Plans (4)
GENERAL NOTES AERIAL VIEW R ED CODE AND STANDARDS = 41 1 ALL WORK SHALL COMPLY WITH 2017 OREGON ELECTRIC SPECIALTY CODE(OESC),2019 OREGON . " $ U BRAVE STRUCTURAL SPECIALTY CODE,2017 OREGON RESIDENTIAL SPECIALTY CODE,AND ALL STATE AND LOCAL ' , `BUILDING AND ELECTRICAL CODES - _ _2.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS G,, '-"'� ` it.' .. 14. 5-'41114� • ' SITE NOTES/OSHA REGULATION )" �yy �� Y t�i";l r.'b N - .,r ; #lam 1.A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. {,�, „ s 800.377 4480 2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM. (b ,F'+'� ..-/I.,..' W W W.BLUERAVENSOLAR.GOM 3.THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING ROOF VENTS. j '- �" INFORMATION CONFIDENTIAL-THE 4.ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND " ' cr ' HEREIN CONTAINED SHALL NOT BE so....t. 0 �'• nr x THE APPROVED MANUFACTURERS INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT '. 1 3'a-x,-.`" atUSED FOR THE BENEFIT OF ANYONE THE BUILDING OR STRUCTURE. OFFICE COPY - 4"T EXCEPT BLUE RAVEN SOLAR NOR SHAL L ir LL IT BE DISCLOSED IN WHOLE OR SOLAR CONTRACTOR ', a, IN PART TO OTHERS OUTSIDE 1.MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEG61646,IEC61730. '' RECIPIENTS ORGANIZATION,EXCEPT 111 2.IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PER .a IN CONNECTION WITH THE SALE AND 1 ;, THE MANUFACTURERS INSTALLATION REQUIREMENTS. c,t' USE OF THE RESPECTIVE EQUIPMENT, - PERMISSION 3.AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF �°0 '- WITHOUT THE WRITTEN ;' OF BLUE RAVEN SOLAR STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ . ; ,via "" LLC. 4.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO '" LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS iii Ili VIP ///p o/�� 5.CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A r /, 1 V A BC E r SUITABLE SEALING COMPOUND. ' 6.DC WIRING LIMITED TO MODULE FOOTPRINT W/ENPHASE AC SYSTEM. :wx£" CERTIFIED 7.ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/SUITABLE WIRING CLIPS. i ..—_.- 8.MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT L. PV INSTALLATION AVAILABLE :.. - , PROFESSIONAL 9.ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS,AC 0 at PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT COMBINERS,AND ^� , i c460 SW Aiderbr `' Scott Gurney CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND OP 97224 #PV-01 1 71 9-01 5866 LISTED FOR THE APPLICATION PER NEC 690.4(B). _ - Cir, Tigard, . • c 10.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. .� F T"= >n 3. CONTRACTOR: 11.TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS(WHEN PROVIDED) ` BRS FIELD OPS R. IN ACCORDANCE WITH NEC CODE 110.14(D)ON ALL ELECTRICAL CONNECTIONS. ` £ _ 800-377-4480 EQUIPMENT LOCATIONS p - 4,4 1.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT �"' P +, ,: WILL BE PROVIDED AS PER SECTION NEC 110.26. < ., 2.EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31(A)AND NEC TABLE 310.15(B). - �� '" '' 0 3.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC (/) `. < (� APPLICABLE CODES. c1r "'' Z 0 4.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. ` '`-L '"' ape 1 0 nt $k N .*R `j TM„ _ - 1 <. ,' ., T P 1--).. PROJECT INFORMATION: CITY OF TIGARD • .." 3 U REVIEWED FOR ODE COMPLIANCE ' Y N 0 NUMBER OF STORIES: 1 ° - r ID 03 N N CONDUIT RUN: Interior Approved: [ '` -- U_ ECOBEE QTY: 1I U 4 Z c a5 c N fn OTC: ., ' x2 -° w 22 LIGHT BULB QTY: 18 ".�:, _t .�"..�'°,� . '" " PV METER: Not Required Permit#: S'`)�23' DESIGN CRITERIA SITE SPECIFICATIONS SHEET INDEX w 2 N m H H ROOF TYPE (1) INFORMATION:'dress'• '1 it) J .IEM 0 N fn WIND SPEED: 100 mph CONSTRUCTION -V-B PV1 -COVER SHEET Approved plans -a y >- ROOF TYPE: Comp SFfingl9e #: ZI GROUND SNOW LOAD: 40 Ib/ft2 ZONING: RESIDENTIAL PV2 - SITE PLAN shall be on job site. mi (,� v FRAMING TYPE: Manafaatured Truss Date: 66//1 3 WIND EXPOSURE FACTOR: C PV3 - ROOF PLAN Ln — SHEATHING TYPE: PL1K/VOOD CI SEISMIC DESIGN CATEGORY: D PV4 -STRUCTURAL U r H Q ATTACHMENT: SFM Infinity Flashkit PV5 - ELECTRICAL 3-LINE DIAGRAM RACKING: Unirac SFM Infinity @ 48"OC Portrait/48"OC Landscape PV6 ELECTRICAL CALCULATIONS DRAWING BY: NUMBER OF ATTACHMENTS: 50 SCOPE OF WORK PV7 -WARNING LABELS AND LOCATIONS PremiumCAD ROOF TYPE (2) INFORMATION (IF APPLICABLE): INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM AND ANY (ALL OTHER SHEETS AS REQUIRED) PLOT DATE: *SEE PV4.2 NECESSARY ADDITIONAL WORK NEEDED FOR INSTALLATION. SS PRODUCT SPEC. SHEETS '�/ February 7, 2023 r IDI1 I OF PERMIT PROJECT NUMBER. SYSTEM TO BE INSTALLED INFORMATION: UTILITY COMPANY: THE ISSUANCE OF A PERMIT LIABILITY 702016 9 DC SYSTEM SIZE: 8.4 kW DC BASED ON CONSTRUCTION The City of Tigard and its Portland General Electric (PGE) SHEET NAME:AC SYSTEM SIZE: 6.09 kW AC DOCUMENTS AND OTHER employees shall not be MODULE TYPE: (21) QCells Q.PEAK DUO BLK ML-G10+400 DATA SHALL NOT PREVENT responsible for discrepancies PERMIT ISSUER: COVER SHEET INVERTER TYPE: Enphase IQ8PLUS-72-2-US THE CODE OFFICIAL FROM w3 tch may appear herein REVISION: PAGE NUMBER: MONITORING: Enphase IQ Combiner 4 X-IQ-AM1-240-4 REQUIRING THE CORRECT' City of Tigard OF ERRORS. ORSC 105.4 0 PV1 IIIINIpew. PV SYSTEM SPECIFICATIONS LEGEND TOTAL NUMBER OF MODULES: 21 le JUNCTION BOX MODULE MAKE AND MODEL: QCells Q.PEAK DUO BLK ML-G10+400 B LU E RAVE N MODULE WATTAGE: 400W DC (MD UTILITY METER INVERTER MAKE AND MODEL: Enphase IQ8PLUS-72-2-US 1403 N. Research Way ' INVERTER TYPE: Microinverter (1 Inverter per PV Module) MSP MAIN SERVICE PANEL Orem, UT 84097 INVERTER CURRENT OUTPUT: 1.21A AC B00.377.4480 INVERTER NOMINAL VOLTAGE: 240V if AC DISCONNECT WWW,BLUERAVENSOLAR.COM INVERTER WATTAGE: 290W AC CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR �I SHALL IT BE DISCLOSED IN WHOLE OR I LOAD CENTER IN PART TO OTHERS OUTSIDE LC RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, ISI SUB SUBPANEL WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. / \_ } PV METER NABCEP ►. 0. 0 0 0 0 j TS TRANSFER SWITCH CERTIFIED 0 0 o 0 0 / PV INSTALLATION ESS SUNPOWER ESS PROFESSIONAL ,`, n' re �r re I' / Scott Gurney HUB SUNPOWER HUB+ MPV-011719-015866 / CONTRACTOR: Lu / RPO REMOTE POWER OFF BRS FIELD OPS U 800 377-4480 oC / U re .,, ' / Y FIRE SETBACK LL1O i m I LC 1 / TRENCHING C.) O W I----I / `-- 1 Z Q p z o IMSPI no. 4 % - 1 PROPERTY LINE 0 (1) 0Q --J / I H i2 cocc u_ / SCALE: 1/8" = 1'-0" U o Y CO CO /% CC OL N 0 r in Piz!, . _o LL NN/ ZC N c In fn W O C N W W 0 0' % 03 / ~ s 2 fn fn / U2Lrlz QC DRAWING BY: CB M� �\ PremiumCAD PLOT DATE: L - - - - - ___ ___ _1February7, 2023 PIER! '3' 1O1 Y JJW PROJECT NUMBER: i1 s_.rt9.,..$$A■i10 ^v ekuaa at>r 702016 • SHEET NAME: 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER 2. 11 q OttlA aToBtouooa ROOF ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24 IN. 3:"ic(T` tt !S"< de AT�CI SITE PLAN OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OF A ROOF REVISION: PAGE NUMBER: EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3) N ,t r 1147:',3 '3li Q w:, yr,a y0 0 PV2 LEGEND " . PV SYSTEM SPECIFICATIONS TOTAL NUMBER OF MODULES: 21 101 JUNCTION BOX MODULE MAKE AND MODEL: QCells Q.PEAK DUO BLK ML-G10+400 E RAVEN MODULE WATTAGE: 400W DC �MJ UTILITY METER . INVERTER MAKE AND MODEL: Enphase IQ8PLUS-72-2-US 1403 N. Research Way INVERTER TYPE: Microinverter(1 Inverter per PV Module) MSP MAIN SERVICE PANEL Orem, UT 84097 INVERTER CURRENT OUTPUT: 1.21A AC 800.377.4480 INVERTER NOMINAL VOLTAGE: 240V AC AC DISCONNECT WWW.BLUERAVENSOLAR.COM INVERTER WATTAGE: 290W AC MP1 CONFIDENTIAL-THE INFORMATION T BE #OF MODULES: 21 USED OROTHEABENDEFITOF ANYONE AZIMUTH:AZIMUTH: 270 CB COMBINER BOX EXCEPT BLUE RAVEN SOLAR NOR PITCH: 18 SHAIN PART TO OTLL IT BE OHERS OUTSIDE SED IN E OR TSRF: 86% A LC LOAD CENTER RECIPIENTS ORGANIZATION,EXCEPT IN AREA: 804 ft.2 USE HOF THTE HROES FN ICTIVNE PEQU PMENTH THE SALE DT, --{//f1' SUB SUBPANEL WITOFUBLUERAVENSOLARMICSION / /St , Iry r.. r.. �.. r4. / �� PV METER 4(1. BCE 0 0 0 0 0 0 / TS TRANSFER SWITCH CERTIFIED / PV INSTALLATION ESS SUNPOWER ESS PROFESSIONAL r' !<' r.' !' !' !' % Scott Gurney o n n n n 0 HUB SUNPOWER HUB+ #PV-011719-015866 \ / / CONTRACTOR: HEREIN / RPO REMOTE POWER OFF BRS FIELD OPS � � �, �, � 800-377-4480 O 0 0 0 % N FIRE SETBACK O 1LCI Z F__-I I TRENCHING O O IMSPI ►' ►. / Q U -- I 0 0 / 1 PROPERTY LINE 0 N f / I H E rn j SCALE: 1/8" = 1' 0" 2 o N ari oci / cy, N N F. c a1 c N (7) ►. // W o Q Ec H H n2 = NO tncn . CB AC M� DRAWING BY. PremiumCAD POINT OF INTERCONNECTION - - UNDERGROUND SERVICE LINE PLOT DATE: February 7, 2023 PROJECT NUMBER. 702016 SHEET NAME: 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER 2. ROOF ROOF PLAN ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OF A ROOF EDGE, HIP, EAVE, REVISION: PAGE NUMBER: OR RIDGE (OSISC 305.4.3) . 0 PV3 STRUCTURAL INFORMATION: STRUCTURAL NOTES: PV MODULE UNIRAC SFM 2" MICRORAIL /-UNIRAC SFM 6.5" SPLICE NINILe..- ROOF TYPE(1): ROOF TYPE: Comp Shingle 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER I � f I 4 ,11 i p RAVEN SHEATHING TYPE: PLYWOOD 2. ROOF ATTACHMENTS SHALL BE SPACED NO GREATER BLUE R H Y E FRAMING FRAMING SIZE:2 Manufactured" Truss ) r'rI THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN It 3 FT. OF A ROOF EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3) JOIST SIZE: 2x4 CO 24"OC 1403 N. Research Way None — MAX 48" MAX. - — — LANDSCAPE Orem, UT 84097 ATTACHMENT: SFM Infinity Flashkit 800.377.4480 RACKING: Unirac SFM Infinity wWW.BLUERAVENSOLAR.COM @ 48" OC Portrait/48'OC Landscape PV MODULE UNIRAC SFM 2" MICRORAIL UNIRAC SFM 6.5" CONFIDENTIAL-THE INFORMATION SPLICE HEREIN CONTAINED SHALL NOT BE NUMBER OF ATTACHMENTS: 50 USED FORC THE ONTAINEDRA EFITOFANYONE y?