Specifications (12) . MQC2022- 034q3
k
1 M IVY
TM RIPPEY Tigard,Oregon 97223
7650 S.W.Beveland St.
ECECONSULTING ENGINEERS Phone: (503}443-3900 �:S,"R Z 2023
Fax. (503)443-3700 cm( OF TiCaAlp
BUILDING DIVISIpN
STRUCTURAL CALCULATIONS
S3RUCTLink
PROJECT: COOLSYS-12045 SW HALL BLVD.-RTUs \5,&E0 P R 0 fEs f/o
�,::, 41.1GIN 4 49!
LOCATION: 12045 SW HALL BLVD, / BsrzPEt
TIGARD,OR 97223 K/a//
CLIENT: COOLSYS . OREGON ,
d oti
DATE: JANUARY 26,2022 -1, liCH 9, 2 \�
yG'4 XY l E W EZ\E�
PROJECT NUMBER: 23008
EXPIRES: 6-30-24
TABLE OF CONTENTS:
ITEM SHEET NUMBER
GENERAL NOTES N 1
DETAIL SIC 1 -3
CALCULATIONS C 1-6
DESCRIPTION:
THIS DESIGN PACKAGE INCLUDES DETAILS AND CALCULATIONS FOR THE SUPPORT
OF(2)REPLACEMENT ROOFTOP MECHANICAL UNITS.
GENERAL STRUCTURAL NOTES
CODE REOUIREMENTS•
CONFORM TO THE 2018 INTERNATIONAL BUILDING CODE AS AMENDED BY THE 2019 OREGON STRUCTURAL SPECIALTY CODE,
REFERENCED HEREAFTER AS IBC
DESIGN CRITERIA'
DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE IBC. IN ADDITION TO THE DEAD LOADS,THE FOLLOWING
LOADS WERE USED FOR DESIGN,WITH LIVE LOADS REDUCED PER IBC:
UNIT WEIGHT: RTU 1&2=531 LB
ROOF DEAD LOAD: 12.5 PSF
ROOF SNOW LOAD:25 PSF
WIND SPEED:97 MPH(3-SECOND GUST),EXPOSURE:C
SEISMIC IMPORTANCE FACTOR le: 1.0
SITE CLASS:D(ASSUMED)
SDS 0.686
ap=2.5,Rp=6.0
EXISTING CONDITIONS:
THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,DIMENSIONS AND ELEVATIONS. TUB CONTRACTOR SHALL NOTIFY
THE ENGINEER OF ANY DISCREPANCIES FROM CONDITIONS SI IOWN ON THE DRAWINGS PRIOR TO THE START OF THE WORK.
TEMPORARY CONDITIONS:
THE CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL STABILITY OF THE NEW AND EXISTING STRUCTURES AND WALLS DURING
CONSTRUCTION. THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER THE FINAL CONFIGURATION
ONLY.
MECHANICAL:
THE CONTRACTOR SHALL COORDINATE SEISMIC RESTRAINTS OF ELECTRICAL EQUIPMENT,MECHANICAL,PLUMBING,FIRE SPRINKLER,
MACHINERY,AND ASSOCIATED PIPING WITH THE STRUCTURE. ANY CONNECTIONS TO STRUCTURE NOT CONFORMING TO SHEET METAL
AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION(SMACNA),OR SPECIFICALLY DETAILED ON THE MECHANICAL
ENGINEER'S DRAWINGS,SHALL BE DESIGNED IN ACCORDANCE OF THESE GENERAL NOTES,BY AN ENGINEER REGISTERED IN THE STATE
OF OREGON,AND SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION.
TM RIPPPY Co —
�1 Consulting Engineers By: Al' Date:
7650 SW Beveland Street Chk By: Date:
Suite 100 CoolSys - 12045 SW Hall Blvd - RTUs Job#: 23008
Tigard,Oregon 97223 ---
s Phone:(503)443-3900 Sheet: NI Of
TR I./. 4 A i 41..c,'' eve,
0 4
'a . . / \\\\.
t �
I
I I
II I
I
I
SIM, RTU
1 1
SK3
' (E) OPEN WEB
I I o TRUSSES
I I ti
I I
I I
I I
I I
I I
1 I
\ I / 2
EXISTING 2X4 BLKG.
