Report (2) RECEIVED AUG v 2023 FP5-7 3_ v©012.4 CITY OF TIGARD JILDING DIVISION ♦ • WTAuI_ _hl.1 FIRE PROTECTION , INC. 9095 S.W. Burnham Tigard, OR 97223 YETI WASH SQ 9355 SW WASHINGTON SQUARE RD, SUITE T19 TIGARD, OR 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL tij1O Worldwide Fire Protection Contacts www.tyco-fire.com Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE .g Description The TYCO Series TY-FRB Sprinklers " .w described herein must be installed and maintained in compliance with this doc- ,, t The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable i *$ .. ,, Upright (TY313) and Pendent(TY323) standards of the National Fire Protec Sprinklers described in this data sheet tion Association,in addition to the stan- "t - ANA are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction. Failure to do so may impair i ) sprinklers designed for use in light or the performance of these devices. .- A. ordinary hazard,commercial occupan- cies such as banks, hotels,and shop- The owner is responsible for maintain- ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: • A two-piece Style 15 Recessed Sprinkler Escutcheon with recessed adjust- ment merit up to 5/8 inch (15,9 mm)from Identification ,, ►' ;. the flush pendent position. Number (SIN) - • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT i merit up to 1/2 inch (12,7 mm) from TY323 Pendent 5.6K, 1/2"NPT "--- the flush pendent position. The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series 175°F(79°C) Approvals 200°F(93°C) TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(141°C) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes - in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics • 175 psi (12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper "The maximum working pressure of 250 psi Sealing Assembly Stainless ' IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psiv2(80,6 LPM/bar112) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 - 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 47711AGZ(tiL 5 7/16" I \ \ (11,1 mm) 4 NOMINAL 2" } i� MAKE-IN (50,8 mm) 2 \NINN 1 / 1 3 (50,8mm) + (34,9 mm) / WRENCH FLATS ' f 1/2" NPT** DEFLECTOR* — 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB, 5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright (TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. ^ glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air WRENCH bub- Criteria ble should be present. The diameter of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch (1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) �� Sprinklers are intended for fire protec- temperature ratings. i tion systems designed in accordance with the standard installation rules rec- A leak-tight 1/2 inch NPT sprinkler joint ognized by the applicable Listing or should be obtained by applying a min- 411. I Approval agency(such as, UL Listing imum to maximum torque of 7 to 14 is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels �r1 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler. IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER WRENCHING AREA eon Plate by under-or over-tightening FIGURE 3 the sprinkler. Re-adjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4" DIA. - Sprinkler Wrench to the wrench flats. FACE OF (57,2 mm) — Torque sprinklers 7 to 14 ft.-Ibs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers 1 , , ; FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16" -- Sprinklers must be installed in accor- (9,5±7,9 mm) _ �� iv dance with the following instructions. } Step A.After installing the Style 15 or MOUNTING ' • 1/8" J Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE - 9 P 3/4" (19,1 mm) sprinkler fitting. FIGURE 4 Step B.Tighten the sprinkler into the SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) sprinkler fitting using only the W-Type WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 7 Recessed Sprinkler Wrench (Figure RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque _ 2-7/8" DIA. - , sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF StepC.After ceilinginstallation and fin- SPRINKLER 2-1/4" DIA. _ FITTING (57,2 mm) fishing,slide on the Style 15 or Style 20 Closure over the Series TY-FRB Sprin- 5/16±1/4" kler and push the Closure over the (7,9±6,4 mm) 1/2"(12,7 mm) Mounting Plate until its flange comes in FLUSH contact with the ceiling. ,� I Care and 1/8' i MOUNTING Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, Upright(TY313) and Pendent (TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON - that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hay- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing _ and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. if they cannot be completely cleaned Absence of the outer piece of an by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover by brushing it with a soft bristle brush. ommended to be inspected, tested, a clearance hole, can delay sprinkler and maintained by a qualified Inspec- - operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like, must be replaced. with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX I I SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 g PURE WHITE(RAL9010)°° 155 155°F(68°C) POLYESTER 