. r PEC PROFESSIONAL ENGINEERING CONSULTANTS,P.A. June 8,2022 Westside Surgery Center 13240 SW Pacific Hwy Portland,OR 97223 RECEIVED AUG 1 2022 Reference: Westside Surgery Center Generator Pad 13240 SW Pacific Hwy, Portland, OR 97223 CITY OF TIGARD PEC Project No.210205-000 BUILDING DIVISION To whom it may concern: This letter is written regarding the generator and fuel tank and the new support slab at the Westside Surgery Center located at 13240 SW Pacific Hwy in Portland,Oregon. It was requested that PEC perform a structural analysis to determine the required dimensions of the concrete slab and the necessary anchorage for the generator. Information provided to PEC Structural for analysis included the cutsheets for the new generator as well as information regarding the site. See Appendix A for generator locations and weights. Below is an outlined summary of PEC's findings. PEC has determined that a 6"concrete slab with(10) 5/8"diameter anchors with 4"embedment is adequate to support the new generator for all code level loads. See Appendix B for calculations of generator anchorage and concrete foundations. Contractor to review for discrepancies from dimensions and weights shown in Appendix A and notify the engineer of record if any discrepancies are found. Thank you for the opportunity to work with you on this project. Should any questions come up please do not hesitate to contact me. OFFICE COPY Sincerely, CITY OF TTGAR , . D PROFFS REV WEI) FOIL l)E COMPLIANCE Parer , 99076PE 06/08/2022 OREGON ;unit #: g �.1 ' C')C1.7 - `'9 idress: l .�a�.. c �1RY 1\2�2ti uitc #: Th' O By: Date 9- Zachary Bowden,PE PROFESSIONAL ENGINEERING CONSULTANTS,P.A. VALIDITY OF PERMIT THE ISSUANCE OF A PERMIT BASED ON CONSTRUCTION DOCUMENTS AND OTHER DATA SHALL NOT PREVENT THE CODE OFFICIAL FROM REQUIRING THE CORRECTION OF ERRORS.OSSC 105.4 351 LINDEN STREET,SUITE 100 FORT COLLINS, CO 80524 970-232-9558 www.peci.cam DESIGN CRITERIA 1: BUILDING CODE: INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION, INCLUDING LOCAL SUPPLEMENTS. THE STRUCTURE IS CLASSIFIED AS A RISK CATEGORY II FACILITY. 2. SEISMIC: SITE CLASS: D SEISMIC DESIGN CATEGORY: D SEISMIC IMPORTANCE FACTOR: 1.0 • Ss: 0.854 Si: 0.394 SDs: 0.660 SD1: 0.086 WESTSIDE SURGERY CENTER GENERATOR PAD 13240 SW PACIFIC HWY, TIGARD, OR 97223 ,<�ED PROP-4-S, GENERAL NOTES Project number 210205-000 99076PEPE 351 LINDEN STREET Date 06/08/22 06/08/2022 SUITE 100 Drawn by BCH �- OREGON 2� ��� FT.COLLINS,CO 80524 '�2� 2� 970 232 9558 Checked by ZMB c' AIRY�� 9 PROFESSIONAL ENGINEERING CONSULTANTS,P.A. Scale 1 1/2"= 1'-0" �qRY BO www.peC1.com Sheet Number S-001 CONCRETE 1,- ALL CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH ACI 318 AND THE BUILDING CODE, AND IN CONFORMANCE WITH THE CURRENT "ACI MANUAL OF _ CONCRETE PRACTICE." 2. THE CONCRETE REQUIREMENTS ARE: A. CEMENT SHALL BE TYPE I OR II CONFORMING TO ASTM C150. FLY ASH CONFORMING TO ASTM C618 TYPE C OR F MAY BE USED TO REPLACE A MAXIMUM OF 20% OF THE CEMENT BY WEIGHT. B. FINE AGGREGATE FOR NORMAL WEIGHT CONCRETE SHALL MEET ASTM C33. C. COARSE AGGREGATES FOR NORMAL WEIGHT CONCRETE SHALL CONFORM TO ASTM C33, GRADE 67 OR LARGER. COARSE AGGREGATES SHALL BE NO LESS THAN 50% OF THE TOTAL AGGREGATE BY WEIGHT, UNLESS APPROVED BY THE ENGINEER PRIOR TO MIX DESIGN SUBMITTAL. D. MIX REQUIREMENTS ARE: MINIMUM MINIMUM MAX. W/C AIR SLUMP LOCATION F'c (PSI) CEM. (PCY) RATIO CONTENT INCHES§ EXTERIOR SLAB 4,500 564 0.42 3%MAX. 2-5 3. ADMIXTURES, HARDENERS, & CURING COMPOUNDS A. ALL CONCRETE ADMIXTURES SHALL, WHEN MIXED INTO CONCRETE, BE NON- CHLORIDE AND NON-CHLORIDE FORMING. B. ALL ADMIXTURES MUST CONFORM TO ASTM C-494 AND C-260. C. CONCRETE CURING COMPOUND AND SEALERS SHALL MEET ASTM C-309 TYPE 1 OR 1 D. D. USE OF "SELF CONSOLIDATING" CONCRETE MUST BE SUBMITTED FOR APPROVAL WITH THE CONCRETE MIX DESIGN. WESTSIDE SURGERY CENTER GENERATOR PAD 13240 SW PACIFIC HWY, TIGARD, OR 97223 (QED PROFFS GENERAL NOTES Project number 210205-000 On 99076PE r 351 LINDEN STREET 06/08/2022 Date Os/08/22 �� SUITE 100 Drawn by BCH "9 OREGON2� ��� FT.COLLINS,CO 80524 'I'li 2� PE970 232 9558 Checked by ZMB r9�nRY�� PROFESSIONAL ENGINEERING CONSULTANTS,P.A. Scale 1 1/2" = 1'-0" qRY BO www.pec1.Com Sheet Number S-002 CONCRETE REINFORCING bvPZG UoZI 1. MATERIALS ASTM GRADE REINFORCING STEEL: A615 60 2. DETAILS: A. WELDING OF REINFORCING STEEL IS PROHIBITED UNLESS NOTED OTHERWISE. WHEN WELDING IS APPROVED, WELDING SHALL BE IN ACCORDANCE WITH AWS D1.4 "WELDING REINFORCING STEEL, ETC." B. SHOP DRAWINGS SHALL BE SUBMITTED WITH REINFORCING STEEL IN ACCORDANCE WITH ACI 315. 3. PLACEMENT: A. ALL REINFORCING AND EMBEDMENTS SHALL BE SUPPORTED ON CHAIRS/BOLSTERS TO THE DESIGN DIMENSIONS. SPACING SHALL BE SUFFICIENTLY CLOSE TO PREVENT DISPLACEMENT OR PERMANENT DEFORMATION DUE TO CONCRETE PLACEMENT, FOOT TRAFFIC, OR VIBRATION. "PUDDLING IN" OR "PULLING UP" REINFORCING IS NOT AN ACCEPTABLE METHOD FOR PLACING REINFORCING. CHAIRS/BOLSTERS SHALL HAVE PLASTIC COATED FEET OR BE MADE OF STAINLESS STEEL. CHAIRS/BOLSTERS IN CONTACT WITH EARTH SHALL HAVE BOTTOM PLATES AND BE COATED TO PREVENT CORROSION. ANCHOR RODS SHALL BE HELD IN PLACE WITH TEMPLATES SUFFICIENTLY STRONG TO PREVENT DISPLACEMENT OR TILTING. B. MAINTAIN ACI CLEAR COVER ON REINFORCING AS LISTED BELOW UNLESS NOTED OTHERWISE. CAST AGAINST EARTH (BOTTOM OR SIDES): 3" SLABS ON GRADE (FROM TOP OF SLAB): 1.5" C. PROVIDE CORNER BARS OF THE SAME SIZE AND SPACING AS ADJACENT REINFORCING. D. REINFORCING STEEL SHALL BE LAPPED PER ACI. WESTSIDE SURGERY CENTER GENERATOR PAD 13240 SW PACIFIC HWY, TIGARD, OR 97223 PROF6- GENERAL NOTES � ''40-- Project number 210205-000 99076PE • 351 LINDEN STREET Date 06/08/22 06/08/2022 SUITE 100 OREGON �� Drawn by BCH �y Z ��� FT.COLLINS,CO 80524 'I'L 2� 970 232 9558 Checked by iti ZMB c AIRY\\ PROFESSIONAL ENGINEERING CONSULTANTS,P.A. Scale 1 1/2"= 1'-0" 7ARY 80� www.pec1.com Sheet Number S-003 5' - 6" i EQ. 4' - 6" EQ. C'1 NEW GENERATOR AND FUEL TANK (WT = 11,300 LBS) (10) 5/8" 0 ANCHORS, 0 o REF. GEN. NOTES ;:r 6" CONC. SLAB ON GRADE ,/ W/ #5 @ 12" O.C. EA. WAY 0 w 1 FOUNDATION PLAN S-101 1/4" = 1'-0" WESTSIDE SURGERY CENTER GENERATOR PAD 13240 SW PACIFIC HWY, TIGARD, OR 97223 EO PROFFS FOUNDATION PLAN Project number 210205-000 99076PE r 351 LINDEN STREET 06/08/2022 Date 06/08/22 �� SUITE 100 Drawn by BCH �9 OREGON ��� FT.COLLINS,CO 80524 '�i 2� PE970 232 9558 Checked by ZMB 4RY� PROFESSIONAL ENGINEERING CONSULTANTS,P.A. Scale 1/4" = 1'-0" 4RY 60 WWW.pec1.com Sheet Number S-101 �,, GENERATOR AND . r/ , FUEL TANK, REF. PLAN 6" CONC. SLAB, 5/8" 0 ANCHOR REF. PLAN (MIN. 4" EMBED.), ''IL, TYP. imMil SLAB REINF, REF. PLAN — REF. PLAN 1 TYPICAL ANCHOR DETAIL s-5o1 3/4" = 1'-0" \ Z = PLATE 0 o WASHER DIAMETER A B PLATE SIZE p ISM U CO = STANDARD p u m WASHER 5/8" 4" 3" 1/4"X2" IY = \ a- \ _=o r\ = 1. ALL ANCHOR BOLTS ARE TO BE Z SUPPLIED WITH 3 NUTS. - 2. MINIMUM EMBEDMENT LENGTH OF N ANCHOR MUST BE PLACED INTO A 1— SINGLE POUR OF CONCRETE. Z 3. ANCHOR BOLTS SHALL BE ASTM w Q o F1554 WITH SUPPLEMENT S1 w co 2 w PLATE N e WASHER mam TACK 3/16 V 2 TYPICAL ANCHOR BOLT DETAIL S-501 3/4" = 1'-0" WESTSIDE SURGERY CENTER GENERATOR PAD Ro 13240 SW PACIFIC HWY, TIGARD, OR 97223 P;Ro FOUNDATION DETAILS . �r i 99076PE� y um Project number 210205-000 06i08i2022 351 LINDEN STREET Date 06/08/22 SUITE 100 OREGON b. PEC Drawn by BCH FT.GOLLINS,CO 80524 2° Checked by ZMB c'��gRY�� ��' PROFESSIONAL ENGINEERING CONSULTANTS,P.A. 970-232-9558 Scale 3/4" = 1'-0" ARY BO www.pec1.com.com Sheet Number S-501 PEC PROFESSIONAL ENGINEERING CONSULTANTS,P.A. APPENDIX A: CALCULATIONS Bop 20 -00 225-1 351 LINDEN STREET,SUITE 100 FORT COLLINS,CO 80524 970-232-9558 www.pec 1.cam 6/7122,5:19 PM rspr , t: m ,,___.__ ,_. _ _ t�`Aa0E 7 Hazarc. � .,r Can ; i _.r. :! : „9 Search Informs I. t-‘ Vancouver Address: 13 E 215 ft Coordinates: 44 U,r < 11: . x [l fl{:7 Elevation: 21 '` �� d' Timestamp: 2C Hazard Type: -ai"`= i-lri ' . Reference At Map data c;2022 Google • Document: I r Sler1n Risk Category: II [I f, Liar Site Class: D Basic Parametet 1,-1rdci i r Name Value r,ry,r3 d .