Loading...
Report FIRE ALARM RECEIVED SUBMITTAL GUIDE AUG 21 2023 CITY OF TIGARD BUILDING DIVISION FP52o2.3- CC--C) 9l FOWLER MIDDLE SCHOOL 10865 SW WALNUT STREET TIGARD OR 97223 Prepared By: PLEASE PROVIDE COMPLETED NFPA 72 RECORD OF COMPLETION AT FINAL INSPECTION PERFORMANCE SYSTEMS INTEGRATION 7324 SW Durham Road Portland, Oregon 97224 info a,psintegrated.com (503) 641-2222 Phone (503) 641-1464 Fax 7/18/2023 SUPPLIED EQUIPMENT DEVICE MANUFACTURER DESCRIPTION AFC-1000V POTTER FIRE ALARM/VOICE CONTROL PANEL SYSTEM SCA-5025 POTTER DUAL CHANNEL VOICE 70v AMPLIFIER PANEL PSN-1000E POTTER POWER SUPPLY NAC EXPANDER PANEL UD-2000 POTTER DACT COMMUNICATOR FOR AFC FA/VOICE PANEL RA-6500R POTTER 160 CHARACTER LCD REMOTE ANNUNICATOR RLY-5 POTTER MULTI-RELAY MODULE AE2 POTTER 2 CARD ACCESSORY ENCLOSURE PAM-1 POTTER MULTI-VOLTAGE RELAY PAD100-PSDA POTTER ADDRESSABLE PULL STATION PAD100-SIM POTTER ADDRESSABLE SINGLE INPUT MODULE PAD100-DIM POTTER ADDRESSABLE DUAL INPUT MODULE PAD100-SLCE POTTER 127 POINT SLC EXPANDER PAD100-LEDK POTTER ADDRESSABLE LED W KEY SWITCH PAD300-4DB POTTER 4" DETECTOR BASE PAD300-CD POTTER CARBON MONOXIDE DETECTOR PAD300-DUCT POTTER SMOKE DUCT DETECTOR STN-5 POTTER DUCT DETECTOR SAMPLING TUBE PAD300-HD POTTER HEAT DETECTOR PAD300-PCD POTTER SMOKE PHOTO/CO DETECTOR PAD300-PD POTTER SMOKE PHOTO DETECTOR 5000-103 FIRERAY FIRERAY BEAM DETECTOR (REFLECTOR) 5000-031 FIRERAY FIRERAY BEAM DETECTOR (TRANSMITTER & RECEIVER) 1000-019 FIRERAY WIRE GUARD (BEAM DETECTOR) PAD100-TRTI POTTER BEAM DETECTOR DUAL RELAY/INPUT MODULE PAD100-ORTI POTTER BEAM DETECTOR SINGLE RELAY/INPUT MODULE PAD100-RM POTTER ADDRESSABLE RELAY MODULE SPSCWL SYSTEM SENSOR CEILING MOUNT WHITE SPEAKER/STROBE APPLIANCE SPCWL SYSTEM SENSOR CEILING MOUNT WHITE SPEAKER APPLIANCE SCWL SYSTEM SENSOR CEILING MOUNT WHITE STROBE APPLIANCE SPSWL SYSTEM SENSOR WALL MOUNT WHITE SPEAKER/STROBE APPLIANCE SPWL SYSTEM SENSOR WALL MOUNT WHITE SPEAKER APPLIANCE SWL SYSTEM SENSOR WALL MOUNT WHITE STROBE APPLIANCE SSU-00672 SPACE AGE RECORDS STORAGE CABINET SSU-03503 SPACE AGE WIRE GUARD (NOTIFICATION DEVICES) DURA12-18F2 DURACELL 12V 18AH BATTERY DURA12-8F DURACELL 12V 8AH BATTERY P POTTER AFC-1000 The Symbol of Protection Fire Alarm Control Panel Features p5 EMB`Fo • 1,270 addresses available on this analog addressable system • • Additional system capacity achieved via multi-point SLC modules -�` r xt `'P • 1500 software zones - A ' ®�Flt •... FC ip0o .1 • NFPA 72 Compliant Smoke Sensitivity Test Built-In " a • System Operates as Class A or Class B for SLC.P-Link and NACs • 10 Amp Power Supply,Expandable to 315 amps • 6 NACS,Regulated,Rated at 3 Amps each,expandable to 192 • 4 Input/Output(I/O)Circuits for system flexibility rated at 1 Amp each • Strobe Synchronization and System Wide Sync for Gentextit 11-1 AMSECO®.Cooper Wheelock®and System Sensor®strokes • Dedicated Alarm,Supervisory and Trouble Relays • 4,000 Event History Butler • Optional two line DACT with UD-2000 that can report General,Zone or Point Information • Built in IP communicator • Ethernet Port for Programming and Network Connectivity -- • E-Mail System Status,Reports and Event Information • Product includes 5 year warranty ® NYC Fire Dept "Certificate of Approval APPROVED 6256 1- •-"I LISTED 7165-0328:0509 S735 Description Technical Specifications The AFC-1000 is an expandable analog/addressable releasing fire alarm Dimensions 18%a'W x 27%<'H x 4 7-'D system with a total system capacity of 1270 addresses.Additional capacity 5.0 Amps a 120 VAC 50/60 HZ on the system is achieved using multi-point SLC modules The control AC Mains panel utilizes the exclusive Potter protocol that includes a complete line of 3.0 Amps a 240 VAC 50/60 HZ sensors and modules.Each SLC may be comprised ofany combination of 16 gauge cold rolled steel with removable Enclosure smoke sensor,heat detectors or modules and allows fora total of 50 ohms locked door with Lexan viewing window of impedance and may use any wire compliant with the National Electrical Standby Current-I30 mA Code(NEC)_ Alarm Current-220 mA "I he AFC-1000 has a 10 Amp power supply with six Notification • 10 Amps power for NACS.I/O,and P-Link Appliance Circuits (NACs) and four Input/Output (I/O) circuits. The Battery • 3 Amps per NAC,regulated NACs are rated at 3 Amps each and the 1/Os are rated at I Amp each. • I Amp per I/O circuit,regulated Each output is regulated and power limited. In addition_each output is • Batter Charger range 8-55 Ah • uniquely programmable and may be configured for steady signal.strobe Battery Charger voltage 27.3 VDC • P-Link maximum current of 1 Amp synchronization, constant power, door holder power, or releasing. 'the strobe synchronization includes Gentex,AMSECO, System Sensor and 'temperature and 32°to 120°(0°C to 49°C)with a maximum Cooper/Wheelock and with the exclusive Quadrasync each output may Humidity Range humidity of 93%non-condensing. have a unique brand and all strobes will flash together. • NPPA. 13.15.16, 17, 17A,70,72.and 750 The NACs may be expanded using the PSN-1000 series intelligent power • ANSI/UL 864-Local(L).Remote Station supplies. Each PSN-1000 adds another 10 Amps of power. 2 additional (RS),Central Station(CS),Propriety input circuits and the A FC-1000 will support up to 31 power supplies.The (PPU),Auxiliary(AUX).Type of Service: system will synchronize the strobes system wide In addition,the PSN- Automatic(A),Manual(M).Water flow 1000E has space to allow the installation ofup to six PAD 100-SLCE SLC Standards (WF)Sprinkler Supervisory(SS)Type of loop expansion cards.The cards mount on a stacker bracket that allows Signaling:Digital Alarm Communicator access to all SLC circuit connections. (DAC).March Time(March).Non Coded (NC).Reverse Polarity(Rev Poi).Other Technologies(UT) • IBC(International Building Code) Potter Electric Signal Company, LLC • St. Louis. MO • Phone. 8t10-325-3936 • www.poticrsignal.com 55311135-RE\`1 • 2/22 PAGE I OF 5 AFC-1000 The symbol of Protection Fire Alarm Control Panel SLC Loop Accessories Hie control panel may be connected with up to 1,270 addressable devices or modules in any combination.the SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PAD200-PD Analog Photoelectric Smoke Detector is a smoke detector with a listed obscuration of 1 0 to 3.7%/foot. UL 268 7th Edition. PAD200-PHD Combination Analog Photoelectric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.0 to 3.5%/foot obscuration and a fixed temperature range of 135°to 185°F heat detector.Smoke detection compliant with UL 268 7th Edition. VAD200-PCD Combination Photoelectric Smoke/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Carbon Monoxide detection compliant with UL 2075. Combination Photoelectric Smoke/Heat/Carbon Monoxide Detector. Smoke detection compliant with 111,268 7th Edition. Heat PAD200-PCHD detection with a fixed temperature range of 135°to 185°F and is UI.268 and UL 521 7th Edition compliant. Carbon Monoxide detection compliant with UL 2075. PAD100-HD Analog Fixed Temperature(135°- 185°F)or Rate-of-Rise Heat Detector(software selectable). PAD200-DUCTR Addressable Duct Smoke Detector with Form C Relay rate at I0Amps @ 250/120VAC or 8 Amps at 30VDC. PAD200-DUCT Addressable Duct Smoke Detector. PAD100-6B 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD100-4B 4"round base that may be mounted to an electrical box and wired for connection to the above sensors. PAD100-1B Isolator base that intemtpts a short in a SLC and prevents the short from affecting protected devices on the loop. PAD I00-RB Addressable Relay Base that contains one relay controlled by the SLC.Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125 VAC. PADI00-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. PADI00-CD Addressable CO gas detector. PAD 100-DD Addressable photoelectric smoke detector for use in DUCT/DUCTR enclosure. PADI00-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. The LFSB complies with the Low Frequency Signal Requirements(520 Hz) PADI00-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from I/8 W to 4W. Potter Electric Signal Company. LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersienal.com 8830136-REV H • 222 PAGE 2 OF 5 POTI-ER AFC-1000 ® The Symbol of Protection Fire Alarm Control Panel _ _.... Modules Device Description PAD 1 00-MI M Micro Input Module provides a small loot print contact module lb(mounting inside an enclosure. PAD100-PSSA Single Action Addressable Pull Station. PAD100-PSDA Dual Action Addressable Pull Station. PAD100-S1M Single Input Module is a standard contact module with an LED that mounts into a 4-square electrical box. PAD100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel.Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.Also provides two contact inputs. PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD100-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RNI Relay Module that provides one form C relay controlled by the control panel.Relay is rated for 2 amps at 30VDC or 0.5 amps at I 25VAC. PAD100-LED Module provides a single addressable LED that is controlled by the control panel. PAD100-SM Speaker Module provides switching for two audio channels. PAD100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.For use with the PAD100-DUCTR only. PAD100-0R01 One Relay One Input Module provides one form C relay and one input.The relay is rated at 2 amps at 30VDC or 0.5 amps at 125 VAC. ... - .._ Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com - - 8810136-REV 1 • 2/22 PAGE 3 OF 5 P POTTER AFC-1 000 ® The Symbol of Protection Fire Alarm Control Panel SLC Features RA-6075R-2 x 16 LCD annunciator with a key pad in a locked The Potter protocol is a digital protocol with a proven design for metal enclosure. reliability and noise immunity.The system does not require special RA-6500R(F)-4 x 40 LCD annunciator with a key pad in a locked cable or conductors for connection of the Signaling Line Circuit metal enclosure.Flush mount version available. as long as the cable is compliant with NFPA 70 and NFPA 72. LED-16(F)-16 LED annunciator with common indicators in a The system allows for Class A or Class R installations as well as locked metal enclosure.Flush mount version available. "T-Taps."Each loop is capable of 127 points,with a max wiring PSN-1000(E)- 10 amp,remote intelligent power supply with distance of 10,000 ft. 6 NACs,2 Inputs and a P-Link repeater.This panel is listed in conjunction with the AFC-100 as releasing circuits Sensor Features CA-6500-Class A convertor that converts the SI.C.NACs and The sensors through the fire alarm control panel provide a real P-Link connection time status as to the condition of the system.The smoke detector UD-2000--UL listed,Dual line telephone alarm communicator sensitivity,heat detector temperature level and drift compensation DRV-50-LED driver expander,used to connect up to 50 LEDs in a are all programmable options.The system also allows for a day/night graphic display mode where the panel automatically adjusts the sensitivity depending FCB-1000-Fire communication bridge,provides remote mounting on the time of day.To assist in the reduction of false alarms,the of the Ethernet connection smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer FIR-1000-Fiber interface module,used to extend P-Link to multi- maintain the programmed sensitivity. mode fiber(2 required) RLY-5-Relay module,provides 5 form C relay contacts rated at 3.0 User Interface amps 24VDC/l25AC The fire alarm control panel has a 4 x 40 LCD display to provide SPG-1000-Serial parallel gateway,allows for the connection to a information to the system status.The keypad has navigation keys serial or parallel printer to allow manipulation of the Menu on board the panel.The panel is The FIB-1000,FCB-I000 and the SPG-1000 may be installed in the shipped standard with the following LEDs: stacker bracket or ordered with the optional rack mount enclosure. • AC Power-Green MC-1000 Multi-Connect allows up to sixty-three AFC series panels • Alarm-Red to share a single reporting technology. • Earth Fault-Amber IDC-6-Initiating device circuit provides 6 programmable inputs • Supervisory-Amber AE-2-Two card expansion cabinet • Silenced-Amber AE-8-Eight card expansion cabinet • Trouble-Amber AE-14-Fourteen card expansion cabinet • Pre-Release-Anther • Release-Red Ethernet/I.P. Connection The AFC-1000 is shipped standard with an Ethernet connection. The common buttons include a Silence,Reset,Acknowledge,and Drill.All of the buttons are accessible once the locked door is This connection is the programming port and may he connected opened. to a building Wide Area Network(WAN)or Local Area Network (LAN).Once connected to the Internet.the panel may be selectively P-Link programmed to e-mail alarm conditions,trouble conditions. supervisory conditions,test.Event History and detector status.An The AFC-I 000 has a proprietary communication protocol that e-mail may be sent to the panel and the panel will e-mail the event communicates through a RS-485 connection to field devices.Up history,detector status,configuration file or server status to an to 64 devices may be connected to a single P-Link connection.The authorized E-mail account.In addition.reminders may he set to send P-Link includes the communication terminals and regulated 24 VDC an e-mail for service testing or other conditions, connection for the field devices.The field devices may he any of the following: In addition, the Ethernet connection is UL listed as an IP communicator.The IP communicator is listed to report to the UTPAD100-SLCE-Analog/Addressable loop expansion module listed Sur-Gard Ill IP receiver.The IP communicator replaces the SLCE-127-Nohmi addressable loop expansion module for retrofit traditional less reliable alarm communicator transmitter that utilized applications. telephone lines.The IP communicator is an active method of connection and communication to the monitoring station. Potter Electric Signal Company, LLC • St. Louis. MO • Phone: 800-325-3936 • www.pottersignal.com 8830136-REV I1 • 2122 PAGE 40F5 P® AFC-1000 The Symbol of Protection Fire Alarm Control Panel Dimensions 18.91" 17.60" Q 0 a TOP a ° d of _ 4.41" 3.7 3J5" __ l -I DEPTH O C o V O d N r 0 O O Q C LEFT SIDE _ RIGHT SIDE BOTTOM ° a Ordering Information Model Description Stock No. _ ' AFC-1000 Fire Alarm Control Panel 3992754 Replacement Board AFC-1000 3992758 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www_pottersignal.com 8830136-REVJ • 2/22 PAGF5OF5 par-fER SCA/DCA The Symbol of Protection Single/Dual Channel Amplifiers Features • 25W,50W and 100W amplifier • 25VRMS and 70VRMS audio powerka"` • 8 Class A or 8 Class B speaker outputs • P-Link device • Single channel and dual channel amplifiers • I 20VAC or 240VAC with battery charger circuit • Maximum of 31 amplifiers Q .,_SCA nGu (211 LISTED Description Technical Specifications The SCA and DCA amplifiers are a new addition to the Potter SCA-2525-58 mA proprietary P-Link device catalog. Potter offers seven variations of SCA-2570-58 mA amplifiers with wattages up to 100W to support small, medium, and SCA-5025-58 mA hi-rise applications.The amplifiers have the capability to distribute up Standby Current SCA-5070-58 mA to two audio channels simultaneously across multiple speaker zones. SCA-10070-60nrA Each amplifier is supplied with a stacker terminal block to provide DCA-5025-48 mA accommodations for 8 Class B or 8 Class A speaker outputs.The SCA DCA_10025-48 mA and DCA amplifiers offer output power at 25VRMS and 70VRMS. SCA-2525-608 mA Up to 31 amplifiers can be linked to the IPA-4000V panel and offer up SCA-2570-608 mA to 248 Class B or Class A speaker outputs. SCA-5025-608 mA The DCA-10025 (Dual Channel. 