371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003)POLYESTER 175 175,E(79°C) •Use suf fix"I"for ISO 7-t connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-I "Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order, indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent (specify)Sprinkler, SIN (specify), K=5.6, Quick Response, (specify)tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N (specify*) Specify: Style 20 Recessed Escutch- eon with(specify*)finish, P/N(specify*) 'Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright®2014 Tyco Fire Products,LP. All rights reserved. t"Co TEFLON is trademark of The DuPont Corporation. Fire Pro(ee Uan Products Cho Worldwide www.tyco-fire.com Contacts Series ELO-231B - 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General for any given corrosive environment. The effects of ambient temperature, Description concentration of chemicals, and gas/ p chemical velocity, should be consid- TYCO Series ELO-231B 11.2K Standard ered,as a minimum,along with the cor- =— Response,Standard Coverage Upright rosive nature of the chemical to which and Pendent Sprinklers (Ref. Figure 1) the sprinklers will be exposed are automatic sprinklers of the frangible An upright intermediate level version bulb type.They are standard response, of the Series ELO-231B Sprinklers for spray sprinklers that produce a hemi- in-rack applications can be obtained by spherical water distribution pattern utilizing the Series ELO-231B Upright below the deflector. Sprinkler with the WSG-2 Guard & The 11.2 K-factor,ELO-231B Sprinklers Shield, and a pendent intermediate were subjected to full-scale,high-piled level version of the Series ELO-231B storage fire tests to qualify their use Sprinklers can be obtained by utilizing in lieu of 5.6 or 8.0 K-factor standard the Series ELO-231B Pendent Sprinkler spray sprinklers for the protection of with the WS-2 Shield. If there is a pos- high-piled storage. sibility of the pendent intermediate level version being exposed to mechanical Higher flow rates can be achieved at damage,a G-2 Guard can be added. much lower pressures with the 11.2 K-factor,ELO-231B Sprinklers,making NOTICE their use highly advantageous in high density applications, such as the pro- The 11.2 K-factor, Series ELO-2318 tection of high-piled storage. Upright and Pendent Sprinklers 'M described herein must be installed Wax or lead coatings can be used and maintained in compliance with this ai to extend the life of the copper alloy document,as well as with the applica- components used in Series ELO-231B ble standards of the National Fire Pro- Sprinklers beyond that which would tection Association(NFPA), in addition otherwise be obtained when exposed to the standards of any other authori- to corrosive atmospheres. Although ties having jurisdiction.Failure to do so wax, lead,and polyester coated sprin- may impair the performance of these klers have passed the standard corro- devices. sion tests of the applicable approval agencies, the testing is not repre- The owner is responsible for main-sentative of all possible corrosive taming their fire protection system Sprinkler atmospheres. Consequently, it is rec- and devices in proper operating con- Identification ommended that the end user be con- sulted with respect to the suitability tor or product manufacturer with any Numbers (SINS) of these corrosion resistant coatings questions. Installation of Series ELO-2318 Pendent Refer to Table A for sprinkler identifica- IMPORTANT Sprinklers in recessed escutcheons will tion numbers. Refer to Technical Data Sheet void all sprinkler warranties, as well as TFP2300 for warnings pertaining to possibly void the sprinkler's Approvals regulatory and health information. and/or Listings. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 AUGUST 2018 TFP342 TFP342 Page 2 of 6 1/2"(12,7 mm) Components: NOMINAL MAKE-IN 1 - Frame • 3/4" OP 2 - Seal I 3 - NPT 1 Assembly } 2-13/16" 2 4 Bulb (71,4 mm) WRENCH THREAD 5 m TYP / FLATS RELIEF 3 7.11,1 Screw 6 Deflector* 4 1/2 3/4" �All ■ � 5_ Ill *Temperature NPT NPT • �_ rating is ---I��-- indicated on L 7/16"(11,1 mm) L 1/2"(12,7 mm) 6 deflector. NOMINAL MAKE-IN NOMINAL MAKE-IN UPRIGHT UPRIGHT PENDENT CROSS TY5851 TY5151 TY5251 SECTION FIGURE 1 SERIES ELO-231B 11.2K UPRIGHT 3/4 INCH NPT(TY5151), UPRIGHT 1/2 INCH NPT(TY5851),AND PENDENT 3/4 INCH NPT(TY5251)SPRINKLERS, STANDARD RESPONSE Technical Item Description Data TY5151 -Upright 3/4 in. NPT TY5251 -Pendent 3/4 in.NPT Sprinkler Identification Number(SIN) TY5851 -Upright 1/2 in.NPT Approvals UL and C-UL ListedTY5151 is a re-designation for Central SIN C5151. FM Approved TY5251 is a re-designation for Central,Gem,and NYC Approved Star SINs C5251,G1871,and S2531,respectively. TY5851 is a re-designation for Central SIN C5851. Refer to Table C for specific details on K-factor,(gpm/psi)(Ipm/bar) 11.2 GPM/psi' (161,4 LPM/bars=) laboratory and approvals, including corrosion-resistant status.The approv- 155°F(68°C)1 als apply to the service conditions indi- Temperature Rating°F(°C)1 200°F(93°C) cated in the Design Criteria section.) 