ALIGN WITH THE EXT.
CURB.
NOTES:
- INSTALL ALL NEW FRAMING PRIOR TO INSTALLING CURB.
-ALL WATERPROOFING IS BY OTHERS.
- EXACT LOCATION PER MECHANICAL PLANS.
et) FRAMING PLAN AT RTU
(41,
N.T.S.
1 f \/ 1 K MRII PE1. nY, AI- DATE
.L X J. CONSULTING ENGINEERS •
CHI(BY DATE
7650 S.W.lieveland St,Suite 100 COOLSYS - 12045 SW HALL BLVD. - RTUs 1013 NO 23008
Tigard,Oregon 97223
,Phone(503)443-3900 SNEE (2_of
I'-0 ', TYP. PLATE CONN.
LOCATION TYP. .4
8 TOTAL 3''t "'
CLIP EQ.SPACED ElOR
TIIER
LOCATION, TYP. BOTH WAYS
TYP. Ire
6„ R
I-- NEW RTU
16 GA.CLIP 16 CAKE snsuicCLIP
we.
•
4 PLAN NEW MECHANICAL
N.T.S. UNIT.
16 GA.CLIP W/(8)#10 x 3/4"
GALVANIZED TEK SCREWS, i;
(4)CLIPS REQ'D.SEE DETAIL
(PLAN1'VIEW)FOR CLIP '
LO
LOCAATION.
NEW CURB ADAPTOR
(DESIGN BY OTHERS)
#10 x 1 1/2"GALVANIZED TEK
SCREWS @ 2'-0"0/C.AND 6"
FROM ENDS.(4)MIN.PER
SIDE,TYP.
11
I EXISTING CURB
' TO REMAIN.
EXISTING I SLOT PLYWOOD SHEATHING AND
LEVELING CURB PROVIDE 16 GA PLATE X 8"X REQ'D WI
ASSUMED (2)#10X2 1/2"SCREWS @6"0/C TO THE
TRUSS/BLOCKING AND(4)#10 X 3/4"
SCREWS TO CURB
mom
(E)OPEN WEB TRUSSES
OR BLOCKING PER PLAN
SECTION AT CUiRE3
NOTE:1.FLASHING AND INSULATION NOT SHOWN FOR111,
N.T.S.
CLARITY.
2.ALL SCREWS SHOULD BE MIN.6"FROM THE STEEL PINS IN
THE TRUSSES.
/IV 1:\. TM RIPPEY BY AP
CONSULTING ENGINEERS CM(BY DATE
7650 SW Beveland,Suite 100 CoolSys - 12045 SW Hall Blvd - RTU JOB N 22008
Tigard,Oregon 97223
Phone:(503)443-3900 SHEET SK3 or
Fax:(503)443-3700
I )
RE PU+f_EvitvU h0 - 1' Vs) E: e tv-A ( .
R"ch J i () 5.S )tc, t So 16 CV:--'0R, l.ii('P A 11ApTOR) i too rZ
C-UI
_. -711 ►1�
i
(.E) U turl tn)E
= 8-1s
f l{a
l Ex T. Gur2.P. )
TR F RE-c>LAC_ nrentT UN-A'S r V-'t- (IiCj_. Less -THAt,) ;CE )
1-1-4E, () F C''Atkl C e.11 SNs.rteAt it ,
f JoF DeAb 1/,o A 0 -
RnbF = 3 P-S-
?t-Y woof) • e 2.0 7'GS
Mtc.,I c Lt_ = 1.5 psi
e•usSes
5►.,su . b .s Ps�
�p�7LtJ1! _ 1• n ‘ s
INtx..)p r ,C- t) cS�
sps w 0 g
/r TM RIPPEY
BY DAIL
CONSULTING ENGINEERS
CHK BY DATE
7650 S.W. Beveland St, Suite 100 Caa1„i,s -) 26 e15 Svt1 Na t t BWp r2TU ioBMO 23Ob
Tigard,Oregon 97223
Phone(503) 443-3900 sHEETC( OF
ASCE
ASCE 7 Hazards Report
AMERICAN=ETV OF MIL MOWERS
Address: Standard: ASCE/SEI 7-16 Latitude: 45.387551
19100 Willamette Dr Risk Category: 11 Longitude: 0
-11722.9.62 ft(NAVD 88)4 0 9 8 9
West Linn, Oregon Soil Class: D - Default(see Elevation:97068 Section 11.4.3)
, _- ,
,:,,,,—..yr.1 , \ ' ,••• I i
• ' I . '
4" Robit 1%
nyood a '""k •, • ' .
