Plans
ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE AC ALTERNATING CURRENT BLDG 1. THIS SYSTEM IS GRID-INTERTIED VIA A UL-LISTED FEB 2 7 2023 BUILDING CONC CONCRETE DC DIRECT CURRENT POWER-CONDITIONING INVERTER. EGC EQUIPMENT GROUNDING CONDUCTOR (E) 2. A NATIONALLY - RECOGNIZED TESTING CITY OF TIGARD EXISTING EMT ELECTRICAL METALLIC TUBING FSB LABORATORY SHALL LIST ALL EQUIPMENT IN VALIDITY OF PERMIT BUILDING DIVISION FIRE SET-BACK GALV GALVANIZED GEC GROUNDING COMPLIANCE WITH ART. 110.3. THE OF A PERMIT ELECTRODE CONDUCTOR GND GROUND HDG HOT 3. WHERE ALL TERMINALS OF THE DISCONNECTING BASED ISSUANCEON CO OF A PERMIT DIPPED GALVANIZED I CURRENT Imp CURRENT AT MEANS MAY BE ENERGIZED IN THE OPEN POSITION, DOCUMENTS AND OTHER N MAX POWER Isc SHORT CIRCUIT CURRENT kVA A SIGN WILL BE PROVIDED WARNING OF THE KILOVOLT AMPERE kW KILOWATT LBW LOAD HAZARDS PER ART. 690.17. DATA SHALL NOT PREVENT BEARING WALL MIN MINIMUM (N) NEW NEUT 4. EACH UNGROUNDED CONDUCTOR OF THE THE CODE OFFICIAL FROM NEUTRAL NTS NOT TO SCALE OC ON CENTER PL MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY REQUIRING THE CORRECT'ON PROPERTY LINE P01 POINT OF INTERCONNECTION PHASE AND SYSTEM PER ART. 210.5. OF ERRORS. ORSC 105.4 PV PHOTOVOLTAIC SCH SCHEDULE S STAINLESS 5. CIRCUITS OVER 250V TO GROUND SHALL COMPLY OFFICE COPY STEEL STC STANDARD TESTING CONDITIONS TYP WITH ART. 250.97, 250.92(B). TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V 6. DC CONDUCTORS EITHER DO NOT ENTER BUILDING LIABILITYVOLT Vmp VOLTAGE AT MAX POWER Voc VOLTAGE OR ARE RUN IN METALLIC RACEWAYS OR AT OPEN CIRCUIT W WATT 3R NEMA 3R, RAINTIGHT ENCLOSURES TO THE FIRST ACCESSIBLE DC The City of Tigard and its CITY OF TIGARD DISCONNECTING MEANS PER ART. 690.31(E). employees shall not be R EVIis��'I ll FOft,COI�E COMPLIANCE 7. ALL WIRES SHALL BE PROVIDED WITH STRAIN responsible for discrepancies ✓/ RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY which may appear herein. Approved plans tit-proved: [ ] UL LISTING. U I C: [ I 8. MODULE FRAMES SHALL BE GROUNDED AT THE UL shall be on job site. - LISTED LOCATION PROVIDED BY THE Per i»it #: Pik.51 Z — O<7>CO2 MANUFACTURER USING UL LISTED GROUNDING ticiclress: I1S57y SW TeLi �-' HARDWARE. 9. MODULE FRAMES, RAIL, AND POSTS SHALL BE Suite #: BONDED WITH EQUIPMENT GROUND CONDUCTORS. I3): MS Date: /2,7/Z...5 VICINITY MAP INDEX �'1 ' =t '� Sheet 1 COVER SHEET i , �' Sheet 2 SITE PLAN ,,,,,,,, /.:, 44 :1*-::- v Sheet 3 STRUCTURAL VIEWS " ° '" Sheet 4 UPLIFT CALCULATIONS y. Sheet 5 THREE LINE DIAGRAM LICENSE GENERAL NOTES ` � " ` s ' Sheet 6 ELECTRICAL CALCULATIONS 1. ALL WORK TO BE DONE TO THE 2022 OSSC $ X Ii"'{ " ' . i'VZi te Sheet 7 ELECTRICAL LOAD CALCULATIONS OR # 180498 . ��'I Sheet 8 SITE PLAN PLACARD RGC, CGC1 AND. 2021A ORSC I 2. ALL ELECTRICAL WORK SHALL COMPLY WITH � - � �"� R $ � - , .10 IF, = ,� Cutsheets Attached THE CURRENT NATIONAL ELECTRIC CODE AS - - AMENDED BY THE OREGON ELECTRICAL SPECIALTY CODE. MODULE GROUNDING METHOD: ZEP SOLAR ° e. - ' "REV BY DATE COMMENTS AHJ: Tigard �EN DATE COMMENTS Star BiIinquaI Daycai-e ©iIlil © , A " , UTILITY: Portland General Electric ©©© ° . re �. f Oregon, . {. e 1e i � ©© . CUSTOMER DESCRIPTION: MICR CONFIDENTIALESHALL- THE NOT BE US USED HEREIN JOB NUMBER: JB-9726577 OO NirajNischal 5 L WHEW n CONTAINED BE FOR NE SPEC Phase 1 Lot 68 6.8 KW PV ARRAY BENEFIT OF ANYONE EXCEPT OLEO INC., NOR MOUNTING 15574 SW Peace Ave 13.5 KWH ENERGY STORAGE SYSTEM SHALL IT BE DISCLOSED IN YkiOLE OR IN ZS Comp V4 w Flashing-Insert PART TO OTIIERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH Tigard, OR 97224 Electric Vehicle Charging System --- - - - --- NE SALE AND USE OF THE RESPECTIVE (17) Hanwha # Q.PEAK DUO BLK ML-G10.a+/TS 400 SHEET: REV: DATE TESLA EQUIPMENT, WITHOUT THE WEN goo.lEk PAGE NAME PERMISSION OF TESLA NC. Powerwall+ 240V ;1850000-00-C PVI Ass . 1538000-25-F River Terrace Crossing COVER SHEET 1 2/22/2023 PITCH: 18°(4:12) ARRAY PITCH:18° (4:12) MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180 MATERIAL:Comp Shingle STORY: 2 Stories E-Stop 1 © RELAY AC V'_dHH III ,-�, I I .--•, I .--•, I ( WC , ; ; I D , ; ESS) I I I • I LEGEND Q (E) UTILITY METER & WARNING LABEL U L----J 0 ® INVERTER W/ INTEGRATED DC DISCO Ei & WARNING LABELS (E) DRIVEWAYco AUTOMATIC RELAY -n �� DC DISCONNECT & WARNING LABELS F9 ,— AC DISCONNECT & WARNING LABELS f I °- 1.�If Q DC JUNCTION/COMBINER BOX & LABELS - -- �a-MP1 'fS8 —I ENERGY STORAGE SYSTEM FOR STAND I 141 I I ALONE OPERATION 4/1 I V I 1I O DISTRIBUTION PANEL & LABELS 36'I FBI L� 0LOAD CENTER & WARNING LABELS r J T Front Of House 7 1 I OB O DEDICATED PV SYSTEM METER is Rso RAPID SHUTDOWN Ili I I I 0 STANDOFF LOCATIONS -mwmffiva CONDUIT RUN ON EXTERIOR I - -- CONDUIT RUN ON INTERIOR L 4-21L FSB— J — GATE/FENCE 0 HEAT PRODUCING VENTS ARE RED liiil � , I INTERIOR EQUIPMENT IS DASHED L=J E-Stop EMERGENCY STOP PUSHBUTTON we TESLA WALL CONNECTOR SITE PLAN N TOTAL ARRAY AREA (SF): 369 TOTAL ROOF AREA (SF): 2330 Scale: 1/8" = 1' w °r E TOTAL ARRAY AREA IS a 15.82 0 1 8' 16' PERCENT OF TOTAL ROOF AREA n• S CUSTOMER: DEsaTwnaN: �� _ CONFIDENTIALISHALL- THE INFORMATION FORHEREINNE JOB NUMBER: ,J g-9726577 00 NirajNischal T -E 5 L n CONTAINED NOT BE USED NE SPEC Phase 1 Lot 68 6.8 KW PV ARRAY BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTER 15574 SW Peace Ave 13.5 KWH ENERGY STORAGE SYSTEM SHALL IT BE DISCLOSED IN WHOLE OR IN ZS Comp V4 w Flashing-Insert PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, EXCEPT IN CONNECTION WITH Tigard, OR 97224 Electric Vehicle Charging System -- NE SALE AND USE OF THE RESPECTIVE (17) Hanwha # Q.PEAK DUO BLK ML-G10.a+/TS 400 TESLA EQUIPMENT, PAGE NAME: SHEET: REV: DATE: 'MTHIXIT THE WRITTEN INVERTER: PERMISSION OF TESLA INC. Powerwall+ F240V) #1850000-00-C / PVI Assy. 1538000-25-F River Terrace Crossing SITE PLAN 2 2 22 2023 w �. (N) PV MODULE 0 �i �� (E) MOUNTING PLANE (MP) 0, TYPICAL PV SIDE VIEW NTS PV MODULE 5/16"x1.5" BOLT WITH 5/16" FLAT WASHER INSTALLATION ORDER ZEP LEVELING FOOT i LOCATE RAFTER, MARK HOLE ZEP ARRAY SKIRT (1) LOCATION, AND DRILL PILOT HOLE. ZEP MOUNTING BLOCK r,, Ji ATTACH FLASHING INSERT TO ��r __ •r_ ; (2) MOUNTING BLOCK AND ATTACH ZEP FLASHING INSERT `IPr� TO RAFTER USING LAG SCREW. (E) COMP. SHINGLE y -- INJECT SEALANT INTO FLASHING INSERT PORT, WHICH SPREADS (E) ROOF DECKING (3) SEALANT EVENLY OVER THE ROOF PENETRATION. 