HomeMy WebLinkAboutReport RECEIVED E s A 7 4 2023 mnw 1 5caasiLsrrr III. CITY OF T(G ErsgfrssrierFirsgallual' BOIL❑❑ 400 25125 S. Mt. View Rd. Robert C. Seubert, PE Phone/Fax (503) 824-5030 Colton, OR 97017 Rseubert@seubertmachininu.com Cell (503) 805-2920 Delta Fire, Inc. 5/23/23 14975 S.W. 72nd Ave. Portland, OR 97224 ATT: Lisa P5202.3 D00.7l Subject: System Review/PE Stamping 6gzo Su) ZNa A✓6 Grocery Outlet 3129 Delta project#23-6202 Hi Lisa, I've reviewed the drawing for this tenant improvement project. Design criteria is per NFPA 13 I find no concerning issues with the design or layout with respect to the applicable NFPA standards the project is adhering to. Given the compliance with the stated and supplied specifications it's my pleasure to approve this package with my PE stamp. Best Regards, Robert Seubert, PE 0 IICE Cd.7py IL°E COPY DELTA 7R9A O7,2O 992722 RECEIVED PHONE: 503,620.4020 v `, '] O FIRE, INC. vc"4h.DELTAF]RE.COM P�j;A;! 7 4 2023 CCB# 64174 CITY OF TIGARD BUILDING DIVISION GROCERY OUTLET STORE 3129 TIGARD TIGARD, OR DATA SUBMITTAL FOR FIRE PROTECTION SYSTEM 04/ 14/ 2023 DELTA FIRE, INC. PROJECT # 23-6202 FIRE PROTECTION CONTRACTORS TABLE OF CONTENTS Pipe & Fittings STEEL DOMESTIC PIPE DUCTILE IRON SCREWED FITTINGS VICTAULIC MECHANICAL TEE FIG.#922 Hangers RING HANGER THREADED ROD SAMMY SWG-20 HORIZONTAL ANCHOR Sprinkler Heads RELIABLE F1FR-56, 1/2", 155° F, SSP, CHROME RELIABLE F3QR56, DRY, 1/2", 155°F, SSP, CHROME VICTAULIC 1/2" x 48" BRAIDED FLEX DROP FIRE PROTECTION CONTRACTORS 14795 SW 72" AVENUE D E LTA PORTLAND, OR 97224 PHONE: 503.620.4020 FIRE' INC. VVWW.DELTC B# 64174AFIRE.COh1 PIPE & FITTINGS FIRE PROTECTION CONTRACTORS pz i •i =WI i liNmiir i f ip. anew ma �M -_==INUk f'INUL'N !Pipe and Supply Corp. Pipe Specification A135 Specification A135 NPS 1/4 -- 30", Schedules 10, 40 and XL THD, Lightwall Scope Covers two grades of electric resistance welded steel pipe. Grade A is adapted for flanging and bending and is suitable for welding. Purpose for which pipe is intended should be stated on order. Kinds of Steel Permitted Open-hearth Basic-oxygen For Pipe Material Electric-furnace Permissible Variations The minimum wall thickness at any point shall not be more than 12.5%under the nominal wall thickness specified. in Wall Thickness Threadable,lightwall(XL)must meet manufacturers minimums. Chemical C max% Mn max% P max% S max% Requirements Seamless or ERW Grade A 0.25 0.95 0.05 0.06 Grade B 0.30 1.20 0.05 0.06 Tensile Grade A Grade B Requirements Tensile Strength,min.,psi 48,000 60,000 Yield Strength, min., psi 30,000 35.000 NDE& Hydrostatic inspection test pressures for plain end and threaded are specified. Hydrostatic pressure shall be maintained Hydrostatic for not less than 5 seconds for all sizes of electric resistance weld pipe. Non-destructive electric test should be in accordance Testing with practices E213,method E227 or practice E213. Permissible Variations Plus or Minus 10%schedule 10 in Weights per Foot Plus 10%minus 3 1/2%schedule 40 Permissible Variations Plus or minus 1% in Outside Diameter Mechanical Tests Tensile Test--Transverse returned on pipe NPS 8 and larger. Specified Flattening test--Three steps required with weld located 0°or 90°from the line of direction of force required. Number of Flattening and tensile on one length of pipe from each lot of 400 lengths or less of a style. Tests Required Lengths Pipe shall be furnished in 38'with a minimum of 20 ft. Pipe furnished to schedule 10 shall be in a specified length between 16 and 22 ft. Required Markings Rolled,Stamped or Stenciled(Mfgrs.Option) on Each Length Name or brand of manufacturer. (On Tags attached to Kind of pipe,that is,electric-resistance welded A,electric welded B,same schedule wall thickness,schedule 10 or 40,NL each Bundle in case ASTM A135 of Bundled Pipe) Length of pipe. General End finish may be plain end beveled or plain end square cut. Information PF Ductile Iron Threaded Fittings V ASC Engineered Solutions Fig. 3201 90° Elbow Material Specifications Dimensions:ASME B16.3 Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPTperASME B1.20.1 Agency Approvals:ALL ductile iron threaded fittings are UUULC Listed and FM Approved. .. cogs FM Note:Ductile iron fittings have highertensile strengththan LIST® APPROVED that of steel pipe.Therefore,over tightening can cause For Listings/Approval Details and Limitations,visit damage to pipe threads which may cause leakage.Ductile our websaeaww,w.asc—es.r°mor contact anASC iron fittings should be tightened approximately three turns Engineered solutions'sates Representative. beyond hand tight,but no more than four turns. Figure 3201 90° Elbow NominalSize Maximum Working Pressure Dimension A Approx Wt.Each A—rl In.(mm) psi(kPa) ---. In.(mm) Lbs.(kg) 1 500 1.50 0.62 20 3450 38.10 0.68 114 500 1.75 0.90 32 3450 44.45 0.41 A P/a 500 1.94 1.20 40 3450 49.276 0.54 i 2 500 2.25 1.85 50 3450 57.15 _ - 0.84 ♦—Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering Solutions°°'Representative. 0 scim An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3201-v0120220118 Ductile Iron Threaded Fittings ro ASC. ko./ Engineered Solutions Reducing 90° Elbow Fig. 3201R Material Specifications • Dimensions:ASME B16.3 • Material:ASTM A536 Grade 65-45-12 • Finish:Black //�`/// • Threads:NPT per ASME B7.20.1 i. • Agency Approvals:All ductile iron threaded fittings are UL/ULC Listed and FM Approved. Note:Ductile iron fittings have higher tensile strength than c©1R FM that of steel pipe.Therefore,over tightening can cause usiEV APPROVED damage to pipe threads which may cause leakage.Ductile For Dstings/Approval Details and Limitations,visit iron fittings should be tightened approximately three turns our websde atvmw.asc-exmm or contact an ASC beyond hand tight,but no more than four turns. Engineered Solutions"Sales Representative. Fig.3201R Reducing 90°Elbow Nominal Size Max.Working Dimensions Approx 1x2 Pressure A Wt.Each B n.imm) PSI(kPal __---In.(mm) In.(mm) Lbs.(kg) 1 x 1/2 500 1.26 1.36 0.44 25 x 15 3450 32.00 34.54 0.20 1 x 3/4 500 1.37 1.45 0.52 25 x 20 3450 34.79 36.83 0.24 i<-B --'- 11/, x l/2 500 1.34 1.53 0.64 32 x 15 34550 34.03 38.86 0.29 I 2 11/4 x 3/4 500 1.45 1.62 0.72 r-- 32 x 20 3450 36 83 41.14 1/ xi 500 1.58 1.67 0.75 i 32 x 25 3450 4013 42.41 0.34 A 1 1/ x 1/2 500 1.41 1.66 0.64 - 40 x 15 3450 35.81 42.16 0.29 1 I 1 X 2 11/2x3/4 500 ---- 1.52 1.75 0.77 --- 40 x 20 3450 38.61 44.45 0.35 11/2 x 1 500 1.65 1.80 0.92 40 x 25 3450 41.91 45.72 0.42 11/2 x 11/4 500 1.82 1.88 1.08 40 x 32 3450 46.22 47.75 0.49 2 x 1/2 500 1.49 1.88 1.08 50 x 15 3450 37.84 47.75 0.49 2 x Y4 500 1.60 1.97 1.24 50 x 20 3450 40.64 50.03 0.56 2 x 1 500 1.73 2.02 1.40 50 x 25 3450 43.94 51.30 0.64 2X1'/4 500 1.90 2.10 1.52 50 x 2x13 3450 48.22.02 53.341.0.65 SC I 2x11/z 500 2.02 2.16 1.65 50 x 40 3450 51.30 54.86 0.75 An ASC Engineered Solution ♦-Working Pressure Ratings are far reference only and based on Sch.40 pipe.For the latest UL/U LC,and FM pressure ratings versus pipe schedule,please visit www.asc-es.com or contact your local ASC Engineered Solutions",Representative. PROJECT INFORMATION APPROVAL STAMP Project: 0 Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/DI-11.21 page 1 PS-SUB-3201R-v01 2 0 21010 6 SPF Ductile Iron Threaded Fittings .. Engineered Solutions 45° Elbow Fig. 3202 Material Specifications Dimensions:ASME B16.3 '�`` Material:ASTM A536 Grade 65-45-12 �..,;,�, Finish:Black r,)ti Threads:NPT per ASME B1.20.1 Agency Approvals:All ductile iron threaded fittings are UL/ULC Listed and FM Approved. 'GIs FM tut® APPROVED Note Ductile iron fittings have higher tensile strength than - --- For ustags/Approvametails and um Rations,mit that of steel pipe.Therefore,over tightening can cause our websihatwwwasc-es.com or contact anASC damage to pipe threads which may cause leakage.Ductile Engineered Solutions-Sates Representative iron fittings should be tightened approximatelythree turns ------ beyond hand tight,but no more than four turns. Figure 3202 45° Elbow Nominal Size Maximum Working Pressure A Dimension A Approx Wt Each P In.(mm) psi(kPa) In.(mm) Lbs.(kg) 1 _ 500 1.12 0.46 25 3450 28.44 0.21 " 11/4 500 1.29 0.73 32 3450 32.76 0.33 1'/z .—_ _ _. 500 1.43_... __ 0.92 co 3450 36.32 0.42 I__ 2 500 1.68 1.50 I. 50 3450 42.67 0.68 A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC EngineeringSolutionsrm Representative. gill 5cr., An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ['Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3202-v0120220118 SPF Ductile Iron Threaded Fittings r) Asc / Engineered Solutions Straight Tee Fig. 3205 Material Specifications Dimensions:ASME B16.3 Material:ASTM A536 Grade 65-45-12 - Finish:Black Threads:NPT perASME B1.20.1 Agency Approvals:All ductile iron threaded fittings are UL/ULC Listed and FM Approved. Note:Ductile iron fittings have higher tensile strength than that of steel pipe.Therefore,over tightening can cause damage to pipe threads which may cause leakage.Ductile cas pM iron fittings should be tightened approximately three turns LISTED APPROVED beyond hand tight,but no more than four turns. For listings/Approval Details and limitations.visit our web site at www.asc-es.com or contact an AS( Engineered Solutions Sates Representative. ..... .............._ _...-.. Figure 3205 Straight Tee Nominal Size Maximum Working Pressure A Dimension A Approx Wt.Fach In.(mm) psi(kPa) In.(mini -_.. Lbs.(kg) 1 500 _ 1.50 - 85 500 25 3450 38.10 0.39 A - 1/4 1.22 0.55 32 -- - 3450 41745 - -----r----- — - -- 500 1.94 1.55 -.-40 3450 927 0.70 I--Ash—A-.I 2 500 2.25 2.45 50 3450 57.15 111 A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering SolutionsT"Representative. • 5C10 An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3205-v01 2 022 0118 SPF Ductile Iron Threaded Fittings It) ASC Engineered Solutions Reducing Tee Fig. 3205R Material Specifications Dimensions:ASME B16.3 Material.:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPT per ASME 61.20.1 Agency Approvals:All ductile iron threaded fittings ", are UL/ULC Listed and FM Approved. c lIt us O Note:Ductile iron fittings have higher tensile strength than that of steel pipe.Therefore, LISTED APPROVED over tightening can cause damage to pipe threads which may cause leakage.Ductile iron For Listings/Approval Derails and limitations,visit fittings should be tightened approximately three turns beyond hand tight,but no more our website atwww.asc-es.cam or contact an ARC than four turns. Engineered Solutions Sales Representative. Figure 3205R Reducing Tee :-.1- C 1--- 2 Nominal Size Maximum Dimensions Working Approx Wt. B tx2x3 Pressure A g C Each 1-- 1, 3 In.(mm) psi(kPa) In.(mm) In.(mm) In.(mm) Lbs.(kg) t 1x1/2x1 500 1.50 1.36 1.50 0.64 A 1 25 x 15 x 25 3450 38.10 3454 38.10 0.29 I_ 1x2x3 1 x 3/a x 1 500 1.50 1.45 1.50 0.73 25 x 20 x 25 3450 38.10 36.83 38.10 0.33 1 x 1 x 1/2 500 1.26 1.26 1.36 0.71 25 x 25 x 15 3450 32.00 32.00 34.54 0.32 Figure 3205R Reducing Tee 1 x 1 x 34 500 1.37 1.37 1.45 0.76 25 x 25 x 20 3450 34.80 34.80 36.83 0.34 - -- --- Nominal. Maximum l x 1 x 114" 500 1.67 1.67 1.58 0.98 Size Dimensions 25 x 25 x 32 3450 42.41 42.41 40.13 0.44 Working _._- _ __ _.. Approx 1 x 2 x 3 Pressure A A B C Wt.Each 1 x 1 x 11/2" 500 1.80 1.80 1.65 136 25 x 25 x 40 3450 45.72 45.72 41.91 0.53 In.(mm) psi(kPa) In.(mm) In.(mm) In (mm) lbs.