<:. , e % T' ' • ' I '
II, % ' ..k ' ' ' : - '• 1.''' : 7
o ,4.q'ee 6.LOIC. 8 -4+ - 4"D
.* L". . —
.'• - ,1,t
0, 11.-A1' ' 'r ISt‘ IuI
pI,
I ' '
-,,• - %,,-, 0 •6 l','?‘is • r •‘, , .1„„,4-,. •
•• • -, b Ged.al..a0 ' ,'
' ' n
. . • y
. .s.
'' • 'Itz., ' : ' 1; .04(04 City
•
_• . , , I 1 \'lb .„,,,„,,,,,,
I
ArIE VAiLEY '..: T" 1.1 I hmiakt-I
,nt ..,,,
• •
"-,'- ! •----•,'I i* ;. /clielti, • ' ' ..i ,
, 64„ • , j ,. •,i•.x' , .0,
/ . : • t '
•
g /
,•'
•
:,-rr^ ',
r., I lilt.lSi,„ '/'
''' -4 }''' '' .,
. -
Thu Jan 19 2023
1141
Page 1 of 3
haus://asce7hazardtoolonline/
AscE.
AMEFN.AN SOCIETYOF LMl aiGIVEFRs
Seismic
Site Soil Class: D-Default(see Section 11.4.3)
Results:
Ss ; 0.858 SDI : N/A
Si : 0.383 TL : 16
Fe : 1.2 PGA : 0.386
F, : N/A PGA M : 0.469
SMs : 1.03 FpGA : 1.214
SMI : N/A le : 1
SOS 0.686 C„ : 1.229
Ground motion hazard analysis may he required. See ASCE/SEI 7-16 Section 11.4.8.
Data Accessed: Thu Jan 19 2023
Date Source: USGS Seismic Desian Macs
C-4
htiss://asce7hazardtool.online/ Page 2 of 3 Thu Jan 19 2023
Wind and Seismic Loads on Mechanical Unit
Based on ASCE 7-16 Section 29.4.1 and 13.3.1
Seismic Parameters
SDS= 0.69 Spectral acceleration
1p= 1.00 Importance factor
Rp- 6.0 Component response modification factor
a = 2.5 Component amplification factor
Wind Parameters
V= 98.00 mph Ultimate Wind Speed 3-Second Gust
C Exposure Category
Building Parameters Mechanical Unit Parameters Curb Parameters
h= 16.0 ft Wt= 711.0 lbs Height= 20.00 in
Building Depth = 41.0 ft Height= 33.40 in Width= 48.00 in
Building Width= 60.0 ft Width= 46.60 : in Length= 72.00 in
Length= 74.40 in
Loading Summary(all values in ASD)
W Uplift =401 lbs
Wt=711 lbs
E= 171lbs
,� YY
m W = 5741bs
co
. v T
N
� C
4ft
CONSULTING ENGINEERS
I Net Wind = 306 lbs
T Net Seismic=-49 lbs
TM RIPPEY
•
Performance Summary For RTU - 1-2 store 23999
Project: FM-23999 Tigard,OR(12045 SW Hall Blvd)- 09/21/2022
Prepared By: 12:45PM
Part Number:50FC-A06A1A5-0A0A0
ARI SEER. 14.00
Base Unit Dimensions
Unit Length. 74.4 in
Unit Width: 46.6 in
Unit Height: 33.4 in
Operating Weight
Base Unit Weight: 511 lb
Accessories
15.8/19.3 kW 208/230-1/3-60 Volt Electric Heater 10 lb
Single Point Kit' 10 lb
Total Operating Weight: 531 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge' Vertical
Fan Drive Type- Vane Axial
Actual Airflow: 2000 CFM
Site Altitude' 0 ft
Cooling Performance
Condenser Entering Air DB' 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB' 59.3 F
Evaporator Leaving Air WB' 57.7 F
Evaporator Leaving Air Enthalpy' 24.85 BTU/lb
Gross Cooling Capacity; 59.31 MBH
Gross Sensible Capacity' 44.73 MBH
Compressor Power input: 4.14 kW
Coil Bypass Factor 0.163
Heating Performance
Heating Airflow' 2000 CFM
Entering Air Temp: 70.0 F
Leaving Air Temp' 95.0 F
Electric Heating Capacity: 15.80 kW
Supply Fan
External Static Pressure' 1.00 in wg
Options/Accessories Static Pressure
Electric Heaters: 0.18 In wg
Total Application Static(ESP+Unit Opts/Acc.)• 1.18 in wg
Fan RPM. 2138
Fan Power' 1.05 BHP
NOTE' Selected IFM RPM Range: 215.2150
Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated.