5/16" DIA STAINLESS LOWEST MODULE SUBSEQUENT MODULES STEEL LAG SCREW INSTALL LEVELING FOOT ON TOP (4) OF MOUNTING BLOCK & (E) RAFTER � SECURELY FASTEN WITH BOLT. Th.. 1 STANDOFF Scale: 1 1/2" = r CU5TOMETC DESCRWTNN: DESIGN: CONFIDENTIAL- THE INFORMATION HEREIN JCB MINDER:CONTAINED SHALL NOT BE USED FOR THE JB-9726577 00 SPEC Phase 1 Lot 68 6.8 KW PV ARRAY Niraj Nischal T 5 L P'1 BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM SHALL IT BE DISCLOSED IN MNOLE OR IN ZS Comp V4 w Flashing—Insert 15574 SW Peace Ave 13.5 KWH ENERGY STORAGE SYST EM PART TO OTHERS OUTSIDE THE RECIPIENTS MDDuIEs Tigard, OR 97224 Electric Vehicle Charging System 'M1 ORGANIZATION, EXCEPT IN CONNECTION H THE SALE MD USE OF THE RESPECTNE (17) Hanwha # Q.PEAK DUO BLK ML—G10.a+/TS 400 TESLA EQUIPMENT, WITHOUT PAGE NAME: SHEET REv: DATE: WITHOUT 7NE MITTENNYETER. PERMISSION OF TESLA INC. Powerwall+ [240V1 #1850000-00—C / PVI Assy. 1538000-25—F River Terrace Crossing STRUCTURAL VIEWS 2/22/2023 Jobsite Specific Design Criteria Design Code ASCE 7-16 Risk Category II Table 1.5-1 Ultimate Wind Speed V—Ult 115 Fig. 1609A Exposure Category C Section 26.7 Ground Snow Load pg 25 Table 7-1 Edge Zone Width a 3.8 ft Fig. 30.3-2A to I MP Specific Design Information MP Name MP1 Roofing Comp Shingle Standoff ZS Comp V4 w Flashing—Insert Pitch 18 SL/RLL: PV 25.0 SL/RLL: Non—PV 25.0 Standoff Spacing and Layout MP Name MP1 Landscape X—Spacing 72 Landscape 24 X—Cantilever Landscape Y—Spacing 41 Landscape — Y—Cantilever Portrait X—Spacing 24 Portrait X—Cantilever 15 Portrait Y—Spacing 74 Portrait Y—Cantilever — Layout Staggered X and Y are maximums that are always relative to the structure framing that supports the PV. X is across rafters and Y is along rafters. DESORPTION: DE9GN: CONFIDENTIAL- THE INFORMATION HEREIN JGB NUMBER: J B-9726577 00 CUSTOMER: Nira Nischal -r ® L CIXJTAINED SHALL NOT BEBE USED FORR THE S E SPEC Phase 1 Lot 68 6.8 KW PV ARRAY � BENEFIT OF ANYONE EXCEPT TESLA INC.,NOR MOONING SYSTEM 15574 SW Peace Ave 13.5 KWH ENERGY STORAGE SYSTEM SHALL IT BE DISCLOSED IN WHOLE OR IN ZS Comp V4 w Flashing—Insert PART TO OTHERS OUTSIDE THE RECIPIENT'S Tigard, OR 97224 Electric Vehicle Charging System ORGANIZATION, EXCEPT IN CONNECTION WITH MfOULES 9 9 9 THE SALE AND USE OF THE RESPECTIVE (17) Hanwha # Q.PEAK DUO BLK ML—G10.a+/TS 400 PACE NAME: SHEET: REV. DAIS: TESLA EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF IESLA INC. Powerwall+ [240V1 #1850000-00—C / PV1 Assy. 1538000-25—F River Terrace Crossing UPLIFT CALCULATIONS 2/22 2023 MAIN PANEL SPECS GENERAL NOTES PRODUCT SPECS MODULE SPECS LICENSE_ (17)Hanwha #Q.PEAK DUO BLK NL-G1D.o+/TS 400 OR i 180498 PanelNumber: Inv 1: DC Ungrounded 1 - (1)Powerwall+ [240V]/I850000-00 C/PM Assy. 1536000 25 F PV Module, 400W,371.5WPTC, ZEP, Black Frame, MC4, 1000V RGC, CGC1 Meeterr Number: Underground Service Entrance 2 Voc: 45.3 Vpmax: 37.13 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER (E) 225A MAIN SERVICE PANEL E—STOP Product 1 (E) 200A/2P MAIN CIRCUIT BREAKER BUTTON © AC DISCONNECT Q ENERGY STORAGE Q A Q DC* —/ 1ESLA 200A P ` I may i / U U DC, 4y MP1: 1x9 BACKUP SWITCH Y r • zv EGC / C11-71 O (E) LOADS r LI r O 0— —• • �- NJ �r� DC. I z 50 2P A -_ GND _ EGC - �, •f Dc. 0 . • 0 DC —� u _� DC- DC- y MPl: lx8 EGC ` EGC—7 �`• e B I GND I_ _ r uj (I:1 If) ^ — N_ (I)Conduit Kit; 3/4" EMT -- o EGC METER U __n_'L co- GEC -1 I z — I I 40A 2P I A I O L1 _n_• B I I L2 TO 120/24oV N 1 W— (N) WALL SINGLE PHASE L J1_1., EGC CONNECTOR CONDUCTORS RATED TO 100A OR GREATER MAY BE UTILITY SERVICE INSTALLED WITH ALUMINUM RATED EQUIVALENT WIRE SIZE AND THE RESULTING CONDUIT SIZE. REFERENCE THE 'WIRE & CONDUIT SIZE EQUIVALENCE TABLE' ATTACHED TO THE PLANSET. i CONDUCTORS RATED TO 100A OR GREATER MAY BE INSTALLED WITH ALUMINUM RATED EQUIVALENT WIRE SIZE Panel Limit feature for Powerwall unit(s) AND THE RESULTING CONDUIT SIZE. REFERENCE THE 'WIRE & to Field label de zed CONDUIT SIZE EQUIVALENCE TABLE' ATTACHED TO THE Fto be at the point of interconnection: PLANSET. "PCS Controlled Current Setting: 200A The maximum output current from this system towards the main panel is controlled electronically. Refer to manufacturer's instructions for more information." Voc* = MAX VOC AT MIN TEMP GD —Please see MO wiring detail page for more information (1)1624171-00-C (1)AWG/8, THWN-2, Block -(1)AWG 18, 1HWN-2, White A ' A —(1)Tesla 4J 4-StringCombiner Box D�'` Z Backup Switch O (1)AWG#8, THWN-2, Red H UNFUSED, GROUNDED, Black, Nag DIN Roil with Bracket/Cord Grip 1. -(1)Eaton 204 MS68 III���LLL(1)AWG#10, THWN-2, Green EGC Vmp =240 VAC Imp=32 AAC Pv (6)Tesla MO, 650V, 12A B-Line Meter Socket, 200A, AW Hub top,Overhead, 4 jaws, Ring type -(I)Conduit Kit; 3/4' EMT (1)CUTIER-HAJIMER DG100NB y Greund/Neutrol lit; 60-100A, General Duty(DG) Existing -(1)CUTLER-HAMMER /DG222URB (3)AWG�2/0, THNN-2, Black Disconnect; 60A, 240Voc, Non-Fusible, NEMA 3R X I—(1)UL 508 Emergency Stop Device- NEMA 4X IJ (1) 2 PVC; Schedule 80 I''l'(1)AWG /8, 7HWN-2,Black � (1)AWC /10, THWN-2, Black Voc* =409.69VDC Isc =11.14 ADC --� (2)PV We, AWG 10 Voc* =460.9 VDC Isc =11.14 ADC POI—(1)LEWTON /L62S0 T5OA O�iF(1)AWG /8, THYM-2,Red k" (1)AWG /10, 1HWN-2, Red Vmp =297.04VDC/ Imp=10.77 ADC O j(1)AWG p10, Solid Bare Copper EGC Vmp =334.17 VDC Imp=10.77 ADC Breaker, 50A/2P, 2 Spaces EEELLL(1)AWG #10, HWN-2,, Green EGC O (I)A'AG 10, THHN/IHNN-2, Green EGC-(I)Conduit Kit; 3/4' EMT -(1)Conduit Kit; 3/4'EMT —(1)AWG It O, THWN-2, Black Voc* =460.9 VDC Isc =11.14 ADC [�(2)PV Wire, ANC 10 Voc* =409.69VDC Isc =11.14 ADC —(1)TGENsla 31 WALL q. Q-(1)AWG 110, THWN-2, Red Vmp =334.17 VDC Imp=10.77 ADC O fs7-(1)AWG #10, Solid Bore Copper EGC Vmp =297.04 VDC Imp=10.77 ADC W I GEN 3 WALL CONNECTOR, NA, 1P, 48A, 18FT • L1 (1)AWG 110, 7HHN/THWN-2, Green EGC-(1)Conduit Kit; 3/4" FIAT CUSTOMER DESCRMIKW: ��: _ CONFIDENTIAL- THE T BE USED HEREIN JOB NUMBER: JB-9726577 00 NirajNischol T -- 5 L n CONTAINED SHALL NOT BE USED FOR THE SPEC Phase 1 Lot 68 6.8 KW PV ARRAY BENEFIT OF ANYONE EXCEPT 1ESIA INC., NOR MOUNTING SISILM: 15574 SW Peace Ave 13.5 KWH ENERGY STORAGE SYSTEM SHALL IT BE DISCLOSED IN WHOLE OR IN ZS Comp V4 w Flashing—Insert PART TO OTHERS OUTSIDE THE RECIPIENTS Tigard, OR 97224 Electric Vehicle Charging System _ ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (17) Hanwha # Q.PEAK DUO BLK ML—G10.a+/TS 400 PAGE RAVE: SHEET: REV: DATE TESLA EQUIPMENT, `MIHOUT THE WRITTEN INVERTER: PERMISSION OF TESLA INC. Powerwall+ [240V] #1850000-00—C / PVI Assy. 1538000-25—F River Terrace Crossing THREE LINE DIAGRAM 2 2/22/2023 ELECTRICAL CALCULATIONS Module: Inverter 1: 17 Hanwha/Q Cells:Hanwha Q Cells Q.PEAK DUO BLK ML G10.a+/TS 40I71.5 W 1 Testa Powerwall+(Controller) 0.98 Inv Power PTC 7600 Voltage Drop Calculations 6157.61 Vdrop= Imp) * (2*Length)*(Resistance) / rVmp) Version 5_8.0 ( Module: Hanwha/Q Cells:Hanwha Q Cells