Loading...
Specifications (12) . MQC2022- 034q3 k 1 M IVY TM RIPPEY Tigard,Oregon 97223 7650 S.W.Beveland St. ECECONSULTING ENGINEERS Phone: (503}443-3900 �:S,"R Z 2023 Fax. (503)443-3700 cm( OF TiCaAlp BUILDING DIVISIpN STRUCTURAL CALCULATIONS S3RUCTLink PROJECT: COOLSYS-12045 SW HALL BLVD.-RTUs \5,&E0 P R 0 fEs f/o �,::, 41.1GIN 4 49! LOCATION: 12045 SW HALL BLVD, / BsrzPEt TIGARD,OR 97223 K/a// CLIENT: COOLSYS . OREGON , d oti DATE: JANUARY 26,2022 -1, liCH 9, 2 \� yG'4 XY l E W EZ\E� PROJECT NUMBER: 23008 EXPIRES: 6-30-24 TABLE OF CONTENTS: ITEM SHEET NUMBER GENERAL NOTES N 1 DETAIL SIC 1 -3 CALCULATIONS C 1-6 DESCRIPTION: THIS DESIGN PACKAGE INCLUDES DETAILS AND CALCULATIONS FOR THE SUPPORT OF(2)REPLACEMENT ROOFTOP MECHANICAL UNITS. GENERAL STRUCTURAL NOTES CODE REOUIREMENTS• CONFORM TO THE 2018 INTERNATIONAL BUILDING CODE AS AMENDED BY THE 2019 OREGON STRUCTURAL SPECIALTY CODE, REFERENCED HEREAFTER AS IBC DESIGN CRITERIA' DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE IBC. IN ADDITION TO THE DEAD LOADS,THE FOLLOWING LOADS WERE USED FOR DESIGN,WITH LIVE LOADS REDUCED PER IBC: UNIT WEIGHT: RTU 1&2=531 LB ROOF DEAD LOAD: 12.5 PSF ROOF SNOW LOAD:25 PSF WIND SPEED:97 MPH(3-SECOND GUST),EXPOSURE:C SEISMIC IMPORTANCE FACTOR le: 1.0 SITE CLASS:D(ASSUMED) SDS 0.686 ap=2.5,Rp=6.0 EXISTING CONDITIONS: THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,DIMENSIONS AND ELEVATIONS. TUB CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES FROM CONDITIONS SI IOWN ON THE DRAWINGS PRIOR TO THE START OF THE WORK. TEMPORARY CONDITIONS: THE CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL STABILITY OF THE NEW AND EXISTING STRUCTURES AND WALLS DURING CONSTRUCTION. THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER THE FINAL CONFIGURATION ONLY. MECHANICAL: THE CONTRACTOR SHALL COORDINATE SEISMIC RESTRAINTS OF ELECTRICAL EQUIPMENT,MECHANICAL,PLUMBING,FIRE SPRINKLER, MACHINERY,AND ASSOCIATED PIPING WITH THE STRUCTURE. ANY CONNECTIONS TO STRUCTURE NOT CONFORMING TO SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION(SMACNA),OR SPECIFICALLY DETAILED ON THE MECHANICAL ENGINEER'S DRAWINGS,SHALL BE DESIGNED IN ACCORDANCE OF THESE GENERAL NOTES,BY AN ENGINEER REGISTERED IN THE STATE OF OREGON,AND SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION. TM RIPPPY Co — �1 Consulting Engineers By: Al' Date: 7650 SW Beveland Street Chk By: Date: Suite 100 CoolSys - 12045 SW Hall Blvd - RTUs Job#: 23008 Tigard,Oregon 97223 --- s Phone:(503)443-3900 Sheet: NI Of TR I./. 