-; Ss 0.854 Si SMS 1.025a snr, SM1 * null Site-modified spectral acceleration value SDS 0.683 Numeric seismic design value at 0.2s SA SD1 *null Numeric seismic design value at 1.0s SA * See Section 11.4.8 ®Additional Information Name Value Description SDC *null Seismic design category Fa 1.2 Site amplification factor at 0.2s Fv *null Site amplification factor at 1.0s CRs 0.885 Coefficient of risk(0.2s) CR1 0.866 Coefficient of risk(1.0s) PGA 0.389 MCEG peak ground acceleration FPGA 1.211 Site amplification factor at PGA PGAM 0.471 Site modified peak ground acceleration https://hazards.atcouncil.org/#/seismic?lat=45.4240031&Ing=-122.7815022&address=13240 SW Pacific Hwy%2C Tigard%2C OR 97223%2C USA 1/2 6/7122,5:19 PM ATC Hazards by Location TL 16 Long-period transition period (s) sRT 0.854 Probabilistic risk-targeted ground motion(0.2s) SsUH 0.965 Factored uniform-hazard spectral acceleration (2%probability of • exceedance in 50 years) SsD 1.5 Factored deterministic acceleration value(0.2s) Si RT 0.394 Probabilistic risk-targeted ground motion (1.0s) S1 UH 0.455 Factored uniform-hazard spectral acceleration(2% probability of exceedance in 50 years) S1 D 0.6 Factored deterministic acceleration value(1.0s) PGAd 0.5 Factored deterministic acceleration value(PGA) * See Section 11.4.8 The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building code adoption process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before proceeding with design. Disclaimer Hazard loads are provided by the U.S. Geological Survey Seismic Design Web Services. While the information presented on this website is believed to be correct,ATC and its sponsors and contributors assume no responsibility or liability for its accuracy.The material presented in the report should not be used or relied upon for any specific application without competent examination and verification of its accuracy,suitability and applicability by engineers or other licensed professionals.ATC does not intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the report provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of this website does not imply approval by the governing building code bodies responsible for building code approval and interpretation for the building site described by latitude/longitude location in the report. https://hazards.atcouncil.org/#/seismic?lat=45.4240031&Ing=-122.7815022&address=13240 SW Pacific Hwy%2C Tigard%2C OR 97223%2C USA 2/2 guPZ0Z2-OnZ • PROJECT 2.1O1OS.OQO DATE (p/'i /ZZ • •••* ITEM WEST'S fiNC 504. htfoi CE++IC,R -6404:XATOR too BY 6c PRO Li' #GNAE iNGINEE=RINC, CC3NSUE1ANT3 YOU DREAM IT, WE'LL DESIGN IT. 6 c M Ci.d rit ia. book, fij et„ rA g N. 6Chi CIL.►TCIr� HE IA* ccocrea. or' &CAS Y .aI. ea ,/ „ i ' I 3 _ 1(� Ia /�t o..mow,p� I g MO 'G C4CiAl'ott14%4 { fir, f .144 SaS P "f 4 +: .( I~)] ASCC 1-ta.,020/wre004 t3.3-t OP/Xi. ) '1'ket,.C. I+SA. !« ( Ar Re 2.S — t+Jp gi StO at; * 5EC I►1Ta att=cs gErge.cfACC rot t)Cru rt^r * ASICX y t.Q 0.. w C.RAG� . r' 'fit' r ,4(r.q)(..a$)(1r�3Qo lb.) _ ! I r zs r Ir2,(o) 3 - 1.3 w, Ci..g.a ) ' C4 )/4 or1 Cat/AT/64 13.173. .._A..rtr+r 13,SbsIs i'' P . .. r na.i s z.31 rat (tars) 4' GOve"4 t s.31 f. ( to.31,,) x 3o.Z1 +t :«. 44.ge) r ® (3o.Z .141 K .Id® 14 4c.ar1eg) APJCADa, ?Ir1 'S$be (IS tf,) z a (Z.:3at . ) _ ("in)) A.4.0.00.E (►0 A f4c 4oa.S) t9S( (t°) 5(3" 0 *MC.Mo&S (v►i+t. CARsCD ) Project Title: 210205-000 GENERATOR PAD Engineer: ZMB Project ID: 210205-000 ' .. Project Descr: 1 General Footing .7''''''"Trm:-----,.:,:-.------- .ri.! Project File:210205-000 BCH Enercalc.ec6 LIC#:KW-06005112,Build:20.21.9.6 PEC (c)ENERCALC INC 1983-2021 DESCRIPTION: Generator Pad Code References Calculations'per ACI 318-11, IBC 2012, CBC 2013,ASCE 7-10 Load Combinations Used : ASCE 7-16 General Information NE '•r'.:11 fr2pe-t.r:“- Soil Design Values fc:Coiffete 28 day strength • egi...„,. *141 Allowable Soil Bearing = 1.50 ksf fy Rebar Yieici = 60.0 ksi Soil Density = 110.0 pcf Ec:Concrete Elastic Modulus = 3,122.0 ksi Increase Bearing By Footing Weight = No Concrete Density = 145.0 pcf Soil Passive Resistance(for Sliding) = 250.0 pcf 9 Values Flexure = 0.90 Soil/Concrete Friction Coeff. = 0.30 Shear = 0.750 Increases based on footing Depth Analysis Settings Footing base depth below soil surface = 0.50 ft Min Steel%Bending Reinf. = Allow press.increase per foot of depth = ksf Min Allow%Temp Reinf. = 0.00090 when footing base is below = ft Min.Overturning Safety Factor = 1.0 :1 Min.Sliding Safety Factor = 1.0 : 1 Increases based on footing plan dimension Add Ftg Wt for Soil Pressure •. Yes Allowable pressure increase per foot of depth Use ftg wt for stability,moments&shears : Yes = ksf when max.length or width is greater than •Add Pedestal Wt for Soil Pressure . No = ft Use Pedestal wt for stability,mom&shear •. No Dimensions 72 4101111* mi AN* . i 1 . . - .. . , . ..i . Pedestal dimensions... . •. — ' . .• '..1 ' : i I-4- , ., • : px:parallel to X-X Axis = 54.0 in • , . . ,. i pz:parallel to Z-Z Axis = • 144.0 in • - . ••• •• ;i i Height = 12.80 in Rebar Centerline to Edge of Concrete... • II II at Bottom of footing = 3.0 in • • Fi:inileA•ii II,343:1 ., - - . .. ..._—,..„.....,— ., Reinforcing Bars paralle,to X-X Axis = Number of Bars • .. . ...• # Reinforcing Bar Size = Bars parallel to Z-Z Axis :. . .. ., = . . ....., .. ....„...,,,,,,,,,......,-;;size = Bandwidth Distribution Check (ACI 15.4.4.2) ,, :jiiiNtir.f?17*it#WII1•4;N'.!j4064, Direction Requiring Closer SeparationBars along X-X Axis . . • . •.• #Bars required within zone #Bars required on each side of zone 43.6% Applied Loads D Lr L S W E H P:Column Load = :#1016 k OB:Overburden = ksf M-xx = k-ft M-zz = k-ft V-x = CtSt k V-z = k Project Title: 210205-000 GENERATOR PAD Engineer: ZMB Project ID: 210205-000 - Project Descr: General Footing Project File:210205-000 BCH Enercalc.ec6 LIC#:KW-06005112,Build:20.21.9.6 PEC (c)ENERCALC INC 1983-2021 DESCRIPTION: Generator Pad DESIGN SUMMARY `tt' DesignO O _ ,. Min.Ratio Item Applied Capacity Governing Load Combination PASS 0.1705 Soil Bearing 0.2557 ksf 1.50 ksf +D+0.70E about Z-Z axis PASS n/a Overturning-X-X 0.0 k-ft 0.0 k-ft No Overturning PASS 10.718 Overturning-Z-Z 2.599 k-ft 27.856 k-ft +0.60D+0.70E PASS 2.095 Sliding-X-X 1.659 k 3.476 k +0.60D+0.70E PASS n/a Sliding-Z-Z 0.0 k 0.0 k No Sliding PASS n/a Uplift 0.0 k 0.0 k No Uplift PASS 0.01932 Z Flexure(+X) 0.02819 k-ft/ft 1.459 k-ft/ft +1.20D+E PASS 0.01761 Z Flexure(-X) 0.02568 k-ft/ft 1.459 k-ft/ft +1.40D PASS 0.01319 X Flexure(+Z) 0.1027 k-ft/ft 7.785 k-ft/ft +1.40D PASS 0.01319 X Flexure(-Z) 0.1027 k-ft/ft 7.785 k-ft/ft +1.40D PASS 0.01716 1-way Shear(+X) 1.727 psi 100.623 psi +1.20D+E PASS 0.01560 1-way Shear(-X) 1.569 psi 100.623 psi +1.40D PANS 0.03970 1-way Shear(+Z) 3.995 psi 100.623 psi +1.40D PASS 0.03970 1-way Shear(-Z) 3.995 psi 100.623 psi +1.40D PASS 0.02723 2-way Punching 3.143 psi 115.421 psi +1.40D Detailed Results Soil Bearing Rotation Axis& Xecc Zecc Actual Soil Bearing Stress @ Location Actual/Allow Load Combination... Gross Allowable (in) Bottom,-Z Top,+Z Left,-X Right,+X Ratio X-X,D Only 1.50 n/a 0.0 0.2193 0.2193 n/a n/a 0.146 X-X,+0.60D 1.50 n/a 0.0 0.1316 0.1316 n/a n/a 0.088 X-X,+D+0.70E 1.50 n/a 0.0 0.2193 0.2193 n/a n/a 0.146 X-X,+D+0.5250E 1.50 n/a 0.0 0.2193 0.2193 n/a n/a 0.146 X-X,+0.60D+0.70E 1.50 n/a 0.0 0.1316 0.1316 n/a n/a 0.088 Z-Z,D Only 1.50 0.0 n/a n/a n/a 0.2193 0.2193 0.146 Z-Z,+0.60D 1.50 0.0 n/a n/a n/a 0.1316 0.1316 0.088 Z-Z,+D+0.70E 1.50 1.847 n/a n/a n/a 0.1828 0.2557 0.171 Z-Z,+D+0.5250E 1.50 1.386 n/a n/a n/a 0.1919 0.2466 0.164 Z-Z,+0.60D+0.70E 1.50 3.079 n/a n/a n/a 0.09510 0.1680 0.112 Overturning Stability Rotation Axis& Load Combination... Overturning Moment Resisting Moment Stability Ratio Status X-X,D Only None 0.0 k-ft Infinity OK X-X,+0.60D None 0.0 k-ft Infinity Ott X-X,+D+0.70E None 0.0 k-ft Infinity OK X-X,+D+0.5250E None 0.0 k-ft Infinity OK X-X,+0.60D+0.70E None 0.0 k-ft Infinity OK Z-Z, D Only None 0.0 k-ft Infinity OK Z-Z,+0.60D None 0.0 k-ft Infinity OK Z-Z,+D+0.70E 2.599 k-ft 46.427 k-ft 17.863 OK Z-Z,+D+0.5250E 1.949 k-ft 46.427 k-ft 23.817 OK Z-Z,+0.60D+0.70E 2.599 k-ft 27.856 k-ft 10.718 OK Sliding Stability All units k Force Application Axis Load Combination... Sliding Force Resisting Force Stability Ratio Status X-X,D Only 0.0 k 5.502 k No Sliding OK X-X,+0.60D 0.0 k 3.476 k No Sliding OK X-X,+D+0.70E 1.659 k 5.502 k 3.317 OK X-X,+D+0.5250E 1.244 k 5.502 k 4.422 OK X-X,+0.60D+0.70E 1.659 k 3.476 k 2.095 OK Z-Z, D Only 0.0 k 5.237 k No Sliding OK Z-Z,+0.60D 0.0 k 3.211 k No Sliding OK Z-Z,+D+0.70E 0.0 k 5.237 k No Sliding OK Z-Z,+D+0.5250E 0.0 k 5.237 k No Sliding OK Z-Z,+0.60D+0.70E 0.0 k 3.211 k No Sliding OK Project Title: 210205-000 GENERATOR PAD Engineer: ZMB Project ID: 210205-000 ' • Project Descr: General Footing Project File:210205-000 BCH Enercalc.ec6 LIC#:KW-06005112,Build:20.21.9.6 PEC (c)ENERCALC INC 1983-2021 DESCRIPTION: Generator Pad Footing Flexure Flexure Axis&Load Combination Mu Side Tension As Req'd Gym.As Actual As Phi*Mn Status k-ft Surface in"2 in"2 in^2 k-ft X-X, +1.40D 0.1027 +Z Bottom 0.06480 AsMin 0.6764 7.785 OK X-X, +1.40D 0.1027 -Z Bottom 0.06480 AsMin 0.6764 7.785 OK ' X-X,+1.20D 0.08802 +Z Bottom 0.06480 AsMin 0.6764 7.785 OK X-X,+1.20D 0.08802 -Z Bottom 0.06480 AsMin 0.6764 7.785 OK X-X, +0.90D 0.06601 +Z Bottom 0.06480 AsMin 0.6764 7.785 X-X,+0.90D 0.06601 -Z Bottom 0.06480 AsMin 0.6764 7.785 ' X-X, +1.20D+E 0.08802 +Z Bottom 0.06480 AsMin 0.6764 7.785 X-X,+1.20D+E 0.08802 -Z Bottom 0.06480 AsMin 0.6764 7.785 X-X,+0.90D+E 0.06601 +Z Bottom 0.06480 AsMin 0.6764 7.785 X-X,+0.90D+E 0.06601 -Z Bottom 0.06480 AsMin 0.6764 7.785 Z-Z,+1.40D 0.02568 -X Bottom 0.06480 AsMin 0.1107 1.459 .. Z-Z,+1.40D 0.02568 +X Bottom 0.06480 AsMin 0.1107 1.459 Z-Z, +1.20D 0.02201 -X Bottom 0.06480 AsMin 0.1107 1.459 OK Z-Z,+1.20D 0.02201 +X Bottom 0.06480 AsMin 0.1107 1.459 OK Z-Z,+0.90D 0.01651 -X Bottom 0.06480 AsMin 0.1107 1.459 OK Z-Z,+0.90D 0.01651 +X Bottom 0.06480 AsMin 0.1107 1.459 OK Z-Z,+1.20D+E 0.01584 -X Bottom 0.06480 AsMin 0.1107 1.459 `K Z-Z,+1.20D+E 0.02819 +X Bottom 0.06480 AsMin 0.1107 1.459 OK Z-Z,+0.90D+E 0.01033 -X Bottom 0.06480 AsMin 0.1107 1.459 OK Z-Z,+0.90D+E 0.02268 +X Bottom 0.06480 AsMin 0.1107 1.459 OK One Way Shear Load Combination... Vu @-X Vu @+X Vu @-Z Vu @+Z Vu:Max Phi Vn Vu/Phi*Vn Status +1.40D 1.57 psi 1.57 psi 4.00 psi 4.00 psi 4.00 psi 100.62 psi 0.04 OK +1.20D 1.35 psi 1.35 psi 3.42 psi 3.42 psi 3.42 psi 100.62 psi 0.03 OK +0.90D 1.01 psi 1.01 psi 2.57 psi 2.57 psi 2.57 psi 100.62 psi 0.03 OK +1.20D+E 0.96 psi 1.73 psi 3.42 psi 3.42 psi 3.42 psi 100.62 psi 0.03 +0.90D+E 0.63 psi 1.39 psi 2.57 psi 2.57 psi 2.57 psi 100.62 psi 0.03 Two-Way"Punching"Shear All units k Load Combination... Vu Phi*Vn Vu/Phi*Vn Status +1.40D 3.14 psi 115.42psi 0.02723 OK +1.20D 2.69 psi 115.42psi 0.02334 OK +0.90D 2.02 psi 115.42psi 0.01751 OK +1.20D+E 2.69 psi 115.42psi 0.02334 OK +0.90D+E 2.02 psi 115.42psi 0.01751 OK 13DPzO2l-0022q Hilti PROFIS Engineering 3.0.78 www.hilti.com Company: Professional Engineering Consultants Page: 1 Address: 351 Linden Street,Suite 100,Fort Collins,CO 80524 Specifier: Zach Bowden Phone I Fax: 970-232-9558 I E-Mail: Zach.Bowden@pecl.com Design: Concrete-Jun 7,2022 Date: 6/7/2022 Fastening point: Specifiers comments: 1 Input data Anchor type and diameter: Hex Head ASTM F 1554 GR.36 5/8 11.1111111111111111.1111111111111111111 Item number: not available Effective embedment depth: het=4.000 in. Material: ASTM F 1554 Evaluation Service Report: Hilti Technical Data Issued I Valid: -I- Proof: Design Method ACI 318-14/CIP Stand-off installation: Profile: Base material: cracked concrete,,fc'=4,500 psi;h=6.000 in. Reinforcement: tension:condition B,shear:condition B; edge reinforcement:none or<No.4 bar Seismic loads(cat.C,D,E,or F) Tension load:yes(17.2.3.4.3(d)) Shear load:yes(17.2.3.5.3(c)) Geometry[in.]