Q.PEAK DUO BLK ML-G10.a+/TS 4001.5 Imp(A) Max.Length(ft) Wire Inverter 2: String: 10.77 25 AWG#10 at Max Ave Hi:81 deg F Module: Hanwha/Q Cells:Hanwha Q Cells Q.PEAK DUO BLK ML-G10.a+/TS 4c Y1.5 Vdrop= (10.77 50 0.00124 Ohms) / 291.88 0.23 Branch: 110.77 I 50 I AWG#10 at Max Ave Hi:81 deg F Inverter 3: Module: Hanwha/Q Cells:Hanwha CellsQ.PEAK DUO BLK ML-G10.a+/TS 40D71.5 Vdrop= (10.77 100 0.drop in Ohms) / tors= D..6 Q Total voltage drop in DC conductors= 0.69 Inverter 4: Inverter: 132 I 15 I AWG#8 at 240V Vdrop= (32 30 0.00078 Ohms) / 240 V 0.11 Total: 17 Modules Total Inv Pwr: 7600 6157.61 PTC Combined: at 240V i Photovoltaic Module Electrical Specifications: Total STC: 6800 Vdrop= Ohms) / 240 V Voc: 45.3 V deg F deg C Vmp: 37.13 V Record Low Temp: -10 -23.33 Total voltage drop in AC conductors= 0.11 !so: 11.14 A Max Average Hi Temp: 81 27.22 Total voltage drop in AC and DC conductors= Imp: 10.77 A Record Hi Temp: 108 42.22 Tvoc: -0.12 V/deg C Tisc: 4.46 mA/deg C String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf TVoc Data I Branch Circuit Type A 1 way wire length: 50 Tesla Powerwall+(Controller) Voc Correction Factor: 1 strings per branch 1 1 strings per branch 2 9 Hanwha/Q Cells:Hanwha Q Cells Q.PEAK DU2e + e90U 57 91 modules per series string 8 modules per series string Voc= 407.7 n mp aMax mp: 291.88 Voc= 407.7 V Voc= 362.4 V Vmp= 334.17 Max Voc at Min Temp: 460.9 InverterVmp= 334.17 V Vmp= 297.04 V Max Vdc Input: 600 Isc= 11.14 Isc 11.14 A Isc= 11.14 A Imp= 10.77 Max String Size: 11 Imp= 10.77 A Imp= 10.77 A Icont= 13.92 Art 690.8(A)(1) 1-way wire length: 50 Icont= 13.92 A Icont= 13.92 A Art 690.8(A)(1) 1.a Conductor: AWG#10 PV Wire 2.a Conductor 1: AWG#10 Conductor 2: AWG #10 Icont*1.25=(Amps) 17.41 Conductor I Conductor2 30 deg C ampacity= 40 Icont*1.25=(Amps) 17.41 17.41 1.b Icont=(Amps) 13.92 30 deg C ampacity= 40 40 Start ampacity 40 2.b Icont=(Amps) 13.92 13.92 Temperature derate(%=F) 0.82 Start ampacity 40 40 Conduit fill derate(%_#) 1 Temperature derate(%=F) 0.82 0.82 Derated ampacity 32.8 Conduit fill derate(%_#) 0.8 0.8 1.c Derated ampacity 26.24 26.24 Icont*1.25=(Amps) 17.41 2.c Term 1 Term 2 Ampacity 40 Temp table 90°C:Tab a 310.15(8)(16) 90°C:Table 310.15(B)(16) Icont*1.25=(Amps) 17.41 17.41 1.d Icont*1.25=(Amps) 17.41 Ampacity 40 40 OCP Size= 20 Inverter Type A Output 2.d OCP Size= 20 20 Testa Powerwall+(Controller) 1 way wire length: 15 ft Combined Inverter Output Icont= 32 A Art 690.8(A)(1) Service Voltage= 3.a Icont*1.25=(Amps) 40 Art 690.8(B)(1) Total Inverter Power= 1 way wire length= 15 OCP Size= 40 Art 240.6(A) Icont=#of inverters*max inverter current Art 690.8(A)(1) 3.b Conductor: AWG#8 THWN-2 at 90 deg C:Table 310.16 Icont=(Amps) 4.a Icont*1.25=(Amps) 40 Art 690.8(B)(1) Icont*1.25=(Amps) AO OCP size= 40 Art 240.6(A) 30 deg C ampacity= 55 4.b Conductor: AWG#8 THWN-2 at 90 deg C:Table 310.16 3.c Icont=(Amps) 32 Icont*1.25=(Amps) 40 Start ampacity 55 30 deg C ampacity= 55 Temperature derate(%=F) 0.91 32 Conduit fill derate(%=#) 1 4.c kart=(Amps) Start ampacity 55 Derated ampacity 50.05 3.d Icont*1.25=(Amps) 40 Temperature derate(%=F) 0.91 Conduit fill derate(%_#) 1 Ampacity 50 Derated ampacity 50.05 4.d Icont*1.25=(Amps) 40 Ampacity 50 CUSTOMER DESatWllpi: DESIGN: CON"IANEDASHALLiNOTBEE"�U�FORRn+lE N0" JB-g726577 00 SPEC Phase 1 Lot 68 6,8 KW PV ARRAY Niraj Nischal T � 5 L inBENEFIT OF ANYONE EXCEPT TESTA INC., NOR MOUNTING SYSTEM: 15574 SW Peace Ave 13.5 KWH ENERGY STORAGE SYSTEM SHALL IT BE DISCLOSED IN PMOLE OR IN ZS Comp V4 w Flashing-Insert PART TO OTHERS OUTSIDE THE RECIPIENT'S MODULES: Tigard, OR 97224 Electric Vehicle Charging System ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (17) Hanwha # Q.PEAK DUO BLK ML-G10.o+/TS 400 PAGE NAME SHEET: REV: DATE: TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PERMISSION OF TESTA INC. Powerwall+ [240V1 #1850000-00-C / PVI Assy. 1538000-25-F River Terrace Crossing ELECTRICAL CALCULATIONS 2/22/2023 Residential Load Calc era] Lighting L tl :We E Load from table 220-19 8 berate to 80% 6400 Amount Load, VA Sq. ft. 2700 8100 .. . ., Y.:ting and Cooling Small Appliance 2 3000 Volts Amps Load, VA Laundry 1 1500 12600 Heating Unit 0 Demand Factor A/C Unit 0 1st 3000 or less at 100% 3000 Heat Pump 240 20 4800 From 3001 to 120,000 at 35% 3360 I Remainder over 120,000 at 25°/© 0 0 Largest Load 220.60 4800 0 6360 0 Largest Motor Fixed Appliances Volts Amps Load, VA Volts Amps Load, VA 25% of Largest Motor Load 120 12 360 Water Heater 240 18.75 4500 Dishwasher 120 12.5 1500 Disposal 120 9,8 1176 Additional Loads 10010 Fans 0 Volts Amps Load, VA Microwave 120 12.5 1500 Hood Fan 120 3 360 EV Charging 240 40 9600 Water Pump 0 Electric Fireplace 120 12.5 1500 Others 0 0 9036 0 --' 0 Demand Factor More than 3 Fixed Appliances, 75% 6777 More than 3 Fi) 0 Service Size. Electric Clothes Dryer Total Calculated Amps 170 Total KW: KW Load, VA Main breaker to next nominal size, X .83 for conductor size based on single family 3I _I Nameplate Rating I 5 I 5000 z, 49.1 . ` "Load - _ CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT REUSED FORE THE NUMBER: J -9726577 00 SPEC Phase 1 Lot 68 6.8 KW PV ARRAY Niraj Nischal BENEFITOF ANYONE EXCEPT TESLA INC., NOR M SYSTEM: 15574 SW Peace Ave 135 KWH ENERGY STORAGE SYSTEM SHALLLL IT BE DISCLOSED IN WHOLE OR ZS Comp V4 wFlashing—Insert . PART TO O OTHERS OUTSIDE THE RECIPIENTS ZS MGDULES Tigard, OR 97224 Electric Vehicle Charging System ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (17) Hanwha # Q.PEAK DUO BLK ML-G10.a+/TS 400 PAGE NAME SHEET: REV: DATE TESLA EQUIPMENT, W1IHOUT THE WRITTEN INVERTER: 7 2/22/2023 PERMISSION OF TESLA INC. Powerwall+ [240V1 #1850000-00-C / PVI Assy. 1538000-25-F River Terrace Crossing ELECTRICAL LOAD CALCULATIONS 0GOMPA7.4. ROOFING SYSTEM SPECIFICATIONS p®� GROUND ZEP LEVELING Fool Listed to UL 2703 Listed to UL 2703 DESCRIPTION PV mounting solution for composition shingle roofs. Part#850-1511 Part#850-1397 . 40`ti Works with all Zep Compatible Modules. r ®` `��� Auto bonding UL-listed hardware creates structural and electrical bond. Z. , I AO r SPECIFICATIONS Designed for pitched roofs. Installs in portrait and landscape orientations. DC WIRE CLIP HOME RUN CLIP Engineered for spans up to 72" and cantilevers up to 24". Listed to UL 1565 Listed to UL 1565 Part#850-1509 Part#850-1510 ZS Comp has a UL 1703 Class "A" Fire Rating when installed using modules from any -`/ manufacturer certified as"Type 1"or"Type 2". Attachment method UL listed to UL 2582 for Wind Driven Rain. 015-:›411, ZS Comp supports 50 psf(2400 Pa)front and up to 72 psf(3450 Pa) rear side design load rating for Portrait module orientation per UL 2703. _____ ZS Comp supports 50 psf(2400 Pa)front side and up to 72 psf(3450 Pa) rear side design ARRAY SKIRT END CAP /**1111 load rating for Landscape module orientation. Listed to UL 2703 Listed to UL 2703 -- - _ - Part#850-1608 Part#850-1586(Left) Engineered for compliance with ASCE 7-05, 7-10, and 7-16 wind load requirements. Part#850-1588(Right) Zep wire management products listed to UL 1565 for wire positioning devices. ZS Comp grounding products are listed to UL 2703 and UL 467. 