4 A i 41..c,'' eve, 0 4 'a . . / \\\\. t � I I I II I I I SIM, RTU 1 1 SK3 ' (E) OPEN WEB I I o TRUSSES I I ti I I I I I I I I I I 1 I \ I / 2 EXISTING 2X4 BLKG. ALIGN WITH THE EXT. CURB. NOTES: - INSTALL ALL NEW FRAMING PRIOR TO INSTALLING CURB. -ALL WATERPROOFING IS BY OTHERS. - EXACT LOCATION PER MECHANICAL PLANS. et) FRAMING PLAN AT RTU (41, N.T.S. 1 f \/ 1 K MRII PE1. nY, AI- DATE .L X J. CONSULTING ENGINEERS • CHI(BY DATE 7650 S.W.lieveland St,Suite 100 COOLSYS - 12045 SW HALL BLVD. - RTUs 1013 NO 23008 Tigard,Oregon 97223 ,Phone(503)443-3900 SNEE (2_of I'-0 ', TYP. PLATE CONN. LOCATION TYP. .4 8 TOTAL 3''t "' CLIP EQ.SPACED ElOR TIIER LOCATION, TYP. BOTH WAYS TYP. Ire 6„ R I-- NEW RTU 16 GA.CLIP 16 CAKE snsuicCLIP we. • 4 PLAN NEW MECHANICAL N.T.S. UNIT. 16 GA.CLIP W/(8)#10 x 3/4" GALVANIZED TEK SCREWS, i; (4)CLIPS REQ'D.SEE DETAIL (PLAN1'VIEW)FOR CLIP ' LO LOCAATION. NEW CURB ADAPTOR (DESIGN BY OTHERS) #10 x 1 1/2"GALVANIZED TEK SCREWS @ 2'-0"0/C.AND 6" FROM ENDS.(4)MIN.PER SIDE,TYP. 11 I EXISTING CURB ' TO REMAIN. EXISTING I SLOT PLYWOOD SHEATHING AND LEVELING CURB PROVIDE 16 GA PLATE X 8"X REQ'D WI ASSUMED (2)#10X2 1/2"SCREWS @6"0/C TO THE TRUSS/BLOCKING AND(4)#10 X 3/4" SCREWS TO CURB mom (E)OPEN WEB TRUSSES OR BLOCKING PER PLAN SECTION AT CUiRE3 NOTE:1.FLASHING AND INSULATION NOT SHOWN FOR111, N.T.S. CLARITY. 2.ALL SCREWS SHOULD BE MIN.6"FROM THE STEEL PINS IN THE TRUSSES. /IV 1:\. TM RIPPEY BY AP CONSULTING ENGINEERS CM(BY DATE 7650 SW Beveland,Suite 100 CoolSys - 12045 SW Hall Blvd - RTU JOB N 22008 Tigard,Oregon 97223 Phone:(503)443-3900 SHEET SK3 or Fax:(503)443-3700 I ) RE PU+f_EvitvU h0 - 1' Vs) E: e tv-A ( . R"ch J i () 5.S )tc, t So 16 CV:--'0R, l.ii('P A 11ApTOR) i too rZ C-UI _. -711 ►1� i (.E) U turl tn)E = 8-1s f l{a l Ex T. Gur2.P. ) TR F RE-c>LAC_ nrentT UN-A'S r V-'t- (IiCj_. Less -THAt,) ;CE ) 1-1-4E, () F C''Atkl C e.11 SNs.rteAt it , f JoF DeAb 1/,o A 0 - RnbF = 3 P-S- ?t-Y woof) • e 2.0 7'GS Mtc.,I c Lt_ = 1.5 psi e•usSes 5►.,su . b .s Ps� �p�7LtJ1! _ 1• n ‘ s INtx..)p r ,C- t) cS� sps w 0 g /r TM RIPPEY BY DAIL CONSULTING ENGINEERS CHK BY DATE 7650 S.W. Beveland St, Suite 100 Caa1„i,s -) 26 e15 Svt1 Na t t BWp r2TU ioBMO 23Ob Tigard,Oregon 97223 Phone(503) 443-3900 sHEETC( OF ASCE ASCE 7 Hazards Report AMERICAN=ETV OF MIL MOWERS Address: Standard: ASCE/SEI 7-16 Latitude: 45.387551 19100 Willamette Dr Risk Category: 11 Longitude: 0 -11722.9.62 ft(NAVD 88)4 0 9 8 9 West Linn, Oregon Soil Class: D - Default(see Elevation:97068 Section 11.4.3) , _- , ,:,,,,—..yr.1 , \ ' ,••• I i • ' I . ' 4" Robit 1% nyood a '""k •, • ' . <:. , e % T' ' • ' I ' II, % ' ..k ' ' ' : - '• 1.''' : 7 o ,4.q'ee 6.LOIC. 8 -4+ - 4"D .* L". . — .'• - ,1,t 0, 11.-A1' ' 'r ISt‘ IuI pI, I ' ' -,,• - %,,-, 0 •6 l','?‘is • r •‘, , .1„„,4-,. • •• • -, b Ged.al..a0 ' ,' ' ' n . . • y . .s. '' • 'Itz., ' : ' 1; .04(04 City • _• . , , I 1 \'lb .