be configured indMdually The iO-SDC2 is a 500-point dual loop controller card for the for several device types, i01000 that provides two SLC circuits,each with 125 detector It requires 18 consecutive addresses on the Signaling lJne Circuit addresses and 125 module addresses. (SLC).Addresses are assigned electronically.There are no address Specifications 1 10-SDC1 [ iO-SDC2 switches to set. 01000:one loop, ; The RZI16-2 incorporates two 8-segment DIP switches that 250 device addresses KA gal two loops, are used to select the Alarm or Supervisory default device type Device Addresses i064:64 addresses,.,500 device addresses for each of the 16 IDC circuits.The module also includes one Wiring Class B or Class A 4-segment DIP switch used to select the default Relay or MAC Operating Voltage 24 VDC output device type.Device types other than the default are Operating Current Standby:55 mA Standby:45 rnA accomplished through programming. (fully loaded loop) . Alarm:80 mA , Alarm:70 mA Note:these ratings do not include the use or two-wire smoke modules. RZI16-2 Specifications Communication Voltage Line Voltage Max.20.6 V peak-to-peak 24V/Aux nominal: 24 VDC Terminal Rating 1 12 to 18 AWG(0.75 to 2.5 mm2) Supervisory current: 250 mA at 24 WC nominal Circuit Current i 0.5 A max. Alann Current 1000 mA 24V/Aux minimum: 18.4 VDC Max total loop resistance 66 0 24V/Aux maximum: 26.4 VDC Max total loop capacitance. 0.5uF NAC1,NAC2 nominal: 24 VDC 64 isolators maximum per loop(total both Current Isolators : isolator bases and modules) Standby current Ground Fault Impedance 1 Oto5k0 for 4.7 k EOL(U.S.) 4.8 rnA/circuit -i- 32 to 120°F(0 to 49°C) Standby current for Operating Environment I 0 to 93%noncondensing at 90°F(32°C) 3.9 k EOL(Canada) 5.7 rnA/circuit Alarm current at nominal voltage 31.1 rnA/circuit Relay outputs SA-ETH Ethernet Interface CanVIP Communicator Quantity 2 Type Rating(pi The SA-ETH card provides a standard 10/100 Base T Ethernet lot duly) Programmable 24 VDC at 2.5 A network connection for connecting to an Intranet,a local network, Input circuit wiring 25 0 per wire resistance or the Internet.The card supports IP connectivity for monitoring Initiating device circuits services by a supervising station to meet Quantity 16 4 NFPA 72 Chapter 26. The Ethernet card uses 4.7 kO(U.S.):3.9 Id)Canada the FIBRO protocol to communicate with EOL resistor Zone voltage 22.78 V for 4.7 kfl(U.S.) Sur-Gard System receivers(see below).The 22.08 V for 3.9 kr)(Canada) card can be used to download configuration Alarm current 31.1 mA/channel at nominal voltage from the 10-CU tothe panel. pil The Ethernet card is installed on the plastic Alarm impedance range <680(1 Trouble Impedance range >5.55 kfl Supervised output circuits assembly and connects to the main circuit EOL resistor 15 kO board via a ribbon cable. Quantity 2 Short circuit detection <2.6142 SA-ETH specifications Open circtit detection >61.9 kfl , Ethernet 10/100 Base-T Contact ratings 24 VDC at 2.5 A(5 A for two NACs) , Operating environment Compatible cabkiets MFC-A,ol000,APS Temperature 32 to 120°F(0 to 49°C) Humidity 0 tv 93%RH,nonoondensing at 90eF(32°C) Compatible Str-Gard Receivers SG-System I,II,Ill,IV and 5 Page 5 of 8 E85001-0135 Issue 2.0 SA-DACT Dialer SA-232 RS-232 interface The SA-DACT provides communications between the control The SA-232 card provides an RS-232 panel and the central station over a telephone line system.It interface with IO panels. It can be used transmits system status changes(events)to a compatible digital for connecting a printer to the control alarm communicator receiver over the public switched telephone panel to print system events.The card network.The dialer is capable of single, dual,or split reporting also can be used for connecting a II um of events to two different account and telephone numbers.The computer to download a configuration 'IIBI modem feature of the SA-DACT can also be used for uploading program from the iO-CU to the `„ and downloading panel configuration,history,and current status control panel. to a PC running the iO-CU. The RS-232 card is Installed on the The dialer phone lines connect to connectors plastic assembly and connects to the . . . • °"OAC """`"' main circuit board via a ribbon cable, wVinp T. on the dialer's main circuit board.Phone line °'°°°jef* 1 connects to connector J4 and phone line 2 miLxiirin 1"I' °A'J.6., connects to connector J1. SA-232 specifications It Fuld Operating voltage Standard BA-232 1 i Terminal rating 12 to18 AWG(0.75 to 2.5 sq mm) 1 I-"c`a The SA-DACT queues messages and Operating environment •s I■ ' transmits them based on priority(alarm, Temperature 32 to 120°F(0 to 49°C) °C.. I. supervisory,trouble,and monitor).Active- Humidity 0 to 93%RH,noncorxiensing at 90°F(32°C) °a°o�P�••f • lions are transmitted before restorations. _.._ . ._ li,=o.f ° i°'r° I The SA-DACT is installed on the plastic assembly and connects to the main SA-CLA Class A Module 0064 only) circuit board via a ribbon cable. The SA-CLA card provides Class A capability for NAC wiring. Its terminal block provides the wiring connection for NAC return SA-DACT specifications Phone ire type wiring.The card is required for annunciator Class A wiring even One or two loop-start lines on a public, though this wiring does not return to the SA-CLA card.The SA- switched network _ .. CLA is compatible with iO64 control panels only.iO1000 panels Phone line connector RJ-31/33B)CC(C31/38X) __- . are Class A Ready.The SA-CLA is installed directly to the control Communication formats Contact ID(SIA DC-05) __ panel circuit board using its plastic standoffs and plug connection. — ------— ---- Operating environment Temperature 32 to 120°F(0 to 49°C) SA-CLA specifications Humidity 0 to 93%RH,rtorrcrorcdertsing at 90°F Operating voltage 24 VFWR _-- Operating current 3.75 A FWR total at 120/230 VAC 60 Hz 3.0 A FWR total at 230 VAC 50 Hz Compatible DACRs 2.5 A max per circuit Formats - Grcuit impedance 26 o_hns_0.35uF Receiver Models _-- _ -------.. mi l 12 to18 AWG(0.75 to 2_5 sg mm) _ Contact ID Terminal rating Ademco 685 -- - - --- — _ FBII CP220 Contact ID Operating environment Osborne-HoffmanContact ID Temperature 32 to 120°F(0 to BoschD ---._._ Humidity 0 to 93%Po-I.nonoondensircg at 90°F(32°C) O660 2000 0 Contact ID -- Contact Silent Knight 9800 ID ID Sur-Gard SG MLR7 ___ -__. . _ D16L-iO LED Display Expander(01000 only) The D16L-iO LED Display Expanders provide LED annunciation for up to 16 zones.It provides two LEDs for each zone.Two D16L-iO The SA-USB Interface Card LED display expanders can be installed in each 101000 panel. The SA-USB Interface Card provides a USB connection to a sup- ported printer or a connection to a PC.The card can be used for (3) th (4) connecting a printer to the control panel to print system events. ;x) lir^fl t21 HIS LED 2(1) LED i The card can also be used for uploading and downloading panel OMEN configuration,historty,and current status to a PC running the riiIIINIIIN ':1III (3)LED Expander 1q1— NIA configuration utility(Ct.). ;:Ifs :1INEN (4)LED Expander 2 O .I (5)Alarm/non-Warn SA-USB specifications kl and trouble zone LEDs Operating voltage 24VDC Current Standby/Alarm 13 m4,max 20mA rit1.11.1 .1 IMI Universal Serial Bus 1 USB Type A Most port J3(printer connection) NON :1111111110 (USB)ports 1 USB Type B dedevice port J4(CU connection) silo 1__ • — -Supported Printer Pr-1S alb lid {IF3'ik7 �IE«'1 Printer communication 9600 baud '{I (5) ,:t Operatingumill ronment {lid •1� TTeemperature 32 to 120°F(0 to 49°C) I19=Era i1lY Humidity 0 to 93%RH,noncondensing E850O1 -0135 Page 6 of 8 Issue 2.0 Specifications 11064 ; 101000 Device loops 1 loop Class B or Class A(Styles 4,6,7)supporting up to j 1 loop,expandable to 4,Class A or B(Styles 4,6,7), I 64 device addresses(any combination of detectors and each loop supporting up to 250 device addresses(125 modules) ; detectors and 125 modules max.).Addresses 1 to 125 are Maximum T-taps:63 for detectors and addresses 126 to 250 are for modules (each device can be on its own branch) Maximum T-taps/loop: 124 Notification appliance 2 Class B(Style Y),Class A(Style Z)optional 4 Class B(Style Y)or 2 Class A(Style Z) circuits 13.75 A FWR total at 120/230 VAC 80 Hz 6.0 A FWR total at 120/230 VAC 60 Hz 3.0 A FWR total at 230 VAC 50 Hz i 5.0 A FWR total at 230 VAC 50 Hz 2.5 A FWR each max.per circuit 1 2.5 A FWR each max.per circuit Primary power j 120 VAC,60 Hz, 1.3 A max. 120 VAC,80 Hz,2.0 A max. 230 VAC,50-60 Hz,0.62 A max. 230 VAC,50-60 Hz,0.97 A max. Base panel current standby 155 mA 172 mA Base panel current alarm 204 mA 267 mA Input zones , 16 max. 32 max. Remote annunciator 8 drops max.,RS-485 Class B,Class A is optional 8 drops max.,RS-485 Class A or B Data line length:4,000 ft.(1,219 m) ! Data fine length:4,000 ft.(1,219 m) Operating voltage 24 VDC panel Atndiary power output Aux power 1:500 mA,24 VDC(1 A Bible if amuit �. you reduce total available NAC power by 500 mA) Aux power 2:500 mA,24 VDC Output:28.3 to 21.9 VDC,special application Note:For a list of compatible devices,see the i064 and i01000 Series Compatibility list(P/N 3102353-EN) Loop circuit Maximum l oop resistance:66 f] Maximum loop capacitance:0.5 pF Communication line voltage:Maximum 20.8 V peak-to-peak Operating current(fully loaded loop)Stand by:55 mA/45 mA i Alarm:125 mA/115 mA(not including two-wire smoke modules) Circuit current:0.5 A max.Style 4,6,and 7 wiring Max.resistance between isolators:Limited only by overall wire run lengths 64 isolators maximum per loop(total both isolator bases and modules) Batteries Type:Sealed lead acid Voltage:24 VDC Charging current:2.47 A max.Amp hour capacity:26 Ah Standby operation:24 hour or 60 hour Placement:Up to two 10 Ah batteries will fit in the i064 control panel cabinet and two 18 Ah batteries will fit in the i01000 control panel cabinet.If larger batteries are required,use an EDWARDS battery cabinet. SA-DACT dialer Phone line network .. ..—— type:One or two loop-start lines on a public,switched network Phone line connector:RJ-31/38X(C31/38X) Communication formats:Contact ID(SIA DC-05) Operating current Standby/Alarm:41 mA Max.: 100 mA FCC registration number:GESALO1 BSADACT Industry Canada Registration number.3944A-SADACT Ringer equivalence number:0.1 B Ground fault impedance 0 to 5 Id) Alarm contact Form C N.O.24 VDC at 1 A(resistive load) Trouble contact Form C 24 VDC at 1 A(resistive load — SupeMsory contact ; Form A N.O.24 VDC at 1 A(resistive Ioac Environmental Temperature:0 to 49°C(32 to 120 F)Relative humidity:0 to 93%noncondensing — — Terminal rating A!temhinals rated for 12 to 18 AWG(0.75 to 2.5 rrrn2) Page 7 of 8 E85001-0135 Issue 2.0 Ordering Information Part Description 101000 Fire Alarm Systems 1010e0G Four loop system with one 250-point loop installed.110v,gray door. WDWAR DS IO1000G-2 Four loop system with one 250-point loop installed.230v,gray door. 101000G-2-PG Four loop system with one 250-point loop Installed.230v,gray door,Portuguese. 101000G-2-SP Four loop system with one 250-point loop installed.230v,gray door,Spanish. SAF,1 r trO:LIF N VANIAGEMLI41 101000T-b.-A- Four loop system,.one 250-point loop installed.110v,gray door,LED strips,Canada. 101050G6 Four loop system,one 250-point lowinstalled,110vt_gray door,with dialer. Contact us 101000G-F Four loop systerNone 250-point loop.11 ikgray door,_LED strips,FrenchCanada. Phone: 800-855-4497(Option 4) 101000G-PG Four loop_stem wHil one 250-point loop_Installed.110yl,grm door,Portuguese. Email: eoWards.fire@carriercom IO1000G-SP Four looseystem with one 250-point loopinstalled.110v„aey 0_121:2r,Swish. Website: edwardsfiresafetYcorn 101000R loop sotet,n;virh one 250-poini loop Installed.110v,red door 8985 Town Center Pkwy A 101000R-2 Four low system with one 250-point loo installed.230v,red door. Bradenton,FL 34202 10100ORD Four looRwatem,one 250-point loop installed.110v,red door,with dialer. SA-TRIM2 i01000 Rush mount trim,black. 02021 Carrier All Rights Reserved. 1064 Fire Alarm Systems 1064G _ One loop system with one 64-_point loop installed.110v,,g_ray door. I064G-2 One loop sys-tem with one 64-point loop installed.230v,_ ay door. 1064G-2-PG One loop_system with one 64-point loop installed.230v,grAdoor,Portuguese. 108146-2-SP One loopffstem with one 64-point loop Installed.230v,gray door.Spanish. 1064GD One low system,one 64-point loop Installed.110v,gray door,with dialer. - I064GL One loop system,one 64-point loopinstalled.110v,gray door,English Canada. I064GL-F One loop_wsterri,one 64-point km2 installed. 110vt_grN door,French Canada. I064G-PG One loop system with one 64_7point loop installed.110v,gay door,Portuguese. I064G-SP _ One looigstern with one 64_7point loop installed.110v,kw door;, 2aNah. 1064R One loop system with one 64:Lxi1nt loop installed.110v,red door I064R-2 One k2op system with one 847a:int loop installed.230N,red door. I064RD One loopgstem,one 134-point loop installed. 110v,red door,with dialer. SA-TRIM1 1064 Rush mount trim,black Option Cards 10-SDC1 Expansion module,one 250-device loop. 10-SDC2 Expansion module,two 250-device loo ,500 devices total.For i01000 RZ116-2 Remote Zone Interface Module.16 Class B ICCs,2 Class B Output Includes bracket. SA-DACT Dual Line Dialer/Modem,supports Contact ID,mounts in cabinet on basekkate. SA-232 RS-232 Serial Port for connection to printers&computes,mounts in cabinet. SA-ETH Ethernet Port,IP Communicator,mounts in cabinet on base plate. SA-CLA Class A adapter module.Provides Class A capacity on NACs.Mounts in cabinet on rnain board.1064 wstems ony. SA-FS13 Held Server Bridge for connection to 3rd Party Building Management Systems. Supports BACnet and Modbus protocols.Mounts in the MFCA cabinet using the FSB-BRKT2 mounting plate.See separate SA-FSB datasheet E85010-0156 for additional information. SA-USB RS-232 Serial port for connection to printers&computers,mounts in cabinet. D16L-10-2 LED Annunciator module,16 X 2-LED zones(4 programmable for sup). Mounts in cabinet to right of I_CD display for zones 17-32.For 101000 D16L-i0-1 LED Annunciator module,16 X 2-LED zones(4 programmable for sup). Mounts in cabinet to left of LCD diepkiy for zones 1-16.For i01000 only._ D6RY-i0-2 Canada only:LED Annunciator module,two LEDs per zone,16 zones(4 alarm only, 8 supervisory only,4 alarm or supervisory).Mounts in cabinet.For i01000 only. D8RY-10-1 Canada only:LED Annunciator module,two LEDs per zone,16 zones(4 alarm only, __ 8 swervisory_onty,4 alarm or supervisory).Mounts in cabinet For i01000 only. Accessories CTM City Tie Module.2-gang.Connection to a local energy fire alarm box. MFC-A Multifunction Fire Cabinet,8 x 14'x 3.5"-red. SIGA-REL Releasing Module PT-1S System Printer BC-1 Battery Cabinet.14.0'x 1825'x 7.25.Holds two 12V24A batteries. BC-1R Battery Cabinet-Red.14.0"x1825'x 725.Holds two 12V24A batteries. BC-1EQ Seismic hardening 19t for 10 series panels.Includes battery hardening for BC-1 enclosure and components to harden panel Internal components. Programming Tools i0-CU 10 S0008 configuration and ckajpostics 1 260097 RS232 cable,4 conductor.DB9 PC interface Page 8 of 8 E85001-0135 Issue 20 POWER„///%,..,. PS-12180 12 Volt 18.0 AH i Rechargeable Sealed Lead Acid Baftery We've Got The Power."" r g `,.''' ' . > . Features • Absorbent Glass Mat (AGM)technology for superior performance Sealed Re �� • Valve regulated, spill proof construction allows safe pOOVEB 5D# operation in any position �a FS'`'Y "` • Power/volume ratio yielding unrivaled energy density Rugged impact resistant ABS case and cover(UL94-HB) • Approved for transport by air. D.O.T., LA.T.A., F.A.A. and C.A.B. certified • U.L. recognized under file number MN 20845 Performance Specifications • F2-Quick disconnect F2 h..3.4- x8 tabs,0.250"x 0.032" T o j � 635 •,Tr- Nominal Voltage 12 volts(6 cells) -Mate with AMP.INC -L (�J 8 12 FASTON"250"series F-ass-I Nominal Capacity • NB2:Tin plated brass 20-hr. (900mA to 10.50 volts) 18.0 AH post with nut&bolt T1I + 10-hr. (1.7A to 10.50 volts) 17.0 AH connectors • T12-Threaded insert l Q 5-hr. (3.2A to 10.20 volts) 16.0 AH with 5mm stud Don 1-hr. (11.1A to 9.00 volts) 11.1 AH 15-min. (34.3A to 9.00 volts) 8.58 AH Physical Dimensions: in (mm) Approximate weight 12.60 lbs.(5.72 kg) --- T Energy Density(20-hr.rate) 1.53 W-h/in3(93.51 W-h/l) W Specific Energy(20-hr.rate) 17.14 W-h/Ib(37.79 W-h/kg) Flo o o la l 1_ Internal Resistance(approx.) 14 milliohms Max Discharge Current(7 Min.) 54.0 amperes I t I �_..4 I j ls1 i Max Short-Duration Discharge Current(10 Sec.) 180.0 amperes 1 Shelf Life(%of nominal capacity at 68°F(20°C)} `" 1 Month 97% HI H 3 Months Wert PSARIt0 WI ,Ala 0 It "�. 6 Months 83% Operating Temperature Range r L '1 Charge -4"F(-20C)t0122'F(50°C) Discharge -40°F(-40°C)to 140°F(60°C) L:7.13(181) W:3.00(76) H:6.59(167) HT:6.59(167) Case ABS Plastic Tolerances are+/-0_04 in.(+/-1mm)and+/-0.08 in.(+/-2mm)for Power-Sonic Chargers....PSC-122000A,124000A, 122000A-C,124000A-C height dimensions.All data subject to change without notice. To ensure safe and efficient operation always refer to the latest adder of our Technical Manual,as published on our webs"de:" www,power-sonic.COm a/i : 1 s , :, l ° - /N////:u/� I„�/,�/,/,sw/,f I/50N/C. P Shelf Life &Storage Discharge Characteristics 100 14.0 III I 1 1 1 I I I Charging is not Ambient Temperature 20°C(68°F necessary unless G 100%of capacity 13.0 F _ is required. -� ell 80 5.c Charging before, 12.0 __ use Is necessary m o (41°F)- to I recover full capacity. r 60 C T 11.0 -dTh C ml 0.90 e - - `- ro realare full I.e I C0 (104T)- 6stateT 18 0 2 4 6 8 10 12 14 16 18 20 Voltage Standing Period(Months) 6.0 III 36 1.2 2.4 6 12 24 36 481 2 4 6 810 20 4 0 Discharge Time vs. Discharge Current E, min --►I h 1 Discharge Time 20 10 10 \. Life Characteristics in Stand-By Use .c o Ambient Temperature 20°C(68�F) m 5 Final v 100 ' E Voltage 80 F 10.5V \\ A m 2 s. 10.2V m 60 u 1 \ t) Float Charging Voltage m \ `o_ 40 2.25-2.30 V/Cell G 9.6V \ . 20 30 m tY \ 0 E 9.0V k 0 1 2 3 4 10 N, 40°C(104°F) Years _L 20°C (68°F) 0°C (32°F) 5 8.1I Life Characteristics in Cyclic Use 0.90 1.8 3.6 9.0 18 36 120 Discharge Current(A) 100 iT L Charging 60 Cycle Applications:Limit initial current to 5.4A.Charge until battery voltage co (under charge)reaches 14.4 to 14.7 volts at 68°F(20°C).Hold at 14.4 to 14.7 rj 60 Discharge Discharge Discharge volts until current drops to under 180mA.Battery is fully charged under these Depth 100% Depth sour Depth 30% conditions,and charger should be disconnected or switched to"float"voltage. • 40 I I e 1.Discharge Current 0.2C(Final Voltage LTV/Cell) "Float"or"Stand-Sy Service:Hold battery across constant voltage source of u• 20 2.Charge Current:0.1c I I I 13.5 to 13.8 volts continuously.When held at this voltage,the battery will seek its re 3.Ambient Temperature:20°C to 25°C(68°F to 77°F) own current level and maintain itself in a fully charged condition. 0 0 200 400 600 800 1000 1200 Note:Due to the self-discharge characteristics of this type of battery,it is Number of Cycles imperative that they be charged within 6 months of storage,otherwise permanent loss of capacity might occur as a result of sulfation. Chargers Further Information Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to our website www.power-sonic.corn for a complete range of useful Please refer to the Charger Selection Guide in our specification sheets for"CSerieS downloads,such as product catalogs,material safety data sheets(MSDS),ISO Switch Mode Chargers"and"Transformer Type A and F Series".Please contact our certification,etc.. Technical department for adviceif you have difficulty in locating suitable models. Contact Information www.power•sonic.com DOMESTIC SALES CUSTOMER SERVICE TECHNICAL SUPPORT INTERNATIONAL SALES Tel:+1-619-661-2020 Tel:+1-619-661-2030 Tel:+1-619-661-2020 Tel:+1-650-364-5001 Fax+1-619-661-3650 Fax+1-619b61-3648 Fax+1-619-661-3648 Fax+1-650-366-3662 supportopower-sonic.com intemational-sales@praver-aortic.com CORPORATE OFFICE• 7550 Panasonic Way•San Diego,CA 92154• USA•Tel:+1-619-661-2020 • Fax:+1-619-661-3650 MU iu 01012 Parer-Seek Cremation.MI fights essered.Nha orris,oaths pmpe9'°r their"Imdia ewwe. Annunciation bWARDB i' , t 1 liiC;ii jai „n; i ' Fr^F, ! A-Series RemoteF -- 0 A'snn I 0 Annunciators im Cnadei Fnsp RLCD, RLCD-C, RLED, RLED-C, ; L C , *papa some RLED24, GCI Low L9LnpTesI (� j FDNY C ® CAA 6020 7120-1657: Overview Features coaso6r 0254 s3424 EDWARDS R-Series Annunciators are high-performance remote • LCD models feature large 4 x 20 character backlit LCD display annunciators that provide status indication and common controls • LED models provide 16 pairs of LEDs for zone annunciation for compatible fire alarm control panels, including i0-Series small analog fire alarm systems.This family of annunciators offers LCD • Available expander extends capability with 24 pairs of LEDs or LED annunciation. Models are available with and without corn- • Up to two expanders may be wired to each annunciator mon controls. • Status LEDs and internal buzzer standard on all models There are three R-Series annunciator models, plus an LED-based expander. Up to two expanders can be connected to any annun- • Common controls available for LED and LCD display models ciator.The expander includes 24 pairs of LEDs that extend the • Available keyswitch for disabling common controls capabilities of any of the annunciators. • Standard 4-inch square electrical box mounting All annunciator models include status LEDs and an internal buzzer. • Class B or Class A RS485 wiring standard Two models have an LCD text display,and one has 16 pairs of LEDs for zone annunciation. LCD models feature a large back-lit, • One-,two-,and three-position enclosures available four by twenty character per line,super-twist liquid crystal display. • Graphic Annunciator interface, includes common control, indi- R-Series annunciators and expanders are mounted on a standard cators and 32 LEDS 4-inch square electrical box, using the included mounting ring. • No programing required,set the address and unit receives all They can also be surface mounted in locking steel enclosures. information from panel Three different enclosures are available. A keyswitch and graphic annunciator interface is available for R-Series annunciator applications.The keyswitch enables or dis- ables common controls.The graphic annunciator interface cards supports 32 LEDs and 16 switches on the graphic panel display. Page 1 of 4 E85005-0128 Issue 1.1 Application Annunciator Wiring R-Series annunciators communicate with the FACP on the RS-485 Annunciator,Class A data riser.This can be configured for Class A or Class B commu- FADPunciator Annunciator nication.Annunciators do not provide ground fault isolation. 13s485 0 CH„(+)IN 0 c,n(,)IN These annunciators are stand-alone units that can be powered by 0H1' m--i I 0`H1(-tip 0`HI(-)IN CHI- 0 9ae el our 0CH,MOUT the FACP or by an approved power supply. D,42, 0 9 CAN(-)OUT 0 CHI(-)olrr \ CH2- 0--i I 0cH2(+)W 0CH2(+)IN _ LISTED24VDC 9 (')� 0 (+) OUT - I n.. $ - r...� SUPPLY 9 o2HOUT 0 CH2(-)OUT iI �� .^�° 24 VDC•0 02N01N 024V MIN C/... $(-- v� ..., 24VDC-0 0 2NHM -0 24V(-)IN ®®l� GJ ar . ggf abpru.u,,. @ 24V l+l OUT 0 24V(+)OUT - ., 1 81 ;.,• 92NHOM 024V(-)OUT N ' W e u `\ N 1l t ll \ GROUND 4 • 0 GROUND RICO-C //J�7 (�\\ RIF0.0 Annunciator,Class B f ^ram—lr— _' FRCP Annunciator Annunciator t�A _„ iet.--gl �,�,-^ r 11 g� RSd35 0 CHIcm(+)IN 0 CHI TN IN t 0 cm(-)N 0 CH1(-)IN ®®® .1 01 gl .. CHI Q CHI(+)OUT 04N(+)OUT . "^— ..///� C_s .$I - 0 TO CHI Hour 0ClnHOUT �� e l� K __- �� a 0CH2 NIIN 0CH2(-)IN (( 0 CH2 H IN 0 CHZ(-)IN RLCD RIE024 LISTED 20 WC 0CN2(+)OUT 0CH2(')OUT SUPPLY 0CH2(-)OUT 0CH2(-)OUT Features by RLCD RLCD-C RLED-C RLED2424 VDC+0 024v()IN 024V(+)IN model 2/VDC-0 0240-)IN 02 11-)w ✓ ✓ ✓ _ ._ . _ 924V(.9 OUT - 024y(+)OUT AcWSilence ✓ ✓ ✓ - 4'"v(-)OUT 02°v(-)OUT Fire Alarm ✓ ✓ 0 GROUND 1 0 GROUND Supervisory ✓ I ✓ _. — I I I Ground Fault - Trouble _ ✓ '� ✓ Controls Enabled -. / ✓ ✓ - Expander AcWSilence I ✓ I - _____..___--____._ -____ __-. __..__ _ -._ Annunciator First Expander Sawnd Expander Reset ✓ ✓ - ___ OUT IN OUT IN OUT Signal Silence 1 ._'r v(-10 0VH v(0- -0VH YH0 Drill ✓ _ —_-i__._---_-.._—_ V1H0 0V(41 VN)0 --(Dv(*) vl+10 -- _ Lamp Test ✓ ✓ ✓ - F0 OF FO• QF P CD -__ E0 0E E0- -.0 E E0 LCD Display ✓ I - - Zone Active LEDs - 16' 24" 00 0C C0- 0C CO Zone Trouble LEDs -__ 16_—-_.—.