1 A4k-':,Alo ZS Comp bonding products are listed to UL 2703. I ' MOUNTING BLOCK I I FLASHING INSERT SKIRT GRIP n INTERLOCK Listed to UL 2703 Listed to UL 2703 and UL 2582 for wind Driven Rain Listed to UL 2703 Listed to UL 2703 Part#850.1633 Part#850-1628 " Fart#850-1606 Part#850-1613 P rfi °‘ A" ;If ., °-2 11 Ai riCAPTURED WASHER LAG �� HYBRID INTERLOCK Part#850-1631-002 and#850-1631-004 Listed to UL 2703 Part#850-1281 4 ,---'40401-141 Ile T = S i,.. = ZS COMP DATASHEET 2 T c S L n Z5 COMP DATASHEET 3 TESL n ai- i 4I `I y iC(III II 21 .III III 2 e..50-. ii'1.E< (� ii=. SE\ E � AL \ OTES • DRAWING OF STANDARD MCI WIRING DETAIL FOR ANY GIVEN STRING LENGTHG E • IF INITIATED, RAPID SHUTDOWN OCCURS WITHIN 30 SECONDS OF ACTIVATION AND LIMITS VOLTAGE ON THE ROOF TO NO GREATER THAN 165V (690.12.6.2.1) • MID CIRCUIT INTERRUPTER (MCI) IS A UL 1741 PVRSE CERTIFIED RAPID SHUTDOWN DEVICE (RSD) / DC+ MCI J—BOX J—BOX J—BOX i J—BOX J—BOX J—BOX 'TJ MCI ETOFIT PV V O' ULES / DC- T - • MCIS ARE LOCATED AT ROOF LEVEL, JUST UNDER THE PV MODULES IN ACCORDANCE WITH 690.12 REQUIREMENTS 1 • THE QUANTITY OF MCIS PER STRING IS DETERMINED BY STRING LENGTH — NUMBER OF MODULES BETWEEN MCI UNITS = 0-3 — MAXIMUM NUMBER OF MODULES PER MCI UNIT = 3 J—BOX J—BOX J—BOX J—BOX — MINIMUM NUMBER MCI UNITS = MODULE COUNT/3 Mci * L / / *Exception: Tesla (Longi) modules installed in locations where the max Voc for 3 modules at low design temperature exceeds 165V shall be limited to 2 modules between MCIs. PLEASE REFER TO MCI CUTSHEET AND PVRSA INSERT FOR O [} (2)AWG, PV Wire, 600V, Black DC MORE INFORMATION BACKUP SWITCH "/„ The Tesla Backup Switch controls connection to the grid in a ;' Powerwall system, and can be easily installed behind the utility _1 meter or in a standalone meter panel downstream of the utility meter. The Backup Switch automatically detects grid outages,providing a seamless transition to backup power. It communicates directly "*"' with Powerwall, allowing home energy usage monitoring from .� any mobile device with the Tesla app. a u PERFORMANCE SPECIFICATIONS - 176mm Model Number 1624171 xx-y Continuous Load Rating 200A, 120/240V Split phase -- Short Circuit Current Rating 22 kA with breaker Communication CAN _ TOP I .;„ Product Compatibility Powerwall 2 with Backup Gateway 2, //\� I t 1- Powerwall+....... _. I,I I,I Expected Service:::aua, ze'nst to o-greater than the available fault cu--ent. �ii 205-rim l Ill COMPLIANCE INFORMATION �—„�luiumm„n! Safety Standards USA.UL 414,UL 2735,UL 916 ►r-- =1 CA Prop 66 �' arrnoerar Emissions FCC ICES tau ENVIRONMENTAL SPECIFICATIONS Operating Temperature -40°C to 50°C(-40°F to 122°F) I F Storage Temperature -40°C to 85°C(-40°F to 185°F) , Enclosure Rating NEMA 3R I Pollution Rating PD3 MECHANICAL SPECIFICATIONSmom Dimensions 176 mm x 205 mm x 74 mm III (6.9 inx 8.1inx 2.9in) IF Weight 2.8 lbs Meter and Socket Compatibility ANSI Type 2S,nngless or ring type External Service Interface Contactor manual override Reset button 74 mm Conduit Compatibility 1/2-inch NPT 'Manually overrides the co0tactor position during a service event. 'ESLA CON/EVFRSY 1 1.a POWERWALL+ r fI,I ,. ' iiiiaii-iiii PHOTOVOLTAIC (PV) AND BATTERY ENERGY MECHANICAL SPECIFICATIONS r i .,, STORAGE SYSTEM ( ES ) SPECIFICATIONS Dimensions 596 x 755 x 160 min(62.8 x 29.7 x 6.3 in) B S iii �, -vs-«+`^ -'� - Total Weight 140 kg(310 ICY � � , a _( i Powerwall+Model Number 1850000-xx-y ,¢ -.a Battery Assembly 118 kg(26l Ib) °' _ Solar Assembly Model Number 1538000-xx-y i-77 FNli i. '� rl ';- Nominal Battery Energy 13.5 kWh' Solar Assembly 22 kg(49 Ib) ,i it v ¥ ° ,' +. l' gt.;,^ "" Nominal Grid Voltage(Input/Output) 120/240 VAC Mounting options Floor or wall mount i 1 ' - °' i i g ie«„ -f Grid Voltage Range 211.2-264 VAC 755 min 160 min Ti .t1H "'-' ii.i -" # Frequency 60 Hz ' _ 240 VAC:2W+N+GND cm-Si - -., : _ Phase i l - ,A -k Maximum Continuous Power On-Grid 7.6 kVA full sun/5.8 kVA no sun' Maximum Continuous Power Off-Grid 9.6 kW tull sup/7 kW no sun' j Peak Off-Grid Power(10 s) 22 kW full sun/10 kW no sun' r ' " @ Maximum Continuous Current On-Grid 32 A output 111111111I >- Y -,�o- Maximum Continuous Current Off-Grid 40 A output I', Load Start Capability 98-118 A LRA' I T = 5 L n I 1 PV Maximum Input Voltage 600 VDC 596 min iiiiiiiii rr • _ PV DC Input Voltage Range 60-550 VDC ;. i i;^_ -�- PV DC MPPT Voltage Range 60-480 VDC (i i,'..- r .. >' .. ;, ., MPPTs 4 1 ' ii�i ( «; - is ° Input Connectors per MPPT 1-2-1-2-- ' iii.i - i' ' Maximum Current per MPPT(Imp) 13 A' li i ii)-fiMHit �--I 'i i .. i. Maximum Short Circuit 17 A' i t . _ :. Ir,_ I n Current per MPPT Ra) IIiii e Ili (i r . . E1"i 1i i;' r+--� i. i�i rya=:�t Allowable DC/AC Ratio 1.7 ____i , I 'u° iIONME �. 1, —ig GI I II Overcurrent Protection Device 50Abreaker ENVIRONMENTAL SPECIFICATIONS i + ii'-iiiiriiiiiiiii•i,All ° - Maximum Supply Fault Current 10 kA _. �.x k i'I �I r ,., ,� 6 9 Operating Temperature -20°C to 50°C(-4°F to 122 F)" I : '* •,(r '•f Output Power Factor Rating +/-0.9 to 1° 0°C i ..... , '•` - - v Round TripEfficiency 90%' Recommended Temperature CC C F _6 r - ° to 30°C 32° to 8 °F) -� + ,r, L E. ..- .7 oun Ef"c' ncy _> a ,-.: '4� mow 1 x s,is > " rF * t 91 - -- operating Humidity(RH) Up to l00%,condensing °, _a x Sig S a ° >Y,. Solar Generation CEC Efficiency 97.5%at 208 V umi . PE ilj Ail ti Vi kl,p a - r 98.0%at 240 V Storage Conditions -20°C to 30°C(-4°F to 86°F) s.>..; t� ?1 s k._ IT 'i'LI�.I"h«41,:iDii3 tItiiiii,D, d:., ''Nit -t,.Jer3n.,, t Ll::& .