„,,,„,,,,,, I ArIE VAiLEY '..: T" 1.1 I hmiakt-I ,nt ..,,, • • "-,'- ! •----•,'I i* ;. /clielti, • ' ' ..i , , 64„ • , j ,. •,i•.x' , .0, / . : • t ' • g / ,•' • :,-rr^ ', r., I lilt.lSi,„ '/' ''' -4 }''' '' ., . - Thu Jan 19 2023 1141 Page 1 of 3 haus://asce7hazardtoolonline/ AscE. AMEFN.AN SOCIETYOF LMl aiGIVEFRs Seismic Site Soil Class: D-Default(see Section 11.4.3) Results: Ss ; 0.858 SDI : N/A Si : 0.383 TL : 16 Fe : 1.2 PGA : 0.386 F, : N/A PGA M : 0.469 SMs : 1.03 FpGA : 1.214 SMI : N/A le : 1 SOS 0.686 C„ : 1.229 Ground motion hazard analysis may he required. See ASCE/SEI 7-16 Section 11.4.8. Data Accessed: Thu Jan 19 2023 Date Source: USGS Seismic Desian Macs C-4 htiss://asce7hazardtool.online/ Page 2 of 3 Thu Jan 19 2023 Wind and Seismic Loads on Mechanical Unit Based on ASCE 7-16 Section 29.4.1 and 13.3.1 Seismic Parameters SDS= 0.69 Spectral acceleration 1p= 1.00 Importance factor Rp- 6.0 Component response modification factor a = 2.5 Component amplification factor Wind Parameters V= 98.00 mph Ultimate Wind Speed 3-Second Gust C Exposure Category Building Parameters Mechanical Unit Parameters Curb Parameters h= 16.0 ft Wt= 711.0 lbs Height= 20.00 in Building Depth = 41.0 ft Height= 33.40 in Width= 48.00 in Building Width= 60.0 ft Width= 46.60 : in Length= 72.00 in Length= 74.40 in Loading Summary(all values in ASD) W Uplift =401 lbs Wt=711 lbs E= 171lbs ,� YY m W = 5741bs co . v T N � C 4ft CONSULTING ENGINEERS I Net Wind = 306 lbs T Net Seismic=-49 lbs TM RIPPEY • Performance Summary For RTU - 1-2 store 23999 Project: FM-23999 Tigard,OR(12045 SW Hall Blvd)- 09/21/2022 Prepared By: 12:45PM Part Number:50FC-A06A1A5-0A0A0 ARI SEER. 14.00 Base Unit Dimensions Unit Length. 74.4 in Unit Width: 46.6 in Unit Height: 33.4 in Operating Weight Base Unit Weight: 511 lb Accessories 15.8/19.3 kW 208/230-1/3-60 Volt Electric Heater 10 lb Single Point Kit' 10 lb Total Operating Weight: 531 lb Unit Unit Voltage-Phase-Hertz: 208-3-60 Air Discharge' Vertical Fan Drive Type- Vane Axial Actual Airflow: 2000 CFM Site Altitude' 0 ft Cooling Performance Condenser Entering Air DB' 95.0 F Evaporator Entering Air DB: 80.0 F Evaporator Entering Air WB: 67.0 F Entering Air Enthalpy: 31.44 BTU/lb Evaporator Leaving Air DB' 59.3 F Evaporator Leaving Air WB' 57.7 F Evaporator Leaving Air Enthalpy' 24.85 BTU/lb Gross Cooling Capacity; 59.31 MBH Gross Sensible Capacity' 44.73 MBH Compressor Power input: 4.14 kW Coil Bypass Factor 0.163 Heating Performance Heating Airflow' 2000 CFM Entering Air Temp: 70.0 F Leaving Air Temp' 95.0 F Electric Heating Capacity: 15.80 kW Supply Fan External Static Pressure' 1.00 in wg Options/Accessories Static Pressure Electric Heaters: 0.18 In wg Total Application Static(ESP+Unit Opts/Acc.)