Electrical Data
Voltage Range: 187-253
Compressor#1 RLA• 16
Compressor#1 LRA. 110
Actual Electric Heater kW: 15.8
Electric Heater FLA• 43.8
Indoor Fan Motor Type- STD C-
Packaged Rooftop Builder 1.69 Page 8 of 10
Unit 1 Unit Type:e. PackagedE
Unit �`fi�3`
Unit 1 Vixxo Asset Tag Number: 819644 11!',! L ii 2023
Unit 1 Make: Trane CITY OF TIGARD
BUILDING DIVISION
Unit 1 Model: WCD060C300BD
Unit 1 Serial Number: Z06102039D
Unit 1 Manufacture Year: 2001
Unit 1 Condition: Not Running
Unit 1 Reason not running: Bad compressor
Unit 1 size: 5-ton
Unit 1 Heat Type: Heat Pump
Unit 1 Voltage: 208/230v-3P
Unit 1 Control Type: Thermostat
Unit 1 air flow configuration: Vertical return,Vertical Supply, both through curb
Unit 1 mounted on: Standard roof curb with curb adapter
Unit 1 Provide photo of unit equipment tag:
4l
�,, r
t
ti l Nam. 4< i414. E P
t
.4!urname lttstwf—" '+
9a
33 image 3566.jpg
Unit 1 Provide 2 photos of unit from opposite corners of unit:
•
ME
yy
y} A
10.
•
frrli
29 image 6151.jpg image 406jpg
Unit 1 Ductwork configuration: Concentric
8
Unit 2 Unit Type: Packaged Unit
Unit 2 Vixxo Asset Tag Number 883507
Unit 2 Make: Trane
Unit 2 Model: Wcd060c300BD
Unit 2 Serial Number: Z06102672D
Unit 2 Manufacture Year: 2001
Unit 2 Condition: Fair
Unit 2 size: 5-ton
Unit 2 Heat Type: Heat Pump
Unit 2 Voltage: 208/230v-3P
Unit 2 Control Type: Thermostat
Unit 2 air flow configuration: Vertical return,Vertical Supply, both through curb
Unit 2 mounted on: Standard roof curb with curb adapter
Unit 2 Provide photo of unit equipment tag:
..... '1 i.mow
x`c
ia.mFMR a
•:••
iI�Y.w 17:
I. Me xb or itmy.gp- � a
Of $6 n.{k x �f4.*" iiTT++CCRR
So
%� s.
'
r, �t
286 image 7304.jpg
Unit 2 Provide 2 photos of unit from opposite corners of unit:
9
p ,
r i.
Nat
x '3
287 image 1839 jpg image 8159jpg
Unit 2 Ductwork configuration: Concentric
10
Carr;Dm
SUBMITTAL
Project
FM - 23999 Tigard, OR (12045 SW Hall Blvd)
Date
Monday, August 8, 2022
Unit Report For RTU - 1-2 store 23999
Project: FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/2022
Prepared By: 11:56AN
Unit Parameters Dimensions(R.in.)&Weight(lb.)***
Unit Model. 50GCQMO6F2M5-SW4C0 Unit Length. 6'2.375"
Unit Size- 06 (5 Tons) Unit Width. 3'10.625"
Volts-Phase-Hertz. 208-3-60 Unit Height: 3'5.375"
Heating Type• Heat Pump ^'^ Total Operating Weight: 872 lb
Duct Cfg: Vertical Supply/Vertical Return
Two Stage Cooling Models Weights and Dimensions are approximate. Weight
does not include unit packaging. Approximate
dimensions are provided primarily for shipping purposes.