(kg) 11/a x 1 x'/z" 500 1.34 1.26 1.53 0.82 114 x 11/a x 3/a 500 1.45 1.45 1.62 0.92 32 x 25 x 15 3450 34.04 32.00 38.86 0.37 32 x 32 x 20 3450 36.83 36.83 41.15 0.42 1/ax1x3 500 1.45 1.37 1.62 0.90 11/a x1 1/a x1 500 1.58 1.58 1.67 0.95 32 x 25 x 20 3450 36.83 34.80 41.15 0.41 32 x 32 x 25 3450 40.13 40.13 42.42 0.43 14 x 1 x 1 500 1.58 1.50 1.67 1.00 1/x P 4 x 1 2" 500 1.88 1.88 1.82 1.45 32 x 25 x 25 3450 40.13 38.10 42.42 0.45 32 x 32 x 40 3450 47.75 47.75 46.22 0.66 11/4x 1 x 11/4 500 1.75 1.67 1.75 1.08 32 x 25 x 32 3450 44.45 42.42 44.45 0.49 13/4 x 1 x 1/ 500 1.88 1.80 1.82 1.42 -2 x 25 x 40 3450 47.75 45.72 46.22 0.64 4 x Y x Y 500 1.34 1.34 1.53 0.86 r 32 x i5 3450 34.04 34.04 38.86 0.39 re A Workingg Pressure Ratings are for reference only and based on Sch.40 pipe.For the Latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or SC'® contact your local ASC Engineering Solutions" Representative. An ASC Engineered Solution "Part supplied as"Bull Head Tee". PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor. ❑Not approved Engineer: -Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3205R-v0120220202 SPF Ductile Iron Threaded Fittings 1111141440001.11r) Engineered Solutions Reducing Tee Fig. 3205R c f 2 B T 3 l j 1 1x2x3 Figure 3205R Reducing Tee Figure 3205R Reducing Tee Nominal -- - ----- Size Maximum Dimensions Nominal Maximum Dimensions Working APProx Wt. Size Work pPProx Wt. 1x2x3 Pressure♦ - - Each g A B 1 x 2 x 3 Pressure♦ A B Each In.(nwm) psi(kPa) Ir.(mm) In.(mm) In.(mm) Lbs.(kg) In.(mm) psi(kPa) In.(mm) In.(mm) In.(mm) Lbs.(kg) P/a x 1'/4 x 2* 500 2.10 2.10 1.90 1.75 11/2 x 1Y x 2* 500 2.16 2.16 2.02 1.98 32 x 32 x 50 3450 53.34 53.34 48.26 0.79 40 x 40 x 5D 3450 54.86 54.86 51.30 0.90 11 x 1 x 1/2 500 1.41 1.34 1.66 0.95 2 x 1 x 2 500 2.25 2.02 2.25 2.15 40 x 25 x 15 3450 35.81 34.04 42.16 0.43 50 x 25 x 50 3450 57.15 51.31 57.15 0.98 11/2x1x3/4 500 1.52 1.37 1.75 1.14 2x1'/4x2 500 2.25 2.10 2.25 2.30 40 x 25 x 20 3450 38.61 34.80 44.45 0.52 50 x 32 x 50 3450 57.15 53.34 57.15 1.04 11/2x1x1 500 1.65 1.50 1.80 1.17 2x11/2x1/2 500 1.49 1.41 1.88 1.50 40 x 25 x 25 3450 41.91 38.10 45.72 0.53 50 x 40 x 15 3450 37.85 35.81 47.75 0.68 11/2x1x1% 500 1.82 1.67 1.88 1.34 2x11/2x3/4 500 1.60 1.52 1.97 1.62 40 x 25 x 32 3450 46.23 42.42 47.75 0.61 50 x 40 x 20 3450 40.64 38.61 50.04 0.73 11x1x11/2 500 1.94 1.80 1.94 1.45 2x11/2x1 500 1.73 1.65 2.02 1.64 40 x 25 x 40 3450 49.28 45.72 49.28 0.66 50 x 40 x 25 3450 43.94 41.91 51.31 0.74 11/2x14x1/2 500 1.41 1.34 1.66 1.05 2x11/zx111A 500 1.90 1.82 2.10 1.80 40 x 32 x 15 3450 35.81 34.04 42.16 0.48 50 x 40 x 32 3450 48.26 46.23 53.34 0.82 11/2x114x34 500 1.52 1.45 1.75 1.15 2x11/2x11/2 500 2.02 1.94 2.16 2.00 40 x 32 x 20 3450 38.61 36.83 44.45 0.5 50 x 40 x 40 • 3450 51.31 49.28 54.86 0.91 12x11/4x1 500 1.65 1.58 1.80 1.25 2x11/2x2 500 2.25 2.16 2.25 2.35 40 x 32 x 25 3450 I 41.91 40.13 45.72 0.57 50 x 40 x 50 3450 57.15 54.86 57.15 1.07 11/2 x 114 x 2* 500 2.16 2.10 2.02 - 1.90 2 x 2x Y 500 1.49 1.49 1.88 1.60 40 x 32 x 50 3450 54.86 53.34 51.30 0.86 50 x 50 x 15 3450 37.85 37.85 47.75 0.73 11/2 x 11/2 x 1/2 500 1.41 1.41 1.16 1.15 2 x 2 x 3/4 -_ -- __- -- -- _- _-1-_ -- 500 1.60 1.60 1.97 1.68 4 0 x 40 x 15 3450 35.81 35.81 29.46 0. 0 52 50 x 50 x 20 3450 40.64 40.64 50.04 0.76 11/2 x 11/2 x 34 500 152 1.52 1.75 1.24 2 x 2 x 1 500 1.73 1.73 2.02 1.85 40 x 40 x 2D 3450 38.61 38.61 11.45 0.56 50 x 50 x 25 3450 43.94 43.94 51.31 0.84 11/2 x 11/2 x 1 500 1.65 1.65 1.80 1.30 2 x 2 x 11/4 500 1.90 1.90 2.04 40 x 40 x 25 3450 41.91 41.91 45.72 0.59 50 x 50 x 32 3450 44.45 42.42 44.45 0.93 1/2x11/2x11/4 500 1.82 1.82 1.88 1.48 2x2x11/2 500 2.02 2.02 2.16 2.18 40 x 40 x 32 3450 46.23 46.23 47.75 0.67 50 x 50 x 40 3450 44.45 42.42 44.45 0.99 A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering SoLutions'm Representative. 'Part supplied as"Bull Head Tee". 4111 SCL An ASC Engineered Solution SPF/MI-1.15 page 2 P5-SUB-3205R-v0120220202 SPF Ductile Iron Threaded Fittings r(j) ASC 411411114000110111 --- Engineered Solutions Coupling Fig. 3221 Material.Specifications Dimensions:ASME B16.3 Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPT per ASME B1.20.1 Agency Approvals:All ductile iron threaded fittings are UL/ULC Listed and FM Approved. Note:Ductile iron fittings have higher tensile strength than that of steel pipe.Therefore,over tightening can cause o UL vs O damage to pipe threads which may cause Leakage.Ductile lIBT® APPROVED iron fittings should be tightened approximately three toms mval Details one❑mitabnn:,visa beyond hand tight,but no more than four turns. rartisnngstspp our webs ite at www.a$-es.com or contact an AS[ Engineered Solutions"Sales Representative Figure 3221 Coupling Nominal Size Maximum ------------------- Working pressures DimensionA Approx Wt Each n In.(mm) psi(kPa)_-_-- In.(mm) Lbs.(kg) Fi 1 500 1.67 0.40 25 3450 42.42 0.18 lW4 500 1.93 0.57 32 3450 49.02 0.26 (11-N P/z 500 40 2.15 0.75 3450 54 61 0.34 I 2 500 2.53 1. 64.26 50 3450 1.5 0.52 ♦-Working Pressure Ratings are far reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local A5C Engineering Solutionsn"Representative. • 5(1. An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ['Approved Address: 0 Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3221-v01 20220118 SPF Ductile Iron Threaded Fittings aril) . Engineered Solutions Reducing Coupling Fig. 3221R Material Specifications Dimensions:ASME B16.3 - Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPTperASME B1.20.1 Agency Approvals:All ductile iron threaded c@us FM fittings are UL/ULC Listed and FM Approved. Laren APPROVED Note:Ductile iron fittings have higher tensile strength than For Listings/Approval Details and Llmdadia o ,via S gC aurwehsite at www.ax-esmmorcontact an ASC that of steel pipe.Therefore,over tightening can cause Engineered Solutions'Sates Representadve. damage to pipe threads which may cause leakage.Ductile iron fittings should be tightened approximately three turns beyond hand tight,but no more than four turns. Figure 3221R Reducing Coupling Nominal Size Maximum Working Pressure Dimension A Approx Wt.Each In.(mm) psi(kPa) In.(mm) Lbs.(kg) P 't' + 'a, 1 x).6 500 1.69 25 x 15 0.39 m 1 > A 3450 42.92 018 � 1x34 500 1.69 0.53 ' .-°rt 25 x 20 3450 42.92 0.24 13/4 x 4 500 2.06 0.64 32 x 20 3450 52.32 0.29 ♦-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your Local ASC Engineering Solutionr^Representative. elSCL An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ['Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3221R-v012022011B SPF Ductile Iron Threaded Fittings L.fli AA6C. ikkt . :,. Engineered Solutions Cross Fig. 3207 Material Specifications Dimensions:ASME B16.3 Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPT per ASME B1.20.1 Agency Approvals:All ductile iron threaded fittings are UL/ULC Listed and FM Approved. Note:Ductile iron fittings have higher tensile strength than that of steel pipe.Therefore,over tightening can cause c UL us rm damage to pipe threads which may cause leakage.Ductile LISTED APPROVED iron fittings should be tightened approximatelythree turns For Listings/Approval Detaik and Limitations,nisi[ beyond hand tight,but no more than four turns. our website at www.asc-es.com or contatt LEASE Engineered Solutions Safes Representative. Figure 3207 Cross Nominal Size Maximum Dimension A r A—''—A l Working Pressure♦ pp ox Wt.Each } ,,. In.(mm) __.. psi(kPa) In.(mm) Lbs.(kg) 1 500 1.50 0.98 A 25 3450 38.10 0.44 _-- - 1Y4 500 1.75 1.50 32 3450 44.45 068 A 1Y2 500 1.94 1.90 y 40 3450 49.27 0.86 2 500 2.25 2.95 50 3450 57.15 1.34 •-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UUULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering Solutionsrm Representative. 11311 5(1® An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ID Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUe-3207-v0120220118 SPF Ductile Iron Threaded Fittings IL0) ASC. Engineered Solutions Reducing Cross Fig. 3207R MateriaL Specifications Dimensions:ASME B16.3 Material:ASTM A536 Grade 65-45-12 Finish:Black a_ Threads:NPTperASME B1.20.1 Agency Approvals:All ductile iron threaded '1 fittings are UL/ULC Listed and FM Approved. C 'fL US FM usr® APPROVED Note:Ductile iron fittings have higher tensile strength than For LetingsApproval Details and umnations,vim that of steel pipe.Therefore,over tightening can cause ourwebme atwww.asr-escom or contact an ASC damage to pipe threads which may cause leakage.Ductile Engineered Sowbonr'Sales Representative iron fittings should be tightened approximately three turns beyond hand tight,but no more than four turns. Figure 3207R Reducing Cross Nominal Size Max. Dimensions WorkingAPProx Wt.Each ,—B 1xlx2x2 Pressure - - BSI 1 A B + n.(mm) ps(k Pa) In.(mm) ... In.(mm) Lbs.(kg) A 2—}-2 1Yax1Yexlx1 500 1.58 - 32 x 32 x 25 x 25 3450 40.13 4.41 .57 0.58 A 1 viz x1'/zxlx1 500 1.65 1.80 1.48 1 x1 x2x2 40 x 40 x 25 x 25 3450 41.91 45.72 0.67 2x2x1x1 500 1.73 2.02 2.10 50 x 50 x 25 x 25 3450 43.94 51.30 0.95 A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering Solutions'Representative. 1311 5cr An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SU8-3207R-v0120220118 SPF Ductile Iron Threaded Fittings (0). . ., ^-/ Engineered Solutions Bushings .. Fig. 3283 Material Specifications Dimensions:ASME B16.14 Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPT perASME B1.20.1 Agency Approvals:All ductile iron threaded fittings are UL/ULC Listed and FM Approved. _.. c us FM Note:Ductile iron fittings have higher tensile strength than ustm APPROVED that of steel pipe.Therefore,over tightening can cause - For Listings/Approval Detaiu and Limitations,visit damage to pipe threads which may cause leakage.Ductile our website at www.asc-es.com or contact an ASC iron fittings should be tightened approximatelythree turns Engineered Solutions Sates Representative. beyond hand tight,but no more than four turns. Figure 3283 Bushings Nominal Size Maximum Dimensions [4-C-.I Male(M)x Working _.. __ - Style Approx Wt. I t� Female(F) Pressure A A B C Each F )■�® B In.(mm) psi(kP0) In (mm) In.(mm) In.(mm) - Lbs.(kg) A 1x1 500 0.75 0.25 1.42 0.22 M- 25 x 15 c 6 35 36.06 Outside 0.10 x a 500 0.75 0.25 1.42 0.17 Inside Head 25 x 20 3450 03 6.35 36.06 Outside 0.08 11/4 x 1 500 0.80 0.28 1.76 0.28 32 x 25 3450 20.32 7.11 44.70 Outside 013 11/2 x 1 500 0.83 0.31 2.00 0.45 V C�1 40 x 25 3450 2108 7.874 50.80 Outside 0.204. 11/2 x P/a 500 0.83 0.31 2.00 0.30 F-M11iiiii1.1. -B 40 x 32 3450 21.08 7874 50.80 Outside 014 2 x 1 500 0.88 0.41 1.95 A 50 x 25 3450 22.35 10.414 49.43 Inside 0.67 0.30 M- 2 x P/e 500 0.88 0.34 2.48 0.73 _ 50 x 32 3450 22.35 8.636 62.99 Outside 0.33 Outside Head 2 x 1 1 500 0.88 0.34 2.48 60 x 40 3450 22.35 8.636 62.99 Outside 0.61 0 28 ♦-Working Pressure Ratings are for reference onty and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering Solutionsn Representative. SCL An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ['Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3283-v01 20220118 SPF Ductile Iron Threaded Fittings V MC.. Engineered Solutions Cap Fig. 3224 Material Specifications Dimensions:ASME 616.3 Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPT per ASME B1.20.1 Agency Approvals:All ductile iron threaded s 4t ut PM fittings are UL/ULC Listed and FM Approved. ._r ustm APPROVED Note Ductile iron fittings have higher tensile strength than Far ustingaApprn 1 Details and Limitations,vist that of steel pipe.Therefore,over tightening can cause our website at www.asc-es.com or contact an A5C Engineered Solutions'sates Representative. damage to pipe threads which may cause leakage.Ductile iron fittings should be tightened approximately three turns beyond hand tight,but no more than four turns. Figure 3224 Cap Nominal Size Maximum -- Working Pressure A Dimension A Approx Wt Each In.Inn) psi(kPa) In.(mm) Lbs.(kg) 1 • SDO 116 0.32 25 — 3450 _ 29.46 0.15 A 11/4 500 1.28 0.40 32 3450 32.51 0.20 1V 500 1.33 0.60 40 3450 33.78 0.27 2 500 1.45 0.91 50 0.41 3450 36.83 ♦-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering Solutions""Representative. 41 SCI,s An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 P5-SUB-3224-v0120220118 SPF Ductile Iron Threaded Fittings eC, . Engineered Solutions Cored Plug Fig. 3388 Material Specifications Dimensions:ASME B16.14 Material:ASTM A536 Grade 65-45-12 Finish:Black Threads:NPT perASME B1.20.1 Agency Approvals:All ductile iron threaded fittings are UUULC Listed and FM Approved. ♦Pressure-Temperature Ratings in accordance with '," ASME B16.3 Class 150 ''. c©L us O Note Ductile iron fittings have higher tensile strength than IBtED APPROVED that of steel pipe.Therefore,over tightening can cause For usengs/ApprovalDetaits and umltadons,visit damage to pipe threads which may cause leakage.Ductile ourwebsite atwww.asc-es.com or contact a,nsc iron fittings should be tightened approximatelythree turns Engineered SoWWtioni Sales Representative. beyond hand tight,but no more than four turns. Figure 3388 Cored Plug Nominal Size Maximum Approx. Working Pressure♦ DimensionA W ach In.