• 1.18 in wg Fan RPM. 2138 Fan Power' 1.05 BHP NOTE' Selected IFM RPM Range: 215.2150 Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated. Electrical Data Voltage Range: 187-253 Compressor#1 RLA• 16 Compressor#1 LRA. 110 Actual Electric Heater kW: 15.8 Electric Heater FLA• 43.8 Indoor Fan Motor Type- STD C- Packaged Rooftop Builder 1.69 Page 8 of 10 Unit 1 Unit Type:e. PackagedE Unit �`fi�3` Unit 1 Vixxo Asset Tag Number: 819644 11!',! L ii 2023 Unit 1 Make: Trane CITY OF TIGARD BUILDING DIVISION Unit 1 Model: WCD060C300BD Unit 1 Serial Number: Z06102039D Unit 1 Manufacture Year: 2001 Unit 1 Condition: Not Running Unit 1 Reason not running: Bad compressor Unit 1 size: 5-ton Unit 1 Heat Type: Heat Pump Unit 1 Voltage: 208/230v-3P Unit 1 Control Type: Thermostat Unit 1 air flow configuration: Vertical return,Vertical Supply, both through curb Unit 1 mounted on: Standard roof curb with curb adapter Unit 1 Provide photo of unit equipment tag: 4l �,, r t ti l Nam. 4< i414. E P t .4!urname lttstwf—" '+ 9a 33 image 3566.jpg Unit 1 Provide 2 photos of unit from opposite corners of unit: • ME yy y} A 10. • frrli 29 image 6151.jpg image 406jpg Unit 1 Ductwork configuration: Concentric 8 Unit 2 Unit Type: Packaged Unit Unit 2 Vixxo Asset Tag Number 883507 Unit 2 Make: Trane Unit 2 Model: Wcd060c300BD Unit 2 Serial Number: Z06102672D Unit 2 Manufacture Year: 2001 Unit 2 Condition: Fair Unit 2 size: 5-ton Unit 2 Heat Type: Heat Pump Unit 2 Voltage: 208/230v-3P Unit 2 Control Type: Thermostat Unit 2 air flow configuration: Vertical return,Vertical Supply, both through curb Unit 2 mounted on: Standard roof curb with curb adapter Unit 2 Provide photo of unit equipment tag: ..... '1 i.mow x`c ia.mFMR a •:•• iI�Y.w 17: I. Me xb or itmy.gp- � a Of $6 n.{k x �f4.*" iiTT++CCRR So %� s. ' r, �t 286 image 7304.jpg Unit 2 Provide 2 photos of unit from opposite corners of unit: 9 p , r i. Nat x '3 287 image 1839 jpg image 8159jpg Unit 2 Ductwork configuration: Concentric 10 Carr;Dm SUBMITTAL Project FM - 23999 Tigard, OR (12045 SW Hall Blvd) Date Monday, August 8, 2022 Unit Report For RTU - 1-2 store 23999 Project: FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/2022 Prepared By: 11:56AN Unit Parameters Dimensions(R.in.)&Weight(lb.)*** Unit Model. 50GCQMO6F2M5-SW4C0 Unit Length. 6'2.375" Unit Size- 06 (5 Tons) Unit Width. 3'10.625" Volts-Phase-Hertz. 208-3-60 Unit Height: 3'5.375" Heating Type• Heat Pump ^'^ Total Operating Weight: 872 lb Duct Cfg: Vertical Supply/Vertical Return Two Stage Cooling Models Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights,refer to appropriate product data catalog. Lines and Filters Return Air Filter Type. Throwaway Return Air Filter Quantity. 