- —_. _ e 0 0 e e 0 0 B B 0 'zones 13-16 maybe selected as Supervisory on 1064 A 0 0 A A 0- 0 A A 0 -zones 13-16 and 29-32 maybe selected as Supervisory on i01000 __- Graphic Annunciator Interface The GCI Graphic Annunciator Driver is an interface card that Remote Ke switch connects the fire alarm control panel to the display panel of an Key switch graphic annunciator. Annunciator LSRARK The annunciator card supports 32 LEDs and 16 switches on the KEYSWITCHI-)0 0 re1-1 graphic panel display. It includes status LEDs and an internal BKEYSWITCH(+)0 0TBi2 buzzer. LP? The graphic interface is supplied with snap track mounting. It is Keyswitch Specifications '�Ir attached to a plastic mounting rail that requires two EIA panels. Maximum 5 Vdc voltage The annunciator communicates with the FACP on the RS-485 Maximum 200 niA ' data riser.This can be configured for Class A or Class B commu- current nication.The annunciator does not provide ground fault isolation. Mounting 2-1/2 in(64 mm) l It is a stand-alone unit that can be powered by the FACP or by an deep 1-gang box Pk, I �' approved power supply. P -termination Screw terminals 90 �I n--_ Maximum —. um 12 AWG Alarm current Graphic Annunciator Interface mAA at 24 Vdc(with 36 LEDs ON) _ wirect (2.5 mm sq) -Contact Normally open / Standby current 36 mA at 24 Vdc(with no LEDs ON) configuration Maximum current 10 mA per LED 11, a - o Page 2 of 4 E85005-0128 Issue 1.1 Annunciator Connections Annunciator Mounting Annunciator ANNUNCIATOR RS-485 RISER Mounting slot • ` A r A i • DIP switch ) II- .8 Remote keyswitch RStermina s terminals _—— Expandercable __ O Power terminals °" terminals —��._�� O Communication n • Lw '' - _f LEDs • — ® • 0 Expander 0 Mounting slat • Q .. .` C ] r EXPANDER CABLE Expander cable Expander cable ) terminals l terminals • ® • O DIP switch settings O itrt Switch Description and values a e- -- O Si to S5 The annunciatorr network address(in binary). Network The factory setting is for address 2. address Examples: 10000=1 01000=211000=3 00100=4 J S6 Network OFF=9600 baud(factory default setting) E ) -11il_ baud rate ON=38,400 baud S7 to S8 Not used MOUNTING RING ,--__-- _ _---- ---__.....__----------.,--— EXPANDER ELECTRICAL BOX Annunciator Enclosures The RA Remote Annunciator Enclosures provide secure,surface mounted protection for annunciators and extenders. Each con- sists of a back plate, hinged cover,and key lock. i' •The enclosures are 16-gauge welded steel with a white, painted I I 6.0 in finish.Each enclosure includes a security lock and two keys.The I I 15.2 cm two-and three-position enclosures have wiring channels for cor- i i• H rest routing of interconnections. The enclosures attach to a standard electrical box, and provide a I �1 ii mounting lip that takes the place of the integral mounting ring sup- ,0 r U plied with the annunciators and expanders. j — 0.9 in 2.3 cm 1 ) 1 , ,� 4� - /0 t IIIII RA-ENC3 .L.—j 9.5 r 24.1 cm I L. 2.0 in 9.8in r 5.1cm j 24.9 cm Dimensions(H x W x D) RA-ENC1 6.3 x 9.8 x 2.0 in(18.0 x 24.9 x 5.1 cm) RA-ENC2 12.0 x 9.8 x 2.0 in(30.5 x 24.9 x 5.1 cm) RA-ENC3 17.7 x 9.8 x 2.0 in(45.0 x 24.9 x 5.1 cm) w" Note:Allow approximately 2 Inches(50 cm)clearance on both sides of the enclosure,to permit inserting and removing the key,and opening the door RA-ENC2 through 90 degrees. Page 9 of 4 E85005-0128 Issue 1.1 Specifications �jw1vV ROS RLCD-C RLCD RLED-C RLED24 \`►G is Y Y l+U'S �7 Operating voltage 24 VDC,continuous. sa err s iNaoENr vANnuE,ncra Standby current 99 mA 98 mA 28 mA 6 mA Alarm current 115 mA 113 mA 62 mA 34 mA Contact us RS-485 communications Class A or Class B,9600 baud Phone: 800-655-4497(Option 4) Email: edwards.fire?carrier.com Data wiring 18 to 14 AWG(1.0 to 2.5 sq mm)twisted pair(6 twists per foot Website: edwardsfiresafetv.com minimum).Maximum wire run is 4,000 ft.(1,219 m) Remote key switch circuit 5 VDC at 1 mA,power-limited,unsupervised 8985 Town Center Pkwy Bradenton,FL 34202 Ground fault impedance 0 Power wiring 18 to 14 AWG(1.0 to 2.5 sq.mm) ®2020 carder All rights reserved. Display area 4 lines of 20 characters each Dimensions(H x W x D) 5-5/8 x 8-1/2 x 1-1/2 in.(14.3 x 21.4 x 3.8 cm) -__ ___ _— Mounting North American 4-inch square electrical box or listed enclosure Agency Listing UL,ULC Operating environment Temperature:32 to 120°F(0 to 49°C)Humidity:0 to 93%RH, noncondensing at 90°F(32°C) — — — Ordering Information Part Description Remote Annunciators RLCD LCD text annunciator without common controls.English — _ RLCD-R LCD text annunciator without common controls.English.Red. RLCDF LCD text annunciator without common controls.French. RLCD-C LCD text annunciator with common controls.English. RLCD-CR LCD text annunciator with common controls.English.Red. RLCD-CF LCD text annunciator with common controls.French, BLED-C 16-pair LED zone annunciator with common controls.English. BLED-CR 16-pair LED zone annunciator with common controls.English.Red. RLED-CF 16-pair LED zone annunciator with common controls.French. Remote Expanders RLED24 24-pair LED zone expander with expander cable and zone card insert. RLED24R 24-pair LED zone expander with expander cable and zone card insert.Red. Enclosures RA-ENC1 One-position enclosure for Remote Annunciator. RA-ENC2 Two-position enclosure for Remote Annunciator and one Remote Expander, including one interconnection cable. RA-ENC3 Three-position enclosure for Remote Annunciator and two Remote Expanders, including two interconnection cables. LSRA-SB Surface Mount Box-for single R Series annunciator. Graphic Annunciator Drivers GCI Graphic Annunciator Driver,provides outputs for common indicators and 32 alarm/ supv zones as well as inputs for common switches.Provided with a snap track for mounting in custom graphic enclosures. Accessories --- RKEY Remote key switch on plate for enabling or disabling common controls(Lock/ Unlock). 27193-16 Electrical box,surface mount,white,single-gang,for RKEY. E85005-0128 Page 4 of 4 Issue 1.1 1Power Supplies and Accessories EST 1111'1 Life Safety d Communications � 11111 1i�q Remote Booster '��''' ' ii ,III!, a Power Supplies <i> BPS6A, BPS1 OA • MEA 476-91-E Vol 13 0 S3424 0') imol 7300-1657', 0229 Overview Standard Features The Booster Power Supply(BPS)is a UL 864, 9th Edition listed • Allows for reliable filtered and regulated power to be installed power supply. It is a 24 Vdc filtered-regulated,and supervised where needed unit that can easily be configured to provide additional notification • Cost effective system expansion appliance circuits(NACs)or auxiliary power for Mass Notification/ Emergency Communication(MNEC),as well as life safety,security, • Provides for Genesis and Enhanced Integrity notification ap- and access control applications, pliance synchronization • The BPS contains the circuitry to monitor and charge internal Supports coded output operation • or external batteries. Its steel enclosure has room for up to two or restoring overcurrent protection 10 ampere-hour batteries.For access control-only applications, • Multiple signal rates the BPS can support batteries totaling up to 65 ampere-hours in • Can be cascaded or controlled independently an external enclosure.The BPS has four Class B(convertible to • Fasy field configuration two Class A)NACs.These can be activated in one or two groups from the BPS's unique dual input circuits. • On-board diagnostic LEDs identify wiring or internal faults The BPS is available in 6.5 or 10 ampere models. Each output • Standard Edwards keyed lockable steel cabinet with remov- able door circuit has a capacity of three amperes;total current draw cannot exceed the unit's rating. • 110 and 230 Vac models available • The BPS meets current UL requirements and is listed under the Accommodates 18 to 12 AWG wire sizes following standards: • Optional tamper switch Standard(CCN) Description • Dual battery charging rates UL884 9th edition(UOx7gFre warm Systems UL636(ANE,LIEFIX7) 4 warn Units and systems • Optional earthquake hardening:OSHPD seismic pre approval uueo9(AOTX,aot7) Loral Sumter darn;units and systems for component Importance Factor 1.5 uL294(a_w u BO(7( Access Controlbystems ------.. UL365(AP.4W,APAW7) Porte Station Connected Burglar Alarm Units and Systems UL1076(APOU,APaU7) Proprietary Burglar Hann System Units UL1610(AMC)Q Central Sleben Alarm Unit ULC-5527 ruo)og Control Units,Fire Alarm(Canada ULGS303(AOTX7) Local Burglar Alain Units and Systems(Canada) C22.2 No i 205 _._ Signaling Equipment(Canada)-- Page 1 of 4 85005-0125 Issue 5 Application Dimensions The BPS provides additional power and circuits for notification ap- f pliances and other 24 Vdc loads. It is listed for indoor dry locations Q Q and can easily be installed where needed. 0 Top View Fault conditions are indicated on the on-board diagnostic LEDs, opening the BPS input sense circuit and the trouble relay(If D2 4 D3 ► programmed).While this provides indication to the host system, ) i the BPS can still be activated upon command.A separate AC p�—D4--►0 Fail contact is available on the BPS circuit board,which can be . programmed for trouble or AC Fail.There are seven on-board Front View diagnostic LEDs:one for each MAC fault, one for battery fault, one 0 for ground fault,and one for AC power. . The unique dual-input activation circuits of the BPS can be acti- vated by any voltage from 6 to 45 VDC(filtered-regulated)or 11 D1 • D6 to 33 Vdc(full-wave rectified, unfiltered).The first input circuit can • u) be configured to activate 1-4 of the four possible outputs.The All m • second input circuit can be configured to control circuits 3 and 4. for All knockouts m When outputs are configured for auxiliary operation,these circuits 3/4(1 in c conduit f can be configured to stay on or automatically deactivate 30 sec- ° onds after AC power is lost.This feature makes these circuits ideal for door holder applications.The BPS also has a separate 200 mA 24 Vdc output that can be used to power internal activation � .... • "i.=... modules. D1 D2 D3 D4 D5 D6 BPS NACs can be configured for a 3-3-3 temporal or continuous output.California temporal rate outputs are also available on cer- 17.0 in 3.5 in 13.0 in 6.5 in 3.375 in 12.0 in taro models.This makes the BPS ideal for applications requiring (43.2 cm) (8.9 cm) (33.0 cm) (16.5 cm) (8.6 cm) (30.4 cm) signaling rates that are not available from the main system. In addition to the internally generated signal rates,the BPS can also be configured to follow the coded signal rate of the main Wire routing Power-limited system NACs.This allows for the seamless expansion of existing wiring area NACs. The BPS enclosure has mounting brackets for up to three Signa- ■ -■ ture modules to the right of the circuit board. - 0 ° ■ Engineering Specification 1111111111Illi 11. '7—.. Supply,where needed, Edwards BPS Series Booster Power Sup- °0° plies(BPS)that are interconnected to and supervised by the main I i� : —■ system.The BPS shall function as a stand-alone auxiliary power •g (31 ■ supply with its own fully-supervised battery compliment.The BPS •""0 — • II battery compliment shall be sized to match the requirements of Route AC supply - - �u-. _ °o the main system.The BPS shall be capable of supervising and through these — _ — charging batteries having the capacity of 24 ampere-hours for knockouts only • Ali • Mass Notification/Emergency Communication(MNEC),life safety (Nonpower-limited Battery wiring(nonpower and security applications,and the capacity of 65 ampere hours for and supervised) limited and supervised) access control applications. «The BPS shall be capable of installation for a seismic corn- Battery Battery ponent Importance Factor of 1.5.»The BPS shall provide a minimum of four independent,fully supervised Class B circuits - that can be field configurable for notification appliance circuits or auxiliary 24 Vdc power circuits. BPS NACs shall be convertible to a minimum of two Class A NACs.Each BPS output circuit shall Notes be rated at 3 amperes at 24 Vdc. Each output circuit shall be 1. Maintain 114-inch(6 mm)spacing between power-Milted and no"power-f""red wising or use type FPL,FPLR,or FPLP cable per NEC. provided with automatically restoring overcurrent protection.The [2] Power-Imited and supervised when not configured as auxiary power.Non- BPS shall be operable from the main system NAC and/or Edwards supervised when configured as auuaiary power. Signature Series control modules. BPS NACs shall be configurable pit source must be power-limited.source determines supervision, for continuous,3-3-3 temporal or optionally,California rate.Fault 4. When ustig larger batteries,make sure to position the battery terminals towads conditions on the BPS shall not impede operation of main sys- the door. tern NAC.The BPS shall be provided with grand fault detection circuitry and a separate AC fail relay. 85005-0125 Page 2 014 Issue 5 Typical Wiring Single or cascaded booster NAC Circuit >To next signaling NAC Circuit device,booster,or anywhere on a notification appliance circuit `/ )EOL resistor ExistingNAC end-of-line resistors are not required to be g' vg' )NAC output#1 q Fire Alarm = _ >NAC output#2 installed at the booster's terminals.This allows multiple Control Panel - isr >NAC output#3 boosters to be driven from a single NAC circuit without the .8 .8 ) NAC output#4 need for special configurations. E. S Booster Power Supply Configuring the Booster for Multiple CC1(S) modules using the AC Power Fail delay operation* BPS's sense inputs 7B1 Notification appliance circuit(NAC) TB1 Notification appliance circuit(NAC) AUXNAC1/+ f U li 15d AU NAC1/ +I�] �� listed AUX1 - I� Sall EOL to k(] AUX1 -[o.,]� ©4 ©� EOL 15 KW NAC2/ +a Notification appliance circuit(NAC) AUX2 -Ubl Notification appliance circuit(NAC ) - r PP ( ) NAAUX3 3/ + UL listed 3/ -1[A UL listed AU - �1 = = EOL 15 kR AUX3 -Iq.,]� © EM EOL 15 KW NAC4/ + (S31 NAC4/ +I`-] AUX4 -31 AUX4 -EA 200 mAAUX + 200 mAAUX EA — Continuous Continuous m IF.,]� IN eA + IN Fill Sense i COM IN Sense 1 COM [o7Mill r OUT OUT II-]fit im EOL 47 K iiikIN I IN Ebl " ' Sense 2 COM ME EOL 47 K2 1 1e s [ I Sense 2 COM Elt�!! EOL—� OUT CC1(S)module[1][3] OUT LI -' I+ c Trouble COM a 7 6 5 o a3 2 1 Trouble COM [�] � E"i'�� l MIME'L�� NCV- ;iiis ,Jzi t; NC Ill to' o. TB?" BI O I + TB2LC odule CC1(S)module C• • Data in from Data out to o 4321 43previous device next devicel� l,� l; a ,L M moaiulg[4] or Signature kill. ' ' 3 ' controller Data in from previous Data out to "The Booster supports AC Power fail delay [3] device or Signature y next device of three hours via its trouble contact when controller dip switch SW2-6 is on.All other troubles are reported to supervising module or panel without delay via Sense inputs. Security and access BPS Tel 24 V 12 V NAC1/+I,i Security Security EOL AUX1 -IFA -■ 24DC12 ■�� device device monitoring NAC2/+Ire] device AUX2 -IUD] NAC31+I��l AUX3 -IE.4 NAC4/+FM AUX4 -VI Control panel BPS[1] Card reader Card reader Card reader + — controller controller controller T �♦ ♦♦ ]—� ♦ — ♦ — I To next device [7 j Disable the BPS's ground fault jumper(JP3) or end ' Page 3 of 4 Issue 5 f Specifications Model 6.5 amp Booster 10 amp Booster §r ( ,,,, S..:« ., .;„,. ;; AC Line Voltage 120VAC or 220-240VAC 50/60Hz 120VAC or 220-240VAC 50/60Hz . - 390 watts 580 watts Notification Appliance 3.0A max.per circuit it 24Vdc 3.0A max.per circuit 0 24Vdc Contact us... Circuit Ratings nominal 6.5A max total all NACs nominal 10A max total all NACs Email: edwards.fire®fs.utc.com Web: www.est-fire.com Trouble Relay 2 Amps®30Vdc Auxiliary OutputsFour configurable outputs replace NACs 1,2,3 or 4. as stalls y EST is an EDWARDS brand. outputs and 200 mA dedicated auxiliary.(See note 2.) 1016 Corporate Park Drive Mebane,NC 27302 Input Current 3mA 0 12Vdc,BmA ft 24Vdc (from an existing NAC)_ - -- - In Canada,contact Chubb Edwards... - Booster Internal 70mA+35 mA for each circuit set to AUX Email: inquiriesachubbedwards.com Supervjgpry Current Web: www.cbubbedwards.com Booster Internal Alarm 270mA 0 2013 UTC Fire&Security Americas Current Corporation,Inc.All rights reserved. Specifications subject to change Signature Mounting Accomodates three two-gang modules. without notice.Edwards is part of UTC Space Climate,Controls&Security,a unit of Maximum Battery Size 10 Amp Hours(2 of 12V10A)in cabinet up to 24 Amp hours with ex- United Technologies Corporation. ternal battery cabinet for fire and security applications;up to 65 Amp hours for any^-rrcc control applications in external battery box. Terminal Wire Gauge 18-12 AWG Relative Humidity 0 to 93%non condensing 0 32°C Temperature Rating 32°to 120°F(0°to 49°C) NAC Wiring Styles Class A or Class B_--- Output Signal Rates Continuous,California rate,3-3-3 temporal, or follow Installed panel's NAC.(See note 1.) Ground Fault Detection Enable or Disable via jumper Agency Listings UL,ULC,CSFM 1. Model BPS'CAA provides selection for California rate,In place of temporal. 2. Maximum of 8 Amps can be used for auxiliary output. Ordering Information Catalog Description Shipping Number Wt'lb(kg) BPSS A 6.5 Amp Booster Power Supply 13(5.9) BPS6AC 6.5 Amp Booster Power Supply(ULC) 13(5.9) BPS6A/230 6.5 Amp Booster Power Supply(220V) 13(5.9) BPS6CAA 6.5 Amp Booster Power Supply with California rate 13(5.9) - - BP51 0A 10 Amp Booster Power Soppy 13(5.9)_ _-- BPS1OAC 10 Amp Booster Power Soppy(ULC) - _ - -- _ ---- 13(5.9) BPS10A/230.. 10 Amp Booster Power Supply(220V) 13(5.9) BPSI OCAA 10 Amp Booster Power Supply with California rate 13(5.9) 1. Requires installation of sepa- rate battery cabinet. Related Equipment 12V6A5 7.2 AmpHour Batt two required 3. 2. BPS supports batteries greater -_-... 4(1.6) than 24 Amp hours for access --_ - -.-.. only.. 12V1 OA 1 10 0 Amp 9.5(4.3) control applications on mp Hour Battery,two required --_-- _ 3. For earthquake anchorage. 3-TAMP Tamper switch ----- including detailed mounting BC-1 EQ Seismic Kit for BC-1. Order BC-1 separately.See note 3. _ -_--- weights and center of gravity BPSCQ Seismic kit for BPS6A or BPS10 Booster Power Supplies.See detail,refer to Seismic Appica- note 3 tbn Guide 3101878. Approval ----.___--___.-_-_----- ----- - ..._. -- 58(26.4) of panel anchorage to site 1 Battery Cam(up to 2-40 Amp Hotx Batteries) structure may require local BC-2 _ Battery Cabinet(up to 2-17 Amp Hour Batteries) AHJ.structural or civil engineer 12V17A 18 Amp Hour Battery,two required(see note 1) 13(5.9) review. 12V24A 24 Amp Hour Battery,two required(see note 1) 20(9.0 7) 12V40A 40 Amp Hour Battery,two required(see notes 1,2) 32(14.5) 12V50A V50A 50 Amp Hour Battery,two required(see notes 1,2) 40(18.14) 12V65A 65 Amp Hour Battery,two required(see notes 1,2) 49(222) 85005-0125 Page 4 of 4 ISSUe 5 ._.... Ida POWER SsoN/c FEr W y CL _ ppWER SONIC fy..z.,.H r r 1 mttn o ' AI r I r Mp47EL i, I tow, I tttt ttrtt ,_i PS-1 21 0 0 H FEATURES 12Y 10.5 AH @ 20-hr. • Absorbent Glass Mat(AGM)technology for 12Y 10.0 AH @ 10 hr. superior performance • Valve regulated,maintenance free spill proof construction • Power/volume ratio yielding excellent energy density • Rugged vibration and impact resistant ABS case F2: Quick disconnect tabs, and cover 0.250"x 0.032"-Mate with • Gas recombination technology AMP INC FASTON"250"series • 5 year design life —•i t4-2.5 ..,40 APPROVALS -+i • j • Approved for transport by air. D.O.T.,I.A.T.A.,F.A.A. 1 7.B E and C.A.B.certified -+53 f • U.L.recognized Torque-Not Applicable • IS09001:2015-Quality management systems DIMENSIONS:inch(mm) PERFORMANCE SPECIFICATIONS L: 5.94(151) Nominal Voltage 12 volts(6 cells) aEl W: 2.56(65) e H. 4.40(112) Nominal Capacity W HT:4.67(118) Tolerances ere+/-o.04In. 20-hr. (525mA to 10.50 volts) 10.50 AH a (+/-1mm)and+/-0Aa in 10-hr. (1.00A to 10.50 volts) 10.00 AH an (+/-2mm)for height 5-hr. (1.87A to 10.20 volts) 9.35 AH -_ dimensions.All date subject 1-hr. (6.82A to 9.00 volts) 6.82 AH to change without notice. Approximate Weight 7.23 lbs.(3.26 kg) I I I-I , Internal Resistance(approx.) 12.0 milliohms # ""°="w" . Max Short-Duration Discharge Current(10 Sec.) 105.0 amperes PDWERP HT H Shelf Life(%of nominal capacity at 68'F(20'C) 1.1009.R'121aeN Illt ,..". 1 Month 97% 3 Month 91% t t°..„-- NY 4 6 Month 83% iI Operating Temperature Range r L , Charge 5°F(-15°C)to 122°F(50°C) l Discharge -4°F(-20°C)to 140°F(60-C) CORPORATE HEADQUARTERS POWER-SONIC EUROPE LIMITED ! Case ABS Plastic (USA AND INFEAMAIN)NAL EXCLUDING EYEA) (EMFA-BAWL MIDDLE FAST AND AFRICA) Power-Sonic Corporation 3 Buckingham Square, ; Power Sonic Chargers PSC-122000A-C 7550 Panasonic Way,San Diego, Hurricane Way,Wickford, PSC-122000-PC California 92154 - Essex SS11 8YU T: +1(619)661 2020 T: +44(0)1266 560686 F: +1(619)661 3650 F: +44(0)1268 560902 E: customer-service@power-sanic.com E: salesEMEA@power-sonic.com 72 To ensure safe end elfichm opentlon steers Stale the latest edition of ow TaMiml Manuel,ea published on our webalte. ` u 0 2010.Power-onlc Corporation.Al rights reamed.At trademarks are the properly of their respective owners. pO.W•.er-sonic.co m '` MI date subject to change without notes.EBA.E r VI W POWER .SSDNIC y TRUSTED BATTERY SOLUTIONS a PS-12100H ,20;00011@ oar. �.,.. t. ... _ _ _,I. f„1ia Acid Battery Pr ._ fi et"1er i Purpose Series SHELF LIFE&STORAGE LIFE CHARACTERISTICS IN STAND-BY USE 100 paying Is not Ambient Temperature 20°C(68'F) necessary unless 100 l I I I 0 —"� 1 requir0%ofed cepad y o is requretl. 