&Loading[Ib,in.Ib] 4 I (] .„ ..,,...,, 0..y\j" 4 .:„...„,..„„,...*RP,,,E, ,::• Q 1/011 \ X Q Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2022 Hilti AG,FL-9494 Schaan HiS is a registered Trademark of Hilti AG,Schaan 1 Hilti PROFIS Engineering 3.0.78 www.hilti.com Company: Professional Engineering Consultants Page: 2 Address: 351 Linden Street,Suite 100,Fort Collins,CO 80524 Specifier: Zach Bowden Phone I Fax: 970-232-9558 I E-Mail: Zach.Bowden@pecl.com Design: Concrete-Jun 7,2022 Date: 6/7/2022 Fastening point: 1.1 Design results Case Description Forces[lb]/Moments[in.lb] Seismic Max.Util.Anchor[%] 1 Combination 1 N=320;Vx=480;Vy=480; yes 14 Mx=0;My=0;MZ=0; Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2022 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 2 iffr.. 9:N ksL setk y ifi arat.s �41 u - Hilti PROFIS Engineering 3.0.78 _ www.hilti.com Company: Professional Engineering Consultants Page: 3 Address: 351 Linden Street,Suite 100,Fort Collins,CO 80524 Specifier: Zach Bowden Phone I Fax: 970-232-9558 I E-Mail: Zach.Bowden@pecl.com Design: Concrete-Jun 7,2022 Date: 6/7/2022 Fastening point: 2 Proof I Utilization (Governing Cases) Design values[lb] Utilization Loading Proof Load Capacity PN/Pv[%] Status Tension Concrete Breakout Failure 320 6,762 5/- OK Shear Steel Strength 679 5,112 -/14 OK Loading PN Pv Utilization PN,v[%] Status Combined tension and shear loads 0.047 0.133 5/3 5 OK Fastening meets the design criteria! Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2022 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 3 Hilti PROFIS Engineering 3.0.78 _ www.hilti.com Company: Professional Engineering Consultants Page: 4 Address: 351 Linden Street,Suite 100,Fort Collins,CO 80524 Specifier: Zach Bowden Phone I Fax: 970-232-9558 I E-Mail: Zach.Bowden@pecl.com Design: Concrete-Jun 7,2022 Date: 6/7/2022 Fastening point: 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user.All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you. Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility.The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software.In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website.Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you. Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering(c)2003-2022 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan 4 • )o? 2tx23•.-04:512J4 , Ner6,. A FOR REFERENCE ONLY v.- - THE VMC GROUP The Power of Together CERTIFICATE OF COMPLIANCE SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS . ......................... 4‘Eo Certification No. re- U v c VMA-5 1 07 1 -O 1 C PREVISION 06) THE WIC EPTOLJP Expiration Date: 06/30/2021 Certification Parameters: The nonstructural products(mechanical and/or electrical components)listed on this certificate are CERTIFIED' FOR SEISMIC APPLICATIONS in accordance with the following building code2 releases. IBC 2012, 2015, 2018 The following model designations,options,and accessories are included in this certification. Reference report number VMA-51071-01 as issued by The VMC Group for a complete list of certified models,included accessories/options,and certified installation methods. Cummins Power Generation, Incorporated; Diesel Gensets Commercial Series; 10 kW—200 kW The above referenced equipment is APPROVED for seismic application when properly installed', used as intended, and contains a Seismic Certification Label referencing this Certificate of Compliance4.As limited by the tabulated values,below grade,grade,and roof-level installations, installations in essential facilities,for life safety applications, and/or of equipment containing hazardous contents are permitted and included in this certification with an Equipment Importance Factor assigned as Ip=1.5.The equipment is qualified by successful seismic shake table testing at the nationally recognized Dynamic Certification Laboratories under the review of the ISO Accredited Product Certification Agency, The VMC Group. Certified Seismic Design Levels? Importance Ip_< 1.5 SDS 5 2.500 g Sps 5 2.000 g Certified Soil Classes A-E z/h = 0.0 z/h 5 1.0 IBC Risk Categories I-IV Horizontal F,, _ ap zl Design Categories A-F Design10 yyp 0.4Sos/yRp�l+2 hJ < 2.400 g Test Datum ISO 17025 Laboratory AFLEX H 53.200 g AFLEX v 5 1 667 g AC156 Re/Post-Shake Functionality ARIL H < 2.400 g ARIG V 5 0.667 g Tri-axial,5% Damping SRS ZPAH 5 2.160 g Av <_ 0.600 g Certified Seismic Installation Methods Rigid mounting from unit base to rigid structure THIS MEETS OR EXCEEDS DESIGN PARAMETERS: RISK CATEGORY II SOIL CLASS D (ASSUMED) SEISMIC DESIGN CATEGORY C SDS = 0.698 z/h = 0 The VMC Group•113 Main Street,Bloomingdale,NJ 07403•Tel:973-838-1780•Fax:973-492-8430•www.thevmcgroup.com Page 1 of 3 102S-103387 Rev 10 NOrih, A FOR REFERENCE ONLY 0> - THE VMC GROUP The Power of Together ' CERTIFICATE OF COMPLIANCE SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS Certified Product Table: Maximum Dimensions(in.) Max Weight Certified Fuel SDS(g) Model Power RPM with Tank Rating Enclosure Capacities Length Width Height (lbs.) (gal.) z/h=0.0 z/h=1.0 C10D6 10 kW 4,300 C15D6 15 kW 98 4,400 46,74,91, 132, 195,263 C20D6 20 kW 4,470 C25D6 25 kW 5,890 C30D6 30 kW 34 88 5,930 2.000 C35D6 35 kW 131 5,960 74, 132, 195, C40D6 40 kW 6,140 263,389 C50D6 50 kW 6,260 C60D6 60 kW 1800 6,260 2.500 C50D6C 50 kW 8,943 C60D6C 60 kW 8,990 C80D6C 80 kW 170 40 104 9,040 250,1425,625 C100D6C 100 kW 9,216 2.500 C125D6C 125 kW 9,300 C125D6D 125 kW C150D6D 150 kW 180 71 111 14,300 351,737, 1055 C175D6D 175kW C200D6D 200 kW This certification includes the open generator set and the enclosed generator set when installed with or without the sub-base tank. This certification also includes the sub-base tank as a stand-alone accessory. The generator set and included options shall be a catalogue design and factory supplied. The generator set and applicable options shall be installed and attached to the building structure per the manufacturer supplied seismic installation instructions. This certification excludes all non-factory supplied accessories, including but not limited to mufflers, isolation/restraint devices,remote control panels,remote radiators,pumps and other electrical/mechanical components. DESIGN WEIGHT OF UNIT INCLUDES 9300 LB MAX. WEIGHT WITH ENCLOSURE AND 1500 LBS OF GASOLINE (11,300 LBS TOTAL) VMA-51071-01C (Revision 06) Issue Date: July 3, 2015 Revision Date: August 28, 2018 NE VM19C 6Qo Expiration Date: June 30, 2021 The VMC Group•113 Main Street,Bloomingdale,NJ 07403.Tel:973-838-1780•Fax 973-492-8430•www:thevmcgroup.com Page 2 of 3 102S-103387 Rev 10 FOR REFERENCE ONLY C ` - THE VMC GROUP The Power of Together"V CERTIFICATE OF COMPLIANCE SEISMIC DESIGN OF NONSTRUCTURAL COMPONENTS AND SYSTEMS Notes and Comments: 1. All equipment listed herein successfully passed the seismic acceptance criteria for shake testing non-structural components and systems as set forth in the ICC AC-156.The Test Response Spectrum(TRS)enveloped the Required Response Spectrum(RRS)for all units tested.The units cited in this certification were representative sample(s)of a contingent of models and all remained captive and structurally sound after the seismic shake simulation.The units also remained functionally operational after the simulation testing as functional testing was completed by the equipment manufacturer before and after the seismic simulations. Although a seismic qualified unit inherently contains some wind resisting capacity, that capacity is undetermined and is excluded from this certification.Snow/Ice loads have been neglected and thus limit the unit to be installed both indoors(covered by an independent protective structure)and out of doors(exposed to accumulating snow/ice)for ground snow loads no greater than 30 psf for all applications. 