� EXCEPT BLUE RAVEN SOLAR NOR PV MODULE COUNT: 21 Modules i . ' , i II . I SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE TOTAL ARRAY AREA: 428.4 ft2(20.4ft2/panel) RECIPIENTS ORGANIZATION,EXCEPT TOTAL ROOF AREA: 2267 ft2 IN CONNECTION WITH THE SALE AND �( USE OF THE RESPECTIVE EQUIPMENT, ARRAY/ROOF AREA: 18.9°/c Ll WITHOUT THE WRITTEN PERMISSION ARRAY WEIGHT: 1,050 lbs (50 lbs/panel) 23, OF BLUE RAVEN SOLAR LLC. p ) MAX. F 48" MAX. PORTRAIT DISTRIBUTED LOAD: 2.45 lbs/ft2 / I�p/ POINT LOAD: 21 lbs/attachment 'NOTE:LISTED NUMBER OF ATTACHMENT POINTS ARE AN ESTIMATE ONLY AND MAY VARY O ATTACHMENT SPACING- FRONT VIEW -RACKING ATTACHMENTS TO BE STAGGERED ABCEP BASED ON FIELD CONDITIONS.MAXIMUM ATTACHMENT SPACING TO BE FOLLOWED PER t ENGINEER OF RECORD SPECIFICATIONS. SCALE: 3/4" = 1'-0" CERTIFIED UNIRAC SFM INFINITY UNIRAC SFM MICRORAIU SPLICE O PV INSTALLATION PV MODULE PROFESSIONAL �- Scott Gurney QCELLS Q.PEAK DUO BLK ML-G10+400IIIII aPv-ou7lurney s PV MODULE PORTRAIT �I'�1 CONTRACTOR: air UNIRAC SFM SLIDER BRS HELD OPS ROOF STRUCTURE 800 377-4480 FM (E) ROOF MODULE iii � SHEATHING WIDTH O FLASHING Q U (1) 5/16" STAINLESS STEEL LAG BOLT Fir /�z/� 0 LANDSCAPE WITH 2-1/2" MIN. EMBEDMENT I _0 v 5 AND FLAT WASHERj2Y2. MINjEMBED1- _ " . 1 / 18" rn -�• MODULE U .--- WIDTH 2 ,e N cD co A MIDDLE/TOP STANDOFF DETAIL I ATTACHMENT SPACING- SIDE VIEW Z N °' N N SCALE: 3" = 1'-0" (E) BUILDING STRUCTURE ` U CC ,1 = 0 2 2 �J SCALE: 1/2" = 1'-0" W 2 a ' W H QCELLS Q.PEAK DUO BLK ML-G10+ 400a.62 _ c) Q N N PV MODULEillal6 a- N N I 0) 0 0 M V � � H Q a UNIRAC SFM TRIMRAIL FLASHING DRAWING BY. UNIRAC SFM SLIDER AND PremiumCAD TRIMRAIL ROOF ATTACHMENT 11111111151, (E) ROOFPLOTDATESHEATHING February 7, 2023 (1) 5/16" STAINLESS STEEL LAG BOLT A_ "//�// PROJECT NUMBER: WITH 2-1/2" MIN. EMBEDMENT s 702016 AND FLAT WASHER s 2/V MIN. EMBED. eSHEET NAME: STRUCTURAL BOTTOM STANDOFF DETAIL STRUCTURE REVISION: PAGE NUMBER. (E) BUILDING 0 PV4 SCALE: 3" = 1'-0" (1) 8 AWG THHN/ITIWN-2,CU.,SLACK(LTI 25.4 AAC 121 10 AWG THHN/THWN-2,CU.,MAC((L1) MAX 13.3 A AC (II 10 AWG THHN/THWN-2,CU.,BLACK I MAX 13.3 A AC 411 12.2 TC-E12,1104N/THWN-2,CU. MAX 13.3 A AC 15 (1) $AWG THHN/'THWN-z CO.,RED(L2) 240 V AC 3 (2) 10 AWG THHN/TNWN-2,CU.,RED(1.2} 240 V AC ry (1) 10 AWG THHN/TH NN-2.CU..RED(1.2) NO V M 1 41) 6 AWG RARE CU(EGC) 240 VAC Cl) 6 AW6 THHN/THWN-2,CU.,WHITE(N) Ill 10 AWG THHN/THWNs2,CU.,GREEN(EGC) L 111 10 AWG T1•HN/110NMI-2,CU.,GREEN(EGC) NIIINIILL16°' (1) 10 AWG THHN/THWN-2.CU,.GREEN(EGC) OR 10-2)$-S W/G(OR NM-8),THHN/THWN-2.,SOUD CU (1) 3/4 INCH EMT EXTERIOR (1) 3/4 INCH ENT EXTERIOR (11 3/41NCH EMT(Not Required for UF-Oa NM-8 Cable) INTERIOR EXTERIOR y ') AV E N (1) 6 AWG THHN/THWN-2,CU..BRACX(L 1 S 1) 261 A AC 11 1) B-3 NM- W/G,THSOWN/THWN-2,SO CU. BLUE 16 (1) 6 AWG THHN/TKWN-2.CU.,RED(LT) 240 V AC 17 (1) 6 AWG THHN/?HWN-2.CU.,WHITE(N) 1403 N. Research Way (1) 8 AWGTHHN/THW -2,C11-.GREET((EGC)N (1) 3/4 INCH ETAT EXTERIOR` Orem, UT84097 ---- - - 800.377.4480 W W W.BLUERAVENSOLAR.COM DESIGNER NOTES: ELECTRICAL NOTES: CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE SUPPLY SIDE TAP>10'AWAY&INDOOR,POI INTERIOR ALL CONDUIT TO BE RAN AT LEAST 7/BIN.ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. USED FOR THE BENEFIT OF ANYONE AC DISCONNECT TO BE LOCATED WITHIN 10 FEET OF THE UTILITY METER. EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE (21)QCeIIs Q.PEAK DUO BLK ML-G10+400 RECIPIENTS ORGANIZATION,EXCEPT (N)60A LOAD CENTER ENPHASE IQ COMBINER 4 UL 1703 COMPLIANT IN CONNECTION WITH THE SALE AND (E)125A MAIN SERVICE PANEL OCPD AND DISCONNECTING X-10-AM1-240-4 (21)Enphase IQ8PLUS-72-2-US USE OF THE RESPECTIVE EQUIPMENT, (E)100A/2P MAIN BREAKER MEANS FOR CONDUCTOR TAP (SOLAR LOAD ONLY) WITHOUT THE WRITTEN PERMISSION 4'x4'x4'PVC JB-1 EZ SOLAR UL 1741 COMPLIANT OF BLUE RAVEN SOLAR LLC. PV AC DISCONNECT JUNCTION BOX JUNCTION BOX NON-FUSED (N)20A/2P JB L, JB-1 L, Ll • (N)35A/2P LOCKABLE, L, _^ .r,,(1) OF 60A,240V,2-POLE N/ B CEP • EGG } C _ _1 11 MODULES �-. N r (E)100A/2P — ENVOYI 15A/2P CERTIFIED (E)LOADS -"` LN 2 1 PV INSTALLATION li r — n o N n I — (N)o20A/2P A JB-1 L ^ _ _ PROFESSIONAL (''�_ _ (1) CIRCUIT OF Nel I z -� N EGC ECC EGC l_ L \—� 10 MODULES Scott Gume r -- _-- G EGC r F EGC -- _ r -} BPV-01 171 9-01 5866 G I Y 120/240 VAC N s n --_J (�� CONTRACTOR: 3 lJ 60HZ 6BRS FIELD OPS 1 PHASE 800-377-4480 TO UTILITY GRID G --- I . „ r ,.,.- Ll 40 (E)GROUNDING '�� �' - ELECTRODE(S) r r, O - )e a ..r:,-. V O N W W �. c N c W Q cr W W R � 2 3 L HH li co co }- ". i 1 II In r).i((1 • m al 't Co U V .s O�IOC Sr;av svr , 1.- E11TS %, - �". n Ptitr(w tiMNl4 ENeta'�s y DRAWING BY: �� )r1'r! n PremiumCAD :x.n k(`Oh , II � 1tT6%q�g T�1 p� z PLOT DATE: February 7, 2023 PROJECT NUMBER: Nolitithi lop 702016 SHEET NAME: INTERCONNECTION NOTES 705.11 AN ELECTRIC POWER PRODUCTION SOURCE,WHERE ELECTRICAL CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING F " MEANS AS PERMITTED IN 230.82(6), SHALL COMPLY WITH 705.11 (A) �" . ' REVISION. PAGE NUMBER: THROUGH (E). UTILITY COMPANY: Portland General Electric (PGE) PERMIT ISSUER: City of Tigard 0 PV5 MODULE SPECIFICATIONS QCeIIsQPEAK DUO BUT ML-G10+400 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(SIC) 400 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC MODULE VOC 45,3 V DC I STATE Oregon JUNCTION BOX(1) MAX.CURRENT(ISC X1_25)= 16.6 AAC MODULE VMP 37.13 V DC I CITY Tigard CONDUCTOR(TC-ER,COPPER(90°C))= 12 AWG BLUE RAVEN MODULE IMP 10.77 A DC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING= 30 A 1I MODULE ISC 11.14 A DC ASHRAE EXTREME LOW TEMP('C) -6 ANS.TEMP.AMP.CORRECTION= 0.91 VOC CORRECTION -0.27%PC ASHRAE 2%AVG.HIGH TEMP('C) 361 ADJUSTED AMP.= 27.3 > 16,6 1403 N. Research Way - VMP CORRECTION -0.34%/'C JUNCTION BOX TO MAX.SHORT CIRCuITCURRRENT(ISC)= 13.3 AAC Orem, UT 84097 800.377.4480 SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS OR 1 OR 2 OR 3 OR 4 OR 5 OR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X125)= 16.6 A AC WWW.BLUERAVENSO LAR.COM ADJ.MODULE VOC fa ASHRAE LOW TEMP 49.1 V DC NUMBER OF MODULES PER MPPT 11 10 CONDUCTOR(Uf•e,COPPER(60'C))= 1D AWG CONFIDENTIAL-THE INFORMATION ADJ,MODULE VMP JI ASHRAE 2%AVG.HIGH TEMP 3L7 V DC DC POWER RATING PER CIRCUIT(STC) 4400 4000 CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE TOTAL MODULE NUMBER 21 CONDUIT FILL DEBATE= 1 EXCEPT BLUE RAVEN SOLAR NOR MICROINVERTER SPECIFICATIONS En phase 1Q84 Mtcrotnverters STC RATING OF ARRAY 8400 AMB.TEMP-AMP-CORRECTION= 0.91 SHALL IT BE DISCLOSED IN WHOLE OR , IN PART O OTHERS OUTSIDE POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP) 13.3 12.1 ADJUSTED AMP.= 27.3 > 16.6 RECIPIENTS ORGANIZATION,EXCEPT MAXI MOO INPUT VOLTAGE 60 V DC MAX.CURRENT IMP X L25 16.6375 15.125 JUNCTION BOX TO MAX,SHORT CIRCUIT CURRRENT(ISC)- 13.3 A AC IS CONNECTION RESPECTIVE ECTI THE SUIPMEN { ) { �- USE OF THE RESPECTIVE EQUIPMENT, MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC XL25)= 16.6 A AC WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB,ARRAY AC CURRENT(IMP) 25.4 CONDUCTOR(UF-B,COPPER(60`C))= 10 AWG MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 6090W AC CONDUCTOR RATING= 30 A AC OVERCURRENT PROTECTION 20 A CONDUITFILLDERATE- 0.8 /(ABCEEI MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. /RISE(V)VEND(V) %VRISE AMB,TEMP.AMP.CORRECTION= 0.91 CERTIFIED CEC WEIGHTED EFFICIENCY 97% VRISE SEC. 1(MICROTOJBOX) 39.6 12Cu. L76 241.76 0,73% ADJUSTED AMP.= 21.84 > 16.6 VRISE SEC.2(JBOX TO COMBINER BOX) 15 10 Cu. 0.51 240.51 0.21% COMBINER BOX TO INVERTER RATED AMPS= 25.4 A AC PV INSTALLATION AC PHOTOVOLTTIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 25 8 Cu, L00 24L00 0.42% MAIN PV OCPD 1 LS) MAX.CURRENT(RATEDAMPS XL25)= 31.76 A AC PROFESSIONAL NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 3,27 243.27 1,36% CONDUCTOR(THWN-2,COPPER(75'C TERM))= 8 AWG Scott Gurney APV-011719.015866 NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 50 A MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR: MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT-CURRENT 25.4 A AC AMB-TEMP.AMP.CORRECTION= 0.91 BRS FIELD OPS MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP-= 45-5 > 3L8 800 377 4480 0 GROUNDING NOTES WIRING &CONDUIT NOTES Z Q 0 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE O PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. [~ 2 - USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). a V USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE >[ 'CT' CO CO 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED CC 0 N THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SMALLER THAN tt6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF 0 O CV MI LU PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-8)]. Um N- N N SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)). 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z COi u) N 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. - C 4) C COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND cc Y _D 0 2 2 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS Cl)V,( Q N W W PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.46]. REQUIRED. 0 i I-5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE 6.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O I1J) O U) N MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8'ABOVE )- -C O 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DEBATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE Cl) ,C CO CO tit* Cl) MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(B)(3)(C)). _ c� 0) 0 0 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL L OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC RATED FOR 8 0V, UV DUCTORS SHALL BE USE-2,RATED SPIRALRAP SHADE RATED,WET AND UV RESISTANT,AND UL GROUNDING EQUIPMENT WITH TERMINATION GROUNDINGTOG USEDPROTECT WIRE FROM SHARP 0 '- I- a 0 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, DRAWING BY: 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. PremiumCAD MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE: 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) February 7, 2023 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) , 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED:PHASE A OR L1-BLACK,PHASE 8 OR L2-RED, PROJECT NUMBER. ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY 702016 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. 18.IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME: FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING ELEC CALCS MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.15]. 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18'BELOW ROOF SURFACE COMPLYING WITH[NEC 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER: 0 PV6 STANDARD LABELS ADDITIONAL LABELS INIter BLUE RAVEN " '" LABELI'Al A - _ FOR PV SYSTEM DISCONNECTING MEANS WHERE THE I WARNING . .T.- `Tiw-. LINE AND LOAD TERMINALS MAY BE ENERGIZED IN THE cw *- ..�. ...A.2-..rsEt LABEL 3 _ ELECTRIC SHOCK HAZARD OPEN POSITION. DUAL POWER SUPPLY IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL 1403 N. Research Way ANYWHERE THAT IS POWERED BY BOTH THE UTILITY (2010 NEC 690.13(B)) AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL SOrem, UT 840 7 TERMINALS THE LINE AND (2020 NEC 690.13(B)) SOURCES:UTILITY GRID AND AND SUBPANELS.[NEC 705.12(B)(3)] 800.377.4480 LOAD SIDESDES MAY BE ENERGIZED PV SOLAR ELECTRIC SYSTEM WWW.BLUERAVENSOLAR.COM IN THE OPEN POSITION CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE LABEL 2 EXCEPT BLUE RAVEN SOLAR NOR PHOTOVOLTAIC SYSTEM SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT SHALL IT BE DISCLOSED IN WHOLE OR THE DISCONNECTING MEANS AS A POWER SOURCE IN PART TO OTHERS OUTSIDE A AC DISCONNECT A AND WITH THE RATED AC OUTPUT CURRENT AND THE RECIPIENTS ORGANIZATION,EXCEPT NOMINAL OPERATING AC VOLTAGE. IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, RATED AC OUTPUT CURRENT 25.41 A [2017 NEC WITHOUT THE WRITTEN PERMISSION [2020 NEC 680.54] OF BLUE RAVEN SOLAR LLC. NOMINAL OPERATING AC VOLTAGE 240 V LABEL3 /BCEP AIF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL CERTIFIED ANYWHERE THAT IS POWERED BY BOTH THE UTILITY DUAL POWER SUPPLY AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL PV INSTALLATION AND SUBPANELS. - LABEL 10 SOURCES:UTILITY GRID AND [2010 NEC 705.12(B)(3)J PERMANENT PLAQUE OR DIRECTORY TO BE PROFESSIONAL (2020 NEC 705.12(B)(3)J A LOCATED AT MAIN SERVICE EQUIPMENT DENOTING Scott Gurney PV SOLAR ELECTRIC SYSTEM #Pvon71 s-015866 POWER TO THIS BUILDING IS ALSO SUPPLIED THE LOCATION OF THE RAPID SHUTDOWN SYSTEM FROM A ROOF MOUNTED SOLAR ARRAY.SOLAR DISCONNECTING MEANS IF SOLAR ARRAY RAPID SHUTDOWN DISCONNECTING SWITCH IS NOT CONTRACTOR: LABEL 4 ARRAY RAPID SHUTDOWN DISCONNECT IS GROUPED AND WITHIN LINE OF SITE OF MAIN BRS FIELD OPS AAPPLY TO THE DISTRIBUTION EQUIPMENT ADJACENT LOCATED OUTSIDE NEXT TO THE UTILITY METER. SERVICE DISCONNECTING MEANS.[2017 NEC 705.10 AND 690.56(C)(1)(a)] 800-377-4480 TO THE BACK-FED BREAKER FROM THE POWER [2020 NEC 705.10 AND 690.56(C)] POWER SOURCE OUTPUT CONNECTION SOURCE. DO NOT RELOCATE [2017 NEC 705.12(B)(2)(3)(b)J (2020 NEC 705.12(B)(3)(2)] THIS OVERCURRENT LABEL 11 DEVICE I R PERMANENT PLAQUE OR DIRECTORY TO BE < V .r. .gin' LOCATED AT AC COMBINER PANEL. PHOTOVOLTAIC SYSTEM [2017 NEC 110.21(B)J Z � ❑ COMBINER PANEL [2020 NEC i1D.21(H)] 0 U Y ?� DO NOT ADD LOADS a U o Tr N 07 CO CC °o CV W W 0 IL L 0) N N -CISUBPANEL Z U N UTILITY MAIN (IF INTERCONNECTION AC PV PV COMBINER c c METER SERVICE PANEL IS MADE HERE) DISCONNECT METER BOX W G) O Q a W W O O 0 0 O O 0 = y0 tncn oL o ° � } SOLAR PV SYSTEM EQUIPPED LABEL 6 Cl) W �n BUILDINGS WITH PVL LOCATED AT SHALL HAVE A O O O O O WITH RAPID SHUTDOWN PERMANENT LABEL LOCATED AT EACH SERVICE 2 3 2 3 7 = Cc l() O) V V EQUIPMENT LOCATION TO WHICH THE PV SYSTEMS 0 C .- H 4 0 TURN RAPID SHUTDOWN ARE CONNECTED OR AT AN APPROVED READILY SWITCH TO THE IF BREAKER 'OFF'POSITION TO VISIBLE LOCATION AND SHALL INDICATE THE LOCATION 4 4 1 1 DRAWING BY: SHUT DOWN PV SYSTEM �°""�� OF RAPID SHUTDOWN INITIATION DEVICES. O IS USED 0 AND REDUCE [2017 NEC 690.56(C)(1)(a)J 0 _ SHOCK HAZARD IMIll (2020 NEC 690.56(C)] IN THE ARRAY io _ Premium CAD LABEL 7 O OR PLACARD PLOT DATE: 3 RAPID SHUTDOWN SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT February 7, 2023 SWITCH FOR SWITCH 4 (2017 NEC 690.56(C)(3)] PROJECT NUMBER: SOLAR PV SYSTEM [2020 NEC 690.56(C)(2)] 702016 LABELING NOTES SHEET NAME: 1)LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO DETERMINE EXACT LABELS REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL 2)LABELING REQUIREMENTS BASED ON THE 2017&2020 NEC CODE,OSHA STANDARD 19010.145,ANSIZ535. REPRESENTATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED REVISION: PAGE NUMBER: 3)LABELS BASED BE THE REQUIREMENTSDIREMENTY OFO WI AHJ. MAY VARY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON 3 LINE 4)LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND SHALL NOT BE HANDWRITTEN[NEC 110.21] DIAGRAM. 3 LINE DIAGRAM ON PV5 TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. 0 PV7 N'INifro- BLUE RAVEN wit - - powered cy 1403 N.Research Way MECHANICAL SPECIFICATION Orem,UT 84097 Q°ANTVM /Dunn Format 74.0inx41.1inx1.26in(including frame) (1879m-1.1045mm.32mm) 70Ysomwx u°a..c,..b I�^•^^+ •I 800.377.4480 • .... - Weight 48.5Ibs(22.0kg) - . �•,- I WWW.BLUERAVENSOLAR,COM Front Cover 0.13in(3.2mm)thermally pre-stressed glass with 1+I ..ua°.., d 1 l anti-reflection technology CONFIDENTIAL THE INFORMATION Beck Cover Composite film • SIB.z',wen..) HEREIN CONTAINED SHALL NOT BE y Frame Black anodized aluminum I USED FOR THE BENEFIT OF ANYONE Cell 6 x 22 monocrystelllne OANTUM solar half cells ® •..co.r.., EXCEPT BLUE RAVEN SOLAR NOR Junction Sox 209-3.98in x1.26-2.36in e 0.59-0.71in SHALL IT BE DISCLOSED IN WHOLE OR • (53-101mm a 32-60mm x 15-18mm),IP67,with bypass diodes `•u- 440.7.w5...1 IN PART TO OTHERS OUTSIDE Cable 4mmz Solar rabic,(+)>49.2in(1250mm),(-)a 49.2in(1750mm) -'-t3 e.o.m.... RECIPIENTS ORGANIZATION,EXCEPT Connector Steami MCa;IP68 •i"°"'' °`°"r'°`n +I ,_ IN CONNECTION WITH THE SALE AND 'I I I-'''nzi,,,,' cr.,.ex a...f USE OF THE RESPECTIVE EQUIPMENT, ,„.,m,rmm)IO ioa.o,,,.,n WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. OuaRly ELECTRICAL CHARACTERISTICS Q. PEAK DUO BLK ML-GiO+ l��/:i%������ Controlled IN N ABCEP POWER CLASS SSS SRO 9flS 400 405 385-405 TOVRheln4rd MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS,SIC'(POWER TOLERANCE a5 W/-OW) CERTIFIED w-.turmm Power at MOP' Paw (WI 385 390 395 400 405 CERTIFIED ENDURING HIGH ID 1111232616 E Short Circuit Current' Is, [A] 11.04 11.07 11.10 1114 11.17 PERFORMANCE YR "-"3 E Open Circuit Voltage' Voc [VI 4519 45.23 45.27 45.30 45.34 PV INSTALLATION i.-j 1 Wee RESEARcn' Q Current at MPP le„ [AI 10.59 10.65 10.71 10.77 10.83 A PROFESSIONAL 25 ' Voltage at MPP Vuw [VI 36.36 e19.b 36.88 3713 3239 moutfs Efficiency. 8 [`%J e19.6 >_19.9 e20.1 �>20.4 e20.8 Scott Gurney �ll� _ - - #PV-011719-015866 "f AT"' 2pmarr MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS,NMOTr 111(USA 2021 Warranty Q CELLS Power et MPP Puw [MI 288.8 292.6 296.3 300.1 -- 303.8 Prw'..,s,,,emmve Yielh Sncu.ity E Short Circuit Current sc [Al 8.90 fisz B.95 CONTRACTOR: aw 9.00 E Open Circuit Voltage V., [V) 42.62 42.85 42.69 42.72 42.76 BRS FIELD OPS BREAKING THE 20%EFFICIENCY BARRIER S Current at MPP I,.,,p [A) 8.35 8.41 8.46 8.51 8.57 385-498-6700 n'if l O ANTUM DUO Z Technology with zero gap cell layout Voltage at MPP [V) 34.59 34.81 35.03 35 75 35.46 boosts module efficiency up to 20.9%. 'Meesuremenl tolerances Purr4.3%;1,6Va c5%at STC:1000 W/mW,25:2•C,AM 1.5 according to IEC 60904-3.r800 W/m'.NMOT,spectrum AM 1.5 0 CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE THE MOST THOROUGH TESTING PROGRAMME IN THE INDUSTRY -K °°'• AHessl98%oi nominal power during Ka° T O CELLS is the first solar module manufacturer to pass the most comprehen- &L le ye ar ar Thereafter m .a s% d9 sive quality programme in the industry:The new'Quality Controlled PV'of tt • degradation per year.ANeast a35% 9P •r ofnominal power up to l0 years.At /� the independent certification institute TUV Rheinland. zg least 86%of nominal power up to '" /' z. 6i 25 years. a e--- ----'' 3 .r. INNOVATIVE ALL-WEATHER TECHNOLOGY I'- ... ... ........ All data within measurementmlerenc- E Optimal yields,whatever the weather with excellent L es.Fullwermmies in accomencewith '0 ace w wee 11111 �' ° the werr on terms either GULLS we vaeaeups Iwr.1 low-light and temperature behavior. E sales organisation of your respective o •° ° u a s coumry m....., u,°up P•°s.,ma YEARS TYpicelmontnSTdule rtormencrsI25°C,e under 100 W/m'ce toMaions In $ ENDURING HIGH PERFORMANCE °" m"° comparison to aTC conditions(zs°C l00ow/m0 m O' Long-term yield security with Anti LID Technology,Anti PID TEMPERATURE COEFFICIENTS 0 Technology',Hot-Spot Protect and Traceable Quality Tra.Q"'. Temperature coef8rient of l,r o [%/K] +0.04 Tempereture Coefficient of V,rc [%/K] -027 y ' Temperature Coefllciemofpum y [%/KJ -0.34 Nominal Module Operating Temperature NMOT 1°F) 109x54)43x3°C) EXTREME WEATHER RATING o High-tech aluminum alloy frame,certified for PROPERTIES FOR SYSTEM DESIGN � high snow(5400 Pa)and wind loads(4000 Pa). Maximum System Voltage V,,, [VJ 1000(IEC)/1000(ULJ PV module cleonificafion Class II p 0' c�FF�� A REL ABLE INVESTMENT Maximum Series Fuse Rating [A DC) 20 Fire Rating based on ANSI/UL 01730 TYPE 2 1 CS€'1 Max.Design Load,Push/Pule pbs/rh 75(3600 Pa)/55(2660Pa) Permitted Module Temperature -40•P upto+185°F u awy/f Inclusive 25-year product warranty and 25-year on continuous Duty (-a0°c uv to+85•c) R F( near performance Warrantyz. Max.Test Load,Push/Pulp bsn 1315400 Pe)/84(4000 Pe) ,See Installation Manual s a euseAe ueuseAa 'APT test conditions according mlEc/Ts e2604-1_2ms.memos A(-ls0ov.son) QUALIFICATIONS AND CERTIFICATES PACKAGING INFORMATION G� I CELL TECHNOLOGY CELL TECHNOLOGY See date sheet on rear for further information. 