4 Return Air Filter Size- 16 x 16 x 2 Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated. Unit Configuration RA Smoke Detector and CO2 Sensor Direct Drive-EcoBlue-Medium Static Al/Cu-Al/Cu-Louvered Hail Guards 7-Eleven Special Controls and Sensors Enthalpy Ultra Low Leak Econo w/Baro Relief Hinged Panels and Unpowered Convenience Outlet Non-Fused Disconnect Standard Packaging Warranty Information 5-Year compressor parts(STD.) 1-Year parts(STD.) Complete Unit Year 2-5 Parts&Carrier CCS Labor Complete Unit 1st Year Carrier CCS Labor Compressor Year 6-10 Parts Only NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods. Ordering Information Part Number Description Quantity 50GCQMO6F2M5-SW4C0 Rooftop Unit 2 Base Unit RA Smoke Detector and CO2 Sensor Direct Drive-EcoBlue-Medium Static Al/Cu-Al/Cu-Louvered Hail Guards Hinged Panels and Unpowered Convenience Outlet Non-Fused Disconnect 7-11 Models, Ultra LOW LEAK EconoMi$er2 enthalpy economizer with barometric relief. Field Installed Accessories CRSDTEST001A00 Smoke detector remote test/Reset/Alarm indicator kit 2 CRPWREX7002A00 Modulating Power Exhaust(7-Eleven only) 2 CRHEATER331A00 15.8/19.3 kW 208/230-1/3-60 Volt Electric Heater 2 CRSINGLE039A00 Single Point Kit 2 Packaged Rooftop Builder 1.67 Page 4 of 10 Certified Drawing for RTU - 1-2 store 23999 A Project:FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/202Z Prepared By: 11:56AN NOTES' —._ / �11 01 MOOT IS 9N PROMO IF VC C1NWT1,CONTROLS...,.w w CHILI,A,a KKURna \� CIC THE CMM F•ii it Ll/IN i511001l0[0 eEAYim o0T101 PRt ROT cwaTIIHIE TUT'MM..,OH 1. DIMENSIONS ARE IN INCHES. DIMENSIONS NTTwJt WRITTEN COYFRT ACCEPTANCE Cf CONTRACT. IN 1 1 ARE IN MILLIMETERS. ........... 2 CENTER OF GRAVITY UNIT J M1 9 50GC0.04 33 3/8 11 SIB CONNECTION SIZES 1 Bdll [I121 A 13/8' 1351 DIA FIELD POWER SUPPLY HOLE 3.y DIRECTION OF AIR FLOW BOGCO.OS 41 3/8 16 518 33-3/8 - - 110511 ?AN? 18481 B 2' [51]DIA POWER SUPPLY KNOCKOUT 1 B 4. 'C','"'C','" .0 ALL VIEW DRAWN USING 3RD ANGLE 50GC06 d C 131 d' fldl DIA GAUGE ACCESS PLUG D51]3/8 I[115/e21 32-Ill • p 1/8' C221 DIA FIELD CONTROL WIRING MOLE if 18171 ECO NOYI2EA HOOD 10 Pi]DMAL) IG E 3//'-14 XPI CONDENSATE DRAIN '_-25-S18 11031 G 2 1/2 • I611 DIA POWER SUPPLY ANOCK-DUT [NODI RETURN AIR . 