2. The following building codes are addressed under this certification: IBC 2012—referencing ASCE7-10 and ICC AC-156 IBC 2015—referencing ASCE7-10 and ICC AC-156 IBC 2018—referencing ASCE7-16 and ICC AC-156 3. Refer to the manufacturer supplied installation drawings for anchor requirements and mounting considerations for seismic applications. Required anchor locations,size,style,and load capacities(tension and shear)may be specified on the installation drawings or specified by a 3rd party.Mounting requirement details such as anchor brand, type, embedment depth, edge spacing, anchor-to-anchor spacing, concrete strength, special inspection, wall design, and attachment to non-building structures must be outlined and approved by the Engineer of Record for the project or building.Structural walls,structural floors, and housekeeping pads must also be seismically designed and approved by the project or building Structural Engineer of Record to withstand the seismic anchor loads as defined on the installation drawings.The installing contractor is responsible for observing the installation detailed in the seismic installation drawings and the proper installation of all anchors and mounting hardware. 4. For this certificate and certification to remain valid,this certificate must correspond to the"Seismic Certification Label"found affixed to the unit by the factory. The label ensures the manufacturer built the unit in conformance to the IBC seismic design criteria set forth by the Certified Seismic Qualification Agency,The VMC Group,and meets the seismic design levels claimed by this certificate. 5. Mechanical,Electrical,and Plumbing connections to the equipment must be flexibly attached as to not transfer load through the connection.The structural integrity of any conduit,cable trays,piping,ductwork and/or flexible connections is the responsibility of others.This certification does not guarantee the equipment will remain compliant to NEMA,IP,UL,or CSA standards after a seismic event. 6. This certificate applies to units manufactured at: 1400 73rd Ave NE,OF 143,Minneapolis,MN 55432 7. This project follows The VMC Group's ISO-17065 Scheme for Product Certification of Nonstructural Components. 8. The qualified seismic design level stated is the lowest for all series this certificate covers,for more detailed ranges of qualified seismic design levels,see the certified product tables. ///:414,,e,------ John P. Giuliano, PE (ILL:7 President, The VMC Group 4O MIS „ L E., :; VMA-51071-01C (Revision 06) ACCREDITED Issue Date: July 3, 2015 'THE HC®ROUP PiOdUCt Revision Date: August 28, 2018 Certification Agency Expiration Date: June 30, 2021 The VMC Group.113 Main Street,Bloomingdale,NJ 07403.Tel:973-838-1780•Fax:973-492-8430•www.thevmcgroup.com Page 3 of 3 102S-103387 Rev 10 Bo F 2ozz-ash DR REFERENCE ONLY 4 1 3 2 1 I • D �n, • . , •.a r /40 6 8 Oramn9 Name:A960P699 Revisio: Part Name:1660P696 Revisio: ECO-1694)6 Sheer r • REFERENCE ONLY 3 5 J Fr.) . SEISMIC INSTALLATIONS NOTES I THE DESIGN OF POST INSTALLEC ANCHORS IN CONCRETE USED FOR THE COMPONENT AN.C,,"C S FND-000LiPiEO FOR TEITISIA._C,"IONS IN ACCORCANCE WITH A3I 35:2,, ANC VOLUMENTED IN A REPORT 51 A REAQQ-A5LE AA';SH A5ANT' INN THE EVALUATION SERvICE REPORT INNATE El THE INTERNATIONAL COPE 50.4"t 0 0 T. ANCHORS MUST IRE INSTALLED TO AN kUnED0401 DEPTH AS PECT,MMENDED IN THE EkE-SENt. FILET NH TEST HEPSPN FE SENI000 1.0%,") FOR 05C 201 s APPLICATIONS INCLUDED CALCULATIONS PROVIDE 3 ANCHORS MAST BE INATALLER IN MINIUCIU 3000 PSI COMPRESS INS STRENGTH NORMA.WE 5,--5--055-3.51A.CORONETS CORONETS 055R000TE MUST COMPL,W D STRUCTURAL DESIGN OF ANCHORAGE AND CONCRETE EQUIPMENT PAD A. ANCHORS MUST ETC INSTALLED TO THE TORQUE SPECIFICATION AS RES:OMANNEEEI OF 'Ft ANCHOR MAN,QA,- AEA — S. ANCHORS MUST TA INSTALLED IN LOCATIONS SPECIFIES ON THIS INHEAEENTICONI1HENiFS. — ANSHEHS HOST MASHERS MAST!!EE1 INSTALLED VPIE.2 YVATFPELMENING'A'.541rtNI8111 ANCHORI '01405 AOL E?E -A1(ME F. CONCRETE FLOOR CAN AND CONCRETE HOIJOEFEEPINO PADS MUST BE DESIGNEE A3,,551 SAID REPS iCATiOAD IN ACCORDANCE W AL 3 8 5 ALL HOU,EVEEPIN6 PAC TH1CKNEATET'MUTT BE DESIGNED IN ACCORDANCE WITH THE NO 0,A.IT ICATIOSL-ES-DEPORT 05 DEE bED 10 ROTE I ON A MINIMUM OF 1 'M THE ALMHOP 4T,PEDVEN1 DEPTH WHICHEVER IS[APTEST A.TTS NEAP" QFPEW SAI C C A ALL HOUSEITEEPINS PADS UOST tE DTIAELLEG OR'AEI EATS THE)(IICING ER N 'X.,• F 0, PER "'NCI TIT II AND HIS APPROVES 511 THE SERLCTLHAU ENGINEER OF RECORD. 10 FLOOR MOUNTED EQUIPMENT bAlER OR WITHOUT A HOUSEKEEPING PAD MOST REl Nm'A.1.00 TOR STILL I.. EEl FORCED STALICTLILAI CONCENCVETE ' 00- THAT IS SEISMICALLY DESIGNED AND APPRCNEC,Y IEEE ENGINEER F SE All 'C k")• •' )4, 'MEN'P, TO THE fLOOP I I .°ORDINATE REINFOR,[WO Of SUPPORT )1RUCTUPF MuFF EQUIPMENT ANCHOR L050TiiTNO. 12 ATTk HINu CERTIFIEDEQUIPMENT TO FLOOR OTHER THAN THOSE CF0 F,OF TO ACCEPT4' T.IONIC LEADS'ROM EEHTIET'"'0 P-MEN-F RE THE STRUCTURAL IN"INEER 04 RECORD IS PRC+11,1TED IT. INSTALI AlION ONTO A STEEL ROOF N1RIMURE LEA MANUFACTURED STEEL AR,S Cia,D J WI TO: THE S),CA,PAL TAC I STLT LEE IA. CONNECTIONS T( THE FOUIPMEN1 INNUCINF tlf NOT LIMITER TO:AMIE AIEIRSI PHON CANOES TEATS. LETHIER,_:C",ICTI SE,.CI,G.) NNT,TICNs ART THE RE)PON,IBILII)OF THE INCTALLIN,'ONTNA(10P ANC B 'OFD'kE 5205E 0' '-5)0CAMEN FTEX1"LE ATTAIN ENDS MUST BL USED TA SEISMIC CONNECTIONS 0 FE I TA A 0%)S sOEAED Cu, ,MEN) EAT FIEm15LE ATTACHMENT MAST IF) ICE NSA ENOUFH RELATIVE PITRIAQEMENA POMON'ONN''PC -0'4E EC,.MEN' AN NC 08 ERA IRS AND AEI.A SEIS01( MAT I, PEFEP TO UN,ET OUTLINE DRAWINGS DEER WEIGHT C,AND CONFIGURATION SPEC: A A rV:Itda' i(04 Pwa' 3 5 PGGIVrlITZ:ZmtPasc18 ""ti Relg IMCWAPD ECXY159499 Shmil „,„,•_,-;;;;;-,::: . _ 1 5 1,,.L,L,,,,, ,,._1,..,,,..T..i,._..K....... ri,,,,,,,,,,•-_ !, 0 0 7 GRADE MOUNTED GENERATOR SETS 1 cs,,,Cri,,,,N,j,,,. CONF!GHAT ION EVAE00/i ON PAPAW TiRC ON/ROTE ANCHORS 0,-E,6,NT 1. AVHCR S,ACINO 1 ''',..e,... '3U1-,. - C5,DK CB,-20 3,I5,:„2012 ,5 CEO D6,. GENERATOR,iE” 00/C . SE,NOTE , C 0116,C ENSLO,LIRF ,.25 DV i n,,5 NOIL 1,1,ANCHOR,ANCHOR ATTACHMLN'SPEC ,f,,,ANEr.111INLIu 1300 THI3011:S.;TO HE DESIGN:I,By,,,,EER 0,RL,O.., C C GRADE/ROOF MOUNTED GENERATOR SETS 1 ,'ACHMENT TO STEEL , GE CVM'NI, CONI,GURAI:ON •- EvALJA,ON PARAMETERS STEEL BUTS I C.5,DV .,,,,,BC 2012 g.,T,al`,P. 060 DV 6ENRATOR SET Tao<-?5 3/AM/,ER WM AT/NI OR A4.BOLT, CV 1,6`. W li,OR V FH011, I.,-I 5 WITH WA,NER,1HRO. II C I 0,Di, ENCLOSURE ap/Iip,2;r2 6 TIE BASE RAIL MOUNTING 5 C.125. HOLE, _ J - . & A pc.....,,,„„, N;.-ALLAT iON 5ENSET ,u5419. '` ' - 1 .., 6 5 4 ',.‘ 3 a p. 19`.1.T;',117.1"`'Approval 1""o'd1"1,rht°.`"a"Rmothl' m Drawing Name:A0547598 Revisio - - - 1 Rem impactisBrarplc,e, wrt th se xtemalRegulations: Part Name:A0547597 %veto ECO-159499 Sheet 2 • - 13uP202 _- oOzi?-1 3 1 2 ... 1 SU, RELEASE 0 MOUNTING HOLE LOCATIONS FOR FUEL TANK WITH 10 BOLTS TO MOUNTING STRUCTURE • -GAnIIC OP ROOT OUNTIMU 1 011FF oN 1 C Eii�t B I„ C IXn1 I I CONTROL EMI f9; J c 25 II 6298 55.3,. -.. —_— — -22T8.6 [89 fldfl C50 D6C,COO DU C80 D6C,C100 P6(.C125 DK. FM_TAOS WITH-8 NO,[ATTACHMf NLJ A A vc a m N � AiyTUP E�YST T _6 '2.2-22 a vl,, u i c .. F,.w 5ti.�AB PbT p 0541`9' 6 5 ^ 3 i l 2' I Regulatory Review and Approval is required prior to cha ing this ttem per Drawleg Name:A054T596 Revise PGD 1-Ot-01-116.Thia item Impecls Marl Hence with these External Regulations: Part Name:A054T597 Remo IBC,OSHPD ECO 159499 Sheets Qom? 2/52 7002211 Specification sheet ,�c'NO GJ�` Diesel generator set QSB5 series engine 50-125 kW Standby 1r EPA Tier 3 emissions AUG 8 202Z OF TIGARD Description r -)!NG Diu�SIO Cummins®generator sets are fully integrated ooling system - Standard cooling package power generation systems providing optimum provides reliable running at up to 50 °C performance, reliability and versatility for (122 °F) ambient temperature. stationary Standby applications. Enclosures-The aesthetically appealing Features enclosure incorporates special designs that deliver one of the quietest generators of its kind. Heavy duty engine - Rugged 4-cycle industrial Aluminium material plus durable powder coat diesel delivers reliable power and fast response paint provides the best anti-corrosion to load changes. performance. The generator set enclosure has Alternator Several alternator sizes offer been evaluated to withstand 180 MPH wind selectable motor starting capability with low loads in accordance with ASCE7 10. The reactance 2/3 pitch windings, low waveform design has hinged doors to provide easy access distortion with non-linear loads and fault clearing for service and maintenance. short-circuit capability. Fuel tanks - Dual wall sub-base fuel tanks are offered as optional features, providing Control system - The PowerCommand® 1.1 electronic control is standard equipment and economical and flexible solutions to meet provides total generator set system integration extensive code requirements on diesel fuel including automatic remote starting/stopping, tanks. precise frequency and voltage regulation, alarm NFPA-The generator set accepts full rated load and status message display, output metering, in a single step in accordance with NFPA 110 for auto-shutdown at fault detection and NFPA 110 Level 1 systems. Level 1 compliance. The PowerCommand 2.3 Warranty and service Backed by a control is also optional and is UL 508 Listed and comprehensive warrantyand worldwide provides AmpSentryTM protection. p distributor network. Standby Prime 60 Hz 60 Hz Model kW kVA kW kVA Data sheets C50D6C 50 63 45 56 NAD-6333-EN C60D6C 