For exact dimensions and weights,refer to appropriate
product data catalog.
Lines and Filters
Return Air Filter Type. Throwaway
Return Air Filter Quantity. 4
Return Air Filter Size- 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated.
Unit Configuration
RA Smoke Detector and CO2 Sensor
Direct Drive-EcoBlue-Medium Static
Al/Cu-Al/Cu-Louvered Hail Guards
7-Eleven Special Controls and Sensors
Enthalpy Ultra Low Leak Econo w/Baro Relief
Hinged Panels and Unpowered Convenience Outlet
Non-Fused Disconnect
Standard Packaging
Warranty Information
5-Year compressor parts(STD.)
1-Year parts(STD.)
Complete Unit Year 2-5 Parts&Carrier CCS Labor
Complete Unit 1st Year Carrier CCS Labor
Compressor Year 6-10 Parts Only
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
50GCQMO6F2M5-SW4C0 Rooftop Unit 2
Base Unit
RA Smoke Detector and CO2 Sensor
Direct Drive-EcoBlue-Medium Static
Al/Cu-Al/Cu-Louvered Hail Guards
Hinged Panels and Unpowered Convenience Outlet
Non-Fused Disconnect
7-11 Models, Ultra LOW LEAK EconoMi$er2 enthalpy economizer
with barometric relief.
Field Installed Accessories
CRSDTEST001A00 Smoke detector remote test/Reset/Alarm indicator kit 2
CRPWREX7002A00 Modulating Power Exhaust(7-Eleven only) 2
CRHEATER331A00 15.8/19.3 kW 208/230-1/3-60 Volt Electric Heater 2
CRSINGLE039A00 Single Point Kit 2
Packaged Rooftop Builder 1.67 Page 4 of 10
Certified Drawing for RTU - 1-2 store 23999 A
Project:FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/202Z
Prepared By: 11:56AN
NOTES' —._ / �11 01 MOOT IS 9N PROMO IF VC C1NWT1,CONTROLS...,.w w CHILI,A,a KKURna
\� CIC THE CMM F•ii it Ll/IN i511001l0[0 eEAYim o0T101 PRt ROT cwaTIIHIE TUT'MM..,OH
1. DIMENSIONS ARE IN INCHES. DIMENSIONS NTTwJt WRITTEN COYFRT ACCEPTANCE Cf CONTRACT.
IN 1 1 ARE IN MILLIMETERS. ...........
2 CENTER OF GRAVITY UNIT J M1
9 50GC0.04 33 3/8 11 SIB CONNECTION SIZES
1 Bdll [I121 A 13/8' 1351 DIA FIELD POWER SUPPLY HOLE
3.y DIRECTION OF AIR FLOW BOGCO.OS 41 3/8 16 518 33-3/8 - -
110511 ?AN? 18481 B 2' [51]DIA POWER SUPPLY KNOCKOUT
1 B
4. 'C','"'C','" .0 ALL VIEW DRAWN USING 3RD ANGLE 50GC06 d C 131 d' fldl DIA GAUGE ACCESS PLUG D51]3/8 I[115/e21
32-Ill • p 1/8' C221 DIA FIELD CONTROL WIRING MOLE
if
18171 ECO NOYI2EA HOOD
10 Pi]DMAL) IG E 3//'-14 XPI CONDENSATE DRAIN
'_-25-S18 11031 G 2 1/2 • I611 DIA POWER SUPPLY ANOCK-DUT
[NODI
RETURN AIR
. 1 TXRU TNC-BASE CHARTO
THESE HOLES REQUIRED 9AD USE
3.. CRBTMPWNOOBA00, 009AD0
G 111NI1/ IO U8 THREADED WIRE IZE'D HOER
s^g N
- 6 'J/ a a 121/1 RETURN CONDUIT SIZE AVE SIZES 12.21
YI, AIR W I/O" 115V I/8' 122.21
µ Y 11,i n--- HORIZONTAL X I/2' 24V 7l8' 122.21
• HORIZONTAT ION N' POWER I I/B' (28.61
8
` ' i' Y J i•R 1009A001 1/2' FPi GAS I IIB' 128.61
[1121] E ALL FOR'INFO-THE-BASEPAN"FACTORY OPTION,
_ CONDENSATE 17.3/d FITTINGS FOR ONLY G.Y, d 1 ARE PROVIDED
DRAIN OPENING 1/511
? TI IN BAbEPAX SUPPLY 26-5/B 29 1/2 SUPPLY SELECT EITHER 3/4'OA I/2'
�R3 AIR 11181 AIR • FOR POWER. DEPENDING ON WIRE SIZE
;1`2 1695] HORIZONTAL
1d-I/2 12-1/2 11-1/2 SEE THOU TNE A 1 CONFIGURATION •• 100080 D1 PROVIDES 31d• !PI 1XAB CURB
13691 13181 12931 BASE CHART - FLANGE d FITTING.
