HomeMy WebLinkAboutPlans FPsZoz3 - 000G-z
I2.409 SW 68'T" PKWY
RECOVED
SUBMITTAL FOR APPROVAL MAY 3 1 2023
MERCER GLOBAL-Job#: 23080. CITY OF TIGARD
BUILDING DIVISION
DATE:4/27/2023
PACKAGE NUM: 7
PACKAGE REV: 0
SPEC#: 210000
To: Ron Tesch From: Jim Silvis
Pacific Realty Associates, L.P. Walen Construction, LLC
15350 SW Sequoia Parkway, Suite 300 16655 SW 72nd Avenue, Suite 200
Portland, OR 97224 Portland, OR 97224
We are transmitting the following Submittal Package Number:"7", Revision: "0" Description: "FIRE SPRINKLER PLAN"
for your review, intended to be compliant with contract Specification Number: "210000".
Please review and respond to Jim Silvis by 04/28/2023.
Additional Notes:
Submittal Item Revision Description Status
7 0 FIRE SPRINKLER PLAN For Approval
Notes:
Sincerely,
Pis Sava
SHOP DRAWING AND SUBMITTAL REVIEW
® CONFORMS TO DESIGN CONCEPT (REVIEWED BY WALEN CONSTRUCTION
❑ CONFORMS TO DESIGN CONCEPT EXCEPT AS NOTED
❑ NON-CONFORMING,REVISE AND RESUBMIT REVIEW of this submittal by WALEN CONSTRUCTION is only for
❑ REVIEWED general conformance with the design concept of the project and general
compliance with the information given in the contract documents. The
THIS SUBMITTAL HAS BEEN REVIEWED FOR GENERAL CONFORMANCE WITH THE contractors and vendors are responsible for conformance to the
DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE
INFORMATION GIVEN IN THE CONTRACT DOCUMENTS.ANY ACTION SHOWN IS SUBJECT requirements of the contract documents and this review does not relieve
TO THE REQUIREMENTS OF THE PLANS,SPECIFICATIONS AND APPLICABLE CODES,ALL that obligation. The contractors and vendors and responsible for.OF WHICH HAVE PRIORITY OVER THIS SUBMITTAL.CONTRACTOR IS RESPONSIBLE FOR
QUALITY, DIMENSIONS(WHICH SHALL BE CONFIRMED AND CORRELATED AT THE JOB dimensions which shall be confirmed and correlated at the job site,
SITE),FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION, fabrication processes and methods of construction,coordination of work
WITH COORDINATION OF THE WORK THAT OF ALL OTHER TRADES AND THE
SATISFACTORY PERFORMANCE OF THE WORK with all other trades,and satisfactory performance of work.
Date:4/27/2023
Date 04/27/2023 By RonT .001
IIWa 16655 SW 72nd Avenue,Suite 200 I Portland,OR 97224
6 ConstructionIEn P:(503)718-6680 I F:(503)210-7090 I W:Walen.com
OR CCB:223805 I WA LIC:WALENCL816BP
0
SUBMITTAL RETURN
MERCER GLOBAL -Job#: 23080.
DATE:04/28/2023
PACKAGE NUM: 7
PACKAGE REV: 0
SPEC#: 210000
To: Jason Sampson From: Jim Silvis
Fire Systems West Walen Construction, LLC
206 Frontage Rd N -Suite C 16655 SW 72nd Avenue,Suite 200
Pacific,WA Portland, OR 97224
98047
We are transmitting the following Reviewed Submittal Package Number: "7" Revision: "0"Description:"FIRE
SPRINKLER PLAN"for your use.
Please review and respond to Jim Silvis, should you have any questions,or need additional information regarding
any of the items.
REVIEW of this submittal by Walen Construction is only for general conformance with the design concept of the
project and general compliance with the information given in the contract documents.The contractors and vendors
are responsible for conformance to the requirements of the contract documents and this review does not relieve that
obligation.The contractors and vendors and responsible for dimensions which shall be confirmed and correlated at
the job site,fabrication processes and methods of construction,coordination of work with all other trades,and
satisfactory performance of work.