(mm) psi(kPa) In.(rim) Lbs.(kg) 5 500 0.94 0.10 13450 23.87 0.05 MI t /< 500 1.07 20 3450 008 27.17 0.08 IA 1 500 1.25 i 25 3450 0.28 31.75 0.13 1b 500 32 1.36 0.44 3450 34.54 0.20 1Yz 500 401.45 0.62 3450 36.83 0.28 2 500 1.56 0.41 50 3450 39.62 0.41 A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,and FM pressure ratings versus pipe schedule,please visit asc-es.com or contact your local ASC Engineering SolutionsT"Representative. 'Part supplied as Solid Plug. SCL An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: ❑Approved Address: ❑Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/MI-1.15 page 1 PS-SUB-3388-v0120220124 FireLock' Outlet-T ✓ctaulrc' Style 922 10.52 • 1.0 PRODUCT DESCRIPTION Available Sizes • 11/4- 21/2"/DN32— DN65 • Threaded Outlet Sizes: 'h"/DN15, 3/4"/DN20, and 1"/DN25 NOTE • IGS Grooved 1'/DN25 Outlets available for this product.See publication 10.54. Maximum Working Pressure • 300 psi/2068 kPa/21 Bar Application • Provides a convenient method of incorporating outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and other outlet products Pipe Material • Carbon steel • Contact Victaulic for use on additional pipe types and wall thicknesses 2.0 CERTIFICATION/LISTINGS cOus ® VdS -LPct `L UK aP PISTED APPRALD CA LPS 1186. EN 10311 BS EN 10311 Issue 3.1 CPR(EU) CPR(UK) Cert/LPCB Ref. No.305/2011 2019 No.465 491a/27 NOTES • See Section 7.2 REFERENCE MATERIALS for additional certification information. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • victaulic.com ln en O9FC o....I i i..,r.,.,.A nl,••nao �nm v,,..., I victaulic.com 3.0 SPECIFICATIONS - MATERIAL Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12. Ductile iron conforming to ASTM A395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ❑ Orange coating. ❑ Red coating (standard for EMEA-I and Asia Pacific). ❑ Optional: Contact Victaulic with your requirements for other coatings. ❑ Optional: Hot dipped galvanized. Gaskets: ❑ Grade "E" EPDM (Type A) EPDM (Violet color code) Applicable for wet and dry(oil-free air) sprinkler services only. Listed/Approved for continuous use in wet and dry systems. Listed/Approved for dry systems at -40°F/-40°C and above. NOT COMPATIBLE FOR USE WITH HOT WATER SERVICES OR STEAM SERVICES. Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: ❑ Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (metric). Carbon steel hex flange nuts meeting the mechanical property requirements of ASTM A563 Grade B (imperial — hex nuts) and ASTM A563M Class 9 (metric— hex nuts). Track bolts and hex flange nuts are zinc electroplated per ASTM B633 Fe/Zn 5, finish Type III (imperial) or Type II (metric). • 10.52 3355 Rev L Updated 01/2023 ®2023 Victaulic Company.All rights reserved. DELTA PORTLAND, OR 97224 PHONE: 503.620.4020 FARE, INC. CC# 64174AFIRE.COM HANGERS FIRE PROTECTION CONTRACTORS Threaded Accessories B3205 -Threaded Rod (right-hand threads - both ends) B3205L- Threaded Rod (right & left hand threads) TL Size Range: 3/8" 16 thru 3"-4 rod Specify Length \l�1��1 �� Material: Steel Function: Recommended for use as a hanger support in hanger assemblies. TL „l�l�� oth available with Rod is ed on left and right ends with threadsh specify Fig. B3205L and threads of the when shown.th Also �111)0)ll' A hread Size Maximum Temperature: 750°F hread) Finish: Plain. Contact customer service for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205-3/8 x'L' 3/8"-16 21/2" (63.51 730 (3.25) 572 12.54) B3205-1/2 x'L' 1/2"-13 21/2' (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 x'L' 3/4"-10 3" (76.2) 3230 114.37) 2530 (11.25) B3205-7/ax'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205.1 x'1' 1"-8 4" 1101.6) 5900 (26.24) 4620 (20.55) B3205-11/8x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) 83205.11/4x'L' 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2 x'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) B3205-13/4 x'L' 13/4"-5 7" (177.6) 18600 (82.73) 14566 (64.79) B3205-2x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) B3205-21/4 x'L' 21/4%41/2 9" (228.61 32300 (143.67) 25295 (112.51) B3205-21/2 x'L' 21/2"-4 10" (254.0) 39800 (177.031 31169 (138.64) 133205-23/4x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3x'L' 3"-4 12' (304.8) 60100 (267.32) 47066 (209.351 ATR -All Threaded Rod 120" (3.05m) Lengths Fig. 99 - All Threaded Rod Cut To Length Size Range: 3/8"-16 thru 11/2"-6 rod in 120" 13.05m1 lengths or cut to lengthA101 9 *91 Material: Steel ,y~,.,_ Maximum Temperature: 750°F (399°C) ' ~" "" Finish: Plain. Contact customer service for alternative finishes and materials15� W Order By: Part number, rod diameter and finish o W N W d Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) F ci ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/e"x 120 99-3/8"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 5/8"x 120 99-5/e"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/e"x 120 99-1/8"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.061 ATR 11/8"x 120 99-11/8"x length 7 7450 (33.14) 280 (127.01) ATR 11/4"x 120 99-11/4"x length 7 9500 (42.25) 351 (159.21) ATR 11/2"x 120 99-11/2"x length 6 13800 (61.38) 510 (231.33) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in mill'meters unless otherwise specified. B-Line series Pipe Hangers &Supports - -251 Eaton 14795 SW 72"AVENUE DELTA PORTLAND, OR 97224 PHONE: 503.620.4020 FIRE' INC. WWW.DELTCCB# 64174AFIRE.COM SPRINKLER HEADS FIRE PROTECTION CONTRACTORS Bulletin 074 January 2023 FIFR56 Series Reliableo Quick Response Sprinklers K-factor 5.6(80) Features • Standard coverage quick-response sprinklers • Upright, pendent,horizontal sidewall,and vertical sidewall i deflectors • Low profile,compact design • Available in a wide variety of finishes t - Product Description Model F1FR56 Pendent Model F1 FR56 Upright Reliable Model F1FR56 series sprinklers are quick-response standard spray automatic fire sprinklers utilizing a sensitive 3.0 mm glass bulb thermal element. Pendent and horizontal sidewall sprinklers may be installed A i eie 3 ir r exposed or surface mounted using escutcheons such as the Reliable Models B, C, or HB(reference Technical Bulletin 204). When installed recessed or concealed,the Model F1 FR56 series - sprinklers are specifically listed with and may only be installed with listed Reliable escutcheons and cover plates. Refer to the Model Fl FR56 Vertical Sidewall Model F1FR56 technical information on the following pages for specific listings Horizontal Sidewall for recessed and concealed installations and refer to Figures 5 and 6 for dimensional information. Note:Not all versions of the product are shown. When fitted with an approved water shield, these sprinklers may considered intermediate sprinklers for use in racks, below grated walkways, and other areas where intermediate level sprinklers are required. Note:This bulletin may contain information on New and Legacy Table A provides a summary of the approvals and availability of sprinklers that reflects a dimensional change only.Sprinkler Iden- specific Model F1 FR series sprinkler configurations.Additional aptiproval tion Numberrenot (SIN), application, Sprinklers with and listings/am technical information for each sprinkler model is provided on the approval are the suffix otherwise affected. Sprinklers New frames following pages. will include "N"in the order. F1FR Series Sprinklers Summary Sprinkler K-Factorgpm/psi'i' Max.Working Pressure Sprinkler Model (Ipm/bar'n) Orientation Listings&Approvals Identification psi(bar) Number(SIN) Upright cULus, FM,LPCB,VdS, 175(12) RA1425 Intermediate Upright EC,WM,UKCA 250(17)(cULus only) Pendent cULus,FM, LPCB,VdS, 175(12) RA1414 EC,WM,UKCA 250(17)(cULus only) F1FR56 5.6(80) Concealed Pendent cULus,VdS,EC,WM, 175(12) RA1414 UKCA 250(17)(cULus only) Horizontal Sidewall cULus,FM 175(12) RA1435 250(17)(cULus only) Vertical Sidewall cULus,FM,LPCB, 175(12) RA1485 UKCA www.reliablesprinkler.com Model F1FR56 Upright Sprinkler SIN RA1425 Technical Specifications Guards&Shields(New Frames) Style:Upright,Intermediate Upright Factory Water Shield(cULus,FM) Threads: 1/2"NPT or ISO 7-R1/2 F-1 Guard(cULus,FM) Nominal K-Factor:5.6(80 metric) F-3 Guard with Shield(cULus, FM) Max.Working Pressure: 175 psi(12 bar) Guards and Shields(Legacy Frames) 250 psi(17 bar)(cULus only) Factory Water Shield Material Specifications C-1 Guard(FM) Thermal Sensor:3 mm Glass Bulb C-3 Guard with Shield(cULus,FM) Sprinkler Frame:Brass Alloy D-3 Guard with Shield(cULus) D-1 Guard(cULus) Cap:Bronze Alloy ill Sealing Washer:Nickel with PTFE Sprinkler Wrench Load Screw:Copper Alloy Model W2 Deflector:Brass Alloy Model J(New frame with guard installed) Model JD(Legacy frame with guard Sprinkler Finishes installed) (See Table B) Listings and Approvals ' Sensitivity cULus Listed ' Quick response FM Approved LPCB Temperature Ratings VdS 135°F(57°C) EC 155°F(68°C) EC 175°F(79°C) WM 200°F(93°C) UKCA:0832-UKCA-CPR-S5045 286°F(141°C) Model Fl FR56 Upright Sprinkler Components and Dimensions Figure 1 31/4"[83mm] Load Screw 1 3/8"[33mm] Deflector IN gli Glass Bulb (3 mm) F1F�HgLF-UPR JNr Wrench Flat r4ii 'A� . _ . 2 1/4"[58mm] 1 'C I 6A:-® Threads Cap/Seal Assembly Shown with Optional Factory Installed Water Shield (Intermediate Upright) Bulletin 074 January 2023 Reliable www.reliablesprng ercom Model F1FR56 Pendent Sprinkler SIN RA1414 Technical Specifications Recessed Escutcheons Style: Model F1 (cULus,LPCB,VdS,CE,WM) Pendent Model F2(cULus,FM,LPCB,VdS,CE, Recessed Pendent WM) Concealed Pendent Model FP(cULus,VdS,CE,WM) Threads: 1/2"NPT or ISO 7-R1/2 Nominal K-Factor:5.6(80 metric) Cover Plate Max.Working Pressure: Model CCP(cULus,VdSi2j, CEP2)) 175 psi(12 bar) 250 psi(17 bar)(cULus only) Guards&Shields(New Frames)t') • Material Specifications F-1 Guard(FM) • Thermal Sensor:3 mm Glass Bulb F-5 Guard/Shield Kit(FM) • Sprinkler Frame:Brass Alloy F-7 Guard(cULus) • Cap:Bronze Alloy F-8 Guard/Shield Kit(cULus) Sealing Washer:Nickel with PTFE S-1 Shield(cULus,FM) Load Screw:Co pper Alloy Guards&Shields(Legacy Frames)i3l Deflector:Brass Alloy C-1 Guard(FM) f Sprinkler Finishes C-5 Guard/Shield Kit(FM) (See Table B) D-1 Guard(cULus,FM) + ` Sensitivity D-4 Guard/Shield Kit(FM) Quick response D-5 Guard/Shield Kit(cULus,FM) S-1 Shield(cULus,FM) Temperature Ratingst'l Sprinkler Wrenches 135°F(57°C) Model W2(pendent) 155°F(68°C) Model W4(recessed or concealed) 175°F(79°C) Model J(New frame with guard installed) 200°F(93°C) Model JD(Legacy frame with guard 286°F(141°C) installed) Listings and Approvalsl'i cULus Listed FM Approved LPCB VdS EC WM UKCA:0832-UKCA-CPR-S5045, 0831-UKCA-CPR-5072(CCP) Notes: 1. 286°F(141°C)temperature rated sprinkler not listed for recessed or concealed use. 2. VdS and CE approval for CCP concealed use is for 155°C(68°C)sprinkler ONLY. 3. Not suitable for recessed or concealed pendent installations. 4. When used surface mounted or exposed.See Recessed Escutcheon and Cover Plate section for specific approvals when installed recessed or concealed. Model Fl FR56 Pendent Sprinkler Components and Dimensions Figure 2 3 1/4"[83mm] Threads10 01%111 F1FR-NFLF PENT INT Wrench Flat ' q j 2 1/4"[57mm] ` Cap/Seal Glass Bulb Assembly 111 (3 mm) Deflector Load Screw --�I 1"[25mm] -.