1 TXRU TNC-BASE CHARTO THESE HOLES REQUIRED 9AD USE 3.. CRBTMPWNOOBA00, 009AD0 G 111NI1/ IO U8 THREADED WIRE IZE'D HOER s^g N - 6 'J/ a a 121/1 RETURN CONDUIT SIZE AVE SIZES 12.21 YI, AIR W I/O" 115V I/8' 122.21 µ Y 11,i n--- HORIZONTAL X I/2' 24V 7l8' 122.21 • HORIZONTAT ION N' POWER I I/B' (28.61 8 ` ' i' Y J i•R 1009A001 1/2' FPi GAS I IIB' 128.61 [1121] E ALL FOR'INFO-THE-BASEPAN"FACTORY OPTION, _ CONDENSATE 17.3/d FITTINGS FOR ONLY G.Y, d 1 ARE PROVIDED DRAIN OPENING 1/511 ? TI IN BAbEPAX SUPPLY 26-5/B 29 1/2 SUPPLY SELECT EITHER 3/4'OA I/2' �R3 AIR 11181 AIR • FOR POWER. DEPENDING ON WIRE SIZE ;1`2 1695] HORIZONTAL 1d-I/2 12-1/2 11-1/2 SEE THOU TNE A 1 CONFIGURATION •• 100080 D1 PROVIDES 31d• !PI 1XAB CURB 13691 13181 12931 BASE CHART - FLANGE d FITTING. 6 1/4 N + ... .. 1I _. •y 11581 TO-TIN 2R 23-3// 12561 16031 12-TIE r 3-1,1 �— 2R 25 [301] 1811 16351 18-315 -- N TOP I4661 STD. 2%/5/8 COXOENSAIE [1181 DRAIN ID-UB [2151 I LECTR ICA 1251 _ DISCONNECT r,i _ J , LOCATIONCONDENSER 1- iCONTROL BOX AL OPTIONAL IA.B.G OPTIFACONALORYACCESS PANEL ACC�OS BLOWED 11-3/B 25 3/4 CRICIK FACTORY t- INSTALLED [111] [6531 INSIALLfD - I DISCd1Xf[T� SUPPLI AIR . DTI RR �; etaNMER I ` AIRSID[ CONVENIENCEOUTLET 1302] PPP-,I6-5/0 [19112cJ M 11 6-318 -�___ \ Ill --- I6-SIB l --- R ^ MAN® NANOLE T y [116] It 61] 6 1/ [1111 11161 ' [5391 .�11.:I11M=M�Ir�IE. 00 I 1 I t'•'_'—I ) 1 061 �r�M� FATE 11861 1951 14 3/8 2 8 4 BAROMETRIC LEFT I1009I [682]31 RELIEF EOM [7861 FLOW ASUPPLY A RETURN EA AIR VERTICAL VERTICAL CONFIGURATION CONFIGURATION RIGHT ITC CLASSIFICATION SHEET DATE SUPERCEDES REV 50GC0 04-06 SINGLE PACKAGE HEAT PUMP 18TC003351 U.S- CCCN,NSR 1 OF 3 08/15/19 - Packaged Rooftop Builder 1.67 Page 5 of 10 Certified Drawing for RTU - 1-2 store 23999 Project: FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/20Z Prepared By: 11:56AN 1Nf6"mr"T 19 1Nf 9M6fi11,Ulf ilillil.71"'SUONI55106 p iMiL"."*M 9MMP15 W�iK1 1 SIXMfiI.m 15 mLINS[E E91Y 1NE E9v9E54 CCXNi]M 5 IIOT 711111Y1f 541>m(7. OS STD. UNIT CORNER CORNER COPNEi CORNER - mowiEnnni<msOff. le ElmrsmNuue eanmaacaKmel. UNIT REIM• NE16N1 II) NEINNT 1Bl ]]EIGHT (0 WEIGHT 161 C-G. HEIGHT O r+w++W 6 LBS. KG. LDS. KG. LB5. KG. LBS. KG. LBS. KG. S 1 Z 50000*01 975 215 128 58 120 51 110 50 III 53 36 [914] 22 3/8 15681 16 1/8[1101 506C0105 590 268 162 13 191 61 131 Al 118 61 35 3/8 [0931 22 5116 15511 16 1/2 [119] 506(0.06 596 210 163 11 118 61 125 61 119 68 35 3/1i [993) Z2 5116 15511 16 Ill 11191 1-STANDARD SUIT WEIGHT IS WITHOUT ELECTRIC HEAT AND WITHOUT PACKAGING. i FOR OTHER OPTIONS AND ACCESSORIES REFER TO THE PRODUCT DATA CATALOG. BACK WITH ECNOMIZER CORNER A CORNER B e30-1/8 P. I \ 0 BACK WITHOUT 1 • ECONOMI ZER ELBX(mIIfR 100D 7� . /� Z \ (OPTIONAL) / ` OPTIONAL DOOR /////// 'j �\ /9f7 r27 �‹ \ ,VI SWING , 'y�/Till .111011ui1[. 