80 to 80 5°c Charging before K use h necessary 60 e (41°F)— to help recover o full[wady. Float Charging Voltage m 60 - 40 2,25-2.30 VlCell w `� 20 K 40°C 30°C 20°C •� 40 (104°F)-(86°F) (68°F) 0 0 1 2 3 4 5 te 01 I I I U Years 0 2 4 6 8 10 12 14 16 18 20 Standing Period(Months) CHARGING CHARGERS Cycle Applications:Apply constant voltage charge at Power Sonic offers a wide range of chargers suitable 2.35v/c-2.45v/c(14.1 - 14.7v for 12v Monobloc)at 20°C. for batteries with a variety of capacities. Initial charging current should be set at less than 0.25C Please refer to our website for more information on Amps.Switch to float charge to avoid overcharging. our switch mode and transformer type chargers. "Float"or"Stand-By"Service:Apply constant voltage Please contact our technical department for advice if charge of 2.25v/c-2.30v/c(13.5 to 13.8 volts for 12v you have difficulty in locating a suitable charger. Monobloc at 20°C.When held at this voltage,the battery will seek its own current level and maintain itself in a fully FURTHER INFORMATION charged condition. Please refer to our website www.power-sonic.com Temperature Compensation:Charging Voltage for both for a complete range of useful downloads,such as Cyclic and Standby applications should be regulated in product catalogs,material safety data sheets(MSDS), relation to ambient temperature.As temperature rises ISO certification,etc. charging voltage should be reduced to prevent overcharge and increased as temperature falls to avoid undercharge. For further charging information including temperature compensation factors,see Power Sonic Technical Manual/ Power Sonic Charger specifications. APPLICATIONS • General purpose • Medical ppWEpt .ONIC I • Emergency lighting • Fire and security 1a100 ri Y� MODEL PS°,,,r. CORPORATE HEADQUARTERS POWER-SONIC EUROPE LIMITED f f` ,'%�""'" -.1.,,6`pn"..t,I P (USA AND INTERNATiONAL(XCLUIIN8 ESIG) (SMEA-EUROPE MILE EAST ANB AFRICA) a+bacc p„aa Power-Sonic Corporation 3 Buckingham Square, 7550 Panasonic Way,San Diego, Hurricane Way,Wickford, California 92154 Essex SS11 8YQ T: +1(619)661 2020 T: +44(0)1268 560686 F: +1(619)661 3650 F: +44(0)1268 560902 E: customerservice@power-sonic.com E: salesEMEA@power-sonic.com - 7. To ensure safe and efficient opaet art always refer to the latest edion ulcer Technical Manuel.as published on DIM webaie. M c M //rr�a //�� ��yy�� C2018.Power-Sonic Corporation.All rights mewl_Al hedemarka aelhe property ofthelr respective owners. power-son•\aaVoNaN a All data subject to change without notice.EPC.E 77__ Intelligent Input-Ontnu, EST Life Safety & Communications Synchronization Output Module SIGA-CC1 S, MCC1 S �t-i of • • Patented 4,00 pL MEA 73%157: 0121 S3424 Overview Standard Features SIGA-CC1 S and MCC1 S Synchronization Output Modules are • Provides UL 1971-compliant auto-sync output for visual intelligent analog addressable devices that form part of EST's signals Signature line of products.The actual operation of the SIGA-CC1 S Use for connecting a supervised output circuit to a supervised and MCC1 S is determined by the"personality code"selected by 24 Vdc riser input and synchronizing multiple notification appli- the installer,which is downloaded to the module from the Signa- ance circuits. ture loop controller during system configuration. • Functions as an audible signal riser selector Depending on their assigned personality, Synchronization Output Use as a synch module or for connecting supervised 24 Vdc Modules may be used as a signal power riser selector to provide Audible/Visible signal circuits,or 25 and 70 VRMS Audio synchronization of fire alarm signals across multiple zones,or for Evacuation and Telephone circuits to their power inputs. connecting,upon command from the loop controller, supervised • Built-in ring-tone generator Class B signal or telephone circuits to their respective power When configured for telephone circuits,the SIGA-CC1 S gener- inputs.The power inputs may be polarized 24 Vdc to operate au- ates its own ring-tone signal,eliminating the need for a sepa- dible and visible signal appliances or 25 and 70 VRMS to operate rate ring-tone circuit. audio evacuation speakers and firefighter's telephones. • Automatic device mapping Signature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop. • Electronic addressing Programmable addresses are downloaded from the loop con- troller,a PC,or the SIGA-PRO Signature Program/Service Tool; there are no switches or dials to set. • Intelligent device with microprocessor All decisions are made at the module to allow lower com- munication speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties;twisted or shielded wire is not required. Page 1 of 4 85001-0543 Issue 3.1 Application Installation The SIGA-CC1S mounts to a standard North American two-gang The SIGA-CC1S:mounts to North American 2-1/2 inch(64 mm) electrical box,making it ideal for locations where only one module deep 2-gang boxes and 1-1/2 inch(38 mm)deep 4 inch square is required.Separate I/O and data loop connections are made to boxes with 2-gang covers and SIGA-MP mounting plates.The each module. terminals are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2) wire size. The SIGA-MCC1S is part of the UIO family of plug-in Signature Series modules. It functions identically to the SIGA-CC1 S, but , takes advantage of the modular flexibility and easy installation that O characterize all UIO modules.Two-and six-module UIO mother- O , boards are available.These can accommodate individual risers for o each on-board module,or risers that are shared by any combina- o i lion of its UIO modules.All wiring connections are made to termi �' - 1, 01 nal blocks on the motherboard. UIO assemblies may be mounted �'> ' �, in Edwards enclosures. ' ®O ` °' ti Personality Codes 'c%) The operation of the SIGA-CC1S is determined by their sub-type -' code or"Personality Code".The code is selected by the installer SIGA-MCC1S: mount the UlOxR motherboard inside a suitable depending upon the desired application and is downloaded from Edwards enclosure with screws and washers provided. Plug the the loop controller. module into any available position on the motherboard and secure Personality Code 5:Signal Power or Audio Evacuation (sin- the module to the motherboard with the captive screws.Wiring gle riser).Configures the module for use as a Class B Audible/ connections are made to the terminals on the motherboard(see Visible Signal power(24 Vdc polarized)or Audio Evacuation(25 wiring diagram). UlOxR motherboard terminals are suited for#12 or 70 VRMS) power selector.The ring-tone generator is disabled. to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. The output circuit is monitored for open or shorted wiring. If a Ulo Motherboard short exists,the control panel inhibits the activation of the audible/ 1 6-32 visible signal circuit to prevent connection to the power circuit. Self-tapping screws Personality Code 6:Telephone with ring-tone(single riser). — — Configures the module for use as a Telephone power selector. - -{1--44 When a telephone handset is plugged into its jack or lifted from its Plug-in(U10) o,Captivehook,the module generates its own Ring-Tone signal.A separate Module ring-tone circuit is not needed.The module sends this signal to -- i--'"l the control panel to indicate that an off-hook condition is present. — When the system operator responds to the call,the ring-tone RI Flat washers signal is disabled. _4--Cabinet or electrical enclosure Personality Code 25:Visual Signal Synchronization.This personality code configures the module to provide synchronization of fire alarm signals across multiple zones. It functions as a signal power(24 Vdc)riser selector.The output wiring is monitored for Electronic Addressing open circuits and short circuits.A short circuit will cause the fire The loop controller electronically addresses each module saving alarm control panel to inhibit the activation of the audible/visual valuable time during system commissioning.Setting complicated signal circuit so the riser is not connected to the wiring fault. switches or dials is not required. Each module has its own unique serial number stored in its"on-board memory".The loop control- ler identifies each device on the loop and assigns a"soft"address Warnings & Cautions to each serial number. If desired,the modilPs can be addressed using the SIGA-PRO Signature Program/Service Tool. This module will not operate without electrical power.As fires fre- quently cause power interruption,we suggest you discuss further safeguards with your fire protection specialist. Testing & Maintenance Edwards recommends that these modules be installed according The module's automatic self-diagnosis identifies when it is defec- to latest Fxugn zed edition of national and local fire alarm codes. Live and causes a trouble message.The user-friendly maintenance program shows the current state of each module and other perti- nent messages.Single modules may be turned off(de-activated) Compatibility temporarily from the control panel. These modules are part of EST's Signature Series intelligent Scheduled maintenance(Regular or Selected)for proper system processing and control platform.They am compatible with EST3, operation should Having Jurisdiction to om) Refert the requirements �t NFPAf the 72 and EST3X and 0Series control panels. ULC CAN/ULC 536 standards- 85001-0543 Page 2 of 4 Issue 3.1 Typical Wiring SIGA-CC1S(Standard Mount) SIGA-MCC1S(UIO Mount) Personality Typical Speaker Circuit Personality Typical Speaker Circuit Code 5 Cade 5 UUULC LMLd trWLC Listed 47KW EOL 1711W EOL Personality Typical Telephone Circuit Personality Typical Telephone Circuit Code 6 � Code6 C C ` aUULC Lila 77KWEEOL d OKA OWLC Listed 1TKW Eel Personality Enhanced Integrity and Genesis Devices Personality Enhanced Integrity and Genesis Devices Code 25 Code 25 lila: 41KW EOL� '3 - rit . UlN1[ueL 17kW Eel 1IE4 /--um series meK.ebeo.d _-_�I ,u a__l-I' re.ir / to 5 co Oao In 1 �, _ �� seer 1tM Out 'l r s ; 4 Data Z lee e } • 5 4 1 Graft t%j l M , 0 0 �v %' Data Out+ .0 rt tt u' u u u b��� -^ - 111r111 „_HI Riserout IA Green LED Women nu' To naRtdWice Rad LED Lectird "' iiii' Riser out I-I 11 J 4 Riser in l+l From contra panel I Data out Cot Riser lln_T+1J II �L_ + Riser lout Riser inl-I To next device or EOL resistor. Data out i-1 Data in(+1 From Syrwtur.Controker Data in I-I o'Frndaus Device Multiple CC1(S)modules using the BPS's sense inputs TB1 Notification appliance circuit(NAC) 1/ +[w] � ULlisted [r AUX1 - l�I©� I EOLI5KW NAC2/ +ICJ] AUX2 ..� Notification appliance circuit(NAC) NAC3/ +1E4 UL listed AUX3 —I.Pm © © EOL 15 KW NAC4/ +I��] AUX4 -I'b] 200 mAAUX in EA Continuous�Ii'Iflg IN[�b]�III Sense 1 COM IktI 1. OUT FA " EOL47 K ' IN[��lMill I Sense 2 COM bi' NE OUT FI EOL 47 K ' ' NO IrD1 + Trouble COM E] 1� ^iM111111 1NE_ 11111111 NC Ibi 1D' 1t •. 1376 I T CC1(S)module CC1(S)module : 04321 �i 04321 ItZ 1.1:,.. 1 21011, I;ssi:.'Pk .i..la +oMN—_off I (31 —__Page 3o14 85001-0543 Issue 3,1 Specifications Catalog Number SIGA-CC1S SIGA-MCC1S ., North American 214 Inch(64 mm) deep two-gang boxes and 11/2 Plugs into UIO2R,UIO6R or U106 Contact us... Mounting inch(38 mm)deep 4 inch square Motherboards Email: edwanrs.fire@fs.utc.com boxes with 2-gang covers and I Web: www.est-fire.com SIGA-MP mounting plates EST is an EDWARD9 brand. Description Synchronization Output Module lore a Corporate Park Drive Type Code 50(factory set) Mebane,NC 27302 Address RequirementsUses one module address In Canada,contact Chubb Edwards... Wiring Terminations Suitable for#12 to#18 AWG(2.5 mm2 to 0.75mm2) Email: inquiries@chubbedwards.com Operating Current Standby=223pA ww Web: w.chubbedwards.aom Activated=1001IA ®2013 UTC Fire 8 Security Americas Operating Voltage 152 to 19.95 Vdc(19 Vdc nominal) ._. _ _ . _- - -- Corporation,Inc.All rights reserved. i 24 Vdc=2 amps Specifications subject to change Output Rating 25 V Audio=50 watts without notice.Edwards is part of UTC j 70 V Audio=35 watts Climate.Controls aPolymer s Corporation.Security,a unit of United Technologies — -- Construction High Impact Engineering ._._ - — -- Operating:32°F to 120°F(0°C to 49°C) Storage and Operating Storage:-4°F to 140°F(-20°C to 60°C) Environment Humidity:0 to 93%RH LED Operation Green LED-Flashes when polled Red LED-Flashes when in Glenn/ active Compatibility Use with Signature Loop Controller under EST3 version 2.0 or higher Agency listings UL,ULC,CSFM, MEA Ordering Information Catalog Shipping Wt. ` Number Description lbs(kg) SIGA-CC1S Synchronization Output Module(Standard Mount)_UL/ULC listed 0.5(0.23) SIGA- Synchronization Output Module(UIO Mount)-ULJULC Listed 0.18(0.08) MCC1 S Related Equipment 27193-21 Surface Mount Box- 2-gang 27193-26 Surface Mount Box-White,2-gang 2(1.2) SIGA-U102R Universal Input-Output Module Board w/Riser Inputs 0.32(0.15) -Two Module Positions SIt;A-U106R Universal Input-Output Module Board w/Riser Inputs 0.62(0.28) -Six Module Positions SIGA-U106 Universal Input-Output Module Board-Six Module Positions 0.56(0.25) 235196P Bi-p 0.010olar Transient Protector .._ ----(0.05) MFC-A Multif notion Fire Cabinet-Red, 7.0(3.1) supports Signature Module Mounting Plates SIGA-MP1 Signature Module Mounting Plate,1 footprint -_- 1.5(0.70) SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5(0.23) SK3A-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02(046) 85001-0543 Page 4 014 Issue 3.1 Intelligent Initiating Devices Intelligent Smoke Detector wags mina, 000 swim waft SIGA-OSD /, .111 � M. � 4 1 w i UL Overview Standard Features The Signature Optica Series SIGA-OSD smoke detector • Multi-criteria optical smoke sensing technology brings advanced optical sensing technology to a practical • Wide 0.5 to 4.36%/ft.(1.6 to 13.6%/m)smoke obscuration design that increases efficiency, saves installation time, cuts costs,and extends life safety and property protection • Uses Existing Wiring capabilities.Continuous self-diagnostics ensure reliability • Integrated nuisance rejection reducing unwanted alarms over the long-haul,while environmental compensation helps from general cooking particulates reduce maintenance costs. • Listed to UL 268 7th edition Like all Signature Optica Series detectors,the SIGA-OSD is an intelligent device that gathers analog information from multiple • Automatic Device Mapping optical sensors, converting this data into digital signals. Utilizing • Up To 250 Total Signature Addresses Per Loop dual optical wavelengths combined with multiple detection angles, the SIGA-OSD differentiates particles that are not representative • Two Levels of Environmental Compensation of actual smoke. Particle data is input into digital filters which • Two Levels of Dirty Detector Warning feed a series of ratios removing signal patterns that are typical of nuisance sources,thus reducing unwanted alarms.To make an • Twenty Pre Alarm Settings alarm decision,the detector's on-board microprocessor measures • Five Sensitivity Settings and analyzes all optical sensor readings and compares this • Non-Volatile Memory information to preprogrammed settings. • Electronic Addressing • Automatic Day/Night Sensitivity Adjustment • Bicolor(Green/Red)Status LED • Standard, Relay, Fault Isolator,and Audible Mounting Basal • Sensor Markings Provide FaSy Testing Identification Note:Some features described here may not be supported by all control systems. Check your control panel's Installation and Operation Guide for details. Page 1 of 4 E85001-1001 Issue 1 Application Testing & Maintenance The SIGA-OSD detects particles from a wide range of combustion Each detector automatically identifies when it is dirty or defective sources and will trigger an alarm when smoke density in the and causes a"dirty detector"message.The detector's sensitivity chamber reaches preprogrammed level.Thanks to its high- measurement can also be transmitted to the loop controller. performance reflective response technology,the smoke sensor A sensitivity report may be printed to satisfy NFPA sensitivity responds quickly and reliably to a wide range of fire types, measurements,which must be conducted at the end of the first including both fast and slow burning fires fueled by combustibles year and every two years thereafter. typically found in modern multi-use buildings. The user-friendly maintenance program shows the current state of each detector and other pertinent messages.Single detectors may be turned off temporarily from the control panel,Availability of Compatibility maintenance features is dependent on the fire alarm system used. The SIGA-OSD detector is compatible only with control panels using a Signature Loop controller. Accessories Detector mounting bases have wiring terminals that are Installation -- accessible from the"room-side"after mounting the base to the Signature Series detectors mount electrical box.The bases mount to North American 1-gang boxes to North American 1-gang boxes, �.,"� i! ''.�`r and to 31/2 inch or 4 inch octagon boxes, 11 inches(38 mm) 3-1/2 inch or 4 inch octagon --- deep.They also mount to European BESA and 1-gang boxes with boxes, and to 4 inch square - se1-1ock tab 60.3 mm fixing centers.The SIGA-SB4, SIGA-RB4,and SIGA-IB4 electrical boxes 1-1/2 inches r'L mount to North American 4 inch sq.electrical boxes in addition to (38 mm)deep.They mount to ,r the above boxes.They include the SIGA-TS4 Trim Skirt, which is European BESA and 1-gang used to cover the"mounting ears"on the base.The SIGA-AB4G boxes with 60.3 mm fixing N " LED iota mounts to a 4 inch square box only. centers. See mounting base installation and wiring for r tom__ more information. f'`' , v ' Sensing and reporting technology �"F � �Bass SIGA-RB La sBa.. p The microprocessor in each detector provides additional benefits-Self-diagnostics and History Log,Automatic Device Remote LED SIGA-LED-The remote LED connects to the Mapping,and Fast,Stable Communication. SIGA-SB or SIGA-SB4 Standard Base only. It features a North American size 1-gang plastic faceplate with a white finish and Self-diagnostics and History Log- Each Signature Series red alarm I Fn. detector constantly runs self-checks to provide important maintenance information.The results of the self-check are SIGA-TS4 Trim Skirt-Supplied with 4 inch bases, it can also automatically updated and permanently stored in the detector's be ordered separately to use with the other bases to help hide non-volatile memory surface imperfections not covered by the smaller bases. Automatic Device Mapping -The loop controller learns where Sounder Bases -Signature Series sounder bases are designed each device's serial number address is installed relative to other for use where localized or group alarm signaling is required. devices on the circuit.The mapping feature provides supervision • SIGA-AB4G bases provide sounder capability to Signature of each device's installed location to prevent a detector from being Series to heat and smoke detectors.They are not intended reinstalled(after cleaning,etc.)in a different location from where it for use with combination carbon monoxide detectors in was originally. Fire-plus-CO mode. Fast Stable Communication-On-board intelligence means • SIGA-AB4GT bases provide sounder capability to Signature less information noel-is to be sent between the detector and the Series smoke and heat detectors, as well as carbon loop controller.Other than regular supervisory polling response, monoxide detectors when used with a SIGA-TCDR Temporal the detector only needs to communicate with the loop controller Pattern Generator. when it has something new to report. • SIGA-AB4G-LF bases provide 520 Hz low frequency sounder capability to Signature Series smoke and heat detectors,as well as carbon monoxide detectors when used with a SIGA-TCDR Temporal Pattern Generator.The SIGA-AB4G-LF is suitable for applications requiring low frequency audible tones. E85001-1001 Page 2 of 4 Issue 1 Typical Wiring The detector mounting bases accept#18 AWG(0.75mm2), #16 Audible Sounder Bases,Fire Mode (1.0mm2), #14 AWG(1.5mm2),and#12 AWG(2.5mm2)wire sizes. AB4GT,AB4G,AB4G-LF sounder bases Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are preferred for ease of installation. Standard Detector Base,SIGA-SB,SIGA-SB4 s a AAA T ® o o ® SIGA-As4c-I.F; SIThis is the basic mounting SIGA-AB4G-LF: Jumper outs Output Motle Volume SettingDefault=Fire =wl plus base for EDWARDS Signature Remote LED DefaultCOO Series detectors.The SIGA- I Max resistance CuVrremove LED Remote LED is supported 'e; must nut exceed jumper for gire �A.AD4G: 10 Ohms low dB et al Tone Betting by this Base. aw Default=Temporal ,•', - en. s em w e ovr Cut/remove jumper Term ... Steady 1 Not Ua d� _it - -�j�\ (,'( )T) (iI (�� )T( o for 2 DATA IN/OUT(+) • •�• e.-.� 1 t�.I at rltt 3 Not Used r✓ rv' 4 DATA IN(-) DATA IN I-I ,' /1q� v I�+��GI�1C'f�ICf�.f CI�I 4 Remote LED(-) 't'+i' DATA OUT 1-) 1 1 �`r�•I t''`I 5 Remote LED(+I 111111 6 Not Used DATA IN(+I DATA OUT l+l 24 Vdc InVde _ 7 DATA OUT(-) From Signature Controller To Next Device From power supply ■-■' - 24 next Previous Device or previous Dees • NM To next base a C-0L relay Date Isolator Detector Base,SIGA-IB,SIGA-IB4 From Signature Cotttrooll� - ron.xt°ut Sigrlao,rede„ee or previous device F + This base includes a built-in line fault isolator for use on Class A circuits.A detector must be installed for it to operate.The isolator base does not support the SIGA-LED Remote LED. Warnings & Cautions The isolator operates as follows: • This detector does not operate without electrical power. -a short on the line causes all As fires frequently cause power interruption,discuss isolators to open within 23 msec. / s1 \ further safeguards with the local fire protection specialist. - at 10 msec intervals,beginning i11 p on one side of the Class A • This detector does not sense fires in areas where smoke circuit nearest the loop • cannot reach the detector.Smoke from fires in walls, controller,the isolators DATA IN(- 'T f DATA OUT(-) roofs,or on the opposite side of closed doors may not close to provide the reach the detector. next isolator down DATA IN O.) To Next OU be • In Canada, install according to CAN/ULC-5524 Standard for the line with power. From Signature Device Controler the Installation of Fire Alarm Systems,CSA C22.1 Canadian or Previous Devi -when the isolator next Ttm, ()ascription Electrical Code,and the local authority having jurisdiction. 1 Not Used to the short closes,it 2 DATA IN/OIfT(.) reopens within 10 msec. 3 DATA IN(-) 4 Not Used The process repeats beginning on 5 Not Used 6 DATA OUT(-J the other side of the loop controller. 7 Not Used Relay Detector Base,SIGA-RB,SIGA-RB4 This base includes a relay. cmx,aD Normally-Nowak- closed Normally Open or Normally Open Closed operation is selected during installation.The dry contact is rated for 1 amp it l (pilot duty)@ 30 Vdc.The ! relay's position is supervised lV 1.21 to avoid accidentally jarring it DATA eI(-> " I / DAtA OUT(-> out of position.The SIGA-RB can be operated as a control DATA INt+) DATA art t+> To Nee Drape relay if programmed to do so D` onirelerame Deeat the control panel.The relay T1 nn Dana,, on Open base does not support the CONTACT RATS 2 DATA ((+) SIGA-LED Remote LED. T.o Ate®ut 3 Column(RotDuly)y) 4 DATA IN(-) 5 Not Used 6 Nommay-Closed 7 DATA OUT(-) Page 3 of 4 E85001-1001 Issue 1 Dimensions 1 Phone: 800-255-4497,Option 1 a I isave.tom ea ! i4 77:91 iTir E E86a226,212E / i Bi lINIE--'_-� " 1 �, - Email: F�wards.techsupport@fs.uto.com ',\ '�/% Webster https://wwedwardsfiresafety.coN - _,. � �� ` . B985 Town Center Pkwy Bradenton,FL 34202 EDWARDS is a registered mark in the United States and other countries. C 2019 United Technologies Corporation. Specifications All rights reserved. Operating voltage 15.20 to 19.95 VDC Normal operating current 32A IA— — --_—-- -___ Alarm current `5 pA Smoke Sensitivity Range ULNLC:0.5 to 4.36%/ft.(1.6 to 13.6 96/m)obscuration Vibration level 10 to 35 Hz,with an amplitude of 0.01 in. Air velocity 0 to 4,000 fL/min(0 to 20 m/s) Wall mounting 12 in.(305 mm)max.from ceiling Compatible bases See Ordering Information Compatible detector testers restive 1000,Testifire 2000 ---- _----—_ _ Operating environment 32 to 120°F(0 to 49°C),0 to 93%RH,noncondensing Construction High Impact Engineering Polymer,White Storage temperature -4 to 140°F(-20 to 60°C) Environmental compensation Automatic Agency Listings CAN/ULC 5529,UL 268-7,UL 268A Ordering Information Catalog Ship WL \ Number Description 0 SIGA-OSD Intelligent Optical Smoke Detector .4(0.16) Accessories SIGA-SB Detector Mounting Base-Standard SIGA-SB4 4-inch Detector Mounting Base c/w Trim Skirt SIGA-RB Detector Mounting Base w/Relay SIGA-R84 4-inch Detector Mounting Base w/Relay,c/w Trim Skirt 0.2(.09) SIGA-IB Detector Mounting Base w/Fault Isolator 61GA-IB4 4-inch Detector Mounting Base w/Fault Isolator,c/w Trim Skirt SIGA-LED Remote Alarm Lt3)(not for F_N54 applications) SIGA-AB4G Audible(Sounder)Base for Fie Detectors 0.3(0.15) SIGA-AB4G-LF Low Frequency Audible(Sounder)Base for CO and/or Fie Detectors 0.3(0.15) A A SIGB4GT_.__. .Audible(Sounder)Base for CO and/or Fire Detectors 0.3(0.15) SIGA-TS4 Trim Skirt(suppled with 4-inch bases) 0.1 (0.04) 0.1(0.04) SSA-Ts Trim Skirt-(optional for non flinch bases)---- SIGA-DMP Detector Mounting Plate 3.0(1,4) SIGA-RTA Detector Removal Tool --SIGA VA Detector Cleaning Tool E85001-1001 Page 4 of 4 Issue 1 Intelligent Initiating Devices Intelligent Heat Detectors . SIGA-HRD, SIGA-HFD0010ftlift, 1 1S853 IMt Overview Standard Features The Signature Series smoke detectors bring advanced sensing Note:Some features described here may not be supported by technology to a practical design that increases efficiency, saves all control systems. Check your control panel's Installation and installation time, cuts costs, and extends property protection Operation Guide for details. capabilities.Continuous self-diagnostics ensures reliability over • Next Generation Heat SensingTechnology the long-haul, while the latest thermister technology makes these detectors ideal wherever dependable heat detection is required. • 135°F(57°C)fixed temperature alarm point(HRD and HFD) The SIGA-HRD is an intelligent fixed temperature/rate-of-rise fire • 15°F(9°C)per minute rate-of-rise alarm point(HRD) detector. It monitors the temperature of the surrounding air and • Uses existing wiring analyzes the data from the sensor to determine whether to initiate an alarm.The rate-of-rise heat function quickly detects a fast, • Automatic device mapping flaming fire.The faced-temperature heat function detects fire when • Sensor Markings Provide Facy Testing Identification the air temperature near the detector exceeds the alarm point. • Up To 250 Total Signature Devices Per Loop The SIGA-HFD is an intelligent fixed-temperature heat detec- tor that contains a fixed-temperature heat sensor rated at 135°F • Non-volatile memory (57.2°C). It does not have a rate-of-rise function.The heat sensor • Electronic addressing monitors the temperature of the air in its surroundings and the detector analyzes the data to determine when the air temperature • Bicolor(green/red)status LED near the detector exceeds the device's alarm point. • Standard, relay,fault isolator,and audible mounting bases • 50 foot(15.2 meter)spacing Page 1 of 4 E85001 -0647 Issue 2 Application Accessories The SIGA-HRD combination fixed temperature/rate-of-rise heat Detector mounting bases have wiring terminals that are acces- sibledetector provides a 15°F(9°C)per minute rate-of-rise heat sen- from the"room-side"after mounting the base to the electrical box.The bases mount to North American 1-gang boxes and to sor for the detection of fast-developing fires,as well as a 135°F 31/2 inch or 4 inch octagon boxes, 1' inches(38 mm)deep.They (57°C)fixed temperature sensor for slow building-fires.The SIGA- also mount to European BESA and 1-gang boxes with 60.3 mm HFD fixed temperature detector provides a 135°F(57°C)fixed fixing centers.The SIGA-SB4, SIGA-RB4,and SIGA-IB4 mount to temperature sensor for slow building-fires. North American 4 inch sq.electrical boxes in addition to the above boxes.They include the SIGA-TS4 Trim Skirt,which is used to cover the"mounting ears"on the base.The SIGA-AB4G mounts Compatibility to a 4 inch square box only. Signature Series heat detectors are compatible only with the Sig ,'" nature Loop Controller. ( s; I • % 4. :go . .