52 A. & ulmrw.casorrp-T O'' r0 CD r„t pg A. • n DRAWING BY: ou°n11 ccordee Pli C-T3V201.5,en4 • w• tiVF"// tit/ LJ ro-ol I I THE IDEAL SOLUTION FOR: dcmtensmalEca15[mi..,c (! ue.Palem Nu.e.eae.215lwu.cessy .art..+ packaging 76.4in 43.3in 48.0 in 1856 bs 24 24 32 C„„...US \\\ -_ packaging 1940mm 1100 arm 1220mm 751kg pallets pellets modules .y vy Rooftopar'ays Sror °`•71° •maw S residential buildings PLOT DATE: Mete:Installation instructions most be followed See the installation end operating manual or contact our technical service department for further information on approved installation and use of this product. CELLS 400 Spe Gum Cent-Drive, Suit. PROJECT NUMBER: Engineered In Germany 400 Spectrum Center erica Suite 1400,Irvine.CA 92618,USA TEL*1 949 748 59 96I EMAIL inquiry®us q cells com WEB www.q-celle.us SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: SS Noir SLUE RAVEN ENPHASE 0ArA SHEET I08 and IQ8+ Microinverters 1403 N.Research Way Orem,UT 84097 INPDt DATA lecl Ire-60-2-US TQ8PLUS-72-2-AS 800.377.4480 Commonly used module pairings' w 235-350 235-440 WWW.BLUERAVENSOLAR.COM . * )01 Module compatibility 60-cell/120 half-cell 60-cell/120 half-cell,66-ce1l/132 half-cell and 72-ce11/144 CONFIDENTIAL-THE INFORMATION 4 as half-cell HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE MPPT voltage range v 27-37 29-45 EXCEPT BLUE RAVEN SOLAR NOR Operating range V 25-48 25-58 SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE Min/max start voltage V 30/48 30/58 RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION Max input DC voltage V 50 60 USE OF THE RES ECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Max DC current'[module Isc] A 15 OF BLUE RAVEN SOLAR LLC. Overvoltage class DC port II DC port backfeed current mA 0 IKN i* PV array configuration lx1 Ungrounded array;No additional DC side protection required;AC side protection requires max 2OA per branch circuit BCE P III I 11. - CERTIFIED [Dr FBI GAIA 1111. L)$-bD-L-DJ Peak output power VA 245 300 PV INSTALLATION Max continuous output power VA 240 290 PROFESSIONAL Nominal(L-L)voltage/range' v 240/211-264 Scott Gurney • Max continuous output current A 1.0 t21 #PV-011719-015866 IQ8 and IQ8+ Microinverters Nominal frequency Hz 60 CONTRACTOR: Easy to install Extended frequency range Hz 50-68 BRS FIELD OPS Our newest 108 Microinverters are the industry's first microgrid-forming,software- • Lightweight and compact with AC short circuit fault current over 2 385-498-6700 defined microinverters with split-phase power conversion capability to convert DC plug-n-play connectors 3 cycles Arms power to AC power efficiently.The brain of the semiconductor-based microinverter Power Line Communication Max units per 20 A(L-L)branch circuit' 16 13 •is our proprietary application-specific integrated circuit(ASIC)which enables the (PLC)between components Total harmonic distortion <5% microinverter to operate in grid-tied or off-grid modes.This chip is built in advanced 55nm technology with high speed digital logic and has super-fast response times • Faster installation with simple Overvoltage class AC port III to changing loads and grid events,alleviating constraints on battery sizing for home two-wire cabling AC port backfeed current mA 30 energy systems. Power factor setting 1.0 High productivity and reliability Grid-tied power factor(adjustable) 0.85 leading-0.85 lagging ,1 - Produce power even when the Peak efficiency % 97.5 97.6 Enphase grid is down* CECwelghted efficiency % 97 97 • More than one million cumulative Night-time power consumption mW 60 hours of testing year limited MECHANICAL DATA arranty • Class II double-insulated -, Ambient temperature range -40°C to.6O°C(-40°F to+140°F) enclosure Part of the Enphase Energy System,IQ8 Series 1O8 Series Microinverters redefine reliability Relative humidity range 4%to 100%(condensing) Microinverters integrate with the Enphase IQ Battery, standards with more than one million cumulative • Optimized for the latest high- Enphase IQ Gateway,and the Enphase App monitoring hours of power-on testing,enabling an industry- powered PV modules DC Connector type MC4 and analysis software. leading limited warranty of up to 25 years. Dimensions(HxWxD) 212 mm(8.3")x175 mm(6.91 x 30.2 mm(1.2") Microgrid-forming weight 1.08 kg(2.38 Ibs) 11/1 U • Complies with the latest Cooling Natural convection-no fans advanced grid Support" Approved for wet locations Yes E 1 i I I t t_) • Remote automatic updates for Pollution degree PD3 DRAWING BY: the latest grid requirements Enclosure Class II double-Insulated,corrosion resistant polymeric enclosure Connect PV modules quickly and easily to 108 Series 108 Series Microinverters are UL Listed as • Configurable to support a wide Microinverters using the included O-DCC-2 adapter PV Rapid Shut Down Equipment and conform with g pp Environ.category/UV exposure rating NEMA Type 6/outdoor cable with plug-n-play MC4 connectors. various regulations.when installed according to range of grid profiles PLOT DATE: COMPLIANCE manufacturer's instructions. • Meets CA Rule 21(UL 1741-SA) CA Rule 21(UL 1741-SA),UL 62109-1,UL1741/IEEE1547,FCC Pert 15 Class 8,ICES-0003 Class B,CAN/CSA-C222 NO.1O7.1-01 requirements Certifications This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014,NEC 2017,and NEC 2020 section 690.12 and C22.1-2018 Rule 84-218 Rapid Shutdown of PV Systems,for AC and DC conductors,when installed according to PROJECT NUMBER: C 2O22 Enphase Energy.All rights reserved.Enphase,the Enphase logo,1O8 Microinverters,and other •Only when installed with IQ System Controller 2, manufacturer's instructions. names are trademarks of Enphase Energy,Inc.Data subject to change. meets UL 1741. (1)No enforced DC/AC ratio.See the compatibility calculator at httpsf/link.enphase.corn/module-compatibility ••108 and 108PIus supports split phase,240V (2)Maximum continuous input DC current is 10.6A(3)Nominal voltage range can be extended beyond nominal if required 1O8SP-DS-0002-01-EN-US-2022-03-17 installations only. by the utility.(4)Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. 1085P-DS-0002-01-EN-US-2022-03-17 SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: SS 11141%.e.- Enphase IQ Combiner 4/4C BLUE RAVE N , . MODEL NUMBER Enphase Networkln[g oo trnrGlner 4.MiLIQ A141,210a1 tO Cmrbielee 4 rpThE+tplwua R7Dateteare omen ca•:un cola Int iningrown interim lit win Pv Meorr'LbnnwnnhigAeMt 1403 N.Research Way _ 112,20 vri OS%)arid Ga4Euipton ter"'2.5'k}Makatea a: eta'r alweletOresenn Ow tp&atnry p}9taTa ark IO Orem,UT 84097 ay84etn Coninakr 2.arela beat:. R/Cnmarner 4C*nthEtrphase IQ Gateway vented Oc.xuw,i bG Mr sictuaral Mu'menus grade i'Y peed n ucurel wtenne IP4S1 8E0.3 C12 20 or-0:S h naW and canptt+4rr trtarvin+iny s* t ! .Ski 1Metdc ode s Emirate Mobile Cremort coautter morainal i;CELtM40D EM1. W1NW.BLUERAVENSOLAR.COM 0 ENS _ .. _.__. .. _..... _ ._. M104 Sb'o5),a phg am play tndorsinal-grape car madam tnr systems nolo SO nurt•e;atu r!ani (,Avertable In Ito NS..Canada. CONFIDENTIAL-THE INFORMATION Witco,Pueno Roo and the LIS Vagin MAIM*,whew mare is ada4 ateceRIar set incite in the lnsuitiatiion area.l Inctutirns a HEREIN CONTAINED SHALL NOT BE Enphase The Enphase IQ Combiner 4/4C with i,Irtx suit,trued tpma[ehiher4 Satter y and tt}Spoon Control*and lo deflect ix 0USED FOR THE BENEFIT OF ANYONE .T MICROINVERTERS,ACCESSORIES AND REPLACEMENT PARTS(not included.order separately) EXCEPT BLUE RAVEN SOLAR NOR IQ Gateway and Integrated LE-MI Grill . . _. -.-....___ _._.. __._ -.-_. ____._ .......____ SHALL IT BE DISCLOSED IN WHOLE OR Iti Combiner 4/4C d S.ups.>r tad l.4.crt,rt:er:u,r. I06 lg7.1Q4 Do rim no IOrs.7 Micro imwtMe wthlEI8 IN PART TO OTHERS OUTSIDE 6l)1 E IE ! Y modem ;included Dill}+"r.'Itt'I IQ Combiner � � E ble ConmstonatiOne hit trwIncip9 COMMS-10T-01 and C t.LMBDEkittt•96-.8P•iab with slim Spnnrdata pfanior RECIPIENTS ORGANIZATION,EXCEPT v p/'� to ,Ay ,�ta CQMMi$•CELLMOOFM-MI 66 Ensemble sites IN CONNECTION WITH THE SALE AND +�`�El`�M�` '+0"i CGn'a'olltla1eS interconnection equipment CE1LdriCOtM441•O4.SP,.,OS 4a bated LTE M1 e4ik m alei modern with 5-year Sew dale plan USE OF THE RESPECTIVE EQUIPMENT, X-{ AM1-24O-4C CELLht00EM•MrU 4O ATOs bssedLtE-M1reanl�modem...ash WITHOUT THE WRITTEN PERMISSION �- into a single enclosure and streamlines IQ OF BLUE RAVEN SOLAR LLC. C,rcult Breakers Suppwrs Eaton 8a210,BR215,8R220.aR230.a a240.8a2.6.0 and 8p2G0 elona tveaaerS. microinverters and Storage installations by BRk10A'2240V Coma breaker,2 pole,ISA Eaton BR2b0 8RK-15A2.240V CN{W1 Weaken,:.pole,ISA Eaton 8R2t5 providing a consistent• pre-wired solution for BRK20A•2PQs0V Cocktt streaker.2 pole.70A,Felon 8R220 NABCEP BRK 15A.2P-240N8 Circuit breaker 2 pole.I SA Eaton Be215a with avid ooe r k•i supix,.:it .<..:x.. T residential applications. It offers up to four Loot20A-2R240B Y• Casuitbreaker.2 poll,20A.Enron 891708 ernh sold down kti cuppoil CERTIFIED EPIC,01 Power tine•Caner(awnmunrvabn Mudge pawl,peaMty one pair r. 2-pale input CtfCUIlS and Eaton BR series XA SOLA85a#IEl.El E-5 Replacement solar shnaid too IQContkhlct4f4L PV INSTALLATION 4 brusher assembly XA ptId-wa-3 ,to beaky hmtptarat Mt Paw.e Lam Comer in id nomeiner 4r4C Orgt aaafot EPIC-bat PROFESSIONAL Scott Gurney I .. ... _ -.,... .......... ........ XA ENV,PC8h.0 Pralacenent 14 Caraway pnrinn corner bawd(PC.p7 ra Comrtinae era[: IIPV-011719-015866 € X-IO-NA-NO-125A Moittdown kit for Lalan ntrult M0410'Mak 3Crew;, s` s"}; 1 Smart ELECTRICAL SPECIFICATIONS CONTRACTOR: • Includes:Q Gateway for communication and control R4rtn9 r'Far.ir,L.oi:a 441y BRS FIELD OPS 4. Includes Enphase Mobile Connect cellular modem System vohaga i,^0,:s0 VAG.67+c, 385-498-6700 (CILLMO)EM-Mt-Drx-Sr-051,included only with 10 Eaton ell aeries brothel wane 12SA as Combine'4C Mar toltrwout mmernrat g 75A irk . „I • Includes solar shield to match Enphase IQ Battery Mak crtn6nadusarnaommVravwhOmPYRAoraRl 64A aesthetics and deflect heal Max ruaetc.rcun,rating Soutpan 70A • Flexible networking supports WI-Ft, O OOP areas pour endior atonspel up to dote 2-0ceEetorkeR wan Oatriknedoeretatten too)swaaken only Inol Indrawn Ethernet,or cellular L • Optional AC receptacle available for PLC bridge M4x total branch crc i treater r u r6 rating llnpa: 0A of distributed generation i r3SA wrIn re G m tieway breaker cluaed • Provides production metering and consumption ill Queerer Masker 10Ace ISAt BE191emetWEatodinchakd, monitoring Prioductuut metering CT 200 A tend core pieanr railed Sod wired ro 10 Gaieaar tmenptianmanikring CT ICT-2no-&VLitil Abair of 3ii0 A spilt core currant Van Owners a Simple MECHANICAL OATH Oinlena#oMttenaktittit 375t49.5a tattoo(t4.75't19,r z.. 43'i,tikyttr as 2h o6`!(535 airJ wart mewrnng tnacitett. • Centered mounting beackeIo support Single weight 75 kg rlb,S tOs'r Suptud mounting bottom, Ambient temperature range •oil•C to s44•C t-40'to 115k Ft Supportsbottom,back and side conduit entry 1 • Lap to four 2-pole branch circuits for 240 VAC Cadarng Nebula corere tron,plusnearshield plug•in breakers(not included) Enettaarlan enlr r Rer44Iralnq thAgoor,NRiL•earthed.AIWAtypo3ftep aatr constructme X-IQ-AMI-240-4C • BOA total PV or storage branch circuits wee Fuca •20 A to 50 A breaker tooeis.14 to 4 AWG capper cooducrma ( •A6 A Le rake'branch again 4 to Ir0 AWO coppe Conductors •Mon lug coentened ontpul.10 to 21b AWG cooper cookie to6 Reliable -Neutral and ground 14 to 1,0 copper conductors Always tallow local cede itquwements for conductor saamg • tableMRTL-ceriirredNEMAtype3Renclosure ' (*teammate's8c2teeN C3 • e „ - Five-yearilmited warranty INTERNET CONNECTION OPTIONS , Two years Tabor reimbursement program coverage brregratad W,t1 0424141/11M Included'or both the IQ CombinerSK{rs ceimar CELLMooEMM1OOSPitt.CELLMODEMMi05AT-OS(40basedLIE•MIce0Waxmodern) terXe Oat anInsfe!.• , 3`'', • IIL listed tionne5t oattrlarmmodwn is raRired to ea Enasrnbdr hwiaaakens Y-in 1 Ethernet Oputarte2.4 0Cat5E for Cat 6)utPElltemet cable tool ineluddi e j i t. $ COMPLIANCE •{;nnrnlaande,rtl Combiner tat.I'M%CANtC3AC222 No.107.1,42 OSR Pan 15•ctesa8ICES WY PaggragOlannaktrettng-ANSIC12,20accureCfgrata05ri'Hromoucrionl Xd0•AMI-240 4 Conatsstt#an metering:accuracy dace 2.5 Compliance,10 G4teway Ut.a060t liCAN1:SA 22 2 tiro.41010 1 To learn more about Eriphae.e offerings,visit ,.in ___ _-.�__ — __— .- SHEET NAME ` ? ENPHASE TA learn more about Enphase offerings,visit ram• : ``^.'' 0 t''2 i,vis4:r in N1 ^O.norba rirrFrtr I'OFWA^IN'f" inc f.1[r-r•u COnL=w-,!1 AC ,n••I anu.r u,xa sin:uaw,,,,r ty� EN P HAS E, F.-on:Fr.Frfor,n,in Irma 3u1rc!i i.. � 11'':;rrr; SPEC SHEETS REVISION: PAGE NUMBER: 0 SS BLUE RAVEN 1403 N.Research Way Orem,UT 84097 800.377.4480 W W W.BLUERAVENSOLAR.COM 6.63 .62 D I A W I R I NG D I AGRAMS CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE 168 16 USED FOR THE BENEFIT OF ANYONE 31 D I A FUSIBLE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR 8 IN PART TO OTHERS OUTSIDE I I 50 RECIPIENTS ORGANIZATION,EXCEPT 1 3 I ' IN CONNECTION WITH THE SALE AND __ __ _ USE OF THE RESPECTIVE EQUIPMENT, if 1 WITHOUT THE WRITTEN PERMISSION _ A B OF BLUE RAVEN SOLAR LLC. i ? ? NABCEP O TERMINAL LUGS * CERTIFIED \ I AMPERES MAX. WIRE MIN. WIRE TYPE PV INSTALLATION 14 B 1 1 85 �til `O 60 #3 AWG #14 AWG CU OR AL PROFESSIONAL 378 285 Scott Gumey KNOCKOUTS #PV-011719-015866 SYMBOL CONDUIT SIZE I DIAMETER CONTRACTOR: A,B,C IN MM IN MM BRS FIELD OPS KNOCKOUTS A,B,C A 50 13 BB 22 385-498-6700 KNOCKOUTS B .75 19 1.13 29 I C 1.00 25 1.36 35 j D 1.25 32 1.75 45 1 .641 42 -3.76—.- - 4.87 96 124 .31 DIA 8 - 7.45 (2 HOLES) 189 AiiIIIIIIIL li NEMA TYPE 3R pi A,B,C,D KNOCKOUTS ry�./�,'u' — A C 1 : CO KNOCKOUTS DUAL DIMENSIONS: INCHES MILLIMETERS .28 DIA KNOCKOUT A,B,C HORSEPOWER RATINGS 7 KNOCKOUTS CATALOG WIRING AMPERE 240VAC NOTES: NUMBER VOLTAGE RATINGS DIAG. RATING STD. MAX. FINISH - GRAY BAKED ENAMEL ELECTRODEPOSITED OVER CLEANED PHO5PHATIZED STEEL UL LISTED - FILE E-2875 1 0 30 1 0 3 0 DRAWINGBY: ALL NEUTRALS - INSULATED GROUNDABLE D222NRB 240VAC A 60 3 7.50• 10 15• SUITABLE FOR USE AS SERVICE EQUIPMENT SHORT CIRCUIT RATINGS: D322NRB 240VAC B 60 3 * 7.50 10 15 10,000 AMPERES WHEN USED WITH OR PROTECTED BY CLASS H OR K FUSES PLOT DATE: 100,000 AMPERES WHEN USED WITH DR PROTECTED BY CLASS R FUSES TOP ON NEMA 3R ENCLOSURES HAVE PROVISIONS FOR MAXIMIM 2.50 BOLT-ON HUBS. WHEN MOUNTING THESE SWITCHES, ALLOW 3.00 IN / 76 MM MIN. CLEARANCE BETWEEN ENCLOSURES FOR OPENING OF SIDE HINGED DOOR. GENERAL DUTY SAFETY SWITCHES 11 SQUARE L] COMPANY PROJECT NUMBER: *USE OUTER SWITCHING POLES VISIBLE BLADE TYPE •FOR CORNER GROUNDED DELTA SYSTEMS ONLY. 60 AMPERE LUGS SUITABLE FOR 60°C OR 75°C CONDUCTORS. ENCLOSURE - NEMA TYPE 3R RAINPROOF DUG. 863 NO. SHEET NAME: JUNE 2000 REF DWG ♦1863 SPEC SHEET REVISION: PAGE NUMBER: SS RSTC Enterprises, Inc. RAVEN 2214 Heimstead Road BLUE f LADEcK 1403 N.Research Way Eau Claire, WI 54703 3N. searchIT ? 715-830-9997 FLASHED PV ROOF-MOUNT 800.377.4480 COMBINER/ENCLOSURES WWW.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXEPT BLUE RAVEN SOLAR NOR Outdoor Photovoltaic Enclosures 0799 Series SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT Composition/Cedar Roof System IN CONNECTION WITH THE SALE AND ' . USE OF THE RESPECTIVE EQUIPMENT, ` °^ .. WITHOUT THE WRITTEN PERMISSION ETL listed and labeled _ ,;- OF B UE RAVEN SOLAR LLc. Report #3171411 PRT-002 Revised May, 2018 " �� / \,ABCEP • UL50 Type 3R, 11 Edition Electrical equipment enclosures CERTIFIED • CSA C22.2 No. 290 Nema Type 3R ,n -_- • Conforms to UL 1741 Standard PV PROFESSIONAL SIONAL £, Scott Gurney 8PV.011719-015866 0799 Series Includes: ;_ CONTRACTOR: 0799 -2 Wire size 2/0-14 �aE d °?saes BRS FIELD OPS 385-498-6700 0799 -5 Wire size 14-6 0799 -D Wire size 14-8 Modelsavalable in Grey, Back or Rainless Seel Basic Specifications Material options: f ,. • Powder coated, 18 gauge galvanized 90 steel (1,100 hours salt spray) • Stainless steel SolaDedr0799-5G - Process -Seamless draw (stamped) Flashing -15.25" x 17.25" Height -3" Cavity -255 Cubic inches Base Plate: } DRAWING BY: rt ri$ • Fastened to base using toggle fastening system • 5 roof deck knockouts PLOT DATE: • Knockout sizes: (3) .5", (1) .75" and (1) 1" • 8", 35mm slotted din rail • Ground Block PROJECT NUMBER: Passthrough and combiner kits are available for either SnlaDeck0799-DG `= SHEET NAME: AC or DC applications. SPEC SHEET REVISION: PAGE NUMBER: SS Ni„,-- .......- BLUE RAVEN SFM INEII� ITaUNIRAL 1403Orem,UT 84097VaY BETTER SOLAR STARTS HERE 800 377 4480 W W W.BLU ERAVENSOLAR.COM 1 CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE - • _--- EXCEPT BLUE RAVEN SOLAR NOR IIII �, �jj'jj,/�`/S� SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE 2 =�•r•�+vv - RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, ift 16 I 24:1, SYSTEM OVERVIEW 20% FEWER ATTACHMENTS WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. S PART NAME DESCRIPTION Save time and money on every project:SFM INFINITY requires fewer attachments than rail systems. N A BC E P 1 2 INSTALLS PER DAY gif TRIMRAIL Structural front trim provides aesthetic and aligns modules. CERTIFIED i PV INSTALLATION Make two installs per day your new standard.SFM INFINITY has fewer TRIMRAIL SPLICE Connects and electrically bonds sections of TRIMRAIL. r' PROFESSIONAL roof attachments,one tool installation,and pre-assembled components soon Gurney to get you off the roof 40%faster. • #PV-01 n,s-o,sass -:. 111 lap TRIMRAILFLASHKIT Attaches TRIMRAIL to root.Available for comp shingle or tile. CONTRACTOR: I O OF HOMEOWNERS SFM INFINITY15Attachments BRS 3 5 4198 6 00 OPS ,Q lel lir MODULE CLIPS Secure modules to TRIMRAIL. © �it.