100W, 25VRMS Amplifier) may Alarm Current SCA-5070-608mA be programmed to provide an extraordinary 200W for single channel SCA-10070-766 mA applications via Potter Fire Panel Programmer. DCA-5025-520 mA The 70V-1000 converter module will extend output power to 70 V RM S DCA-10025-520 mA on the DCA dual channel amplifiers."I'he BUA-1000 backup amplifier Operating DEC 49°C(32'F-120°F) provides a failsafe solutions for potential lapse in service and Temperature compatible with the DCA dual channel amplifiers. Operating Humidity 10%93%«30°C(86°F)nunwndcnsing humidity Range Maximum P-Link Length 6500 ft Maximum V-I ink Length 6500 ft. Maximum Amplifiers 31 Size(WxHxD) SCA Enclosures(WxHxD)- i6`x 17"x 3 7/8" DCA Enclosures(WxHxD)- 19"x 27 3/8"x 4 5/8" Potter Electric Signal Company. LLC • St. Louis, MO • Phone. 800-325-3936 • www.pottersignal.com 8830185-REVA • 921 PAGE I OF 5 POTTER SCA/DCA e The Symbol of Protection Single/Dual Channel Amplifiers Installation Accessory List The SCA and DCA amplifiers communicate in conjunction with the IPA- Model Description Accessories 4000V using a RS-485 connection via P-Link.The SCA amplifiers are equipped with one V-Link and the DCA amplifiers provide two V-Link SCA-2525 SINGLE CHANNEL 25W,25V None to receive audio from the IPA-4000V. AMPLIFIER SCA-2570 SINGLE CHANNEL 25W,25V OR None 70V SELECTABLE AMPLIFIER SCA-5025 SINGLE CHANNEL 50W,25V None AMPLIFIER SCA-5070 SINGLE CHANNEL 50W,25V OR None 70V SELECTABLE AMPLIFIER SCA-10070 SINGLE CHANNEL 100W,25V OR None 70V SELECTABLE AMPLIFIER DCA-5025 DUAL CHANNEL 50W,25V 70V-1000 AMPLIFIER BUA-I000 DCA- DUAL CHANNEL 100W,25V 70V-1000 10025 AMPLIFIER BUA-1000 Wiring Options SCA-2525,SCA-2550,SCA-5025 and SCA-5070 Connections t20VAC 0Hz /400.00111111 24OVAC 50Hz-50Hz to separate Connect to separate unswitched AC circuit l O o w.. FUSE 1 _ 1- (r \ n___. iiiiiia& . � w ,_,,,CD)e ,. ,,. Battery connection(non-power limited). 1 / /t ` Use two(2)12V batteries connected in series_— ...._ 1 r l 1 1 i om pi '0K fl15A Go,I COL v-ni'x ce 11 tror �,n class o Ucmo L Lik1 (IPA<OCOV SCA°, . LOC-1000) Out bn PiiM COOL:0 Out to VOr I (SCA or L OC-1000L Potter Electric Signal Company. LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottcrsignal.com 8830185-REVA • 9/21 PAGE 20p5 • POTTER SCA/DCA The Symbol of Protection Single/Dual Channel Amplifiers SCA-10070 Connections 122Vne.:0211.6004 Connect oann Connect b separate un un If C¢tl AC circuit r. O b - qP. II f I I '(\ —J [ T i i �J I L-- I I I<"" � PI II 1`i� > Enmity conneatlw{non pfnrtrlm1ed) ---- , /II: Eno two U112V taioras n re and in seines / 1 ' t III lw. Ont.,. Omni Ow"circuit r is..•roG,necl Class A P-Link Wiring :L 1 CA-6500 I I Connection PLINK PLINK 2 VM-1000 II SCAor DCA * A B - * A B Amplifier I Panel 0 �J��.'I 0 `�' .i. O Connection ••za 1 .y — _. • 1 PLINK I PLINK 2 I t K t I- -I A 3 - • A B - - ma Class B P-Link Wiring Panel VM.1000 SCA or DCA Connection Amplifiet PLINKI PLINK 2 �yy ,.' it INK (1 9 - * AB e1! I I +-- 111- I ------- \I To the next device Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830185-REV A • 9/21 PAGE 3 OF 5 POTTER SCA/DCA The Symbol of Protection Single/Dual Channel Amplifiers Class A V Link I Wiring SCA or LOC-1000 SCA or LOC-1000 Connection r^Coonnection Connecti ar�J lm V-INK 1 VLIG K G 1ILIN171 VUN 1 -7UTt -INn -OUT+ -IN+ II l Class B V-Link 1 Wiring VM,1000 SCAor LOC ectron x1 SCnor ec-boq ro CVnneClinn COnnecllnn CmnGcign I W�� Oo iI G VI..IN<1 VLI•K2 D.NFs\ ---- -- `1�'I 1 -DUTI. -IN* -OUT• IN,• i S 1 --1, To the neat device VLINK 1 s (15K EOLR on last device) Class A V-Link I and V-Link 2 Wiring 1 DCAor LOC-1000 DCA or LOC-1000 Connection Co mectmn '�Ii5I�i^IIFi1^IOIOI Oir.111- DTI 1 VM.1000 1.GIf►�V V ►d ►/►.% �V!O_V Conl>rl{Io11�I I•� —II iaria I S ! (� �y I IN I VLINK2 Class 8 V-Link I and V-Link 2 Wiring Vrd-1000 DCA or LOC-1000 DCA or LOC-1000 Connection Connection Connection 414:� Inl^i^I^1 V OUT+NK1 OU-IN+ - Tin 2 IN 1 l�i7 r-1 •-- i. To the next device VLINK 1 - -----' 1 ). (15K EOM on fast device) -- - -- - - --- ----- `- ► To the next device VLINK2 (15K EOLN on last device) Potter Electric Signal Company. LLC • St. Louis, MO • Phone: 800-325-3936 • www-pottersignal.com 8830185-REV A • 9/21 PAGE 4 OF 5 S+xe SCA/DCA The Symbol of Protection Single/Dual Channel Amplifiers Ordering Information Model Description Stock No. SCA-2525 SINGLE CHANNEL 25W.25V 3520667 AMPLIFIER SCA-2570 SINGLE CHANNEL 25W,25V OR 3520668 70V SELECIABLEAMPLIFIER SCA-5025 SINGLE CHANNEL 50W,25V 3520662 AMPLIFIER SCA-5070 SINGLE CHANNEL 50W.25V OR 3520663 70V SELECTABLE AMPLIFIER SCA-10070 SINGLE CHANNEL 100W,25V OR 3520666 70V SELECTABLE AMPLIFIER DCA-5025 DUAL CHANNEL 50W.25V 3520659 AMPLIFIER DCA- DUAL CHANNEL 100W.25V 3520660 10025 AMPLIFIER Piutci I.Icctric Siena] Company, LLC • St- Louts, MO • Phone: 800-325-3936 • www.pottersignal.cum 8830185-REV A • 9/21 PAGES OFF PSN-1000E(gPOUER The Symbol of Protection Power Expander Features • 10 Amp Power Supply I • 3 Amps,regulated per NAC • 6 NACs Class B or 3 NACs Class A ° - ' • 2 dry contact inputs r • Fully programmable and monitored through control panel Fitv • Isolated P-Link repeater connection,Class A or B • Up to 31 power supplies per control panel with system wide e sync j LW"!yr �� s-`, • Quadrasync feature synchronizes strobes from AMSECO, vt i[AS P*rsN 1000 abnex Neow ANA.Sucwry, Gentex,Cooper-Wheelock and System Sensor- yki*Vrtleril APPROVED 7165-0328: 0195 S2930 Description Technical Specifications The PSN-1000 series is a UL listed intelligent 10 amp notification PSN-1000: 16 3/4"x 16 1/8"x 3 12" power supply and P-Link(RS-485)repeater.The power supply Size(H x W x D) connects to the P-Link bus from the control panel and is operated and PSN-1000 E:26'x 17.6"x 3.75" supervised from the panel.The power supply may be installed 6,500 Enclosure Sixteen(16)gauge sheet steel with hinged,locked feet from the control panel.The PSN-1000 then repeats the P-Link door; communication for another 6,500 feet. 120 VAC at 50 L1Z Power Input 240 VAC at 60 H7 The power supply has six(6)Class B or three(3)Class A power 5.1 Amps/3.0 Amps max draw outputs.Each output is regulated and power limited with a 3 Amp maximum rating. In addition,the PSN-I000 has two(2) Current Standby 60 mA programmable dry contact inputs.The dry contact inputs are Class B, Alann 200 mA supervised inputs. Temperature 32°to I20°E humidity 93%non-condensing The power supply operates on either 120 or 220 VAC power and IPA Series.AFC/ARC Series. PFC-4064. has a regulated 24 VDC output.In addition,the panel can charge Compatible Panics P Series*. PFC-6000 Adressable Series* up to 55 All batteries and will house 18 AH batteries.The cabinet * Legacy Product is constructed out of 18 gauge cold rolled steel with a durable red powder coat finish.A standard Potter key lock is provided for The power supplies are programmed and controlled through the main securing the door.Electrical conduit knockouts are provided on the control panel P-Link bus.The panel displays any troubles or off sides and top providing installers with multiple options for installing normal conditions of the power supply and the events are stored in conduits and providing proper power separations. the panel history buffer. The PSN-1000 is a self contained intelligent power supply/P-Link Each output can be independently configured to provide one of'four repeater complete with cabinet.The PSN-I000E is the intelligent synchronization patterns.Amsecoli.,Gentex®.Cooper Wheelock power supply/P-Link repeater with additional cabinet roomfor and System Sensor.The ouputs can be also configured for constant mounting stacker bracket modules including PAD100-SLCE loop power,resettable power.sounder base power.door holder power expanders.Both cabinets include space for 18 AH batteries. (with or without a low AC drop out).ANSI temporal Code 3.City Tie or be a releasing circuit for 24vdc solenoids. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830032-REV F • O420 PAGE I OF 2 j OTT PSN-1000(E) d° • The Symbol of Protection Power Expander PSN-1000(E) Intelligent Power Supply Potter Fire Alarm Control Panel o V fl 0 a n 0 L 7 D ® ° °.a n f 0r ° — nofa ° o o -��e 8 ° °.... Du III ° ° 0 0 ❑a0000 t - ®0 oDO 4 8 a MOTE °❑ 0.7 o o�E ° ° o OOec�� _ ❑ uMNM _ ] • 6 Class B/3 Class A NAC Circuits 4-Wire P-Link Circuit Y•L —•- 1 • 2 Input Monitoring Points(IDC) ---........_.-,—__---,,.._._.—_--_._..--___._.........._.._ —___..__.._ v - ° • P-Link Circuit Repeater o 0 0 / \ L._ Ordering Information Model Description Stock No. PSN-1000 Power Expander Standard 3992662 Cabinet PSN-1000(E) Power Expander Large Cabinet 3992665 Potto Electric Signal Compan I IS • St. Louis. MO • Phone: 800 325-3936 • www.pottersignal corn 8830032-REV E • 04/20 PAGE 2 OF 2 Yalk POTTER UD-2000 The Symbol of Protection Digital Alarm Communicator Features •• � u • Allows for communication to Monitoring Station - • Communicates using SIA-DCS or Ademco Contact ID Protocols • For use with IPA,AFC,and ARC series Addressable Panels and PFC-4064 Conventional Panel • Status LEDs indicate operation of DACE card • Installs with ease behind main panel LCD display via User Interface bracket • Device address is set internally to address 1 • Includes two(2)RJ45 phone cords • • •, � 1MI# rsf •at � a r �~ 44000. 41) '► LISTED Description Technical Specifications The UD 2000 Digital Alarm Communicator Transmitter (DACT) Operating Voltage 22.0-24.OV provides for up to Iwo (2) phone lines for communication to a monitoring station. The UD-2000 communicates using the SIA- Standby Current 16mA DCS or Ademco Contact ID protocols. When enabled, the DACT Alarm Current 23rnA automatically monitors each phone line or voltage and has the Max UD-2000s per panel ability to seize the line and connect with a remote receiver. Once the communication is complete,the DACT will hang up. Dimensions 4"W 61'H* The DACT is provided with terminal blocks for each phone line and Operating Temperatures 0°C-49°C(32°F-120°F) two RJ45 cords. In order for the DACT to work properly, it must be Operating Humidity Range 10%-93%(a)30°C(86°F) installed on a plain old telephone service (POTS) line or equivalent (non-condensing) deemed by the authority having jurisdiction. The DACE must be Mounting Options In FRCP Behind keypad installed before any other equipment to ensure it can seize the phone Shipping Weight 0.47 lbs line. Phone lines are high voltage and should he run in a separate conduit from other circuits.The wire conductors connecting the DACT to the phone system should be 26 AWG or larger. Potter Electric Signal Company. L.LC • St. Louis. MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • watt pouersignalcom S830146-REV 13 • 6/19 PAGE I OF 3 POTTER U D-2000 a The Symbol of Protection Digital Alarm Communicator RJ3 1 X Phone Jack to UD-2000 Plain Old Telephone (POTS) lines Tip(Brown) Ring(Grey) Out to Premises Phones Out to Premises Phones Ring(Grey) Tip(Brown) — 8 -Grey 2-Tan 2 7 3-Black 2 7 4-Red 5-Green l 5 6-Yellow 3 7-Blue 4 5 8-Broom 4 5 Ring(Red) "L" Tip(Green) Line In From Telco Tip(Green) Ring(Red) Line In From Telco Tely7 oue 2 Te o 1 hone I 75p Ripg�E Ring Ti R dg R Ring UD-2000 Communicator Telco Tip=Red Telco Ring=Green Phone Tip=Brown Phone Ring=Grey NOTICE • Install in accordance with compatible fire alarm control panel installation manual Installation The UD-2000 DACT is connected to the control panel using the provided four-wire cable connection(P/N 5210514)between P4 and UD-2000 PI.The connection is power limited and supervised. I. Power system down. 2. Slide the UD-2000 into the card guides located under the User Interface bracket. 3. Secure the UD-2000 to the User Interface bracket using the provided#6-32x3/8"screw 4. Install the provided four-wire conductor jumper between UD-2000 PI and P4. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830146-REVB • 6.:19 PAGE2OF3 PUTTER UD-2000 ® The Symbol of Protection Digital Alarm Communicator UD-2000 DACT Installation on UD-2000 DACT Installation on Small Platform Panel Large Platform Panel Fig i Fig 2 re ° ILe o _ ? • ' l i — , N a t i -Scre wI:1, R� q1 Q4 buses in guides under main Doan. LA ' °o v. ° [MG 09331F 1 d' d J o o .i O 5 }I/ s< P Connector on 1 -l) small platform 1 Cl j1 control panel o __ — a. . e ' P Connector �'d I on main board h h n H , 1 Ordering Information Model Description Stock No. -t UD-2000 Digital Alarm Communicator 3992769 Potter Electric Signal Company. LLC • Si. Louis. MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830146-REV B • W19 PAGE 3OF1 (1) POTTER '`a The Symbol of Protection LCD ANNUNCIATOR ��- Features i :, ti -E` I4.