0 • '���1�h�11nkkk� l111ll11 `1 A LEFT — CORNER D CORNER C l — RIGHT • X ., , TOP . FRONT • NOTE' 1. FOR ALL WHIM CLEARANCES LOCAL CODES OR JURISDICTIONS NAT PREVAIL. U.ESERNIICE i SERVICE N1714 SERVE W17k OPB KIING cw SURFACE COEl00TNE BARRER NONCOFOIICTIVE BARREN CLEAAA/4CE = ..-ILL, 1L=C FROM 48 [1219mm] 36 1914mm] 18 [457mm] l-- ^ LEFT 48 [12'9mml 12 C1067mm1 18 [457nm] I• l L7 I L..,„,..,.l L_ I I (DO: I. BACK W/0 ECON 48 [12''9mml /2 [1067mm1 18 [457mm] BACK N/ECON 36 1914mm) 36 1914mm] 18 [457mm] WONT 36 1914mml 36 1914mm1 18 [457mm] FRONT TOP 72 [1829mml /2 118291n81 72 C1829mm] ITC CLASSIFICATION SHEET DATE SDPERCEDES REV 506C0 04-06 SINGLE PACKAGE HEAT PUMP 48T6003351 _ U.S. ECCN:NSR 2 OF 3 08/15/19 - Packaged Rooftop Builder 1.67 Page 6 of 10 Certified Drawing for RTU - 1-2 store 23999 Project: FM-23999 Tigard, OR(12045 SW Hall Blvd) 08/08/2022. Prepared By: 11:56AN �IrIKrYY WIYM Enr E WffNrzY a a( aa aE ni1YL[FaMI4a LUp UrDnD-.UMW!rpnEE Lasar. 1-1 la r [18051 /� `,,`11 (INSIDE THE BASE RA[.6 BX[Ril \\D.... 2�' T� .auz �A, �� � ( ISi1114 L � 11.1/A 0 1 �� 1Xa1 zz 1 [1001 ^ �� L251 /4''1%' 't ti: 0„,,-,' (INSIDE BA]E04 DE BASE AA IL61 _ 1 _ �[ c �GGG��� / L f821 118] L F 2X 1-3i6 6] 3-1/8 [991 INSIDE BASERAIL DIMENSIONS DETAIL C BOTTOM TYP 4 PLCS . r I FILTER ACCESS PANEL CONDENSER COIL CONDENSER 100E-LES 61 tONP CONTROL B0H INDOOR BLOWER ACCESS COIL ACCESS PANEL ACCESS PANEL • . PANE,. • INDOOR COIL O ACCESS PANEL I Eg _ SEE DETAIL C O I I i I N J I f 1 j p j I 1 I I e=--p 1.; I f I L11 �1 1 1 100.. LEFT BACK 2-3/6 3-1/4 5953/8 161.51 162.0] H509.01 l 1/8 TYP [1110.11 CURB FRONT WIDTH ITC CLASSIFICATION SHEET DATE SUPERCEOES - REV U.S. ECCX NSA 3 OF 3 08115l19 5030 04-06 SINGLE PACAAGE HEAT PUMA 48TC003351 Packaged Rooftop Builder 1.67 Page 7 of 10 Performance Summary For RTU - 1-2 store 23999 Project: FM-23999 Tigard, OR(12045 SW Hall Blvd) 08/08/2022 Prepared By: 11:56AN Part Number:50GCQM06F2M5-SW4C0 ARI SEER- 16.20 Base Unit Dimensions Unit Length- 74.4 in Unit Width: 46.6 in Unit Height: 41.4 in Operating Weight Base Unit Weight: 596 lb RA Smoke Detector and CO2 Sensor 9 lb Al/Cu-Al/Cu-Louvered Hail Guards: 17 lb 7-Eleven Special Controls and Sensors. 2 lb Enthalpy Ultra Low Leak Econo w/Baro Relief. 37 lb Hinged Panels and Unpowered Convenience Outlet: 9 lb Non-Fused Disconnect 5 lb Accessories Modulating Power Exhaust(7-Eleven only): 177 lb 15.8/19.3 kW 208/230-1/3-60 Volt Electric Heater 10 lb Single Point Kit 10 lb Total Operating Weight: 872 lb Unit Unit Voltage-Phase-Hertz: 208-3-60 Air Discharge' Vertical Fan Drive Type' Belt Actual Airflow: 2000 CFM Site Altitude. 