6 1/4
N + ... .. 1I _. •y 11581
TO-TIN 2R 23-3//
12561 16031 12-TIE r 3-1,1
�— 2R 25 [301] 1811
16351 18-315 --
N TOP I4661
STD.
2%/5/8 COXOENSAIE
[1181 DRAIN ID-UB
[2151 I
LECTR ICA 1251
_ DISCONNECT r,i _
J
, LOCATIONCONDENSER 1- iCONTROL BOX AL OPTIONAL IA.B.G OPTIFACONALORYACCESS PANEL ACC�OS BLOWED 11-3/B 25 3/4
CRICIK
FACTORY t- INSTALLED [111] [6531
INSIALLfD - I DISCd1Xf[T� SUPPLI AIR . DTI RR �; etaNMER I ` AIRSID[
CONVENIENCEOUTLET
1302] PPP-,I6-5/0 [19112cJ M 11 6-318 -�___ \ Ill
--- I6-SIB l --- R ^ MAN® NANOLE T y [116] It 61] 6 1/ [1111 11161 ' [5391
.�11.:I11M=M�Ir�IE. 00 I 1 I t'•'_'—I ) 1 061 �r�M� FATE
11861
1951 14 3/8 2 8 4 BAROMETRIC
LEFT I1009I [682]31 RELIEF
EOM [7861 FLOW
ASUPPLY A RETURN
EA AIR
VERTICAL VERTICAL
CONFIGURATION CONFIGURATION
RIGHT
ITC CLASSIFICATION SHEET DATE SUPERCEDES REV
50GC0 04-06 SINGLE PACKAGE HEAT PUMP 18TC003351
U.S- CCCN,NSR 1 OF 3 08/15/19 -
Packaged Rooftop Builder 1.67 Page 5 of 10
Certified Drawing for RTU - 1-2 store 23999
Project: FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/20Z
Prepared By: 11:56AN
1Nf6"mr"T 19 1Nf 9M6fi11,Ulf ilillil.71"'SUONI55106 p iMiL"."*M 9MMP15
W�iK1 1 SIXMfiI.m 15 mLINS[E E91Y 1NE E9v9E54 CCXNi]M 5 IIOT 711111Y1f 541>m(7. OS
STD. UNIT CORNER CORNER COPNEi CORNER - mowiEnnni<msOff. le ElmrsmNuue eanmaacaKmel.
UNIT REIM• NE16N1 II) NEINNT 1Bl ]]EIGHT (0 WEIGHT 161 C-G. HEIGHT O r+w++W 6
LBS. KG. LDS. KG. LB5. KG. LBS. KG. LBS. KG. S 1 Z
50000*01 975 215 128 58 120 51 110 50 III 53 36 [914] 22 3/8 15681 16 1/8[1101
506C0105 590 268 162 13 191 61 131 Al 118 61 35 3/8 [0931 22 5116 15511 16 1/2 [119]
506(0.06 596 210 163 11 118 61 125 61 119 68 35 3/1i [993) Z2 5116 15511 16 Ill 11191
1-STANDARD SUIT WEIGHT IS WITHOUT ELECTRIC HEAT AND WITHOUT PACKAGING. i
FOR OTHER OPTIONS AND ACCESSORIES REFER TO THE PRODUCT DATA CATALOG.
BACK WITH ECNOMIZER
CORNER A CORNER B
e30-1/8 P. I
\ 0 BACK WITHOUT 1
• ECONOMI ZER ELBX(mIIfR 100D
7� .