• S SIGA-A54G/r/LF SIGA-BB SIGA-IB SIGA-Rs SIGA-LED Installation Audible Base Standad Base Isolator Base Remy Base Remote LED Signature Series detectors mount Remote LED SIGA-LED -The remote LED connects to the to North American 1-gang boxes, SIGA-SB or SIGA-SB4 Standard Base only. It features a North 3-1/2 inch or 4 inch octagon . - American size 1-gang plastic faceplate with a white finish and red boxes,and to 4 inch square elec- -i�saya°`""g1ae alarm LED. trical boxes 1-1/2 inches(38 mm) /, — --u SIGA-TS4 Trim Skirt-Supplied with 4 inch bases, it can also deep.They mount to European (�� — — be ordered separately to use with the other bases to help hide BESA and 1-gang boxes with 60.3 a . ,- surface imperfections not covered by the smaller bases. mm fixingcenters.See mounting "ice?-'""'° ` LEDI « r -- .-r Sounder Bases-Signature Series sounder bases are designed base installation and wiring for for use where localized or group alarm signaling is required. more information. • SIGA-AB4G bases provide sounder capability to Signature Series to heat and smoke detectors.They are not intended for use with combination carbon monoxide detectors in Fire- Sensing and reporting technology plus-CO mode. The microprocessor in each detector provides additional benefits- • SIGA-AB4GT bases provide sounder capability to Signature Self-diagnostics and History Log,Automatic Device Mapping,and Series smoke and heat detectors,as well as carbon monox- Fast,Stable Communication. ide detectors when used with a SIGA-TCDR Temporal Pattern Generator. Self-diagnostics and History Log-Each Signature Series • SIGA-AB4G-LF bases provide 520 Hz low frequency detector constantly runs self-checks to provide important mainte- sounder capability to Signature Series smoke and heat detec- nance information.The results of the self-check are automatically tors,as well as carbon monoxide detectors when used with a updated and permanently stored in the detector's non-volatile SIGA-TCDR Temporal Pattern Generator.The SIGA-AB4G-LF memory. is suitable for applications requiring low frequency audible Automatic Device Mapping -The loop controller learns where tones. each device's serial number address is installed relative to other devices on the circuit.The mapping feature provides supervision Warnings & Cautions of each device's installed location to prevent a detector from being g reinstalled(after cleaning etc.)in a different location from where it • This detector does not operate without electrical power.As was originally. fires frequently cause power interruption,discuss further safe- Fast Stable Communication-On-board intelligence means less guards with the local fire protection specialist. information needs to be sent between the detector and the loop • This detector does not sense fires in areas where heat cannot controller.Other than regular supervisory polling response,the reach the detector.Heat from fires in walls,roofs,or on the detector only needs to communicate with the loop controller when opposite side of closed doors may not reach the detector. it has something new to report. • This heat detector by itself does not provide life safety protec- tion Use this detector with ionization and/or photoelectric smoke detectors. • This detector does not detect oxygen levels,smoke,toxic gases,or flames.Use this device as part of a broad-based fife safety program which includes a variety of information sources pertaining to heat and smoke levels,extinguishment systems,visual and audible devices,and other safety mea- sures. • Independent studies indicate that heat detectors should only be used when property protection alone is invoked.Never rely on heat detectors as the sole means of fire protection. E85001-0647 Page 2 of 4 Issue 2 Typical Wiring The detector mounting bases accept#18 AWG(0.75mm2), #16 Relay Detector Base,SIGA-RB,SIGA-RB4 _ Normaly- (1.0mm2), #14 AWG(1.5mm2), and#12 AWG (2.5mml wire sizes. This base includes a relay. Nor- Common aned open Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are preferred malty Open or Normally Closed for ease of Installation. operation is selected during in- stallation,The dry contact is rated Standard Detector Base,SIGA-SB,SIGA-SB4 for 1 amp(pilot duty)@ 30 Vdc. falai The relays position is supervised • ' This is the basic mounting base Remote LED to avoid accidentally jarring it out __ for EDWARDS Signature Series 1 Max resistance of position.The SIGA-RB can be DATA'"(') ilk'k' DATA OUT(•) detectors.The SIGA-LED Re- 4Il0 per wire operated as a control relay if pro- - exceed mote LED is supported by thism io on grammed to do so at the cotrol DATANc> DATA our(T) Base. to Next Device • panel.The relay base does not From signature Tarn Not _t;•�. \� support the SIGA-LED Remote T1 °�allyOp 1 DATANorm lr.LOpen 2 DATA IWOUT(+) —; __ -11' LED. CONTACT RATING 2 DATA IWOUT(+) 43 NotUTA ea(-) .,.r.'8., 1.0 Amp el 30 VOC 3 Common 4 Remote((-) - DATA IN 1-1 \n' (Rot Duty) 4 DATA IN(-) O `�eI DATA Ol1T FI 5 Not Used 5 Remote LED(+) 6 Normally-Closed 6 Not Used 7 DATA OUT(-) 7 DATA OUT(-) DATA IN(+I DATA OUT I+1 From Signature Controller To Next Device or Previous Device Audible Sounder Bases,Fire Mode Isolator Detector Base, SIGA-IB,SIGA-IB4 AB4GT,AB4G,AB4G-LF sounder bases This base includes a built-in line fault isolator for use on Class A circuits. A detector must be installed for it to operate.The isolator base does not support the SIGA-LED Remote LED. SIGA-AS4GT, O o SIGA•AB4GLF: The isolator operates as follows: SIGA-A ®Jumper ® output Mode GA• B4G-LF: Default=Fire - a short on the line calicos all iso- 1..�., .:7' \ Volume Setting Cut/remove jumper for lators to open within 23 msec Default h Fire plus co -at 10 msnrr intervals, I II jumper for SICA.Aeac, beginning on one side ry`� low dB [ID ID Iona Setting \ i . MA CM. �, Default=Temporalof the Class A DATA IN(• 4` / DATA OUT(-) e . . en a uamn CuVremove Jumper for circuit nearest the loop ( n ee Steady controller,the isolators III I�III�IIIIII o close to provide the DATA IN(+) DATA OUT(+) r r r�:r r r ram;r SIGA AB4GT: next isolator down the From Signature Controler To Next Devoe I ee I ee'1 }.:1 }�:1�}.:1 Not used or Previous Device (••�r...t �� t'�`t line with power Term Description �I���I 1 Not used 24 Vde a -when the isolator next 2 DATA IN/OUT(+) From power supply - ■-■' - u Vrk out to the short doses,it reopens within 10 3 DATA IN(-) or previous base + 4 Not used .,' + To text ase a EOL elay msec. 5 Nol Used 8 DATA OUT(-) Data in - Data out The procP-sc repeats beginning on the 7 Not Used From Signature Controller to next Signature device other side of the loop controller. or previous device + Page 3 at 4 E85001-0647 Issue 2 Dimensions i ��-r li p l(11' . ) ��_�_ Contact us... 6I if 4 JfMd1D'1W 1Z4\ It/ Email: edwards.fire®fs.utc.com .. ? r'S 7 ' • \� ' �/� Web: Edwards-fire.corn/ EDWARDS is a UTC brand. 1016 Corporate Park Drive Mebane,NC 27302 ®2017 United Technologies Corporation. All rights reserved- Specifications SIGA-HRD SIGA-HFD Operating voltage 15.20 to 19.95 VDC Normal operating current 32 pA Alarm current 32 pA Vibration level 10 to 35 Hz,with an amplitude of 0.01 in. Rate-of-rise rating 15°F/min(B°C/min) _ 1 NA Faed temperature rating 135°F(57.2°C).Actual alarm point 129 to 141°F(53.9 to 60.6°C). Maximum spacing 50 tL(15.2 m)centers Compatible bases See Ordering Information Compatible detector testers Testifire 1000,Testifire 2000 i i Testifire 2000 Operating environment 32 to 100°F(0 to 36°C),0 to 93%RH,noncondensing Construction High Impact Engineering Polymer,White Storage temperature -4 to 140°F(-20 to 60°C) Agency Listings CAWULC-S530 UL521 CANNLC-S530-M91,UL 521 Ordering Information Catalog Ship Wt. Number Description lbs Ik91 SIGH HRD Intelligent fixed temperature/Rate-of-rise heat detector 0.4(0.16) SIGA-HFD Intelligent fixed temperature heat detector --— Compatible Bases y SIGA-SB Detector Mounting Base-Standard SIGA-SB4 4-inch Detector Mounting Base c/w Trim Skirt SIGA-RB Detector Mounting Base w/Relay --- 0.2(.09) SIGA-RB4 4-inch Detector Mounting Base w/Relay, c/w Trim Skirt SIGA-IB Detector Mounting Base w/Fault Isolator SIGA-IB4 4-inch Detector Mounting Base w/Fault Isolator,c/w Trim Skirt SIGA-AB4G Audible(Sounder)Base for Re Detectors SK3A-AB4G-LF Low Frequency Audible(Sounder)Base for CO and Are Detectors 0.3(0.15) SIGA-AB4GT Audible(Sounder)Base for CO and Are Detectors SIGA-LED Remote Alarm LID(not for EN54 applications) SIGA-TS4 Trim Skirt(supplied with 4-inch bases) 0.1 (0.04) SIGHTS Trim Skirt(optional for non 4-inch basns) — SIGA-RTA Detector Removal Tool E85001-0647 Page 4 of 4 Issue 2 Intelligent Initiating Manual Pull ,PULL N CASE Stations LlLH THANEN IL { FIRE PULL SIGA-270, SIGA-270P, SIGA-278 Hitt oWAAos SIGA-270 SERIES Patented — 0 SIGA-278 I04 EC MEA 0 7150-1657: 0129 S2318 Overview • Break glass operation The SIGA-270 and SIGA-278 series Manual Pull Stations are part An up-front visible glass rod on the SIGA-270 discourages of EDWARDS's Signature Series system.The SIGA-270 Fire Alarm tampering. Manual Pull Stations feature our very familiar teardrop shape.They • Intelligent device with integral microprocessor are made from die-cast zinc and finished with red epoxy powder- All decisions are made at the station allowing lower corn- coat paint complemented by aluminum colored stripes and mark- munication speed while substantially improving control panel ings. With positive pull-lever operation,one pull on the station response time. Less sensitive to line noise and loop wiring handle breaks the glass rod and turns in a positive alarm, ensuring properties;twisted or shielded wire is not required. protection plus fool-proof operation. Presignal models(SIGA-270P) • ADA Compliant are equipped with a general alarm(GA)keyswitch for applications Meets ADA requirements for manual pull stations. where two stage operation is required.The up-front highly visible glass rod discourages tampering, but is not required for proper • Electronic Addressing with Non-volatile memory operation. Permanently stores programmable addraes,serial number, EDWARDS's double action single stage SIGA-278 station is a type of device,and job number.Automatically updates historic information including hours of operation, last maintenance contemporary style manual station made from durable red colored date, number of alarms and troubles,and time and date of last lexan. To initiate an alarm,first lift the upper door marked"UFT alarm. THEN PULL HANDLE",then pull the alarm handle. • Automatic device mapping Each station transmits wiring information to the loop control- Standard Features ler regarding its location with respect to other devices on the Note:Some features descnbed here may not be supported by all control sys- circuit. tems.Check your control panel's Installation and operation Guide fordetai7s. • Diagnostic LEDs • Traditional familiar appearance Status LEDs;flashing GREEN shows normal polling;flashing SIGA-270 models feature our familiar teardrop design with RED shows alarm state. simple positive pull action and sturdy die-cast metal body. • Designed for high ambient temperature operation • One stage(GA),two stage(pre-signal),and double action Install in ambient temperatures up to 120°F(49°C). models SIGA-270 models are available for one or two stage alarm systems.The single stage double action SIGA-278 features a rugged Lexan housing with keyed reset mechanism. Page 1 of 4 E85001-0279 Issue 1 Application Typical Wiring The operating characteristics of the fire alarm stations are deter- The fire alarm station's terminal block accepts#18 AWG(0.75mmz) mined by their sub-type code or"Personality Code". NORMALLY- to#12 AWG(2.5mm2)wire sizes.See Signature Loop Controller OPEN ALARM-LATCHING(Pesonality Code 1)is assigned by the catalog sheet for detailed wiring requirement specifications. factory;no user configuration Is required.The device is configured for Class B IDC operation.An ALARM signal is sent to the loop Wiring Notes controller when the station's pull lever is operated.The alarm con- Q Refer to Signature Loop Controller manual for maximum dition is latched at the station. wire distance. 2. All wiring is power limited and supervised. NB Compatibility REAR VIEW of 278 Signature Series manual stations are compatible only with ED- WARDS's a f� Signature Loop Controller. o 0 ram, 13.2 MIMI Warnings & Cautions ° ' This device will not operate without electrical power.As fires fre- quently cause power interruption,we suggest you discuss further cNam/Active)Red 1ED o o (Normal) safeguards with your local fire protection specialist. ,,,Irm,E1 '.1 Testing & Maintenance To test(or reset)the station simply open the station and operate r DATA IN v) 11111 DATA OUT(+l the exposed switch.The SIGA-270 series are opened with a tool; 1 DATA N(d • DATA OUT(-) the SIGA-278 requires the key which is supplied with that station. Ran SiRrwMe Gonlra.er To Next Device a Previous Device Q The station's automatic self-diagnosis identifies when it is defec- tive and causes a trouble message.The user-friendly maintenance Figure 4. Single Stage Systems program shows the current state of each Signature series device and other pertinent messages.Single devices may be deactivated temporarily,from the control panel.Availability of maintenance REAR VIEW - features is dependent on the fire alarm system used. of 270P,270P8 M G C Scheduled maintenance(Regular or Selected)for proper system operation should be planned to meet the requirements of the El fr „ o Authority Having Jurisdiction(AHJ). Refer to current NFPA 72 and o Te2 1:`jZ ,,. ULC CAN/ULC 536 standards. ° , ti 5 Red LED I O Green LED (NmNAttNe) I • (Nand) I'':11.v o'. _ • i �, h RATAN(+) - , DATA OUT(+)} DAUN(-0 DATA OUT(-) • From Sambre Controller To Neal DENIM a Erevan Device Q Figure 5. Two Stage Systems E85001-0279 Page 2 of 4 Issue 1 Installation Single-stage Signature Series fire alarm manual pull stations mount to North American 21/2 inch(64 mm)deep 1-gang boxes. Two stage presignal(270P)models require 11/2 inch(38 mm)deep 4-inch square boxes with 1-gang, 1-inch raised covers. Openings must be angular. Rounded openings are not acceptable. Recommended box:Steel City Model 52-C-13;in Canada,use Iberville Model Cl- 52-C-49-1/2. All models include terminals are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. EDWARDS recommends that these fire alarm stations be installed according to latest recognized edition of national and local fire alarm codes. Electronic Addressing: The loop controller electronically addresses each manual station,saving valuable time during system com- missioning. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board memory.The loop controller identifies each device on the loop and assigns a~soft"address to each serial number. If desired,the stations can be addressed using the SIGA-PRO Signature Program/Service Tool. Ii �--. Cover Release i Compatible Electrical Box Compatible Electrical Box ,,r 1111 • Back \ Key-Latch r Cover Rele�� /� siggill Screw -.0°) nUae ll r 'pyPRFR� a , ; ° Back lam: l Plate Toggle Ow— Switch , Toggle ° • • Switch 11111 it 11 class Rod ' a OPEN Woci°f '-----,/ *I1 • ‘, \ riii\iii:1:9 ,:_ - \1/4„... ei Figure 1. SIGA-278 installation Figure 2. SIGA-270,SIGC-270F,SIGC-270B installation Cover Release k Oh I •O_ �Conpotible 1.0 P Electrical Roe with Y.-inch •` raised covers illedcu` 4 � Pg� i J!I l I 1\ 4 ° • j';ll Toggle 4 • Switch Oi l %.-J • 0,‘ • lk ‘., +� kW Glace Rod V' yt Release laver Do notes r` boxes with MAMBA Figure 3. SIGA-270P,SIGC-270PB installation Page 3 of 4 E85001-0279 Issue 1 Specifications F... DWARDE SIGA-270,SIGC- SIGA-270P, Catalog Number 270F,SIGC-27013 SIGC-270PB , SIGA-278 Single Action Single Action-Two Diable Action Description -One Stage I Stage(PresignaQ -One Stage Addressing Uses 1 Module Uses 2 Module Uses 1 Module Contact us... Requkements Address 1 Addresses Address Email: edwards.fireefs.utc.com Standby=250pA , Standby=396pA Standby=250pA Operating Current Web: Edwards-fire.com Activated=400pA I Activated=680pA Activated=400pA Drecast Zinc-Red Epoxy Li3xan-Red wkh Construction&Finish EDWARDS is a UTC brand. with aluminum markings white markings tore Corporate Park Drive Type Code Factory Set Mebane,NC 27302 Operating Voltage 15.2 to 19.95 Vdc(19 Vdc nominal) Operating Temperature:32"F to 120"F(0"C to 49"C) 0 2016 United Technologies Corporation. Storage and Operating Storage Temperature:-4"F to 140"F(-20"C to 60"C)Humidity:0 to 93% All rights reserved. Environment RH On-board Green LED-Rashes when polled LED Operation On-boare Red LED-Flashes when in alarm Compatibility i Use With:Signature Loop Controller Agency Listings UL,ULC(note 1),MEA,CSFM,FM Note:SIGC-270F SIGC-27013 and SIGC-270PB are ULC listed only.Suffix'F"indicates French markings. Suffix 13°indicates English/French biting us!markings. Ordering Information Catalog Ship Wt. Number Description lbs(kg) SIGA-270 One Stage Fire Alarm Station, English Markings-UL/ULC Usted SIGC-270F One Stage Are Alarm Station, French Markings-ULC Listed SIGC-270B One Stage Are Alarm Station,French/English Markings-ULC Listed Two Stage(Presignal)Are Alarm Station.English Markings-UL/ULC SIGA-270P Listed 1 (0.5) SIGC- Two Stage(Presignal)Fire Alarm Station,French/English Markings 270PB -ULC Listed 278 Double Action(One Stage)Fire Alarm Station,Enghsh Markings SIGA- -UL/ULC Listed Accessories 32997 GA Key w/Tag-for pre-signal station(CANADA ONLY) 276-K2 GA Key-for pre-signal station (USA ONLY) 276-K1 Station Reset Key, Supplied with all Key Reset Stations 0.1 (.05) 27165 12 Glass Rods-for SIGA-270 series(CANADA ONLY) 270-GLR 20 Glass Rods-for SIGA-270 series (USA ONLY) 276-GLR 20 Glass Rods-for SIGA-278 series 276B-RSB Surface Mount Box,Red-for SIGA pull stations ---- -- 1 (0.6) Page 4 of 4 E85001-0279 Issue 1 Intelligent Input-Output 411-4111 • Input Modules SIGA-CT1 , SIGA-CT1 HT, � SIGA-CT2, SIGA-MCT2 1=7 • • phf. L s 1 SIGA-CT1/2 sNiA-MCT2 -'' 0 ® MEA (., ,) thz 0121 53424 Overview Standard Features The SIGA-CT1 Single Input Module,SIGA-CT1 HT High Tern- • Multiple applications perature Single Input Module and SIGA-CT2/SIGA-MCT2 Dual Including Alarm,Alarm with delayed latching(retard)for water- Input Modules are intelligent analog addressable devices used to flow applications, Supervisory, and Monitor.The installer selects connect one or two Class B normally-open Alarm, Supervisory,or one of four"personality codes"to be downloaded to the mod- Monitor type dry contact Initiating Device Circuits(IDC). ule through the loop controller. The actual function of these modules is determined by the"personal- • SIGA-CT1 HT rated for high temperature environments ity code"selected by the installer.This code is downloaded to the Suitable for attic installation and monitoring high temperature module from the Signature loop controller during system configure- heat detectors. tion. • Plug-in(U10)or standard 1-gang mount The input modulesgather analogUIO versions allow quick installation where multiple modules are p information from the initiating required.The 1-gang mount version is ideal for remote loca- devices connected to them and convert it into digital signals. tions that require a single module. The modules on-board microprocessor analyzes the signal and decides whether or not to input an alarm. • Automatic device mapping Signature modules transmit information to the loop controller The SIGA-CT1,SIGA-CT1HT and SIGA-CT2 mount to standard regarding their circuit locations with respect to other Signature North American 1-gang electrical boxes, making them ideal for lo- devices on the wire loop. cations where only one module is required.Separate I/O and data • Electronic addressing loop connections are made to each module. Programmable addresses are downloaded from the loop con- The SIGA-CT1HT module operates at an expanded temperature troller,a PC,or the SIGA-PRO Signature Program/Service Tool. range of 32"F to 158"F(0"C to 70"C)for those applications There are no switches or dials to set. requiring more extreme environmental temperature variation. • Ground fault detection by address The SIGA-MCT2 is part of the UIO family of plug-in Signature Detects ground faults right down to the device level. Series modules. It functions identically to the SIGA-CT2, but takes advantage of the modular flexibility and easy installation that characterizes all UK)modules.Two-and six-module UIO mother- boards are available.All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in EDWARDS enclosures. Page 1 of 4 E85001-0241 Issue 1 Signature Series Overview U10 MotheiboeN 1 6-3 The Signature Series intelligent analog-addressable system from sal—rapping EDWARDS Security is an entire family of multi-sensor detectors i <EI-- J and mounting bases, multiple-function input and output modules, {1__14 network and non-network control panels,and user-friendly mainte- Plug 1n(U10) Captive nance and service tools.Analog information from equipment con- Module ace nected to Signature devices is gathered and converted into digital - fl--.1 signals,An onboard microprocessor in each Signature device ---=13 — measures and analyzes the signal and decides whether or not to Ne Flat washers input an alarm.The microprocessor in each Signature device pro- vides four additional benefits—Self-diagnostics and History Log, —*Cabinet MN/otrlcal enclosure Automatic Device Mapping, and Fast,Stable Communication. Self-diagnostics and History Log—Each Signature Series Electronic Addressing -The loop controller electronically ad- device constantly runs self-checks to provide important mainte- dresses each module,saving valuable time during system corn- nance information.The results of the self-check are automatically missioning.Setting complicated switches or dials is not required. updated and permanently stored in its non-volatile memory.This Each module has its own unique serial number stored in its information is accessible for review any time at the control panel, on-board memory.The loop controller identifies each device on PC,or using the SIGA-PRO Signature Program/Service Tool. the loop and assigns a"soft"address to each serial number. If Automatic Device Mapping—The Signature Data Control- desired,the modules can be addressed using the SIGA-PRO ler(SDC)learns where each device's serial number address is Signature Program/Service Tool. installed relative to other devices on the circuit.The SDC keeps a EDWARDS recommends that this module be installed according map of all Signature Series devices connected to it.The Signature to latest recognized edition of national and local fire alarm codes. Series Data Entry Program also uses the mapping feature.With interactive menus and graphic support,the wired circuits be- tween each device can be examined. Layout or"as-built"drawing Application information showing branch wiring(T-taps), device types and their address are stored on disk for printing hard copy. The duty performed by the SIGA-CT1 and SIGA-CT2/MCT2 is de- termined by their sub-type code or Personality Code". The code Installation is selected by the installer depending upon the desired application and is downloaded from the loop controller. SIGA-CT1,SIGA-CT1HT and SIGA-CT2: modules mount to North American 21/2 inch(64 mm)deep 1-gang boxes and 11 inch One personality code can be assigned to the SIGA-CT1.Two per- (38 mm)deep 4 inch square boxes with 1-gang covers and SIGA- sonality codes can be assigned to the SIGA-CT2/MCT2. Codes MP mounting plates.The terminals are suited for#12 to#18 AWG 1,2, 3 and 4 can be mixed on SIGA-CT2/MCT2 modules only. For (2.5 mm2 to 0.75 mm2)wire size. example,personality code 1 can be assigned to the first address (circuit A)and code 4 can be assigned to the second address alb (circuit B). Compatible electrical box11 NORMALLY-OPEN ALARM LATCHING (Personality Code 1) to -Assign to one or both circuits. Configures either circuit A or B or both for Class B normally open dry contact initiating devices such as Pull Stations, Heat Detectors,etc.An ALARM signal is sent to � the loop controller when the input contact is closed.The alarm •I `I Wall pla white condition is latched at the module. �1 ! <9% NORMALLY-OPEN ALARM -DELAYED LATCHING(Person- ality Code 2)-Assign to one or both circuits. Configures either Oil \\ ,,,.. circuit A or B or both for Class Bnormally-open dry contact intiat- ing devices such as Waterfiow Alarm Switches.An ALARM signal JJJ Q, is sent to the loop controller when the input contact is closed for approximately 16 seconds.The alarm condition is latched at the Status LEDs ` module. NORMALLY-OPEN ACTIVE-NON-LATCHING(Personality LED viewing ports + �` ,� Code 3)-Assign to one or both circuits.Configures either circuit • A or B or both for Class B normally-open dry contact monitoring input such as from Fans,Dampers, Doors,etc.An ACTIVE signal is sent to the loop controller when the input contact is closed.The SIGA-MCT2:mount the UIO motherboard inside a suitable ED- active condition is not latched at the module. WARDS enclosure with screws and washers provided. Plug the NORMALLY-OPEN ACTIVE-LATCHING(Personality Code SIGA-MCT2 into any available position on the motherboard and 4)-Assign to one or both circuits. Configures either circuit A or secure the module to the motherboard with the captive screws. B or both for Class B normally open dry contact monitoring input Wiring connections are made to the terminals on the motherboard such as from Supervisory and Tamper Switches.An ACTIVE signal (see wiring diagram).UIO motherboard terminals are suited for#12 is sent to the loop controller when the input contact is closed.The to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. active condition is latched at the module. E85001-0241 Page 2 014 Issue'I Typical Wiring Modules will accept#18 AWG (0.75mm2),#16(1.0mm2),and#14AWG(1.50mm2), and#12 AWG(2.50mm2)wire sizes. Note: Sizes#16 AWG(1.0mm2)and#16 AWG(0.75mm2)are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Initiating(Slave)Device Circuit Wire Specifications Maximum Allowable Wire Resistance 50 ohms(25 ohms per wire)per Circuit Maximum Allowable Wire Capacitance 0.1NF per Circuit For Design Reference: Wire Size Maximum Distance to EOLR #18 AWG(0.75 mm2) #16 AWG(1.00 mm2) 4,000 ft(1,219 m) #14 AWG(1.50 mm2) #12 AWG(1.50 mm2) Typical N.O.Initiating Device Typical N.O.Initiating Device ♦ INPUT I INPUT 2 HIH HIH pinto A AA Style B(Class B) / Bit I I .