«..5: £ 3vio-€ ,t`E riYo-.. . --- - Uo to 95%RH,non-condensing Customer Interface Tesla Mobile App -- -- State of Energy(SoE):25%initial Internet Connectivity Wi-FI,Ethernet.Cellular LTE/4G)Y - - -- - • -- - Maximum Elevation 3000 m(9843 ft) POWERWALL+ PV AC Metering Revenue grade(+/-0.5%) Environment Indoor and outdoor rated Protections Integrated arc fault - - circuit interrupter(AFCI), Enclosure Type Type 3R Powerwall+is an integrated solar battery system that stores energy from solar production. Powerwall+ has two _ PV Rapid Shutdown Solar Assembly Ingress Rating IP55(Wiring Compartment) separate inverters, one for battery and one for solar, that are optimized to work together. Its integrated design and Warranty 10 years Battery Assembly Ingress Rating IPs6(Wiring Compartment) streamlined installation allow for simple connection to any home, and improved surge power capability brings whole IP67(Battery&Power Electronics) home backup in a smaller package. Smart system controls enable owners to customize system behavior to suit their COMPLIANCE INFORMATION Noise Level @ 1 m < 40 db(A)optimal, - a 50 db(A)maximum renewable energy needs. PV Certifications UL 1699B,UL 1741,UL 3741,UL 1741 SA,UL 'Values provided for 25°C(77°F) 3.3 kW charge/discharge power. 1/41 SB,UL 1998(US).IEEE 1547,IEEE 1547.1 'Load start capability may vary. KEY FEATURES Battery Energy Storage UL 1642,IJL 1741.UL 1741 PCS,UL 1741 SA, 'Where the DC input current exceeds an MPPT rating,jumpers can be used to System Certifications UL 1741 SB.UL 1973,UL 9540,IEEE 1547, allow a single MPPT to intake additional DC current up to 26 A i,,,,/34 A • Integrated battery, inverter, and system controller for a more compact install IEEE 1547.1,UN 38.3 "Power factor rating at max real power. 'AC to battery to AC,at beginning of life. Grid Connection United States 'Cellular connectivity subject to network service coverage and signal • A suite of application modes, including self-powered, time based control, and backup modes - Emissions FCC Part 15 Class B strength. • Wi-Fi, Ethernet, and LTE connectivity with easy over-the-air updates - - - - - 'The total weight does not include the Powerwall+bracket,which weighs an Environmental RoEIS Di'ective 2011/65/EU additional 9 kg(20 Ib). Seismic AC156,IEEE 693-2005(high) `Performance may be de-rated at operating temperatures below 10°C(50°F) o«greater than 43°C(109°F). TESLA.COM/ENERGY m. SOLAR SHUTDOWN DEVICE SYSTEM LAYOUTS • The Tesla Solar Shutdown Device is a Mid-Circuit Powerwall+with Backup Switch Installed Behind Utility Meter Interrupter(MCI)and is part of the PV system rapid _` , ... .„ % 4/f ., '�� shutdown(RSD)function in accordance with Article 690 / ff; 1 .- .N of the applicable NEC. When paired with Powerwall+, /IN solar array shutdown is initiated by pushing the System IIIN Shutdown Switch if one is present. Solar Backup Switch ELECTRICAL SPECIFICATIONS MECHANICAL SPECIFICATIONS T -- --- ---- -- Electrical Connections Meter Model Number MCI-1 _ MC4 Connector v i..;+ Nominal Input DC Current Rating(IM,) 12 A -- - - - T L.5 u Housing Maximum Input Short Circuit Current(Ix) 15 A Plastic _._. Load center Meter socket panel Grid Maximum System Voltage 600 V DC Dimensions 125 rim x 150 torn x 22 rem (5 in x 6 in x 1 In) Weight --- 350 g(0.77 IS) -�- RSD MODULE PERFORMANCE Mounting Options ZEP M4 Screw(1eRu0n Clip Powerwall+ Backup loads M8 Bolt(5/16") Maximum Number of Devices per String 5 Nail/Wood screw Control Power Line Excitation Passive State Norman open 5 Warranty0 Powerwall+with Backup Switch Installed Downstream of Utility Meter 2 Y 111 LLL Maximum Power Consumption 7 W i 25 years 0 1un • M4 Screw COMPLIANCE INFORMATION ---(:/// Solar Backup Switch Utility Meter Certifications UL 1741 PV RSE,UL 3741, 650 min 150 min ,i G M8 Bolt PVRSA(Photovoltaic Rapid Shutdown Array) - ° T _� ///''��� RSD Initiation Method External System Shutdown Switch _./ .;- Nail/ Compatible Equipment Soc Compatibdrty Table below - x Wood Screw \\ Load center Meter socket panel Meter socket panel Grid I ENVIRONMENTAL SPECIFICATIONS Ambient Temperature -40°C to 50°C(40°F to 122°F) ..,f.... 125 min _.. i Storage Temperature -30°C to 60°C(-22°F to 140°F) 22 minI Ql-pni.. Enclosure Rating NEMA 4/IP65 Powerwall+ Backup loads UL 3741 PV HAZARD CONTROL (AND PVRSA) COMPATIBILITY Tesla Solar Roof and Tetle/Zep Z5 Arrays using the following modules are certified to UL 3741 and UL 1741 PVRSA when installed with the Powerwall+ and Solar Shutdown Devices.See Powerwall+Rapid Shutdown:Module Selection Based on PV Hazard Control System Listing for guidance on installing Powerwall+and Solar Shutdown Devices with other modules. Brand Model Required Solar Shutdown Devices Testa Solar Roof V3 1 Solar Shutdown Device per 10 modules Tesla Tesla TxxxS(where xxx=405 to 450 W.increments of 5)or 1 Solar Shutdown Device per 3 modules' Tesla TxxxH(where xxx=395 to 415 W,increments of 5) Henwha Q,PEAK DUO 8LK-65 or Q PEAK DUO 8LK-G6+ 1 Solar Shutdown Device per 3 modules 'Exception:Testa solar modules nstalled in locations where the max Voc for tnree modules at low design temperatures exceeds l65 V shall he limited to two nodules between Solar Shutdown Devices. TESLA.COM/ENERGY S 5) '• TESLA.COM/ENERGY Powerwall+with Backup Gateway 2 for Whole Home Backup // Solar Y n Meter T _sss 111 Load center Backup Gateway 2 Meter socket panel Grid Powerwall+ Backup loads Powerwall+with Backup Gateway 2 for Partial Home Backup / .. Solar • r-- Meter (i) 'cSLA I 1 Backup panel Backup Gateway 2 Meter socket panel Grid == Powerwall+ Backup loads -- Non-backup panel 555 Non-essential loads TESLA.COM/ENERGY lis poweredby MECHANICAL SPECIFICATION • , Q.ANTUM (DUO Format (1.4inx41.2 inx1.57 in(ncludingframe) l ,iry- (1890 mmx1046mmx40mm) �ue°ry x.'B®mmu aae•wnmei enI - 46.3.11.1.60°.n 1 Weight 51.81bs(23.5 kg) _ 1 B�PanJ,p PYYse 0l8'19 mm1 x6).rt°tr°, t '1 i Front Cover 0.13in action)thermally pre-stressed glass whh II ' ( 1 '1 anti-reflection technology ram^^ 1II Back Cover Composite film I { I{ I 1 Frame Black anodized aluminum •traew,.m 1 If \ \ ,1 ' } �, Cell 6 x 22 mortocrys[alline Q.ANTUM solar half cells ] i ] Junction Box 2.09-3.98 in x 1.26-2.36In x 0,59-0.71in I +, 1 1 [ � ': I (53-101mmx32-80mmx 15-18mm),IP67,with bypass diodes ~� Bn PeruP Worn 6r1'•9.1'IA6mm+° ' ,:. li II ° Cable 4mm�Solar cable:(+)z4Z21n(1200mm),(-)>_4Z2in(1200mm) 4,r.r.+nw+.lF,w•1 y , 1 ? 11 4 `] li '�� ! Connector SteubliMC4;IP66 ��r ie-100.ei or9Ke n��,� , 1 1 : 1 _ k �'t _ � Iw' 0 S 9sr l°°rm uarin°.n 1 ELECTRICAL CHARACTERISTICS Q.PEAK DUO BLK ML-G10.a+/TS , Coat oiled PV POWER CLASS 385 390 385 400 405 MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS,STC'(POWER TOLERANCES W I-OW) 385-4�5 Power at MPP' P.,re [W] 385 390 395 400 405 ] TUVRhalnland ,.