^, x Operates with all Potter PFC-6000 series 'X „:0 ,a; • Industry leading 4 line by 40 Character LCD • Common buttons for navigation • Common LEDs for status indication + ,a�v,': - 31 annunciator per panel iT • Maximum wire length of 6.500 feet Size(W x H x D):9 13/16"x 7 1/6"x 111/16" Electrical Specs Standby Current 20 mA lir Alarm Current 50 mA S2930 7165-0328: 0195 Product includes a 5 year warranty Description Installation The RA-6500 is a LCD remote annunciator for the PFC-6000 Series The RA-6500 is connected to the fire alarm control panel using a addressable fire control panels.The RA-6500 communicates using a four wire RS-485 connection.The connection is power limited and RS-485 connection to the main panel providing common indication supervised.Up to thirty-one(31)RA-6500 LCD annunciators can be of Alarms.Supervisory.Trouble and other system status and control connected using Class B or Class A wiring. functions. The RA-6500 features a 4x40. 160 character LCD display with LED's for Power.Alarm.Supervisory,Trouble,and Silenced conditions. NOTICE g - It can he mounted on a single gang electrical box or a four square electrical box.The annunciator is enclosed in a sheet metal enclosure Install in accordance with compatible installation manual. and has a Potter lock securing the keypad. Figure 1:Class B Wiring Example Figure 2:Class A Wiring Example To the next annunciator _ 18181111M EelpandeSS r r 111111111Panel �'�I ElConnecton ! Remote (.MInnn I�--LIN 1Annunciator 1 �E -t 1111111/(trti ® Remote ! Annunciator Potter Electric Signal Company, LLC • St. Louis. MO • 800-325-3936- Canada. 888-882-1833 • wm w.pottcrsignal_corn PRINTED IN USA MEG.48830031-RFV I IDE,t I(II I II/II POTTER RLY-5 The Symbol of Protection Relay Expander Features 4,ssmerFo • Mounts with included stacker bracket :$ p• • Provides 5 user configurable relays • Contact Rating of 24VDC/3.0A, 125 VAC/3.0A (resistive) • Maximum 31 RLY-5s per panel • Maximum P-Link wire length of6,500 feet. - e+' , a • Product includes a 5 year warranty flF i� �1: • UUKL Listed for Smoke Control y ' SIGNALING I 0 APPROVED 7305-0328:0200 UOXX.S2930 Description Technical Specifications The RLY-5 is a relay expander for compatible Potter fire alarm control panels.The RLY-5 communicates with the control P-link Current35 mA(Alarm) panel via the RS-485 (P-Link)communication bus providing 5 (24 VDC) 25 mA(Standby) user configurable relay outputs programmable with the Potter Configuration Software. RLY PWR Current 135 mA(Alarm) (16 VDC—33 VDC) 10 mA(Standby) Installation WA Series The RLY-5 is connected to a four wire RS-485 (P-Link) AFC/ARC Series Compatible Panels PFC-4064 connection.Each card is mounted to the exclusive Stacker P-Series* Bracket for secure and accessible mounting..This connection PFC-6000 Addressable Series* is power limited and supervised.The RLY-5 can be installed in the AE-2,AE-8,and AE-14 Accessory Enclosures.The RLY-5 *Legacy Product can also be installed inside the PSN-1000E Intelligent Power 1'Ote: RLY PWR can be provided by any fire listed source. Supply and larger control panel enclosures that include space Output power must be 16 VDC-33 VDC and must be power for mounting stacker bracket modules. limited. Note:All connections to relay contacts shall be power limited. Potter Electric Signal Company, LLC • St. Louis. MO • Phone: 800-325-3936 • www.pottersignal.com 8830127-REV C 12/18 PAGE I OF 2 POTTER R ® The Symbol of Protection Relay Expander RLY-5 WIRING TO CONTROL PANEL OR AUXILIARY POWER SUPPLY EXAMPLES Example Example. Powered by Powered by ccn olpanel au•aupply LV P -to A B P-Linty fromPower from P.tdok from control Panel Nary control panel apply RLY-5 NORMALLY OPEN AND NORMALLY CLOSED CONTACTS NC(Normally Closed) C(Common) NO(Normally Open) NIm O NC REL Y2 C NO NC C NO NC C NO NC C NO RELAY 3 RELAY 6 RELAY5 IOIO IOIO O O O O O O O O O O O Ordering Information Model Description Stock No. RLY-5 Relay Expander 3992667 Potter Electric Signal Company. LLC Si Lotus. MO Phone: 800-325-3936 • www.pottersienal.com 8830127-REV C 1218 PAGE_2 OF 2 AE-2 POTTER The Symbol of Protection Accessory Enclosure Features s�Ms • 18 Gage Steel Enclosure � • '6S •+7nE,fp • Accommodates up to 2 standard size stacker bracket expansion cards • UUKL Listed for Smoke Control eN ' ® 43APPROVED 1 "1 Description Technical Specifications Thu AE-2 expansion enclosure accommodates up to 2 standard size Total Expansion Card Capacity 2 PAD100-SLCE, RLY-5, or other stacker bracket sized cards. The enclosure size is(WxHxD)9 3/4"x 8"x 2 l/2 Size(WxHxD) 9 3/4"x 8"x 2 1/2" Installation Secure the AE-2 enclosure to a suitable surface using#8 sized screws located in four of the five mounting holes provided.One expansion device can be installed in the location shown using the#6-32 sized hex nuts.An additional expander can be stacked on top of the one that is directly attached to the back box. Fig I 9 3/4" - MOUNTING HOLES EXPANDER MOUNTING 8 USE#6-32 HEX NUTS PROVIDED WITH EXPANDER— MOUNTING HOLES Ordering Information Model Description Stock No. AE-2 Expansion Enclosure 3992726 Potter Electric Signal Company. LLC • St. Louis, MO • Phone 800-325-3936 • www.pottersignal.com 8830095-REV B • 1 /18 PAGE I OF I • r POTTER PAM-1 °® The Symbol of Protection Multi-Voltage Relay Module Features • Single SPD'f relay with LED • Double-sided adhesive tape .rya_., • Mounting screw a ' • Six 12-"flying"leads 18 AWG• 6 wire-nutsoifff r , ask t, 0 I" -4I LISTED Description Technical Specifications The PAM-I Relay provides 10.0 A form "C" contacts. The relay A,nbient may he energized by one of three input voltages: 24VDC. 24VAC, Tempe,at„rc 32°F to 120`F(0°C to49''C) or 120VAC. The input voltages are polarity-sensitive and diode- Lso"(38,nm)ltx 120 (3li„n,)wx0??'(20 n,,,)D protected. PAM-1 Relays contain a red LED which indicates when the Dimensions 12'(304.8mtn)18 ga wire leach relay coil is energized. 10A at 120 VAC The PAM-SD may be mounted by using the double-sided adhesive contact rating 7.Aat 24VDC tape,the self-drilling screw,or loosely placed in an electrical backbox. 250 xscruamps ai svDc PAM Relays are ideal for applications where remote relays are required Power for fire alarm control or status feedback.They are only suitable for use Requirements 20mA n 24VDC_iomA az4VAC and 120VAC within t1L864 applications and installed in accordance with NFPA 70' and NFPA 72'. Relay EL recognized SPOT Installation RELAY ENERGIZED LED mum WHT . BLU + ` YEL NC �� 10.0 A �'© CONTACTS RED '�; ORG ®©� A NO 120VAC @ 50mA 24VAC t 50mA Ordering Information 24VDC c 20mA Model Description Stock No. r-► PAM-I Multi-Voltage Relay Module 1000262 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830164-REV 13 • 2!21 PAGE 1 OF 1 PAD100-PSSA/PSDA POTTER Addressable Pull Station The Symbol of Protection Single/Dual Action Features SSE Aefp� • Single or Dual Action versions :��p� • Durable die-cast construction rHE • Reset key matches the fire alarm control panels • Compatible with IPA Series panels RE .LA RM • SLC Class A,Class X&Class B ��ttC `�� �_ ���� • Product includes a 5 year warranty T • UUKL Listed for Smoke Control Li DOWN 8r L a. PULL PULL' p01 is 7 ®roT R400. 5) (1)11 APPROVED I•. -1 Description Technical Specifications The PAD100-PSSA (Single Action) is activated by simply pulling Operating Voltage 24.0 VDC the white "T" bar handle down. The PAD100-PSDA (Dual Action) is activated by lifting the front cover and then pulling the white "T" Max SLC Standby Current 200uA bar handle down.Once activated,the"T"bar cannot be reset without Max SLC Alarm Current 200uA opening the front cover.Opening the front cover will also activate the 32°F 120°F(0° 49°C) pull station.To reset the PAD 100-PS Series,use the Potter WS-93 key Environmental Limitations Indoor Only to unlock and open the front cover. Once the cover is open, push the “T"bar back into the normal position and re-secure the front cover. Dimensions 4.75"H x 3 25-W x 1.75"D Relative Humidity Range 0-93%(non-condensing) Application Single gang box or The PAD100-PSSA/PSDA is compatible with Potter's WA and AFC/ Mounting Options Potter P32-BB/DBB ARC series addressable fire alarm control panels. It is a non-coded APS-SA- 1.2216s_ addressable pull station available in either a single or dual action Shipping Weight model and installs on a single gang box or surface mounts using the APS-0A- 1.46Ibs. P32-BB or P32-DBB(deep)back box. Potter Electric Signal Company, LLC • St. Louis, MO • Phone 800-325-3936 • www.pottersignal com 8810097-REV D • 12,18 PAGE 1 OF 2 pOT'ER PAD100-SIM The Symbol of Protection Single Input Module Features ,st-MSS • One(1)Class B monitoring input • SLC Class A,Class X&Class B '$ • Mounts in a standard 4"or double gang box P $ TNE 5 • Wiring terminals accessible when mounted in box • All wiring terminals accept 22 to 12 AWG • Product includes a 5 year warranty re)ro7 • UUKL Listed for Smoke Control ° ""'' NOTE:This addressable module does not support 2-wire smoke detectors. APPROVED ,—f Description Technical Specifications The PADI00-SIM uses one(1)SLC loop addresses when monitoring Operating Voltage 24.OV one(I) Class B circuit.The module mounts on either a 4"square or double gang box.The module is capable of monitoring one(1)Class Max SLC Standby 240pA Current tt B circuit. The PAD100-SIM includes one red LED to indicate the module's status.In normal condition,the LED flashes when the device Max SLC Alarm 240P A is being polled by the control panel. When the input is activated,the Current LED will flash at a fast rate. Max Wiring Resistance 1004 of IDC Application Max Wiring Capacitance of TDC I pF The PADI00-S1M is compatible with Potter's WA and AFC/ARC series addressable fire alarm control panels. The PAD100-SIM is an EOL Resistor S.IK S2 interface module used to monitor dry contact devices such as sprinkler Operating Temperature 32 to 120°F(0 to 49°C) waterfow, valve tamper switches, or conventional pull stations. The Range module is capable of monitoring one Class B circuit. Operating Humidity 0 to 93%(non-condensing) Range Setting the Address Max no.of Module Per 177 units Each addressable SLC device must be assigned an address.The address Loop is set using the DIP switch located on the PAD100-SIM. 4.17"(106mm)1,x 4.1T Dimensions (106mm)W x 1.14-(29mm)D Before connecting a device to the SLC loop. take the following precautions to prevent potential damage to the panel or device: Mounting Options Standard 4"Square or I. Power to the device is removed. Double Gang Box 2. Field wiring is correctly installed. Shipping Weight 0.6 lbs 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com ---------------- 8830083-REV D • 12/18 PAGE I OF 2 P POTTER PAD1 00-SIM The Symbol of Protection Single Input Module Installation Using Compatible Electrical Box rig 11. ,opw I ortgre Wiring Diagram PAD100-SIM With Class B Circuit Fig 2 1-- - r1-77 0 FROM FACP OR PREVIOUS MODULE TO NEXT MODULE END-OF-LINE RESISTOR - , 51K OHM W Part#3005013 _ _CA Ordering Information Model Description Stock No. PAD100-SIM Single Input Module 3992704 - - - Potter Electric Signal Company, I_LC • St. Louis, MO • Phone: 800-325-3936 • www.pottersi al.corn 8830083-REV i • 12118 PAGE 2 OF 2 Pou PAD100-DIM The Symbol of Protection Dual Input Module Features themez,O • Single module with dual contact monitoring inputs ; ;•° • two(2)Class B or one(1)Class A monitoring inputs • SLC Class A.Class X&Class B THE s)- • Mounts in a standard 4"or double gang box • Wiring terminals accessible when mounted in box • All wiring terminals accept 22 to 12 AWG TT • Product includes a 5 year warranty "__, • UUKL Listed for Smoke Control A'(1TE: I his addressable module does not support 2-wire smoke detectors. 411.1fr COI APPROVED I 7 Description Technical Specifications The PADI00-DIM uses one (1) SLC loop address when monitoring Operating Voltage 24.OV two(2)Class B circuits or one(1)Class A circuit.The module mounts on either a 4" square or double gang box. The module is capable Flax SLC Standby 240µA Current of monitoring two (2) separate class B circuits making it ideal for monitoring sprinkler waterflow and valve tamper switches when they Max SLC Alarm 240µA are located in the same proximity.The PADI00-DIM includes one red Current LED to indicate the module's status. In normal condition, the LED Max Wiring Resistance 10052 flashes when the device is being polled by the control panel.When an of 1DC input is activated,the LED will flash at a fast rate. Max Wiring I µF Capacitance of IDC Application EOL Resistor S.IK Sz The PAD100-DIM is compatible with Potter's IPA and AFC/ARC Operating Temperature 32 to 120°F(0 to 49°C) series addressable fire alarm control panels. The PADI00-DIM is an Range interface module used to monitor dry contact devices such as sprinkler Operating Humidity 0 to 93%(non-condensing) watertlow, valve tamper switches, or conventional pull stations. The Range module is capable of monitoring two separate Class B or one Class A Max no.of Module Per 127 units circuits. Loop 4.17"(106mm)1,x 4.17- Setting the Address Dimensions (106m,,,)wx 1.14"(29nn)D Each addressable SLC device must be assigned an address. The Standard 4"Square or address is set using the DIP switch located on the PAD100-DI M.When Mounting Options Double Gang Box the PAD100- DIM is used to monitor two individual Class B circuits a single device address is assigned_each input is then identified as a Shipping Weight 0.6 lbs sub-point of the module address. For example. if the address number is assigned as "8"_ the first input will be "8.1" and the second input will be"8.2-. Before connecting a device to the SLC loop. take the following precautions to prevent potential damage to the panel or device: I. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830082-RFVD • t2/I PAGE IOF2 POTTERPAD100-DIM The Symbol of Protection Dual Input Module Installation Using Compatible Electrical Box Fig I _ 41w"I Wiring Diagrams PAD!00-DIM V!iih One Class A Circuit Fig 2 MOVE THE"CL-A"DIP SWITCH - .--- ----, TO"UP"POSITION ir 0 ♦ 461 FOR CLASS A WIRING FROM FACP OR _'� ✓PREVIOUS MODULE �,}I a-i-B TO NEXT MODULE 447,1 { NOTE: END-OF-LINE RESISTOR IS NOT REQUIRED PAD100-DIM With Two Class B Circuits Fig 3 MOVE THE"Cl-A"DIP SWITCH TO"DOWN"POSITION FOR CLASS B WIRING FROMFACPOR PREVIOUS MODULE \ - TO NEXT MODULE \ + END SOF-LINE RESISTOR P1KOHMOW Part a3005013 _ _ . END-OF-LINE RESISTOR .. ._____. c...