■..► MEM TB2I',,,Y_il it u1i'=., 8 7 UL/ULC Listed Style B(pass B) /• e ® • • 47Kg EOL UL/ULC Listed 6 5 UL/ULC Usted 47Kt1 EOL 1Q Q A I e e e ( 471ag EOL Red LED Green LED Worm/AcINe) :{{ 0 0 (Normal) Red LED Green LED 1 4 3 1 I (Alarm/ACIWe) i . 3020 i (Normal) TBlI90It U/Pl. T81 II n=S4. ( DATA IN(+) ,� I DATA OUT(+) (DATA IN<+> t DATA OUT(+)1 1 DATA IN(-) ► DATA OUT(-) 1DATA IN(-) •MNI DATA OUT(-)/> From Signature Controller To Next Device From Signature Controller To Next Device or Previous Device or Previous Device Q 1 SIGA-CT1, SIGA-CT1HT SIGA-CT2 1 i .we+NON�Ye Om.1 1 1 1 NOTES umacume OWN ' H�H '' lb (11 202 xnac Listed Maximum 25 Ohm resistance per wire. 4mv rot A Maximum#12 AWG(2.5 mm2)wire;Minimum#18 AWG(0.75 mm2). — ARefer to Signature controller installation sheet for wiring c(urfiptions. A Maximum 10 Vdc @ 350 pA AThe SIGA-UIO6R and the SIGA-U102R do not come with TB14. 1214 MOW.w.„N.em, 8 Al wiring is supervised and power-limited. 4. r WbF mint }:1 A - 7 These modules will not support 2-wire smoke detectors. - fg 6emw 1 ::`., ,/ NommrlWe naiNbr "Cn ma Out+ / mA.4aN Warnings & Cautions — r,, .r. na This module will not operate without electrical power.As fires fre- `""`®"°'®" ti r1' Rd un Na;rN :... quently cause power interruption,we suggest you discuss further N. ' safeguards with your local fire protection specialist. �� arlospar lettings wired fox 11412 Compatibility SIGA-MCT2 These modules are part of EDWARDS's Signature Series intelligent processing and control platform.They are compatible with EST3, EST3X and i0 Series control panels. Page 3 of 4 E85001-0241 Issue 1 Specifications t'D WAR D S Catalog Number SIGA-CT1HT SIGA-CT1 SIGA-CT2 SIGA-MCT2 en Description Single Input Module Dual Input Module Type Code 48(factory set)Four sub-types 49(factory set)Four sub-types (personality codes)are available (personality codes)are available s Requirements_. Uses Two Module Addresses Address Uses One Module Address 396NA; Contact us... Operating Current Standby=250pA Standby Email: edwards.fire®fs.uto.00m Activated=400pA Activated= - - 15.2 to 19.95 Vdc(19 Vdc nominal) Web: Edwards-fire.com Operating Voltage Construction High Impact Engineering Polymer EDWARDS is a UTC brand. Mounting North American 2Yz inch(64 mm)deep one-gang box UI02R/6R/6 t Corporate Park Drive es and 114i Inch (38 mm)deep 4 inch square boxes Motherboard Mebane, N NC C 7 27302 with one-gang covers and SIGA-MP mounting plates ®2016 United Technologies Corporation. Operating Environment 32°F to 158°F 32°F to 120°F(0°C to 49°C) All rights reserved. (0°C W 70°C) 1_ Storage Environment -4°F to 140°F(-20°C to 60°C):Humidity:0 to 93%RH _ - ---- -----LED Operation 1 On-board Green LED-Rashes when polled;On-board Red LED- Flashes when in alarm/active. Compatibilitywith Signature Loop Controller Use - ----_. Ag ency Listings ' UL,ULC,MEA.CSFM Ordering Information Catalog Ship Wt. Number Description lbs(kg) SIGA-CT1 Single Input Module 0.4(0.15)UUULCListed .._-- "............A, SIGA-CT1HT Single Input Module High Temperature Operation UUULC Listed _ 0.4(0.15) SIGA-CT2 Dual InputModule UVULC Listed 0.4(0.15)__.._ " - 0.1 (0.05) SIGA-MCT2 Dual Input Plug_In(UIO)Module -UL.ULC Listed -_.. -._- Related Equipment 27193-11 Surface Mount Box-Red,1-gang 1.0(0.6)_._ 27193— — 27193-18 Surface Mount Box-White,1-gang 1.0(0.6)_.. .- - --- ------- ----- - SIGA-U102R Universal Input-Output Module Board w/Riser Inputs 0.32(0.15) -Two Module Positions SIGH-U106R Universal Input-Output Module Board w/Riser Inputs 0.62(0.28) - Six Module Positions --- - ------------- SIGArUl06 Universal Input-Output Module Board -Six Module Positions 0_56(0.25) MFC-A Multifunction Fire Cabinet-Red,supports Signature Module 7.0(3.1) Mounting Plates SIGA-MB4 Transponder Mounting Bracket(allows for mounting 0.4(0.15) an two 1-gang modules in a 2-gg box) SIGA-MP1 Signature Module Mounting Plate.1 footprint SIGA-MP2 Signature Module Mounting Plate,1/2 footprint 0.5(0.23) -- -------- -SIGA-MP2L Signature Module Mounting Plate,1/2 extended footprint ----- 1.02(0.48) E85001-0241 Page 4 of 4 Issue 1 Intelligent Input/Output Control Relay Modules • SIGA-CR, SIGA-MCR, SIGA1-77-1 - 0 T CRR, SIGA-MCRR c41 � • e g .-i ��. SIGA-CP O U0 yl SIGA-MCR 4 MEA 730001-1621 57' °°5342 24 Overview Standard Features The Control Relay Module and the Polarity Reversal Relay Module • Provides one no/nc contact(SIGA-CR/MCR) are part of the Signature Series system.They are intelligent analog Form"0"dry relay contact can be used to control external ap- addressable devices available in either plug-in(UIO)versions, or pliances such as door closers,fans,dampers etc. standard 1-gang mount versions. • Allows group operation of sounder bases The SIGA-CR/MCR Control Relay Module provides a Form "C" The SIGA-CRR/MCRR reverses the polarity of its 24 Vdc out- dry relay contact to control external appliances such as door clos- put,thus activating all Sounder Bases on the data loop. ers, fans,dampers etc.This device does not provide supervision • Plug-in(UIO)or standard 1-gang mount of the state of the relay contact. Instead,the on-board micro- UIO versions allow quick installation where multiple modules processor ensures that the relay is in the proper ON/OFF state. are required.The 1-gang mount version is ideal for remote Upon command from the loop controller,the SIGA-CR/MCR relay locations that require a single module. activates the normally open or normally-closed contact. • Automatic device mapping The SIGA-CRR/MCRR Polarity Reversal Relay Module provides Signature modules transmit information to the loop controller a Form"C"dry relay contact to power and activate a series of regarding their circuit locations with respect to other Signature SIGA-AB4G Audible Sounder Bases. Upon command from the devices on the wire loop. Signature loop controller,the SIGA-CRR reverses the polarity of its • Electronic addressing 24 Vdc output,thus activating all Sounder Bases on the data loop. Programmable addresses are downloaded from the loop con- Standard-mount versions(SIGA-CR and SIGA-CRR)are troller,a PC,or the SIGA-PRO Signature Program/Service Tool; installed to standard North American 1-gang electrical boxes, there are no switches or dials to set. making them ideal for locations where only one module is re- • Intelligent device with microprocessor quired.Separate I/O and data loop connections are made to each All decisions are made at the module to allow lower corn- module. munication speed with substantially improved control panel Plug-in UIO versions(SIGA-MCR and SIGA-MCRR)are part response time and less sensitivity to line noise and loop wiring of the UIO family of plug-in Signature Series modules.They func properties,twisted or shielded wire is not required. tion identically to the standard mount versions, but take advantage of the modular flexibility and easy installation that characterizes all UIO modules.Two-and six-module UIO motherboards are available.All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in EDWARDS enclosures. Page 1 of 6 E85001-0239 Issue 1 Installation Application SIGA-CR and SIGA-CRR:modules mount to North American The operation of Signature Series control relays is determined by 21/2 inch(64 mm)deep 1-gang boxes and 1 Y2 inch(38 mm)deep their sub-type code or"Personality Code." 4 inch square boxes with 1-gang covers and SIGA-MP mounting Personality Code 8:CONTROL RELAY(SIGA-CR/MCR) - Dry plates.The terminals are suited for#12 to#18 AWG(2.5 mm2 to Contact Output.This setting configures the module to provide 0.75 mm2)wire size. one Form"C"DRY RELAY CONTACT to control Door Closers, eh Fans, Dampers,etc. Contact rating is 2.0 amp©24 Vdc;0.5 Compatible electrical box amp @ 120 Vac(or 0.25A it 220 Vac for non-UL applications). ' Personality Code 8 is assigned at the factory. No user configura- tion is required. ` Personality Code 8:POLARITY REVERSAL RELAY MODULE (SIGA-CRR/MCRR).This setting configures the module to re- 1 wan Pure,white verse the polarity of its 24 Vdc output.Contact rating is 2.0 amp ( (1-gang) 24 Vdc(pilot duty). Personality Code 8 is assigned at the factory. 'I( <:y/ No user configuration is required. ,:I /, Q. Compatibility J� 0., These modules are part of EDWARDS's Signature Series intelligent Status LEDs processing and control platform.They are compatible with EST3, EST3X and iO Series control panels. LED viewing ports • ^` � Le„......t.1, bets, Warnings & Cautions This module will not operate without electrical power.As fires fre- SIGA-MCR and SIGA-MCRR: mount the UIO motherboard quently cause power interruption,we suggest you discuss further inside a suitable EDWARDS enclosure with screws and wash- safeguards with your local fire protection specialist. ers provided. Plug the module into any available position on the motherboard and secure the module to the motherboard with the captive screws.Wiring connections are made to the terminals on Testing & Maintenance the motherboard(see wiring diagram). Ulo motherboard terminals are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2 wire size. The module's automatic self-diagnosis identifies when it is defec- tive and causes a trouble message.The user-friendly maintenance uio Motherboard program shows the current state of each module and other per- - 1 & tinent messages.Single modules may be turned off(deactivated) 32 1 sou-tapping temporarily,from the control panel.Availability of maintenance Elfeatures is dependent on the fire alarm system used. Scheduled - -0--„� maintenance(Regular or Selected)for proper system operation Plug-in(ulO) Captive be planned to meet the requirements of the Authority Hav- ing Jurisdiction(AHJ). Refer to current NFPA 72 and ULC CAN/ - i fl--� _ ULC 536 standards. I e6 Flat washers -CaInq or electrical enclosure — Electronic Addressing-The loop controller electronically ad- dresses each module,saving valuable time during system com- missioning.Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on- board memory.The loop controller identifies each device on the loop and assigns a"soft"address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool. EDWARDS recommends that this module be installed according to latest recognized edition of national and local fire alarm codes. E85001-0239 Page 2 of 6 Issue 1 Typical Wiring Modules will accept#18 AWG(0.75mm2),#16(1.0mm2), #14 AWG(1.50mm2)and#12 AWG(2.5mm2)wire sizes. Note:Sizes#16 AWG(1.Omm2)and#18 AWG(0.75mm2)are preferred for ease of installation.See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Normally Normally- Open Common Closed TB2 II''Ill 111 ll.I. 8 7 6 • e • 1 Red LED i Green LED (Alarm/Active) ® (Normal) I 321 I? TB1 'I II 111 II 4 I. Notes Q Refer to Signature Loop Controller Installation Sheet for wiring specifications. IIII ® NFPA 72 requires that the SIGA-CR/SIGA-MCR 1 DATA IN(-)DATA IN(+) �• DATA OUT(-)I DATA OUT(+) be installed in the same room as the device it is From Signature Controller To Next Device controlling.This requirement may not apply in all or Previous Device markets.Check with your local AHJ for details. A ®The SIGA-U106R and the SIGA-UIO2R do not SIGA-CR Control Relay come with TB1 a. ®The SIGA-U106 does not come with TB8 through TB13. Normally Open Common Normally Closed ®Supervised and power-limited. r ® If the source is nonpower-limited,maintain a space of 1/4 inch from power-limited wiring or use FPL, FPLP,FPLR,or an equivalent in accordance with the National Electrical Code. LICIPJ 7) Maximum#12 AWG(2.5mm2)wire. A+ 1 /� 1 2 3 4 Min.#18(0.75mm2. Data In_ Ara i mood 3 a S ,.u ' -_! ;>4 3 E l ; I3It. 2 .'1 • I ral2TB14Noconnections uiredfor + , required Data Out 1 MCR.Other modules may ' i r''' require connections. 'oe _ g la4 .-u I5 (\ 3 Green LED INormol ! ! z .>1 Red LED(Active! IrMseal; : T815 r1rlaEre A No connections required for MCR.Other modules may require connections. SIGA-MCR Control Relay Page 3 of 6 E85001-0239 Issue 1 Typical Wiring Modules will accept#18 AWG(0.75mm2),#16(1.0mm2),#14 AWG(1.50mm2)and#12 AWG(2.50mm2)wire sizes. Note:Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are preferred for ease of installation.See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. AB4G AB4G AB4G Audible Base Audible Base Audible Base /43 a n d\ /AD a s /19 a s a_ 6254A-003 I :. EOL Relay Listed 24VDC + © Nominal Power Wig . HUM ,. I py� it li a A Supply _ © Q © Q o• Q z jWI= 1_1 1 e e e e e e e CTl CR CRR © SIGA-CRR ® o i 0 0 0 0 Signature Controller . .A © Optional CR for disabling/disconnecting sounder base SIGA-MCRR SIGA-CRR Schematic SIGA-MCRR Schematic /® 0 0 ®\ a Pawe,n Foyer Out Fbb-M ReVas Power In power PowerOut pdmv. E625•A-003 WenA Ned I- - .la emnlw. } IP O t I 1 PPIPI/II Audible ? _} requrdfo r eases o = ` 3supeio e a S • Ilil11114 O a Q r- 'Ia1 km Ell Ia _,_,ter_,..I�4 3 2 �1 Q o 8 7 r Notes FA e . . DOM Out + ® Refer to the Signature controller installation sheet for For normal aperauon CTI • 1+ For Gerrr rin wiring. «} A `'`�_-.Ammo OWrdon 4 ®z 1� 8 One Pair of Wires(24 Vdc power). uuuic Listed 24 Vdc power — ® One Pair of Wires(Signature Data). soppy _ Of 'PI I''I' Single Wire(24 Vdc power). _} t zr 3• �0 23 &The SIGA-UIOBR and the SIGA-U102R do not come ,,,,,,,� :''�, r MUIR withT614. AA $wifi n1•Mem ua(R1serienmurboard 4 I>`, ®The SIGA-UIOB does not come with TBB through lam oar_ �;• A. 13, TB13. Nill( N.y, No connections required for Sgmtre ■_�f / 7B14 MCRR Other modules may ® Supervised and power-limited. unm i i ; tel N require connections. Onset® If the source is n empower-limtted,maintain a space , -of 1/4 inch from power-limited wiring or use FPL, 4.FPLP,FPLR,or an equivalent in accordance with the °000 6,— -w -" t Green LED Normal National Electrical Code. El Ned lEO(MIMI 9 Maximum 612 AWG(2.5 mrmR)wire:Minimum 618 llllllr� [ No connections required for ,wwrr re rsrre Naar. ' a z MCRR.Other modules may AWG(0.75 mmz). Green LED N+ormaq ■r■r' it}� require connections. End-of-Line Relay must monitor and report power Red<mCCOMM supply trouble to control panel. A ' A 11 Class B Data wiring may be'T-tapped., optiond moot or MIXfr No connections required for MCRR.Other disabbrgidisconnectig an audible hoe. modules may require connections- E85001-0239 Page 4 of 6 Issue 1 Specifications Catalog Number SIGA-CR SIGA-MCR 1 SIGA-CRA I SIGA-MCRR Description Control Relay Polarity Reversal Relay , Type Code Personality Code 8(Factory Set) i Personality Code 8(Factory Set) Address Requirements Uses 1 Module Address Operating Current ' Standby=75 µA Activated=75 µA Operating Voltage I 15,2 to 19.95 Vdc(19 Vdc nominal) Relay Type and Rating Form C,2 Mips 0 24 Vdc(pilot duty),0.5 Amps FP 120 Vac and 0.25 Amps @ 220 Vac(220 Vac is non-UL) Not rated for capacitive loads. Mounting North American 21/2 inch Plugs into U102R,U106R or North American 21/2 inch 1 Plugs into U102R,UIOSR or (64 mm)deep 1-gang boxes ' U106 Motherboards (64 mm)deep 1-gang boxes : U106 Motherboards and 111/2 inch(38 mm)deep . and 11/2 Inch(38 mm)deep 4 inch square boxes with : 4 inch square boxes with 1-gang covers and SIGA- 1 1-gang covers and SIGA- MP mounting plates i 1 MP mounting plates Construction&Finish High Impact Engineering Polymer Storage and Operating Operating Temperature:32°F to 120°F(0°C to 49°C) Environment Storage Temperature:-4°F to 140°F(-20°C to 60°C)Humidity:0 to 93%RH LED Operation On-board Green LED-Flashes when polled On-board Red LED-Flashes when in alarm/active Compatibility Use With:Signature Loop Controller Agency Listings . UL,ULC,CSFM,MEA Ordering Information Ship Weight-ibs Catalog Number Description ---..„A ow SIGA-CA Control Relay Module(Standard Mount) 0.4(0.15) SIGA-MCR Control Relay Module(U10 Mount) 0.18(0.08) SIGA-CRR Polarity Reversal Relay Module(Standard Mount) 0.4(0.15) SIGA-MCRR Polarity Reversal Relay Module(U10 Mount) 0.18(0.08) Related Equipment 27193-11 Surface Mount Box-Red, 1-gang 1 (0.6) 27193-16 Surface Mount Box-White,1-gang 1 (0.6) SIGA-U102R Universal Input-Output Module Board w/Riser Inputs-Two Module Positrons 0.32(0.15) SIGA-U106R Universal Input-Output Module Board w/Riser Inputs-Six Module Positions 0.62(0.28) SIGA-U106 Universal Input-Output Module Board-Six Module Positions 0.56(0.25) SIGA-AB4G Audible(Sounder)Detector Base 0.3(0.15) Accessories MFC-A Multifunction Fre Cabinet-Red,supports Signature Module Mounting Plates 7.0(3.1) SIGA-MB4 Transponder Mounting Bracket(allows for mounting two 1-gang modules in a 2-gang box) 0.4(0.15) SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5(3.7o) SIGA-MP2 Signature Module Mounting Plate,1/2 footprint 0.5(0.23) SIGA-MP2L Signature Module Mounting Plate,1/2 extended footprint 1.02(0.46) Page 5 of 6 E85001-0239 Issue 1 Signature Series Overview e t The Signature Series intelligent analog-addressable system from EDWARDS is an entire family of multi-sensor detectors and mounting bases,multiple-function input and output modules,network and non-network control panels,and user-friendly maintenance and service tools.Analog information from equipment connected to Signature devices is gathered and converted into digital signals.An onboard microprocessor in each Signature Contact us... device measures and analyzes the signal and decides whether or not to input an alarm. Email: edwards.firelfs.utc.com The microprocessor In each Signature device provides four additional benefits-Self-diag- Web: Edwards-fire.com nostics and History Log,Automatic Device Mapping,and Fast,Stable Communication. Self-diagnostics and History Log-Each Signature Series device constantly runs self- EDWARDS is a urc brand. checks to provide important maintenance information.The results of the self-check are Mebane, ne,NC 27302 Park Drive automatically updated and permanently stored in its non-volatile memory.This information Mebane.NC is accessible for review any time at the control panel,PC,or using the SIGH-PRO Igna- ®2016 United Technologies Corporation. ture Program/Service Tool.The information stored in device memory includes: All nights reserved. • Device serial number,address,and type •Time and date of last alarm •Most recent trouble code logged by the detector—32 possible trouble codes may be used to diagnose faults. Automatic Device Mapping-The Signature Data Controller(SDC)learns where each device's serial number address is installed relative to other devices on the circuit.The SDC keeps a map of all Signature Series devices connected to it.The Signature Series Data Entry Program also uses the mapping feature.With interactive menus and graphic support,the wired circuits between each device can be examined.Layout or"as-built" drawing information showing branch wiring(T-taps),device types and their address are stored on disk for printing hard copy.This takes the mystery out of the installation.The preparation of as-built drawings is fast and efficient. Device mapping allows the Signature Data Controller to discover: •Unexpected additional device addresses • Missing device addresses •Changes to the wiring in the circuit. Most Signature modules use a personality code selected by the installer to determine their actual function.Personality codes are downloaded from the SDC during system configu- ration and are indicated during device mapping. E85001-0239 Page 6 of 6 Issue 1 • Intelligent Input/Output q WARD S .i � , ' II ` +; I „A IA(;I. P4t-Il •High Power . mit . Control Relay - . _ Module SIGA-CRH El) I) Description Standard Features The SIGA-CRH High Power Control Relay Module is an address- • High Power Rating able device designed for interface applications that require a high 120/240 VAC or 24 VDC rated contact can be used to control voltage, high current relay.Two identical sets of relay terminals are external appliances such as door closers,fans,dampers etc. provided. Both sets of relay contacts transfer when the module • Provides one relay with two Form C contacts is activated or restored.The state of the output terminals is not Relay accepts 12 to 18 AWG(1.0 to 4.0 mm2)wiring from two supervised. sources The module requires one address on the signaling line circuit • Automatic device mapping (SLC).The address is assigned electronically.There are no ad- Signature modules transmit information to the loop controller dress switches to set. regarding their circuit locations with respect to other Signature devices on the wire loop. • Removable terminal blocks Easy wiring and module replacement. • Electronic addressing Programmable addresses are downloaded from the loop con- troller or PC;there are no switches or dials to set. • Intelligent device Distributed intelligence allows lower communication speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties;twisted or shielded wire is not required. Page 1 of E85001-0644 Issue 1.1 Application Installation Personality code Compatible electrical box Use Personality Code 8 to configure the SIGA-CRH module: Personality code 8:Signal-dry contact output.Configures ® SIGA-CRH the module as a dry relay contact to control external appli- ances(door closers,fan controllers,dampers)or equipment ! Wall plate shutdown. 0 i % ° �, -tee ---- l Indication \ / Irilli �° The status LED shows the state of the module through the cover vs l plate: o ° • Normal:Green LED flashes �� ° • Alarm/active: Red LED flashes e-_ Compatibility The SIGA-CRH is part of the Signature Series intelligent process- ing and control platform. It is compatible with EST3, EST3X,and C tion Sheet for details. i0 Series control panels. Warnings&Cautions Wiring The SIGA-CRH will not operate without electrical power.As fires frequently cause power interruption,we suggest you discuss further safeguards with your local fire protection specialist. (1) p o O EDWARDS recommends that this module be installed according —+ o to latest recognized edition of national and local fire alarm codes. ' ,,ill ill r� NC2 (4) 4I (3) C2 M'i (5) —(7) ' III Testing&Maintenance �I H NO2 I� (6) — SIGA-CRH automatic self-diagnosis identifies when it is defective I VI ' NC - (4) and causes a trouble message.The user-friendly maintenance t c), MITI (5) —(8) program shows the current state of each module and other per- III I NO`� (6) tinent messages.Single modules may be turned off(deactivated) o il�i — temporarily,from the control panel.Availability of maintenance +_ • features is dependent on the fire alarm system used. Scheduled (2) 0 o 0 CJ/') maintenance(Regular or Selected)for proper system operation should be planned to meet the requirements of the Authority Hav- ing Jurisdiction(AHJ).Refer to current NFPA 72 and ULC CAN/ (1) Signaling line circuit(SLC)from previous device ULC 536 standards. (2) Signaling line circuit(SLC)to next device (3) Power-limited and supervised (4) Normally closed contact(NC) Electronic Addressing (5) Common contact(C) The loop controller electronically addresses the SIGA-CRH,saving valuable time during system commissioning.Setting complicated (6) Normally open contact(NO) switches or dials is not required.The module has its own unique (7) Relay terminal set 2. serial number stored in its on-board memory. Not supervised.Power-limited unless connected to a nonpowerlimited source.If the source is nonpower-limited,eliminate the power-limited mark and maintain a minimum of 0.25 in.