Additional Notes:
Submittal Item Revision Description Status
7 0 FIRE SPRINKLER PLAN Approved
Notes:
Sincerely,
n 16655 SW 72^d Avenue,Suite 200 I Portland,OR 97224
W3�E 1 I P:(503)718-6680 I F:(503)210-7090 I W:Walen.com
�,Construction OR CCB:223805 I WA LIC:WALENCL816BP
Bulletin 014 Rev. P
co
® Model Fl FR Series
Quick Response o
• liellable Glass Bulb Sprinklers Dcr
Model Fl FR56 Sprinkler Types rt pf
Standard Spray Upright k , {-I -
Standard Spray Pendent •7 �e� *is
0.1114
Conventional Upright/Pendent
Vertical Sidewall
Horizontal Sidewall
Model F1 FR56 Recessed Sprinkler Types Upright Pendent Conventional
Standard Spray Pendent
Ala Horizontal Sidewall -_. .
Model Fl FR56 Concealed Sprinkler Types IR N ,
Standard Spray Pendent
Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler
Types
Standard Spray Upright Vertical Sidewall Horizontal Sidewall Recessed
Standard Spray Pendent Pendent/F11F2
Model F1 FR40 Sprinkler Types - z ; Q •''
Standard Spray Pendent / N` s ,
Model F1FR42, F1FR40, F1FRXLH & F1FR28 ..
Recessed Sprinkler Types ;r=:� �,: >„
Standard Spray Pendent ;•, „ " '
- Model F1 FR56LL&F1 FR42LL Low Lead Sprnker Recessed Concealed Recessed
Types Horizontal Sidewall Pendent Pendent/FP
Standard Spray Pendent with less than 0.25% Lead
Content ) l
Listing &Approvals , _ , d
The following organizations provide Listings or Approvals ' r
for various Model F1FR series sprinklers. See the Design
and Installation table in this Bulletin for information on
specific listings and approvals applicable to each sprin- XLH Upright XLH Pendent XLH Recessed
kler. Pendent F1/F2
1. Underwriters Laboratories Inc. and Certified for Product Description
Canada(cULus) in accordance with ANSI/UL199. Reliable Model F1FR series sprinklers .,----
2. FM Approvals (FM) are quick-response automatic sprin- i ' -''
3. Loss Prevention Certification Board (LPCB) klers with a glass bulb thermal element. ' . ' �-
4. VdS Schadenverhutung GmbH (VdS) Model F1FR series sprinklers are Stan
5. Underwriters Laboratories Inc. and Underwriters dard Spray sprinklers, with the excep
Laboratories of Canada Certified for Health Effects tion of the Model F1 FR56 Conventional XLH Recessed
to NSF/ANSI Standard 61 Annex G (ULH) sprinkler which is an Old-style/Conven- Pendent FP
6. EC Certificate: 0786 CPD-40239 (RA1414), 0786- tional sprinkler.
CPD-40251 (R 0785), 0786-CPD-40252 (R 5) The Model F1FR Series automatic sprinklers utilize a 3.0
(EC) mm frangible glass bulb.These sprinklers have demonstrat-
ed response times in laboratory tests which are five to ten
UL Listing Category times faster than standard response sprinklers. This quick
Sprinklers, Automatic&Open (VNIV) response enables the Model Fl FR Series sprinklers to apply
Quick Response Sprinkler water to a fire faster than standard-response sprinklers of the
same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
At normal temperatures, the glass bulb contains the fluid Model FIFA Series sprinklers must be installed with the
in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design
be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other
expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinkler joint'
uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m).
to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended
opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended'
ute the discharging water. installation torque may cause leakage or impairment of the
Model F1FR Series sprinklers provide a wide range of op- sprinkler.
tions where quick-response,glass bulb sprinklers are used: Recessed Sprinklers
• Pendent, recessed pendent, upright, horizontal Model F1 FR Series Recessed sprinklers are to be installed
sidewall, and vertical sidewall deflectors as shown in Fig. 1, Fig.2,or Fig.3,as applicable to the spe-
• K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data
metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons
• Flush, recessed, and concealed installations that are permitted to be used with each Model F1FR Series
See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch-
Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties.