__— SIKOHM$W1 Part X3005013 Ordering Information Model Description Stock No. PAD100-DIM Dual Input Module 3992703 Potter Llectric Signal Company, LLC • St. Louis. MO • Phone: 800-325-3936 • www.pottersignal.com 8830082-REVD • 12'18 PAGE2OF2 ( POTFER The Symbol of Protection Addressable Loop Expander Features YcSEMgrFO • No special wiring for SLC or P-Link connection P Tit 9 • SLC Class A.X or B capable • Mounts with included stacker bracket • May mount in panel,accessory cabinet or PSN-1000/E Power Supply �� 4 • Product includes a 5 year warranty • UUKL Listed for Smoke Control {z APPROVED F ` I Description Technical Specifications The Signaling Line Circuit Expander PADI00-SLCE allows up to thirty one additional loops.Each loop adds 127 addressable sensors or Standby Current 50mA modules in any combination.The PADI00-SLCE,may be configured Alarm Current 50mA for Class A or Class B wiring without the need for additional modules. The PADI00-SLCE communicates with the control panel via the Operating Temperature 0°C 49°C(32°P-120°P) Potter P-Link communication bus.The loop adder is mounted in either Operating Humidity Range I0%-93%(non-condensing) the control panel cabinet,the intelligent power supply,AE-2,AE-8 or Max no.of PAD100-SLCE 31 the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting. Dimensions (W x H x D)4"x 6"x 1-1/8" Installation The PAD100-SLCE is connected to the IPA and AFC/ARC series panels using a lour wire RS-485 connection. This connection is power limited and supervised. The PADI00-SLCE can be installed in the AE-2 Accessory Enclosure.AL-8 Accessory Enclosure,AE-14 Accessory Enclosure or inside the large IPA or AFC series enclosure using the supplied bracket. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830091-REV E • 9,19 PAGE 1 OF 2 (PPOTTER PAD100-SLOE The Symbol of Protection Addressable Loop Expander PADI00-SLOE Class B P-LINK Wiring Example PADI00-SLCE Class A P-LINK Wiring Example Fig I Fig 2 To the next device Class A 'Ziff) r� Expander CIJ ff) i Connection � r I? m PLINK LLLLLL 11' I+� \�� F-P Panel* 'Connection -1+i Expansion Panel Connection _ Expansion P-LIN Device Device i'il a , Expansion Expansion --y__._ Device Device Ordering Information Model Description Stock No. fp PAD100-SLCE Addressable Loop Expander 3992722 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-393(n • www_potters'gnal.com 8830091-REV E • 9t19 PAGE 2 OF 2 P POTTER PADI OO-LEDK ® The Symbol of Protection Addressable LED With Key Switch Features p5 s`M1340 • Addressable LED and key switch ' may rHE ySP • Key matches the fire alarm control panels • Compatible with IPA Series panels • Mounts in a single gang box • SLC Class A.Class X&Class 13 4 T4Y • All wiring terminals accept 22 to 12 AWG • Product includes a 5 year warranty off • UUKL Listed for Smoke Control C 5) 113 APPROVED I .. Description Technical Specifications The PAD100-LEDK provides a mappable key-switch input making it Operating Voltage 24.0V ideal for key control of a variety of system functions. The PAD100- LEDK provides mappable red LED which can be used to indicate a Max SLC Standby 200pA Current variety of status conditions. Max SLC Alarm 2000 Application Current The PAD100-LEDK is compatible with Potter's IPA and AFC/ARC Environmental 32°F-120°F(0°-49°C) Limitations Indoor Only series addressable fire alarm control panels.It installs on a single gang box. Operating Humidity 0 to 93%(non-condensing) Range Setting the Address Max no.of Module Per 127 units The PAD100-LEDK uses one SLC address assigned to the device.The Loop address is set using the DIP switch located on the back of the PAD I00- 4.757(187mm)11 x 2.75'' LEDK device. Dimensions (108mm)W x 17(40mm)D Before connecting a device to the SLC loop, take the following Single gang box or Mounting OptionsPrecautions to prevent potential damage to the panel or device: Potter P32-BB/BB13 1. Power to the device is removed. Shipping Weight 0.65 lbs 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis. MO • Phone: 800-325-3936 • www.pottersignal.com 8830088-REV E • 12 18 PAGE 1 OF 2 • P POTTER PAD100-LEDK ® The Symbol of Protection Addressable LED With Key Switch Installation Using Compatible Electrical Box fig i - frf A __r_n-----'.-C-) 1 --- 1-71 - I„ , r____, ,._..„ , ( ,,,, (----,,, ) i ' �\I 4 __. - , __ ___, PAD100-LEDK Back View and Wiring f'i,2 FROM FACP OR /,, PREVIOUS MODULE \ TO NEXT MODULE • Ordering Information Model Description Stock No. _,.t PADI00-LEDK Addressable LED with Kevswitch 3992709 Potter Electric Signal Company. LLC • St. Louts MO Phone: 800-325-3936 • www.pottersignal.com 8830088-REV[ • 12,1g PAGE 2 OF 2 P ; POTTER PAD300-CD The Symbol of Protection Carbon Monoxide Detector Operation The PAD300-CD is an analog addressable detector that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled.The LED flashes every time the unit is polled and it will flash at a fast rate if the unit is in an active status.The polling LED can be turned off if desired for less conspicuous operation. The PAD300-CD with the PAD300-4DB or PAD300-6DB has a low profile of less than two(2)inches to blend into the surrounding environment. Detection Levels The PAD300-CD will provide alarm reports at these required levels: Alarm Set-point 70 ppm for 2 hours 150 ppm for 30 minutes 400 ppm for 10 minutes Compatible Bases All bases will mount on a single gang,3-1/2"octagon. 3-1/2"square,double gang,4"octagon,4"square,50 min c/c.60 min c/c and 70 mm c/c boxes.. Device Description Stock No. PAD300-4DB 4"Detector Base 3992781 PAD300-6DB 6"Detector Base 3992782 PAD300-IB 6"Base with an Isolator Module Included 3992783 PAD300-RB 6"Base with one Form-C Relay Contact. 2A @ 30VDC,0.5A cif 125VAC 3992784 PAD300-SB 6"Base with sounder module included.Sound pattern is provided from external source 3992785 PAD300-LFSB 6"Base with 52011z sounder module included.Sound pattern is provided from external source 3992786 Ordering Information Model Description Stock No. PAD300-CD Carbon Monoxide Detector 3992778 Potter Electric Signal Company, LLC • St. Louis. MO • Phone: 800-325-3936 • www.pottersienal.com PRINTED IN USA 8830205-REV B • 2123 PAGE 2 Or 2 PO PAD300-DUCT s The Symbol of Protection Analog Addressable Duct Detector Features • Detects Smoke in Building HVAC Ducts • Ships Complete with I lousing and Head • Compatible with Addressable IPA and AFC/ARC Series Panels -'s- . 4,44,444 • SLC In-and-out Wire Terminals ' • SLC Class A,Class X&Class B - 4. • Installation Without Removing the Head , ;I ▪ Listed Air Velocity of 300 to 4,000 ft/minute ,, • No Screens or Filters in Housing • Durable Plastic Enclosure and Clear Cover • Integrated Cover Tamper Switch • UUKL Listed for Smoke Control • Utilizes Simple Snap in Sampling Tubes STN Series • Product includes 5-year warranty gtO 04") Description Technical Specifications The PAD300-DUCT is designed and built to meet all local Duct Detector Model Number PAD300-DUCT requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two (2) tubes which Operating Voltage 24 VDC protrude into the duct. An exhaust tube of one standard length (7") Current Draw 3001tA is supplied in the installation kit with the smoke duct unit. Once the Detector Head Model PAD300-DD duct width has been determined the air intake,sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths:2.5 ft.. Detector Head Type Photoelectric 5 ft..and 10 ft.and cut to size to fit the duct.Mounting the duct smoke Alarm Set Point Fixed at 2.5%/ft(8%/m) unit is accomplished by the use of a template and two(2)sheet metal Sensitivity Test Method Self-diagnostic Test screws, which are provided. Mounting can be achieved without the Air Velocity 300 ft min to 4000 ft min removal of the clear cover which is secured by four(4)capture screws. Ambient Temperature 32°F to 120°F(0°C to 49°C) Application Humidity !try.to 85%Relative Humidity The Potter Electric PAD300-DUCT duct smoke detector provides (Non-condensing) early detection of smoke and products of combustion present in Plastic Backbox.Clear Plastic air moving through 1IVAC ducts in commercial, industrial and I lousing Material Cover residential applications. The PAD300-DUCT is compatible with Finish Gray Backbox with Clear Cover the IPA and AFC/ARC series addressable fire alarm control panels. Dimensions 13 I12'Lx 4 1/2'W x2 I/4"H Maximum Net Weight 2 lbs. Sampling Tubes 2.5 ft..5 ft..or 10 ft. PH'ter Electric Signal Company. LTC • St. Louis. MO • Phone: 800-325-3936 • WIN pottersignal.com 8830208-REV 13 • 4/23 PAGE 1 OF 2 Pil'OTTER PAD300-DUCT ® The Symbol of Protection Analog Addressable Duct Detector Engineering Specifications Air duct smoke detectors shall be Potter Electric PAD300-DUCT Series.The detectors shall be listed by Underwriters Laboratories per 1JL 268A.The detectors shall operate at air velocities from 300 feet per minute to 4000 feet per minute.The duct detector housings shall be of plastic construction and complete mechanical installation may he performed without removal of detector cover.Visual indication of alarm and power must be provided on detector front. Detector heads shall not require additional filters or screens which must be maintained.The housing shall contain a detector base and PAD300-DD duct smoke detector head.Terminal connections shall be of the screw type and be a minimum of 412 screw.All wiring must comply with local codes and regulations.Detector shall use the SIN series of sampling tubes. Wiring Diagram Fig I \ O< jo -R 1U ¢R 0 o I)/ a ,�,1 ►� +SLC ® I/\�1 0-2 J-SLC TO NEXT MODULE [U�\J I Li / \ +SLC \ FROM FUS O tL Li or -SLC PREVIOUS MODULE 4rr. O p--� O rn f� Ordering Information Model Description Stock No. PAD300-DUCT Analog Addressable Duct Detector 3992795 Model Description Stock No. STN-2.5 2.5'Sampling Tube 1000274 .1, STN-5 5'Sampling Tube 1000275 STN-10 10'Sampling Tube 1000276 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830208-REV 6 • 4/23 PAGE 2 OF 2 BASICALLY:When Sampling n determining the N best way If the duct is Not only will YOU Tubes can always be cut to monitor the Tubes greater than remember the second down to size if necessary. entire airflow round of labor(when 18" wide, that you are past N conveyed Know and Understand the 12" sample scheduled Some manufacturers allow ' through an tube will not completion),that two metal tubes to be HVAC system, Code-Driven Requirements Inspector will spliced together to meet the Codes will pass code. p g of Air Sampling Tube Lengths probably remember, the distance requirement. v direct you to In fact, if you do and be less likely to ti follow the in Duct Smoke Detector Check your installation choose to use the trust that future jobs c'n manufacturer's Installations shorter tube you could you've done are to instructions. '� installation be breaking the law. Code. o instructions. The Codes are not just On the reverse, if you o h Reference Le ngth en t guidelines,they are prove to your Tube9 Chances are, law once adopted. Inspector that you are Duct Width %-80% o you will read aware of the Code that the air - 7 3 Feet 24" 29" a - requirements and • sampling tube �' consistently perform ' 5 Feet 40"-48" ° Your Inspector must extend2/3 onlyneeds to witness your installations 5 80% accordingly,the 7Feet 56"-67" o andofthe f one incorrect O duct width. installation before Inspector may look to 9 Feet 72"-86" likely asking you to you more favorably a: T and consider your firm v Air sampling �,' prove each and every a trusted resource. Tube support is tubes that will b " - ,� ,' i detector location is to required in all instances ' ' code before sign-off. q o accommodate where the tube length is E duct widths ,, . 4 . greater than three feet. `^ C between one t., 0 and ten feet are � �Make sure you ¢ available from all i DUCT WIDTH ---1 manufacturers �' r purchase the o that provide _ . „" +s .-u,, , .7 tx. 5 ; correct size tubes w air duct smoke Don't Allow Smoke to Bypass F for your particular Q detectors. Yp __ The Sample Tubes application. __.--. Zm - i '/a-80%of O kd 9i the width N E Comply with 25 Corporate Drive the Codes! The sampling tube MUST extend at least'/s into the width Auburn Hills, MI 48326 r14E74', v � j ry of the duct, 80%in the case of some manufacturers. www.apcfire.com IMC,IFC,ICC,NFPA AIR PRODUCTS Sc CONTROLS ?r< ��z;� 4�� ,'AYy .. �� #'#,hN ,"�, � . urn ,., a = .r :., + h Tubes Proper Installation Required by Code Installation Examples , In all cases the Codes state that , installations,tests and inspections / 'ry shall be made in accordance with the n�` Insert a plug in this end manufacturer's published instructions. I I I 1 1 ! The illustration at right shows two sample .� _ 5q air duct smoke detector installations.Both Tube support is required for r are"clean"installations, however only the tubes longer than 3 ft(.9 m) r detector to the left has been set up to I •r • f , properly monitor the airstream sample as Air Sampling Tubes That Extend At Least'/3 to 800/0 of the -,; required by the IMC(Chapter 606.3)and Duct W}dth Will Monitor the Entire Airstream Sample as Required by Code* el < NFPA 72e(Chapter 5.16.5.2). A tea' O ,, NFPA90A Chapter 6 requires that smoke — C y$` detectors be installed,tested and As shown here, r 2/3-80%duct width 1 maintained in accordance with NFPA 72, Airflow Direction > the sample tuber I Q falls short and r p t/1 National Fire Alarm Code®. 0. would fail the r 2 2 W Designed to Save Lives ANJ inspection r — lMany people fail to remember that Sample tube holes face r •op more people are killed by smoke upstream of airflow a Do not insertthe r u inhalation than byfire. exhaust plug in the • y r tube t yO „ If the installations you are responsible 1 .g= for fail because the deadly smoke stream I 1 11 11 11 1 1 11 1 I I - O,'r` by-passed the sample tube and did not a trigger sensor head alarm and system v rs shutdown (or other functions),you may I ( J -0 ; face liability. In addition to monetary k.O losses,think about the lives that may be lost or in jeopardy.It's simply not worth it *Always the provided manufacturer's installation instructions. If the to install short tubes and "sneak it past" the Building Inspector to save your time instruction booklet is lost or missing, most can be downloaded from the and cost nor is it legal to do so. manufacturer's website. Myth Fact The duct smoke detector you bought came If the supplied sample tube fit in the product's unit Building Inspectors are reporting with a sample tube in the box.You don't carton,it's probably around 12"in length.A 12"tube instances of non-compliant v need to buy any additional tubes for your will only be code-compliant in ducts up to 18"wide. tube spans in more and more V commercial installation. Are all your commercial ducts only 18"wide? commerical applications... TV . .,ax,nr.,...as�acax..:. x, k<.,.Eo:.xa.