Report
2 -03 RECEIVED ,UL 2 5 2023 OFFICE COPY CITY OF TIGARL --3UILDING DIVISION VV Ib1AT "T -;,:fita4,4,- FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 WASH SQ B09 EXPANSION 9577 SW WASHINGTON SQUARE RD STE B071B09 TIGARD, OR 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL •t[/co Worldwide Fire Protection Contacts www.tyco-fire.com Products Series TY-FRB, 5,6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers "'` Description described herein must be installed and y maintained in compliance with this doc- The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- Sprinklers described in this data sheet Lion Association,in addition to the stan- t are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair .°Rm+ 1 F 4. sprinklers designed for use in light or the performance of these devices. t. '.' ordinary hazard,commercial occupan- = cies such as banks, hotels,and shop- The owner is responsible for maintain- in their fireprotection system and - ping malls. 9 Y devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. . finished ceiling.This recessed pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed 4 Escutcheon with recessed adjust- Identification x'. ment up to 5/8 inch (15,9 mm)from the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT ' the flush pendent position. "' The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) 175°F(79°C) Intermediate level versions of Series Approvals 200°F(93°C) TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(141°C) Technical Data Sheet TFP357. Sprin- FM,LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler:Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics • 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)° Button Brass/Copper The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the `INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi112(80,6 LPM/bar1r2) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 5 1I \ \ 7/16" I �s= (11,1 mm) opil f 1mFc 4 NOMINAL 2° (I MAKE-IN (50,9 mm) \ -// 1 imminw 2 D• •, g 2„ 1-3/9" L 3 1 (50,8 mm) 1 (34,9 mm) �_. WRENCH 1 FLATS 1 1 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, 7' WRENCH RECESS expands when exposed to heat.When Upright(TY313) and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. ^ glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air WRENCH bub- Criteria ble should be present. The diameter of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch (1,6 mm)for the 135°F(57°C)and Upright(TY313) and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) Sprinklers are intended for fire protec- temperature ratings. tion systems designed in accordance with the standard installation rules rec- A leak-tight 1/2 inch NPT sprinkler joint ognized by the applicable Listing or should be obtained by applying a min- * i Approval agency(such as, UL Listing mum to maximum torque of 7 to 14 is based on the requirements of NFPA ft.-Ibs. (9,5 to 19,0 Nm). Higher levels 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler. IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER WRENCHING AREA eon Plate by under-or over-tightening FIGURE 3 the sprinkler. Re-adjust the position of W-TYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- . dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position.Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8"DIA. sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench(Figure 2).With ref- erence to Figure 1,apply the W-Type 6 2-1/4"DIA. Sprinkler Wrench to the wrench flats. FACE OF - (57,2 mm) Torque sprinklers 7 to 14 ft.