(6.4 mm)space from power-limited wiring.For other mounting methods,see enclosure and bracket installation sheets to maintain separation of power-limited and nonpower-limited wiring.The wire size must be capable of handling fault current from a nonpower-limited source. —or— Use type FPL,FPLR,FPLP,or permitted substitute cables,provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 In.(6.4 mm)space or by a nonconductive sleeve or nonconductive barrier from all other conductors.Refer to the NFPA 70 National Electrical Code for more details. (6) Relay terminal set 1.Identical to(7). E85001-0644 Page 2 of 4 Issue 1.1 Specifications Ordering Information SLC operating voltage 15.20 to 19.95 VDC Catalog Description Ship Weight SLC current Number lbs(kg) Standby 75 pA max. SIGA-CRH High Power Control Relay Module 0.4(0.15) Activated 75 pA max. Contact ratings[1][2] 240 V 50/60 Hz 7 A(PF 0.75), 1.5 A(PF 0.35) 120 V 50/60 Hz 7 A(PF 0.75),3.0 A(PF 0.35) 24 VDC 6 A resistive Audio switching 0 to 20 kHz[3] Relay type 2 Form C,programmable Relay ready delay 30 s max.(includes initial state set) From power up 5 s max.(one activation) From previous activation 8 s max.(two activations, 1 s apart) Circuit designation Signaling line circuits Class A,Style 6 or Class B,Style 4. Refer to the control panel technical publications for SLC wiring details. Relay circuits Class E Number of SIGA-CRH per SLC 60 max. Wire size 12 to 18 AWG(1.0 to 4.0 mm2) North American double-gang x 2-1/8 Compatible electrical boxes in.(54 mm)deep box North American standard 4 in.square x 2-1/8 in.(54 mm)deep box Agency Listings CAWULC-S527, UL 864 Operating environment Temperature 32 to 120°F(0 to 49°C) Relative humidity 0 to 93%,noncondensing Storage temperature -4 to 140°F(-20 to 60°C) [1] Provide external fusing and back-EMF mitigation as required by your application.Do not use the SIGA-CRH in a mixed application, where one set of relay terminals has high-power requirements and the other set carries a low-power signal,as this may result in physical contamination of the low-power signal contacts. [2] The minimum load required in order to avoid long-term contact oxidation is 100 mA and 12 V. [3] Power must not exceed the contact ratings shown for a given PF (power factor). Page 3 of 4 E85001-0644 Issue 1.1 Strobes,Horns,Bells,Chimes cEstiWARD Wall Mount ::..•.........•.• .: • Signaling '••••••••••••• ...•.......... F Appliances Genesis LED G4 Seriescous sz1a, 85.989 111 n co 110 I .,I FC Overview Standard Features Genesis LED G4 Series horns and LED strobes feature a sleek • High Performance LED Strobe Technology low profile design and energy-efficient technology that makes -Ultra low device current consumption allows: them less expensive to install and operate by reducing overhead. -More devices per circuit High performance LEDs require fewer power supplies, backup -Ability to use lower gauge wire power, and batteries.These new appliances are designed with, -Longer wire runs energy-efficiency,and life safety in mind. -Fewer booster power supplies - Genesis LED G4 Series uses high efficiency optics, combined High efficiency optics - with patented electronics,to deliver a highly controlled and Selectable 15,30, 75, or 110 cd light output efficiently focused light distribution pattern in exchange for - LED devices may be mixed with legacy Xenon strobes lower current requirements.Strobes feature field-selectable • Efficient Audible Output 15, 30,75,or 110 cd light output. -Selectable high or low dB horn output -Selectable temporal or steady horn output Compared with Xenon-type strobes,Genesis LED G4 Series -Improved audio frequency range for better wall penetration appliances need fewer power supplies and often smaller wire gauge,which lightens conduit requirements.They are also • Low-profile Design backwards compatible with legacy strobes,so there's no need to -Ultra-slim...protrudes about 1.5"from the mounting surface replace all your existing devices to upgrade to new LED technology. -Attractive appearance...no visible mounting screws In fact,G4 strobes can be mixed on the same circuit and used in • Multiple"FIRE" Marking Options the same field of view as Xenon-based strobes.This makes Genesis -Order English,French,Spanish or no FIRE markings LED G4 Series ideal for new installations and retrofits alike. -Change markings at any time with replaceable Field-configurable sound output levels provide the flexibility quick-swap covers modern life safety projects demand,while the Genesis LED • Easy to Install control protocol keeps multiple strobes on compatible NAC -Pre-install and pre-wire with convenient universal room circuits synchronized to well within NFPA 72 requirements. side wiring plate Serviceability is another area where G4 Series appliances shine. Check electrical continuity on room side wiring plate with The universal room side wiring plate allows for pre-installation included diagnostics check bar and electrical wiring as well as checking continuity with the -Diagnostics port streamlines device circuit testing included diagnostics check bar.G4 Series devices can then be -Fits 1-gang,2-gang,3.5-inch octagon,and 4-inch square easily snapped into place with the confidence of knowing the electrical boxes wiring is correct.The innovative under-cover diagnostic test points -Optional red and white trim plates available provide easy access to device circuit testing while mounted. -Slide switches for field configuration -12 to 18 AWG in-out screw terminals for quick wiring Page 1 of 6 E85001-0668 Issue 1.1 Application Genesis LED G4 Series horns,strobes,and horn-strobes mount to pp any standard one-gang,two-gang,3.5-inch octagon,and 4-inch Strobes square electrical box.Matching optional G4T trim rings are available Genesis G4 Series strobes are UL 1971-listed for use indoors as to cover oversized openings.Optional color matched double-gang wall-mounted public-mode notification appliances for the hearing surface boxes are also available. impaired. Prevailing codes require strobes to be used where ambient noise conditions exceed 105 dBA(87 dBA in Canada), Double Gang Electrical Box where occupants use hearing protection,and in areas of public accommodation as defined in the Americans with Disabilities Act. :rllt F \ • Trim Plate(optional) Synchronization is important in order to avoid triggering seizures `r® in people with photosensitive epilepsy.All Genesis strobes exceed UL synchronization requirements(within 10 milliseconds over a Se Mounting Plate two-hour period)when used with a synchronization source.See ) - �, the specifications table for a list of compatible sources. \ , Machine Screw i ♦� ♦ !P V Signaling Appliance 0 ° �7i' (i Horns � , '�'�� 11 Genesis horn output reaches as high as 92 dBA and features an I''.q.;,.4e, 11 ,10°,11P improved audio frequency range compared with other Genesis Ji'� l�iJ� ' i \ 11111.1 horns.This results in excellent sound penetration through walls and �� i a clear warning of danger.Horn only models may be configured for either coded or non-coded notification appliance circuits.They can ,;v'I / ,i 1 also be set for high or low dBA output.This setting reduces horn \�*a Shorting Clip l ' output by about 6 dBA.Horn only models may be ceiling mounted ,, or wall-mounted. j ,�. The suggested sound pressure level for each signaling zone used \ d iis�i),o Optional Trim Plate with alarm signals is at least 15 dBA above the average ambient I�r Using a trim plate is optional. sound level,or 5 dBA above the maximum sound level having a `�;r- duration of at least 60 seconds,whichever is greater.These values 3.5-inch Octagon Electrical Box are measured at five feet(1.5 m)above the floor.The average ambient sound level is A-weighted,fast response sound pressure measured over a 24-hour period. Doubling the distance from the signal to the ear will theoretically ` result in a 6 dBA reduction of the received sound pressure level. ' .; The actual effect depends on the acoustic environment in the space. A 3 dBA difference represents a barely noticeable change in volume. Installation I4,.f `'', -- Genesis G4 horns and strobes mount to the required GP10 room Two-gang Electrical Box One-gang Electrical Box side wiring plate.The GP10 mounting plate is ordered separately from the G4 device In packs of 10 for convenient pre-installing and pre-wiring.The device can be removed easily from the room side wiring plate by pushing up with a screwdriver.The cover can also Wiring be removed from the device easily with a screwdriver to access the light and sound output settings and a diagnostics test port for voltage testing. `%, O O O Ji Removing Cover Removing Device CO 0 7 7 l'Ili --' \\ / Horn/strobe + +Horr✓strobe ci cu tIn _ 1II1 1 _ circukout(3gna polarityir2jr�p ^I�IliOI showninthe •+� ]���} I�.�OIO�O�O� � activecondttion) ' l '.( L�' .ill:: 1--Stab g Clip 'III ` h � � CPA j r hP ”in II i RI / �.�' ' 1 _ I E85001-0668 Page 2 of 6 Issue 1A Dimensions Field Configuration G4 Notification Appliances Temporal horn and horn-strobe models are factory set to sound in 1.62' a three-pulse temporal pattern. By sliding the tone selector switch, (4.11 cm) 4.95" horn only models may be configured for constant horn output that (12.57 cm) can be coded at precise intervals by EDWARDS control panels and I control modules. •e°00.00000.., 00000o.°e°s•,•,.0000_„_0000 .°. Note:Temporal 3 coding is the required output for fire not fication ee,•,00o0e,�,eoo0o0°,e,o°e, oeoo°,,;,000mo°°, ,. devices per NFPA 72.Any device coding other than temporal .....o000oe' '00000.°°•°' 3 is at the discretion and approval of the local authority having 0 0 . 00 . . . ▪ o °000000.1400000°.".°••.o...00000�.� 000000.°e°sjurisdiction(AHJ). • • .°0006o0,„o000.,,. . o e.e.•,.0000 ..Op0000..•.° 5 76 Horns and horn-strobes are factory set for high dB output. Low s°ee°,000O OG . O . e f ..00o0°9'_•_:;0000°0°..... ) dB outputmaybysliding e ° o o e0o o °•.°. (1 a.sfi cm be selected the tone selector switch. e,•,•,00000,,:,0000 0,.•.,. This reduces the output by about 6 dBA. °e,°,0000oe0a00000,.,o°e /` Genesis LED clear strobes and hom-strobes may be set for 15, MII 30,75, or 110 candela output.The output setting is changed by /Ai"m'erd % IIIII ,,/� _ simply removing the cover and sliding the candela switch to the desired settin .The device does not have to be removed from the wall to change the output setting.The setting remains visible through a small window on the left-hand side of the device after the cover is closed. G4T Trim Plate(optional) Light and Sound Output Settings 0.3" (0.76 cm) 5.6" // �J F (14.22 cm) 1 1 5, - M . �o o� o \(19.05 cm) (5)- - (1) (6)— se-LOW l ea•NW — (2) (7)— T4T-L„ — (3) O o 0 o O (8)— ' :. I — (4) (1)Constant,low dB (5)110 candela J (2)Constant,high dB (6)75 candela (3)T3 temporal,low dB (7)30 candela (4)T3 temporal,high dB (8)15 candela Diagnostics Operating current 4111 Horns Strobes Sound 16to33 16to33 Strobe 16to33 16to33 -_I' fMIMMENNEMI) setting VDC VFWR setting VDC VFWR _._._._ �` C-Low. 15,30, +0 _id T Low 18 mA 22 mA 75, 110 28 mA 36 mA ��I _ — — 0 ' i' T--High, — ;', 11 C.�� ©J T--High 28 mA 38 mA \`',��� - Horn-Strobes ILrt-ri-'4I setting Sound setting 16 to 33 VDC 18 to 33 VFWR 15,30, C-Low,T-Low 40 mA -_--_ 48 mA Test points indicated above are used to validate the 75, 110 C-High,T-High 50 mA 60 mA Notification Appliance Circuit and verify device function. Page 3 of 6 E85001-0668 Issue 1.1 Sound Output Light Distribution Horn&Horn-Strobe H ° Horizontal Right Horizontal Left is Io 1 5 10 15 Reverberant Anechoic zs 20 20 Sound setting (UL464) (CAN/ULC-5925) 3s 30 460 25 10 35 C-Low,T-Low 80 dBA 86 dBA 40 140 40 45 45 C-High,T-High 85 dBA 92 dBA so so 55 55 1130.4 .. 60 60 1 65 I g0 65 70 • 70 i 60 75 ♦ 75 Sound pattern(ULC) so 40 80 85 20 1 85 Axis Angle Change in output 135°and 45° -3 dBA -c as Horizontal 150°and 30° -6 dBA so 135°and 40° -3 dBA • 75 Vertical 150°and 30° -6 dBA 70 60 55 50 45 . 40 35 30 0 5 10 is 20 25 Vertical Bottom Measured UL Minumum Specifications Operating voltage 16 to 33 VDC,16 to 33 VFWR Horn signal type ---Constant or TC3 temporal Light output 15,30,75,or 110 candela Strobe flash rate 1 fps(flash per second)approx. _ . _____ Synchronization to fl max.between any two devices.To determine allowed wire resistance,refer to these specifications,and the specifications for the synchronized signal source. Synchronization Sources Edwards CC Series Signal Modules,Booster and Auxiliary Power Supplies, Intelligent and Conventional Control Panels Wire size 12 to 18 AWG(0.75 to 2.50 mm2) __ Dimensions(WxHxD) 4.95 x 5.78 x 1.62 in(12.57 x 14.68 x 4.11 cm) Strobe-to-box center offset -1.70 inches(-4.32 cm) Compatible electrical boxes[1] 1-gang,2-gang,3.5-Inch octagon,4-inch square -- —_ Trim plates G4TR,G4TW(5.6 x 7.5 x 0.3 in(14.22 x 19.05 x 0.76 cm)) Operating environment Temperature 32 to 122°F(0 to 50°C) Relative humidity 0 to 93%noncondensing Storage Temperature -40 to 158 F(-40 to 70 C) (tl Electrical boxes must be at least 1-1/2 In.(3.81 cm)deep. E85001-0668 Page 4of8 Issue 1.1 Ordering Information FOR REFERENCE ONLY Notification Appliances Color Marking Replacement Appliance Covers Color Marking . . G4ARF Red FIRE G4ARA-CVR Red ALERT G4ARF-CVR Red FIRE G4ARF-FR Red FEU G4ARF-FR-CVR Red FEU G4ARN G4AWF 111 G4ARF-SP Red FUEGO G4ARF-SP-CVR Red FUEGO Red White None FIRE _ . G4ARN-CVR G4AWA-CVR . .. Red None White ALERT Horns G4AWF-FR White FEU Horn G4AWF-CVR White FIRE G4AWF-SP White FUEGO Covers G4AWF-FR-CVR White FEU G4AWF-SP-CVR White FUEGO G4AWN White None G4AWN-CVR White None G4VRF Red FIRE G4VRA-CVR Red ALERT _.. . . _ . .. . G4VRF-FR Red FEU G4VRF-CVR Red FIRE G4VRF-SP Red FUEGO G4VRF-FR-CVR Red . FEU .G4VRF-SP-CVR Red FUEGO.4.......A G4VRN Red None G4VRN-CVR Red None it-*- G4VWF VVhite FIRE — — G4VWA-CVR White ALERT Strobes G4VWF-FR White FEU _ Strobe G4VWF-CVR White . FIRE _ G4VWF-SP White FUEGO Covers G4VWF-FR-CVR White FEU G4VWN White None G4VVVF-SP-CVR White FUEGO G4VWN-CVR White None G4AVRF Red FIRE _G4AVRF-FR Red G4AVRA-CVR Red ALERT FEU ---- G4AVRF-CVR Red FIRE G4AVRF-SP Red FUEGO _ G4AVRF-FR-CVR Red FEU G4AVRN lit Red None G4AVRF-SP-CVR Red FUEGO G4AVWF White FIRE : AN, G4AVRN-CVR G4AVWA-CVR Red None White ALERT Horn-strobes G4AVWF-FR White FEU Hom-strobe G4AVWF-CVR White FIRE G4AVWF-SP White FUEGO Covers G4AVWF-FR-CVR White FEU G4AVWN White None G4AVVVF-SP-CVR White FUEGO G4AVWN-CVR White None Accessories Room Side Wiring • • ri plate, eries, Trim plate,G4 Series, 4111 GP10 Plate(required, ,..---, G4TR TmG4 S i G4TVV. .... red white ordered separately) 27193-21 Two-gang surface 27193-26 Two-gang surface mount box,red mount box,white .. _. ._ Model Number Syntax, Appliances Model Number Syntax, Replacement Covers —Genesis Series G4=Wall mount appliances —Genesis Series G4=Wall mount appliances Housing Color R=Red • Housing Color R=Red W=White W=White I 1 G4AVRF Housing Marking IG4AVRF-CVR Cover Designation T Functions N=None F-FR=FEU F-SP=FUEGO F=FIRE 'ALERT Marking available on white strobe model only. See replacement T Cover Marking N=None A=Horn only A=ALERT. covers for more Functions F-FR=FEU A=Horn only F-SP=FUEGO V=Strobe only options. V=Strobe only F=FIRE AV=Hom-Strobe AV=Hom-Strobe A=ALERT Page 5 of 8 E85001-0668 Issue 1.1 Strobes,Horns,Bells,Chimes Genesis LED GC Series • Ceiling Mount •'•'•'•'•'•'•'• • • • • • • Notification Devices � ' ••••••• . • ,,i-ll . .•.•S•.•••. hl • . • . '.• e �L1u S21 e. S5389 115. NV tom. FC Overview Standard Features Genesis LED GC Series horns and LED strobes feature a sleek • High Performance LED Strobe Technology low profile design and energy-efficient technology that makes -Ultra low device current consumption allows: them less expensive to install and operate by reducing overhead. -More devices per circuit High performance LEDs require fewer power supplies, backup -Ability to use lower gauge wire power,and batteries.These new appliances are designed with, -Longer wire runs energy-efficiency,and life safety in mind. -Fewer booster power supplies Genesis LED GC Series uses high efficiency optics,combined -High efficiency optics with patented electronics,to deliver a highly controlled and -Selectable 15,30, 75,or 115 cd light output efficiently focused light distribution pattern in exchange for -LED devices may be mixed with legacy Xenon strobes lower current requirements.Strobes feature field-selectable • Efficient Audible Output 15, 30,75,or 115 cd light output. -Selectable high or low dB horn output -Selectable temporal or steady horn output Compared with Xenon-type strobes,Genesis LED GC Series -Improved audio frequency range for better wall penetration appliances need fewer power supplies and often smaller wire gauge,which lightens conduit requirements.They are also • Low-profile Design backwards compatible with legacy strobes,so there's no need to -Ultra-slim... protrudes about 1.5"from the mounting surface replace all your existing devices to upgrade to new LED technology. -Attractive appearance... no visible mounting screws In fact,GC strobes can be mixed on the same circuit and used in • Multiple"FIRE" Marking Options the same field of view as Xenon-based strobes.This makes Genesis -Order English, French,Spanish or no FIRE markings LED GC Series ideal for new installations and retrofits alike. -Change markings at any time with replaceable Field-configurable sound output levels provide the flexibility quick-swap covers modern life safety projects demand, while the Genesis LED • Easy to Install control protocol keeps multiple strobes on compatible NAC -Pre-install and pre-wire with convenient universal room circuits synchronized to well within NFPA 72 requirements. side wiring plate Serviceability is another area where GC Series appliances shine. -Check electrical continuity on room side wiring plate with The universal room side wiring plate allows for pre-installation included diagnostics check bar and electrical wiring as well as checking continuity with the -Diagnostics port streamlines device circuit testing included diagnostics check bar.GC Series devices can then be -Fits 1-gang,2-gang,4-inch octagon,and 4-inch square easily snapped into place with the confidence of knowing the electrical boxes wiring is correct.The innovative under-cover diagnostic test points -Optional red and white trim plates available provide easy access to device circuit testing while mounted. -Slide switches for field configuration -12 to 18 AWG in-out screw terminals for quick wiring Page 1 of 6 E85001-1 021 Issue 1 Application Genesis LED GC Series horns,strobes,and horn-strobes mount pp to any standard one-gang,two-gang,4-inch octagon,and 4-inch Strobes square electrical box.Matching optional GCT trim rings are available Genesis GC Series strobes are UL 1971-listed for use indoors to cover oversized openings.Optional color matched double-gang as ceiling-mounted public-mode notification appliances for the surface boxes are also available.Genesis LED GC series are listed to hearing impaired.Prevailing codes require strobes to be used be both wall mounted or ceiling mounted. where ambient noise conditions exceed 105 dBA(87 dBA in Canada),where occupants use hearing protection, and in areas of public accommodation as defined in the Americans with (1) - C.) Disabilities Act. \ I Synchronization is important in order to avoid triggering seizures in people with photosensitive epilepsy.All Genesis strobes exceed �'�' UL synchronization requirements(within 10 milliseconds over a I two-hour period)when used with a synchronization source. See (2)-„, I I the specifications table for a list of compatible sources. Horns Genesis horn output reaches as high as 92 dBA and features an I I improved audio frequency range compared with other Genesis horns.This results in excellent sound penetration through walls and a clear warning of danger. Horn only models may be configured for (3) 1 +�I either coded or non-coded notification appliance circuits.Theycan \ ■�1�" PP — .e, also be set for high or low dBA output.This setting reduces horn / J output by about 6 dBA. I '` -='i-P. I The suggested sound pressure level for each signaling zone used (4)\1 with alarm signals is at least 15 dBA above the average ambient 5) sound level,or 5 dBA above the maximum sound level having a ( '',0111111111111111111111111111111111111111 duration of at least 60 seconds,whichever is greater.These values are measured at five feet(1.5 m)above the floor.The average ;4, iiiiii / ambient sound level is A-weighted,fast response sound pressure '.. �t4 - ,-�� measured over a 24-hour period. l *. , !�,� Doubling the distance from the signal to the ear will theoretically � (1)Electrical Box result in a 6 dBA reduction of the received sound pressure level. (2)Trim Plate(optional) The actual effect depends on the acoustic environment in the space. (3)wiring plate(required,ordered separatery) A 3 dBA difference represents a barely noticeable change in volume. (4)Machine screw(2X,supplied with wiring plate) (5)GC signaling appliance Installation Genesis GC horns and strobes mount to the required GP10 room side wiring plate.The GP10 mounting plate is ordered separately Wiring from the GC device in packs of 10 for convenient pre-installing and pre-wiring.The device can be removed easily from the room side wiring plate by pushing up with a screwdriver.The cover can also be removed from the device easily with a screwdriver to access the Q Q Q light and sound output settings and a diagnostics test port for voltage testing. 0' 0 Horn/Strobe + +Horn/strobe circuit in _ Y 11 II I - circuit out Removing Device (signal polarity I IG-a; Iololor RemovingCover :i ( ( • shown in the . . �"{;� + �_I'.IO�O�❑� �,,,,,,e„�, il/ active condition) l - ' `111 �1lil! [Iil 4—Shorting Clip J P1111 III1çi u X E85001-1021 Page 2 of 6 Issue 1 Dimensions Field Configuration GC Notification Appliances Temporal horn and horn-strobe models are factory set to sound in 1 s2" a three-pulse temporal pattern.By sliding the tone selector switch, (4.62 cnl) 6.8' horn only models may be configured for constant horn output that (17.27 cm) can be coded at precise intervals by EDWARDS control panels and control modules. ���, Note:Temporal 3 coding is the required output for fire notification devices per NFPA 72.Any device coding other than temporal ' ' i . 1 ' \ 3 is at the discretion and approval of the local authority having o •0- oe - _ 1J�1 't I °;•'•'•�•'•co tO ) Horns and horn-strobes are factory set for high dB output. Low °°••:'!^•'�° dB output may N��. ``� o o •.••...•o° „ � p be selected by sliding the tone selector switch. 11�!_ YJ. o'. '0 11, s�' This reduces the output by about 6 dBA. 000 . ° • oo ° coo 0000�. ° °° °°'°° Genesis LED clear strobes and horn strobes may be set for 15, 30,75,or 115 candela output.The output setting is changed by I o simply removing the cover and sliding the candela switch to the I �� desired setting.The device does not have to be removed from the wall to change the output setting.The setting remains visible through a small window on the device after the cover is closed. GCT Trim Plate(optional) Light and Sound Output Settings (0.76 an) 10.6' IIAW (1) 1urgK3H (21 �'� (31 I,:�.