- 11.04 11.07 11.10 11.14 11.17 CEannED •tuv°an Short Circuit Currents I� [A] Iq nnxszats ENDURING HIGH EE Open Circuit Voltage' V� [V] 45.19 45.23 45.27 45.30 45.34 PERFORMANCE r,01IPATjQ euro$aeEARcn YR Q F Current sit MPP a [A] 10.59 10.65 10.71 10.77 10.83 y4 ( ' Voltage at MPP VraW [V] 36.36 36.62 36.88 37.13 37.39 / �t 7saP.Ra• ARR.tTr , % z19.5 z197 z200 z20.2 z20.5 i ,r�u, s Efticfency, n 11 • ` s, wwre ® MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS.NMOT W �FA `�V 021 Warranty QCELLS Power at MPP PMW [WI 288.8 292.6 296.3 300.1 303.8 COPIP0 aoa larola„ate ldesec°nry E Shut CrrcuitCurrent 1sc [A] 8.90 8.92 8.95 8.97 9.00 e Open Circuit Voltage Vip [V] 42.62 42.65 42.69 42.72 42.76 'c Currant etMPY Ium IAl 8.35 8.41 8.46 8.51 8.57 BREAKING THE 2Te EFFICIENCY BARRIERQ.ANT V , [VI 34ss 34.81 35.03 35.25 as.a6 (\i? Voltage at MPF M° boosts o DUO Z Technology with zero gap cell layout `Measurement tolerances Pa°a t3%;196 VBB t5%at S7C:1000 W/m2,25t2°G AM 1.5 according to IEC 60904-3•'800 W/m°,NMOT,spectrum AM 1.5 boosts module efficiency Up t020.7%. 0 CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE THE MOST THOROUGH TESTING PROGRAMME IN THE INDUSTRY _n W5 At least s8%ot nominal power du ring >a° 7 Eleig .ON b...e n Q CELLS is the first solar module manufacturer to pass the most comprehen- v ' first year Thereafter max.0.5% z I 3 . degradation per year.At least 93.5% a i,-re° I- �I slue quality programme in the industry:The new"Quality Controlled PV"of g of nominal power up to 10 years.At " i the independent certification institute T UV Rheinland. z least es%of nominal power to I -J 5' .°: 25 years. '°-- -- - i, az 1 S INNOVATIVE ALL-WEATHER TECHNOLOGY E + All data within measurement toleranc- 1 the warranty warranties in accordance with p 1 1 N Optimal yields,whatever the weather with excellent < the warranty terms of the 0 CELLS IRkAcln;rca w;,.3 e;,. sales organisation of your respective e low-light and temperature behavior. a . IS r< country. 'Z'a e m rugs Typical module performance under low irradiance conditions in r°'.°e �v*m,r I•`'�"'^`•1re comparison to SIC conditions(25'C.1000W(m°) 12 ENDURING HIGH PERFORMANCE V Long-term yield security with Anti LID Technology,Anti PID TEMPERATURE COEFFICIENTs o ` Technology',Hot-Spot Protect and Traceable Quality Tra.QTM. Temperature CoaffSdant at l n 6 [%/Kj o.04 Temperature Coefficient of V 9 l%/K] 0.27 Y Temperature Coefficient of PMm y 1%/K] -0.34 Nominal Module Operating Temperature NMOT [°F] 109±5.4(43t3°C) m 0 ZEP COMPAT1BLETM FRAME DESIGN o ] High-tech black Zep Compatible°frame,for improved aesthetics, PROPERTIES FOR SYSTEM DESIGN ia easy installation and increased safety. Maximum System Voltage V, [V] 1000(IEC)/1000(UL) PV module classification Class II o Maximum Series Fuse Raking IA DC] 20 Fite Rating based on ANSI t UL 61730 TYPE 2 e gj' A RELIABLE INVESTMENT Max.Design Load,Push/Pull' bs/it'] 85(4080 Pa)/ Permitted Module Temperature -40°Fupto+185°F 9 P -40°C up to+BS°C '.+""' Inclusive 25-yearproduct warrantyand 25-year on Continuous Duty (-40°C ) \qMax.Test Load,Push/Pull (Ibs/ftj 128(6120 Pa)/128(6120Pa) lr� linear performance warranty'. 'See Installation Manual f 'APT test conditions according to IEC/TS 62804-1:2015,method A(-1500V,96h) QUALIFICATIONS AND CERTIFICATES i °See data sheet on rear for further information. s UI.61T30,OE-complaint, 8 Quality Controlled PV- tpr+e\+r, TUV Rheinland,IEC61215:2016, J�'������/\ S ® (/ [./. a° IEC 61]302016. ^J�./�" C `1,U°, ` ` i THE IDEAL SOLUTION FOR: U.S.Patent 302o1.9.90a,u6 T.ro\M/ t' (solar OBITS) Rooftop arrays on Rooftop arrays on residential buildings commercial/Industrial Ai buildings Note:Installation instructions must be followed.See the installation and operating manual or contact our technical service department for lurlher information on approved installation and use of this product. CELLS 4004a0 Spectrum Crum Center AmericaDrive.Inc. Hen hea ELLS rDrive,Suite 1400,Irvine,CA 9261$USA ITEL+1 949 74 6 59 96 1EMAII Inquiry@us.q-cells.comI WEB www.q-ceils.us GI Engineered in Germany Wire & Conduit Size Equivalence Table: Copper & Aluminum Copper Aluminum Rating (A) Conductor Min. EGC Conductor Conduit Conduit AWG or kcmil (AWG or kcmil) (AWG) ( ) 100 3 8 1" - EMT 1 1-1/4" - EMT 115 2 6 1-1/4" - EMT 1/0 2" - PVC 130 1 6 1-1/4" - EMT 2/0 211 - PVC 150 1/0 6 2" - PVC 3/0 2" - PVC 175 2/0 6 2" - PVC 4/0 2" - PVC 200 3/0 6 2" - PVC 250 2" - PVC NEC Code references NEC Table 310.15(8)(16) (formerly Table 310.16) NEC Table 250.122 Table 310.104(A) CONFIDENTIAL - THE INFCRMATION HEREIN T JG s CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT TESLA INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE PERMISSION EQUIPMENT,TESLT THE WRITTEN WIRE & CONDUIT SIZE EQUIVALENCE TABLE PERMISSION OF TESLA INCINC. • PV HAZARD CONTROL SYSTEM I ZS PVHCS PV HAZARD CONTROL SYSTEM PVHCS I CERTIFICATION UL 3741 REPORT DATE 10-20-21 (APPLICABLE TO ZS COMP, ZS SPAN, ZS RAMP, AND ZS SEAM) UL 3741 REPORT DATE 8-12-21 PV RAPID SHUTDOWN ARRAY, UL 1741 CATEGORY QIJR PV RAPID SHUTDOWN ARRAY, UL 1741 CATEGORY QIJR, REPORT DATE: 2021-06-11 (REV 8-10-21) WARNING:To reduce the risk of injury,read all instructions. WARNING:To reduce the risk of injury, read all instructions. PV HAZARD CONTROL EQUIPMENT AND COMPONENTS PV HAZARD CONTROL EQUIPMENT AND COMPONENTS Firmware Versions Certification Standard Firmware Versions Certification Standard Function Manufacturer Model No. and Checksums Function Manufacturer Model No. and Checksums PVRSE Mid Circuit Tesla MCI-1 N/A UL 1741 PVRSE PVRSE Mid Circuit Tesla MCI-1 N/A UL 1741 PVRSE Interrupter(MCI) Interrupter(MCI) 1550379' 7.6 kW: 1538000' V4,CEA4F802 UL 1741, 1998 7.6 kW:1538000' V4,CEA4F802 Inverter or Powerwall+ Tesla 3.8 kW: 1534000' V4,FF7BE4E1 UL 1741,1998 PVRSS/PVRSE Inverter or Powerwall+ Tesla 3.8 kW: 1534000' V4,FF7BE4E1 pVRSS/PVRSE 7.6 kW: 1850000' V4,CEA4F802 7.6 kW: 1850000' V4,CEA4F802 Q.PEAK DUO BLK-G5/SC310-320 PV Module Tesla SR60T1,SR72T1 N/A UL 61730 Hanwha/Q-CELLS Q.PEAK DUO BLK G6+/SC330-345 UL 1703 SR72T2 PV Module N/A Diode Harness Tesla Tesla TxxxS No(=405 to 450) UL 61730 Tesla SRDTH N/A UL 9703 Tesla TxxxH(xxx=395 to 415) (Not applicable to SR72T2) PV Wire Jumper(s) Tesla SR-BJ2X,SR-BJ3X, N/A UL 9703 PVHCS Initiator Dedicated PV system AC circuit breaker or AC disconnect switch,labeled per NEC 690.12 N/A SR-BJ4X,SR-BJMini (PV Inverter) requirements. Pass-Through Box Tesla SRPTB-4 N/A UL PVHCS Initiator Emergency stop device(NISD)-Listed"Emergency Stop Button"or"Emergency Stop UL 508 or UL 60947 Parts PVHCS Initiator: Dedicated PV system AC circuit breaker or AC disconnect switch,labeled per NEC N/A (Powerwall+) Device"or"Emergency Stop Unit". 