-lbs. (9,5 to SPRINKLER 19,0 Nm). FITTING` 5/8"(15,9 mm)1 Recessed Pendent Sprinklers ; Ns FLUSH The Series TY-FRB Recessed Pendent 3/8±5/16' —_1 I Sprinklers must be installed in accor- (9,5±7,9 mm) „2,71 iv dance with the following instructions. } I Step A.After installing the Style 15 or MOUNTING ' • 1/8" Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread --Y — sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE 3/4"(19,1 mm) sprinkler fitting. FIGURE 4 Step B.Tighten the sprinkler into the SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) sprinkler fitting using only the W-Type WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 7 Recessed Sprinkler Wrench (Figure RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/8" DIA. sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4" DIA. ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" 1/2"(12,7 mm) kler and push the Closure over the (7,9±6,4mm)Mounting Plate until its flange comes in + - FLUSH contact with the ceiling. Zzal Care and f I — MOUNTING 1 1/3 Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB, 5.6 K-factor, Upright(TY313) and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. if they cannot be completely cleaned Absence of the outer piece of an by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- escutcheon, which is used to cover by brushing it with a soft bristle brush. ommended to be inspected, tested, a clearance hole, can delay sprinkler andand maintained by a qualified Inspec- - operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like,must be replaced. with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad- cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro- inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion(e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX I I SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57"C) 370 5.6K UPRIGHT(1/2-NPT) TY313 g PURE WHITE(RAL9010)" 155 155`F(68'C) POLYESTER 371 5.6K PENDENT(1/2"NPT) TY323 4 SIGNAL WHITE(RAL9003) 175 175°F(79'C) POLYESTER 'Use suffix"I"fcr ISO 7-1 connection, 9 CHROME PLATED 200 200"F(93"C) for example,77-370-4-1/S-I "Eastern Hemisphere sales only 286 286'F(141"C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability. When placing an order, indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent (specify) Sprinkler, SIN (specify), K=5.6, Quick Response, (specify)tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify: Style 15 Recessed Escutcheon with (specify)finish, P/N (specify*) Specify: Style 20 Recessed Escutch- eon with (specify`)finish, P/N (specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. NCO TEFLON is trademark of The DuPont Corporation Fire Arotettion Products ,. ....,: FireSprinklerPipe Schedule 10 and Schedule 40 -- Submittal Data Sheet FM Approved and Fully Listed Sprinkler Pipe SCHEDULE 10 SPECIFICATIONS Wheatland's Schedule 10 and Schedule 40 steel fire sprinkler pipe is FM Approved and UL, NOMINAL NOMINAL , C-UL and FM Listed. NPS NOM OD NOM ID WALL WEIGHT UL PIECES In. non in. mm in. mm lbs./ft. kg/m CRR' Lift Approvals and Specifications Both products meet or exceed 1% 1.660 42.2 1.442 36.6 .109 2.77 1.81 2.69 73 61 the following standards: 1% 1.900 48.3 1.682 42.7 .109 2.77 2.09 3.11 5.8 61 • ASTM A135,Type E,Grade A(Schedule 10) 2 2.375 60.3 2.157 54.8 109 2.77 2.64 3.93 4 7 37 • ASTM A795,Type E,Grade A(Schedule 40) 2% 2.875 73.0 2.635 66.9 .120 3.05 3,53 5.26 3.5 30 • NFPA 13 3 3.500 88.9 3.260 82.8 120 3.05 4.34 6.46 2.6 19 Manufacturing Protocols Schedule 10 and Schedule 40 are subjected 4 4.500 114.3 4.260 1082 azo 3.05 5.62 8.3719.6 to the toughest possible testing protocols to 5 5.563 141.3 5295 134.5 .134 3.40 7.78 11.58 1.5 13 ensure the highest quality and long-lasting performance. 6 6.625 168.3 6.357 161.5 .134 3.40 9.30 13.85 1.0 10 8 8.625 219.1 8,249 209.5 188 478 16.96 25.26 21 7 Finishes and Coatings All Wheatland black steel fire sprinkler pipe •Calculated using Standard UL CRR formula,UL Fire Protection Directory,Category VIZY. 