�II �� IGH j (4) ho 0 0 .0Q) v^ _',,�/4 a / 1 O O - O cI , �;` (5) (1)Constant,low dB �� �1� (6) (2)Constant,high dB : (3)T3 temporal,low dB � �91 O l ' (7) (4)T3 temporal,high dB " (6) `�,`,. .,',`'2 (6)75candela Ir.. `/♦, (7)30 candela ``! /'� (8)15 candela s_=- Diagnostics Operating current A►b -'"' Horns Strobes Sound 16 to 33 16 to 33 Strobe 16 to 33 16 to 33 iiP4, 1,ii ' settingVDCVFWRsettingVDCVFWR15,30, k ���� i T-Low 20 mA 25 mA 75,115 35 mA 45 mA C H' h, \\ /j'% immil T-High 30 mA 40 mA �® ® Horn-Strobes Test points indicated — Abe above are used to validate setting Sound setting 16 to 33 VDC 16 to 33 VFWR the Notification Appliance 15,30, C-Low T-Low 50 mA -- 60 mA Circuit and verify device function. 75, 115 -__-__------C+igh'T Hgh------ 60 mA 75 mA Page 3 of 6 E85001-1021 Issue 1 Sound Output Light Distribution Horn&Horn-Strobe Horizontal Left o Horizontal Right Reverberant Anechoic 15 10 20 AG - 5 10 15 20 Sound setting 25 25 30 ‘ 30 (UL464) (CAN/ULC-6925) 35 • . 35 C-Low,T-Low 80 dBA 86 dBA 45 40 \A\ \_-:• 40 45 C-High,T-High 86 dBA 92 dBA 50 55 \ \ .•, es 60 65 f•- 7,,,,,,, 4 L „ ,,, 66 70 7575 Sound pattern-Horn Models(ULC) BO ,_ .4.',.• \;NVI f i.•'•',"' oo 85 _. Ma. -'ai,...p.....4t......,-..••. •,.. 85 Axis Angle(°) Output(dBA) ' Horizontal 115 and 55 93.9- oo 85 - .. 85 Vertical 125 and 50 91.7 80 c , so .. ...-,...• - N\ 70 - --'-'-- '- ej* •, ‘‘.4. 70 65 (,,,,.,,-1 .,, 80 ,..\ „ / , , 80 / 55 Sound pattern-Horn-Strobe Models(ULC) 50 <</ ,, 50 45 Axis Angle(1 Output(dBA) 40 / / , "-{ , / ! I 3°35' 4° 145 and 35 93.0 Horizontal 3°2'5'20-• 1 1 1 20 25 155 and 35 90.8 0 5 10 15 Vertical Bottom 135 and 35 92.0 Vertical 155 and 25 85.4 ..,-- Measured — — — UL Minumum Specifications Operating voltage 18 to 33 VDC,16 to 33 VFWR Horn signal type Constant or TC3 temporal Light output 15,30,75,or 115 candela Strobe flash rate 1 fps(flash per second)approx. 20 fl max.between any two devices.To determine allowed wire resistance,refer Synchronization to these specifications,and the specifications for the synchronized signal source. Edwards CC Series Signal Modules,Booster and Auxiliary Power Supplies, Synchronization Sources Intelligent and Conventional Control Panels Wire size 12 to 18 AWG(0.75 to 2.50 mm2) Mounting Wall or Ceiling mount Dimensions(0 x D) 6.8 x 1.82 In.(17.27 x 4.62 cm) Strobe-to-box center offset -1.70 inches(-4.32 cm) Compatible electrical boxes[1] 1-gang,2-gang,4-inch octagon,4-inch square Trim plates GCTR,GC1W 10.8 x 0.3 In.(26.92 x 0.76 cm) Operating environment Temperature 32 to 122°F(0 to 50°C) Relative humidity 0 to 93%nonconciensIng Storage Temperature -40 to 158 F(-40 to 70 q 1[1]Bectrical boxes must be et least 1-1/2 in.(3.131 cm)deep. Page 4018 E85001-1 021 Issue 1 Ordering Information Notification Appliances Color Marking Replacement Appliance Covers Color Marking GCARF Red FIRE GCARA-CVR Red ALERT GCARF-FR Red FEU GCARF-CVR Red FIRE GCARF-SP Red FUEGO GCARF-FR-CVR Red FEU GCARFSP-CVR Red FUEGO GCARN Red None GCARN-CVR Red None GCAWF White FIRE GCAWA-CVR White ALERT Horns GCAWF-FR White FEU Horn GCAWF-CVR White FIRE Covers GCAWF-SP White FUEGO GCAWF FR CVR White FEU GCAWF-SP-CVR White FUEGO GCAWN White None e GCAWN-CVR White Nonee GCVRF Red FIRE GCVRA-CVR Red ALERT GCVRF-FR Red FEU GCVRF-CVR Red FIRE GCVRF-SP Red FUEGO GCVRF-FR-CVR Red FEU - _ GCVRFSP-CVR Red FUEGO GCVRN Red None � r - -- - -- _ --- - GCVWF White ARE GCVRN CVR Red None GCAWA-CVR White ALERT Strobes GCVWF-FR White FEUStrobe GCVWF-CVR White FIRE GCWVFSP White FUEGO Covers GCVWF-FR-CVR White FEU GCWVN White None GCAWF-SP-CVR White FUEGO GCVWN-CVR White None GCAVRF Red FIRE --- --_-- --.- GCAVRA-CVR Red ALERT GCAVRF-FR Red FEU --- _.----. GCAVRF-CVR Red FIRE GCAVRFSP Red FUEGO —....--- N GCAVRF-FR-CVR Red FEU m • Fr� GCAVRN Red None i GCAVRF-SP-CVR Red FUEGO GCAVWF White FIRE GCAVRN-CVR Red None 4. GCAVWA-CVR White ALERT Horn-strobes GCAVWF-FR White FEU .. -- ----- Horn-strobe GCAVWF-CVR White FIRE GCAVWFSP White FUEGO Covers GCAVWF-FR-CVR White FEU GCAVWN White None GCAVWF-SP-CVR White FUEGO GCAVWN-CVR White None Accessories AORoom Side Wiring GP10 Plate(required, 0.' GCTR Trim plate,GC Series, GC W Trim plate,GC Series, ." .r ordered separately) red white 27193-21 Two-gang surface 27193-26 Two-gang surface mount box,red mount box,white Model Number Syntax, Appliances Model Number Syntax, Replacement Covers r Genesis Series GC=Ceiling mount appYances Genesis Series 6si=Ceiag mount appliances r Housing Colorp=Red Housing Color W=White R=Red W-White GCAVRF Housing Marking I r Cover I I N=None .,,,�� GCAVRF-CVR Designation F-FR=FEU available on Marking FSP=FUEGO white I Cover Marking Functions F=RRE See replacement N=Nona A=Horn only A=ALERT' covers for more Functions F-FR=FEU V=Abe only options. A=Han way FSP=FUEGO AV=Hom-Strobe V=Strobe only F=flRE AV=Horn-Strobe A=ALERT Page 5 of 6 E85001-1021 Issue 1 Strobes, Horns,Bells,Chimes cg-bliVAR D S �1 l� Field Configurable ': _CeilingStrobes r'f'TT Genesis Series F> Fe ('„j LC Ir�l MEA (E 7125-1 02197 95389 Overview Standard Features Genesis fife safety and mass notification/emergency communica- • Field configurable—no need to remove the device! tions(ECS/MNS)ceiling strobes are small,compact, and attractive — 15/30/75/95 cd and 95/115/150/177 cd clear strobe lens visible emergency signaling devices. Protruding no more than 1.6" models available (41 mm)from the ceiling,Genesis strobes blend with any decor. — Switch settings remain visible even after the unit is installed Thanks to patented breakthrough technology, EDWARDS Gen- • ECS/MNS models available esis strobes do not require bulky specular reflectors and lenses. — Amber and blue lens models available. Instead,an exclusive cavity design conditions light to produce See Ordering Information for details. a highly controlled distribution pattern.Significant development • Unique low-profile design efforts employing this new technology have given rise to a new — 30 per cent slimmer profile than comparable signals benchmark in strobe performance—FuIlLight technology. — Attractive appearance FullUght strobe technology produces a smooth light distribution — No visible mounting screws pattern without the spikes and voids characteristic of specular — Available with white or red housings reflectors.This ensures the entire coverage area receives consis- • y to install tent illumination from the strobe flash.As a result,Genesis strobes — Fits all standard 4"square electrical boxes with plenty of with FullUght technology go well beyond the minimum UL-required room behind the signal for extra wire—no extension ring or "cross"pattern,significantly exceeding UL-1971 and ULC-S526 trim plate needed light distribution requirements. — #18 to#12 AWG terminals—ideal for long runs or existing wiring Depending on the model, clear lens Genesis ceiling strobes fea- • Unparalleled performance ture 15 to 95, or 95 to 177 candela output(see ordering informa- — Exclusive FullLight strobe technology produces the industry's tion),which is selectable with a conveniently-located switch.The most even light distribution candela output setting remains clearly visible even after final instal- — Precision timing electronics meet tough synchronizing lation,yet it is locked in place to prevent unauthorized movement standards for strobes after installation. — Low current draw minimizes system overhead Genesis ECS/MNS appliances offer emergency signaling with • Approved for public and private mode applications clear amber or blue lenses.They are ideal for applications that re- — UL 1971-listed as signaling devices for the hearing impaired quire differentiation between life safety and mass notification alerts. — UL 1638-listed as protective visual signaling appliances — UL/ULC listed for ceiling or wall use Page 1 of 4 E85001-0557 Issue 2.1 Application Dimensions Genesis strobes are UL 1971 or 1638 listed for indoor use.Prevailing 6.8"dia. codes require strobes to be used where ambient noise conditions (173 min) i exceed specified levels,where occupants use hearing protection, 1.0• and in areas of public accommodation.Consult with your Authority (251 m) Having Jurisdiction for details. All Genesis strobes exceed UL synchronization requirements (within 10 milliseconds over a two-hour period)when used with a synchronization source.Synchronization for multiple strobe lights in a single field of view is required. ECS/IVINS Applications Genesis ECS/MNS appliances bring the same high-performance life Light output (effective cd) safety features and unobtrusive design to mass notification applica- Percent of UL rating versus angle tions.Available as standard units with clear,amber or blue lenses Percentage of rated output -- with optional ALERT markings,they are ideal for applications that 1p 110 100 ao 80 TO 80 m o w JO 20 1 20 30 40 SO BO ,0 90 00 100 110 1mgy. require differentiation between life safety and ECS/MNS signals. — Units are also available(special order)with red or green lenses. 5k is Installation -� /-• All models are intended for indoor applications only.Strobes mount to any flush North-American 4"square electrical box,2'4" 45, (54 mm)deep. Genesis ceiling strobes simply unlatch and twist to open.This • 30' gains access to mounting screws and the selectable candela -15• 0, 15' switch.The shallow depth of Genesis devices leaves ample room ---Aogm---- behind the signal for extra wiring.Once installed with the cover in Horizontal and vortical outputs railed Ma alma Patton,. place, no mounting screws are visible. O O O 0•• 'IN Field Configuration 0 0 0 0• i - - Depending on the model,Genesis ceiling r v speaker-strobes have multi-candela output Candela switch 0 ;'` (see ordering information).The output / 1 !� setting is changed by simpy opening the V �1. °,:iii^"$�c'•s I device and sliding the switch to the desired ` • 1�" .'"'Kf ,•; !l setting. The strobe does not have to be µ:��• / removed to change the output setting. r `. i:i•v`: :• , •ti`^ ;r'.j The setting remains visible through a small ` Indicator � window on the front of the device after the cover is closed. Wiring Field wiring terminals accommodate#18 to#12 AWG(0.75 mm2 WARNING:Thesedeviceswill notoperate without electrical power.As fires frequently cause power interruptions,we suggest you discuss further safeguards with your to 2.5 mm2)wiring.Strobes are interconnected with a single pair of Iota fire protector specialist. wires as shown below. il�ii To listed To next fire alarm appliance, control iri II end-of-line panel or return to control equipment E85001-0557 Page 2 of 4 Issue 2.1 ) Current Draw Ught output switch settings for UL 1971 listed models are selectable by numeric candela value. ECS/MNS appliances are selectable by A, B,C,or D designations. Standard output models(mA) High Output models(mA) UL "15"or"D" "30"or"C" "75"or"B" "95"or"A" "95"or"D" "115"or"C" ! "150"or"B" : "177"or"A" Rating RMS RMS RMS RMS RMS , RMS ! RMS RMS 16 Vdc 109 151 281 318 330 392 502 565 16 Vfwr 131 194 379 437 432 518 643 693 Standard output models(mA) High output models(mA) Typical "15"or"D" "30"or"C" i "75"or"B" "95"or"A" "95"or"D" ! "115"or"C" . "150"or"B" "177"or"A" Current RMS RMS RMS _j_ RMS RMS ! RMS ' RMS 1 RMS — 16 Vdc 94 140 273 325 333 392 499 551 20 Vdc 74 108 205 244 259 303 378 429 _. . 24 Vdc 63 90 168 194 212 245 306 342 33 Vdc 48 70 124 139 155 180 211 236 16 Vfwr 126 187 368 403 484 570 673 724 20 Vista 108 156 281 333 380 438 537 604 24 Vfwr 97 139 240 270 318 381 434 484 33 Vfwr 89 119 197 214 245 269 308 338 light Output Standard output models High output models Switch Settings(candela) Switch Settings(candela) Lens Listings Lens Listings cow standard Setting Setting Setting Setting color Standard Setting Setting Setting Setting A 8 C D A El C D Clear UL 1971 95 cd 75 cd 30 cd 15 cd Clear UL 1971 177 cd 150 cd 115 cd 95 cd Amber UL 1638 82 cd 65 cd 26 cd 13 cd Amber UL 1638 155 cd 130 cd 100 cd 82 cd Blue UL 1638 40 cd 31 cd 12 cd 6 cd Blue UL 1638 80 cd 78 cd 59 cd 48 cd Specifications H Textured UV stabilized,color impregnated engineered plastic.Exceeds 94V-0 UL flammability rating.Red and white models ousing available. Lens Optical grade polycarbonate(clear). Mount Flush mount to North American 4-inch square electrical box,2-1/6(54 mm)Inches deep. No extension ring required.Suitable for ing indoor wall or ceiling applications, Wire Connections Screw terminals:#18 to#12 AWG(0.75 mm2 to 2.5 mm2)wire size. Operating Voltage Regulated 16 to 33 Vdc,16 to 33 Vfwr. Operating nt Indoor:32-120°F(0-4.9°C)ambient temperature;0-93%relative humidity. environme Meets or exceeds year 2004 UL requirements for standards UL1638 and UL1971 and Canadian requirements for standards Agency lisfings/ CAN/ULC S526-02 and CAWULC S524-01.All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final approvals Rule.CSFM,MEA,FM. Strobe output rating Clear UL 1971, UL 1638,ULC S526:selectable 15/30/75/95 cd(GC-VM)and 95/115/150/177 cd(GC-VMH) Amber: CAWCSA-C22.2 No.205,CAN/ULC-5526,UL 1638:selectable 13/26/65/82 cd(GCW-VMA),82/103/130/155 cd(GCW-VMHA) Blue: CAN/CSA-C22.2 No.205,CAN/ULC-S526,UL 1638:selectable 6/12/31/40 cd(GO/V.-VMS),48/59/78/80 cd(GCVV*-VMHB) Strobe operating GC-VM series strobes:non-coded,filtered 16-33 Vdc voltage or unfiltered 16-33 Vdc FWR. GC-VM series strobes:one flash per second synchronized with optional G1M Genesis Signal Master indefinitely within 10 Strobe flash rate milliseconds.Temporal setting(private mode only):synchronized to temporal output of Genesis audible signals on same circuit. Synchronization Meets or exceeds UL 1971 requirements.Maximum allowed resistance between any two devices is 20 Ohms. Refer to specifications for the synchronization control module,this strobe,and the control panel to determine allowed wire resistance. Synchronization SIGA-OC1S,SIGA-MCC1S,SIGA-CC2A,SIGA-MCC2A,G1M-RM Sources BPS6A,BPS10A,APS6A,APS10A,I0 Series,Fireshleld Plus 3,5 and 10 zone.Add G1M for G1-CVM&G1-HDVM devices only. Page 3 of 4 E85001 -0557 Issue 2.1 Ordering Information EDWARDS Light output switch settings for UL 1971 listed models are selectable by numeric candela value. ECS/MNS appliances are selectable by A, B,C, or D designations. LIFE SAFETY&INCIDENT MANAGEMENT Model Housing Marking Lens j Strobe i Ship Wt. Contact us Phone: 800-655-4497(Option 4) _ _et.__ White running man icon screen printed on housing) -i. Late safety Appliances(e/w Email: edwards,firacarriercom GC VMNone i Selectable Website: edwardsfiresafety.com GCF-VM White "FIRE" 15,30,75,or 95 cd 1.8 lb. 8985 Town Center Pkwy GCFR-VM Red ! 'FIRE" Clear (p.g2 kg.) 9 P Bradenton,FL 34202 GC VMH White None Selectable hi h out ut 150, or 177 cd 115, ®2020 Carrier GCF VMH White "FIRE" 95, _._. All rights reserved. ECS/MNS Appliances(no running man icon on housing) GCWA-VMA i r Amber ' "Alert" Clear GCWA-VMC Selectable GCWN-VMA 1 I- Amber i A,B,C,D 1 GCWN-VMB ' None Blue I Clear 1.8 lb. GCWN-VMC White ( — Amber ' (0.82 kg.)GCWA-VMHA I "Alert" - - GCWA-VMHC Clear Amber Selectable high output GCWN VMHA A,B,C or D GCWN-VMBH None Blue GCWN-VM_HC Clear *NO E85001-0557 Page 4 of 4 Issue 2.1 Strobes,Horns,Bells,Chimes EST Life Safety & Communications 4 -_ ••..... outdoor Rated r •....... Horns and ........... ..... ........ ..... ..... . .. . ...... ......... Horn -Strobes ...... ............ ......... • ` o Genesis WG4 Series Overview Standard Features Genesis WG4 Series horns and horn-strobe appliances are among • Outdoor and indoor rated the most versatile emergency appliances of their kind. Rated for • indoor or outdoor use,they are suitable for a wide range of wet Low profile design and harsh environments with a listed operating temperature range • Wall or ceiling mount of as low as -40°F to as high as 151 °F(-40°C to 66°C). • Room-side wiring accepts 18 to 12 AWG(0.75 to 2.5 mm2) Field-configurable light and sound output settings add to their on- • Wide operating temperature range site flexibility,while optional FIRE markings make them ideal for fire alarm applications. • Field-selectable settings These appliances are suitable for indoor and outdoor applications, • Fully-compatible with Genesis synchronization protocols and are ideal for challenging conditions such as parking garages • Standard and high-output strobe intensities and process areas.They are available for mounting on the ceiling • or the wall,and thanks to an ingenious optional full backplane Horn only and horn-strobe options sealing gasket, can be installed to recessed(in-the-pour/block) electrical boxes.WG4 notification appliances also mount to suit- able surface boxes.Optional color-matched trim skirts provide a clean,finished appearance.All appliance wiring is accomplished room-side for easy installation. WG4 Series appliances feature an efficient and powerful piezo sounder.The multi-candela shubea are available with clear lenses in two output categories—standard and high-output.They are precision-tined to meet UL 1971 synchronization standards, and field-configurable for one of four candela intensities.Candela settings are viewable even after installation through an innovative sealed viewport display. Page 1 of 4 85001-0628 Issue 2.2 Application Installation and Mounting WG4 Gasket Horns \ Optional trim skirt Genesis horn output reaches as high as 97 dBA in accordance with \ UL 464(104 dBA in accordance with ULC-S525)and features a Backplate unique frequency tone that results in excellent sound penetration and an unmistakable warning of danger.Horns may be configured Front cover IIR� for either coded or non-coded notification circuits.They can also be \ IVset for low dB output with a jumper cut that reduces horn output by t�� about 5 dB. v ! r iiiø I \ The suggested sound pressure level for each notification zone used l ,'\ �, r-, with alarm notification appliances Is at least 15 dB above the average ig rrr% Electrical ambient sound level,or 5 dB above the maximum sound level having a v ;� S:. N x duration of at least 60 seconds,whichever is greater,measured 5 feet `�� !�� (1.5 m)above the floor.The average ambient sound level is A-weighted 'i 1 �\'1�� (fast response)sound pressure measured over a 24-hour period. / ll Doubling the distance from the notification appliance to the ear will v ��i ' '' theoretically result in a 6 dB reduction of the received sound pre.Ssure level.The actual effect depends on the acoustic properties of materi- als in the space. A 3 dBA difference represents a barely noticeable v change in volume. WG4 notification appliances are rated for outdoor use and are suitable for indoor or outdoor applications on walls or ceilings.For surface-mounting in outdoor or wet applications,appliances must be Strobe Application mounted to a 449 or 74347U electrical box.In dry conditions,they Genesis clear-lensed strobes are UL 1971-listed for use indoors are compatible with standard 4-inch square by 11/2-inch deep electri- as wall-or ceiling-mounted public-mode notification appliances for cal boxes.When using the optional WG4WTS or WG4RTS trim skirt, the hearing impaired,and UL 1638-listed for outdoor appfications. a 449 or 4-Inch square by 2-1/8"deep box must be used. Prevailing codes require strobes to be used where ambient noise The Genesis WG4 horn and horn-strobe may be wall-or ceiling - protection,exceed specified levels,where occupants use hearing mounted,and may be placed in one of four positions:strobe above, and in areas of puubliccaccommodation. strobe below,and strobe to either side.The shallow depth of Gen- Visible appliance synchronization is required to avoid causing esis devices leaves room behind the appliance for extra wiring. issues with people who have Photosensitive Epilepsy(PSE). Noti- fication appliance synchronization is also generally required when more than two strobe appliances are in the same field of view from Field Configuration Wife slot any one location.All Genesis strobes meet UL synchronization Horn pattern:Audible tom— 'j requirements(within 10 milliseconds over a two-hour period)when output for WG4 horns and Q/rq‘CI used with a synchronization source. horn-strobes is factory setto to sound in a three-pulse ��� temporal pattern.Units may WARNING:These devices will not operate without electrical power. be configured for use withIlfi ` Flom As fires frequently cause power Interruptions,we suggest you discuss coded systems by cutting '' Ha me further safeguards with your local fire protection specialist. a JP1 on the circuit board. reela is jumper Edwards recommends that these devices always be installed in This results in a steady mlti,Wna �_�_°1_1_1 WPC accordance with the latest recognized edition of national and oval output that can be turned (S2) I mg codes. Refer to the appropriate codes and standards for mounting on and off(coded)as the height information. system applies and removes ¢I-tOJ 30011 power to the notiesisSi sal Pattern I�� � �I circuit.A Genesis Signal (JP1) tf ..an p (I/A, Master is required when . _ _ horn-strobe models are con- figured for coded systems. Jumper(JP4) Horn output Horns and horn-strobes are factory set for high dB output. Low dB output may be selected by cutting a jumper on the circuit board. This reduces the output by about 5 dB. Strobe pattern:Genesis WG4 horn-strobes are factory set for use as UL 1971 compliant notification appliances for public mode operation.These notification appliances may be configured for temporal flash by cutting JP4 on the circuit board.This battery-saving feature is intended for private mode signing only. Strobe output Genesis WG4 horn-strobes may be set for one of four out- put intensities.The output settng is changed by simply opening the device and sliding the switch to the desired setting.The device does not have to be removed to change the output setting.The setting remains visible after the cover is dosed through a small window on the front of the device. 85001-0628 Page 2 of 4 Issue 2.2 Wiring Light Output Angle Field wiring is connected to WG4 notification appliances with Horizontal Plot 0 -25-20-"-" terminals that accommodate#18 to#12 AWG (0.75 mm2 to 2.5 _ .. . mm2)wiring. -..-35 - 35 45 L. 50 65 Signal In- Signal Out - 40 50 -55 55 40 60 Signal In + r!IIIIMIII .7.7-! Signal Out + 45 65 _ . 30! • .,„ .. • 75 17 010171 [1:1 °3 7.2 IM MIN.•in 1110 /, 40 118115 0 40 .es 40 90 11111 MI FI:Eggr.2122S:22:411.1.1Rteg""""gteRAXP44SIMPr=r4S2F Percentage of rated output .049 101 . . 0.P ' Standard Candela Horn-strobes ° 6/ = 0 Standard/rating - S P trobe Switch osition D C B A -/+designations indicate the signal polarity UL 1971 Indoor 15 cd 29 cd 70 cd 87 cd required to activate the device. UL 1638 Outdoor 0-35°C 6 cd 12 cd r8 cd 35 cd CAN/ULC-S526 Outdoor 0-40°C 1 cd 3 cd 8 cd 10 cd High Candela Horn-strobes Specifications Strobe Switch Position Standard/rating Horns and Horn-strobes D C B A UL 1971 Indoor 102cd 123cd 147cd 181cd Operating vottage 24 VDC,24 VFWR nominal UL 1638 Outdoor @-35°C 41cd 50 cd 80 cd 65 cd Dimensions(VV x H x D) 5.6 x 8.5 x 1.4 in.(142 x 216 x 36 mm) CANALC-S526 Outdoor @-40°C 11 cd 14 cd 17 cd 18 cd Hom tone 3.2 kHz Wire size 12 to 18 AWG(0.75 to 2.50 mm2) Compatible electrical box Outdoor Model 449 or 74347U indoor 4 in.square by 1.5 in.deep box Operating Current Operating environment (UL specifies current ratings at 16 volts) Temperature -40 to 151°F(-40 to 66°C)Relative humidity 095%noncondensi Standard Candela Horn-strobes in RMS MA),continuous to ng Strobe Switch Position Input Voltage D C B A 16 VDC 127 168 297 351 Compatible Synchronization Sources 16 VFWR 218 239 393 422 24 VDC 107 130 210 238 Hom-strobes 24 VFWR 190 222 325 356 SIGA-CC1S,SIGA-CC2A,SIGA- Auto-sync Output Modules MCC1S,SIGA-MCC2A Genesis Signal Master G1M-RM High Candela Horn-strobes in RMS(mA),continuous Strobe Switch Position Booster&Auxiliary Power Supplies APS6A,APS10A,BPS6A,BPS10A Input Voltage D C B A Control Panels with Genesis RreShield Plus,rO Series,EST3X 16 VDC 342 408 517 526 Synchronization built-In ---------------- --------- 16 VFWR 447 502 -614 679 24 VDC 240 271 327 365 24 VFWR 390 400 486 540 Sound Output Horn only models(mA) Horns and Horn-strobes OSA) 16V RMS,continuous 2414 typical 16V 24V 33V_ t Setting High dB --1---Low dB High dB t Low dB Volume Setting UL ULC- UL ULC- UL ULC- voc 69.1 ' 41.2 - 49.0 ! 32.3 ' 464 S525 464 q595 464 q-roS ---4-- 1-- I 91.3 99.1 i 6 Continuous High 89.7 94.0 94.7 99.8 97.4 102.9 VFWF1 135 7.1 Continuous Low 85.4 92.8 89.5 97.2 92.5 98.8 Temporal High 84.2 96.5 90.5 I 100.5 93.5 104.2 Temporal Low 81.7 90.3 i 85.4_...i 94.2 r 88.1 97.0 dBA=Decibels,A-weighted. UL 464:Sound level output meowed in a reverberant room at 10 ft.