— Shown with Optional S-1 Water Shield(Ordered Separately) Note: Please refer to Figure 8 for recessed and concealed installation. Bulletin 074 January 2023 Reliable Page 3 of 9 www.reliablesprin kleccom Model F1 FR56 Horizontal Sidewall Sprinkler SIN RA1435 Technical Specifications Recessed Escutcheonsc) Style: Model Fl (cULus) Horizontal Sidewall Model F2(cULus,FM) Recessed Horizontal Sidewall Model FP(cULus) Threads: 1/2"NPT or ISO 7-R1/2 Nominal K-Factor:5.6(80 metric) Guards&Shields(New Frames)3 Max.Working Pressure: F-4 Guard(FM) 175 psi(12 bar) F-7 Guard(cULus) 250 psi(17 bar)(cULus only) Guards&Shields(Legacy Framesy3) Material Specifications C1 Guard(FM) Thermal Sensor:3 mm Glass Bulb D1 Guard(cULus) Sprinkler Frame:Brass Alloy Cap: Bronze Alloy Sprinkler Wrenches Sealing Washer:Nickel with PTFE Model W2(non-recessed) Model W4(recessed) Load Screw:Copper Alloy Model J(New frame with guard installed) Deflector:Brass Alloy Model JD(Legacy frame with guard installed) Sprinkler Finishes (See Table B) Listings and Approvals Sensitivity cULus Listedf6) Quick response FM Approved(5) Temperature Ratings 0) 135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) 286°F(141°C) Notes: 1. 286°F(141°C)temperature rated sprinkler not listed for recessed use. 2. FM approved recessed installation when used with Model F2 escutcheon ONLY. 3. Not suitable for recessed horizontal sidewall installations. 4. cULus Listed for Light and Ordinary Hazard when installed exposed or surface mounted. Listed for Light Hazard ONLY when installed recessed. 5. FM Approved for Light Hazard ONLY. Model F1 FR56 Horizontal Sidewall Sprinkler Components and Dimensions Figure 3 1 1/8" [28mm] Deflector Load Screw - III ,�I'I Frame III „ II Glass Bulb c4 2 3/4"[70mm] (3 mm) pl. FIFR HALF_HSW =_. Wrench Flat _— Cap/Seal Assembly Threads Note:Please refer to Figure 9 for recessed installation. Bulletin 074 � January 2023 Page 4 of 9 www.reliablesprinkler.com Model F1 FR56 Vertical Sidewall Sprinkler SIN RA1485 Technical Specifications Guards&Shields(New Frames) Style: F-2 Guard(FM) Upright Vertical Sidewall Pendent Vertical Sidewall Guards&Shields(Legacy Frames) Threads: 1/2"NPT or ISO 7-R1/2 C1 Guard(FM) Nominal K-Factor:5.6(80 metric) Max.Working Pressure: 175 psi(12 bar) Sprinkler Wrenches Model W2 Model J(New frame with guard installed) Material Specifications Model JD(Legacy frame with guard Thermal Sensor:3 mm Glass Bulb installed) 4 Sprinkler Frame:Brass Alloy Cap:Bronze Alloy Sealing Washer:Nickel with PTFE Listings and Approvalsl'1 Load Screw:Copper Alloy FM Ap Listed Deflector:Brass Alloy FM Approved LPCB(2) Sprinkler Finishes UKCA:0832-UKCA-CPR-S5045 (See Table B) Sensitivity Quick response Temperature Ratings 135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) 286°F(141°C) Notes: 1. Listed and approved for Light Hazard ONLY. 2. LPCB approved for use in pendent position ONLY. Model F1 FR56 Vertical Sprinkler Components and Dimensions Deflector Load Screw 1 1/2"[38mm] �I I Frame ;■ Glass Bulb - (3 mm) F1FR HALF_VSW 2 1/4"[57mm] Pi RA'CO Wrench Flat Cap/Seal Assembly Threads Bulletin 074 January 2023 Reliable Page 5 of 9 www.reliablesprinkler.com Recessed and Concealed Installation:Pendent Sprinklers Figure 5 2-1/4" (57 mm)Dia. 2-1/4" Hole in Ceiling (57 mm)Dia. Hole In Ceiling 1-15/16" (49 mm)Dia. 1-15/16" (49 Reducing mm)Dia. Fitting Reducing Fitting Face of Fitting to Face of Ceiling Face of Fitting 1-1/8'(29 mm)at to Face of Ceiling Max.Recess 7/e"(22 mm)at ! 3/e'(10 mm)at Max.Recess 3/8'Min.Recess ��� Min.(10 ess at r Min.Recess i r 1-3/4" 14" —t�� .. (44 mm) 1•• (25 mm) (�mm) 1-1/4" + Al (32 mm) Minimum ----`----"' Maximum Minimum Recess �2-7/8"(72 mm)Dia.--.- Recess Recess 2-7/8"(72 min)Dia. Maximum Recess Models F1&F1 FR Pendent Sprinkler Models Fl&F1FR Pendent Sprinkler with Model Ft Recessed Escutcheon with Model F2 Recessed Escutcheon 3/4"(19mm)Nominal Adjustment 1/2"(13mm)Nominal Adjustment Fr_Rec PEA cCP 2-1/2" (64 mm)Dla. 2-1/2" (64Hole in Ceiling ole in C Dia. 2-5/16" Hole n Ceiling (59 mm))Dia. tram) Reducing (59 mm)Dia. Fitting Reducing Fitting W I Face of Fitting Face of Fitting Vented Cup to Face of Ceiling to Face of Ceilin 1-1/2"(38 mm)at Vented Cup 9 1-1/2"(38 mm)at Max.Recess Max.Recess 1"(25 mm)at MUM_ ii�,= • Mln.Recess 1"(25 Recess at a'x 111[II["% ni Min. Tlit 1" a OMB(25 mm) u 1/2" (25 mm) �� 1/2'• _i _ ..___ (12 mm) (12 mm) Minimum I Recess 3-3/16"(78 mm)Dia. Minimum Maximum Recess Maximum Recess 3-5/16"(84 mm)Dia. Recess Models Fl&F1FR Pendent Sprinkler with Model FP Recessed Escutcheon 1/2"(13mm)Nominal Adjustment Model Fl FR56 CCP Conical Concealed Sprinkler 1/2"(13mm)Nominal Adjustment Note:Model FP recessed assemblies may not be used where the (Nominal Cover Plate Projection is 1"(25 mm)) pressure In the space above the ceiling Is positive with respect to the protected area.Ensure that the openings in the Model FP cup Note:Model CCP concealed assemblies may not be used where are unobstructed following installation. the pressure in the space above the ceiling is positive with respect to the protected area.Ensure that the openings in the Model CCP cup are unobstructed following installation. i Fl Escutcheon FP Escutcheon (F2 Similar) CCP Cover Plate Bulletin 074 January 2023 ReliablePage r.of 9 www.reliablesprinkler.com Recessed Installation: Horizontal Sidewall Sprinklers Figure 6 1/2"(12 mm) _ Reducing +/-3/8"(10 mm) Fitting Face of fitting 1-3/8"(35 mm)Maximum Recess to face of wall 4"-12" (102 mm-305 mm) r Deflector to ceiling 2-1/4") 1-15/16" 2-7/8" (57 mm (49 mm) Dia. Dia. (73 mm) Hole Dia. —9/16"[14mm] 1 F1 Recessed escutcheon 3/4"(19 mm)Adjustment 2 1/8"(54 mm)Minimum Recess Model F1FR Horizontal Sidewall Sprinkler with Model F1 Recessed Escutcheon 3/4"(19mm)Nominal Adjustment c,rn-sec asw 3/8"(16 mm) Reducing +/- 1/4"(6 mm) 11111 1-5/8" Fitting Face of fitting (42mm)Maximum Recess to face of wall (102 mm-305 mm) 2-1/4" - -_7 Deflector to ceiling 2-7/8" (57 mm) 1.15/16" Dia. DIA. llllr ��it - (73 mm) Hole Dia. i' iw L 9/16"[14mm] F2 Recessed escutcheon 1/2"(13 mm)Adjustment 2-1/8"(54 mm)Minimum Recess Model F1FR Horizontal Sidewall Sprinkler • with Model F2 Recessed Escutcheon 1/2"(13mm)Nominal Adjustment 1-1/4"(32 mm) Reducing +/- 1/4"(6 mm) 7/8.(22 mm)Maximum Recess Fitting Face of fitting to face of wall 4"-12" (102 mm-305 mm) 2-5/8" �-----7erector to ceiling (87 mm) 2-5/16" 3-1/4" Dia (58mm) ----- _ _— Hole. Dia. -' (83 mm) J Dia. —9/16"114mmj +I Vented Cup i — 1-3/8"(35 mm)Minimum Recess Model F1FR Horizontal Sidewall Sprinkler with Model FP Recessed Escutcheon 1/2"(13mm)Nominal Adjustment Note:Model FP recessed assemblies may not be used where the pressure in the space behind the sprinkler is positive with respect to the space in the protected area.Ensure that the openings in the Model FP cup are unobstructed following installation. Bulletin 074 January 2023 Reliable Page 7 of 9 www.reliablesprinkler.com Wrenches o - — Model W2(upright, pendent) fab Model J (New frame with guard installed) Model JD(Legacy frame with guard installed,similar but with zinc finish) Model W4 (recessed,concealed pendent) Finishes)" Table B Standard Finishes Special Application Finishes F1,F2 and FP)2) CCP Cover )2) Sprinkler Fl,F2 and FP Escutcheons Plate(2) Sprinkler Escutcheons CCP Cover Plate)2) Bronze Brass Chrome Electroless Nickel PTFE)3%0) Bright Brass Bright Brass Chrome Chrome White Paint Bright Brass(5) Satin Chrome Satin Chrome White Polyester)3j White Polyester Satin Chrome Custom Color Polyester Custom Color Paint Custom Color Polyester13j Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Model FP escutcheons and Model CCP sprinklers utilize a galvanized steel cup with a finished trim ring or cover plate. 3. cULus Listed as corrosion resistant. 4. FM Approved as corrosion resistant. 5. For 200°F(93°C)maximum temperature rated sprinklers only. Installation Maintenance Model F1 FR Series sprinklers must be installed in accordance with Reliable Model F1 FR series sprinklers should be inspected and NFPA13 and the requirements of all applicable authorities having the sprinkler system maintained in accordance with NFPA 25, as jurisdiction. Model F1 FR Series sprinklers must be installed with well as the requirements of any Authorities Having Jurisdiction. the Reliable sprinkler installation wrench identified in this Bulletin. Prior to installation,sprinklers should remain in the original Any other wrench may damage the sprinkler. The Models W2 and cartons and packaging until used.This will minimize the potential W4 wrenches have two sets of jaws. Use the smallest set of jaws for damage to sprinklers that could cause improper operation or that fit on the wrench flats of the sprinkler. A leak tight sprinkler non-operation. joint can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N•m). Do not tighten sprinklers over the maximum recommended Do not clean sprinklers with soap and water, ammonia liquid or installation torque. Exceeding the maximum recommended any other cleaning fluids. Remove dust by gentle vacuuming installation torque may cause leakage or impairment of the without touching the sprinkler. sprinkler. Replace any sprinkler which has been painted (other than factory applied).A stock of spare sprinklers should be maintained to Glass bulb sprinklers have orange bulb protectors or protective allow quick replacement of damaged or operated sprinklers. caps to minimize bulb damage during shipping, handling and Failure to properly maintain sprinklers may result in inadvertent installation. Reliable sprinkler installation wrenches are designed operation or non-operation during a fire event. to install sprinklers with bulb protectors in place. Remove the bulb protector at the time when the sprinkler system is placed in service for fire protection.Removal of the bulb protector before this time may leave the bulb vulnerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Bulletin 074 Page 8 of 9 January 2023 Reliable www.reliablesprinklercom Guarantee For the guarantee, terms, and conditions,visit www. re l i a b les pri n k le r.c om. Ordering Information Specify the following when ordering: Model • F1FR56 Deflector/Orientation • Upright • Intermediate Upright • Pendent • CCP Concealed Pendent • Horizontal Sidewall • Vertical Sidewall Temperature Rating • See sprinkler technical specifications Sprinkler Finish • See Table B Recessed Escutcheon(1)2 • F1 • F2 • FP Escutcheon Finish • See Table B CCP Cover Plate Temperature Rating • 135°F(57°C) [For use with 135°F(57°C) and 155°F(68°C)sprinklers.] • 165°F(74°C)[For use with 175°F(79°C) and 200°F(93°C)sprinklers.] CCP Cover Plate Finish • See Table B Sprinkler Wrench • Model W2 • Model W4(recessed, concealed) • Model J(New frame with guard installed) • Model JD(Legacy frame with guard installed) Notes: 1. 286°F(141°C)sprinklers are not listed to be used recessed or concealed. 2. For FM, recessed sprinklers must use the Model F2 escutcheon. No 0) rn rn rn rn rn Z a Bulletin 074 PaeJanuary 2023 e a www.reliablesprink err..com Bulletin 157 November 2022 co RelMI iabl ® Model F3QR56 Dry K5.6 (80 metric) Quick-Res ponse, Z Standard Spray Sprinklers Features N 1. Available in the following configurations: o • Pendent with standard escutcheon N • Pendent with Model HB extended escutcheon • Pendent with Model FP recessed escutcheon ' • Pendent with Model F1 recessed escutcheon \t/ • Concealed Pendent with Model CCP cover plate ' • Horizontal Sidewall with Standard escutcheon 4t • Horizontal Sidewall with Model HB extended escutch- " eon Pendent Pendent/HB • Horizontal Sidewall with Model FP recessed escutch- (See Fig. 1) (See Fig.2) eon (FM Standard Response) • Horizontal Sidewall with Model F1 recessed escutch- eon (FM Standard Response) • Upright 2. Available with 1" NPT, ISO7-1R1, 3/4" NPT, or IS07- 1 R3/4 inlet fitting. 3. 3/4" NPT inlet fittings permit replacement of older 3/4" "'' ''' inlet dry sprinklers without changing to a larger sprinkler '. fitting. Recessed FP Pendent Concealed 4. Sprinklers, escutcheons, and cover plates are available (See Fig. 3) (See Fig.4) in a wide variety of standard and special application fin- ishes. 