specific Model F1FR series sprinkler configurations. Concealed Sprinklers
Model F1FR Recessed Pendent and Recessed Horizon- Model F1FR Series Concealed Pendent sprinklers are to
tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig.4 or Fig.5,as applicable to the
Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1FR56 Concealed Pendent
cessed Escutcheon Data table in this Bulletin for listing and and Model F1FR56LL Concealed Pendent sprinklers have
approval information with each specific Model F1FR series a factory-installed Model CCP cup. A protective cap is in-
sprinkler. Model F1 and F2 recessed escutcheons,shown in stalled at the factory that should remain on the sprinkler until
Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on
(19mm) and 1/2-inch (12.7mm)of adjustment, respectively. the sprinkler until the cover plate is installed.The concealed
Model FP recessed escutcheons,shown in Fig.2, provide a sprinkler assemblies are completed by the installation of a
1/2-inch(12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The
Model F1FR56 Concealed Pendent and Model F1FR56LL cover plate and sprinkler cup assemblies are joined using
Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage-
Model CCP cover plates.A standard profile Model CCP coy- ment. A choice of two Model CCP cover plate assemblies
er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch(13mm)or 5/8-inch(8mm)of cover
cover plate adjustment. In addition, a low profile Model CCP adjustment. Do not install Model F1 FR Series Concealed
cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure
(8.0mm) of cover plate adjustment. See the Design and In- in the space above.
stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a
Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching
Application surfaces and to install the sprinkler in the fitting. Remove the
Model F1FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective
accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov-
Data Sheets, and the requirements of the Authority Hav- ing the wrench from the sprinkler/cup assembly,care should be
ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any
temperature rating, deflector style,and sprinkler type are other part of the sprinkler/cup assembly. Installation is corn-
in accordance with the requirements of the applicable plated by removing the protective cap from the sprinkler and
design and installation standards. In addition, Model pushing the cover plate onto the cup.Final adjustment is made
F1FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full
their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the
provided in this Bulletin. cover plate in the counter clockwise direction.After installation,
Installation inspect all sprinklers to ensure that there is a gap between the
Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and
tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above.
dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for
es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover
place.Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with
kler system is placed in service for fire protection. Removal Model F1FR56 Concealed Pendent and Model F1FR56LL
of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP
nerable to damage.Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with
clasp by hand. Do not use tools to remove bulb protectors. which it is not specifically listed my prevent good fire pro-
tection and will void all guarantees, warranties, listings and
approvals.
2.
Technical Data:
Sensitivity: Quick-response
- Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional
Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar)
SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar)
Design and Installation Information
Nominal Nominal Nominal
K-factor Orifice Deflector/ Sprinkler Installation Listings
Model Diameter Hei ht Approval
Orientation g Wrench SIN and Notes
US Metric inches mm inches mm Approvals
Pendent 2.25 57 D or W2 RA1411 cULus 2
F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2
Upright 2.25 57 D or W2 RA1421 cULus 1,2
F1 FR40 4.0 57 3/8 10 Pendent 2.25 57 D or W2 RA1418 VdS
Recessed Pendent 2.25 57 GFR2 RA1418 VdS
Pendent 2.25 57 D or W2 RA1413 cULus 2
F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 D or W2 RA1423 cULus 1,2
F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D or W2 RA1410 cULus,ULH
Recessed Pendent 2.25 57 GFR2 RA1410 cULus, ULH
F1FRXLH Pendent 2.25 57 D or W2 RA1413 cULus 2
(F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
with Pintle) Upright 2.25 57 D or W2 RA1423 cULus 1,2
Pendent 2.25 57 D or W2 RA1414 cULus,FM, 1,2,3,4
LPCB,VdS,EC
Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, 1,2,3,4
LPCB,VdS, EC
F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6
Upright 2.25 57 D or W2 RA1425 cULus, FM, 1,2,3,4
LPCB,VdS,EC
"Conventional 2.25 57 D or W2 RA1475 LPCB,VdS,EC 4
(Pendent or Upright)"
Pendent 2.25 57 D or W2 RA1415 cULus,ULH 1
F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, ULH
Concealed Pendent 2.25 57 RC1 RA1415 cULus, ULH 6
Horizontal Sidewall 2.63 67 D or W2 RA1435 cULus, FM 1,2,3,7
F1FR56 5.6 80 1/2 15 Recessed Horizontal 2.63 67 GFR2 RA1435 cULus, FM 8
Sidewall
F1FR56 5.6 80 1/2 15 Vertical Sidewall 2 25 57 D or W2 RA1485 cULus,FM, 1 2 3 9
(Pendent or Upright) LPCB
0)cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
124 cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
j31 Available with FM approved Polyester coating in black or white.
of Available with LPCB and VdS approved Polyester coating.
(5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin-
•
•
klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only.