__ MICRORAIL Connects modules to SLIDERS.Provides post-install array leveling. BETTER AESTHETICSII a a Install the system with the aesthetics preferred by homeowners, or SPLICE Connects and supports modules.Provides east-west bonding. with integrated front trim,trim end caps,dark components,and ATTACHED SPLICE also available. recessed hardware. El lik SLIDER FLASHKIT Roof attachment and flashing.Available for comp shingle and tile. RAIL 20 Attachments MAXIMUM POWER DENSITY 30% LOGISTICS SAVINGS Easily mix module orientations to achieve optimal power density without incurring the increased bill of materials,labor,and BONDING AND ACCESSORIES With fewer SKUs and compact components,SFM INFINITY is easier to attachments required by rail. stock,easier to transport,and easier to lift to the roof.Plus,make more PART NAME ( DESCRIPTION efficient use of your vehicle fleet. lirTRIMRAIL ENDCAPS Covers ends of TRIMRAIL for refined aesthetic. irTRIMRAIL BONDING CLAMP Electrically bonds TRIMRAIL and modules Pal Pal N/S BONDING CLAMP Electrically bonds rows of modules • • • • DRAWING BY: _ — . , . ..... . PLOT DATE: SFM INFINITY REVOLUTIONIZES ROOFTOP SOLAR WITH BENEFITS ACROSS YOUR BUSINESS, PROJECT NUMBER: FROM DESIGN AND LOGISTICS, THROUGH ARRAY INSTALLATION AND SERVICE . SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: SS ■■ 1 1 ' SU 1 BLUE RAVEN ■ �■ ; SFm FRAME ;UIMICRORAILTM INSTALLATION GUIDE I PAGE 140rN.Uearch Vey 800.377.4480 W W W.BLUERAVENSOLAR.COM r IIII ' r r r ' ' r r ' r r I r CONFIDENTIAL-THE INFORMATION I I I I I I I HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE ili I ECEPT BLUE RAVEN SOLAR NOR I •! S ALL IT BE DISCLOSED IN WHOLE OR / N PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION v, OF BLUE RAVEN SOLAR LLC. ooki A. !y re` B C E P I CERTIFIED PV INSTALLATION I - PROFESSIONAL - Scott Gurney - #PV-071719-015666 I E-W BONDING PATH: �11 CONTRACTOR: 1 E-W module to module bonding is accomplished BRS FIELD OPS with 2 pre-installed bonding pins which engage 385-498-6700 on the secure side of the MicrorailTM and splice. r IIIII , I I I I I 1 1 I I I I • 1 1 1 I I • I t I III I III T III I _ 11f I _ IIlII III I III I I ' I i 1 I I I 1 1 1 1 I I I I le Star Washer is WEEBLUG PA d Single Use Only Single Use OnlyI - Alternate method N-S BONDING PATH: 441 TERMI NAL TORQUE N S module to module bonding is Install Conductor andAll *lb accomplished with bonding clamp with 2 integral torque to the following: TERMINAL TORQUE, TERMINALTOROUE, bonding pins- :et also to alternate method) 4-6 AWG: 35in-Ibs Install Conductor and Install Conductor and 8 AWG 25 in-I6s torque to the following: torque to the following: 1 0-14 AWG 20 in-Ibs 4-14 AWG 35in-Ibs 6-14 AWG 7ft-Ibs , , DRAWING BY: LUG DETAIL& TORQUE INFO LUG DETAIL& TORQUE INFO LUG DETAIL& TORQUE INFO C -- '-f-' Ilsco Lay-In Lug (GBL-4DBT) Ilsoo Range Lug (SCB--4) Wiley WEEEBLug (6.7) PLOT DATE: • 10-32 mounting hardware • 1/4" mounting hardware • 1/4" mounting hardware _ ` "� • Torque = 5 ft-lb • Torque = 75 in-Lb • Torque = 10 ft-lb Alternate method PROJECT NUMBER: • AWG 4-14-Solid or Stranded • AWG 4-14-Solid or Stranded • AWG 6-14-Solid or Stranded TRIM RAIL BONDING PATH: NOTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION Trimrail to module bonding is accomplished with SHEET NAME: System bonding isaocomplished through modules.System grounding accomplished by attaching bonding clamp with integral bonding pin and SPEC SHEET bonding T-bolt. (refer also to alternate method) a ground lug to any module at a location on the module specified by the module manufacturer. REVISION: PAGE NUMBER: -- — SS SUNUL CODE COMPLIANCE NOTES BL . RAVEN ■ FRAME ■ ■ ; MICRORAILTM INSTALLATION GUIDE ; PAGE 740rN Research 800.377,4480 W WW.BLUERAV ENSOLAR.COM CONFIDENTIAL THE INFORMATION SYSTEM LEVEE_Fl RE CLASSI FICALTION THEBENEFIT HEREIN CONTAINEDSHALL NOT BE USED FOR THE B OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR The system fire class rating requires installation in the manner specified in the performance is inherent in the SFM design,and no additional mitigation measures SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE SUNFRAME MICRORAIL (SFM) Installation Guide.SFM has been classified to are required.The fire classification ratingis valid for anyroofpitch.There is no RECIPIENTS ORGANIZATION,EXCEPT q IN CONNECTION WITH THE SALE AND the system level fire portion of UL 1703. This UL 1703 classification has been required minimum or maximum height limitation above the roof deck to maintain USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION incorporated into the UL 2703 product certification. SFM has achieved Class A, the Class A, B & C fire rating for SFM. SUNFRAME MICRORAILTM components shall OF BLUE RAVEN SOLARLLC. B & C system level performance for Low slope & steep sloped roofs when used be mounted over a fire resistant roof covering rated for the application. in conjunction with type 1 and type 2 modules. Class A, B & C system level fire NABCEP CERTIFIED Module Type Fbof Slope System Level Fire Rating Microrail Direction Module Orientation Mitigation Required PV INSTALLATION PROFESSIONAL Type 1 and Type 2 Steep Slope & Low Slope Class A, B & C East-West Landscape OR Portrait None Fbquired Scott Gurney #PV-011719-015866 CONTRACTOR: BRS FIELD OPS UL2703 TESI MODULE 385-498-6700 See pages 22 and 23 for a list of modules that were electrically and mechanically tested or qualified with the SUNFRAME MICRORAIL (SFM) components outlined within this Installation Guide. • Maximum Area of Module = 27.76 sqft • UL2703 Design Load Ratings: a) Downward Pressure - 113 PSF / 5400 Pa b) Upward Pressure - 50 PSF / 2400 Pa c) Down-Slope Load - 21.6 PSF / 1034 Pa • Tested Loads: a) Downward Pressure - 170 PSF / 8000 Pa b) Upward Pressure - 75 PSF / 3500 Pa c) Down-Slope Load - 32.4 PSF / 1550 Pa • Maximum Span = 6ft DRAWING BY. • Use with a maximum over current protection device OCPD of 30A • System conforms to UL Std 2703, certified to LTR AE-001-2012 PLOT DATE: • Rated for a design load of 2400 Pa / 5400 Pa with 24 inch span • PV modules may have a reduced load rating, independent of the SFM load rating. Please consult the PV module manufacturer's installation guide for more information PROJECT NUMBER: • Down-Slope design load rating of 30 PSF/ 1400 Pa for module areas of 22.3 sq ft or less SHEET NAME: SPEC SHEET REVISION. PAGE NUMBER: SS 1161NiIlLe"r I 1 ;):UN1a ; BLUE RAVEN ■ �� 1 RAM& ■ ■ : MICRORAIUm INSTALLATION GUIDE : PAGE '40°N. �T °gWay 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE Manufacture Module Model / Series Manufacture Module Model/ Series Manufacture Module Model / Series USED FORBLUETUE RAVBENENITOLANNORE EXCEPT RAVEN SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE Aleo P-Series Eco Solargy Orion 1000& Apollo 1000 LGxxxN2T-A4 RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND ET Solar ET-M672BHxxXTW LGxxx(A1C/E1C/E1K/N1C/N1 K/N 2T/N2W/ USE OF THE RESPECTIVE EQUIPMENT, WI DNA-120-(BF/MF)26OOFUBLUE RAVEN SOLAR LLC. Aptos Freedom Forever FF-MP-BBB-370 Q1C/Q1K/S1C/S2W)-A5 DNA-144-(BF/MF)26 LGxxxN2T--B5 FreeVolt Mono PER- XI-ABC-El - LGxxxN1 K B6 / CHSM6612P,CHSM6612P/HV,CHSM6612M, GAL GCL-P6& GCL-M6Series LGxxx(A1C/M1C/M1K/N1C/N1K/Q1C/Q1K/ CERTIFIED Astronergy CHSM6612M/HV,CHSM6610M (BL)(BF)/(HF), TD-AN3,TD-AN4, LG Electronics QAC/QAK)-A6 Hansol PV INSTALLATION CHSM72M-HC UB-AN1,UD-AN1 LGxxx(N1C/N1K/N2T/N2W)-E6 PROFESSIONAL AXN6M610T,AXN6P610T, 36M,60M,60P,72M & 72P Series, LGxxx(N1C/N1K/N2W/51C/52 W) G4 IPV-011719-0 5866 Auxin AXN6M612T &AXN6P612T Heliene 144HC M6 Monofacial/Bifacial Series, LGxxxN2T--.5 CONTRACTOR: AXiblackpremium 60(35mm), 144HC M10 SL Bifacial LGxxx(N1K/N1W/N2T/N2W)-L5 BRS FIELD OPS AXI power 60(35mm), HT60-156(M)(NDV)(-F), LGxxx(N1C/Q1C/Q1K)-N5 385-498-6700 HT Solar Axitec AXlpower 72 (40mm), HT 72-156(M/P) LGxxx(N1C/N1K/N2W/Q1C/Q1K)-V5 AXlpremium 60(35mm), KG,MG,TG,RI,RG,TI,MI,HI & KI Series LR4-60(HIB/HIH/HPB/HPH)-xxxM Hyundai AXlpremium 72 (40mm). HiA-SxxxHG LR4-72(HIH/HPH)-xxxM BVM6610, ITEK iT,iT-HE & iT-SE Series LR6-60(BP/HBD/HIBD)-xxxM(30mm) Boviet BVM6612 LR6-60(BK)(PE)(HPB)(HPH)-xxxM (35mm) ,span Solar ,PS-60& S'S-72 Series BYD P6K& MHK-36Series LONG LR6-60(BK)(PE)(PB)(PH)-xxxM (40mm) JAP6 60-xxx,JAM 6-60-xxx/SI,JAM6(K)-60/ LR6-72(BP)(HBD)(HIBD)-xxxM (30mm) CS1(H/K/U/Y)-MS xxx,JAP6(k)-72-xxx/4BB,JAP72SYY-xxx/ZZ, LR6-72(HV)(BK)(PE)(PH)(PB)(HPH)-xxxM CS3(K/L/U),CS3K-MB-AG,CS3K-(MS/P) JAP6(k)-60-xxx/4BB,JAP6OSYY-xxx/ZZ, (35mm) Canadian Solar CS3N MS,C53U MB AG,C53U (MS/P),CS3W J4Solar JAM6(k)-72-xxx/ZZ,JAM72SYY-xxx/ZZ, LR6-72(BK)(HV)(PE)(PB)(PH)-xxxM (40mm) CS5A-M,CS6(K/U),CS6K-(M/P),CS6K-MS CS6P-(M/P),CS6U-(M/P),CS6V-M,CS6X-P JAM6(k)-60xxx/ZZ,JAM605YYxxx/ZZ. Mission Solar Energy MSESeries i.YY:01,02,03,09,10 Centrosolar America GSeries& &Series ii.ZZ:SC,PR,BP,HiT,IB,MW,MR Mitsubishi M,E& MLE Series CT2xxMxx-01,CT2xxPxx-01, CertainTeed CTxxxMxx 02,CTxxxM 03, ,KM& ,KMS Series Neo Solar Power Co. D6M & D6P Series link() Eagle,KMxxxM DRAWING BY: CTxxxMxx-04,CTxxxHC11-04 JKMxxxM-72HL-V Dehui DH-60M Kyocera KU Series PLOT DATE: PROJECT NUMBER: • Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx" • Items in parenthesis are those that may or may not be present in a compatible module's model ID • Slashes "/" between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME: • Please see the SFM UL2703 Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET • SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section, page 12 for further information REVISION: PAGE NUMBER: SS 1 1 I�r~� SUN 23 BLUE RAVEN ■u 1 FRAME . .. ' MICRORAIITM INSTALLATION GUIDE ; PAGE 1403 Research Way 1 4097 800.377.4480 W W W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE FOF Manufacture Module Model/ Series Manufacture Module Model / Series Manufacture Module Model/ Series UEEC EXCEPPTT B BLLUEBL ANYONE UE RAAVEVENNITO SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE EVPVxxx(H/K/PK), TwinPeak Series A-Series A400-BLK,SPR-MAX3-XXX-R, RECIPIENTS ORGANIZATION,EXCEPT Sun Power IN CONNECTION WITH THE SALE AND TwinPeak 2 Series X-Series,E-Series & P-Series USE OF THE RESPECTIVE EQUIPMENT, VBHNxxxSA15 & SA16, WITHOUT THE WRITTEN PERMISSION TwinPeak 2 BLK2 Series Suntech STP,STPXXXS-B60/Wnhb OF BLUE RAVEN SOLAR LLC. VBHNxxxSA17 & SA18, REC(cont.) Panasonic VBHNxxxSA17(E/G) & SA18E, TwinPeak 25(M)72(XV) TP572,TP596,TP654,TP660, VBHNxxxKA01 & KA03 & KA04, TwinPeak 3 Series(38mm) Talesun TP672,Hipor M,Smart NABCEP VBHNxxxZA01,VBHNxxxZA02, TP4(Black) SC,SC B,SC B1,SC B2 CERTIFIED VBHNxxxZA03,VBHNxxxZA04 Fbnesola Vitrus2 Series & 156 Series Ted a TxxxH,TxxxS PV INSTALLATION PROFESSIONAL Foimar SGxxxM (FB/BF) Rsen RSM72-6 (MDG)(M),RSM60-6 PA05,PD05,DD05,DE06,DD06,PE06, Scott Gurney SPV-011719-015866 Phono Solar PS-60,PS-72 SEG Solar SEG-xxx-BMD-HV Trina PD14,PE14,DD14,DE09.05,DE14,DE15, Prism Solar P72 Series S-Energy SN72 & SN60 Series(40mm) PE15H CONTRACTOR: BRS FIELD OPS Plus,Pro,Peak,63,64,65,66(+),67,G8(+) Seraphim SEG-6& SRP-6 Series Upsolar UP-MxxxP(-B), 385-498-6700 Pro,Peak L-G2,L-64,L-65,L-66,L-G7 Sharp NU-SA& NU-SCSeries UP-MxxxM(-B) QPEAK DUO BLK-G6+ SLA, SLG,BC Series & SlLxxx(BL/NL/NT/HL/ D7MxxxH7A,D7(M/K)xxxH8A Q.PEAK DUO