60 75 54 68 NAD-6334-EN C80D6C 80 100 72 90 NAD-6335-EN C100D6C 100 125 90 113 NAD-6336-EN C125D6C 125 156 112.5 141 NAD-6216-EN Our energy working for you.' power.cummins.com ©2019 Cummins Inc. I NAS-6211-EN.DOCX(06/19)A055Y560 1 Generator set specifications Governor regulation class IS08528 Part 1 Class G3 Voltage regulation,no load to full load ±1.0% Random voltage variation ±1.0% Frequency regulation Isochronous Random frequency variation ±0.50% Radio frequency emissions compliance FCC code title 47 part 15 class A and B Engine specifications Design Turbocharged and charge air cooled Bore 107 mm(4.21 in.) Stroke 124 mm(4.88 in.) Displacement 4.5 L(272 in3) Cylinder block Cast iron,in-line 4 cylinder Battery capacity 850 amps per battery at ambient temperature of 0°C(32 °F) Battery charging alternator 100 amps Starting voltage 2 x 12 volt in parallel,negative ground Lube oil filter type(s) Spin-on with relief valve Standard cooling system High ambient radiator Rated speed 1800 rpm Alternator specifications Design Brushless,4 pole,drip proof,revolving field Stator 2/3 pitch Rotor Direct coupled,flexible disc Insulation system Class H per NEMA MG1-1.65 Standard temperature rise 120°C(248 °F)Standby Exciter type Torque match(shunt)with PMG as option Alternator cooling Direct drive centrifugal blower AC waveform Total Harmonic Distortion(THDV) <5%no load to full linear load,<3%for any single harmonic Telephone Influence Factor(TIF) <50 per NEMA MG1-22.43 Telephone Harmonic Factor(THF) <3% Available voltages 1-phase 3-phase • 120/240 • 120/208 • 120/240 4: • 347/600 • 127/220 Generator set options Fuel system Control Cooling system • Basic fuel tanks • AC output analog meters I• Shutdown—low coolant level • Regional fuel tanks I • Stop switch—emerciencvl • warning—low coolant level Engine • Auxiliary output relays(2) I • Extension—coolant drain I • Engine air cleaner—normal or heavy • Auxiliary configurable signal • Coolant heater options: duty inputs(8)and relay outputs(8) -<4°C(40°F)—cold weather • Shut down—low oil pressure Electrical -<-18 °C(0°F)—extreme cold I • Extension—oil drain I • One two or three circuit breaker Exhaust system • Engine oil heater configurations • Exhaust connector NPT Alternator I. 80%rated circuit breakers I • Exhaust muffler mounted • 120 °C temperature rise alternator • 80%or 100%rated LSI circuit Generator set application I • 105 °C teper ture rise alternator I • breakers m • Base barrier—elevated genset f PMG excitation • Battery charger • Radiator outlet duct adapter • Alternator neater, 120 V Enclosure Warranty • Reconnectable full 1 phase output I • Level2 m enclosur Sound Level 1 or • Base warranty—2 year/1000 hours, alternator sandstone o green color Standby • Aluminium weather protective enclosure • Base warranty—1 year/unlimited with muffler installed,green color hours,Prime • 3 year Standby warranty options • 5 year Standby warranty options Our energy working for you." power.cummins.com ©2019 Cummins Inc. I NAS-6211-EN.DOCX(08/19)A055Y560 Generator set accessories • Coolant heater • Remote monitoring device— • Alternator PMG excitation • Battery heater kit PowerCommand 500/550 • Alternator heater • Engine oil heater • Battery charger—stand-alone, 12 V • Remote control displays • Circuit breakers • Auxiliary output relays (2) • Enclosure Sound Level 1 to Sound • Auxiliary configurable signal Level 2 upgrade kit inputs (8) and relay outputs(8) • Base barrier—elevated generator • Annunciator—RS485 set • Audible alarm • Mufflers—industrial, residential or critical Control system PowerCommand 1.1 • Low coolant temperature warning " • High, low and weak battery voltage warning 1> • Fail to start(over crank)shutdown • Fail to crank shutdown • Redundant start disconnect $I$*UQ • Cranking lockout • Sensor failure indication • Low fuel level warning or shutdown PowerCommand control is an integrated generator set Alternator data control system providing voltage regulation,engine protection, operator interface and isochronous governing (optional). Major ' Line-to-Line and Line-to-neutral AC volts features include: • 3-phase AC current • Battery monitoring and testing features and smart starting • Frequency control system. • Total kVA • Standard PCCNet interface to devices such as remote Engine data annunciator for NFPA 110 applications. • DC voltage • Control boards potted for environmental protection. • Lube oil pressure • Control suitable for operation in ambient temperatures from • Coolant temperature -40 °C to+70 °C (-40 °F to+158 °F) and altitudes to 5000 • Engine speed meters (13,000 feet). Other data • Prototype tested; UL,CSA, and CE compliant. • Generator set model data • InPowerrM PC-based service tool available for detailed diagnostics. • Start attempts,starts, running hours Operator/display panel • Fault history • Manual off switch • RS485 Modbus®interface • Alpha-numeric display with pushbutton access for viewing • Data logging and fault simulation (requires InPower engine and alternator data and providing setup,controls and service tool) adjustments (English or international symbols) Digital governing(optional) • LED lamps indicating generator set running, not in auto, • Integrated digital electronic isochronous governor common warning,common shutdown, manual run mode and •Temperature dynamic governing remote start Digital voltage regulation • Suitable for operation in ambient temperatures from • Integrated digital electronic voltage regulator -40 °C to+70 °C • 2-phase Line-to-Line sensing • Bargraph display(optional) AC protection • Configurable torque matching Control functions • Over current warning and shutdown • Over and under voltage shutdown •Time delay start and cooldown • Cycle cranking • Over and under frequency shutdown • PCCNet interface • Over excitation (loss of sensing)fault • (2) Configurable inputs • Field overload • (2) Configurable outputs Engine protection • Overspeed shutdown • Remote emergency stop • Low oil pressure warning and shutdown • Automatic Transfer Switch (ATS)control • High coolant temperature warning and shutdown • Generator set exercise,field adjustable • Low coolant level warning or shutdown Our energy working for you:" power.cummins.com ©2019 Cummins Inc. I NAS-6211-EN.DOCX(08/19)A055Y560 Options • AC output analog meters(bargraph) • Auxiliary output relays (2) -Color-coded graphical display of: • Remote annunciator with(3) configurable inputs and -3-phase AC voltage (4)configurable outputs -3-phase current • PMG alternator excitation - Frequency • PowerCommand 500/550 for remote monitoring and -kVa alarm notification(accessory) • Remote operator panel • Auxiliary,configurable signal inputs (8) and • PowerCommand 2.3 control with AmpSentry protection configurable relay outputs (8) Ratings definitions Emergency Standby Power(ESP): !!— Applicable for supplying power to varying electrical load ` — ' _ for the duration of power interruption of a reliable utility • ,►.• source. Emergency Standby Power(ESP) is inr�r,. - Dim"B" accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046,AS 2789, DIN 6271 and j BS 5514. Limited-Time Running Power(LTP): Applicable for supplying power to a constant electrical !ff _• load for limited hours. Limited Time Running Power(LTP) is in accordance with ISO 8528. uItl,f/ i " Prime Power(PRP): _� r11r�/ Dim"C Applicable for supplying power to varying electrical load • for unlimited hours. Prime Power(PRP) is in accordance with ISO 8528. Ten percent overload capability is Q available in accordance with ISO 3046,AS 2789, DIN 6271 and BS 5514. Dim"A" Base Load(Continuous) Power(COP): Applicable for supplying power continuously to a constant This outline drawing is for reference only. See respective electrical load for unlimited hours. Continuous Power model data sheet for specific model outline drawing (COP) in accordance with ISO 8528, ISO 3046,AS 2789, number. DIN 6271 and BS 5514. Do not use for installation design Our energy working for you.'" power.cummins.com ©2019 Cummins Inc. NAS-6211-EN.DOCX(08/19)A055Y560 Dim "A" Dim "B" Dim "C" Set weight*wet Model mm (in.) mm(in.) mm(in.) kg(lbs.) Open set •_•D6C 2482 (98) 965 (38) 1321 (52) 958(2113) C60D- 4111111111_ 2482 (98) 965 (38) 1321 (52) 1006 (2217 C80D6C _ 2482 (98) 965 (38) 1321 (52) 105' " 24) C100D6C �`482 (98) 965(38) 1321 (52) 06(2439) C125D6CEiritti ) 965 (38) 1321 (52) 11173 (2586) Weather protective enclosure C50D6C 2482 (98) 1016 (40) . ii ■ 1039(2290) C60D6C 2482 (98) 1 0. • (40) 1473(58) 1087(2396) C80D6C 2482 (98) 1016 (400 1473(58) 1135 (2503) C100D6C 2482 (98) 10 . 