(6)Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment.
rn cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. Minimum to maximum deflector to
ceiling distance shall be 4 inches to 12 inches(102mm to 305mm).FM Approval of the F1FR56 Horizontal Sidewall sprinkler is for Light Hazard
occupancies only.
iel cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
Pi The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. LPCB approval of the F1FR56 Vertical
Sidewall sprinkler is for installation in the Pendent position only.
3.
Listed and Approved Temperature Ratings
Ordinary Temp. Intermediate Temp. High Temp.
Classification Classification Classification
Deflector/ 100°F(38°C)Max.Ambient 150°F(65°C) Max.Ambient 225°F(107°C)Max.
Model Orientation Tem . Temp. Ambient Temp.
135°F(57°C) 155°F
F(68°C)
C) 175°F(79°C)
C) 200°F
F(93°C)
C) 286°F(141°C)Temp. •
Temp.Rating Temp. Rating Temp.Rating Temp. Rating Rating
Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb
Pendent cULus
F1FR28 Recessed Pendent cULus --
Upright cULus
F1FR40 Pendent VdS
Recessed Pendent VdS
Pendent cULus
F1FR42 Recessed Pendent cULus
Upright cULus
F1FR42LL Pendent -- cULus,ULH __
Recessed Pendent -- cULus,ULH
Pendent cULus
F1FRXLH Recessed Pendent cULus --
Upright cULus
Pendent cULus,FM,LPCB,VdS,EC
Recessed Pendent cULus,FM,LPCB,VdS,EC —
F1FR56 Concealed Pendent* cULus cULus,VdS,EC cULus --
Upright cULus, FM, LPCB,VdS, EC
"Conventional LPCB,VdS,EC
(Pendent or Upright)"
Pendent -- cULus,ULH --
F1FR56LL Recessed Pendent -- cULus,ULH --
Concealed Pendent* -- cULus, ULH --
Horizontal Sidewall cULus,FM
F1FR56 Recessed Horizontal cULus,FM --
Sidewall
F1 FR56 Vertical Sidewall (Pen- cULus,FM,LPCB
dent or Upright)
* Model F1 FR56 Concealed Pendent and El FR56LL Concealed Pendent sprinklers must be used with Reliable Model
CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover -
plate. For Intermediate Temperature Classification sprinklers use a 165°F(74°C)temperature rated cover plate.
Recessed Escutcheon Data
Listed and Approved Recessed Escutcheons
Deflector/ Model F1 Model F2 Model FP
Model Orientation (Fig. 1 &3) (Fig.1 &3) (Fig.2) SIN
3/4-inch(19mm) 1/2-inch(12.7mm) 1/2-inch(12.7mm)
adjustment adjustment adjustment
F1FR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus,ULH cULus,ULH cULus,ULH RA1410
F1FR42XLH Recessed Pendent cULus cULus cULus RA1413
F1FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM,LPCB, cULus,VdS,EC RA1414
EC VdS,EC
F1FR56LL Recessed Pendent cULus, ULH cULus,ULH cULus,ULH RA1415
F1FR56 Recessed Horizontal Sidewall cULus cULus,FM cULus RA1435
4.
2 1/4'HOLE DIA
[57.2mmJ
1 15/16'DM
' [49.2mod
/
L_ _ _ _--=-I
rs--I==—i7
I Ti 1"X 1/2" REDUCER
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER t
WRENCH BOSS \ \ / FACE OF FITTING
1-- \ —p TO FACE OF CEILING DIMENSION
I1 II El ESCUTCHEON
II r = -- II AT MAXIMUM RECESS = 1[25.4mm]
��� 1 L _ J AT MINIMUM RECESS = 3/879.5mm]
F1 ESCUTCHEON F2 ESCUTCHEON
3/4[19mm] 3� _1, AT MAXIMUM RECESS - 3 4 19mm ADJUSTMENT - / C ]
F2 ESCUTCHEON II ®SStla II' AT MINIMUM RECESS = 3/8[9.5mm]
1/2'[12.7mm] ill' ,���
ADJUSTMENT `0; (14� Fl ESCUTCHEON
III I �I�I 1/e' AT MAXIMUM RECESS = 7/8[22.2mm]
Atilt)
(3.2mmJ AT MINIMUM RECESS = 1-5/8[41.3mm]
���it
F2 ESCUTCHEON
`'II �V AT MAXIMUM RECESS = 1-1/8[28.6mm]
�•�•� AT MINIMUM RECESS = 1-5/8[41.3mm]
2 27/32'DIA.