BLK-G6+/TS Silfab ML/BK/NX/NU/HC) URE FAKxxx(C8G/E8G),FAMxxxE7G-BB Q.PEAK DUO(BLK)-68(+) Solarever USA 5E-166'83 xxxM-120N FAMxxxE8G(-BB) Q.Cells Q.PEAK DUO L-68.3/BFF PowerXT-xxxR-(AC/PD/BD) Eldora, Q.PEAK DUO (BLK)ML-G9(+) Solaria PowerXT xxxC PD Vikram Savo, Q.PEAK DUO XL-69/69.2/69.3 PowerXT-xxxR-PM (AC) Somera Q.PEAK DUO(BLK)ML-G10(+) Vlhaaree AC& Adiya Series Sunmodule Protect, Q.PEAK DUO XL-G(10/10.2/10.3/10.c/10.d) Sol arWorld Sunmodule Pus Winaico WSr& WSPSeries Alpha(72)(Black)(Pure) SS-M-360 to 390 Series, Yingli YGE& YLM Series I N-Peak(Black) SS-M-390 to 400 Series, ZN Shine ZXM6-72, ZXM6-NH144-166_2094 N-Peak 2 (Black) REC Sonali SS-M-440 to 460 Series, PEAK Energy Series SS-M-430 to 460 BiFacial Series, PEAK Energy BLK2 Series SS230-265 PEAK Energy 72 Series SunEdison • F-Series,R-Series & FLEX FXS Series DRAWING BY. Suniva MV Series & Optimus Series PLOT DATE: PROJECT NUMBER: • Unless otherwise noted,all modules listed above include aLL wattages and specific models within that series. Variable wattages are represented as "xxx" • Items in parenthesis are those that may or may not be present in a compatible module's model ID • Slashes "/" between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME: • Please see the SFM UL2703 Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET • SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section, page 12 for further information REVISION: PAGE NUMBER: ---- SS AUTHORIZATION TO MARK AUTHORIZATION TO MARK ' LU RAVE Ul�t'f�C'�C U1�C'f tC'�I Total Quality.Assured. Total Quality-ASsur'ed. 1403 N.Research Way Orem,UT 84097 This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) 900.377.4480 W W W.BLUERAVENSOLAR.COM Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION INED SHALL NOT BE Report. Report. USRED F EIN OORTHE ABENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE applied only at the location of the Party Authorized To Apply Mark. applied only at the location of the Party Authorized To Apply Mark. RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND . . . . _ - _ USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Applicant: Unirac, Inc Manufacturer: Redacted information Applicant: Unirac, Inc Manufacturer: Redacted information OF BLUE RAVEN SOLAR LLC. Address: 1411 Broadway Blvd NE Address: 1411 Broadway Blvd NE NABCEP Albuquerque, NM 87102 Albuquerque, NM 87102 CERTIFIED Country: USA Country: USA PV INSTALLATION Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL Report Issuing Office: Intertek Testing Services NA, Inc. Lake Forest, CA Report Issuing Office: Intertek Testing Services NA, Inc. Lake Forest, CA, Scott Gurney Control Number: 5003705 Authorized by: (1 �, _l- �}_ _,�Ctea(,!/t,c t) C— Control Number: 5014989 Authorized by: C.M0A&LcdeoliPete, #PV-011719'O 5866 for L. Matthew Snyder, Certification Manager for L. Matthew Snyder, Certification Manager CONTRACTOR: BRS FIELD OPS 385-498-6700 COOS C O US trareo CO Intertek lntertek This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of lntenek's Client and is provided pursuant to the Certification agreement between Imertek and its Client.Intertek's responsibility and liability are This Authorization to Mantis for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between mtenek and its Client.Intenek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance writ the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by the use of this Authorization to Mark.only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution el this Authorization to Mark and then only in its entirety.Use of Intenek's Certification mark is restricted to the conditions laid out In the agreement and in this Authorization to Mark.My further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and In this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights, IL 60005 545 East Algonquin Road,Arlington Heights,IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices,and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices,and Ground Lugs for Use with Flat- Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 DRAWING BY: Brand Name: Unirac Brand Name: Unirac Models: Unirac SFM Models: Unirac SFM PLOT DATE: PROJECT NUMBER: SHEET NAME: ATM for Report 102393982LAX-002 Page 1 of 4 ATM Issued: 27-Oct-2022 ATM for Report 102393982LAX-002 Page 2 of 4 ATM Issued:27-Oct-2022 SPEC SHEET ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory REVISION: PAGE NUMBER: ____ SS 'Noe- Intertek AUTHORIZATION TO MARK Intertek AUTHORIZATION TO MARK BLUE RAVE N • Total Quality.Assured, Total Quality.ASStafed.. 1403 N.Research Way Orem,UT 84097 This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) 800.377.4480 Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing WWW.BLUERAVENSOLAR.COM Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION Report. Report. HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUE RAVEN SOLAR NOR This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be SHALL IT BE DISCLOSED IN WHOLE OR applied only at the location of the Party Authorized To Apply Mark. applied only at the location of the Party Authorized To Apply Mark. IN PART TOGAN C RECIPIENTS ORGANIZATION,ZAON,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Applicant: Unirac, Inc Manufacturer: Redacted information Applicant: Unirac, Inc Manufacturer: Redacted information OF BLUE RAVEN SOLAR LLC. 1411 Broadway Blvd NE 1411 Broadway Blvd NE NABCEP Address: Albuquerque, NM 87102 Address: Albuquerque, NM 87102 CERTIFIED Country: USA Country: USA PV INSTALLATION Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL Report Issuing Office: Intertek Testing Services NA, Inc., La Forest, CA i Report Issuing Office: Intertek Testing Services NA, Inc., Lake Forest, CA scat Gurney �_JJ���� NPV-011719-015868 Control Number: 5019851 Authorized by: doithC. Control Number: 5021866 Authorized by: for L. Matthew Snyder, Certification Manager for L. atth�r, CertificationManager CONTRACTOR: BRS FIELD OPS 385-498-6700 C US C US ,. Intertek Intertek This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Interiek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of lntertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party.other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is by the use of this Authorization to Mark.Only the Client Is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of lntertek's Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark.My further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and In this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of thelr obligations In this respect. Intertek Testing Services NA Inc. Intertek Testing Services NA Inc. 545 East Algonquin Road,Arlington Heights,IL 60005 545 East Algonquin Road,Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices,and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar20211 Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:24Mar2021] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 DRAWING BY: Brand Name: Unirac Brand Name: Unirac Models: Unirac SFM Models: Unirac SFM PLOT DATE: PROJECT NUMBER: SHEET NAME: ATM for Report 102393982LAX-002 Page 3 of 4 ATM Issued:27-Oct-2022 ATM for Report 102393982LAX-002 Page 4 of 4 ATM Issued: 27-Oct-2022 SPEC SHEET ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1Ju1.2022)Mandatory REVISION. PAGE NUMBFR: SS t itertek Listing Constructional Data Report (CDR) 111te! ek Listing Constructional Data Report (CDR) BLUE RAVEN Total Quality.Assured. Total Quality,Assured. 1403 N.Research Way Orem,UT 84097 1.0 Reference and Address 1.0 Reference and Address 800.377.4480 Report Number 1D2393982LAx-oo2 Original 11-Apr-2016 Revised: 5-Oct-2022 Report Number 102393982LAX-002 I Original 11-Apr-2016 Revised: 5-Oct-2022 WWW.BLUERAVENSOLAR.COM Email CONFIDENTIAL-THE INFORMATION Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE with Flat-Plate Photovoltaic Modules and Panels [UL 2703:2015 Ed.1+R:24Mar2021] EXCEPT BLUE RAVEN SOLAR NOR Standards ) SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE PV Module and Panel Racking Mounting System and Accessories[CSA TIL No. A-40:2020] RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, Applicant Unirac, Inc Manufacturer 2 WITHOUT THE TE ARIT SOLARNP MISSION OF BVEN1411 Broadway Blvd NE Address Albuquerque, NM 87102 Address NABCEP Country USA Country • • CERTIFIED Contact Klaus Nicolaedis Contact Todd Ganshaw PV INSTALLATION Phone 505-462-2190 Phone PROFESSIONAL Scott Gurney 505-843-1418 #PV-011719-016866 FAX NA FAX Email klaus.nicolaedis@unirac.com Email CONTRACTOR: BRS FIELD OPS toddg@unirac.com 385-498-6700 Manufacturer 3 Manufacturer 4 Address Address Country Country Contact Contact Phone Phone FAX FAX Email Email Manufacturer 5 Address h DRAWING BY: Country Contact PLOT DATE: • Phone FAX PROJECT NUMBER: Page 1-Of 138• Page 2—of 138 This report s to the ea;lusrve We or Inlertek's Client and 4 teO.8ed pursuant to the eene.'bah een Imputes and its Ghnt Intertetes rThis report m for the a oluswe use or Imertek's Client end>S e$Oon y and SHEET NAME: ag+ espon4�ity andprovided Pursuant t0 the agreenrery Wee*"Intertek and is Chant InOertetc'e r tubety are tinned to the terms and eondeione of the agreement anerteh asaumee no babel):to any party.other than to the Deere in accordance well the taeiey atra limped to the terms and owe:eons of the agreement amerteh assumes no liability to any party..other than to the Client in accadand*with to SPEC SHEET agreement to ro any loss.expense or damage octashea by the use of this repot es Obey the Client aulhorued to permit copying orN Mrs of report and agreement for any loss.expense or damage co a:stoned by the use o this report Orgy the Gent rs enhanced to puma coping or drstneution of tee TOW and