40) 1187(2618) C125D6C 2482 (98) 1016 (40) igrialia.11111 1254(2765) Sound attenuated enclosure Level 1 C50D6C 3016 `) 1016 (40) 1473 (58) _ 1221 (2693) C60D6C r 6 (119) 1016 (40) 1473 (58) `1137(2507) C80D6C ' 3016 (119) 1016 (40) 1473 (58) 2614) C100DdigglIM3016 (119) 1016 (40) 1473 (58) Eilliki D6C 3016 (119) 1016 (40) 1473(58) 1304(2876) Sound attenuated enclosure Level 2 C50D6C 3456 (136) 1016 (40) 1473 (58) 1228 (2708) C60D6C 3456 (136) 1016 (40) 1473 (58) 1144(2522) C80D6C 3456 (136) 1016 (40) 1473 (58) 1192 (2629) C100D6C 3456 (136) 1016 (40) 1473 (58) 1244(2744) C125D6C 3456 (136) 1016 (40) 1473 (58) 1311 (2891) Weights above are average.Actual weight varies with product configuration. Our energy working for you.' power.cummins.com ©2019 Cummins Inc. I NAS-6211-EN.DOCX(08/19)A055Y560 Codes and standards Codes or standards compliance may not be available with all model configurations—consult factory for availability. This generator set is designed in facilities certified to ISO 9001 The generator set is available A. ISO and manufactured in facilities Listed to UL 2200, Stationary certified to ISO 9001 or Engine Generator Assemblies. ISO 9002. The Prototype Test Support (PTS)program verifies the performance integrity of the Engine certified to U.S. EPA SI generator set design. Cummins products bearing the PTS U.S. EPA Stationary Emission Regulation symbol meet the prototype test 40 CFR, Part 60. requirements of NFPA 110 for Level 1 systems. All low voltage models are CSA International The generator set is certified to C40certified to product class Building International Building Code (IBC) 4215-01. Code 2012. Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building's electrical system except through an approved device or after building main switch is open. For more information contact your local Cummins distributor or No visit power.cummins.com GO° Our energy working for you." ©2019 Cummins Inc.All rights reserved.Cummins is a registered trademark of Cummins Inc.PowerCommand,AmpSentry,InPower and"Our energy working for you."are trademarks of Cummins Inc.Other company,product,or service names may be trademarks or service marks of others.Specifications are subject to change without notice. NAS-6211-EN.DOCX(08/19)A055Y560 Specification Sheet `, PowerCommand® PuwerCunareund 1 . 1 Control System •sera eo Description Features The PowerCommand control system is a Easy to view: HMI 211 RS for residential use. microprocessor-based generator set monitoring, 128 x 64 pixel graphic LED backlight LCD. metering and control system designed to meet Easy to use:Tactile buttons for generator set the demands of today's engine driven generator start/stop. Residential Standby display for sets.The integration of all control functions into convenient use. a single control system provides enhanced reliability and performance compared to Modbus®interface: Eliminates need for conventional generator set control systems. MODLON. These control systems have been designed and Progressive protective functions:Advanced tested to meet the harsh environment in which Overcurrent Protection—Generator set gensets are typically applied. monitoring &protection. Digital voltage regulation: Single phase full wave SCR type regulator compatible with either shunt or PMSG systems. Digital engine speed governing: Provides isochronous frequency regulation. 12 and 24 VDC battery operation. Automatic mains failure: Smooth&automatic transfer and re-transfer of load from utility to generator set&vice-versa. Exerciser clock: Runs generator set exerciser routines for dependability of operation. Warranty and service: Backed by a comprehensive warranty and worldwide distributor service network. Certification: Suitable for us on generator sets that are designed, manufactured,tested and certified to relevant UL, NFPA, ISO, IEC Mil Std., CE and CSA standards. Our energy working for you.' power.cummins.com ©2019 Cummins Inc.I PDS-1566 I PD00000147 i(09/19) PowerCommand Digital Generator • Configurable inputs and outputs-Four discrete inputs and Set Control two dry contact relay outputs. • PCC 1302 •Warranty and service-Backed by a comprehensive warranty and worldwide distributor service network. • Certifications-Suitable for use on generator sets that are h §;t r fi•m designed,manufactured,tested and certified to relevant UL, NFPA, ISO, IEC, Mil Std.,CE and CSA standards. - .10 r Base Control Functions r )' HMI capability �ai fr i t•�3} t , Operator adiustments The HMI includes provisions for many 14 "; � p � � set up and adjustment functions. Generator set hardware data-Access to the control and software part number,generator set rating in kVA and generator set model number is provided from the HMI or Description lnPowerTM. The PowerCommand generator set control is suitable Data logs-Includes engine run time,controller on time, number for use on a wide range of generator sets in non- of start attempts. paralleling applications.The PowerCommand control is Fault history-Provides a record of the most recent fault compatible with shunt or PMG excitation style. It is conditions with control hours time stamp. Up to 10 events are suitable for use with reconnectable or non- stored in the control non-volatile memory. reconnectable generators,and it can be configured for Alternator data any frequency,voltage and power connection from 120-600 VAC Line-to-Line. •Voltage(single or three phase Line-to-Line and Line-to- Neutral) Power for this control system is derived from the • Current(single or three phase) generator set starting batteries.The control functions over a voltage range from 8 VDC to 30 VDC. • kVA(three phase and total) Features • Frequency • Engine data • 12 and 24 VDC battery operation. • Starting battery voltage • Digital voltage regulation. • Engine speed • Digital engine speed governing(where applicable)- Provides isochronous frequency regulation. • Engine temperature • Full authority engine communications(where • Engine oil pressure applicable)-Provides communication and control • Partial Full Authority Engine(FAE)data(where applicable) with the Engine Control Module(ECM). • Service adiustments-The HMI includes provisions for • Common harnessing-with higher feature Cummins adjustment and calibration of generator set control functions. controls allows for easy field upgrades. Adjustments are protected by a password. Functions include: • Generator set monitoring-Monitors status of all • Engine speed governor adjustments critical engine and alternator functions. •Voltage regulation adjustments • Digital genset metering(AC and DC). • Cycle cranking • Genset battery monitoring system-to sense and • Configurable fault set up warn against a weak battery condition. • Configurable output set up • Engine starting-Includes relay drivers for starter, • Meter calibration fuel shut off(FSO),glow plug/spark ignition power . Units of measurement and switch B+applications. • Generator set protection-Protects engine and alternator. •Advanced serviceability-using InPowerTM, a PC- based software service tool. • Environmental protection-The control system is designed for reliable operation in harsh environments.The main control board is a fully encapsulated module that is protected from the elements. • Exerciser function—Routine exercising of generator set. • Supports dual fuel control. •Automatic Mains Failure function built in generator set controller. Modbus interface-for interconnecting to customer equipment. Our energy working for you.' power.cummins.corn 02019 Cummins Inc. PDS-1566 I PD00000147 I(09/19) Engine control Torque-matched V/Hz overload control-The voltage roll-off SAE-J1939 CAN interface to full authority ECMs(where set point and rate of decay(i.e.the slope of the V/Hz curve) applicable)-Provides data swapping between genset and is adjustable in the control. engine controller for control, metering and diagnostics. Protective Functions 12 VDC/24 VDC battery operations-PowerCommand will On operation of a protective function the control will operate either on 12 VDC or 24 VDC batteries. indicate a fault by illuminating the appropriate status LED Isochronous governing(where applicable)-Capable of on the HMI,as well as display the fault code and fault controlling engine speed within+/-0.25%for any steady description on the LCD.The nature of the fault and time of state load from no load to full load. Frequency drift will not occurrence are logged in the control.The service manual exceed+/-0.5%for a 33°C(60°F)change in ambient and InPower service tool provide service keys and temperature over an 8 hour period. procedures based on the service codes provided. Temperature dependent governing dynamics(with Protective functions include: electronic governing)-Modifies the engine governing Battle short mode control parameters as a function of engine temperature. When enabled and the battle short switch is active,the This allows the engine to be more responsive when warm control will allow some shutdown faults to be bypassed. If a and more stable when operating at lower temperature bypassed shutdown fault occurs,the fault code and levels. description will still be annunciated,but the genset will not Remote start mode-Accepts a ground signal from remote shutdown.This will be followed by a fail to shutdown fault. devices to automatically start the generator set and Emergency stop shutdowns and others that are critical for immediately accelerate to rated speed and voltage.The proper operation are not bypassed. Please refer to the remote start signal will also wake up the control from sleep Control Application Guide or Manual for list of these faults. mode.The control can incorporate a time delay start and Configurable alarm and status inputs stop. Remote and local Emergency stop-The control accepts a The control accepts up to four alarm or status inputs ground signal from a local(genset mounted)or remote (configurable contact closed to ground or open)to indicate (facility mounted) Emergency stop switch to cause the a configurable(customer-specified)condition.The