&use ...av'lia'"' '-.a'. ..aa-i :.rarh�'zj.', ;4.-.,wd "4:`.-..-. ix • PUTTER PAD300-HD The Symbol of Protection Heat Detector Operation The PAD300-11D is an analog addressable detector that uses one address on the Signaling Line Circuit(SLC)of'a compatible fire alarm control panel. The unit communicates with the control panel as it is polled.The LED flashes every time the unit is polled and it will flash at a fast rate if the unit is in an active status.The polling LED can be turned off it'desired for less conspicuous operation. The PAD300-HD with the PAD300-4DB or PAD300-6D13 has a low profile to blend into the surrounding environment.The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on,the PAD300-11D will operate even though the LED will not illuminate. Spacing The ANSI/UL.listed spacing limitations of PAD300-HD smooth ceiling are dependent on alarm set point. Alarm Set-Point Rate of Rise Spacing Fixed Temperature Spacing 135°F to 185°F (57°C to 85°C) Max. 70 ft. Max. 70 ft. Compatible Bases All bases will mount on a single gang,3-1/2"octagon.3-1/2"square,double gang,4"octagon.4"square.50mm c/c,60min c/c and 70mm c/c boxes. Device Description Stock No. J�A PAD300-4DB 4"Detector Base 3992781 PAD300-6DB 6"Detector Base 3992782 PAD300-IB 6"Base with an Isolator Module Included 3992783 PAD300-RB 6"Base with One Form-C Relay Contact 2A;/�30VDC,0.5A 125VAC 3992784 PAD300-SB 6"Base with sounder module included.Sound pattern is provided from external source 3992785 PAD300-LFSB 6"Base with 520IIz sounder module included.Sound pattern is provided from external source 3992786 Ordering Information Model Description Stock No. PAD300-I ID Heat Detector 3993776 Potter Electric Signal Company, LLC • St. 1.ouis, MO • Phone: 800-325-3936 • Hww.pottersignal.com 8830210-REV B • 2/23 PAGE 20F2 POTTER. PAD300-PCD The Symbol of Protection Photoelectric Smoke/CO Detector Features • Photoelectric Smoke Detection compliant with LU1,268 7th Edition • Carbon Monoxide(CO)detection compliant with Ul,2075 • 10 year Carbon Monoxide detection lifespan with built in end of life indication • Walk Test mode allows for fast easy validation()cc 0 sensor operation • Low profile,less than 2 inches with the base ry , • Wide selectable sensitivity range of 1.1 to 3.5%foot /// • Detector communicates sensitivity to control panel • Optional locking tab to prevent unwanted removal • Simple DIP switch address setting,no programming tool required • LED Alarm Indicator • Product includes 5-year warranty • UUKL Listed for Smoke Control gy . • Magnetic Test Switch4 0328-0542 Description Technical Specifications The Photoelectric Smoke detector and the Carbon Monoxide(CO)detector Voltage Range 24 VDC are both listed Analog Addressable detectors compatible with fire alarm Standby Current 300 µA control panels that utilize the Potter Addressable Device(PAD)protocol. Alarm Set-point Range 1.1 to 3.5%/ft(3.6 to 11%/m) The CO sensing portion utilizes a proven electrochemical sensor for accurate detection ofCO gas for life safety applications.'l'he photoelectric Alarm indicator Current 1.4 mA detector complies with UL 268 7th edition enhanced smoke sensitivity CO Alarm Rating 70 ppm, 150 ppm,400 ppm tests. It has a wide sensitivity range of 1.1 to 3.5%per foot.and features drift compensation with built in dirty detector warning. Installation Temperature Range 32°F to 100°F(0°C to 38°C) The detector and the control panel communicate over a proven and robust Operating Humidity Range <93%(Non-condensing) digital communication path and the system analyzes the information at Dimensions 3.93 in(100 mm) the particular device.The total polling speed is less than five(5)seconds, Weight 92 g(3.25 oz) well under the UL requirements. Height 1.42 in(36 mm) The detector is compatible with any of the PAD300 series detector bases and simply twists on.The PAD300-PCD is addressed using_DIP switches in the rear of the detector and can be easily programmed in the field without special tools. Setting the Address Each addressable device on the SLC loop must have a unique address from Ito 127 to function properly. The address is set using DIP switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following: I. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potte- r Electric Signal Company, LLC • St. Louis. MO • Phone- 800-325-3936 • www.pottersignal.com PRINTED IN USA 8830214-REVS - 223 PAGE I OF 2 pPATTER Photoelectric The Symbol of Protection Smoke/CO Detector Air Velocity Rating The PAD300-PCD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. 'Ehe system has a maximum of 30 LEDs that can be turned On simultaneously. If the system already has 30 LEDs on,the PAD300-PCD will operate even though the LED may not illuminate. Operation The PAD300-PCD is an analog addressable detector that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled.The LED flashes every time the unit is polled and they will flash at a fast rate if the unit is in an active status.The polling LED can be turned off if desired for less conspicuous operation. The PAD300-PCD with the PAD300-4DB or PAD300-6DB has a low profile of less than two(2)inches to blend into the surrounding environment. Detector Sensitivity The PAD300-PCD and the compatible control panel work in tandem to keep the sensitivity consistent.As the detector is installed over time,the detector compensates for the dirt in the unit until it is out of range.At that time,the panel will indicate a dirty detector.The detector will then have to be cleaned or replaced. The PAD300-PCD can be programmed to provide a maintenance alert prior to reaching the dirty detector level which will allow for intervention prior to the detector going into trouble.This allows for detector replacement or cleaning prior to a nuisance trouble occurs. The PAD300-PCD will provide CO alarm reports at 70 ppm, 150 ppm.and 400 ppm. Note: As required by NEPA,do not install the detectors until all construction is complete and the work area has been thoroughly cleaned. If the detectors have been installed in a construction environment,they should be cleaned or replaced before the system is placed into service. Compatible Bases All bases will mount on a single gang.3-1/2"octagon,3-1/2"square,double gang,4"octagon,4"square,50mm c/c,60mm c/c and 70mm c/c boxes. Device Description Stock No. -1R PAD300-4DB 4"Detector Base 3992781 PAD300-6DB 6 Detector Base 3992782 PAD300-1B 6"base with an isolator module included 3992783 PAD300-RB 6"base with one Form-C relay contact. 2A a 30VDC.0.5A(ig 125VAC 3992784 PAD300-SB 6"base with sounder module included.Sound pattern is provided from external source 3992785 PAD300-LFSB 6'base wih 52011z.sounder module included.Sound pattern is provided from external source 3992786 Ordering Information Model Description Stock No. �r PAD300-PCD Photoelectric Smoke/CO Detector 3992779 Potter Electric Signal Company, LLC St. Louis. MO • Phone: 800-325-3936 • www.pottersignal.com PRINTED IN USA 8830214-REV B • 2/23 PAGE 2 OF 2 F PAD300-PD a The Symbol of Protection Photoelectric Smoke Detector Features ts • Low profile.less than 2 inches with the base a • Wide selectable sensitivity range of 1.1 to 3.5%/foot • Detector communicates sensitivity to control panel • UT listed smoke calibration and sensitivity • Optional locking tab to prevent unwanted removal i y • Simple DIP switch address setting,no programming tool required y r fp �1 • Magnetic test switch • LED alarm indicator • Product includes 5-year warranty Nuft • HURL Listed for Smoke Control ' • U1,268 7th edition compliant 0328-0541 Description Technical Specifications The Photoelectric Smoke Detector is a listed Analog Addressable smoke detector compatible with fire alarm control panels that utilize Operating Voltage 24 VDC the Potter Addressable Device(PAD)protocol.The PAD300-PD is a low profile smoke detector with a wide sensitivity range.The detector Detector Current Draw 300 µA and base are made of a durable plastic in an off-white color to blend in with the ceiling. Alarm Indicator I LED The PAD300-PD has a sensitivity range of 1.1 to 3.5%per foot and is Alarm Set-point Range 1.1 to 3.5%/ft(3.6 to 11%/m) UL listed.The PAD300-PD features drift compensation and has built in dirty detector warning as well. The PAD300-PD and the control Installation Temperature Range 32 to 120°F(0 to 49°C) panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. Operating Relative Humidity 0%to 93%(Non-condensing) The total polling speed is less than five(5)seconds,well under the III. range requirements. Start-up Time Max. 1 sec. The detector is compatible with any of the PAD300 series detector bases and simply twists on. The PAD300-PD is addressed using DIP Maximum Number of Addresses 127 switches in the rear of the detector and can be easily programmed in Per Loop the field widurut special tools. Maximum Number of Lighted 30 Indicators in Alarm Per Loop Setting the Address Each addressable device on the SI.0 loop must have a unique address Color Eggshell White from I to 127 to function properly. The address is set using DIP witches_ Weight(without base) 91g(3.2oz) sBefore connecting a device to the SLC loop, take the following Dimensions(without base) fleight: 1.42 in(36mm) precautions to prevent potential damage to SLC or device.Verify the Diameter:393 in(100 mm) following: I. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company. TLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8810216-REV B • 223 PAGE I OF 2 • P POTTER PAD300-PD The Symbol of Protection Photoelectric Smoke Detector Air Velocity Ratings The PAD300-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 301,EDs that can be turned on simultaneously. If the system already has 30 LEDs on,the PAD300-PD will operate even though the LED may not illuminate. Operation The PAD300-PD is an analog addressable detector that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled.The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status.The polling LED can he turned off if desired for less conspicuous operation. The PAD300-PD with the PAD300-4DB or PAD300-6DB has a low profile of less than two(2)inches to blend into the surrounding environment.The detector includes an insect screen to prevent foreign objects from reaching the chamber and can be cleaned to restore operation of a dirty detector. Detector Sensitivity The PAD300-PD and the compatible control panel work in tandem to keep the sensitivity consistent.As the detector is installed over time,the detector compensates for the dirt in the unit until it is out of range.At that time,the panel will indicate a dirty detector.The detector will then have to be cleaned or replaced. The PAD300-PD can he programmed to provide a maintenance alert prior to reaching the dirty detector level which will allow for intervention prior to the detector going into trouble. This allows for detector replacement or cleaning prior to a nuisance trouble occurs. NOTE:As required by NFPA, do not install the detectors until all construction is complete and the work area has been thoroughly cleaned. If the detectors have been installed in a construction environment,they should be cleaned or replaced before the system is placed into service. Spacing The PAD300-PD is UI,listed with a recommended maximum spacing of 30 feet.Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. Compatible Bases All bases will mount on a single gang.3-1/2"octagon,3-1/2"square,double gang,4"octagon,4"square,50mm c/c,60mm c/c and 70mm c/c boxes. Device Description Stock No. PAD300-4DB 4"Detector Base 3992781 PAD300-6DB 6"Detector Base 3992782 PAD300-IB 6"base with an isolator module included 3992783 PAD300-RB 6"base with one Form-C relay contact. 2A(ii3 30VDC.0.5A(y), 125VAC 3992784 PAD300-SB 6"base with sounder module included.Sound pattern is provided from external source 3992785 PAD300-LFSB 6"base with 520Hz sounder module included.Sound pattern is provided from external source 3992786 Ordering Information Model Description Stock No. PAD300-PD Photoelectric Smoke Detector 3992775 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignaLcom 8830216-REV 13 • 2/23 P.-AGE 2 OF 2 04, A Smoke Detection firer „, tt 11111 Fireray® 5000 . Motorised Reflective Optical Beam Smoke Detector The Fireray` 5000 System is an auto-aligning,self-correcting infrared Features reflective beam smoke detector.Up to 2 detector heads can reportto a . Up to 2 Detector Heads reporting to One Ground Level Controller single ground level controller. In addition,each system controller houses two pairs of fire and trouble relays,one per detector.Once the detector • Range of 26.2 ft to 328 ft(8 m to 100 m) head is installed,using the easyfit mounting system an integral LASER can be activated.This allows the reflective prism to be located quickly and • Long range prism kit extends range from 60ft(SOm) with confidence. to 330ft(I OOm) • Built in Laser assisted prism mounting The Auto-Align function ensures proper alignment and maximum signal •Auto-Alignment 2 to 4 minutes per head during the beam installation.AutoOptimise automatically steers and maintains the beam in the optimum position for reliable performance. •AutOptimise:Auto-Correction due to building shift The signal generated in the transmitter element and reflected by the • Built-in electronic ULNLC/FM obscuration-acceptance fire test prism back to the receiver element is analyzed for the presence of smoke.The internal microprocessor determines an alarm condition • Contamination compensation when a predetermined level obscuration is reached. • Separate Trouble and Alarm relays for each of the 2 channels The system is designed to be mounted so the beam will project • Password protected settings between 19"(0.5m)and 24"(0.6m)below the ceiling. Lateral detection • Low current draw 5 to S.SmA may be up to 30ft.