5. White polyester, black polyester, and Electroless Nickel PTFE (ENT)finish sprinklers are cULus Listed as Corro- sion Resistant. , 6. Available with cULus Listed 250 psi (17.2 bar) pressure rating for Dry Pendent and select HSW configurations. ; ` FM Approved for 175 psi (12 bar). Product Description Recessed F1 Pendent Horizontal Sidewall Model F3QR56 Dry sprinklers are quick-response, standard (See Fig. 5) (See Fig. 6) coverage sprinklers with a nominal K-Factor of 5.6(80 metric). Available in Dry Pendent, Dry Horizontal Sidewall,and Dry Up- right configurations, Model F3QR56 Dry sprinklers all use a 3 r?r ;. mm glass bulb operating element. See the Temperature Rat- ings table in this Bulletin for available temperature ratings. Mod- , , el F3QR56 Dry sprinklers are intended for installation on wet- ,r• pipe, dry-pipe, or preaction sprinkler systems in accordance with NFPA 13, FM Property Loss Prevention Data Sheets, and Horizontal Sidewall/HB Recessed FP other applicable installation standards. (See Fig. 7) Horizontal Sidewall Model F3QR56 Dry Pendent and Sidewall sprinklers are avail- (See Fig.8) able with a variety of escutcheon options as illustrated in Figs. 1 through 3 and Figs. 5 through 9. In addition, Model F3QR56 '4,— 04 Dry Pendent sprinklers are also available with the Model CCP ` ". .., conical concealed cover plate as illustrated in Fig. 4. Availabley sprinkler, escutcheon, and cover plate finishes are identified in _.. the Finishes table in this Bulletin. The Model F1 escutcheon, v-. 4 Model FP escutcheon, and Model CCP cover plate are the only recessed escutcheons and cover plate listed for use with Model Recessed F1 F3QR56 Dry sprinklers;the use of any other recessed escutch- Horizontal Sidewall t eon or cover plate with Model F3QR56 Dry sprinklers will void (See Fig. 9) Upright all guarantees,warranties, listings and approvals. (See Fig. 10) Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Listing and Approval Agencies See the Available Configurations, Listings, and Approvals table in this Bulletin for listings and approvals applicable to each available configuration. 1. Listed by Underwriters Laboratories, Inc. and UL Certified for Canada (cULus) 2. Certified by FM Approvals (FM) 3. Permitted in New York City based on UL Listing per Local Law 33/2007 (NYC) Technical Data Nominal K-Factor: 5.6 gpm/psi112 (80 L/min/bar112) Sprinkler Listing or Approval Deflector to Ceding Distance Maximum Working Pressure F3QR56 Dry cULus, NYC See note below 250 psi(17.2 bar) Pendent FM See note below 175 psi(12 bar) F3QR56 Dry cULus, NYC 4"to 6" 250 psi(17.2 bar) Horizontal Sidewall 4"to 12" 175 psi(12 bar) FM See note below 175 psi(12 bar) F3QR56 Dry Upright cULus See note below 175 psi(12 bar) Note: Deflector distance to be in accordance with applicable NFPA, FM, or other agency requirements. Information is provided only when additional clarification is necessary. Temperature Glass Bulb Color Sprinkler Cover Plate Maximum Ceiling Listings and Classification Temperature Rating Temperature Rating Temperature Approvals1'' Orange 135°F(57°C) Ordinary 135°F(57°C) 100°F(38°C) cULus,FM, NYC Red 155°F(68°C) Intermediate Yellow 175°F(79°C) 165°F(74°C) 150°F(66°C) cULus, NYC Intermediate Green 200°F(93°C) 165°F(74°C) 150°F(66°C) cULus,FM,NYC High Blue 286°F(141°C) None 225°F(107°C) cULus,FM(2),NYC 165°F(74°C) 150°F(66°C) cULus,NYC ")For listed and approved sprinkler,escutcheon,and inlet configurations see the Available Configurations,Listings,and Approvals table in this Bulletin. (2)High temperature classification is FM Approved with Standard and Model HB escutcheons only. Finish Notes 1. Finishes vary with type of trim selected. See table provided with each sprinkler detail for finish combinations. 2. Paint or any other coating applied over the factory finish will void all approvals and warranties. 3. Other finishes and colors may be available on special order.Consult your Reliable sales representative for details. 4. For Standard, Model HB,and Model Fl trims, both components of escutcheon are finished. 5. For Model FP and CCP trims, only the trim ring and cover plate are finished.The threaded sprinkler cup is unfinished. 3. *CAUTION* RELIABLE DRY SPRINKLERS MAY BE INSTALLED IN A LISTED CPVC SPRINKLER FITTING,ONLY UPON VERIFICATION THAT THE FITTING DOES NOT INTERFERE WITH THE SPRINKLER'S INLET. Do not install dry sprinklers with standard inlets into CPVC fittings that have an internal obstruction;this will damage the sprinkler,the fitting,or both. Short inlet("PL")versions of Reliable dry sprinklers are available that may or may not be compatible with fittings having internal obstructions in existing installations.Sprinklers with the short inlet("PL")should only be installed in CPVC fittings of wet-pipe systems. In all cases,verify sprinkler and fitting dimensions prior to installation to avoid interference. Internal Obstruction No Internal i Obstruction 011 Female Female Pipe Thread �________ Pipe %►�' 4 OThread p 10 / 4 Ad CPVC Fitting with Internal Obstruction CPVC fitting - No Internal Obstruction Shorter -- Longer Inlet i �. ... Inlet Male Male Pipe AMNIIIIIMIMIL. Pipe Thread II Thread IIII —ro_ rgli Dry Sprinkler Dry Sprinkler Short Inlet ("PL") Standard Inlet BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR APPLICATION C:OMORYOEr2 Fig. 12 15. MATERIAL SPECIFICATIONS ITEM# DESCRIPTION MATERIAL SPECIFICATION Is �Fv�\ti, 0 1 FRAME BRASS PER UNS C83600 �'���w�!:-; 2 DEFLECTOR BRONZE PER UNS C51000 ' ;:��4 3 LOAD SCREW BRASS PER UNS C22000 t 4 SEAT ADAPTOR BRASS ALLOY PER UNS C36000 / ! 5 BULB INSERT COPPER ALLOY PER UNS C31400 j�i,,, ` iill 6 GLASS BULB GLASS W/GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 /. ■�' 8 OUTER TUBE GALVANIZED STEEL I i k 9 INNER TUBE BRASS ALLOY PER UNS C23000 EIi• `i c111 10 YOKE BRASS ALLOY PER UNS C38000 .1' 11 INLET BRASS ALLOY PER UNS C .5330 0 12 CAP BRASS ALLOY PER UNS C54400 01 13 SPRING WASHER/SEAL PTFE COATED BERYLLIUM NICKEL 14 FLIP DISK BRASS ALLOY PER UNS C54400 '� PAINTED OR PLATED MILD STEEL,EXCEPT CAN/ESCUTCHEON FOR TYPE 316 STAINLESS STEEL FOR 15 SPRINKLERS WITH ENT FINISH 0 I. III ��A' 0 (PIPE WRENCH MAY ONLY BE USED ON OUTER STEEL PIPE OF SPRINKLER) 11116 O tt III; , i COMDRYDET13 O &nisi \ I 0 © lig 0 •�I,]i1 APPEARANCE OF DEFLECTOR MAY VARY DEPENDING ON MODEL Fig. 15 17. Installation Instructions When used on wet pipe systems, Reliable Model F3QR56 3a.Alternatively, where access to the outer tube of the dry sprinklers may be installed in ductile or malleable cast iron sprinkler is available, the Model F3QR56 Dry sprin- threaded tees, or CPVC tees and adapters upon verification kler may be installed using a pipe wrench. The pipe that the sprinkler inlet fitting does not interfere with the interior wrench shall only be permitted to interface with the of the fitting(see Figure 12). galvanized steel outer tube portion of the sprinkler When used on dry pipe systems, Reliable Model F3QR56 (Item #8 in Fig. 15). Do NOT wrench any other por- dry pendent sprinklers MUST ONLY BE installed in the outlets tion of the sprinkler assembly. A pipe wrench can in- of ductile or malleable cast iron threaded tees on horizontal pipe stall the sprinkler into the fitting with a large amount such that the inlet of the sprinkler protrudes above the bottom of torque; consideration should be given to the need level of the pipe. for future removal of the sprinkler because the instal- When used on dry pipe systems, Reliable Model F3QR56 lation torque will have to be matched or exceeded to dry sidewall and dry upright sprinklers may be installed in duc- remove the sprinkler.The recommended minimum to tile or malleable cast iron threaded tees, or CPVC tees and maximum installation torque is 22 - 30 lb-ft (30—40 adapters upon verification that the sprinkler inlet fitting does not N-m) for 1" NPT and IS07-1 R1 sprinklers, and 14 - interfere with the interior of the fitting(see Figure 12). 20 lb-ft (19—27 N-m) for 3/4" NPT and ISO7-1 R3/4 DO NOT install Reliable dry sprinklers into elbows or cou- sprinklers. plings,welded outlets,mechanical tees,or gasket sealed CPVC 4. Standard and Model HB escutcheons can be installed fittings. by slipping the escutcheon over the can until the es- Dry sprinklers connected to wet pipe systems must be in- cutcheon is seated against the ceiling or wall. Model F1 stalled as indicated in Figure 11 and as required by NFPA 13 escutcheons are installed by pressing the escutcheon with the Exposed Minimum Barrel Length located in a heated onto the collar until the escutcheon is seated against area. the ceiling or wall. The Model FP escutcheon is installed An orange protective clip is factory installed on the sprinkler by pressing or threading the escutcheon into the cup to protect the glass bulb thermal element from damage. The by hand; the escutcheon can be tightened against the clip should remain in place during installation of the sprinkler ceiling or wall by turning the escutcheon in a clockwise and be removed when the sprinkler system is placed in service. direction and removed by turning the escutcheon in a Sprinklers with 3/4" NPT and ISO7-1 R3/4 inlets are supplied counter-clockwise direction. To install the Model CCP with a protective cap on the inlet that must be removed before cover plate, first remove the protective clip. Install the installation. Model CCP cover plate on the sprinkler by pressing or Use the following steps for installation: threading the cover plate into the cup by hand; the cov- 1. Cut a hole in the wall or ceiling directly in-line with the er plate can be tightened against the ceiling by turning outlet of the fitting. See the Installation Data table for the the cover plate in a clockwise direction and removed by recommended hole diameter based on the escutcheon turning the cover plate in a counter-clockwise direction. or cover plate option selected. 5. Remove the orange protective clip when placing the 2. Apply pipe joint compound or PTFE tape to the male sprinkler system in service. threads of the sprinkler's inlet fitting. 3. Install the sprinkler in the fitting using the installation wrench specified in the Installation Data table. The Mod- el F3R wrench is designed to be inserted into the groves in the sprinkler's wrench boss as shown in Fig. 13. The Model XLO2 wrench is designed to fit into the cup and engage the wrench boss as shown in Fig. 14. Do NOT wrench any part of the sprinkler assembly other than the wrench boss. When inserting or removing the wrench from the sprinkler, care should be taken to prevent dam- age to the sprinkler. The sprinkler is then tightened into the pipe fitting to achieve a leak free connection. The recommended minimum to maximum installation torque is 22 -30 lb-ft (30—40 N-m)for 1" NPT and ISO7-1 R1 sprinklers, and 14 - 20 lb-ft (19—27 N-m) for 3/4" NPT and IS07-1 R3/4 sprinklers. 18. Installation Data Sprinkler Suggested Hole Diameter In Installation Required Centerline of Sprinkler Model Escutcheon or Cover Plate Tube/Inlet to Finished Ceiling Wall or Ceiling Wrench Vertical Dimension* Standard Escutcheon 2-1/8"(54 mm) F3R HB Extended Escutcheon 2-1/2"(64 mm) F3R F3QR56 Dry F1 Recessed Escutcheon Not Pendent 2-1/4"(57 mm) XL02 Applicable FP Recessed Escutcheon XLO2 2-1/2"(64 mm) CCP Cover Plate XLO2 Standard Escutcheon 2-1/8"(54 mm) F3R 4-5/8"to 12-5/8" HB Extended Escutcheon 2-1/2"(64 mm) F3R (118 mm to 321 mm) F3QR56 Dry Fl Recessed Escutcheon 2-1/4"(57 mm) XLO2 cULus,NYC Horizontal FP Recessed Escutcheon 2-1/2"(64 mm) XL02 4-5/8"to 6-5/8" Sidewall (118 mm to 168 mm) Fl Recessed Escutcheon 2-1/4"(57 mm) XLO2 FM 4-FP Recessed Escutcheon 2-1/2"(64 mm) XL02 1 m (11188 m mm m tt to 321 m8"m) F3QR56 Dry Upright N/A 1-1/2"(38mm) F3R Not Applicable *Note: Based on 5/8"(16 mm)centerline of sprinkler tube/inlet to defector vertical distance. Maintenance The Model F3QR56 Dry Sprinklers should be inspected and 4. Inlet Fitting: [Long —Standard Inlet Fitting][Short "PL" — the sprinkler system maintained in accordance with NFPA 25. Wet Pipe Systems only] Do not remove the factory applied thermally sensitive wax fillet 5. Sprinkler Temperature Rating: See Temperature Ratings between the bulb supporting cup and the wrenching boss. Do Table not replace this wax with a substitute substance. 