/� Z \ (OPTIONAL)
/ ` OPTIONAL DOOR
/////// 'j �\
/9f7 r27 �‹ \ ,VI SWING ,
'y�/Till .111011ui1[. 0
•
'���1�h�11nkkk� l111ll11 `1 A
LEFT —
CORNER D CORNER C l — RIGHT
• X ., ,
TOP .
FRONT
•
NOTE'
1. FOR ALL WHIM CLEARANCES LOCAL CODES OR JURISDICTIONS NAT PREVAIL.
U.ESERNIICE
i SERVICE N1714 SERVE W17k OPB KIING
cw
SURFACE COEl00TNE BARRER NONCOFOIICTIVE BARREN CLEAAA/4CE
= ..-ILL, 1L=C FROM 48 [1219mm] 36 1914mm] 18 [457mm]
l-- ^ LEFT 48 [12'9mml 12 C1067mm1 18 [457nm]
I• l L7 I L..,„,..,.l L_ I I (DO: I. BACK W/0 ECON 48 [12''9mml /2 [1067mm1 18 [457mm]
BACK N/ECON 36 1914mm) 36 1914mm] 18 [457mm]
WONT 36 1914mml 36 1914mm1 18 [457mm]
FRONT TOP 72 [1829mml /2 118291n81 72 C1829mm]
ITC CLASSIFICATION SHEET DATE SDPERCEDES REV
506C0 04-06 SINGLE PACKAGE HEAT PUMP 48T6003351 _
U.S. ECCN:NSR 2 OF 3 08/15/19 -
Packaged Rooftop Builder 1.67 Page 6 of 10
Certified Drawing for RTU - 1-2 store 23999
Project: FM-23999 Tigard, OR(12045 SW Hall Blvd) 08/08/2022.
Prepared By: 11:56AN
�IrIKrYY WIYM Enr E WffNrzY a a( aa aE ni1YL[FaMI4a
LUp
UrDnD-.UMW!rpnEE
Lasar.
1-1 la r
[18051
/� `,,`11 (INSIDE THE BASE RA[.6 BX[Ril
\\D.... 2�' T� .auz �A,
��
� ( ISi1114
L
� 11.1/A 0 1 �� 1Xa1 zz 1
[1001 ^ �� L251
/4''1%' 't ti: 0„,,-,'
(INSIDE BA]E04 DE
BASE AA IL61 _ 1 _
�[ c �GGG��� / L f821 118]
L
F 2X 1-3i6
6]
3-1/8
[991
INSIDE BASERAIL DIMENSIONS DETAIL C
BOTTOM TYP 4 PLCS
. r I
FILTER ACCESS PANEL CONDENSER
COIL CONDENSER 100E-LES 61 tONP CONTROL B0H INDOOR BLOWER
ACCESS COIL ACCESS PANEL ACCESS PANEL
• . PANE,.
•
INDOOR COIL O
ACCESS PANEL I
Eg _ SEE DETAIL C
O I I i I N J I f 1 j p j I 1 I I e=--p 1.; I f I L11 �1 1 1 100..