413 ft Cooling Performance Condenser Entering Air DB• 95.0 F Evaporator Entering Air DB. 80.0 F Evaporator Entering Air WB: 67.0 F Entering Air Enthalpy: 31.68 BTU/lb Evaporator Leaving Air DB• 57.3 F Evaporator Leaving Air WB• 57.2 F Evaporator Leaving Air Enthalpy 24.67 BTU/lb Gross Cooling Capacity: 62.10 MBH Gross Sensible Capacity' 48.40 MBH Compressor Power Input: 4.24 kW Coil Bypass Factor' 0.039 Heating Performance Outdoor Ambient Temperature- 47.0 F Entering Air Indoor Coil DB: 70.0 F Leaving Air Indoor Coil DB• 95.9 F Total Heating Capacity 55.16 MBH Integrated Heating Capacity 55.16 MBH Heating Power Input 3.45 kW High Temperature COP: 3.9 Low Temperature COP: 2.4 HSPF: 8.3 Electric Heating Capacity: 15.80 kW Unit Leaving Air Temp. 121.3 F Supply Fan External Static Pressure. 1.00 in wg Options/Accessories Static Pressure Electric Heaters: 0.18 in wg Packaged Rooftop Builder 1.67 Page 8 of 10 Performance Summary For RTU - 1-2 store 23999 Project: FM-23999 Tigard, OR(12045 SW Hall Blvd) 08/08/20Z Prepared By: 11:56AN Economizer- 0.12 in wg Power Exhaust (Fan Data Includes Drop) Wet Coil: 0.10 in wg Total Application Static(ESP+ Unit Opts/Acc.)• 1.39 in wg Fan RPM- 2267 Fan Power 1.23 BHP NOTE: Selected IFM RPM Range: 1228-2390 Selection includes construction throwaway filter into the base fan curve.This filter is not MERV Rated. Power Exhaust Return Duct Static- 0.41 in wg Max.Air To Exhaust 494 CFM Electrical Data Voltage Range: 187-253 Compressor#1 RLA- 16.5 Compressor#1 LRA- 110 Actual Electric Heater kW: 15.8 Electric Heater FLA- 43.8 Indoor Fan Motor Type- MED Indoor Fan Motor FLA- 8.6 Power Supply MCA: 78 Power Supply MOCP(Fuse or HACR)• 80 Disconnect Size FLA- 71 Disconnect Size LRA: 136 Electrical Convenience Outlet: None Power Exhaust[Kit Qty/FLA(ea kit)]- 1 /9.5 Outdoor Fan [Qty I FLA(ea)]: 1/1.5 Electric Heater Part Number: 331A Electric Heater Number of Stages- 2 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics Sound Power Levels,db re 10E-12 Watts Discharge Inlet Outdoor 63 Hz 94.5 89.7 85.6 125 Hz 86.1 81.8 84.7 250 Hz 80.1 73.3 80.5 500 Hz 76.0 68.7 76.0 1000 Hz 73.1 70.3 72.4 2000 Hz 71.2 62.3 68.0 4000 Hz 66.1 55.0 62.8 8000 Hz 61.5 49.3 59.3 A-Weighted 79.7 74.2 79.0 Packaged Rooftop Builder 1.67 Page 9 of 10 Performance Summary For RTU - 1-2 store 23999 Project: FM-23999 Tigard,OR(12045 SW Hall Blvd) 08/08/2022 Prepared By: 11:56AN Fan Curve 2.0 300 RPM - 2100 RPM 50b RPM 2700 RPM �'1900 RPM 2900 RP 1.8 1 Ae \ 1700 fp 1.6 �� 1300 1 M \ 1.4 \�� � � - 200 BHP-, c 1.2 N 1100•-M �-„ :C N 1.0 th C. 0.8 \\N 1.50 BH tTi soo M \ 0.6 \ 0.4 Ail \ \\ 0.2 - 0.50 BH,EIL 1 0.0 I I I I I I I I I I I 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 Airflow(CFM-thousands) RPM=2267 BHP=1.23 Maximum RPM=2836 Maximum BHP=3.00 SC-System Curve RP-Rated Point Packaged Rooftop Builder 1.67 Page 10 of 10