1,5-1 and 5-5 (PV Inverter) 690.12 requirements. PVHCS Initiator- Emergency stop device(NISD)-Listed"Emergency Stop Button"or"Emergency Stop UL 508 or UL 60947 'Applies to variations of this part number with suffix of two numbers and one letter. (Powerwall+) Device"or"Emergency Stop Unit" Parts 1,5-1 and 5-5 Note:PVHCS installation requirements may reduce the effective equipment and component ratings below the individual equipment and component 'Applies to variations of this part number with suffix of two numbers and one letter. PVRSE ratings in order to achieve PVHCS shock hazard reduction requirements. Note:PVHCS installation requirements may reduce the effective equipment and component ratings below the individual equipment and component PVHCS INSTALLATION REQUIREMENTS PVRSE ratings in order to achieve PVHCS shock hazard reduction requirements. Max System Voltage 600 VDC PVHCS INSTALLATION REQUIREMENTS PVHCS Maximum Circuit Voltage(Array Internal Voltage After Actuation) 165 VDC(cold weather open circuit) Max System Voltage 600 Voc Max Series-Connected Modules Between MCIs: PVHCS Maximum Circuit Voltage(Array Internal Voltage AfterActuation) 165 VDc(cold weather open circuit) *Exception:Tesla S-Series(TxxxS)modules installed in locations where the max VOC for 3 3* modules at low design temperature exceeds 165V shall be limited to 2 modules between MCIs. Max Series-Connected Panels between MCIs 10 OTHER INSTALLATION INSTRUCTIONS OTHER INSTALLATION INSTRUCTIONS 1.An MCI must be connected to one end of each series string or mounting plane sub-array string. 1.An MCI must be connected to one end of each series string or mounting plane sub-array string. 2.Verification that MCIs are installed with 3 or fewer modules between MCIs shall be documented for inspection,by voltage 2.Verification that MCIs are installed with 10 or fewer modules between MCIs shall be documented for inspection, by voltage measurement logs and/or as-built string layout diagrams. measurement logs and/or as-built string layout diagrams. 3. For PV Inverter:The PVHCS initiator(AC breaker or switch)shall be sized and installed in accordance with NEC requirements. 3. For PV Inverter:The PVHCS initiator(AC breaker or switch)shall be sized and installed in accordance with NEC requirements. The specific part shall be identified on the as-built system drawings. The specific part shall be identified on the as-built system drawings. 4.For Powerwall+:The PVHCS emergency stop initiator shall have the following minimum ratings:Outdoor(Type 3R or higher), 12V, 4. For Powerwall+:The PVHCS emergency stop initiator shall have the following minimum ratings:Outdoor(Type 3R or higher), 12V, 1A, and shall be installed in accordance with NEC requirements.The specific part shall be identified on the as-built system drawings. 1A,and shall be installed in accordance with NEC requirements.The specific part shall be identified on the as-built system drawings. Refer to the Powerwall+installation manual for further details. Refer to the Powerwall+installation manual for further details. CERTIFIED0 Certification Mark of UL on the installation instructions is the only method provided by UL to identify products manufactured under its CERTIFIED Certification Mark of UL on the installation instructions is the only method provided by UL to identify products manufactured under its snrciv us Certification and Follow-UpService.The Certification Mark for these products includes the UL symbol,the words"CERTIFIED"and Certification and Follow-Up Service.The Certification Mark for these products includes the UL symbol,the words"CERTIFIED"and L515336 E515336 "SAFETY,"the geographic identifier(s),and a file number. "SAFETY,"the geographic identifier(s),and a file number. T 5 S L n TEZS-DS-0020-21 1 T S 5 L n TESR-DS-038E-21 1 or PRODUCT OVERVIEW This manual applies to Wall Connectors identified by part number 1457768-"-4. Product Specifications Voltage and Wiring Nominal 200-240 V AC single-phase Current Output Range 12 - 48 amps Terminal Blocks 12-4 AWG (3.5 - 25 mm2), copper only Supported Conduit Sizing '/d' (21 mm) default, 1" (27 mm) optional Grounding Scheme TN/TT Frequency 50/60 Hz Cable Length 8.5' (2.6 m) or 18' (5.5 m) Wall Connector Dimensions Height:13.6" (345 mm) Width: 6.1" (155 mm) Depth: 4.3" (110 mm) Wire Box Bracket Dimensions Height: 9.8" (250 mm) Width: 4.7"(120 mm) Depth: 2.0" (50 mm) Weight (including wirebox) 10 lb. (4.5 kg) Operating Temperature -22°F to 122°F (-30°C to 50°C) Storage Temperature -40°F to 185°F (-40°C to 85°C) Enclosure Rating Type 3R Ventilation Not required Means of Disconnect External branch circuit breaker Ground Fault Circuit Interrupter Integrated, no additional required (CCID20) Wi-Fi 2,4 GHz, 802.11b/g/n Agency Approvals cULus - E351001 Transportation and storage: Ensure that Wall Connector is within storage temperature when moving, transporting, or storing. This device complies with part 15 of the FCC Rules. Operation is subject to the following conditions: (1) This device may not cause harmful interference, and (2)this device must accept any interference received, including interference that may cause undesired operation. 4 Gen 3 Wall Connector Manual CERTIFICATE OF COMPLIANCE SIDE LABEL OF TESLA WALL CONNECTOR: Certificate Number 20191118-E351001 Report Reference E351 001-201 91 11 8 Issue Date 2019-NOVEMBER-18 smm vim R P Issued to: TESLA MOTORS, INC. 3500 DEER CREEK RD TPN:1asz'se_ctti-rrsrUaagssa3rc�oan� :.it PUT zna:4OVYasAi c) .PALO ALTO CA 94304-1317 IourPu�. Zooaov�aea 'tarti .r ::::,"..:1-:',..,,:s1,_..,:,,:-.....i...i'n...,,.:,i.E,„ ,..- TeslawallConnector_143C86 r v This certificate confirms that ELECTRIC VEHICLE SUPPLY EQUIPMENTCRGLt�1THcLECTRtCVENICLES YfE3RENCt.1SUR . - representative samples of Electric Vehicle Charging Station, Series Wall Connector Non RI`ouTc:,e usi.vENTIIttTl4r tvUTRrQuI ' I U ri ' 9NGTEMiS: ! a Gen III Part Number 1457768-XY-Z, where "X","Y","Z" may 3aG T©5aC be any alphanumeric character reserved for manufacturer's CAI UT commercial purposes not related to safety. Do not usa Illspraduc It these is any damage tome EV domTecto(or,czte. xzt°° Risk of electric shock.Do not remove cover or attempt toropen encl°ure. No user servlceabk parts Inside. Reter servicing to qualified service personrtel. rt t Have been investigated by UL in accordance with the ATTENTION. �a I 'x Standard(s) indicated on this Certificate. P - f} q Ne pas utiliser ce prod3it sl fa carsil esr ehdamma e Risque de codC erectodue.Ne pas retire(le eouver le n essayer d'aavrir le bonier. Aucune Alece interne reparable pa futilisateur.Gunner tout travaildentretren Standard(s)for safety: U L 2594 : Standard for Electric Vehicle (EV) Supply ou de reparation a un tecnnicien qualifie :i Equipment WARNING: CSA C22.2 No. 280-16 : Standard for Electric Vehicle (EV) Risk o1 explosion.This equipment has arcing or sparking parts that should not be exposed to flammable vapors.This equipment Additional Information: See the UL Online Certifications Directory at Supply Equipment should be located at least460mm(18 inches)above the flow This device is intended only for charging vehicles not requiring ventilation during charging.Automatic reset feature is provided https:l/iq.ulprospector.com for additional information. AVERTISSEMENT: Risque d'explosion.L'appareil comporte des pieces pouvant produire des arcs electriques ou des elincelles qui ne devraient pas etre This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up • exposees auxvapeurs inflammables.Cet apparel'devrait etre mstalle a au moms 460 mm(18 ponces)au-dessus du plancher Tr :.