[72.2mmJ
Fig. 1
Model F1 FR56,F1 FR56LL,F1 FR42,F1 FR40,F1 FR42LL,Fl FRXLH&Fl FR28
Recessed Pendent sprinkler with Model F1 or F2 escutcheon
L
_
I- =___,
I I I I" X 1/2" REDUCER
2 5/8" DIA. [66.7mm]
HOLE IN CEILING \ I
2 5/16" DIA. [58.7mm]
CUP I 1
CEILING
1.1' FACE OF FCEILI
I. II� 005VH ICI' , TO FACE OF CEILING
` -- III II I . DIMENSION
LL- / toil - - i t I. AT MAXIMUM RECESS = 1-1/2[38mm]
• AT MINIMUM RECESS = 1'(25.4mm]
`� -i' AT MAXIMUM RECESS = 9/16[14.3mm]
%z[12.7mm] '�!„��` AT MINIMUM RECESS = 1[25.4mm]
ADJUSTMENT
••• 3 1/4" DIA. f
[82.6mm] -
Fig.2
Model F1 FR56,F1FR56LL,F1FR42,F1 FR40,F1FR42LL,F1 FRXLH&F1 FR28
Recessed Pendent sprinkler with Model FP escutcheon
5.
FACE OF FITTING
TO FACE OF CEILING DIMENSION
Fl ESCUTCHEON j/�����/�
AT MAXIMUM RECESS = 1'[25.4mm] Fl ESCUTCHEON
AT MINIMUM RECESS = 3/8 T9.5mm]
F2 ESCUTCHEON AT MAXIMUM RECESS = 1-3/8[34.9mm]
•
AT MINIMUM RECESS = 2-1/16[52.4mm]
AT MAXIMUM RECESS = 3/4719mm] / F2 ESCUTCHEON
AT MINIMUM RECESS = 3/87.9.5mm]
AT MAXIMUM RECESS = 1-5/8741.3mm]
2 1/4" HOLE DIA. ---1.— f I/8.. AT MINIMUM RECESS = 2—1/1 6 752.4mm]
[57.2mm] N. [3.2mm]
1" X 1/2" REDUCER
—1'hi
iJ r f I'Vigilmi. I '--F-A \ (I)
1 15/16" DIA.11 El ' ___ II!I'II,,,,j,ll ,ii [101.6mm-304.8mm]
[49.2mm] 1 mil I I6 i lllI "'di' 2 27/32" DIA. CEILING TO
i II 1 [72.2mm] DEFLECTOR
L_om I ��A
TURN COLLAR UNTIL ��\\\Nit
TIGHT WRENCH�BOSS.INST SPRINKLER `.1 F1 ESCUTCHEON
3/4[19mm] ADJUSTMENT
f F2 ESCUTCHEON
1/2[12.7mm] ADJUSTMENT
OINVO E
RECESSED HSW W/F1 OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" — 6" [101.6MM — 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY.
Fig.3
Model F1 FR56 Recessed.Horizontal Sidewall sprinkler with Model F1 or F2 escutcheon -
1" x REDUCING
TEE ORR ELBOW ____
---- -
-, I_ r- 2 5/8" DIA.
2 5/16" DIA _
HOLE IN CEILING
CUP ti —I=.—
-"( 1ll��� 09`tl' 1���1 s 1 1/2" MAX.o i FACE OF FITTING
y
///r//// ° TO FACE OF CEILING
/ — —
r=5! ., :I., T,—;,,-/,/- DIMENSION
CElLING� �1\ IN ///////.,
----
1/2" MAX. —I 15/16"
COVER ADJUSTMENT
COVER PLATE
ASSEMBLY _ 3 5/16" DIA. -
SPRINKLER /
CONCEALED, 1/2" ADJUSTMENT °"Fc°'"
Fig.4
Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch(12.7mm)adjustment-Model CCP cover plate
6.
1" x 1/2" REDUCING
TEE OR ELBOW
III T[
2 5/8" DMA.
2 5/16" DM — — 5 HOLE IN CEILING
1--- -- J
CUP �* 0.
el ' 1��� 1 1/2" MAX.
ji
,;;;/f li. I,III FACE OF FITTING
' TO FACE OF CEILING
CEILING - c-/ .._ y 1 (/ / /7/ DIMENSION
1 �7 , 1
p r
5/16" MAX. 3/4"
COVER ADJUSTMENT
COVER PLATE— / }
ASSEMBLY _ 3 5/16" DIA.