control is programmable for warning,shutdown or status indication generator set to immediately shut down.The generator set is prevented from running or cranking with the switch and for labelling the input. engaged. If in sleep mode,activation of either Emergency Emergency stop stop switch will wake up the control. Annunciated whenever either Emergency stop signal is Sleep mode-The control includes a configurable low received from external switch. current draw state to minimize starting battery current draw General engine protection when the genset is not operating.The control can also be Low and high battery voltage warning-Indicates status of configured to go into a low current state while in auto for battery charging system(failure)by continuously monitoring Prime applications or applications without a battery battery voltage. charger. Weak battery warning-The control system will test the Engine starting-The control system supports automatic battery each time the generator set is signaled to start and engine starting. Primary and backup start disconnects are indicate a warning if the battery indicates impending failure. achieved by one of three methods:magnetic pickup, Fail to start(overcrank)shutdown-The control system will battery charging alternator feedback or main alternator indicate a fault if the generator set fails to start by the output frequency.The control also supports configurable completion of the engine crack sequence. glow plug control when applicable. Fail to crank shutdown-Control has signaled starter to Cycle cranking-Configurable for the number of starting crank engine but engine does not rotate. cycles(1 to 7)and duration of crank and rest periods. Cranking lockout-The control will not allow the starter to Control includes starter protection algorithms to prevent the attempt to engage or to crank the engine when the engine operator from specifying a starting sequence that might be is rotating. damaging. Hydro mechanical fuel system engine protection Time delay start and stop(cooldown)-Configurable for time delay of 0-300 seconds prior to starting after receiving Overspeed shutdown-Default setting is 115%of nominal. a remote start signal and for time delay of 0-600 seconds Low lube oil pressure warning/shutdown-Level is prior to shut down after signal to stop in normal operation pre-set(configurable with InPower)to match the modes.Default for both time delay periods is 0 seconds. capabilities of the engine used.Control includes time Alternator control delays to prevent nuisance alarms. The control includes an integrated line-to-line sensing High lube oil temperature warning/shutdown-Level is pre- voltage regulation system that is compatible with shunt or set(configurable with InPower)to match the capabilities of PMG excitation systems.The voltage regulation system is the engine used.Control includes time delays to prevent full wave rectified and has an SCR output for good motor nuisance alarms. starting capability. Major system features include: High engine temperature warning/shutdown-Level is pre- Digital output voltage regulation-Capable of regulating set(configurable with InPower)to match the capabilities of output voltage to within+/-1.0%for any loads between no the engine used.Control includes time delays to prevent load and full load.Voltage drift will not exceed+/-1.5%for nuisance alarms. a 40°C(104°F)change in temperature in an eight hour Low coolant temperature warning-Indicates that engine period.On engine starting or sudden load acceptance, temperature may not be high enough for a 10 second start voltage is controlled to a maximum of 5%overshoot over or proper load acceptance. nominal level. Sensor failure indication-Logic is provided on the base The automatic voltage regulator feature can be disabled to control to detect analog sensor or interconnecting wiring allow the use of an external voltage regulator. failures. Our energy working for you:' power.cummins.com ©2019 Cummins Inc.I PDS-1566 I PD00000147 I(09/19) Full authority electronic engine protection Advanced Functions Engine fault detection is handled inside the engine ECM. Automatic mains failure* Fault information is communicated via the SAE-J1939 data link for annunciation in the HMI The built in AMF feature provides the automatic transfer Alternator protection and re-transfer of the load from utility to generator set and vice-versa. High AC voltage shutdown(59) Output voltage on any •Automatically starts-stops the generator set in the event phase exceeds pre-set values.Time to trip is inversely of utility failure. proportional to amount above threshold.Values adjustable from 105-130%of nominal voltage,with time delay •Annunciates faults. adjustable from 0.1-10 seconds. Default value is 110%for LOAD 10 seconds. Low AC voltage shutdown(27)-Voltage on any phase has SOURCE 1 dropped below a pre-set value.Adjustable over a range of OOURCE' UTILITY 50-95%of reference voltage,time delay 2-20 seconds. Default value is 85%for 10 seconds. i 1 Overcurrent warning/shutdown-Implementation of the 10 I thermal damage curve with instantaneous trip level 1TRRAP IR "``"— calculated based on current transformer ratio and application power rating. "A'E'°`°'° "°"""' msaloul '" A �ryXI.r c«ry Vrc ma nE [M - AL ERNATOR ' ,•,.,, .., L � 116 T Mf_] F f;RMAL START/STOP I OENSET CONTRO ry d ,AGE OPERATIOR Cu.VE OVERCU Remote HMI Will 10 CROP!RRENT CURVE • 1 *A utility voltage monitoring sensor(as shown in the AMF \ diagram above)must be connected in order to use the AMF feature on the 1302 control. Use Schneider Electric Relay Inst ntaneous Trip Point RSB1 A120U7 and Socket RSZE1S35M. Exerciser clock 0.03 The exerciser clock runs the generator set exerciser routines for dependability of operation. • I 10 Amps(x rated) Field Control Interface Under frequency shutdown(81 u)-Generator set output Input signals to the base control include: frequency cannot be maintained.Settings are adjustable from 2-10 Hz below nominal governor set point,for a 5-20 - Remote start second time delay. Default:6 Hz, 10 seconds. - Local and Emergency stop Over frequency shutdown/warninq(81 o)-Generator set is Configurable inputs:Control includes(4)input signals operating at a potentially damaging frequency level. from customer discrete devices that are configurable for warning,shutdown or status indication,as well as Settings are adjustable from 2-10 Hz above nominal governor set point for a 1-20 second time delay. Default: 6 message displayed. Hz, 10 seconds,enabled. Output signals from the PowerCommand control Loss of sensing voltage shutdown-Shutdown of generator include: set will occur on loss of voltage sensing inputs to the - Configurable relay outputs:Control includes(2)relay control. output contacts rated at 2 A.These outputs can be Field overload shutdown-Uses field voltage to shutdown configured to activate on any control warning or shutdown fault as well as ready to load, not in auto, generator set when a field overload condition occurs. common alarm,common warning and common shutdown. - Ready to load(generator set running)signal: Operates when the generator set has reached 90%of rated speed and voltage and latches until generator set is switched to off or idle mode. Our energy working for you." power.cummins.com ©2019 Cummins Inc.I PDS-1566 I PD00000147 I(09/19) - PowerCommand Human Machine Mechanical Drawing Interface HMI211 33.5(132) 141(5.56) ► 0 0 ' • • 111(4.36) 0000 0 0 •■a•A O - HM • Dimensions:mrn(inches) Description This control system includes an intuitive operator interface panel that allows for complete genset control as well as Software system metering,fault annunciation,configuration and InPower(beyond 6.0 version)is a PC-based software diagnostics.The interface includes five generator set status service tool that is designed to directly communicate to LED lamps with both internationally accepted symbols and PowerCommand generator sets and transfer switches,to English text to comply with customer needs.The interface facilitate service and monitoring of these products. also includes an LED backlit LCD display with tactile feel soft-switches for easy operation and screen navigation. It is Environment configurable for units of measurement and has adjustable The control is designed for proper operation without screen contrast and brightness. recalibration in ambient temperatures from-40°C(-40°F) The run/off/auto switch function is integrated into the to+70°C(158°F),and for storage from-55°C(-67°F)to interface panel. +80°C(176°F).Control will operate with humidity up to All data on the control can be viewed by scrolling through 95%, non-condensing. screens with the navigation keys.The control displays the The HMI is designed for proper operation in ambient current active fault and a time-ordered history of the five temperatures from-40°C*(-40°F)to+70°C(158°F), and previous faults. for storage from-40°C*(-40°F)to+80°C(176°F). Features The control board is fully encapsulated to provide superior resistance to dust and moisture.Display panel has a single • LED indicating lamps: membrane surface,which is impervious to effects of dust, - Remote start moisture,oil and exhaust fumes.This panel uses a sealed - Not in auto membrane to provide long reliable service life in harsh - Shutdown environments. - Warning The