� Services Procedure provides authorization to apply the UL Mark. Ce disposed est destine au chargement des vehicules ne necessitant pas de ventilation au caurs du chargement. '' Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL's Caracteristique de rearmement automatique incluse. Follow-Up Services. rcc.Ttzcuxo.2M11+.1 wa,n,e f Ic yup zemr lz3oay Look for the UL Certification Mark on the product. Jr R0PAzne,7 COM,"tC2.RI 110II„lav ; frit Ccei I dl P2hoTe.CCAin0IYNRiIT:. c Yi. us uP This is to certify that representative samples of the product as specified on this certificate were tested LISTED • according to the current UL requirements. Ic35,001 rF MANUFACTURED BY TESLA MOTORS INC. t Bruce Mahrenhols,DireQer Perth American Certification Program UILI.0 (PI This certificate confirm s ELECTRIC VEHICLE SUPPLY EQUIPMENT representative samples of Electric Vehicle Charging Station, Series Wall Connector Any Information and documerrtaaon Iriee141 UL Mtric saNces are pro:ded on benauot UL LLC(UL) any authorized licensee of UL.Per questions,please celbctalecal ULCu,mm.rgereieetepree.�aa�eatg�/lul,dem�aaelle�,aee� Gen III Part Number 1457768-XY-Z, here "X","Y","Z" may Page 1 of 1 be any alphanumeric character reserved for manufacturer's commercial purposes not related to safety. ___,". T INSTALLATION INSTALLATION Step 1: Prepare Wirebox for Conduit Fittings and Bushings Step 2: Prepare Mounting Surface The default conduit size is 3/4 in (21 mm). 1 in(27 ram)conduit is acceptable if needed 1. If applicable,use a stud firmer to locate a wooden support stud. plywood, or other flat wall surfaces capable of supporting the weight of the Wall Connector, may also be used. Based on fittings and conduit size, prepare the wirebox. • For top or bottom entry: Manually remove the conduit plug. • For rear entry: Drill with 1- 8 in(29 mm)step bit to prepare wirebox for fittings. Table 1.For 3/4 in(21 rani) Conduit 2. Eased on the chosen wire entry path. position the included cardboard grunting template onto the Top Er`r Bottom Entry Pear Leff. Er try Rear Bight Entry installation surface and use a 5/32 in (4 mm) bit to drill two pilot holes(one from the top row and one from the bottom row). m ,, NOTE:When installing for rear left or rear right wire entry select the two mounting holes that are on ': l . the opposite side of the wire entry point. NOTE Use a level tool with the cardboard mounting template to ensure a level installation as desired. g ' '', i.. 4dlii'a-sk.`ae.�A Cr � A f lit 1-V8 in(23 mm) 1 1/8 in (29 ram) Drill bib 5/32 in(4 ram) Table 2. For I in(27 rrrm) Conduit Top Entry Bottom Entry Rear Left Entry Rear Right Entry Top Entry Bottom Entry Rear Left Entry Rear Fight Entry _i_ ,, I 4 ) " 4- ) 0 p': i x1 x1 ili 4. ,P . ate Ifilth Do not expand. l .: , .l .�, t I ,,� ,�.` 1 + .l ' l _ 1 1 -I' i. I 13/llin (35mm) 1 y ; 4 1t 1-3/8 in (35 mm) 1-3/8 in(35 m ) I I I d . a NOTE For 1 in(27 mm)rear and bottom entry options,drill with 1-3/8 in(35 mm) step bit to prepare wirebox for fittings. II 1G 'C-sas 3'Wall CooronQoctor 1olzrooubl Gron 3 Wail CCiiiiiiiCiOr Manual 17 IN TALLATION INSTALLATION Step 3: Prepare Wirebox and Mount to Wall Step 4: Route Wiring Through Wirebox 1_ Use a 1/4 in(65 mm) bit to drill two pilot holes into the wirebox that snatch the locations chosen on 1. Route wiring into selected entry point and through the service loop channel on the right side of the the cardboard mounting template. wirebox. Top Entry aattorn Entry Rear Left Entry Rear Right Entry Drill bib1/4 in (6.5 mm) Top Entry Bottibm Erkry Bottom Left Entry E ttorn Right Entry xi xi . . 2. Use appropriate cable glands,bushings, or fittings to secure the wiring in place and protect from water and debris intrusion. Xi X7 r• CAUTION: Ensure that bushings are in place to avoid damage to conductors and ground wire 11111 when pulled into wirebox_ CAUTION:Use copper conductors only. NOTE:Compression-style fittings are recommended to prevent interference. 2. Attach the wirebox to the mounting location using the included 4 mm hex bit and the two included NOTE:For top or bottom wire entry. if installing fittings with a set screw,ensure that the screw is wood fastener screws. positioned to avoid interference with Wall Connector cables. " ..<_: _ NOTE:Type 3FR rating is only possible when washers have sealing gaskets..If mounting to alternate suuri a (such as a prefabricated pedestal), use alternate fasteners with sealing washers. NOTE:The wood fastener screws are designed to support the weight of the entire Wall Connecter, cable,..and charging handle. Gan 3.Flail Concvactor Manual 19 ll Gun 3 Wail Connector.Manual INSTALLATION IN T L I_ TI Yq {.y` ; Step 5: Strip and Land Wiring Step £ Attach Wall Connector to Wirebox 1. Strip insulation from wires-1/2 in(-13 mm), route through service channel, and land each wire in its 1. Attach the main unit to the wirebox by p ushi it inward.. correct terminal block. NOTE:Terminals are bi-directional. 4 d e • < r l r'.. I 1 a rt i II ,,. i i 1 i2. Secure the main unit to the wirebox with the four included fasteners and the included 4 mm hex bit using a bit driver;applying pressure to the faceplate during the process to compress the internal seat 2. Secure the wiring in the service channel using the included zip tie. Firmly hand-tighten the four fasteners until they are secure, NOTE:Do not use a power drill for this step. 3.. Use a torque driver and the included 4 mm hex bit to torque the terminal screws to SO lbf. in(5.6 Nrri). i Step 7. Energize Wall Connector 1. Energize the Wall Connector by turrkr g on the upstream circuit breaker. NOTE When installing Wall Connector in a split phase electrical system, use Lire-to-Lire instead of 1 A' Line-to-Neutral r ;d i,i,, ;''`. 1 ; , - w I. F ,,,, The Wall Connector's LEDs will turn on. See Wall Connector LEDs on page 26. 2_ Proceed with commission" 20 Gan 3.Wail CC411418CIOr Yl artllai Gan 3 Wall ar Manual 21