SPRINKLER /
CONCEALED, 5/16" ADJUSTMENT 017FG01A
Fig.5-Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with low profile
5/16-inch(8.0mm)adjustment-Model CCP cover plate
Maintenance
The Model F1 FR Series sprinklers should be inspected and Material Data
the sprinkler system maintained in accordance with NFPA Frame: DZR Brass,OM Brass,or Low Lead Brass
25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220,260,or 510
any other cleaning fluids. Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544
or gentle vacuuming. Replace any sprinkler which has been Cup: CDA Alloy 651 or 693
painted(other than factory applied)or damaged in any way. Washer: Nickel Alloy 440 or 360,coated with PTFE
A stock of spare sprinklers should be maintained to allow Adhesive Tape
quick replacement of damaged or operated sprinklers. Bulb: Glass
Finishes (1) —
Standard Finishes
Sprinkler Escutcheon Cover platet't Ordering Information
Bronze Brass Chrome Specify:
Chrome Plated Chrome Plated White 1. Sprinkler Model: [F1 FR28][F1 FR40][F1 FR42]
Polyester Coated(4t White Painted
Special Application Finishes [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL]
Sprinkler Escutcheon Cover platet't 2. Sprinkler Deflector/Orientation: [Pendent][Recessed
Electroless Nickel Electroless Nickel Pendent
PTFE(' PTFE Bright Brass ][Upright][Conventional][Horizontal Sidewall]
Bright Brass(3) Bright Brass Black Plating [Recessed Horizontal Sidewall][Vertical Sidewall]
Black Plated Black Plated Black Paint 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2]
BlackPaint1ztts' Black Paint Off White 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F
Off Whitelzllsl Off White Satin Chrome (68°C)][175°F(79°C)][200°F(93°C)][286°F(141°C)]
Chrome Dull Chrome Dull
I'i Other finishes and colors are available on special order. Consult the 5. Sprinkler Finish
factory for details.Custom color painted sprinklers may not retain their 6. Escutcheon Model: [Fl][F2][FP]
UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, 7. Escutcheon Finish (where applicable)
PI unless specified otherwise 8. Cover plate Model: [standard profile CCP 1/2-inch
cULus Listed only. 12.7mm ad ustment low( ) j ][ profile CCP 5/16-inch
31 200°F(93°C)maximum.
[4) cULus listed "corrosion resistance' applies to SIN Numbers RA1435 (8.0mm) adjustment]
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and 9. Cover plate Temperature Rating: [135°F(57°C)for use
RA1415 (Pendent) in standard black or white. Corrosion resistance in with Ordinary Temperature sprinklers][165°F (74°C)
other polyester colors is available upon request.
FM Approvals finish as"Polyester coated"applies to SIN Number for use with Intermediate Temperature sprinklers]
RA1414,RA1435 and RA1425 in standard black or white. 10. Cover plate Finish
ce LPCB and VdS Approved finish applies only to RA1425, RA1414,RA1418
(VdS)and RA1475. Note: When Model F1 FR Series Recessed sprinklers are ordered, the
m cULus listed Corrosion Resistant sprinklers and escutcheons are packaged separately.
7.
Reliable . . . For Complete Protection.
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock. •
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fre Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.
Manufactured by �� Recycled
Reliable Automatic Sprinkler Co.,Inc. Paper
0 (800)431-1588 Sales Offices
Reliable (800)848-2051 Fax Revision lines indicate updated or new data. •
(914)829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address CO.Printed in U.S.A.11/17 P/N 9999970300
Bulletin 034 Rev. D
co
Model G5-80, Model G5-56,
Model G5-42, Model G5-28
• Quick Response Concealed
Automatic Sprinkler
UL Quick Response
FM Standard Response
Concealed Sprinkler With a
3/4" (19mm) Adjustment
Features
1. Cover plate attachment (Plain or Perforated) with
3/4"(19mm)assembly adjustment.
2. Smooth aesthetic ceiling profile. Plain Cover Plate
3. Factory installed protective cap.
4. Available in Chrome and White as Standard Finish-
es.Special Application Finishes are also available.