(9.144m)on either side of the beam,providing a maximum total coverage area of up to 19,800 square feet(60ft.x 330ft. • Built-in I/2"/M-20 conduit knock-outs on the system controller or I 8.29m x I OOm). For installations complying with UL268/NFPA72, • Programmable alarm thresholds: 10%- 60%in I%increments the maximum distance of Detector and Reflector from the ceiling must be 10%of the distance between floor and ceiling. • Programmable Fault and Alarm delay:2-30 Seconds Engineering Specification The system shall be capable of programming alarm thresholds of 10%to The projected beam type smoke detector shall be listed to U.L.268 and 60%in 1%increments.The system shall be capable of programming shall consist of up to two integrated transmitter, receiver detector heads delay to fault and delay to alarm from 2 seconds to 30 seconds in I and single low level remote control unit.The detector shall operate second increments.Test and acceptance of the system shall be carried out between a range of 26.2 ft to 328 ft(8 m to 100 m).The temperature by using the ULNLC/FM approved internal electronic obscuration fire range of the system shall be-4'F to 13 I`F(-20'C to 55°C).The test.The projected beam type smoke detector shall be a 4-wire 24 VDC beam detector heads shall include an integral built-in laser pointer to device to be used with a separately supplied 4-wire control panel.The assist prism mounting.The beam detector shall feature automatic gain Reflective beam type smoke detector shall be a FFE Ltd Fireray' 5000. control which will compensate for gradual signal deterioration from dirt accumulation on the lenses and prisms.The beams detector heads shall include AutoOptimise self-correcting motorized head feature to ensure unit is always receiving maximum signal available,and shall automatically ( ��� compensate for building shift.The unit shall include a low level remote • �+ �:� display and control unit with LCD read-out for set-up,reporting and testing of up to 2 separate detector heads.The System shall have Fireray 5000 separate Trouble and Alarm relays for each of the 2 channels. Accessories www.ffeuk.com • Fireray® 5000 fireray Construction Specification Listings Housing: Flame Retardant PC UL94 VO • UL-S3417 • CSFM-7260-1508-104 IP Rating: IP54 • ULC-53417 • FM Approved Finish: Light Grey/Black • MBA-22-08-E • Maryland-2243 Weight: Head&Controller 3.24 lbs(I.47 kg) Dimensions: Head:5.28"H x 5.16"L x 5.28"W Dimensions (134mm Hx 131 mm L x 134mm W) 795"(2o2mm) 3.43" (87mm) Controller:3.43"H x 9.06"L x 7.95"W — (87mm H x 230mm L x 202mm W) Up Prism:0.37"H x 4.13"L x 3.94"W 10 ° v M -- (9.5mm H x 105mm L x I00mm W) Y IL. o Electrical Specification Ina --e, cr. 110• Primary Input Power: 14 to 36 VDC IN Standby Current: Low Current Mode:5mA to 8.5rnA @ = j 24VDC depending on number of detector 5.28"(134mm) 5.28"(134mm) heads used 14 41 4--. r High Current Mode:37mA @ 24VDC 7;:,._.�\ 5mA to 8.5mA @ 24VDC depending on ® ` i Alarm Current: III ; h%I< �',r! — number of detector heads used Relay Contacts: IA @ 30VDC Resistive \\`�eon�) - Reset Time: 5 Seconds maximum Start Up Time: 45 Seconds Ordering Information Optical Wavelength: 850nm ,_ 5000-103 Reflective Auto Align beam smoke detector Alarm Threshold: 10%-60%(35%Default) I oft.to 330ft.(5m to I 00m).System includes I Detector Head, I Controller and 1 Prism. Temperature Rating: -4°F to I 3 °F(-20°C to 55°C) �* 5000-031 Additional Detector Head and I Prisms-Use For UL Listed Installations:32°F to 100°F up to one additional head per 5000-103 (0°C to 38°C) 5000-005 Universal Alignment Bracket-Used with F-5000 Relative Humidity: 0%to 93%RH non-condensing Detector Head.5000-007 and 5000-008 Range: 26.2 ft to 328 ft(8 m to 100 m) 5000-20 I Universal 130 Alignment Bracket-Used with F-5000 Cabling Between each 18- 4 AWG I-Pair Detector I lead,5000-007 and 5000-008 Detector&Controller: 5000-003 System Controller Specifications and wiring information are provided for information only and are 5000-006 Wall Bracket Mounts I or 4 Prisms believed to be accurate.FEE Ltd assumes no responsibility for their use.Data and 5000-007 4 Prism Alignment Adaptor Plate design are subject to change without notice.Installation and wiring instructions are 5000-008 I Prism Alignment Adaptor Plate shipped with the products and should always be used for actual installation.For more information.contact your Sales Representative. 5000-009 Controller Back Box 5000-010 Semi-Flush Trim Plate for 5000-009 5000-0I I Detector Surface Mount Uni-Box 5000-012 Detector 2 gang Mounting Plate f I e 5000-014 Ceiling Pendant Mount Bracket 1000-018 Wire Protective Cage for Detector J-, 1000-019 Wire Protective Cage for Controller ..j US Saiet ancl 'UistnOuton 23901 Replacement Prism ,cif i FFE Limited 1455 Jamike Ave Ste 200 - � �2 Erlanger,ICY41018-3147 USA Qzr..:0 T+' t+1 859 957 1570 e america@ffeuk.com v."www.ffeuk.com Document Part Na 24-03 18-04 /ww ffe u I<.eo m Smoke Detection s , - re le- . Accessories Overview For use with Fireray" For use with Fireray 5000 3000 50R/ 2000 "'" - 5000 3000 50R/ 2000 100R EExd ,...,/ 100R EExd 5000-005:Universal Mounting Bracket. d ❑ d ❑ 3000-201:Adjustment Bracket. I IY E( ❑ For use with Fireray`5000 and accessories. Adjustment Bracket for Fireray"3000 offering Bracket pivots for accurate alignment of beam 360"rotation plus 180'adjustment; can also detector and prisms. be used with Prism Adaptor Plates. k-n 5000-201:Adjustment Bracket. 155f ❑ ❑ 3000-202:Flush Mount Plate. ❑ 19i ❑ ❑ Adjustment Bracket for Fireray'5000 offering Flush Mount Plate for Fireray`"3000 360°rotation plus 140°adjustment. F: } 5000-007:4 Prism Adaptor Plate. /Y ❑ _ ❑ 3000-203:Flush Mount Plate. ❑ ❑ ❑ Comes pre-drilled to mount 4 prisms. Flush Mount Plate with 4°square back plate Designed to mount on the Universal Mounting for Fireray 3000 Bracket 5000-005.Prisms and Bracket(5000- 005)are ordered separately. Crr.,���.,...z puII .se.. tt Etfrfl der n. MIR II ■ im IIIu an Eil/A si l¢ " 144"6yt1UYM 5000-008:Single Prism Adaptor Plate. u ❑ [yr ❑!�_4. 1000-019:Protective Wire Cage. ❑ ❑ ❑ Comes pre-drilled to mount I prism.Designed Fireray"5000 Controller Protective Wire Cage. to mount on the Universal Mounting Bracket Made to mount to a gat surface.Includes 4 Philips 5000-005.Prism and Bracket(5000-005)are Head screws and mounting hardware. ordered separately411111* MOW 23901:Prism. Yi ❑ El --,, Replacement prisms for Reflective Beam �, ` Smoke Detectors. -- ,; 1000-018:Protective Wire Cage. LJ ❑ ❑ Fireray`3000&5000 Detector Protective Wire 5000-004:Long Range Prism Kit. IYr ❑ �—/ Cage.Made to mount to either the 5000-01 I lJ El Uni-Box or to a flat surface.Includes 4 Philips 3 additional prisms for use with Fireray'5000 when the prism installation is between 160 and Head screws and mounting hardware. 330 ft from the detector head Itt aw. r .t .sir: • yt s ` <e6 5000-006:Prism Wall Bracket. u ❑ I ❑ 1000-020:Protective Wire Cage. ❑ ❑ d El Reflector Wall Bracket comes pre-drilled to Fireray' 50/100 RU Detector Protective Wire mount I (Up to 160 ft)or 4(160 to 330 ft) Cage.Made to mount to either the 0608 back prisms.Hole pattern on side mounting flange box or to a flat surface.Includes 4 Philips Head similar to Unistrut.Prisms ordered separately, screws and mounting hardware. $ POTTER PAD100-TRTI The Symbol of Protection Two Relay Two Input Module Features PhSEtms�Fo • Single module with dual contact monitoring inputs • Two(2)Class B of one(I)Class A monitoring inputs p. 4 P • 'Iwo(2)Form C relay contacts ` TRg il5 • SLC Class A.Class X&Class B • Mounts in a standard 4"or double gang box • Wiring terminals accessible when mounted in box I • All wiring terminals accept 22 to 12 AWG „••••^".r.i • Product includes a 5 year warranty • HURL Listed for Smoke Control ;VOTE':This addressable module does not support 2-wire smoke detectors. 44* .0) (211 APPROVED 1 Description Technical Specifications The PADI00-TRTI uses one (1) SLC loop address when monitoring Operating Voltage 24.OV two(2)Class B circuits or one(1)Class A circuit.The PADIOO-TRTI also provides two (2) Form C relay contacts. The module mounts Max SLC Standby Current 240pA on either a 4" square or double gang box. The module is capable of monitoring two (2) separate Class B circuits making it ideal for Max SLC Alarm Current 240pA monitoring sprinkler waterflow and valve tamper switches when they are located in the same proximity. The PAD100-TRTI includes one Relay Contacts 2A rt 30VDC,0.5A ty125VAC red LED to indicate the module's status.In normal condition,the LED Max Wiring Resistance of 1004 flashes when the device is being polled by the control panel.When an IDC input is activated,the LED will flash at a fast rate. Max Wiring Capacitance of I I µF DC Application EOLResistor 5.IKS2 The PADI00-TRTI is compatible with Potter's IPA and AFC/ARC Operating Temperature o 0 series addressable lire alarm control panels. The PAD100-1RT1 is Range 32 to 120 F(0 to 49 C) an interface module used to monitor dry contact devices such as sprinkler waterflow. valve tamper switches. or conventional pull Operating Humidity Range 0 to 93%(non-condensing) stations. The module is capable of monitoring two separate Class B or one Class A circuits. The PADI00-TRTI also provides two(2) Max no.of Module Per Loop 127 units form C relay contacts. 4.17 (I06mm)L x 4.17- Dimensions Setting the Address (lo6mm)w h 1.14-(29mmD Each addressable SLC device must be assigned an address.The Mounting Options Standard 4"Square or address is set using the DIP switch located on the PADI00-TRTI.The Double Gang Box he PADI00-'IRTI is assigned a single device address,each input and Shipping Weight 0.6 lbs relay is identified as a sub-point of that single module address.For example. if the address number is assigned as`8".the RLYI relay will be"8.1 the RLY2 relay will he"82.the B I input will be"8.3" and the 132 input will be"8.4". Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device: I. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company. LTC • Si_ Louis, MO • Phone: 800-325-3936 • www.potterstgnal.com 8830080-REV D • 12,18 PAGE I OF 2 P POTTER PAD100-TRTI The Symbol of Protection Two Relay Two Input Module Installation Using Compatible Electrical Box Fig I �arT IG () Wiring Diagrams PAD100-TRTI With One Class A Circuit Fig 2 MOVE THE"CL-A"DIP SWITCH TO"UP"POSITION FOR CLASS WIRING CD i) FROM FACP OR rI sew PREVIOUS MODULE Ber es pq TO NEXT MODULE L \) r 'I H L'w I TWO(2)FORM C w 1 RELAY CONTACTS J14 L Cf f CID NOTE: END-OF-LINE RESISTOR IS NOT REQUIRED PAD100-TRTI With Two Class B Circuits Fig 3 TO"D0WN"POSITION rIO FOR CLASS O WIRING CD riG L]3k4 --` J FROM FRCP OR PREVIOUS MODULE \ I TO THE NEXT MODULE I TWO12)FORM C END OF LINE r .}-. RELAY CONTACTS RESISTOR T r S.1R OHM'0W £ L r - Part 03005013 _ END D- ✓ �� / RESISTOR Part O0 $W Part 05013 NOTICE It is possible that the internal relay in the PAD100-T'RTI may he shipped in the non-normal/activated state.To ensure that the internal relay is set to the normal state,connect the module to the SLC loop and reset the control panel before terminating the wiring to the modules output. Ordering Information Model Description Stock No. PAD100-(RTI Two Relay Two Input Input Module 3992701 Potter Electric Signal Company, LLC • St. Louis. MO • Phone: 800-325-3936 • www-pottersignal com 8830080-REV D • 12,18 PAGE 2 OF 2 P0TTER PAD100-OROI e The Symbol of Protection One Relay One Input Module Features 4thErnsz�o • One(1)Class B monitoring input y • One(1)Form C relay contact � �' talt• SLC Class A.Class X&Class B 2 THE V� • Mounts in a standard 4"or double gang box • Wiring terminals accessible when mounted in box • All wiring terminals accept 22 to 12 AWG • Product includes a 5 year warranty er � , • UUKh Listed for Smoke Control NOTE:'this addressable module does not support 2-wire smoke detectors. ell APPROVED f I Description Technical Specifications The PAD100-OROI uses one (1)SLC loop address when monitoring Operating Voltage 24.OV one (1) Class B circuit and providing one (1) Form C relay contact. The module mounts on either a 4- square or double gang box. The Max SLC Standby 240 A Current N module is capable of monitoring one(1)Class B circuit.The PAD100- OROI includes one red LED to indicate the module's status.In normal Max SLC Alarm 240pA condition, the LED flashes when the device is being polled by the Current control panel. When a the input is activated, the LED will flash at a Relay Contacts 2A r00VDC.0.5A a 125VAC fast rate. Max Wiring Resistance of 1DC 100 52 Application Max Wiring ThePAD100-OR01 is compatible with Potter's IPA and AFC/ARC IµF Capacitance of1DC series addressable fire alarm control panels.The PAD I00-OROI is an EOL Resistor 5.1K S2 interface module used to monitor dry contact devices such as sprinkler Operating Temperature 32 to I20°}'(0 to 49°C) watelflow. valve tamper switches. or conventional pull stations. The Range module is capable of monitoring one Class B circuit. The PADI00- Operating Humidity 0 to 93%(non condensing) OROI also provides one(1)form C relay contact. Range Max no.of Module Per Setting the Address Loop 127 units Each addressable SLC device must be assigned an address.The 4.17-(106mm)L x 4.17" address is set using the DIP switch located on the PAD100-OROI. Dimensions (106mm)W x 1.14-(29mm)D When the PAD 100-OROI is used to monitor one Class B circuit a single device address is assigned.the input and relay are then Mounting Options Standard 4"Square or identified as a sub-point of the module address. For example,if the Double Gang Box address number is assigned as"8".the RI Y1 relay will be"8.1"and Shipping Weight 0.6 lbs the IN I input will be"8.2-. Before connecting a device to the SLC loop. take the following precautions to prevent potential damage to the panel or device: 1. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis_ MO • Phone: 800-325-3936 • www_pottersignal.com 8830081-REV I) • 12,18 PAGE 1 OF 2 POTTER PAD 100-O RO The Symbol of Protection One Relay One Input Module Installation Using Compatible Electrical Box rig I t w, yi I • I \i hr \ i Wiring Diagram PADIOO-OROI With One Class B Circuit Fig 2 r FROM FACP OR — \ PREVIOUS MODULE o �_ ,�, ONE(t)FORMC - RELAY CONTACT END-OF-LINE RESISTOR 5.1KOHM 1/2W — — Part#3005013 NOTICE It is possible that the internal relay in the PAD100-OROI may be shipped in the non-normal/activated state.To ensure that the internal relay is set to the normal state,connect the module to the SI.0 loop and reset the control panel before terminating the wiring to the modules output. Ordering Information Model Description Stock No. �► PAD100-OROI One Relay One Input Input Module 3992702 Potter Electric Signal Company, LLC • St Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830081-REV D • 12/18 PAGE 2 OF 2 POTTER PAD100-RM The Symbol of Protection Relay Module Features 4,,eme4F0 • One(I)Form C relay contact• * •�•, 1 '3"y, • s SLC Class A.Class X&Class B • • Mounts in a standard 4-or double gang box THE O`' • Wiring terminals accessible when mounted in box 1.. - All wiring terminals accept 22 to 12 AWG • Product includes a 5 year warranty • UUKL Listed for Smoke Control OpOTTER APPROVED Description Technical Specifications The PAD100-RM uses one (I) SLC loop address to provide one (I) Operating Voltage 24.OV Form C relay contact. The module mounts on either a 4" square or double gang box.The PAD100-RM includes one red LED to indicate Max SLC Standby 240pA Current the module's status. In normal condition, the LED flashes when the device is being polled by the control panel. Max SLC Alarm 240pA Current Application Relay Contacts 2A n30VDC.0.5A(ry125VAC The PAD100-RM is compatible with Potter's IPA and AFC/ARC Operating Temperature 32toI20°F(0to49°C) series addressable fire alarm control panels. The PAD100-RM is an Range interface module providing one(1)Form C relay contact. Operating Humidity 0 to 93%(non-condensing) Range Setting the Address Max no.of Module Per 127 units Each addressable SLC device must be assigned an address. The Loop address is set using the DIP switch located on the PAD100-RM. The Dimensions 4.17' (106mm)l,>"4.17" PADI00-RM uses a single device address to identity relay contacts. (106mm)W x 1.14"(29mm)D fictive connecting a device to the SLC loop. take the following Mounting Options Standard 4"Square or precautions to prevent potential damage to the panel or device: Double Gang Box I. Power to the device is removed. Shipping Weight 0.6 lbs 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company. LLC • St. Louis MO • Phone: 800-325-3936 • w•ww-pottersignal.com 8830084 -REV t) • 12,18 PAGE I OF 2 d�5l J 4 % •/ Owl y Y p Et,s} l;k. ft.,, Y3{ e Indoor Selectable- ,'01 a - ' 1f ' M1 Output Speaker a . Strobes and Dual fite 5y g4 �M \ Voltage Evacuation 4 i „, , �� . �,', TSpeakers for Ceiling A Applications J System Sensor L-Series selectable-output speaker strobes , and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates, • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers. In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on ceiling units: feedback to ensure that wiring is properly connected,rotary switches 15,30, 75,95, 115, 150,and 177 to select voltage and power settings,and 7 field-selectable candela settings for both wall and ceiling speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic distortion of the SP speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage(25 sound output while still offering high volume sound output for use in and 70.7 Vrms)and power settings(Y, '/a, 1 and 2 watts) high ambient noise applications. • Speakers offer high fidelity and high volume sound output L-Series makes installation easy • 520 Hi+/-10%square wave tone capable with compatible FACP •Attach a universal mounting plate to a 4 x 4 x 2VB inch back box. • Compatible with System Sensor synchronization protocol Flush-mount applications do not require an extension ring. • Electrical compatibility with existing SpectrAlert and SpectrAlert •Connect the notification appliance circuit or speaker wiring to the Advance products terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Tamper-resistant construction inserting the product tabs into the mounting plate grooves.Hinge • Updated modern aesthetics the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. SIGNALING U) ® * ) LISTED Pp :,).F FM { ,acd 'czo{ 732D Ic53Cu`05 Icr A',.Exr mncels AVCJSEFA-cj•0.323;2A'E•Pace 1 L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering SpecificationsR� General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2'/s-inch back box.A universal mounting plate shall be used tor mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•Circuit3^^Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified,unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150, 177. Speaker The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/is x 411/16 x 21/s-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Ceiling-Mount Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in,25 mm With Surface Mount Back Box 6.9 in, 176 rnm 3.5 in,89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in,73 mm With Surface Mount Back Box 6.9 in, 176 mm 5.37 in, 136 mm *When using 12AWG, 14 AWG,or adding extra wires in the box,a deeper box or extension ring is recommended. Electrical/Operating Specifications Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 VDC/FWR 1,2 Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.510 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4,000 Hz3 Power 1/4,'/.1, 2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd. 3.520 Hz+/-10%square wave tone capable with compatible FACP. NVO::%,6 9-03023120iF•°age2 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) 11:8411 8 to 17.5 Volts 16 to 33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Ceiling-Mount Speaker Sound Output Setting UL Reverberant(dBA IR10 ft) UL Anechoic(dBA C 10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 85 85 2 W 88 88 Ceiling-Mount Speaker Strobe Sound Output Setting UL Reverberant(dBA @10 ft) UL Anechoic(dBA C 10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 L-Series Dimensions 6.a'Ga. _. to- --.., 163' It]3 mm) - (Mtmm) (0166 mm) 4_= =ppL i�yi i `2 , �tF \ 4 ti 4 /t t€ .�� P A,�� ICI 111 •,ult1y Y I1 11al IL)IWIII I .. gI \tUX�� fray' 2 'G07044'// \ �Q rr+F`v"iiN.338 `3 Ceiling Speaker _ 2.83' ,_ ._ 6.6'Eia q2.9 mm) L63• (In mm) ow (4166 mm) (aa t mm) 08,8T>µvr m�q s=_:_3i3 ic;.? �t�t'd 'I,' :11:lIl AI 1:084111 i' (48%2:48).. 1y t 4714160f AC54.1 JO Ceiling Speaker Strobe Av::=sec cs•ras,z,.t..:�:;�-. 7 S nv f yk L"�,hddy frafi L s yf 1 ` Indoor Selectable- �t3 `�f' Out ut Strobes and Horn Strobes for Ceiling Applications �.. System Sensor L-Series audible visible notification .. _. products are rich with features guaranteed to cut installation times and maximize profits with lower YY, current draw and modern aesthetics. Features The System Sensor L•Series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry • Plug-in design with minimal intrusion into the back box with lower current draws and modern aesthetics.With white and red • Tamper-resistant construction plastic housings,wall and ceiling mounting options,System Sensor • Automatic selection of 12-or 24-volt operation L-Series can meet virtually any application requirement. at 15 and 30 candela The entire L-Series product line of ceiling-mount strobes and horn • Field-selectable candela settings on ceiling units: 15,30,75,95,115, 150,and 177 strobes include a variety of features that increase their application versatility while simplifying installation.All devices feature a plug-in • Horn rated at 88+dBA at 16 volts design with minimal intrusion into the back box,making installations • Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and time- • Universal mounting plate for ceiling units consuming ground faults. • Mounting plate shorting spring feature checks wiring continuity To further simplify installation,the L-Series utilizes a universal before device installation mounting plate so installers can mount them to a wide array of back • Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes.With an onboard shorting spring,installers can test wiring Advance devices continuity before the device is installed. • Compatible with MDL3 sync module Installers can also easily adapt devices to a suit a wide range of • Listed for ceiling mounting only application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with two volume selections, Agency Listings SIGNALING 's LISTED APPROVED --`� �1 J15 FM eppmvca Fx::en' 7l25 1653I5o1 5401 tel P353 ]135-1 E539503 30510Sr5E3 AVU3Ft'fg0-•12,L1/2'O1?•Page 3 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double- gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series products,when used with the Sync•Circuit'"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts.24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 115, 150,and 177. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for lire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR' Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9"diameter x 3.4'high(175 mm diameter x 86 mm high) (SBBCWL.SBBCWL) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S.PC,and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDs@E6-GL•"�IO�F;r •"one 2 UL Current Draw Data Lit Max.Strobe Current Draw(mA RMS) UL Max,HOrn Cu trDtaw(mA RMS) 8-175 Volts 16-33 Volts 8-175 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 87 41 60 Temporal High 39 44 54 Range 30 153 63 86 temporal Low 28 32 54 75 N/A 111 142 Non-Temporal High 43 47 54 95 N/A 134 164 Non-Temporal Low 29 32 54 115 N/A 158 191 3.1 KHz Temporal High 39 41 54 150 N/A 189 228 3.1 KHz Temporal Low 29 32 54 177 N/A 226 264 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded I1igh 42 43 54 ,UL Max.Curte MM(mA RMS),Ceiling Horn Strobe,Candela Range(15-177 ed) 8-175 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K lemporal Low 103 163 54 88 143 155 185 212 252 3,1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1 K Non-Temporal Low 103 169 54 88 131 155 187 217 259 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones and Sound Output Data Horn Strobe Output(dBA) 4.- sti 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 K1 lz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 AVnS%E32.12/G,r0p 1,.rage 3 L-Series Dimensions 2,47'(62.7 mm) — 1.37"(34.8 mm) - - 6.92"diam. - 6.83"diam. (175.77 mm) (64 mm) (173 mm) 0.eTP4 w l ( 7 '7:-...:';::--1;.:.717. \ lI r 8'o po 0-, 1 i �C • r • II ( . -soOog J A0545-00 40546-00 Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box C3 _ �w+n extxt i ® . --- 1 7 '' Nl/ 4yJTLn5 -emsP /' s f I ` ? - —/ tovnz -,II i dcC °v- „y ,, 1 8+ ' . _ i 0 l0 yl'/ cr rn ��V s,3 - \1JlC A049,1 91 A0531 01 2-Wire Ceiling Mount Horn Strobes 4-Wire Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box with Ceiling Surface Mount Back Box L-Series Ordering Information Model Description Model Description Ceiling Horn Strobes Ceiling Strobes PC2RL 2-Wire,Horn Strobe,Red SCRI. Strobe,Red PC2WL 2-Wire,I loin Strobe,White .--A• SCWL Strobe,White PC4RL 4-Wire,Horn Strobe,Red SCWL-CLR-ALERT Strobe,White,ALERT PC4WL 4-Wire,Horn Strobe,White Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring While SBBCWL Ceiling Surface Mount Back Box,Red SBBCWL Ceiling Surface Mount Back Box,While For a ceiling-listed horn-only device,see AVIJS865"Indoor Selectable- Output Horns,+Strobes,tr_ and Horn Strobes for Wall Applications". ✓,STET r/ fs`2017 System Sensor. �' SENSOR` 3825 Ohio Avenue•St.Charles, IL 60174 Proauctopeckabons ubiecncchangewutroutnape vs asysiemsenacrco, Phone:800-SENSOR2•Fax:630-377-6495 for Loner:product mtarmanon,mdudng the latest wtson arms bate sheet AVD5868 02•le/01/2017 m 1 SjS) S ) SIS))1)Iit;/ 1 tt.I 1.t11.1.1Y01.)�tl 1 fill *0001°1100111' Ili/ P till 11 tt 11111t11ttt1111 111t tl II 1 I. I11i I I 1 1 Indoor Selectable- ;,;� st ; ,;,1 11 w II Output Speakertvor Strobes and Dual Voltage Evacuation Speakers for Wall Applications ) System Sensor L-Series selectable output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. The System Sensor L.Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal Features mounting plate that allow the installer to pre-wire mounting plates, • Plug-in design and protective cover reduce ground faults dress the wires,and confirm wiring continuity before plugging in the speakers. In addition,a protective plastic cover prevents nicked • Universal mounting plate with an onboard shorting spring tests wires by covering exposed speaker components. wiring continuity before installation • No extension ring required These devices also enable faster installations by providing instant • Field selectable candela settings on wall units: feedback to ensure that wiring is properly connected, rotary switches 15,30,75,95, 110, 135, 185 to select voltage and power settings,and 7 field-selectable candela settings for wall speaker strobes. • Automatic selection of 12-or 24-volt operation at 15 and 30 candela The low total harmonic distortion of the speaker offers high fidelity • Rotary switch simplifies field selection of speaker voltage sound output while still offering high volume sound output for use (25 and 70.7 Vrms)and power settings(1/4, Ya,1 and 2 watts) in high ambient noise applications. • Speakers offer high fidelity and high volume sound output System Sensor L-Series makes installation easy • 520 Hz+/-10%square wave tone capable with compatible FACP •Attach a universal mounting plate to a 4 x 4 x 2t/e inch back box. • Compatible with System Sensor synchronization protocol Flush-mount applications do not require an extension ring. • Electrical compatibility with existing SpectrAlert and SpectrAlert •Connect the notification appliance circuit or speaker wiring to the Advance products terminals on the mounting plate. •Attach the speaker or speaker strobe to the mounting plate by • Tamper-resistant construction inserting the product tabs into the mounting plate grooves.Hinge • Updated modern aesthetics the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a Agency Listings catch until it is secured with a captured mounting screw. SIGNALING APPROVED LISTED >pG aF FM appmvec except (320-1653t505 t0F Al.EAT rp0Els 305'493 AVDsps7 G3-€,%25,7-PA!.3e • L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Sp Cations General L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch hack box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate al the universal mounting plate.Also,L-Series speaker strobes,when used with the Sync•Circuitt"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module. 