286°F(141 °C) Finishes Thread Size 3/4 in. NPT or 1/2 in.NPT Refer to Table C Physical Characteristics Sprinkler Orientation Upright/Pendent Frame Bronze Cap Bronze Maximum Working Pressure,psi(bar) 175 psi(12,1 bar) Sealing Assembly..Beryllium Nickel w/TEFLON - Bulb(5 mm dia.) Glass Note: Compression Screw Bronze 1. Refer to Table C for laboratory listings and approvals. Deflector Bronze TABLEA Additional Technical Data SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS Refer to Table A for additional techni- TECHNICAL DATA - cal data. Design and Group A plastics)with a minimum Operation residual(flowing)pressure of 7 psi(0,5 Criteria bar)for wet or dry pipe systems. Refer The glass bulb contains a fluid that to Table B for additional information. expands when exposed to heat.When UL and C-UL FM Approval Requirements the rated temperature is reached, the Listing Requirements The 11.2 K-factor, Model ELO-23113 fluid expands sufficiently to shatter the TYCO Series ELO-231 B 11.2K Standard Sprinklers are to be installed in actor- - glass bulb, allowing the sprinkler to Response,Standard Coverage Upright dance with the applicable control mode activate and water to flow. and Pendent Sprinklers are to be density/area guidelines provided by FM installed in accordance with NFPA 13 Global. standard sprinkler position and area/ Note: FM Approval guidelines may density flow calculation requirements differ from UL and C-UL Listing criteria. for light,ordinary,or extra hazard occu- pancies, as well as high-piled storage occupancies (solid-piled, palletized, rack storage,bin box,and shelf storage including but not limited to Class I-IV TFP342 Page 3 of 6 Storage Type NFPA FM Global Sprinkler Type Standard Coverage Storage Response Type SR SR System Type Wet,Dry Wet,Dry 155°F(68°C)1 155°F(68°C)1 Temperature Rating°F(°C)1 200o F(93°C) 200°F(93°C) 286 F(141 °C) 286°F(141 °C) Open Frame(that is,no solid shelves)Single,Double, Multiple- Row,or Portable Racj Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9 Plastics Solid Pile or Palletized Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9 Plastics Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0,8-9,and 8-24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3 Rolled Paper Storage(Refer to the standard.) Refer to NFPA 13 Refer to FM 8-21 Flammable Liquid Storage(Refer to the standard.) Refer to NFPA 30 Refer to FM 7-29 Aerosol Storage(Refer to the standard.) Refer to NFPA 30B Refer to FM 7-31 Automotive Components in Portable Racks(Control mode only, Refer to NFPA 13 N/A refer to the standard.) Note: 1. Refer to Table C for laboratory listings and approvals. N/A-Not Applicable TABLE B SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW SPRINKLER FINISH SPRINKLER TEMPERATURE BULB TYPE RATING LIQUID NATURAL CHROME LEAD WAX WAX-OVER-LEAD BRASS PLATED COATED COATED COATED 155°F(68°C) Red 3 UPRIGHT 200°F(93°C) Green 1,2,3,4 (TY5151 &TY5851) 286°F(141°C) Blue 3 3a 155°F(68°C) Red 3 PENDENT 200°F(93°C) Green 1,2,3,4 (TY5251) 286°F(141°C) Blue 3 3a Notes: 1. Listed by Underwriters Laboratories,Inc.(UL) 2. Listed by Underwriters Laboratories,Inc.for use In Canada(C-UL) 3. Approved by FM Global(FM Approvals) 4. Approved by the City of New York(NYC)under MEA 291-04-E a. Listed/Approved for a maximum ceiling temperature of 150°F(66°C). TABLE C SERIES ELO-2318 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE LABORATORY LISTINGS AND APPROVALS TFP342 Page 4 of 6 'FITTING SIDE" that an 8 in.or 10 in.adjustable wrench Care and TOWARDS SPRINKLER is to be used for wax-coated sprinklers. FITTING With reference to Figure 1,the W-Type Maintenance 3 Swrench, as ppWrlicah oe, itse bejaptable plied wrench,as applicable, is to be applied TYCO Series ELO-231B 11.2K Standard to the wrench flats. ,=, „ii\- :--0\ Response,Standard Coverage Upright When installing wax-coated sprinklers and Pendent Sprinklers must be main- with the adjustable wrench, additional tained and serviced in accordance with WRENCH care needs to be exercised to prevent this section. RECESS damage to the wax coating on the (END"A") sprinkler wrench flats or frame arms Before closing a fire protection system and, consequently, exposure of bare control valve for maintenance work on FIGURE metal to the corrosive environment. the fire protection system that it con- W-TYPE3 The jaws of the wrench should be trols, permission to shut down the SPRINKLER WRENCH opened sufficiently wide to pass over affected fire protection system must the wrench flats without damaging the an obtainedllen fromn whothh propermy bea affected Installation wax coating.Before wrench-tightening all personnel may affected the sprinkler,the jaws of the wrench are bythis action must be notified. TYCO Series ELO-2318 11.2K Stan- to be adjusted to just contact the sprin- Sprinklers that are found to be leaking dard Response, Standard d Coverage kler wrench flats. After wrench-tight- or exhibiting visible signs of corrosion Upright and Pendent Srkl v must ening the sprinkler, loosen the wrench must be replaced. be installed in accordance with this jaws before removing the wrench. Automatic sprinklers must never be section. After installation, the sprinkler painted, plated, coated or other- wrenchA 3/4 in. NPT sprinkler joint flats and frame arms must wise altered after leaving the factory. A leak-tight be obtained. applying a mint be inspected and the wax