'The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion, up to 6 receives a proprietary mill coating to Threaded Schedule 40 steel pipe is used as the benchmark(value of 7.0). ensure a clean,corrosion-resistant surface that outperforms and outlasts standard lacquer coatings.This coating allows the pipe to be SCHEDULE 40 SPECIFICATIONS easily painted,without special preparation. Schedule 10 and Schedule 40 can be ordered in NOMINAL NOMINAL black,or with hot-dip galvanizing,to meet NPS NOM OD NOM ID WALL WEIGHT UL PIECES FM/UL requirements for dry systems that meet in. mm In. mm in. mm lbs./ft. kg/m CRR' Lift the zinc coating specifications of ASTM A795 or A53.All Wheatland galvanized material is 1 1.315 33.4 1.049 26.6 .133 3.38 1.68 2.50 1.00 70 also UL Listed. 1+% 1.660 422 1.380 35.1 .140 3.56 2.27 3.39 1.00 51 Product Marking 1% 1.900 48.3 1.610 40.9 .145 3.68 2.72 4.05 100 44 Each length of Wheatland fire sprinkler pipe is continuously stenciled to show 2 2a7s 60.3 z 067 szs 54 3s1 ass s.as 00 30 the manufacturer,type of pipe,grade,size •Calculated using Standard UL CRR formula,(IL Fire Protection Directory,Category VIZY. and length.Barcoding is acceptable as a •The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is used as the benchmark(value of 7.0). supplementary identification method. ® C e APPROVED SUBMITTAL INFORMATION • PROJECT: CONTRACTOR: DATE: ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE: LOCATIONS: COMMENTS: ❑ BLACK ❑ HOT-DIP GALVANIZED Wheatland Tube 700 South Dock Street Sharon,PA 16146 Wheatland Tube P 800.257.8182 I F 724.346.72.60 I info@wheatland.com I wheatland.com 2MC STEEL GROUP Ductile Iron Threaded Fittings . .. ...s......„ , ......... ........ ,..,.. P; 2 s,„..s.p...1 .s. ... x`X ........„ , . ,. ,. .., ,, c„. .. ..,.. .. ,,s . ,....,„.......,. ,, ..... ,r . .. „ k , . ..., , . , ,,,,,,,,,,,,,,,:„.., ,-, ,,i, , .vi-,, , 1 , . , .'"4/144.15 1V-' ',,1° 4 1 k4`` " 94r it re 5P ry ,-4,1 �s � rA^rsc ' SMITII , COOPE INTERNATIONAL Ductile Iron Threaded Fittings Specifications • <4> branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP CCOUS • Ductile iron castings conform to ASTM A536 LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings 20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 /-- ucti e ron 'thugs- ass I I c ® us APPROVED LISTED A Fig. 35E 3-90°Elbow Size ilLpart Number A Packing Weight iiiwas in in Inner Master lb _ i 1/2 35F 3001 1-13 IOC 200 02 it,'' a_ 1 3/4 35E 3006 1.31 70 140 0.3 A 1 35L 3010 1.50 40 80 0.5 1=1 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1-1 2 35E 3020 2.25 10 20 1,8 2-1/2 35E 3024 270 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow B Size A B Packing Weight Part Number ,w ' in in in Inner Master lb mpoi 3!4 x 1/2 35RE3006004 1 20 1 72 80 160 0.3 1 x 1/2 35RE3010004 1.26 136 70 140 0.4 -- ai iiii IA T 1 x 3/4 35RE3010006 1 38 1 45 50 100 0.4 1-1/4 x 1/2 350E3012004 34 1.53 35 70 0.5 1 1-1/4 x 3/4 358E3012006 1.45 1 63 35 70 0.6 1-1/4x 1 35RE3012010 1,58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1-75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 3511L3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 35RE3020004 1,60 1,97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 358E3020010 1.73 2.02 16 32 12 2x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2x 1-1/2 3513E3020014 2,02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-1/2 x 2 358E3024020 2,39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow Size Part Number A Packing Weight A in in Inner Master lb �s , 1/2 355 3004 0.88 150 300 0.2 3/4 35F 3006 0.98 80 160 0.3 7. 1 35F 3010 1.13 40 80 0.5 1(4 35F 30124411 1.29 25 50 0.7 A i 1-1/2 35F3014 1.44 20 40 1.0 I_� 2 35F 3020 69 10 20 1.6 I 2-1/2 35r 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size Part Number A Packing Weight in in Inner Master lb 1=1 A 1/2 35T 3004 1-13 80 160 0-3 3/4 35T 3006 31 30 60 0.5 x -I� 1 351 3010 1 50 25 50 0.7 t &••••• .n,. i 1-1/4 35T 3012 1.75 10 20 1.1 N A < A . 