LEFT
BACK 2-3/6
3-1/4 5953/8 161.51
162.0] H509.01 l 1/8 TYP
[1110.11 CURB
FRONT WIDTH
ITC CLASSIFICATION SHEET DATE SUPERCEOES - REV
U.S. ECCX NSA 3 OF 3 08115l19 5030 04-06 SINGLE PACAAGE HEAT PUMA 48TC003351
Packaged Rooftop Builder 1.67 Page 7 of 10
Performance Summary For RTU - 1-2 store 23999
Project: FM-23999 Tigard, OR(12045 SW Hall Blvd) 08/08/2022
Prepared By: 11:56AN
Part Number:50GCQM06F2M5-SW4C0
ARI SEER- 16.20
Base Unit Dimensions
Unit Length- 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
RA Smoke Detector and CO2 Sensor 9 lb
Al/Cu-Al/Cu-Louvered Hail Guards: 17 lb
7-Eleven Special Controls and Sensors. 2 lb
Enthalpy Ultra Low Leak Econo w/Baro Relief. 37 lb
Hinged Panels and Unpowered Convenience Outlet: 9 lb
Non-Fused Disconnect 5 lb
Accessories
Modulating Power Exhaust(7-Eleven only): 177 lb
15.8/19.3 kW 208/230-1/3-60 Volt Electric Heater 10 lb
Single Point Kit 10 lb
Total Operating Weight: 872 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge' Vertical
Fan Drive Type' Belt
Actual Airflow: 2000 CFM
Site Altitude. 413 ft
Cooling Performance
Condenser Entering Air DB• 95.0 F
Evaporator Entering Air DB. 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.68 BTU/lb
Evaporator Leaving Air DB• 57.3 F
Evaporator Leaving Air WB• 57.2 F
Evaporator Leaving Air Enthalpy 24.67 BTU/lb
Gross Cooling Capacity: 62.10 MBH
Gross Sensible Capacity' 48.40 MBH
Compressor Power Input: 4.24 kW
Coil Bypass Factor' 0.039
Heating Performance
Outdoor Ambient Temperature- 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB• 95.9 F
Total Heating Capacity 55.16 MBH
Integrated Heating Capacity 55.16 MBH
Heating Power Input 3.45 kW
High Temperature COP: 3.9
Low Temperature COP: 2.4
HSPF: 8.3
Electric Heating Capacity: 15.80 kW
Unit Leaving Air Temp. 121.3 F
Supply Fan
External Static Pressure. 1.00 in wg
Options/Accessories Static Pressure
Electric Heaters: 0.18 in wg
Packaged Rooftop Builder 1.67 Page 8 of 10
Performance Summary For RTU - 1-2 store 23999
Project: FM-23999 Tigard, OR(12045 SW Hall Blvd) 08/08/20Z
Prepared By: 11:56AN
Economizer- 0.12 in wg
Power Exhaust (Fan Data Includes Drop)
Wet Coil: 0.10 in wg
Total Application Static(ESP+ Unit Opts/Acc.)• 1.39 in wg
Fan RPM- 2267
Fan Power 1.23 BHP
NOTE: Selected IFM RPM Range: 1228-2390
Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated.
Power Exhaust
Return Duct Static- 0.41 in wg
Max.Air To Exhaust 494 CFM
Electrical Data
Voltage Range: 187-253
Compressor#1 RLA- 16.5
Compressor#1 LRA- 110
Actual Electric Heater kW: 15.8
Electric Heater FLA- 43.8
Indoor Fan Motor Type- MED
Indoor Fan Motor FLA- 8.6
Power Supply MCA: 78
Power Supply MOCP(Fuse or HACR)• 80
Disconnect Size FLA- 71
Disconnect Size LRA: 136
Electrical Convenience Outlet: None
Power Exhaust[Kit Qty/FLA(ea kit)]- 1 /9.5
Outdoor Fan [Qty I FLA(ea)]: 1/1.5
Electric Heater Part Number: 331A
Electric Heater Number of Stages- 2
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 94.5 89.7 85.6
125 Hz 86.1 81.8 84.7
250 Hz 80.1 73.3 80.5
500 Hz 76.0 68.7 76.0
1000 Hz 73.1 70.3 72.4
2000 Hz 71.2 62.3 68.0
4000 Hz 66.1 55.0 62.8
8000 Hz 61.5 49.3 59.3
A-Weighted 79.7 74.2 79.0
Packaged Rooftop Builder 1.67 Page 9 of 10
Performance Summary For RTU - 1-2 store 23999
Project: FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/2022
Prepared By: 11:56AN
Fan Curve
2.0 300 RPM
- 2100 RPM 50b RPM 2700 RPM
�'1900 RPM 2900 RP
1.8 1 Ae \
1700 fp
1.6 ��
1300 1 M \
1.4 \�� �
� - 200 BHP-,
c 1.2
N 1100•-M �-„
:C
N 1.0
th
C. 0.8 \\N 1.50 BH
tTi soo M \
0.6 \
0.4 Ail \ \\
0.2
-
0.50 BH,EIL 1
0.0 I I I I I I I I I I I
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
Airflow(CFM-thousands)
RPM=2267 BHP=1.23 Maximum RPM=2836 Maximum BHP=3.00
SC-System Curve RP-Rated Point
Packaged Rooftop Builder 1.67 Page 10 of 10