coating Modified sprinklers must be replaced. should be m bytorape of 10 to 20 retouched (repaired) whenever the Sprinklers that have been exposed to imu -(13,4- at mu N•mu). A l 10 to 0t coating has been damaged and bare corrosive products of combustion, but 11/2b- in. 26,8N e -t be metal is exposed.The wax coating on have not operated,should be replaced obtained NPTby sprinkler joint shouldbe the wrench flats can be retouched by if they cannot be completely cleaned x torqueapplying 7 ato ft minimum-to-- gently applying a heated 1/8 in. diam- by wiping the sprinkler with a cloth or maximum19,0 N to ue ofHighe levels l - tto (9,55 eter steel rod to the areas of wax that by brushing it with a soft bristle brush. tocan distort the sprinkler inlet with con- have been damaged, to smooth it Care must be exercised to avoid sequent leakage or impairment of the back over areas where bare metal is damage to the sprinklers before, sprinkler. exposed. p during, and after installation. Sprin- Notes;Notes: Do not install any bulb type Only retouching of the wax klers damaged by dropping, striking, Notes: if the is cracked orb there coating applied to the wrench flats wrench twist/slippage,or the like,must sprinkler a lossif liquid bulb from the bulb. With and frame arms is permitted, and be replaced. Also, replace any sprin- is os of held from the by, a small the retouching is to be performed kler that has a cracked bulb or that has air bubblep should be present.a The only at the time of the initial sprinkler lost liquid from its bulb. For additional diameter of the air bubble is approxi installation. information,refer to Installation section. mately 1/16 in. (1,6 mm) for the 155°F The steel rod should be heated only Frequent visual inspections are rec- (68°C) to 3/32 in. (2,4 mm) for the to the point at which it can begin to ommended to be initially performed 286°F(141°C)temperature ratings. melt the wax,and appropriate precau- for corrosion resistant sprinklers, after to maketions need to be taken, when handling the installation has been completed,to Do not attempt up for insuf-the escutcheon the heated rod, in order to prevent the verify the long term potential integrity ficient adjustment plate by under- or over-tightening the installer from being burned. of the sprinkler coatings. Thereafter, sprinkler. Re-adjust the position of the if attempts to retouch the wax coating annual inspections per NFPA 25 should sprinkler fitting to suit. with complete coverage are unsuc- suffice; however, insteadinspec ting cting a cessful,additional wax can be ordered from the floor level, random sampling The Series ELO-231B Upright and of close-up visual inspections should Pendent Sprinklers must be installed in the form of a wax stick (the end be made,so as to better determine the . in accordance with the following of which is color-coded). Only the exact sprinkler condition and the long instructions. correct color-coded wax is to be term integrity of the corrosion resistant used, and retouching of wrench flats coating, as it may be affected by the Note: Pendent sprinklers are to be and frame arms is only permitted at installed in the pendent position; the time of initial sprinkler installation. corrosive conditions present. upright sprinklers are to be installed in With the steel rod heated as previ- The owner is responsible for the the upright position. ously described, touch the rod to the inspection,testing,and maintenance of Step 1. With pipe thread sealant area requiring additional wax with the their fire protection system and devices applied to the pipe threads, hand- rod angled downward, and then touch in compliance with this document, as tighten the sprinkler into the sprinkler the wax stick to the rod approximately well as with the applicable standards tighte. 1/2 in. away from the area requiring of the National Fire Protection Associ- retouching. The wax will melt and run ation, such as NFPA 25, in addition to Step 2. Tighten the sprinkler into the down onto the sprinkler. the standards of any other authorities sprinkler fitting using only the W-Type 3 having jurisdiction.Contact the install- Sprinkler Wrench(Ref.Figure 2),except ing contractor or product manufacturer with any questions. TFP342 Page 5 of 6 P/N 50 - XXX - X - XXX 1 SIN SPRINKLER TEMPERATURE FINISH RATING 501 11.2K UPRIGHT(1/2 in.NPT) TY5851 1 NATURAL 155 155°F(68°C) BRASS 510 11.2K UPRIGHT(3/4 in.NPT) TY5151 6 WAX 200 200°F(93°C) COATED 512 11.2K PENDENT(3/4 in.NPT) TY5251 7 LEAD 286 286°F(141°C) COATED 8 WAX-OVER-LEAD COATED 9 CHROME PLATED TABLE D SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE PART NUMBER SELECTION It is recommended that automatic Wax Sticks sprinkler systems be inspected,tested, Ordering (for retouching wrench-damaged wax and maintained by a qualified Inspec- Procedure coating) tion Service in accordance with local Specify: (specify Color) color-coded i requirements and/or national codes. Sprinkler Assemblies with Wax Stick for retouching (specify tern- NPT Thread Connection perature rating) temperature rated Limited Specify: Series ELO-231B 11.2K Stan- Series ELO-231B Sprinklers, P/N dard Response (specify Pendent (specify): Warranty or Upright) Sprinkler, SIN (specify), Red for 155°F(68°C) 56-065-1-155 (specify temperature rating), with Blue for 200°F(93°C) For warranty terms and conditions,visit (specify)finish, P/N(specify from Table and 286°F(141°C) 56-065-1-286 www.tyco-fire.com. D) Notes: Each wax stick is suitable for Sprinkler Wrench retouching up to twenty-five sprinklers. Specify: W-Type 3 Sprinkler Wrench, The wax used for 286°F(141°C)sprin- P/N 56-895-1-001 klers is the same as for 200°F (93°C) sprinklers, and, therefore, the 286°F (141°C)sprinkler is limited to the same maximum ceiling temperature as the 200°F (93°C)sprinkler, such as 150°F (66°C). Fire Sprinkler Pipe Schedule 10 and Schedule 40 Submittal Data Sheet FM Approved and Fully Listed Sprinkler Pipe SCHEDULE 10 SPECIFICATIONS Wheatland's Schedule 10 and Schedule 40 steel fire sprinkler pipe is FM Approved and UL, NOMINAL NOMINAL C-UL and FM Listed. NPS NOM OD NOM ID WALL WEIGHT UL PIECES In. -mm in. mm in. mm lbs./ft. kg/m CRR* Lift Approvals and Specifications Both products meet or exceed 13/4 1.660 42,2 1.442 36.6 .109 2.77 1.81 2.69 7.3 61 the following standards: • 1% 1.900 48.3 1.682 42.7 .109 2.77 2.09 3.11 5.8 61 • ASTM A135,Type E,Grade A(Schedule 10) 2 2.375 60.3 2.157 54.8 .109 2.77 2.64 3.93 4.7 37 • ASTM A795,Type E,Grade A(Schedule 40) 2% 2.875 73.0 2.635 66.9 .120 3.05 3.53 5.26 3.5 30 • NFPA 13 3 3.500 88.9 3.260 82.8 .120 305 4.34 6.46 2.6 19 Manufacturing Protocols 4 4.500 114.3 4.260 108.2 .120 3.05 5.62 8.37 1.6 19 Schedule 10 and Schedule 40 are subjected to the toughest possible testing protocols to 5 5.563 141.3 5.295 134.5 .134 3.40 7.78 11.58 1.5 13 ensure the highest quality and long-lasting performance. 6 6.625 168.3 6.357 161.5 .134 3.40 9.30 13.85 1.0 10 8 8.625 219.1 8.249 209.5 .188 4.78 16.96 25.26 2.1 7 Finishes and Coatings All Wheatland black steel fire sprinkler pipe •Calculated using Standard UL CRR formula,UL Fire Protection Directory,Category VIZY. •The CRR Is a ratio value used to measure the ability of a pipe to withstand corrosion. up to 6" receives a proprietary mill coating to Threaded Schedule 40 steel pipe is used as the benchmark(value 011.0). ensure a clean,corrosion-resistant surface that outperforms and outlasts standard lacquer coatings.This coating allows the pipe to be SCHEDULE 40 SPECIFICATIONS easily painted,without special preparation. Schedule 10 and Schedule 40 can be ordered in NOMINAL NOMINAL black, or with hot-dip galvanizing,to meet NPS NOM OD NOM ID WALL WEIGHT UL PIECES FM/UL requirements for dry systems that meet in. mm in. mm In. mm lbs./ft. kg/m CRR' Lift the zinc coating specifications of ASTM A795 or A53.All Wheatland galvanized material is 1 1.315 33.4 1.049 26.6 .133 3,38 1.68 2.50 1.00 70 also UL Listed. 1% 1.660 42.2 1.380 35.1 .140 3.56 2.27 3.39 1.00 51 Product Marking 11/2 1.900 48.3 1.610 40.9 .145 3.68 2.72 4.05 1.00 44 Each length of Wheatland fire sprinkler 2 2.375 60.3 2.067 52.5 .154 3.91 3.66 5.45 1.00 30 pipe is continuously stenciled to show the manufacturer,type of pipe,grade,size •Calculated using Standard UL CRR formula,UL Fire Protection Directory,Category VIZY. *The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. and length. Barcoding is acceptable as a Threaded Schedule 40 steel pipe is used as the benchmark(value of t.0). supplementary identification method. ® C ® APPROVED SUBMITTAL INFORMATION PROJECT: CONTRACTOR: DATE: ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE: LOCATIONS: COMMENTS: ❑ BLACK ❑ HOT-DIP GALVANIZED Wheatland Tube 700 South Dock Street Sharon, PA 16146 Wheatland Tube P800.2.57.8182 I F724.346.72.60 I infcy@wheatland.com I wheatland.com .MC5 FEEL GROUP Ductile Iron Threaded Fttns ... . ...._ , . ....... ,. . .....„. „A, ,........ .. .......„,„ .., .„. ry' ..... . „. ..,.... .... H 6 4 s //(/f/.,)41.. { f t e SMviITH COOPE .1 ° INTERNATIONAL Ductile Iron Threaded Fittings Specifications • 4' branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP C14) US • Ductile iron castings conform to ASTM A536 LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 411: APPROVED • Fittings are 100% air tested • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings -20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 if ' ' Ductile Iron ittings - ass 10 1 c ® us APPROVED . Fig. 35E 3- 90°Elbow LISTED A Size Part Number A Packing Weight in in Inner Master lb _i_ + 1/2 35E 3004 1.13 100 200 0.2 3/4 35E 3006 1.31 70 140 0.3 A 1 35E 3010 1 5C 40 80 0.5 _ 1-1/4 35E 3012 1.75 25 50 0.8 _ 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2 25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow B Size Part Number A B Packing Weight in in in Inner Master lb 1111 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 A 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 1111111 j v 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1 45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3C14004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x I 35RE3014010 1,65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 3bRE3020004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 '>1 2 x 1 350E3020010 1.73 202 16 32 1.2 2 x 1-1/4 35E1E3020012 1.90 2.10 12 24 1.3 .." 2 x 1 1/2 356E3020014 2,02 2.16 10 20 1.5 1}' 2-1/2x1-1/2 35RE3024014 2.16 2.51 6 12 2.2 }t1 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2,5 - Fig. 35F 3-45°Elbow Size A Packing Weight Part Number / .8n Inner Master lb 2 35F 3004 0. 