5. Ordinary and Intermediate temperature rating.
For additional Sprinklers refer to Bulletin 154 for -- --;- .,
Technical Specification and Approvals tr
Approvals & Listings
1. Underwriters Laboratories Inc.and cULus-
Quick Response
• G5-80, G5-56 - Light Hazard and Ordinary Perforated Cover Plate
Hazard Occupancies
•
• G5-42- Light Hazard Occupancies The Model G5-80, G5 56, G5-42 and G5-28 are designed
• G5-28- Light Hazard Occupancies for use where aesthetic appearance is important.Offices,hos-
2. Factory Mutual Research Corp. (FM)- pitals,motels and restaurants are but a few of the applications
Standard Response (See Page 3) where it can be used.
• G5-56 & G5-28 only. The Model G5-80, G5-56, G5-42 and G5-28 are UL Listed
• See the most recent FM Global Property Quick Response Concealed sprinklers intended for use in
Loss Prevention Data Sheets for installation accordance with NFPA 13. FM Approves the G5-56 and the
and use guidelines. G5-28 sprinkler as a standard response concealed sprinkler
3. Loss Prevention Council (LPCB, UK)- intended for use in accordance with FM Loss Prevention Data
Standard Response Sheet 2.0.
• G5-56 - Light Hazard and Ordinary Hazard Product Description
Occupancies The Reliable Model G5-80, G5-56, G5-42 and G5-28 uses
4. VdS Schadenverhutung GmbH- a proven quick response fusible element in a standard style
Standard Response sprinkler frame with a drop-down deflector. This assembly is
5. EC-Certificate of Conformity 0832-CPD-2062 recessed into the ceiling and concealed by a flat cover plate
U.S. Patent number 6,554,077. assembly.The threaded engagement provides 3/4"(19mm)of
cover adjustment. The flat cover plate is attached to the skirt
Application using either 135°F(57°C) or 165°F(74°C) ordinary tempera-
The Reliable Model G5-80, G5-56, G5-42 and G5-28 are ture classification solder.
the most versatile quick response concealed sprinklers avail- When the ceiling temperature rises, the solder holding the
able. It provides the best form of fire protection while offering flat cover plate melts,the flat cover plate released thus expos-
an attractive appearance and 3/4" (19mm) of cover adjust- ing the sprinkler inside to the rising ambient temperature.
ment for ease of installation. The small diameter cover plate The subsequent fusing of the element opens the waterway
assembly is easily attached and blends into the ceiling, con- and causes the deflector to distribute the water. Any secure
cealing the most dependable fire protection available,an au- engagement between the cover plate and cup will assure that
tomatic sprinkler system. the drop-down deflector is properly located below the ceiling.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
.• .• .,
Ordering Information
Installation -ar.
Do not install the G5-80, G5-56,G5-42 and G5-28 in ceilings 1. Sprinkler Model
which have positive pressure in the space above. 2. Nominal Orifice
• Cut 25A"inch(67mm)diameter hole is cut in the ceiling,the 3. Flat Cover Plate
sprinkler is easily installed with the Model FC Wrench. The Plain or Perforated
wrench has a socket drive which is inserted into the body of 4. Flat Cover Plate
PI .
the sprinkler. When installing a sprinkler the wrench is first Assembly Finish
positioned into the sprinkler/cup assembly until the wrench 5. Inlet Type _.`•
socket engages the body of the sprinkler. The sprinkler is Cover Plate Finishes(') OH
then tightened into the pipe fitting. When inserting or remov- Standard Finishes DQOW;,
ing the wrench from the sprinkler/cup assembly,care should Chrome
be taken to prevent damage to the sprinkler. DO NOT White Paint
WRENCH ON ANY OTHER PART OF THE SPRINKLER/ Special Application x
CUP ASSEMBLY. Install the cover plate by hand turning the Finishes(2)
cover in the clockwise direction until it is tight against the ceil- Bright Brass Model FC Sprinkler Wrench
ing. Finished Bronze UL Listing Category
A protective cap is provided to protect the drop-down sprinkler Black Plating Sprinklers,Automatic and
deflector from damage which could occur during construction Black Paint Open
before the cover plate is installed. The cap is factory installed Off White Quick Response Sprinkler
inside the sprinkler cup.Remove cap to install sprinkler,then re- Satin Chrome UL Guide Number
install cap until the cover plate is installed. o„ Other finishes and colors are VN IV
available on special order.
Maintenance Consult factory for details.