1-1/2 351 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 111 SSI1'FI1-COOPFR LN"I'13RN,1TLONAI.' • 'IOLI, FREE I-SO)-766-0076 • FAX(323)890-1455 • s�ryesc.smithcooper.com 1 ., C 1 ` I ucti a ron fittings- ass III C ® US APPROVED Fig. 35RT3-Reducing Tee LISTED Size Part Number A B C Packing Weight in in in in Inner Master lb C 3/4 x 112 35RT3006004 1.20 1.20 1-22 60 120 0.4 1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 , -rt-- - - 1 x 1/2 x 1 35R13010004010 1.50 1,36 1.5C 30 60 0.6 1 x 3/4 35RT3010006 1.38 1.38 1.45 25 50 0.6 e -)1 1 x 3/4 x 3/4 39813010006006 1.38 1-31 1.45 35 70 0-6 B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35013012004 1.34 1 34 1.53 20 40 0.8 - 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4x3114 3517T3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4x I 35013012010 1.58 1.58 1.67 15 30 1.0 1-1/4x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0,7 1 1/4 x 1 x 3/4 3591-3012010006 1.45 1-38 1.63 20 40 0,8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1 1/4 35RT3012010012 1.75 1.69 1./5 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35013014004012 1 81 1.56 1-88 74 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 35RT3014006 1 52 1.52 1 75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2x3/4x 1-1/2 35013014006014 1,94 1.75 1.94 18 36 1-2 1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35RT3014010004 1.44 125 1.69 20 10 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2x 1 x' 35RT3014010010 1.65 1.50 1-80 16 32 1.0 1-1/2 x 1 x 1-1/4 350T3014110012 1.82 1.67 1.88 12 24 1.2 7- 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1.3 ,` `. 1-1/2x 1-1/4 35813014012 1.82 1.82 1.88 12 24 1.4 t ,r 1-1/2 x 1-1/4 x 1/2 358(30'4012004 1.41 1.34 1-66 16 32 9.9 i 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 1-1/2x 1-1/4x1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 a 41' 14/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 1-1/2x 1-1/4 x 1-1/2 35RT3014012014 1,94 1.88 1.94 14 28 1-4 %'i' 2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 2 x 3/4 35813020006 1.60 1.60 1.97 10 20 1 6 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 tc r 2 x 'I x 2 35RT3020010020 225 2.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 7 35013020012020 225 2.10 2.25 8 16 2-0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2x 1-1/2x 1/2 35813020014004 1.49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2x 1-1/2x 1 35813020011010 1.73 1.65 2.02 8 16 1.5 - 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1 1/2 x 1-1/2 351113020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35RT3-Bull Head Tee Size A B C Packing Weight Part Number JOWLjC in in in in Inner Master lb 11 3I4 x 1 35RT3006010 1.45 1.45 1.37 30 60 0.6 1 x 1-1/4 35BT3010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35013010014 1.80 1.80 1.65 15 30 1-.0 t o )1( B ) 1-1/4 x 1 x 1-1/2 35873012010014 1.88 1.80 1.82 15 30 1.2 1-1/4x 1-1/2 351313012014 1.88 1.88 1_82 15 30 1.3 1-1/4 x 2 35BT3012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 358T3014012020 2.16 2.10 2.02 10 70 1.8 1-1/2 x 2 35BT3014020 2.16 2.16 2.02 8 16 1.8 5\[I'l ll-C OOPF.R I\I'FRNAI'1OAAl;` • 'POLL FREE 1 500-756-0n76 • [ '\X(333)890-4356 • xcxcvc.snlidicunpcl.cum 112 . I ucti a ron ittings- ass I I I c ® us i APPROVED Fig. 35CP3 -Straight Coupling with Ribs LISTED Size Pail NumberA A Packing Weight I in in Inner I Master lb _ 1/2 35CP3004 1.38 200 400 0.1 3/4 35CP3006 -1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 2-19 25 50 0.7 2 350P3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.7 Fig. 35RC3 -Hex Reducing Coupling Size Part Number A Packing Weight in in _Inner Master lb _ A 1 x 1/7 35RC3010004 1.69 80 160 0,3 1 x 3/4 35RC3010006 1.69 60 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master , lb 1 x 1/2 35HB3010004 1.06 180 360 0.7 i I 1 x 3/4 35H83010006 1.06 180 360 0.1 j-- 1 I �A I-1/4 x 1 35HB3012010 1,19 92 180 0.2 ' 1 „ 1-1/2 x 1 35HB3014010 1,25 75 150 0.4 1-1/2 x 1-1/4 351363014012 125 75 150 0-3 2 x 1 35H83020010 1.38 40 80 0.6 