control system is specifically designed and tested for - Auto resistance to RFI/EMI and to resist effects of vibration to - Run provide a long reliable life when mounted on a generator • 128 x 64 pixels graphic LED backlight LCD. set.The control includes transient voltage surge • Four tactile feel membrane switches for LCD defined suppression to provide compliance to referenced operation.The functions of these switches are defined standards. dynamically on the LCD. *Heater accessory(pn:A040H853)is available for •Two tactile feel membrane switches dedicated for off and enhanced operation below-20°C back. Certifications •Allows for complete genset control setup. PowerCommand meets or exceeds the requirements of the • Certifications:Suitable for use on generator sets that are following codes and standards: designed, manufactured,tested and certified to relevant - NFPA 110 for level 1 and 2 systems. UL,NFPA, ISO, IEC, Mil Std.,CE and CSA standards. - ISO 8528-4: 1993 compliance,controls and switchgear. • HMI 211 RS provides convenience for residential use. - CE marking:The control system is suitable for use on generator sets to be CE-marked. Communications Connections - EN 50081-1,2 residential/light industrial emissions or PC tool interface-This RS-485 communication port allows industrial emissions. - EN 50082-1,2 residential/light industrial or industrial the HMI to communicate with a personal computer running susceptibility. InPower. - ISO 7637-2,level 2;DC supply surge voltage test. This RS-485 communication port allows the HMI to - Mil Std.202C,Method 101 and ASTM B117:Salt fog test. communicate with the main control board. - PowerCommand control systems and generator sets are designed and manufactured in ISO 9001 certified facilities. - UL 6200 recognized and suitable for use on UL 2200 Listed generator sets. - CSA C282-M1999 compliance. - CSA 22.2 No. 14 M91 industrial controls. Our energy working for you. power.cummins.com ©2019 Cummins Inc.I PDS-1566 I PD00000147 I(09/19) Warranty All components and subsystems are covered by an express limited one year warranty.Other optional and extended factory warranties and local distributor maintenance agreements are available Accessories 1301-1302 Upgrade Kit(HM) 0541-1431 PowerCommand 500(LAN) A040X126 Remote HMI 211 0541-1394 Remote HMI 211RS A046K103 I/O Expansion(Aux 101) 0541-1291 HMI Heater Accessory Kit A040H853 Parts Ordering Information 1302 Control Board 0327-1617-02 1302 control Board—Arrow A043W505 Aux 104(Governor Control) 0327-1507 HMI 211 Without Heater 0300-6014 HMI 211 with Heater A026G237 Additional Resources Resource Where to find 1302 Service Manual QSOL Accessories Catalog cumminspower.com Additional Controls Information PowerSuite Library RCS COMPATIBLE For more information contact your local Cummins distributor or visit power.cummins.com Gv� Our energy working for you.' ©2019 Cummins Inc.All rights reserved.Cummins is a registered trademark of Cummins Inc.PowerCommand,AmpSentry,InPower and"Our energy working for you."are trademarks of Cummins Inc.Other company,product,or service names may be trademarks or service marks of others.Specifications are subject to change without notice. PDS-1566 1 PD000001471(09/19) S to `v- Generator set data sheet Model: C125D6C Frequency: 60 Hz Fuel type: Diesel KW rating: 125 standby 112.5 prime Emissions level: EPA Tier 3, Stationary emergency Exhaust emission data sheet: EDS-1254 Exhaust emission compliance sheet: EPA-1354 Sound performance data sheet: MSP-1304 Cooling performance data sheet: MCP-1404 Prototype test summary data sheet: PTS-451 Standby Prime Fuel consumption kW(kVA) kW(kVA) Ratings 125(156) 112.5(141) Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full US gph 3.30 6.10 8.30 10.30 3.00 5.60 8.40 9.30 L/hr 12.49 23.09 31.42 38.99 11.36 21.20 31.80 35.20 Standby Prime Engine rating rating Engine manufacturer Cummins Inc. Engine model QSB5-G6 Configuration Cast iron,in-line,4 cylinder Aspiration Turbocharged and charge air cooled Gross engine power output,kWm(bhp) 155(208) 136(183) BMEP at set rated load,kPa(psi) 2317(336) 2041 (296) Bore,mm(in) 107(4.21) Stroke, mm(in) 124(4.88) Rated speed,rpm 1800 Piston speed,m/s(ft/min) 7.44(1464) Compression ratio 17.3:1 Lube oil capacity,L(qt) 12.2(12.9) Overspeed limit,rpm 2250 Fuel flow Maximum fuel flow,L/hr(US gph) 95(25.0) Maximum fuel inlet restriction with clean filter,mm Hg(in Hg) 127(5.0) Our energy working for you. power.cummins.com @2018 Cummins Inc. I NAD-6216-EN(03/18)A055Y559 Standby Prime Air rating rating Combustion air,m3/min(scfm) 10.42(368) 10.48(370) Maximum air cleaner restriction with clean filter,kPa(in H2O) 1.25(5) Exhaust Exhaust flow at set rated load,ma/min(cfm) 25.6(903) 24.4(861) Exhaust temperature,°C(°F) 528(982) 489(913) Maximum back pressure,kPa(in H2O) 10(40.19) 10(40.19) Actual exhaust back pressure with CPG sound level 2 enclosure 0(0) 0(0) muffler,kPa(in H2O) Actual exhaust back pressure with CPG weather enclosure 0(0) 0.5(2) muffler,kPa(in H2O) - Standard set-mounted radiator cooling Ambient design,°C(°F) 40(104) Fan load,kW.(HP) 5.22(7) Coolant capacity(with radiator),L(US Gal) 16(4.2) Cooling system air flow,ma/min(scfm) 218.04(7700) Total heat rejection,MJ/min(Btu/min) 14.17(13429) 13.06(12382) Maximum cooling air flow static restriction,kPa(in H2O) 0.12(0.5) Weight2 Unit wet weight kgs(Ibs) 1173(2586) Notes: 1 For non-standard remote installations contact your local Cummins Power Generation representative. 2 Weights represent a set with standard features. See outline drawing for weights of other configurations. Derating factors Engine power available up to 1097 m(3600 ft)and ambient temperatures up to 40°C(104°F).Above Standby these conditions,derate at 35%per 300 m(1000 ft)and 53%per 10°C(18°F) Engine power available up to 1158 m(3800 ft)and ambient temperatures up to 40°C(104°F).Above Prime these conditions,derate at 35%per 300 m(1000 ft)and 58%per 10°C(18°F) Ratings definitions Limited-time running power Base load(continuous)power Emergency standby power(ESP): (LTP): Prime power(PRP): (COP): Applicable for supplying power to Applicable for supplying power to Applicable for supplying power Applicable for supplying power varying electrical load for the a constant electrical load for to varying electrical load for continuously to a constant duration of power interruption of a limited hours. Limited Time unlimited hours.Prime Power electrical load for unlimited reliable utility source.Emergency Running Power(LTP)is in (PRP)is in accordance with hours.Continuous Power Standby Power(ESP)is in accordance with ISO 8528. ISO 8528.Ten percent overload (COP)is in accordance with accordance with ISO 8528.Fuel capability is available in ISO 8528,ISO 3046, Stop power in accordance with accordance with ISO 3046, AS 2789,DIN 6271 and ISO 3046,AS 2789,DIN 6271 and AS 2789,DIN 6271 and BS 5514. BS 5514. BS 5514. Our energy worldn9 for You power.cummins.com Cd2016 Cummins Inc. I NAD-6216-EN(03/18)A055Y559 So 20Z -002214 Y Alternator data Standard Alternators Single phase2 Three phases Maximum temperature rise above 40°C ambient 120 °C 120 °C 120°C 120 °C 120°C Feature code BB90-2 B946-2 B986-2 B952-2 BB86-2 Alternator data sheet number ADS-209 ADS-208 ADS-208 ADS-208 ADS-208 Voltage ranges 120/240 120/208 120/240 347/600 127/220 Voltage feature code R104-2 R098-2 R106-2 R114-2 R020-2 Surge kW 137.8 141.8 141.8 143.5 142.6 Motor starting kVA(at 90%sustained voltage)Shunt 516 516 422 516 Motor starting kVA(at 90%sustained voltage)PMG 607 607 497 607 Full load current amps at standby rating 521 434 376 188 411 Alternator data Standard Alternators Single phase2 Three phases Maximum temperature rise above 40 °C ambient 105°C 105 °C 105°C 105 °C 105°C 105 °C Feature code BB91-2 BB93-2 BB94-2 BB95-2 BB92-2 BB85-2 Alternator data sheet number ADS-209 ADS-209 ADS-209 ADS-208 ADS-208 ADS-209 Voltage ranges 120/240 120/208 120/240 277/480 347/600 127/220 Voltage feature code R104-2 R098-2 R106-2 R002-2 R114-2 R020-2 Surge kW 137.8 143.5 143.5 143.5 143.5 143.8 Motor starting kVA(at 90%sustained voltage)Shunt 516 516 422 422 516 Motor starting kVA(at 90%sustained voltage)PMG 607 607 497 497 607 Full load current amps at standby rating 521 434 376 188 150 411 Notes: 1 Single phase power can be taken from a three phase generator set at up to 2/3 set rated 3-phase kW at 1.0 power factor 2 Full single phase output up to full set rated 3-phase kW at 1.0 power factor Formulas for calculating full load currents: Three phase output Single phase output kW x 1000 kW x SinglePhaseFactor x 1000 Voltage x 1.73 x 0.8 Voltage Warning:Back feed to a utility system can cause electrocution and/or property damage.Do not connect to any building's electrical system except through an approved device or after building main switch is open. North America 1400 73rd Avenue N.E. Minneapolis,MN 55432 USA Phone 763 574 5000 ��o Fax 763 574 5298 Go`r Our energy working for you.' 02018 Cummins Inc.All rights reserved. Cummins is a registered trademarks of Cummins Inc.PowerCommand,AmpSentry,InPower and"Our energy working for you."are trademarks of Cummins.Other company,product,or service names ppwer.CUmmIt1S.COm may be trademarks or service marks of others.Specifications are subject to change without notice. NAD-6216-EN(03/18)A055Y559