The Model G5-80, G5-56, G5-42 and G5-28 should be in- coverplate custom paint is
spected and the sprinkler system maintained in accordance semi-gloss, unless specified
otherwise.
with NFPA 25. Do not clean sprinklers with soap and water,am- (2) For the perforated style cover-
monia or any other cleaning fluids. Remove any sprinkler that plate, consult factory for avail-
has been painted (other than factory applied) or damaged in ability on these and other cus-
any way. Concealed sprinklers cover plates can not be painted torn finishes.
in the field, after installation or have any other coating applied Maximum Working Pressure
other than the factory finish.A stock of spare sprinklers should 175 psi (12 bar)
be maintained to allow quick replacement of damaged or oper 100%Factory tested Hydrostatically to 500 psi (34.5 bar)
ated sprinklers. Prior to installation, sprinklers should be main-
tained in the original cartons and packaging to minimize the Temperature Rating
potential for damage to sprinklers that would cause improper Cover Max.Ambient
operation or Wort operation. Classification Sprinkler Plate Temp.
Ordinary 165°F/74°C 135°F/57°C 100°F/38°C
Intermediate 212°F/100°C 165°F/74°C 150°F/66°C
2.
Technical Data
Sprinkler Nominal
S
p Sprinkler Inlet Total Nominal K Factor Sprinkler
Thread Approvals
US Metric Identification (SIN)
G5-80 Non Adjustable '/a"(19mm) "/32"(15mm) 8.0 115 3A"NPT(R3/4) 1 RA3412
G5-56 Non Adjustable 3/4"(19mm) 1/2"(15mm) 5.6 80 /"NPT(R'h) 1,2,3,4,5 RA3415
G5-42 Non Adjustable 3A''(19mm) 7/s"(10mm) 4.2 60 /"NPT(RIM 1 RA3413
G5-28 Non Adjustable 3/4"(19mm) 3A"(10mm) 2.8 40 /2"NPT(RY) 1,2 RA3411
For VdS Approval, temperature rating sprinkler 165°F/74°c and cover plate 135°F/57°C only!
i'"x 1/2" REDUCING TEE OR ELBOW / / 1`x 3/4"REDUCING
TEE OR ELBOW
G5-BO ONLY
T II _1-
I 4--- -- 'ii
r, r— 4"[66.55mm]
2a"[5B.42min] DIA -- HOLE IN CEILING
-_
CUP '.-.J
i 2-7/4"[57.15mm] MAX.
"' "M111.111.1.!�__�?1 _'�; FACE OF FITTING
������ �; _tik!4�`�� TO FACE OF CEILING
' ,� - _ . DIMENSION
CEILING I MEE
1
.
'34"[19.05mm] MAX._
COVER ADJUSTMENT "[4.96mm]
FLAT COVER PLATE
ASSEMBLY 34"[84.21mm] Ohl.
SPRINKLER
° °°'" COVER PLATE• 3/4„ (19 05mm_7 ADJUSTMENT
Notice
FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS
1'x 1/2"REDUCING
TEE OR ELBOW
I r-ill
_- 'l,
Ili __
+71-III --,�
-) r-
RELIABLE P/N 6999991900 r =_
v X}'BRASS NIPPLE EXT. L_ J
IIIIMMIIL
4-f66.55mmi
f
2A"[58.42mm]DIA HMI S_.....% HOLE IN CEILING
CUP 3-1/16"[77.72mm]MAX.
__-----'1• FACE OF FITTING
911 TO FACE OF CEILING
DIMENSION
�■ 2-1/4"[57.15mm)MAX.
IF1M1 FACE OF NIPPLE EXT.
••••.‘‘ I _ TO FACE OF CEILING
- •- • DIMENSION
CEILING x�x���x
.=
I Jl i71=.��,
i"[19.05mm]MAX._
COVE??ALVUSTMENT ,J7
FLAT COVER PLATE 3ya"5 T6�(4.96mmJ
ASSEMBLY [84.21mm]DW.
SPRINKLER
°'"°°' COVER PLATE: 3/4" [19.05mm] ADJUSTMENT
NOTE:
1. Testing has shown that use of a"nipple extension"will not affect the listing of the sprinkler.
2. For RETROFIT installations, per NFPA 13(2010)section 8.15.19.4, "which allows the use of nipples as the same pipe
• thread size as the existing outlet when revamping existing systems".
3. Do not exceed 8-18 ft-lbs of torque during installation.
3.
lll�
Reliable. . . For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
•
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by Recycled
Reliable Automatic Sprinkler Co.,Inc. eli Paper
Reliable (800)431-1588 Sales Offices
541 Sales Fax
( Revision lines indicate updated or new data. •
(914)800)848-6208292042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.06/14 P/N 9999970421