2x 1-1/4 35HB3020012 1.38 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 Fig. 35SP3 -Square Head Plug 11 Size Part Number 11 A Packing Weight _ in n Inner Master lb -� 1;7 3SSP3004 0.94 600 1200 0.07 A 3/4 35SP3006 1.12 350 700 0.1 1 35SP3010 1,25 200 400 0.1 1(4 35SP3012 37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size A Packing Weight Part Number !! n n Inner Master lb �,�.. ap. � 9 1 355 301 C 2.19 20 40 1.0 11 1I 1-1/4 35U 3012 2.50 15 30 1.2 ��._ 1-1/2 350 3014 2.62 10 20 1.7 altilliraw 2 35U 3020 3.12 6 12 2.4 Now 113 SN[(TI I-COOPER INTERN VTIO\I, • TOI,I. PRf F 1-3110-766-0076 • F AX(323)890-4455 • wNmr.srnithcoopcccom Y aJ - Ductile Iron Fittings- Class 300 UL/ I Ctw!rY PLUS C ® US APPROVED Fig. 35X 3— Cross LISTED A )1( A ) Size A Packing Weight Part Number 'dMaster lb tk. � '!,� A in in Inner I _ _ 1 35X 3010 1,50 20 40 0.9 �� _ I 1-1/4 35X 3012 1.75 12 24 1.4 _ I �_I 1-1/2 35X3014 1.94 8 16 1.8 N IA 2 35X 3020 225 6 12 2.8 • 6 B Fig. 35RX3—Reducing Cross Size A B Packing Weight ' Part Number �' ' �A in in in Inner Master lb 1-1/4 x 1 35RX3012010 1_67 1.58 15 30 1.2 � 1__ 1-1/2x1 35RX3014010 1.80 1.65 12 24 1.4 ,— I �1 w` 2 x 1 35RX3020010 7.02 1.73 8 6 20 Fig. 35C 3— Cap Size A Packing Weight Part Number in in Inner Master lb 1/2 35C 3004 0-87 300 600 0.1 3/4 35C 3006 0.97 200 400 0.1 • 1 35C 3010 1.16 110 220 0.2 "-' 1-1/4 35C 3012 1.28 70 140 0.4 „ _ 1-1/2 35C 3014 1 33 50 100 0.5 ;= 2 35C 3020 1.45 25 50 0.8 2-112 35C 3024 1.70 18 36 1.6 x7 Fig. 35BC3—Beam Clamp Size A Packing Weight Part Number A in in Inner Master lb 3/8 356C3003 0.75 100 200 0.3 1/2 35BC3004 0.75 80 160 0.5 S\IPI'II-COOPER INl'ER'_VI'1O'1\I," • 'I'O1,I, I-REF; 1-800-706-0074 • FAX(323)890-4-436 • vcwsminccooper.com 114 IPSfpCAARBON�STEEL PIIPP�E9- HOLE CUT PRODUCTS (( 110.52 FireLock.® Ouliet-T c®II! FM IVdS) LPCB 13. SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 -._._. The Style 922 Outlet-T provides a convenient method of incorporating/,34,and 1715,20 and 25mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and other outlet products.Available for 11 through 76.1 mm/32 to 76.1mm piping systems,Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS Ti Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300psi/2068kPa and VdS rated up to 16bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard, lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code).FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America, Latin America,Asia Pacific) • Red enamel(Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaU�I(' REV G IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52 _P-'!.,ock® Outlet-T STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Size z Outlet Size 213,Section 16)(C=120)*,FT 1.7 1 Y< .Y 8.5 32 25 2.6 1' X. 1 8.5 40 25 2.6 2 x 1 8.5 50 25 2.6 215 x 1 8.5 65 25 2.6 76.1 mm X 1 8.5 25 2.6 *Hazen-Williams coefficient of friction is 120 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IQtaU lI C REV G IPS CARBON STEEL PIPE..-HOLE CUT PRODUCTS 10.52 -- r'Ck(ll OutlPf T STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. • WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.52 3355 REVG UPDATED 12/2009 Ictaullc. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. -^-.^•- 10.52 Pipe Hangers Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) ®To1_Co Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317(INFF) O US Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B3176NFC) LISTED Fig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm) pipe Material: Steel, Pre-Galvanized to G90 specifications s . Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation.` Features: ^ ® _ • (1/2" 115mm)thru 2" 15omml) Flared edges ease installation for all pipe it�+ types and protect CPVC plastic pipe from abrasion. Captured design _ s / ''I keeps adjusting nut from separating with hanger. Hanger is easily - B installed around pipe. For hanger with non-captured nut order Fig. 200S. A • (21/2" 165mm)thru 8" (200mm)) Spring tension on nut holds it securely in � , hanger before installation.Adjusting nut is easily removed. ,r'° Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" 1200mm)) Fig 280-1h 200314 in the USA(UL) and Canada (cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved(FM) (3/4" (20mm)thru 8" (200mm)). Fig.z80tto200.z Fig. 2lhwzooB Conforms to Federal Specifications WW-H-171 E &A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69 &SP-58, Type 10. Maximum Temperature: 650°F (343°C) "'r Finish: Pre-Galvanized. Stainless Steel 1 44' materials will be supplied with (2) hex nuts _mow in place of a knurl nut. Order By: Figure number and pipe size Designed to meet or exceed requirements of d FM DS 2-0. 44. W x ,. Fig.200 a Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. Imm) in. (mm) in. (mm) lbs. (kg) 200-1/2 1/2' (151 3/t"•16 31/8" (79.41 25/8" 166.71 11 (5.0) 200-3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" 163.5) 11 15.01 200-1 1" (251 3/8'-16 33/8" (85.7) 25/8' (66.71 12 (5.5) . 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8" (73.0) 13 15.9) 200-11/2 11/2" (40) 3/8"-16 37/8" 198.4) 27/8" (73.0) 14 (6.41 200-2 2" (501 3/8'"-16 41/2" (114.3) 3" (76.3) 15 (6.9) 200-21/2 21/2" (65) 3/8"-16 55/8" 1142.9) 41/e" (104.71 27 (12.3) 200-3 3" 175) 3/8%16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2' 1901 3/8"-16 73/8" 1137.3) 51/4" (133.31 34 (15.61 200-4 4" (100) 3/8"-16 73/8" (187.3) 5' (127.01 35 (16.0) 200-5 5" (125) 1/2"-13 91/8 (231.8) 61/4" 1158.11 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4' (171.4) 73 (33.41 200-8 8" (200) 1/2%13 131/8" (333.41 83/4" (222.21 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. R Fire Protection Solutions �+-Line 21 by E.'i•N Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig. 103) --, � B3205L - Threaded Rod (right& left hand threads) TL -` 9 3 Specify Length 11 Material:ae Range: /a"-16 thru 3"-4 rod / 'i Steel Function: Recommended for use as a hanger support in hanger assemblies. ., TL Rod is threaded on both ends with right hand threads of the length shown.Also A available with left and right hand threads-specify Fig. B3205L when ordering. Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kh) Lbs. (kN) B3205-3/8 x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-1/2 x'1' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/e x'L' 5/8"-11 272" (63.5) 2160 (9.61) 1692 (7.52) 83205-3/4 x'L' 3/4"-10 3" (762) 3230 (14.37) 2530 (11.25) B3205-7/e x'L' 7/e-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) 83205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) 63205-11/e x'1' 11/e"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) 83205-1114 x'L' 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2x'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) B3205-13/4 x'1' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) 83205-2 x'L' 2"-41/2 8" 1 (203.2) 24600 (109.42) 19625 (87.29) 93205-21/4 x'L' 21/4"41/2 9" (228.6) 32300 (143.67) 25295 (112.51) 03205-2112 x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR -All Threaded Rod 120" (3.05m) Lengths (Tom)Fig.100) Fig. 99 -All Threaded Rod Cut To Length Size Range: 3/0"-16 thru 11/2"-6 rod in 120" (3.05m)lengths or cut to length Material: Steel a m Maximum Temperature: 750°F(399°C) >"" 1.4 o Finish: Plain.Contact B-Line for alternative finishes and materials. ) 0 la L la Order By: Part number, rod diameter and finish ~a Threads Recommende -741): 013‘0),:,„ :40\1 d Load r A rox.Nt./100 Ft. Part No. Size x Length PP ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/8"x 120 99-3/8"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 5/s"x 120 99-5/a"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 718"x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B Pipe Hangers&Supports 236 Revised4/28/2014 Line by C.141