6. Sprinkler Finish: See Finish Combinations Table An Alternate substance may interfere with proper operation 7. Escutcheon/Cover Plate Finish:See Finish Combinations of the sprinkler. Do not clean sprinklers with soap and water, Table ammonia or any other cleaning fluids. Remove dust by using 8. Length: a soft brush or gently vacuuming. Replace any sprinkler which *For dry pendents and dry sidewalls: "A" Dimension has been painted(other than factory applied)or damaged in any is from face of tee to face of finished ceiling or wall in way.A stock of spare sprinklers should be maintained to allow 1/4" (6mm) increments. See Fig. 1 through Fig. 9. quick replacement of damaged or operated sprinklers. Prior *For dry uprights: Order dimension is from face of tee to installation, sprinklers should be maintained in the original to top of deflector in 1/4" (6mm) increments. See Fig. cartons and packaging until used to minimize the potential for 10. damage to sprinklers that would cause improper operation or Notes: non-operation. 1. For Dry Upright,customer is responsible for determining the Ordering Information correct deflector distance from structure above. Specify: 2. Length is based on normally gauged pipe thread"make-up" 1. Sprinkler: [Model F3QR56 Dry Pendent SIN R5714] of.600" (15mm)per ANSI B2.1 (approximately 7-1/2 threads). [Model F3QR56 Dry Horizontal Sidewall SIN R5734] [Model F2QR Dry Upright SIN R5724] Installation Wrench 2. Escutcheon/Cover Plate: [None][Standard escutcheon] Model F3R Sprinkler Wrench(Standard and HB escutcheons) [Model HB extended escutcheon][Model F1 recessed Model XLO2 Sprinkler Wrench(FP Recessed and CCP escutcheon][Model FP recessed escutcheon][Model Concealed) CCP cover plate—pendent only] 3. Inlet Threads: [1" NPT][ISO7-1R1][3/4" NPT][IS07- 1 R3/4] The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and prnlrrty for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. Recycled ® (800)431-1588 Sales Offices Jr!'� Pap r Reliable (800)848-6051 Sales Fax 914 829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.11/22 P/N 9999970175 Victaulic° VicFIexTM Sprinkler Fittings ✓ctaulicr Series AH2 and AH2-CC Braided Flexible Hoses 10.85 Vic FIexTM Series AH2 Series AH2-CC 1.0 PRODUCT DESCRIPTION Available Sizes by Component Series AH2 1"/DN25 ID Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830 mm. Note: length includes adapter nipple and 5.757140 mm straight reducer. Series AH2-CC 1"/DN25 ID Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830 mm. Note: length includes captured coupling and 5.757140 mm straight reducer. Connections • From Branchline • 3/72Omm BSPT female thread (VdS only) • 13/4732mm BSPT female thread (LPCB only) • 1"/25mm NPT or BSPT female Thread • 1"/25mm Grooved IGS (refer to Submittal 10.54 for additional IGS connections) • No. 116 CPVC Adapter (1"/25mm Female CPVC Socket x 1"/25mm Grooved IGS) • No. 142 Welded Outlet • Style 922 Outlet-T • Style 920N Mechanical-T Outlet • No. 65 Grooved End of Run Fitting • Hose Inlet • 1"/25mm Grooved IGS • 1'/25mm NPT or BSPT male thread • 3"/20mm BSPT male thread (VdS only) • 11/4"/32mm BSPT male thread (LPCB only) ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • • victaulic.com Aii I I __ victaulic.com 1.0 PRODUCT DESCRIPTION (CONTINUED) • Sprinkler Reducer • Sprinkler Connection: lh" and 3/4715mm and 20mm NPT or BSPT female thread • Straight Lengths: 5.75", 9", 137140mm, 230mm, 330mm • 90° Elbows • Standard Short • Low Profile Short • Standard Long • Low Profile Long (Short elbows typically used with concealed sprinklers. Long elbows typically used with recessed pendent sprinklers) Brackets • Style AB2 for suspended and hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment, and installation before most ceiling tiles in place • Style AB3 for surface mount applications, wood, metal and block walls, or ceilings • Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment • Style AB5 for hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment • Style AB7 for suspended and hard-lid ceilings • Style AB7 Adjustable for suspended and hard-lid ceilings • Style AB10 for Armstrong® TechZone'" ceilings • Style AB11 for lay-in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile installations (use only with 90° low profile elbows) • Style AB12 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and allows for low profile installation down to 4'/100mm. • Style ABBA bracket for suspended, exposed, and hard-lid ceilings • Style ABMM bracket for surface mount and stand off-mount applications, wood, metal and block walls, or ceilings and hard-lid ceilings • Strut channel and pipe clamp, not supplied by Victaulic Maximum Working Temperature • 225°F/107°C • 150°F/65°C (No. 116 CPVC Adapter) Maximum Working Pressure • 200 psi/1375 kPa (FM Approval) • 175 psi/1206 kPa (cULus Listed) • 1600 kPa/232 psi (VdS/LPCB Approved) • 1.4 MPa (CCCf Approved) • 175 psi/1206 kPa (No. 116 CPVC Adapter) Minimum Bend Radius • 77178 mm (FM/CCCf Approval) • 2751 mm (cULus Listed) • 3776.2 mm (VdS/LPCB Approved) 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved. victaulic.com • 1.0 PRODUCT DESCRIPTION (CONTINUED) Maximum Allowable Sprinkler K-Factors • FM (1 715mm reducer) K5.6/8,1 (S.I.), (34"/20mm reducer) K14.0/20,2 (S.I.) • cULus (1/715mm reducer) K8.0/11,5 (S.I.), (3/4720mm reducer) K14.0/20,2 (S.I.) • VdS/LPCB (1/2715mm reducer) K5.6/8,1 (S.I.), (34'/20mm reducer) K8.0/11,5 (S.I.) 2.0 CERTIFICATION/LISTINGS ® DOus VdS] LPCB'; ® w E LISTED wm 2809 nn ounewr iwroi NOTE • The VicFlexSeries AH2 Hose has been tested and evaluated by Spears®for acceptable use with Spears®CPVC Products and is therefore covered under the Spears®FlameGuard®Installer Protection Plan. 3.0 SPECIFICATIONS — MATERIAL Series AH2: Flexible Hose: 300-series Stainless Steel Collar/Weld Fitting: 300-series Stainless Steel Gasket Seal: Victaulic EPDM Isolation Ring: Nylon Nut and Nipple: Carbon Steel, Zinc-Plated Reducer (1/'715mm or 3/4720mm): Carbon Steel, Zinc-Plated Low Profile Elbows: Ductile Iron, Zinc-Plated Brackets: Carbon Steel, Zinc-Plated Series AH2-CC: Flexible Hose: 300-series Stainless Steel Collar/Weld Fitting: 300-series Stainless Steel Gasket Seal: Victaulic EPDM Isolation Ring: Nylon Coupling Retainer Ring: Polyethelene Nut: Carbon Steel, Zinc-Plated Reducer (1/2"/15 mm or 3/4"/20 mm): Carbon Steel, Zinc-Plated Low Profile Elbows: Ductile Iron, Zinc-Plated Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Coupling Housing Coating: • Orange enamel (North America, Asia Pacific). • Red enamel (Europe). • Hot dipped galvanized. Gasket:' Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish No. 116 Adapter Fitting: CPVC and Brass Seal: Victaulic EPDM 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com • • 4.0 DIMENSIONS (CONTINUED) Standard Reducer II11i11111Iulull lllllllil IIIII IIIIIIIIIIIIIIIIII'IIIIIIIIIIIIII/I1 5.75"/140 mm straight reducer Optional Reducers 2.62"/ 66.5mm 2.62"/ "ilk 66.5 mm 11 7.257 _ 184.2 mm C T � 1111 I 1 h) 5.507 i -. I 11 1 1 - 139.7mm = 166.9 6. m mm 5.00'/ 9.0"/229 mm straight reducer _ _ v.o mm g 4.83"/ — — 3.25"/ — 122.7 mm = = 82.6 mm = ` I *LA .. �ti 13.0"/330 mm straight reducer Short 90°elbow reducer Long 90°elbow reducer NOTE • The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90°elbow is typically used in the installation of recessed pendent sprinklers. • FM/VdS Approved only. Low Profile All - = 4.59"/ 5.257 3.50"/ 3.63"/ _ = '16 mm133 mm _ 2.84"/ 89 mm 92 mm 48 mm 1.4"/ 1.4'/ 36mm 36 mm Short 90°elbow reducer Long 90°elbow reducer NOTE • Style AB11:When low profiles elbows are with the Style AB11 bracket,the Low Profile Short Elbow is typically used with concealed sprinklers while the Low Profile Long Elbow is typically used in the installation of recessed pendent sprinklers. No. 116 CPVC Adapter TOE ] NOTES • E to E is 3.0'/76.0 mm • The No.116 CPVC Adapter has 2 ft.(0.6 m)EQL of 1'Schedule 40 pipe. • • 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com • 4.1 DIMENSIONS VicFlex Brackets Style AB2 • Suspended Ceilings • Hard-Lid Ceilings 4,44014 Item 1P1 24"/610mmorr48"/1219mm Square Bar 2 Patented Vertically Adjustable Center Bracket I O 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved,cULus listed lip jiOl) Style AB3 • Surface Mount Applications w�/� • FM/LPCB Approved ( 4111 • Style AB4 • Hard-Lid Ceilings with Hat furring % o channel grid system Item Description e3p 1 24"/610mm or 48"/1219mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracket for Hat Furring Channel NOTE • Both sizes FM/VdS/LPCB Approved,cULus listed. ) • • 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com 4.2 DIMENSIONS VicFlex Brackets Style AB5 • Hard-Lid Ceilings Item Description 1 24"/610 mm or 48"/1219 mm Square Bar e 2 Patented Vertically Adjustable Center Bracket 3 End Bracket r NOTE �ilP O • Both sizes FM/VdS/LPCB Approved,cULus listed. C"S Style AB7 • Suspended Ceilings • • Hard-Lid Ceilings Item Description 24'T/610 mm or 48"/1219 mm Square Bar 2 Patented 1-Beer Center Bracket . 3 End Bracket _ r✓IG NOTE • Both sizes FM/VdS/LPCB Approved. Ij Style AB7 Adjustable © 1;1% • Suspended Ceilings • Hard-Lid Ceilings Item Description \� , 1 700 mm or 1400mm Square Bar 0 2 Patented 1-Beer Center Bracket 3 End Bracket(adjustable) NOTE �A 6�. • Both sizes FM/VdS/LPCB Approved. • 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. victaulic.com 4.3 DIMENSIONS VicFlex Brackets Style AB10 • Suspended ceilingso • Armstrong® 0 TechZone -` ` - •q Y Item Description 1 6/152mm Square Bar 2 Patented 1-Beer Center Bracket 1 ot r t 3 End Bracket NOTE • FM/VdS/LPCB Approved,cULus listed. Style AB11 • Suspended ceilings ` • Hard-Lid ceilings `� r e 'Item Description =' 1 24'y610 mm or 48"/1219 mm Square Bar ' 2 Patented 1-Beer Center Bracket i �� 3 End Bracket 0 NOTE ,'2 • FM/VdS Approved,cULus listed. Style AB12 • Suspended ceilings • ® � Hard-Lid ceilings Description Item i y / 1 j Style AB12 Bracket Body ` � �� 2 #2 Square Drive Set Screw �4,I� O NOTE • FM/VdS Approved. • • 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. victaulic.com_ 4.3 DIMENSIONS (CONTINUED) VicFlex Brackets Style ABBA • Floor-above mount ' • Cantilever mount • Temporary mount in exposed ceilings e Item Description 1 Style ABBA Mounting Plate 2 _, Style ABBA Square Bar 3 Cap Screw,Serated Flange,M6 x 1 x 20, T25 Torx Drive Recessed 4 Style ABMM Bracket Body ' S Cap Screw,Serated Flange,M6 x 1 x 15.24, 0 T25 Torx Drive Recessed ''lhy NOTE • FM Approved. Style ABMM /" co*, %'' • Surface mount ,�r! • Stand-off mount 4110-- Item Description 1 Style ABMM Bracket Body 2 Cap Screw,Serated Flange,M6 x 1 x 15.24, T25 Torx Drive Recessed NOTE • FM Approved. 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com 4.4 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB2 Bracket F IMMI .aIIM t SMIS Bracket Assembly Eili Style AB2 _ irla Ida 41!-MIE 5.- 4.3'/ 23W/60.33 mm 111 mm 2750.80 mm I Xk 1 .... . = = ip I —_ _—_ ��ii Typical r _ — Ill ceiling tile ili I = _ 1.7"/43 mm i _ Typical ceiling grid uS=%L a Vli surface riu mr•-ffiliv, surfaceSee note 24"/610 mm or48"/1219 mm Fi on Center V2707�b"/19 MM MAX.RECESS V2707 MAX.EXTENSION Hose Clearance Chart Straight Reducer Long Elbow Short Elbow V2707 V3802 V2707 V3802 3/4" 1„ '/a" rh" V2707 V3802 V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4"Max Recess V2"Max Recess 3/4"Max Recess t "Max Recess inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm torn "R"Minimum 2.0 I 3.0 • 7.0 Bend Radius 50 80 175 — "A"Minimum Required 8.6 10.1 9.6 11.1 13.6 I 15.1 5.8 5.8 Installation 218 269 244 281 345 383 147 147 Space NOTE .�.__- _ _...___ i • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • 10.85 5839 Rev AL Updated 02/2022 C 2022 Victaulic Company.All rights reserved. victaulic.com 4.5 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB2 Bracket kill �� See cchart -- IB _t See Chart t�T Bracket #105aew - = Assembly Style AB2 ,lit, 29s768 mm '1T "' ��� 1.8745 mm 4— :OW max,hole :=''' III 23/d'/60 mm ; �,0 8 '7 �3tirfe:::::: min.hole j•rep4: LJ "_;:::::: ::* _ 2"x 4" i a,::, '1i INlllM ��I�mom lif§:;:::* ii;•�G'.