8 50 300 0,2 �/ 3/4 356 3006 0.98 80 160 0.3 s111 1 35F 3010 1.13 40 80 0.5 1-1/4 35F3012 1.29 25 50 0.7 TT 1-1/2 35F3014 1.44 20 40 1.0 !�i IA 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 2,7 Fig. 35T 3- Tee Size Part Number A Packing Weight in in Inner Master lb itai !!�L TA 1/2 35T 3004 1.13 80 160 ast 0.3 3/4 35T 300635T 301 1,311.50 3025 6050 0.5 II I-1/4 35T 301P 1.75 10 ast 20 1.1 A A 1-1/2 35T3014 1.94 10 20 1,5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 111 SNII"I'II-COOPER IN"I-ERu\I'ION\l.' • "MIA, FREE I-800-766-0076 • FAX (323)890-4456 • wwwsminc woo per.corn J I ucti e ron rttings- ass I I 1 c0us - APPROVED Fig. 35RT3-Reducing Tee LISTED • Size Part Number A B C Packing Weight in in n in Inner Master lb j 1 k,,-, , �C 3/4 x 1/2 35813006004 1.20 1.20 1.22 60 120 0.4 1 x 1!2 35913010004 1.26 1.26 1.36 30 60 0.6 ? � 1 x 1/2 x 1 35RT301 00040 1 0 '-50 1,36 1.50 30 60 0 6 1 x 3/4 358T3010006 1.38 1.38 1.45 25 50 0.6 � - 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1 45 35 70 0.6 B 1 x 3/4 x 1 35R13010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35RT3012004 1.34 1-34 1 53 20 40 0.8 1.1/4'x1/2x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35R13012006 1 45 1.45 1,62 15 30 0.9 1-1/4 x 3/4 x1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 35RT3012010 1 58 1.58 1.67 15 30 1.0 1.1/4 x 1 x1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4x 1 x3/4 35RT3012010006 1.45 1,38 1-63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 358T3012010012 1.75 1 69 175 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.' 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 35RT3014006 1.52 1.52 1.75 16 32 1 1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35RT3014010004 1 44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35013014010010 1.65 1.50 1.80 16 32 1-0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1 94 12 24 1.3 1-1/2x 1-1/4 35RT3014012 1.82 1 82 1.88 12 24 1.4 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 ` 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 1-1/2 x 1-t/4 x 1 351- 23014012010 1-65 1.58 1.80 16 32 1 1 1-1/2 x 1-114 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/7 35RT3014012014 1.94 1.88 1.94 14 28 1.4 2x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 2 x 3/1 35RT3020006 1.60 1 60 1.97 10 20 1.6 Irk 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 225 7.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35013020012020 225 2.10 2.25 8 16 2.0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x I-1/2 x 1/2 35RT3020014004 1 49 1.41 1.08 10 20 1.3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 - 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1,8 , Fig. 35RT3-Bull Head Tee _ , 1 Size A B C Packing Weight Part Number JONI, � in in in in Inner Master lb � 3l4 x 1 35013006010 1 45 1.45 1.37 30 60 0.6 1 x 1-1/4 35BT3010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35BT3010014 1.80 1.80 1_65 15 30 1.0 t-A B 1-1/4 x 1 x 1-1/2 35BT3012010014 1.88 1.80 1.82 15 30 1.2 1-1/4 x 1-1/2 35BT3012014 1.88 1.88 1-82 15 30 1.3 1-1/4 x 2 358T3012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35BT3014012020 2.16 2 10 2.07 10 20 1.8 1-1/2 x 2 35BT3014020 2.16 2.16 2.02 8 16 1.8 S1II"111-COOP1 R INTER V'A"I'IOSAI " • '11)1.I. FREE 1-800-766-0076 • 1AX(323) 890-1456 • wv,ll.smithcooper.com 112 II ucti a ron fittings - ass I I I / ' c ® us 41> APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED I_VA Size Part Number A Packing Weight in in Inner Master lb _ j - 1/2 35CP3004 38 200 400 C.1 3/4 35CP3006 1.63 100 200 0.2rm 1 35003010 5 60 20 0 4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 219 25 5C 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling 11111 Size /H\ A Packing Weight - in Part Number n Ib /if P x I/2 359C3010004 1 69 80 60 0.3 1 x 314 35RC3010006 1.69 60 120 0.4 , 1-1/4 x 3/4 35RC3012006 2-06 40 Inner Master 80 0.6 i 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master lb 1 x 1/2 35HB30100041 1.06 180 360 0.2 x 3f4 35HB3010006 1.06 180 360 0.1 A 1/4 x 1 35HB3012010 19 90 180 0.2 1-1/2 x 1 35H83014010 1.2575 150 0.4 1-l/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 2x1 35H83020010 1.38 40 80 0.6 2 x 1-1/4 35H83020012 1-38 40 80 0-6 ax 2x 1-1/2 35H83020014 1.38 40 80 0.6 T Fig. 35SP3 -Square Head Plug ilk , Size Part Number A Packing Weight , ..... in in lb 1/2 35S03004 0-94 600 1200 0.07 A 3/4 358P3006 1.121 350 700 0.1 . 