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified,unfiltered power supply Wall- mount speaker strobes shall have field-selectable candela settings including 15,30,75,95, 110, 135, 185. Speaker The speaker shall be aSp System Sensor L-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms.It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize strobes at 1 Hz.The module shall mount to a 4"/1a x 4))/16 x 21/a-inch back box.The module shall also control two Style Y (class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical SpecificationsAfxxximpic. Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10to93%non-condensing Dimensions,Walt-Mount Length Width Depth SPL Speaker 6.5 in, 165 mm 5 in, 127 mm 0.97 in,23 mm With Surface Mount Back Box 6.6 in,168 mm 5.1 in, 130 mm 32 in.82 mm SPSL Speaker/Strobe 6.5 in,165 mm 5.0 in, 127 mm 2.3 in,58 mm (including lens and speaker) With Surface Mount Back Box 6.6 in,168 mm 5.1 in, 130 mm 4S in. 116 mm 'When using 12AWG, 14 AWG,or adding extra wires in the box,a deeper box or extension ring is recommended. Elechical/Operating Specifications ' 1)-.1` '" Nominal Voltage(speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC or regulated 24 DC/FWR' Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4000 Hz' Power Y,,'/, 1,2 watts 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 and 30 cd 3.520 Hz+/-10%square wave tohe capable with compatible FACP. AVDS8O%-03•0E 9019•rage 2 UL Current Draw Data IL Max Strobe Current Draw(mA RMS) = 8 to 1 Z5 Volts 16 to 33 Volts Candela DC DC FWR 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 _ . 185 N/A 222 257 Sound Output Speaker Strobe :.. A. . -.' '. .1 1/4W 3}? 1W 2W UL Reverberant(dBA @10 ft) 77 i7n 83 86 UL Anechoic(dBA @10 ft) 77 80 83 86 Sound Output Speaker '"� '. Z x `3 l `" /W /W 1W 2W UL Reverberant(dBA @10 ft) 79 82 85 88 UL Anechoic(dBA @10 ft) 79 82 85 88 L-Series Dimensions 0.97, _.. __. .-_. 1.63" _ (24.64 mm) (4166 mm) 231 -_ - 1.63" 5' - 5' - (58 mm) f (41.66 mm) (127mm) (127mm) 1.39• e --I. d- (35.31 mm) ifTsti=MIP ae°asse ° . ' ° ° ga eat ° oeoe °? P Yo°N4 �� j' _16mm) 1oa 165mm) gosae ' �g ! Wall-Mount Speaker Wall-Mount Speaker Strobe AVpS4€7—O •6I6129"9•Fags 3 Surface Mounting • -• .. 'r= ,)�tQi�f�rGtFe pQp rreF4j�' <- , r fuQ, . I Itl is f�[t ff�t frtrfr m��� (n 4r,k J(113]�1991�1s.'I r n i t f''sIl l : `''+'5, is rI I ; JJ )))%I � Y p diftti�/I [ »t-^,--..av`' A052301 Wail-Mount Speaker Strobe with SBBSPRU SBBSPWL Surface Mount Back Box L-Series Ordering Information Wall Mount .. . _..' ..... rrr3 - °'`' .. ,a' ir' White Red Description SPWI.. SPRL Speaker only mot, SPSWL SPSRL Speaker Strobe SPSWL-P SPSRL-P Plain Speaker Strobe SPSWL-ALERT — Speaker Strobe,Amber Lens SPSWL-CLR-ALERT Speaker Strobe Clear Lens SPSRL-SP Speaker Strobe,Fuego White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBSPWL SBBSPRL Surface Mount Back Box for Speakers and Speaker Strobes TR-2W I H-2 Wall Mount Trim Ring Notes: All-P models have a plain housing(no"FIRE"marking on the cover) M SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 523,0 lD9stera Sensor C Phone:800-SENSOR2• Fax:630-377-6495 P tlual specacarcns subje tro cnanye wurounerce mans tem;ansocco SEN✓©w y for anent protluct olor aton.ina'ou•tre latest vow:of vas tlam-51me1 WWW.S StemsensOr.GOm AVOSaE'.03•Efal,C9 • L-Series Specifications Architect/Engineer Specifications General L-Series standard horns,strobes,and horn strobes shall mount to a standard 2 x 4 x 1,/8-inch back box,4 x 4 x 1'/-inch back box,4-inch octagon back box,or double-gang back box.L-Series compact products shall mount to a single-gang 2 x 4 x 1'/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series products,when used with the Sync•Circuit"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply Strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95, 110, 135,and 185. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three patterh and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize Strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4"he x 4n/r x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR' Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7-W x 1.91-D(143 mm L x 119 mm W x 49 mm D) Compact Wall-Mount Dimensions(including lens) 5.26"L x 3.46"W x 1.91"D(133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6""L x 4.7"W x 1.25"D(143 mmL x 119 mmW x 32 rom D) Compact Horn Dimensions 5.25"L x 3,45"W x 1.25"D(133 mm L x 88 mm W x 32 mm D) 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. AV[1SF65C5•2/22(2018•Pane 2 • UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High _ 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max.Current Draw(mA RMS),Wall Horn Strobe,Candela Range(15-185 cd) 8-175 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 110Cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Tcmportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 Horn Tones and Sound Output Data Horn and Hom Strobe Output(dBA) 8-17.5 16-33 Switch Volts Volts Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal I ow 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal I ligh 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9" Coded High 85 90 90 10' 3.1 KHz Coded High 84 89 89 'Settings 9 and 10 are not available on 2-wire horn strobes.Temporal coding must be provided by the NAC.It the NAC voltage is held constant.the horn output remains constantly on, IV) ba YFDB nl 4 44 ' F D FIRE DOCUMENT BOX c"` The FDB is the perfect fit to meet the demanding code requirements today. SAE's number one goal is to manufacture code compliant solutions and this FIRE ALARM CU ENTS product allows you to do just that. NFPA 72 2010 Records / Programs ! Software section 6.2.2.1 states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit." This durable 16 gauge steel enclosure with a solid piano hinge and key lock will keep all of your code required documents in one safe place. Along with your fire alarm software you can store your test & inspection documents, service records, manuals & AS built drawings for the system. The FDB is designed to hold critical manuals and documents with a durable steel retainer. It has Standard Features: designated hooks to organize key rings and hold • 2 Key ring hooks to hold system keys important business cards for easy access and • Business card holder for key contacts reference. Inside the cover it has a organized note • Overall Dimensions are 12" x 13" tall and table that allows for documentation for passwords 2 '/4 deep and other critical system information. • 16 gauge steel box and cover for security • Durable powercoat baked on finish other colors available • Standard%"cat 30 key lock other lock as- semblies available • Solid stainless steel piano hinge • Permanently screened white ink 1" high "Fire Alarm Documents" • Legend sheet for passwords and system information ISO 9001 a . lm assirr REGISTERED Space Age Electronics, Inc. COMPANY ADA 0"!sae.com 80 800.486.1723 Toll Free NFPA Made Ini`U.S.A. 508.485.0966 Local 508 485 4740 Fax Space Age Electronics, Inc. 2013 No Excuses, Just Solutions! ED0447 LT10505 Rev 1/2 SPACE AGE ELECTRONICS, INC. Specifications: The fire alarm documents box (FDB) shall be constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "FIRE ALARM DOCUMENTS " with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12" stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure.A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. a wen ` Gropeey lnb,malon Mlnlmu Rep Irce Ooe menulbn itK•fUN) Key Ring Hooks A 4 C i t .l" ceelllcxlons ane Approval ,n� eYtln m.,a m..o w,a„„ _.. k 4 L e 1 s, rm ireienenen cem wr_ "'°" . •` a �..wa ew PY _ Business at Card Holder ' ' y EOUlvmenl Mo,malion Ne Y o •",m Y"X 1 i *:NE . ..... u �` d Aian•w. _ w — A. \.l , 1 Sn_.p.Eenmtr.. Esout_anw inneuagyp e¢-seae ..wx,•xms L10E4<Re, 4 Y Legend sheet for storing system information including contacts, sign-off, maintenance & ' test information,and alternate locations of additional records. Ordering Information: Part# Description SSU00672 Fire Document Box RED BOK Space Age Electronics, Inc. SSU00673 Custom screening with your Logo www.I sae-com 800.486.1723 Toll Free Check out our Infinity line eFAD single gang 2 Gig digital storage 508.485.0966 Local solutions (IAMEFAD) 508.485.4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0447 LT10505 Rev.B 2/2 y�s `:`E SPACE AGE NICS, INC_ Specifications: The Space Age Electronics, Inc. Flush Device Guard (FDG), Horn Strobe Guard (HSG) and Pull Station Guard (PSG) shall be manufactured of hardened steel rod measuring 7 gauge. All joints shall be welded for superior durability. These guards shall be designed to not interfere with the proper operation of the devices nor shall they sufficiently block the device as to render it's purpose unrecognizable. These guards shall be nickel chrome finished. HSG PSG FDG 6.a,. —71 tr- ..- n 1 i 1 4 1/2" 4 9/16" 7.4"6.6"4.5• 6 5/8" 5 5/8" 7 3/8" 6 1/2" 0 07 O I Q 4 5/8" 6 5/8" 7.5"—.- 8 3/16" 63/16"-0- 8 7/8" 6 7/8" z j 7 U_ 3 3/4" 6" 6 1/4" 4 1/4" — 3.7., Ordering Information: Part# Description SSU03502 PSG Pull Station Guard s SSU03503 HSG Horn Strobe Guard ... Z SSU03504 FDG Flush Device Guard Space Age Electronics, Inc. www.lsae.com 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0082 LT10172 Rev.G 2/2 .., D U RAC , . i SLA Batteries General Purpose, ULTRA w -,. -1�. � Duracell® Ultra SLA technology offers high-density power that out- performs traditional lead acid batteries. The Absorbed Glass Mat(AGM) construction is designed for efficient gas recombination and allows for 91,44/164 maintenance-free operation. Duracell' Ultra SLA batteries maintain their high capacity with a design that is resistant to damage caused by deep discharge. ' Every Duracell® Ultra SLA , . ; battery is inspected to ensure ", . 0 I ' J.' the highest standards in materials and fabrication. p'` xi Cycles at 100% Discharge '� �`" '� ,., > •` w aenaw+'. � '., �'' 5EA4E0 NO S%LU������ %., L 4 13)b}))3T1ID)N7U11 S .� PR iI OF GUARANTEE 4 Features: • Duracell® Ultra SLA GEL batteries contain a proprietary grid alloy formula combined with advanced plate curing techniques to provide maximum performance. • Duracell® Ultra batteries contain a unique electrolyte formula with a special sub-colloid additive for higher reliability and longer life. ` • Will achieve more life cycles than standard AGM and Deep Cycle batteries. • The unique construction and sealing techniques of these batteries QUt?ACELL are guaranteed to give you leak-proof operation. ULTRA ,.,,...IT., , • Heavy-duty lead calcium tin alloy grids provide an extra margin of performance +m and service life in cyclic applications, even after repeated over-discharges. T • Quality Assurance Engineers monitor and control the entire production process. • Recycling of used SLA batteries available. ( ,k • Delivery available. Li Quantities LiE3LJ DOD[7:1 AVAILABLE . N: Sealed �Acid Maintenance Free Spill Proof 1 Year Stringent Quality Design Warranty Control , .. � ,,,,, batteriesplus.com 1$00 677-8278 I DURACELL SLA Batteries CATTPRALOG#nMe ULTRA FIXTURE TYPE NOTES s _7 , y � ,:,. atr F 'II� SI':nS ILat,rkN "f"'S) Ti"1117 a ° a�LOf a n3 S tt DU511208WL 12V 0.8 378 098 2.4 WL 0.77 DURAI21.3F 12V 1.3 3.82 1.69 2.28 F1,T1 - 1.37 i DURAIZ 2.3F 12V 2.3 6.97 1.38 264 F1,T12.04 _- DURA12-2.9F 12V 2.9 3.11 2.2 3.9 F1,T1 2.36 -__- DURA12 3 3F 12V 3.3 5.28 2.64 2.63 FI,T1 - 3.18 DURA12-3.3F2 12V 3.3 _ RAYA12-4F 12V 4 3.54 2.76 4.21 Fl,T1 DURA12-5F 12V 5 3.54 2.76 4.21 F1,T1 - • - DURA12 5F2 12V 5 3.56 2.77 3.94 F2,T2 - - DURA12-5.1A --..,_.12V 5.1 5.51 1.89 4.21 F1,T1 - 4.6 DURA12-5.5F 12V 5.5 3.54 2.76 '. 3.98 - - RAYA127F 12V 7 5.95 2.56 3.94 F1,T1 - DURAI27F 12V 7 5.94 2.56 394 FI,T1 - - DURA12 7F2 12V 7 5.94 2.56 3.7 F2,T2 _„_p DURA12-8F 12V ..,.___ 8 5.94 2.56 394 F1,T1 - - _.DURA12 8F2 12V 8 5.94 2.56 3 94 F2,T2 - - DURA12-9NB -- - _-- 12V 9 5.95 2.56 3.9 N81 - - DURA12 9F2 12V 9 5.95 2.56 3.94 F2,T2 . - DURA1210F2 12V 10 5.95 2.54 4.38 F2,T2 7,5 DURA1211N8 12V 11 5.28 3.15 65 - 10.1 DURA12 12F2 .... 12V 12 5.94 3.9 3 98 F2,T2 DURA1212F 12V 12 __-- 5.94 3.86 386 FI,T1 - DURA1214F2 12V 14 5.94 ---3.86 3.98 F2,T2 -- - 8.91 _---," DURAI2 18F2 12V 18 7.13 --- 3.03 6.57 F2,T2 DURA12 18NB 12V 18 7.13 i 3.03 6.57 NB,1 - 12.43 DURA12 26NB 12V 26 6.5 6.93 4 92 NB,1 20.7 DURA12-35C 12V 35 7.72 5.16 6.5 C - 27.3 DURA12 44C/FR 12V 46 7.8 6.54 6.85 C - 38 DURA12 55C/FR 12V 55 9.02 5.43 8.35 - - 42 1 DURA12 80C/FR 12V 80 10.24 6 65 8 46 C .. _.. __ DU8Al2 100CIFR 12V 100 12.09 6 65 8 46 C 74 6 DURA12-140C/FR 12V 140 13.43 6.81 113 C 108 DURA4-4.5F2 4V 4.5 1.85 1.85 3.98 F2,T2 1.4 _-- __.DURA6-13F.-_-.. 6V 1.3 3.82 0.94 2.28 FI,T1 0.715 -__-_- DURA6-2ST 6V 2 1.69 1.45 2.99 ST - 0.75 DURA6 2,9F 6V 2.9 2.6 1.46 3.82 Fl,T1 1.26 DURA633F 6V 3.3 5.28 1.34 2.64 F1,Ti 1.65 RAYA6-4F 6V 4 _.... 2.76 .....1.85 _. . 4.13 F1,T1 - ...DURA6-5SP 6V 5 2.6 26 4.53 _--SP - 2.09 DURA65F 6V 5 _.._ 2.76 1.85 4.21 F1,T1 - - __-.. D'JRA672F 6V 72 594 1.34 - 3.68 Fl,T1 243 I DURA682F 6V - 82 3.9 2.24 4.53 F1,T1, 3.8 DURA6-loF 6V 10 5.94 1.97 3.98 F1,T1 - 4.851 DURA6-12F __-6V 12 5.94 1.97 3.98 F1,T1 DURA6-12F2 6V _....... 12 5.94 _..1.97 3 98 F2,T2 4.602.. .. RAYA6 14T2 6V 14 4.25 2.8 5 51 H - 6.24 DURA6-14A 6V .._ 14 425 2.8 551 F1 OF2(+),T1 OT2(+),FP 6.16 DURA6 42F2 6V 42 6.25 337 6.37 F2,T2 - 16.64 DURA6 42NB 6V 42 6.34 3.43 6.42 NB,1 - 16.62 DURA6-200C 6V 200 12.05 6.65 8.63 C DURA8-3.2F 8V 3.2 5.28 1.44 248 F1,T1 - 1.65 Visit batteriesplus.com for warranty information 02017 DURACELL.Bethel,Cr 06801.Duracell Is a regstered trademark of Mt acelt U.S.OGeratiens,Inc..used under leense.All r-ghts reserved .,,,,, t S �.