�:r?;v =�_ Stud o�SG �� LJ I ,k7-74rE nl l ! �IU., aA miiiir iI � l . Finished Va./16 mmj Typical 161/406 mm C/C ceiling Typical drywall V38 1/2"/13 mm MAX.RECESS V38 MAX.EXTENSION Hose Clearance Chart Straight Reducer V2707 V3802 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/4'120mm 1/2"113mm 3/a 120mm 3/4"I20mm 1/2"113mm 1/2"120mm 3/4"120mm 1/2"113mm 3/4"120mm Max Recess" Max Recess Sidewall Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall inches inches inches inches inches inches inches inches inches mm mm 1 mm mm mm mm mm mm mm "R"Minimum 2.0 3.0 7,0 Bend Radius 50 80 175 "A"Minimum Required 6.2 7.6 6.1 7.2 8.6 7.1 11.2 12.6 11.1 Installation 158 193 155 183 218 180 285 320 282 Space Hose Clearance Chart Long Elbow Short Elbow V2707 V2709 V3802 3/4"120 mm 3/4"120 mm 1/e"113 mm Max Recess Sidewall Max Recess inches inches inches mm mm mm "R"Minimum Bend Radius — "A"Minimum Required 3.3 3.6 3.3 Installation 84 91 84 Space NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • I 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. vlt'i2 LJ C.CCFit • 4.6 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB4 Bracket 0 1E111 See chart NEM inn A See Chart IBracket assembly = Style AB4 Typical Hat i �iTm r 104 mm max.hole Channel i 410 Screw grid —'� 2"/51 mm min.hole 4lf `p,A kk = h 11 W/23 mm lb e I ,rail rA ♦IA Finished krii "- ce ilingpi%cal mm Typical drywallTypical 161/406 mm C/C V27 34"/19 mm MAX.RECESS V27 MAX.EXTENSION Hose Clearance Chart • Straight Reducer g Long Elbow Short Elbow V2707 V3802 V2707 V3802 3/4" 1rr 3A" 1 " V2707 V3802 V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4'Max Recess 1/2"Max Recess 3/4"Max Recess 1/2"Max Recess inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm "R"Minimum 2.0 2.0 3.0 3.0 7.0 7.0 Bend Radius 50 50 80 80 175 175 "A"Minimum Required 8.8 10.2 9.8 11.2 13.8 15.2 8.0 5.9 Installation 224 259 249 285 351 386 203 150 Space NOTE Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. victaulic.com 4.7 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB5 Bracket R ■■ See chart A See chart WAS 411611/ tit Bracket 'im1I l., =g=911. = assembly 57m 'y_ Style ABS m I i i inw. - = • i 23%760 mm 2°X4" 1 I • max.hole metal stud = _= } 2ymm min.hole II I I I 9 1 1♦1 II I 7- 1lal iI =— 14110 Finished :yp.Dr/16 mm �`- ceiling Typ.Drywall I`�'' Typical 16"/406 mm C/C V27%"/19 mm MAX.RECESS V27 MAX.EXTENSION Hose Clearance Chart Straight Reducer "V2707 V3802 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/4'120mm 1/2"113mm 3/4"120mm 3/a 120mm WI13mm 3/4"120mm 3/4"120mm 1/2"113mm 3/4"120mm Max Recess" Max Recess Sidewall Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm "R"Minimum 2.0 3.0 7.0 Bend Radius 50 80 i 175 "A"Minimum Required 6.0 7.7 6.1 7.0 8.7 7.1 11.0 12.7 11.1 Installation 158 196 155 178 221 180 279 323 282 Space Hose Clearance Chart Low-Profile Long Elbow Long Elbow Short Elbow V2707 V3802 V2709 V3802 V3802 3/4"120mm 1/2"113mm 3/s"120mm 1/2"113mm V2"113mm Max Recess Max Recess Sidewall Max Recess Max Recess inches inches inches inches inches mm mm mm mm mm "R"Minimum I Bend Radius I "A"Minimum Required 3.5 4.9 3.6 2.9 3.3 Installation 89 124 91 74 l 84 Space NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved. victaulic.com • • 4.8 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB11 Bracket (LOW PROFILE SOLUTION) 2W/60 mm 291"/68 mm Brackety �I7:jl" max.hole max.hole Style ABAssembM •�1 2"/51 mm 23/e"/60 mm A ., •,.,I min hole min.hole See Chart C� 3.0'/ ItchII- ;�76mm _ if IL M �M 1.7"/43 mm �`'-fI Finished L Typical s/8715.9 mm ceiling face ceiling grid Typical ceiling tile See Note 24"/610 mm or V27 V38 4871219 mm on center Pendent Hose Clearance Chart Low-Profile Low-Profile Long Elbow Short Elbow V2707 V3802 a/a'120mm 1/2"1 13mm Max Recess" Max Recess inches inches mm mm "A"Minimum Required 4.0 3.9 Installation 102 99 Space NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. victaulic.com • 4.9 DIMENSIONS Clearances Style AB12 and ABBA Bracket Suspended Ceiling Grid with Recessed Sprinkler with Suspended Ceiling Grid with Recessed Sprinkler and Low Profile Short Elbow Straight 5.757140mm Reduceit Jnfinlshed I IS inch/ 29 m Ceiling Face m /� -4- -- %aAI wit �� ■a F� IK Inch/ Unfinished Faze =r= See Table =E1= 29mm binch/ _ �- r •. 3mn I (-' I �� I hllllll- ;� pr> alnch/ r__ 7., -. I l I- 1 3mm I See Table 1 all__ EE1I;i 1pr�r"le Table I � 'B'See Table ��i ' I L 0 'rillT I, •�� -Finished A-mm � VNshed Face of Typical lfi-mm �q %.Inch/16mrn Ceiling Tyoicai Ceiling V2707 W/12.7 mm MAX.RECESS V2707 b/19 mm MAX.RECESS Low Profile Low Profile Standard Standard Standard Dimension Short Elbow Long Elbow Short Elbow Long Elbow Straight Reducer 3A719mm 3/;719mm 3A719mm 44719mm 3/4719mm Recessed* Concealed Recessed Concealed Recessed Concealed Recessed Concealed Recessed Concealed inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm A Minimum Required 4.0 5.5 5.6 7.2 5.9 7.5 7.7 9.3 15.0 16.6 Installation Space 101.6 1 39 7 142.2 182.9 149.9 1905 195.6 236.2 ' 381.0 421.6 Distance from Top ofl 0.5 2.0 1.5 1.5 1.5 1.5 3.0 3.0 3.0 3.0 B Typical Ceiling Tile to 12.7 50.8 38.1 38.1 38.1 38.1 76.2 76.2 76.2 76.2 Bottom of Gate *Adjustability will be limited Style ABMM Bracket Stand-off Dimensions 2.22"/ _ _ 56 mm II l 3.93"/ 100 mm i i 75 mm �'3.94"/ 0.28"/ D i1!IMAM 100 mm 7 mm o■ o • • 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. A victaulic.com • • 4.10 DIMENSIONS Clearances Style AB3 and ABMM Bracket Surface Mount Application with Recessed Sprinkler A JJ1 ( I 33/4"/ = 95.3mm - c•1= _ = A LJ till 23/760 m m 4 max.hole mm min.hole Hose Clearances inches inches inches inches inches inches inches inches inches inches Dimension mm mm mm mm mm mm mm mm mm mm WallThickness 2 4 6 , 8 10 2 4 6 8 10 50 100 150 200 250 50 100 150 200 250 i Outlet Length 5.75 9 13 5.75 9 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13 Hose Clearance) 11. 1 18 4 l _15_._i-__ 146..1 228.E 330..22 146.122228.E 330.2 228.E 330.2 330.2 330.2 1461,228.6330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2 .8 19.8 10.6113.8, 17.8 ' 11.8 , 15.8 ' 13.8 11.8 "C" 294 376 478 243 ; 325 427 275 376 1 325 275 319 402 503 268 1 351 l 452 300 i 402 351 300 Bend Radius 7 8 175 200 NOTE ...- • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. victaulic.com • • 4.11 DIMENSIONS BRANCHLINE CLEARANCES Series AH2 Braided Hose with Style 922 threaded outlet Series AH2-CC Braided Hose with Style 922 grooved outlet R See chart mi.. � R See chart ■ ■■A A .. See chart See chart Igt iiii .� 1 I 1 Style 922 Threaded "���47`-' Style 922 Mechanical Tee : Grooved Outlet /�_ _� — Mechanical Tee . /Q . Outlet \,— ill/ 1� wipA `ill .�// 1\.- immi r,.... ........,,, ,r-- pir 1P250mm \� ...." 2"/50 mm Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm ! mm 1 mm , mm i mm R Minimum 3 4 5 6 7 Minimum 3 4 5 6 7 80 100 125 150 175 R i Bend Radius 80 100 125 150 175 A L Bend Radius I9.4 10.4 11.4 1 12.4 13.4 I A Min. 7.7 8.7 9.7 10.7 11.7 j 238 263 289 I 314 339 197 222 i 247 1 273 298 . . 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com 4.12 DIMENSIONS BRANCHLINE CLEARANCES Series AH2 Braided Hose with female threaded outlet Series AH2-CC Braided Hose with grooved outlet jee!rt R :: 't See chart A ME.. See chart A See chart CEO V lh MMMI `1-- �. 111 Female Threaded r1 Weld Cutlet J laR No.142 Grooved Weld Outlet Y/50 mm �J 2"/50 mm _ Hose Clearance Chart Hose Clearance Chart Dimension Dimension inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm Minimum 3 4 5 6 7 i Minimum 3 4 i 5 6 7 R R Bend Radius 80 1001 i 125 _._.50 175 i,. .. Bend Radius 80 100 125 150 175 A Min. 9.4 i 10.4 11.4 12.4 13.41 ,.. 8.1 9.1 10.1 11.1 12.1 239 264 290 315 I341 A Min. 205J,, 231 ,..�„_ 256 281 307 . 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved. victaulic.com 5.0 PERFORMANCE - FRICTION LOSS DATA Ow us Series AH2 and AH2-CC Braided Hoses with Straight 5.75'Y140 mm Reducers LISTED Style AB2, AB4, AB5 and AB10 Brackets Hose Reducer Length UL � ; Equivalent Length of j g Nominal Outlet Size 1733.7mm Sch.40 pipe inches inches feet mm Type DN meters Max Bends 31 '/z 15.0 790 Straight DN15 4.6 3 31 ..._ Straight 1 .. 16.0_. I 790 DN15 4.9 1 4 31 790 Straight DN20 19.0 5.8 _..__ 20.0 31 s/y Straight 790 _.... DN20 6.1 4 36 915 Straight 1/2 18.0 3 DN15 5.5 36 . Straight 2 21.0 5 915 DN15 6.4 36 Straight a 21.0 3 915 DN20 6.4 36 Straight '/4 23.0 915 DN20 7.0 5 41220 Straight Y: _ - 21.0 _.... 3 DN15 6.4 48 !� �/z -__..-..--- _... 1220 Straight 32.0 8 -_ .. DN15 9.8 a 1220 Straight 3 48 ' ___.__. 26.0 -.. DN20 7.9 48 _.. 1220 Straight ;�4 37.0 8 r- --- ---_... g '. .. DN20 11.3 60 y 27.0 ,_.. 1525 Straight 3 -. . .. DN15 j__ 8.2 1626D5 _. Straight _... _. . .. Y _. ..__ 46.0__. 10.__. --- DN15 14.0 6 16025 Straight i 27.0 3 DN20 8.2 162605 Straight '/a -_. .-_ _46.0 '_._ lo _ . _._. _.._ DN20 14.0 72 - /z _.. 31.0 Straight -__.-__---- 1830 DN15 9.4 3 72 1830 Straight Yz 55.0 12 _._ DN15 16.8 1830 Straight s 30.0 3 DN20 9.1 1830 Straight DN20 60.0 12 , _l 18.3 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com 5.0 PERFORMANCE - FRICTION LOSS DATA (CONTINUED) Series AH2 and AH2-CC Braided Hose with 90° Low Profile Elbows CODS LISTED Style AB11 VicFlex Bracket Hose Reducer UL Equivalent Length of Length Nominal Outlet Size 1"/33.7mm Sch.40 pipe inches inches feet mm Type DN meters ' Max Bends 31 790 LP Elbow '/' 18.0 3 __. --. -.. DN15 5.5 31 LP Elbow _. -. ... . �/� 24.0 _. -.. 790 DN15 7.3 4 31 790 LP Elbow 3/4 21.0 3 DN20 - 6.4 _.- 31 LP Elbow - - 3/4 24.0 - 790 DN20 7.3 4 36 LP Elbow '/z 19.0 915 -__ - DN15 5.8 3 36 LP Elbow /z 26.0 _._. 915 _..- _-. DN15 7.9 5 36 LP Elbow 3/4 23.0 915 DN20 7.0 3 36 LP Elbow 3�4 28.0 915 DN20 8.5 5 1280 LP Elbow - -DN15 - 23.0 --_ 3 7.0 48 LP Elbow '/z 43 0 1220 DN15 13.1 8 42 LP Elbow 3/4 30.0 `4 1220 DN20 9.1 3 48 LP Elbow 3/4 42.0 1220 DN20 12.8 8 60 LP Elbow ... '/z 28.0 -....-1525...----- DN15 8.560 3 LP Elbow _.,____..... 49.0 1525 ' I� 14.9 10 DN15 60 LP Elbow 3/4 31.0 1525 DN20 9.4 3 60 LP Elbow 3/4 50.0 -------1525,........__..__ DN20 ...____._ 15.2 10 72 LP Elbow /' 31.0 1830 DN15 9A72 3 1830 --- LP Elbow '/z 65.0 12 �.. DN15 19.8 72 3/4 - 36.0 11330 LP Elbow DN20 11.0 3 72 1830 LP Elbow DN20 69.2 12 . 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.AM rights reserved. victaulic.com 5.0 PERFORMANCE - FRICTION LOSS DATA (CONTINUED) Series AH2 and AH2-CC Braided Hoses Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2751 mm center line bend radius Nominal Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Length Size Bend Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends inches inches feet feet feet feet feet feet feet feet feet feet feet feet mm DN meters meters meters meters meters meters meters meters meters meters meters meters 31 1 11.0 13.0 15.0 16.0 _ 790 DN15 3,4 4.0' 4.6- 4.9 - - - - - 31 3% 12.0 14.0 19.0 20.0 790 DN20 3.7 4.3 5.8 6.1 - - - - - - 36 h 14.0 16,0 18,0 19.0 21.0 915 I DN15 4.3 4.9 5.5 5.8 6.4 36 3/4 17.0 19.0 21.0 22.0 23.0 -915 DN20 5.2 5.8 6.4 6.7 7.0 j - - - - 48 16 18.0 19.0 21.0 23.0 25.0 27.0 30.0 1 32.0 - • 1220 DN15 5.5 5.8 6.4 7.0 7.6 8.2 9.1 9.8 - - 48 3/4 21.0 24.0 26.0 28.0 31.0 33.0 35.0 37.0 1220 DN20 6.4 7.3 7.9 8.5 9.4 10.1 10.7 11.3 60 Y 21.0 24.0 27.0 30.0 32.0 35.0 37.0 40.0 43.0 46.0 _ 1525 ; DN15 6.4 7.3 8.2 9.1 9.8 10.7 11.3 12,2 13.1 14.0 - 60 3/4 23.0 ; 25.0 27.0 29.0 32.0 34.0 37.0 40.0 43.0 46.0 1525 DN20 'i 7.0 7.6 8.2 8.8 9.8 10.4 11.3 12.2 13.1 14.0 72 1/2 27.0 29.0 31.0 34.0 37.0 40.0 43.0 46.0 48.0 50.0 52.0 i 55.0 1830 DN15 8.2 8.8 9.4 10.4 11.3 12.2 13.1 14.0 14.6 15.2 15.8 16.8 72 34 26.0 28.0 1 30.0 33.0 37.0 40.0 44.0 48.0 51.0 54.0 57.0 60.0 1830 DN20 7.9 8.5 9.1 10.1 11.3 1 12.2 1 13.4 I 14.6 15.5 I 16.5 i 17.4 18.3 NOTES • Values for use with 5.757140 mm straight reducers. • The values in this table are provided by the manufacturer for reference only.For friction loss data in accordance with the UL Certification,please refer to pages 19 and 20 of this publication. How to use this Design Guide: • For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. • It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. • . 