35SP3010 25 200 Inner Master 400 0,1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 1 35SP3014 1.44 80 160 0.4 2 1 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size A Packing Weight Pm in Part Number in Inner Master lb - mi 1 35U 3010 2.19 20 40 1.0 ���1" 11111N1 1-114 35U 3012 2.50 15 30 1.2 1-1/2 35U 3014 2.62 10 20 1.7 2 35U 3020 3.12 6 12 2.4 lingo 113 S\II'I'II-COOPER IV'I'ERN. V1'I0\\t;x • 'LOLL FREF. 1-800-766-0076 • FAX(323)890-4456 • wsctic.smithcooper.com l _ Ductile Iron Fittings -Class 300 UL/FM m(,! f r?LI- j CQOUS APPROVED Fig. 35X 3-Cross LISTED • t A-��E A ' Size A Packing Weight -- instilin Part Number in Inner Master lb woo I i �A 1 35X 3010 1 50 20 40 0.9 h =I 1 1 1-1/4 35X 3012 1 75 35X 3014 94 12 24 8 16 1.4 1 '..8 inram A 2 2 35X 3020 2.25 6 12 2.8 B Fig. 35RX3-Reducing Cross BSize Part Number A B Packing Weight �Ilit A in in in Inner Master lb 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.2 __1_-� 1-1/2 x 1 35RX3014010, 1.80 1.65 12 24 1.4 I - Ill A 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 Fig. 35C 3- Cap Size Part Number A Packing Weight , deal,_ in in Inner Master lb A 1/2 35C 3004 0.87 300 600 0 1 3/4 35C 3006 0 97 200 400 0.1 -4, _,y_ I ( _ 1 35C 3010 1 16 110 220 0.2 1-1/4 35C3012 1.28 -ft4 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 5 Al Fig. 35BC3-Beam Clamp Size A Packing Weight AT— in Pail Number in Inner Master lb 0 3 A . g 318 35BC3003 0.75 100 200 . N® �1 1/2 35BC3004 0.75 80 160 0.5 SMITH-COOPER INTERNAT1ONALA • TOLL,FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114 • ]; •, • • - •• •;I , , LPCB Frp nck6 Ou i t®T C) vas) 491a27 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating l ,3/4, and 1715,20 and 25mm outlets for directly connecting sprinklers, drop nipples,sprigs,gauges,drains and other outlet products.Available for 1V4 through 76.1 mm/32 to 76.1mm piping systems,Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard, lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Gasket: • Grade"E" EPDM-Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade "E" Type A Gasket System. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America, Latin America,Asia Pacific) • Red enamel (Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com :MM_sa•J:r-• IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.52 FireLcck® Outlet-T STYLE 922 DIMENSIONS Nominal Size Hole Approx. inches/mm Diameter Dimensions inches/millimeters Weight Each n Branch- 'x.. : +D DB/tY.S ._-: .,” u"". h . .. FPT± 0 00/-0.0 T• V W 2 Ibs/kgi Y �Z - 1 Vs 1.30 32 x 15 130.26 33.0 465 27.9 98.3 6506 1.0 045 PM V ��� 0_1_ � \\�// 3/a -� 13/16 1.28 1.83 1.10 3.87 2.56 1.1 . . 1 vvoJio"I 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 ;air ��r N/ 4�i1 1 1 3/16 1.52 2.185 1,10 3.87 2.56 1.2 1� 2_5 30.2 38.6 55.4 27.9 98.3 65.0 054 ��_1 ih -_--_..--�/____ 1 3/16 1.42 1.95 1.22 4.08 2.56 1,2 40 x 15 I 30.2 36.1 49.5 31.0 103.6 65.0 0.54 3 1, 13/16 1.40 1.95 1.22 4,08 2.56 1.2 20 ' 30.2 35.6 495 31.0 103.6 65.0 0.54 1 13/16 1.64 2.30 1.22 4.08 2.56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 0.59 2 1/2 13/16 1.66 2.19 1.46 4.60 2.56 1.3 50 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 34 13/16 1,64 2.19 146 4.60 2.56 1.4 _ 2.0___ 30.2 41.7 55.6 37.1 '16.8 65.0 0.64 1 13/16 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 478 64.5 37.1 116.8 65.0 0.68 21/2 '/ I 1 3/16 1.91 2.44 1,71 5.40 2.56 1.6 65 x 15 1 30.2 48.5 62.0 434 1372 65.0 0.73 3/4 13/16 1.89 2.44 1.71 5,40 2.56 1.6 20 ' 30.2 48.0 62.0 434 1372 65.0 0.73 1 13/16 2.13 2.79 1.71 5.40 2.56 1.6 25 , 30.2 54.1 70.9 43.4 137.2 65.0 0.73 76.1 mm X '1/2 1 3/16 1.91 2.44 1.71 5.50 2.56 1.6 15 30.2 48.5 62.0 43.4 139.7 65,0 0.73 3 • 13/16 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 1397 65.0 0.73 -_ 1 - 13/16 213 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. *Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com Li- i d.r' IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.52 FireLock® Outlet-T STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Size x Outlet Size 213,Section 16)(C=120),FT 1Ya X 1 8.5 32 25 2.6 11/2 1 , 8.5 40 X 25 2.6 2 X 1 85 50 25 2.6 2 1/2 X 1 8.5 65 25 2.6 76.1 mm X 1 8,5 25 2.6 *Hazen-Williams coefficient of friction is 120 www.victaulic.com .rrtmku rl.n' 0.52 �k STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.52 3355 REV UPDATED 12/2009 \ .f71-_mk• f_ Pipe Hangers i Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig. B3170NF) al'MUM Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig. B317ONFF) UL US Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig. B317ONFC) usreia Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mmi thru 8" 1200mm) pipe Material: Steel, Pre-Galvanized to G90 specifications • Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. -- % \ ,,, - 7 Features: 'is 2-_ A • (1/2" 1t5mm)thru 2" (50mm)) Flared edges ease installation for all pipe �' `,A types and protect CPVC plastic pipe from abrasion. Captured design `r keeps adjusting nut from separating with hanger. Hanger is easily ", e installed around pipe. ,: A For hanger with non-captured nut order Fig. 200S. • • (21/2" le5mm)thru 8" 12o0mm)) Spring tension on nut holds it securely in L- -� hanger before installation.Adjusting nut is easily removed. ,----- Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (2o0mm)1 in the USA(UL)and Canada (cUL)for steel and CPVC plastic pipe and t, Fig.200-1/2.200-3/4 Fig.200-1 to 200-2 Fig.200-21/z to 200-B Factory Mutual Engineering Approved (FM) (3/4" 12omm)thru 8" Izo0mm0. Conforms to Federal Specifications WW-H-171 E &A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, ,,, Type 10. Maximum Temperature: 650°F (343°CI Finish: Pre-Galvanized. Stainless Steel A. materials will be supplied with (2) hex nuts in place of a knurl nut. 4 •, :` *' ' 1"4' Order By: Figure number and pipe size Designed to meet or exceed requirements of 11 t FM DS 