(3.05m). CAN/ULC-S59re Sound level output measured in an anechoic room all0ft(3.05m). Page 3 of 4 85001-0628 Issue 2.2 Ordering Information N EDWARD S , i li If I ,• i II pi • • j Contact us... � 0 Email: edwards.flreefs.utc.com Wa411F-N WY4RF-NVMC Wa4WF-H WMWF-NVMC WN411N-N W41NN-11YMC WO4WN-N WB4WN-NYMC Web: www.est-fire.com EST Is an EDWARDS brand. Model i Housing Marking Strobe Output Ship Wt. 1016 Corporate Park Drive WG4RF-HVMC Red FIRE Mebane,NC 27302 \ ` --'- -- - '"- Selectable y WG4WF-HVMC 1 White standard candelab In Canada,contact Chubb Edwards... - -- - Email: inquidesechubbedwards.com WG4RN-HVMC Red None output Web: wtm:rhubbedwards.com WG4WN-1-1VMC White O 2013 UTC Fire 8 Security Americas WG4RF HVMHC i Red Corporation,Inc.All rights reserved. ----- - -- --- - FIRE Selectable Specifications subject to change WG4WF-I-IVMHC I White 1.5 lbs. __ _ _ high candela WG4RN-HVMHC (0.68 kg) without notice.Edwards is pert of UTC j ; output Climate,Controls&Security,a unit of Red -' None ; United Technologies Corporation. WG4WN-HVMHC 1 White WG4RF-H Red s FIRE White r WG4WF H I Horn Only - WG4RN-H Red None WG4WN-H 1—_ White Accessories --- ------ ---- WG4WTS Surface Skirt for Genesis WG4 appliance family,white WG4RTS Surface Skirt for Genesis WG4 appliance family,red. WG4GSKT Full Body Mounting Gasket for smooth surfaces,WG4 appliance family 74347U 4 Surface mount box,outdoor rated,red 449 Surface mount box,outdoor rated,gray 85001-0628 Page 4 of 4 Issue 2.2 Strobes, Horns,Bees GI EST Life Safety & Communications :: Low Frequency � . . • )Y7IJYLNI.H•f,,ill 520 1111)YH.••••••l,ll,i Audible Signals F •l)3****,..•.•••:.•••„ Genesis G4LF Series :A "=:::****** Overview Standard Features G4LF Series notification appliances provide the benefits of Gen- • Unique low-profile design... esis life safety signals with output suitable for sleeping areas and - Compact UL listed aidlble and audible-visible appliances other applications requiring low frequency audible tones.These - Ultra-slim:protrudes an inch from the mounting surface high-performance appliances generate a crisp 520 Hz tone in the - Attractive appearance:no visible mounting screws standard 3-3 temporal pattern.An optional setting configures the • Choice of colors and markings... appliance for continuous audible output — a critical feature for _ White or red housings notification appliance circuits that are coded with a CDR-3 coder - With or without FIRE markings module. G4LF appliances also feature field-configurable high and low dB output settings. • Easy to install... - Room side wiring accepts#18 -#12 AWG(0.75 to 2.5 mm2) When connected to compatible Edwards control equipment,G4LF x - Fits standard 4-inch square electrical boxes or standard Series audible output remains synchronized with all Genesis au- Gensis G4B or G4RB surface-mount boxes dible signals on the same Notification Appliance Circuit, including standard 3.2 kHz Genesis audible signals. • Easy to configure without removing the device... - High or low dB output Available G4LF models include audible-only appliances, as well - Temporal or continuous audible tone as combination audible-visible signals.Combination appliances - Temporal or continuous visible output feature Genesis FullUght"strobe technology,which produces - 15, 30,75,or 110 candela intensity a smooth light distribution pattern without the spikes and voids that characterize bulky specular reflectors.This ensures the entire • Unparalleled performance... coverage area receives consistent illumination exceeding UL-1971 - Exclusive FullUght' strobe output distribution pattern light distribution requirements. It also results in a slim, low profile - Meets tough synchronization standards for strobes device that blends with any decor.Candela output is field configu- and audible signals rable. When connected to a compatible synchronization source,Genesis appliances synchronize(strobes to UL 1971)to within 10 millisec- onds indefinitely without the need for external modules or other equipment. See the Specifications section for a list of synchroniza- tion sources. Page 1 of 4 85001-0639 Issue 1.1 Application Installation Genesis G4LF Series appliances are UL 464-listed for low-ire- Genesis G4LF Series appliances mount to a standard 4 inch(102 quency audible requirements. Models are also available in combi- mm)square electrical box using the provided mounting spacer or nation with a UL 1971-listed strobe light for indoor wall-mounted directly to a Genesis G4 surface mount box. public-mode notification applications. Many codes and regulations All Genesis appliances have two tabs at the top of the signal. now call for low-frequency audible appliances(520 Hz)in sleeping Unlock the cover to reveal the mounting hardware.The shallow rooms and also require strobe lights under some of these circum depth of Genesis devices leaves ample room behind the signal for stances.Consult with your Authority Having Jurisdiction for details. extra wiring. Once installed with the cover in place, no mounting Low-frequency appliances are not limited to only sleeping rooms screws are visible. applications-they can also be used in other locations.Combina- tion audible-visible appliances are installed in accordance with cow guidelines established for visible(strobe)devices. Flush Mounting / 400 • When used with a compatible Edwards synchronization source,all ,_, (& 0 Genesis xenon based strobes — audible units,and combination �e appliances — maintain fully synchronized indefinitely.This exceeds ii_,_ Compatible the UL synchronization requirements of 10 milliseconds over a '`► •:�.- electrical box two-hour period.Strobe light synchronization is important in order T ', i;1 ,1` 0 to avoid issues with people that have Photosensitive Epilepsy. �. rn :t IF---,.-Ni 11i1.. 1 1i1 WARNING:These devices will not operate without electrical power.As "1"''' ;:?iFlush mount fires frequently cause power interruptions,we suggest you discuss further ;�i6 1' spacer(supplied) safeguards with your local fire protection specialist. �li0 G4LF Edwards recommends that these devices always be installed in • N accordance with the latest recognized edition of national and local ? g codes. Refer to the appropriate codes and standards for mountingHousn ; g CY height information. I ' Surface Mounting j l�r • Audible Signal Application - it Genesis low-frequency audible output features a distinctive 520 (1\� �� Hz signal that results in excellent waking capabilities,superb ,`s sound penetration, and an unmistakable warning of danger. pe .?. ii ,. s a e Mount Audible signals may be configured for either coded or non-coded v'- ` ..', il,,I Box signal circuits.They can also be set for low dB output with a \ `,; jumper cut that reduces audible output by about 5 dB.Audible li�c only models may be ceiling mounted or wall-mounted. ' G4LF ! j For sleeping rooms, most codes and standards require 75 dBA s iiiil' ft fast at the pillow. ® ` E For non-sleeping rooms,the suggested sound pressure level Housing for each signaling zone used with alarm signals is at least 15 dB ��ll above the average ambient sound level, or 5 dB above the maxi- mum sound level having a duration of at least 60 seconds,which- Typical Wiring ever is greater.This is measured 5 feet(1.5 m)above the floor. Room-side field wiring terminals accommodate#18 to#12 AWG Doubling the distance from the signal to the ear will theoretically (0.75 mm2 to 2.5 mm2)wiring.Audible appliances,strobes,and result in a 6 dB reduction of the received sound pressure level. combination audible-visual appliances are interconnected with a The actual effect depends on the acoustic properties of materials single pair of wires as shown. in the space.A 3 dBA difference represents a barely noticeable � change in volume. `' From NAG - 0 _1. output Visible Signal Application 1' - � For sleeping rooms,a strobe light is typically required within 16 r (€a� + light is wall-mounted and at or far- To next device or EOL �l e . the strobe 1 '-- itl/ feet of the pillow. If g ti ther than 24 inches(610 mm)from the ceiling, it should be 110 cd J ' '',._t , . . o(J or greater. If the strobe light is ceiling mounted or wall mounted From NAG closer than 24 inches(610 mm)to the ceiling,it must be 177 cd or outputO t ! _1- greater. S— Note:Polarity is shown In The active condition. Ti III bnl 85001-0639 Page 2 of 4 Issue 1.1 Field Configuration Light Output Genesis G4LF Series audible appliances are factory set to oper- Per cent of UL rating versus angle ate in a Temporal 3 (three-pulse)pattern.Units may be configured %OICnd.I.HSpec for use with coded systems by cutting jumper JP2 on the circuit --„a,.,,,„,,,,,,K board.This results in a steady output that can be turned on and ,a-,5 a 5 15 55 . off(coded)as the system applies and removes power to the signal 5 4 25 55 45 15 circuit.A Genesis Signal Master is required to maintain G4LF „-' a. strobe light synchronization when connected to a coded system. , 50 55 55 Audible signals and combination audible-visible appliances are 45 50 ,5 factory set for high dB output.Low dB output may be selected by 'S - j5 15 75 cutting jumper JP3 on the circuit board.This reduces the output m 55 by about 5 dB. .5 55 m 20 Genesis G4LF Series strobe lights are shippedfrom the lac- "pn----��- -ne� �e-�---- 9 quire Minium UL red candela light output tory ready for use as UL 1971 compliant signals for public mode operation.These signals may be configured for temporal flash by cutting jumper JP1 on the circuit board.This battery-saving Current Draw feature may be used for private mode signaling only. Audible-Visible Appliances r Operating horn strobe current in RMS(mA) with audible set to standard(high)output O Strobe ..__ ._. 15 30 75 T 110 JP3 Audible\, a output(cd) L _ i dB Output: 'y JP3 c.. .._ / _.e...—....._ ' Temporal cut for row. � 1____ -. t « ?).•�IL i f 4- 16 VDC + 219 266 ' 381 437� JP2 Audible t k r I[ 1 ` /f 16 VFWR 1 308 362 ' 510 579 for steady. t V�( - 5 • • �� - -t JP1 Strobe ■Jr �Q1� 24 VDC 151 176 243 278 pettem:an 'Q;r ' o 24 VFWR 228 258 349 395 for temporal-- -r r v rat 33VDC + 112 132 ! 177 I 199 1 a rtrate r o , r'oann it ill 33 VFWR 186 208 267 291 --f---- Continuous _ 16VDC i 221 258 371 433 Candela avach and indicator—a)liaaill .-----_ '.. .—.._ _ _.-_1 , 16 VFWR 305 358 514 I 576 24 VDC 147 l 171 239 I 274 Genesis G4LF Series strobe lights may be set for 15,30,75,or 24 VFWR i 211 I 247 335 i 377 t 175 J 110 candela output.The output setting is changed by simply 33 VDC 110 j - 179 196 opening the device and sliding the switch to the desired setting. 33 VFWR 178 l 199 - 257 I 282 - -- The appliance does not have to be removed to change the output VDC=Volts direct current,regulated and filtered setting.The setting remains visible through a small window on the VFWR=Volts full wave rectified side of the device after the cover is closed. Operating Current Nominal Sound Level Output RMS(mA)Audible appliance only Signal and voltage Low I High UL(dBA) UL 464:Sound - — --- Temporal 16 VDC 88 166 Signal and voltage Low ' High level output at -----------_i__ - 10 ft.(305 m) 24 VDC 43 I 112 . . Temporal I 16 VDC 72.4 78.0 - --- -t--.._------__ measured in a 33 VDC I 36 87 24 VDC 72.3 75.7 I-- _- - reverberant roomi 16 VFWR I 97 215 33 VDC 73.3 - 75.4 24 VFWR 78 159 Continuous 18 VDC 75.7 79.8 - ' - �_______....... 33 VFWR I 78 I 140 j 24VDC 76.1 78.6 _--- - - Continuous 16 VDC 36 160 I33 VDC 75.4 ----I_--- --- _, 78.8 - 24 VDC i 45 , 109 33 VDC � 36 86 18 VFWR -4--.__92 212 24 VFWR 80 _7-- 168" 133 VFWR 77 r- 141 VDC=Volts tired cunent,regulated and filtered VFWR=Volts ful wave'edified Page 3 at 4 85001 -0639 Issue 1.1 Specifications E C3 WA,R D S Genesis G4LF Audible and Visible Signals " -•, a. Operating voltage 24 VDC or 24 VFWR[1] Housing Red or white textured UV stabilized,cobr impregnated engineered plastic. Contact us... Dimensions Height:6.5"(165 mm).Width:5'(127 mm).Depth to wall 1"(25 mm), Email: edwards.firetifs.utc.com Mounting Rush:North-American 4"square box,2 1/8"(54 mm)deep.Requires Web: www.est-fire.com (indoor wall mount supplied spacer. only) Surface:model G4B(white)or G4RB(red)surface mount box. EST Is an SOWARDS brand. SIGA-CC1S,SIGH-MCC1S,SIGA-CC2A,SIGA-MCC2A,G1M-RM 1016 Corporate Park Drive Synchronization BPSCA,BPS10A,APS6A,APS10A,EST3X,1064,10500,VS1,VS2,VM, Mebane,NC 27302 Sources E-FSA64,E-FSA250,Fireshleld Plus. In Canada,contact Chubb Edwards... Wire Size 12 to 18 AWG(0.75 to 2.50 mm)_ Email: Inquiries@chubbedwards.com Operating 32-120°F(0-49°C)ambient temperature;0-93%relative humidity, web: www.chubbedwards.com environment noncondensing---..-.—._ ®2014 UTC Fire&Security Americas Corporation,Inc.All rights reserved. Audible Signal Specifications subject to change Temporal rate with compatible synchronization source:indefinitely within without notice.Edwards is part of UTC Audible pulse rate 10 milliseconds. Climate,Controls&Security,a unit of - - United Technologies Corporation. Temporal audible 'h sec ON,2 sec OFF,1r2 sec ON,Y2 sec OFF,Y sec ON,11/2 sec OFF, pattern then repeat cycle. Visible Signal Strobe Output Rating UL 1971:selectable 15 cd,30 cd,75 cd or 110 cd output Strobe Operating 16-33 Vdc Regulated,16-33 V Full wave rectified(UL Voltage Voltage Designations"Regulated 24"and°24 fwt") —-- . Strobe Flash Rate One flash per second. One flash per second(fps)within 10 milliseconds over a 2 hour time Strobe Flash period on a common circuit.Synchronization source required to comply Synchronization with UL 1971 synchronization standard.Temporal setting(private mode only):synchronized to temporal output on the same circuit. Strobe Lens Materiel Polycarbonate - — [1[This device was tested to the Regulated 24 DC/FWR operating voltage limits of 16 V and 33 V.Do not apply 80%and 110%of these values for system operation. Ordering Information Audible Visible Ship Wt Model Housing Marking Signal Signal lbs(kg) Fore Alarm Appliances(520 Hz screen printed on housing) G4LFWN-HVM , White None Selectable G4LFWF-HVM White FIRE Low 15,30 75, G4LFRN-HVM I ...._Red ILL_None -1 Frequency or 110 cd. t _� 1 H tow dB 5 lbs. i G4LFRF-HVM Red � FIRE (520 Hz)with G4LFWN-H White None � (0.6814 G4LFWF-H White FIRE Audible G4 - - output. G4LFRN-H Red None only. G4LFRF-H Red FIRE Accessories SIGA-CC1S Intelligent Synchronization Output Module(2-gang) SIGA-MCC1 S i Synchronization Output Module(Plug-in U10) -r 0.18 (0.08) +-- — SIGA-CC2A Dual Input Signal Module with Class A Operation(2-gang) 0.5023 l ) SIGA-MCC2A Dual Input Signal Module with Class A Operation(Plug-in U10) 0.18 (0.08) G4B Surface mount box,white i 0.7(0.32) G4RB +Sur ace moult box,red 0.7 (0.32) 85001-0639 Page 4 of 4 Issue 1.1 aas-corp.com �4- 'vAES CORPORATION 7707 Fire Subscribers (.110 IntelliNet A Newer Smarter Alarm0 wasi Communications Platform e a Feature Highlights °`" rn�i,,,,,f • Leverages state of the art technology • Applies advanced security protection • Offers flexible power and configuration options • Engineered for backward compatibility with legacy systems NFPA USED ✓ • Enables future ready capabilities • Provides instant subscriber status through front panel with Power and Trouble LEDs, a backlit LCD display, and Menu/Silence button • Includes robust Multiple Communication Technologies (MCT)feature • Emulates virtual keypad • Improves functionality with an adaptive Graphic User Interface (GUI) for programming via smartphones, tablets and PCs • Plus many more... Key Benefits • Built upon the solid foundation of AES-IntelliNet patented mesh radio technology for use in private licensed wireless networks • Protects subscriber units against unauthorized access and rogue activity with a password-protected Dealer Code • Makes programming and streamlined troubleshooting easy with user friendly interface • Adds integrated supervision of AES-lntelliPro full data module • Provides versatile power options: (1) Direct from the Fire Alarm Control Panel (FACP)without requiring an electrician onsite and without Subscriber backup battery; (2) Directly from the FACP with Subscriber backup battery; or (3)Traditional installation with plug in Class 2 low power transformer • Allows for enhancement upgrades and an expanded number of new features to be added easily with highly flexible and scalable alarm communications infrastructure • Rigorously tested to the highest industry standards and future ready to meet emerging NFPA code and UL. standards - • • • •1 Enhanced Wireless Fire Alarm Monitoring Powered by AES enhanced mesh radio technology, IntelliNet 2.0 7707 Fire Subscribers are next generation universal wireless communicators that provide advanced security protection for any new or existing alarm monitoring network.The AES Model 7707 is ideal for commercial fire applications.With the AES-IntelliPro full data module option, they are the ideal drop-in replacement for Plain Old Telephone Service (POTS) lines. The red metal enclosure comes with a key lock and front panel LCD backlit display with intuitive view that provides an instant visual of the subscriber status.The user friendly GUI makes it easy to program AES subscriber units via a smartphone, laptop,tablet, or integrated Universal Serial Bus (USB)—without the need for special cables or having to use a handheld programmer, Additional knockouts make it easier to mount for faster installation. IntelliNet 2.0 Private Wireless Mesh Radio Network B)Burglary D Subscriber it B C N ; B)Fire ( c / Subscriber ' AESNetwerk Monagement Syeem Ir DI _ ___ __ _____ _ __--- __ eD fi ____-I ® Primary AESMuINNe(Receiver 8 - A)Alarm 7707 r ' I Secondary AES-MulfiNet Receiver Panel Ms B B { 1 C Alarm Automation • A r C)IP Links fiSYi Csto LocSationscnb Mesh Radio Technology Cenral Monitoring Station HarmuParrotm S er M Subcr Multi-path AES-InrelliNetrA Network Primary&Secondary AES-MulGNPI System n seds critical event Signal I delivers alarm signals via smart routing receives transmission in 1-3 seconds normal and reverse polarity, with Y The IntelliNet 2.0 Fire Subscriber has an 8 Zone modular design for expansionP POTS and DACT interfaces with an option for the 7794A AES-IntelliPro full data module add-on accessory board. AES subscribers' intelligent software automatically detects new hardware and devices to reduce installation time. An AES certified WiFi accessory allows seamless wireless connectivity for configuration and programming.A laptop, Ethernet cable, or a Wi-Fi USB dongle is required for IntelliNet 2.0 programming, handheld programmers will not work with 2.0 units. A FACP Power Supply Adapter is required for certain configurations when using flexible power options. The forward compatible design allows for feature add-ons, engineered to adapt seamlessly with future software upgrades as technology advances. IntelliNet 2.0 allows configuration cloning for faster installation time. The AES 7707 was designed with quick configuration and installation in mind to make it easier for field technicians to get in, out, and on to the next install. Visit our Fire Marshal Resources web page for official NFPA and UL Listings: aes-corp.com/products/fire/fire-marshal-resources How to Order 7707 Fire IntelliNet 2.0 Fire Subscribers 2.0 PREMIUM (UL&ULC Listed) 7707P 88 M IntelliNet 2.0 Fire Subscriber, 8 Zone with Multiple Communication Technologies (MCT), Red Enclosure 7707P-88 U LP M IntelliNet 2.0 Fire Subscriber, 8 Zone with 7794A AES-IntelliPro,and integrated onboard Local Annunciator plus MCT, Red Enclosure 7707P-44-M IntelliNet 2.0 Fire Subscriber,4x4 Zone(4 Reversing Polarity,4 Supervised)with Multiple Communication Technologies (MCT), Red Enclosure IntelliNet 2.0 Fire Subscriber,4x4 Zone(4 Reversing Polarity,4 Supervised) 7707P-44-ULP-M with 7794A AES-lnteliiPro, and integrated onboard Local Annunciator plus MCT, Red Enclosure 2.0 ACCESSORIES 7794A Standalone AES-IntelliPro Fire full data module add-on accessory board with firmware for new IntelliNet 2.0 units only, cannot be used in legacy units 77-WiFi AES certified WiFi adapter 77-FACPA FACP Power Supply Adapter for internal mount 77-FACPA-KIT External installation hardware for 2-way Junction Box Legacy Fire Subscribers 7706-ULF Integrated Fire Monitoring System, Red Enclosure 7788E ULP P Legacy Fire Subscriber,8 Zone with 7795 AES-IntelliPro(7794 full data module, 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure 7788E ULP Legacy Fire Subscriber,8 Zone,8 Supervised Zones with 7794 AES-lnteliiPro, Red Enclosure 7788F Legacy Fire Subscriber, 8 Zone,8 Supervised Zones, Red Enclosure 7744E ULP-P Legacy Fire Subscriber,4 Zone with 7795 AES-IntelliPro(7794 full data module, 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure 7744E-ULP Legacy Fire Subscriber,4x4 Zone,4 Supervised Zones with 7794 AES-IntelliPro, Red Enclosure 7744E Legacy Fire Subscriber,4x4 Zone,4 Reversing Polarity, 4 Supervised Zones, Red Enclosure LEGACY ACCESSORIES 7794 Standalone AES-lnteliiPro Fire full data module add-on accessory board for legacy units only, please see 7794A above for IntelliNet 2.0 version www.aes- • • II Technical Specifications 7707 Fire ' , DIMENSIONS ALARM SIGNAL INPUTS/ZONES PORTS 13"H x 8.5"W x 4.5"D • 8 individually programmable Ethernet for configuration (33cmH x 21.5cmW x 11.4cmD) E.O.L. type zone inputs and message communication • 4+4:4 reverse polarity input and USB access for software upgrade WEIGHT 4 individually programmable 5.8 lbs(2.6 kilograms) E.O.L. type zone inputs REMOTE ANNUNCIATOR excluding battery • Optional 7794A AES-IntelliPro for AES Model 7740 13 lbs(5.9 kilograms)with full data via Contact ID, Pulse, Remote Annunciator,supervised 10 Ah battery Modem Ile and Modem II1a2 COMPATIBLE RECEIVERS RADIO FREQUENCY UL LISTINGS 7705i AES-MultiNet Receiver Standard Frequency Range: UL 864 10th Edition 450-470 MHz Standard for Control Units and CONFIGURATION INTERFACE Contact AES for other UHF Accessories for Fire Alarm Systems Web browser capable device and VHF frequencies ULC S559-04 1st Edition accessible via smartphone,tablet, Equipment for Fire Signal laptop, or PC ANTENNA Receiving Centres and Systems 2.5 dB tamper resistant antenna CURRENT CONSUMPTION included, mounts on enclosure Standby w/charged backup battery: Optional remote mounting TROUBLE OUTPUT—ACK 200 mA(1.2 A Transmitting) antenna available DELAY/ANTENNA CUT Standby+charging backup battery: Form C relay, fail secure, rated 24V 900 mA(1.9 A Transmitting- MAX) POWER INPUT DC 1A resistive, unsupervised AC SOURCES POWER OUTPUT Transformer: Class 2 RESET BUTTON 2 or 5 Watts 16.5V AC nominal output Located on main circuit board Factory set 1.9 A max current(40 VA MIN) ELK ELK-TRG1640, OPERATING TEMPERATURE ENCLOSURE MATERIAL MG ELECTRONIC SALES MGT1640, 32 to 120°F(0 to 49°C) Steel with paint finish or AES 1640(not included) DC SOURCES(includes FACP) STORAGE TEMPERATURE FINISH COLOR 24V DC Regulated Power Supply 14 to 140°F(-10 to 60°C) Red with Subscriber Rechargeable Battery RELATIVE HUMIDITY VISUAL INDICATORS 1.9 A max current 0 to 93%, non-condensing Front panel LCD (2 x 20 alphanumeric character BACKUP BATTERY RECHARGE CAPABILITY backlit display) 10-12 Ah, UL recognized lead acid Will charge 12V battery size Power and Trouble LEDs gel cell, size based on subscriber from 10-12 Ah (ALM,Trouble,Tx, Rx,WA) configuration Contact Us For pricing and availability or to learn more about IntelliNet 2.0, please call your local AES Sales Representative at (800) 237-6387 or email sales@aes-corp.com. www.aes-corp.com AES Corporation 1285 Newbury Street ( Peabody, MA 01960 United States ©Copyright 2018 AES Corporation and AES-lntelliNet'J are registered trademarks of AES Corporation STORE FIRE-PANEL, MAINTENANCE & AS BUILT DOCUMENTS THE DOCUMENT BOX 1 It's often important, or even required that you store documents near fire-panels or other systems you've installed. The BW-DocBox li Intiiruct ,n. is the easy answer! JIM" Installation.and _ANL `lairdr urn c %lanai] 1 . , 1 Lam-- lilt. B Y''!-DooB ox - BW-DocBox BW-DocBox2 . . .. 15"W x 13" H x 4" D 11"Wx15"Hx4"D `tIiluani...! includes: Smaller and more basic • THREE labels: model without the door Mime wawa , "Fire Alarm Documents" bracket for CDs and key "As Built Permits" sets. However, it does "Test and Maintenance Documents" have the three labels, te Four boxes in one! • An adjustable bungee allows you to adjustable bungee and The door can be left fit various sizes of binders, a lock with two keys. blank, or one of the three documents, smoke-cans,etc. labels may be used. • A door bracket holds two CDs,three sets of keys and more documents . • A cam lock with two keys Don't see the box you want? Call us or visit our website! Customization and/or silk-screening of logos is available for quantities of 25 or more. (requires lead time) B1^J-Docaox2 ,,lier1411111111111111411 is o y ��1� SJ.s a. r ; ) 4 r c . . . . - - -