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved. victaulic.com • • 5.1 PERFORMANCE - FRICTION LOSS DATA ® Series AH2 and AH2-CC Braided Hoses Style AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB12, ABBA and ABMM VicFlex Brackets • Maximum Equivalent Number Length of Length of of 90°Bends Stainless Steel Outlet 1733.7mm at 7"/178mm Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius inches inches Imperial mm feet • mm S.I. type meters h 13.8 15 31 5.6 Straight 4'2 790 8.1 yz ---..._-- --. 2 75 23.5 • 90°Elbow 7.1 v3 15 16.6 36 5.6 Strai ht 5.1 915 8.1 1/22 15 25.6 90'Elbow 7.8 15 23.4 48 5.6 Strai ht 7:1 1220. 8.1 Yz 3 15 30.7 90°Elbow 9.3 z 15 30.2 60 5.6 Straight 9'2 1525 8.1 ,h 4 15 35.9 90°Elbow 10.9 • 15 37.0 72 5.6 Straight 11.3 1830 8.1 Yz 4 15. 41,1 '.. 90'Elbow 12.5 • • 3A 16.8 20 31 8.0 Straight 5.1 790 11.5 V, 2 20 16.8 90°Elbow 5.1 20 20 36 8.0 Straight i 6.0 • 915 11.5 3/a -- ` 2 20 19.7 90'Elbow 6.0 3/4 27.8 20 48 8.0 Straight 8.4 1220 11.5 �a 3 20 26.6 90°Elbow 81 FM NOTES • The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 standard for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. • EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. • • 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. victaulic.com • 5.1 PERFORMANCE - FRICTION LOSS DATA (CONTINUED) ® Series AH2 and AH2-CC Braided Hoses Style AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB12, ABBA and ABMM VicFlex Brackets Maximum Equivalent Number Length of Length of of 90°Bends Stainless Steel Outlet 1733.7mm at 7/178mm Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius inches inches Imperial mm feet mm S.I. type meters 3A 20 35.7 '.. 60 8.0 Straight 10.9 4 4 1525 11.5 3/a _.. 20 33.6 90"Elbow 10.2 34 20 43.5 72 8.0 Strai•ht 13.2 1830 11.5 14 4 20 40.6 90'Elbow 12.2 1/4 20 16.5 31 11.2 Straight 5.0 790 16.1 _._--.. 3/4 2 20 -17.8 '`,r. a 'z' ;.lu. 90"Elbow 5.4 /a 20 19.5 36 11.2 Straight 5.9 915 16.1 34 2 20 20.7 90°Elbow 6.3 4g (.11.2 5tr3ight 1220 16.7 ` °/a 3 34 20 33.9 60 11.2 Straight 10.3 1525 16.1 34 4 20 35 l 90°Elbow 10.7 3/a 41.3 20 72 11.2 Straight 12.5 4 1830 16.1 3/a 20 42.2 I 90`Elbow 12.8 3/a 14,9 20 31 14.0 Straight 4.5 790 20.2 let - -- 2 20 15.5 90'Elbow 4.72 FM NOTES • The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13, 13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 standard for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. • EXAMPLE A 48-inch hose installed with two 30°bends and two 90°bends is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. • • 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. victaulic.com • 5.1 PERFORMANCE — FRICTION LOSS DATA (CONTINUED) ® Series AH2 and AH2-CC Braided Hoses Style AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB12, ABBA and ABMM VicFlex Brackets •• • Maximum Equivalent Number Length of • Length of of 90°Bends Stainless Steel Outlet 1733.7mm at 77178mm Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius inches inches Imperial mm feet mm S.I. I type meters 3% 20 9.4 36 14.0 Straight 5'9 915 20.2 34 2 20 19.6 90°Elbow i 5.9 3/4 ...._.__ 20 30.3 48 14.0 Strai ht 9.2 1220 20.2 3/4 3 20 29.5 90°Elbow 8.9 20 33.9 60 14.0 i Straight 10.3 1525 20.2 3/4 4 20 34.1 ° f 90°Elbow 10.4 ._....... �4 37.5 20 72 14.0 Straight 11.4 1830 20.2 3/4 4 20 38.6 90`Elbow 11.7 FM NOTES • The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 standard for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. • EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. • • 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved. v;c ti L'li C',com • 5.2 PERFORMANCE - FRICTION LOSS DATA ® Series AH2 Braided Hose with 90° Low Profile Elbows Style AB5, AB11, AB12, ABBA and ABMM VicFlex Bracket 1 Maximum Equivalent Number Length of Length of of 90°Bends Stainless Steel Outlet 1"/33.7mm at 7'Y178mm Flexible Hose I K-Factor Size Sch.40 Pipe Bend Radius inches Imperial inches feet mm S.I. mm meters 31 5.6 Yz 13.7 790 8.1 __. 15 4.2 2 36 5.6 Y= 17.0 2 915 8.1 15 5.2 48 S 5.6 1/2 25.0 1220 8.1 15 7.6 3 60 5.6._-. 1 33.0 4 1525 8.1 15 10.1 72 5.6 y, • 41.1 1830 8.1 15 12.5 4 31 8.0 3/4 - 13.6 �, 790 _ 11.5 20 4.14 2 36 8.0 3/4 _____I16.9 2 915 11.5 j 20 5.2 48 8.0 3/4 I 27.8 1220 11.5 20 8.5 3 60 8.0 3 32.6 1525 11.5 20 9.9 4 72 8.0 3/ 40.6 1830 11.5 20 12.4 4 31 11.2 3A 13.7 790 16.1 20 4.2 2 36 11.2 14 17.0 915 16.1 20 5.2 2 48 11.2 3/4 24.9 1220 16.1 20 7.6 3 60 11.2 3/4 32.9 1525 16.1 20 10.0 4 II 72 11.2 3/4 40.9 4 1830 16.1 20 12.5 31 14.0 1/4 13.5 790 20.2 20 4.1 1 2 l 36 14.0 3/4 16.8 915 - 20.2 20 5.1 2 48 14.0 3/, 24.7 1220 20.2 20 7.5 3 60 14.0 I 3/4 32.7 1525 20.2 20 9.9 4 • 72 14.0 3/4 40.7 1830 20.2 20 12.4 4 FM NOTES • The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 standard for safety include,but are not limited to, pressure cycling,corrosion resistance,flow characterisitics,vibration resistance, leakage,mechanical and hydrostatic strength. • EXAMPLE A 48-inch hose installed with two 30°bends and two 90°bends is permitted and considered equivalent to the data in the table shown above. In this example,the total number of degrees is 240°,which is less than the allowable 270°. • 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved. victaulic.com • • 5.3 PERFORMANCE - FRICTION LOSS DATA VdS Series AH2 and AH2-CC Braided Hose Style AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB11 and AB12 Brackets Length of s f eel pipeEquivalenaccording t Length oto �P Stainless Steel Outlet EN 10255 DN 25 Maximum Number Flexible Hose Size (33,7 x 3,25) of 90°Bends at mm DN meters 3'776.2mm Bend inches inches feet Radius DN15 790 Yz 5.5 31 DN20 18.03 34 DN15 915 Y 6.4 36 DN20 21.0 3 3/4 DN15 1220 Y: 8.5 48 DN20 --- --' 27.9 3 '.. -_. 3/a DN15 __--- -� 1525 '/ 10.7 60 DN20 35.1 4 3/4 DN15 1830 12.8 72 DN20 • 42.0 4 3/a VdS Ceiling Manufacturers List AB2,AB7,AB10,AB11 AB4 AB5,AB8 1.AMF No specific approval 1.Hilti 2.Armstrong 2.Knauf 3.Chicago Metallic 3.Lafarge 4.Dipling 4.Lindner 5.Durlum 5.Rigips 6.Geipel 7.Gema-Armstrong 8.Hilti 9.Knauf 10.Lafarge 11.Linder 12.Odenwald 13.Richter 14.Rigips 15.Rockfon Pagos 16.Suckow&Fischer 17.USG Donn 10.85 5839 Rev AL Updated 02/2022 ©2022 Victau'ic Company.All rights reserved. victaulic.com 5.3 PERFORMANCE - FRICTION LOSS DATA Series AH2 and AH2-CC Braided Hose Series AH2 Braided Hose , ,. Style AB2, AB3, AB4, AB5, AB7, AB8, ® Style AB2, AB3, AB4, AB5, AB7, AB8, AB10 <rULPOBd-;�„ and AB10 Brackets and AB12 Brackets Length of Equivalent Length Maximum Stainless of steel pipe Number of Equivalent Length of Steel according to 90°Bends at Length of i 1'733.7mm Sch.40 Pipe Flexible Outlet EN 10255 DN 25 3'776.2mm Flexible Hose Size (33,7 x 3,25) Bend Radius Hose Straight Configuration Bend Configuration mm mm inches meters mm meters meters i inches type feet inches feet feet 15mm i 1 790 _ ,___Straight ,. 1.8 2 790 0.87 2.70 31 20 mm 6.0 31 i 2.9 8.9 Strai".ht , 15mm ----', i ' 915 Straight 3.6 3 915 1.00 2.80 36 20mm 11.9 36 3.3 9.2 % Strai•ht 15mm I Y 1220 Straight 4.3 1220 2.23 4.66 _. . - 14.0 ', 3 48 20mm 48 7.3 15.3 34 ' Strai ht 15mm ,h 1525 Strai ht 4.1 3 1525 2.90 6.5 60 20mm 13.6 60 9.5 21.3 3A I Straight 15mm Y2 1830 I Straight 5.5 1830 3.31 7.16 72 20mm 18.1 3 72 10.9 23.5 34 Straight j 3"^ ,1 CCCF NOTE • Friction loss data is in accordance with GB5135.16 tested at a flow rate of 114 liters per minute(30 gallons per minute). 10.85 5839 Rev AL Updated 02/2022 ®2022 Victaulic Company.All rights reserved. i victaulic.com 6.0 NOTIFICATIONS A WARNING / • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depres- 0surized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain im- portant information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for use with the intended fluid media within the piping system and external environments. • The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on 300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be acceptable for the intended service. • It is the responsibility of the owner of a building or their authorized agent to provide the sprinkler system installer with any knowledge that the water supply might be contaminated with or conducive to the development of micro- biologically influenced corrosion (MIC), including as required by NFPA 13. Failure to identify adverse water quality issues may affect the VicFlex product and void the manufacturer's warranty. Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage. Victaulic VicFlex Series AH2 and AH2-CC Flexible Sprinkler Fittings may be painted provided the paint is compatible with stainless steel and zinc-plated carbon steel or ductile iron. Care should be taken to ensure the sprinkler and associated escutcheon or coverplate are not painted. Victaulic VicFlex Series AH2 and AH2-CC penetrating through non-fire rated gypsum wall (drywall) will function as designed, provided the components are installed in accordance with the respective installation instructions referenced in this document. 10.85 5839 Rev AL Updated 02/2022 ©2022 Victaulic Company.All rights reserved. 7.0 REFERENCE MATERIALS - CHARACTERISTICS VicF/ex Maximum Load Values Series AH2 Hose with 24" Bracket Actual Length Total Load Max.Uniform Load ft Model Size m lb N lb/linear ft N/linear m • 2.6 31/790 5.2 23 2.6 38 0.8 3 36/915 0.9 5.5 25 2.8 40 H---- 4 48/1220 1.2 6.3 28 3.1 46. .., 5 60/1525 1.5 7.0 31 3.5 51 ._ 72/1830 7.7 34 3.9 57 1.8 Series AH2 Hose with 48" Bracket Actual Length Total Load Max. Uniform Load ft Model Size m lb N lb/linear ft N/linear m 2.6 31/790 6.1 271.5 22 0.8 . 3 36/915 0.9 6.4 29 1.6 23 4 48/1220j 1.2 7.2 32 1.8 26 5 i ' 60/1525 1.5 7.9 35 2.0 29 6 i 72/1830 1.8 8.7 39 1 2.2 32 Total Load is defined as the sum of the weights of the following: • water-filled flexible sprinkler hose with threaded end fittings, including a typical fire sprinkler • bracket assembly (any applicable Victaulic bracket model of the relevant associated size) ASTM C 635: Suspension System Load-Carrying Capabilities (excerpted) Actual Length Min.Allowable Uniform Load Suspension System ft/m lb/linear ft N/linear m Light 5.0 75.7 Direct Hung Intermediate 12.0 181.0 1 Heavy 16.0 241.7 SUM MARY: All direct-hung suspension system duty classifications per ASTM C 635 are able to withstand the maximum water-filled weight of the VicFlex sprinkler hose and bracket. . 10.85 5839 Rev AL Updated 02/2022 c 2022 Victaulic Company.All rights reserved. A' victaulic.com 7.0 REFERENCE MATERIALS — CHARACTERISTICS (CONTINUED) Flexible Hose In-Plane Bend Characteristics One Bend • Two Bends Three Bends % 1x Minimum Minimum I Minimum - I bend radus bend atlas bend radius Minimum OR OR bend radius 90\ Minimum Minimum u ♦ bend radius Minimum -- — bend radius bend inimuius Minimum bend radius Minimum bend radius NOTE For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose. I-VicFlex-AB1-AB2 I-VicFlex-A53 I-V c Flex-AB4 I-VicFlex-AB5 I-VicFlex-A87 I-VicFlex-AB12 I-VicFlex-ABBA I-VicF.ex-ABMM 1-RES • User Responsibility for Product Selection and Suitability Note Each user bears final resoonsinility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions, standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Installation Reference should always be made to -VICFLEXct yoAB2-AB10, -VICFLEX-AB4, or waive any provision of Victaulic Company's standard conditions of sale,installation guide,or this disclaimer. of Victaulic products for complete installation and assembly Intellectual Property Rights data,and are available in PDF format on our website at www.victaulic cons. No statement contained herein concerning a possible or suggested use of any material, product,service,or design is intended,or should be constructed,to grant any license Warranty under any patent or other intellectual property right of Victaulic or any of its subsidaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patentor other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 10.85 5839 Rev AL Updated 02/2022 0 2022 Victaulic Company.All rights reserved.