2-0. ": Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) 200-1/2 1/2" (15) 3/8"-16 31/s" (79.4) 25/8" (66.7) 11 (5.0) 200.3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0) 200-1 1" (251 3/8"-16 33/9' (85.7) 25/8" (66.7) 12 (5.5) 200-11/4 11/4" (32) 3/s"-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8°-16 37/8° 198.41 27/8" (73.01 14 16.4) 200-2 2" (501 3/B"-16 41/2" (114.3) 3" (76.3) 15 (6.9) 200-21/2 21/2' (65) 3/8"-16 55/8 (142.9) 41/8' (104.7) 27 (12.3) 200-3 3" (75) 3/8°-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" (901 3/8'-16 73/8' (187.3) 51/4" (133.3) 34 (15.61 200.4 4" (100) 3/0"-16 73/8" 1187.3) 5" (127.0) 35 116.0) 200-5 5" 1125) 1/2'-13 91/s" (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/3" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. ■ B-Line Fire Protection Solutions 21 by EttsN Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCo Fig. 103) ,> B3205L - Threaded Rod (right& left hand threads) TL Ya Specify Length ��a Size Range: 318"-16 thru 3"-4 rod •c ��1� Material: Steel Function: Recommended for use as a hanger support in hanger assemblies. TL�11 Rod is threaded on both ends with right hand threads of the length shown.Also1 i A available with left and right hand threads-specify Fig. B3205L when ordering. Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish tit0 Standard Design Load Thread Size Thread length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205-3/8 x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 X'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) 83205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B3205-7/8 x'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) B3205-11/3 x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) B3205-11/4 x'L' 11/4"-7 5" (127.0) 9500 (42.25) ' 7440 (33.09) 83205-11/2 X'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) B3205-13/4 x112 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) 133205-2x'L' 2"-41/2 8" (203,2) 24600 (109.42) 19625 (87.29) 133205-21/4 x'1' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) B3205-21/2 x'L' 21/2"-4 10" (254,0) 39800 (177.03) 31169 (138.64) B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267,32) 47066 (209.35) ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig. 100) Fig. 99 - All Threaded Rod Cut To Length „ ,,,L,A0 i* Size Range: 3/8"-16 thru 11/2"-6 rod in 120" (3.05m) lengths or cut to length 1 71400 Material: Steel -, .` ,-,. L Maximum Temperature: 750°F (399°C) '` V 0 Finish: Plain.Contact B-Line for alternative finishes and materials. r iii Order By: Part number, rod diameter and finish 1'a Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/e"x 120 99-3/8"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99.1/2"x length 13 1350 (6.00) 53 ,. (24.04) ATR 5/e"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/8"x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Li n Revised 4/28/2014 e Pipe Hangers&Supports 236 by IFIT411 ' 1111 National Fire Equipment Ltd. BEAM CLAMP FIG. 350 Function:Designed for attaching hanger rod to the top flange of a beam or bar joist,where the flange thickness does not exceed 3/4 inch(19.05mm).The open U design permits rod adjustment. D-0- Material:Malleable iron with hardened steel cup point set screw and locknut(Type 304 or 316 Stainless Steel I upon request for 1/4",3/8",and 1/2"only) , Finish:Plain or electro-galvanized i {{ AIM C Approvals:Underwriters'Laboratories Listed in the U.S.(UL),Canada(CUL),for sizes 1/2"to 7/8"malleable iron only.Factory Mutual Approved for rod size 1/2"malleable iron only.Complies with Federal Specifications I+ A-A-1192A(Type 19)and Manufacturers'Standardization Society ANSI/MSS SPSP-58(Type 19)which 3/4 1 supersedes ANSI/MSS SP-69.(Approvals are only valid for beam clamps with locknut). (19.05) Ordering:Specify figure number,rod size,material,and finish. ,M , NOTE:When a torque wrench is unavailable,the setscrew should be tightened .N A so it contacts the I-beam and then an additional 1/4 to 1/2 turn. ---- E CVt.6 B- LIIIIIITTTTTTEEEEEEa AP9R0vE ....1- Nominal 3/8 1/2 Caution should be Thread Size taken not to over Rec. in-lbs. 60 125 tighten the set screw Torque N-m (6.8) (14.1) `1/4 7/8 (22.23) 1 1/2 (38.10) 1 5/8 (41.28) 1/2 (12.70) N/A N/A 250 (1.11) .34 (.15) , 213f8 7/8 (22.23) 11/2 (38.10) 15/8 (41.28) 1/2 (12.70) 4 (100) 400 (1.78) .33 (.15) 1/2 1 (25.40) 11/2 (38.10) 111/16 (42.86) 1/2 (12.70) 8 (200) 500 (2.22) .34 (.15) 5/8 11/16 (26.99) 11/2 (38.10) 17/8 (47.63) 5/8 (15.88) 8 (200) 600 (2.67) .39 (.18) 3/4 1 5/16 (33.34) 1 3/4 (44.45) 2 3/8 (60.33) 5/8 (15.88) 8 (200) 800 (3.56) .63 (.29) 7/8 1 5/16 (33.34) 1 3/4 (44.45) 2 3/8 (60.33) 5/8 (15.88) 8 (200) 1200 (5.34) .60 (.27) •1/4"Not UL or FM approved.Only available in domestic. • A 3/8"Available in type 304 or 316 stainless steel only.For non stainless steel 3/8"rod sizes,see Fig.345 Steel Top Beam Clamp and Fig.353 Malleable Domestic Beam Clamp. • • • • • TOinROMO:(905)761-6355 VANCOOYER:(6W)tl20-llJl EDMO.NTON:(789)4453870 MONCTO]Y:(906)859-7277 Equipment Fire Ton Meee:(%4U)2b1-USUtl Tuft F:+e:(50V}651-2139 'I'dr 11r s (050)-847-1008 1Wl tree:(577)11Q3i73 Equlp1'nent Ltd. OTTAWA:(613)723.6071 BURNABY:(604)-299-4499 CALGARY:(403)2364661 MISSISSAUGA:(WS)5651361 www.nationalfire.com