Legend
OFFICE COPY >
0 - Supply Diffuser Q
co
CIIY OF TIGAF,D ° o
`i 140g6 PLAN - Return Grille Appr ,d I
I
j r N tv
(m� , Ir' Irs�= ' -c• For , the work as described in: � I""
lv O - Thermostat PEI, . NO. jry-�,ieL(,
See ! ,,tter to: Follow [ ]
- Exhaust fan
Attach [ ] 1
Job Address: lircr,0 sr...) i9e- '•
By: 13 i• Date: i l//y/j;
(E) - Existing
_ - Neck size/ CFM
"Oa I
- -- — - Volume dampers n/� • O
Latimer HVAC
CCB#220839 -
Outside Air Ventilation
AZ RP RA VBZ EZ VOZ Natural Ventilation
Room Code Max Ventilation Area Outdoor Exhaust •
Description/n Room Area Occupant Density Occupancy Factor Air Rate Breathing Zone Air Distribution Zone Outdoor Rate Exh Yes Occupancy Classification Air Distribution Configuration
umbers (SF) (People/1000 SF) (People) (CFM/Person) (CFM/SF) Ventilation(CFM) Effectiveness Airflow(CFM) (CFM) (CFM) or No Area opening(SF)
open115 950 20 15 0 285 0.8 0 0 Yes 42 Physical therapy Ceiling supply and ceiling return
consult 107 100 5 5 0.06 8.5 0.8� 10.625 0 Office space Ceiling supply and ceiling return
consult 108 100 5 5 0.06 8.5 0.81 10.625 0 Office space Ceiling supply and ceiling return
consult 109 100 5 5 0.06 8.5 0.8 10.625 0 Office space Ceiling supply and ceiling return
waiting 100 250 10 5 0.06 27.5 0.81 0 0 Yes 42 Main entry lobby Ceiling supply and ceiling return
hall 260 0 _ 0 0.06 15.6 0.8 19.5 0 Corridor Ceiling supply and ceiling return
RTU1 1760 53
studio 120 400 20 15 0 120 0.8 150 0 Physical therapy Ceiling supply and ceiling return
RR 119 50 0 0 0 0 0.8 0 70 80 Toilet room-public Ceiling supply and ceiling return
stor 117/118 220 0 0 0.12 26.4 0.8 33 0 Storage room Ceiling supply and ceiling return
LMT 116 100 5 5 0.06 8.5 0.8 10.625 0 Office space Ceiling supply and ceiling return
consult 111 100 5 5 0.06 8.5 0.81 10.625 0 Office space Ceiling supply and ceiling return
consult 113 120 5 5 0.06 10.2 0.8' 12.75 0 Office space Ceiling supply and ceiling return
off 104 100 5 5 0.06 8.5 0.8 10.625 0 Office space Ceiling supply and ceiling return
break 03 120 5 5 0.06 10.2 0.8, 12.75 0 Office space Ceiling supply and ceiling return
bull 114 140 5 5 0.06 11.9 0.8 14.875 0 Office space Ceiling supply and ceiling return
recept 105 100 30 5 0.06 21 0.8 26.25 0 Reception area Ceiling supply and ceiling return
RR 102 50 0 0 0 0 0.8 0 70 70 Toilet room-public Ceiling supply and ceiling return
RR 110 50 0 -
0 0 i) 0.81 0 70 80 Toilet room-public Ceiling supply and ceiling return
hall i0i 150 0 0 0.06 9 0.8 11.25 0 Corridor Ceiling supply and ceiling return
RTU2 1700 294 Efs 230
Ventilation Requirements-based on 2019 OMSC table 403.3
Scope of Work RTU1- aJ
Latimer HVAC will perform the following scope of work: SA= 1530 cfm Q
f-
1. Provide (3) ceiling mount exhaust fans for 2 new restrooms and laundry room. RA= 1430 cfm 5
CC
2. Ducting and air distribution modifications as drawn. OSA=100 cfm a CO 0
3• Drc fey 1/za f fb fkl/oQ. u >
Equipment Schedule RTU1- c to ao
RTU1- Existing 4-ton gas/electric package unit. 1530 CFM design. SA= 1400 cfm o C .-
RTU1- Existing 3.5-ton gas/electric package unit. 1400 CFM design. RA=1100 cfm V Ln
OSA=300 cfm
EF1- Existing restroom fan to remain. %-I
EF2- Panasonic FV05-11-80 cfm @ 0.25sp. On switch. •
Mechanical General Notes: NO EXCEPTIONS NOTED W. REJECTED [ ]
1. All steel ducting will be 26 ga minimum galvanized. Flex installed per Mfg. MAKE CORRECTIONS NOTED [ ] REVISE AND RESUBMIT [ ]
2. Heating and cooling ducting to be designed to not exceed 0.5 wc positive(supply)and 0.5 wc negative THIS REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN
(return). CONCEPT ONLY. ANY DEVIATION FROM PLANS OR SPECIFICATIONS
NOT CLEACTOR HAS NOT
3. Provide programmable thermostat.5 degree deadband minimum.7 day. Microprocessor.Set program for REEVIEW DRLRE REVIEW SHALLNOTEY �NOTONT CONSTITUUTTE A COMPLBETE CHECK OF
night energy savings. ALL DETAILED DIMENSIONS OR COUNT OR SERVE TO RELIEVE THE
CONTRACTOR OF CONTRACTUAL RESPONSIBILITY FOR ANY ERROR
4. Seal ducting with UL listed mastic or mastic tape. OR DEVIATION FROM CONTRACT DOCUMENTS.
CIDA
COMMERCIAL INDUSTRIAL DESIGN ARCHITECTURE
PORTLAND,OREGON �O. 0
REVIEWED 10/19/2022,BY myap