then only in its entwety.Any use of the Intent*name or one W its marks to the sale or a.Prerasernent Of the tested malenal,product or service most first be then only in Its entirety Any use of the beret name or one of pe marks for the sae or adretasenere or the tented material.product or seance must fret be Opp-Owed in wrifmg by IMertea.The oeeervatxms and test results a bus report are relevant only to the sample tested This repot by itself does not imply that the aptxoved m v ntxg by!mene t.The ooeervabou and test results.n this report are relevant only to the sample tested This repo by Meet does not impey that the REVISION: PAGE NUMBER: natergt.product,or*entree u or has ever been under en Imenee cerhkabon program mate:i.eI pet a service re or has ever been under an intense Ce tecatiaXf program SS Report No. 102393982LAX-002 Page 3 of 138 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 4 of 138 Issued: 11-Apr-2016 'INle**- Unirac, Inc Revised: 5-Oct-2022 Unirac, Inc Revised: 5-Oct-2022 VE 2.0 Product Description 2.0 Product Description E RA N . Product Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2022SEP28 Models Unirac SFM 1403 N.Research Way Brand name Unirac Model Similarity NA Orem,UT 84097 800.377.4480 The product covered by this report is the Sun Frame Micro Rail roof mounted Photovoltaic WWW.BLUERAVENSOLAR.COM Rack Mounting System.This system is designed to provide bonding and grounding to Fuse Rating: 30A CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE photovoltaic modules.The mounting system employs anodized or mill finish aluminum brackets USED FOR THE BENEFIT OF ANYONE that are roof mounted using the slider, outlined in section 4 of this report.There are no rails Module Orientation: Portrait or Landscape EXCEPT BLUE RAVEN SOLAR NOR within this product, whereas the 3" Micro Rail, Floating Splice, and 9"Attached Splice Maximum Module Size: 17.98 ft2 SHALL IT BE DISCLOSED IN WHOLE ORIN PART TO OTHERS OUTSIDE electrically bond the modules together forming the path to ground. UL2703 Design Load Rating: 33 PSF Downward, 33 PSF Upward, 10 PSF Down-Slope RECIPIENTS WITH ORGANIZATION, SCANT Tested Loads-50 psf/2400Pa Downward, 50psf/2400Pa Uplift, 15psf/720Pa Down Slope INEONNECE IOREN WITH HE E SALE ANDU , The Micro Rails are installed onto the module frame by using a stainless steel bolt anodized Trina TSM-255PD05.08 and Sunpower SPR-E20-327 used for Mechanical Loading WITHOUT THE WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. with black oxide with a stainless type 300 bonding pin,torqued to 20 ft-lbs, retaining the modules to the bracket.The bonding pin of the Micro Rail when bolted and torqued, penetrate Increased size ML test: the anodized coating of the photovoltaic module frame(at bottom flange)to contact the metal, Maximum Module Size:22.3 ft2 7BCEP creating a bonded connection from module to module. UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 30 PSF Down-Slope Description LG355S2W-A5 CERTIFIED The grounding of the entire system is intended to be in accordance with the latest edition of the used for Mechanical Loading test. PV INSTALLATION National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar Mounting configuration: Four mountings on each long side of panel with the longest span of 24" PROFESSIONAL Photovoltaic Systems or the Canadian Electrical Code, CSA C22.1 Part 1 in accordance to the UL2703 Design Load Rating:46.9 PSF Downward,40 PSF Upward, 10 PSF Down-Slope Scott Gurney revision in effect in the jurisdiction in which the project resides. Any local electrical codes must LG395N2W-A5, #PV-011719-015866 be adhered in addition to the national electrical codes.The Grounding Lug is secured to the LG360S2W-A5 and LG355S2W-A5 used for used for Mechanical Loading test. CONTRACTOR: photovoltaic module,torqued in accordance with the installation manual provided in this Mounting configuration: Six mountings for two modules used with the maximum span of 74.5" BRS FIELD OPS R: document. IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 50psf/2400Pa Uplift 385-498-6700 Other optional grounding includes the use of the Enphase UL2703 certified grounding system, Ratings Mechanical Load test to add FlashLoc Slider and Trim Assemblies to UL2703 and IEC 61646 which requires a minimum of 2 micro-inverters mounted to the same rail,and using the same Certifications, & Increase SFM System UL2703 Module Size: engage cable. Maximum Module Size: 27.76 ft2 UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 21.6 PSF Down-Slope Jinko Eagle 72HM G5 used for Mechanical Loading test. Mounting configuration: Four mountings on each long side of panel with the longest span of 24" Mamzimum module size:21.86 ft2 IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 75psf/3600Pa Uplift SunPower model SPR-A430-COM-MLSD used for Mechanical Loading Fire Class Resistance Rating: -Class A for Steep Slope Applications when using Type 1 Modules.Can be installed at any interstitial gap. Installations must include Trim Rail. - Class A for Steep Slope Applications when using Type 2 Modules. Can be installed at any interstitial gap. Installations must include Trim Rail. - Class A Fire Rated for Low Slope applications with Type 1 or 2 listed photovoltaic modules. This system was evaluated with a 5"gap between the bottom of the module and the roof's surface See section 7.0 illustractions# 1, 1 a and 1 b for a complete list of PV modules evaluated with DRAWING BY: these racking systems PLOT DATE: Other Ratings NA PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.315(1-Jul-2022)Mandatory ED 16.3.15(1-Jul-2022)Mandatory —___ SS Report No. 102393982LAX-002 Page 42 of 138 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 43 of 138 Issued: 11-Apr-2016 11111Ne'r Unirac, Inc Revised: 5-Oct-2022 Unirac, Inc Revised: 5-Oct-2022 17.0 Illustrations I 17.0 Illustrations I BLUE RAVEN Illustration 1 -Approved PV Modules Illustration la-Approved PV Modules Continue 1403 N.Research Way ' Orem,UT 84097 800.377.4480 Manu7aeane Modiste Moak/Sevier, Ma1YEKbe. Moue Model/Seriea Manufacture landau Model/Saner Manufacture Module MOM/SerW W W W.BLUERAVENSOLAR.COM Alt,. I'seres L Sutaryy Qesn 1000 S.Avoids 10W ,bxae47`A4 IL'PV IVanr(h17KI>K1 .._.-„_ INFORMATIONCONFIDENTIAL-THE -- HEREIN CONTAINED SHALL NOT BE it tioLar (1•rW/7Wraaarw Ll3aea(AICrESUE 1K/N1C/T1 I K/742T/N 2W/ VBrWXaa5A1S 1 5A16, USED FOR THE BENEFIT OF ANYONE 0e44.170(0KMFt76 EXCEPT BLUE RAVEN SOLAR NOR A1Mar freedom IN veer Fr.MP-669-37e QIC/Q1K/SLUS7Wl}AS VBHN.AaSA17 6 SA.16.. DNA-1ae-ryFMT)/a _. _. .... SHALL IT BE DISCLOSED IN WHOLE OR I'reevnlr Mom f l K( LGnaM77-115 Penavmlr VnadarreSA17(r/G)b SAUSE- IN PART TO OTHERS OUTSIDE (719661./P.CK5rr6617P7Wv(HSM6417M, CCL GCL-06 6 CAL M6 Series LCaxaN111-86 VB0NrouKA01 6 I0,03 8 KAM. RECIPIENTS ORGANIZATION,EXCEPT IS CONNECTIONWITH THE SALE AND Awoormy (:II. KVI 17rv,Csi9A6410M 0Axei VP{r1. , 10•AMS,TO-AH1 lbvrgA1(1141(/MSKJNIC/MIPVQIUQIIV Y01WmexL501V�N14=51AD7 USE OF THE RESPECTIVE EQUIPMENT, (H1M771e•HC µ"'V'i1 i L16 ANl J0.AN1 LG EIeC1701iC5 ' QAC/QAR)-A6 Y(001aYa7A05.V0HNrnv7A04 WITHOUT THE WRITTEN PERMISSION .. _. I _ i 1Laca(01GMIKM2rM2W1ib OF BLUE RAVEN SOLAR LLC. AXN6M6101•AXN6P610T. . . WI,60M,60P,72M&17P Series. I . VnaaM(F B(H7) Ahern LGaai(M1CYM1KM7WP3C/52W.44 ...- _. ... A1N6•16L71 IS A1iN6P6 UT Heliene 1 1444C M6 Mam1au11/Blhcwl Series, PMno LILA, PS 60,PR 71 AXKAx%Wint n 60I15e a 1. 144M(1410 SI 677atial : L1ilora172T-7S Prism Solar Pr/Serves / NABCEP AXlpwrd 60ISimoW. HT6g156(14)MDs1(IL Iblwt(NLKMIwM21M7W1..LS. P 7 Aaife[. Axtpd e,77140aaA1, H7 Auto, HT 72-15G(WP1 lGaaaMl(/Q8C1Q11)#I5 PM.RU•It�a.,�S.Ga.G5.G6('1G G81�1 CERTIFIED AKlpremeam60(lSrnml KG.MG TL.NI,Ar,,TI,M 1.K15[rla+ LGcaA(N10141JIN2W/Q1VQ1K)-VS etalI(041ak L.41,L C.4,►-W,L�.q L-G7 A%Ipretµrm 72 140men1 Hyureta, H;A.S.a.H4 QPFAK DUO BU1{r6• (Ks-60(F4IBMINMP6AtPI/).asuM PV INSTALLATION ._ _._... _._ .._ QPEAK DUO&LK-66.ir5 Kafiri nu fl ,T.IT ME 6,r Si.series LR4-72(r11FIMPM)-auM QPEAK DUD DIM GE•1 PROFESSIONAL BvM6617 - LK6-60(BPMBDMIB($wM(5Cev d Q(eUs Scott Gurney /span Soar 17PS 40 7•rP5 77 semi 1 QPEAK OIIO(-60 1/13FF NPV-011719-015868 ant 1,61(d KKK I6 Sera. __ LK6 60(DKKPEKHPBKHPE)-rwN(SSLwn) l I IAP6 60•m,tAMsrlg•nVIM.V IAM6(KI-60/ LONGI LR6.60(6K)(PF)(f6){PH)-KaaM(401m) QPEAK DUO( ML-C+9(•) CS10061./Y1-M5 -QJYAK DUO K4 I..roK.9 7/GW.1 CONTRACTOR: ua.yape(k).77•arayeadIW 77Sw,ara.M/, IKA.?203S1 MS(04111B0}.:aM(Weer) CS50611U.CS3X-M8 AG.CSSK-IMSM j QPEAK DUO OAK)ML_G1001 BRS FIELD OPS I IA M.{k 7 R/460.1APtl0SYY.K a/77. 6R6-77(HYKBKKPCKPHKPBKNPI(1'a a1aM (.modish Srtea CS%-MS,C 3U-M1144.CSSu-R+S/M.GSS* j .... ...............___. I Q A1I DUO Kt GI1u/10.7/10.Sn0.U10_dl 385-498-6700 IAM6(y-77-.aa/72,7AM775ww aril (ism ALpIMt77){B(ae6llgeel (SSA-M,C56(IW►CS6K-(WP►CS6K-MS JA Sala - (ia0.0401CWI•(14/P(CSAV•M(%A4P I1A146(k)60aNIL 1AA/6�Y'7- � ._ Litt. (2BsAKrrrrnkKl•67(rH)aaxM...... -.. _ .....___- N-Peat Park) II W:01.f41.0 04T,i Mi3von SOW E71ergY NSF Lenen (errrmaq Ur AmIY4a C-brR1 A 1.1enPs II.II'SC.PII-pP,I4T,IE,MW.MR NA,*7 ONaU C17.KM..-01,.C17..P..-01. __.. _ Mipu6,afu M Se. Ih 6 M/k Sees 4CC PEAK VWQY Sent$ Cmem7nd CTuaMax-02,CTAAAM OS, 7KM d IKMS Series ... PEAK Energy Si 17 Series 16 TeaxMex-04.CIeca7K II-04 r' . F.rple/KMaaeM Ned$aloe Ppver Co.. 014604P SC�es PFA(Energy 72 Series I]rM,i DH.6UM IKMaurM-77HL-Y _... _ __... _._ .... Ky01RA KIISenea DRAWING BY: PLOT DATE: PROJECT NUMBER: SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.15(1-Jul-2022)Mandatory ED 16.3.15(1-J01-2022)Mandatory ____ s S Report No. 102393982LAX-002 Page 44 of 138 Issued: 11-Apr-2016 Unirac, Inc Revised: 5-Oct-2022 BLUE RAVEN 17.0 Illustrations n, r; Illustration lb-Approved PV Modules Continue 1403 N.Research Way Orem,UT 84097 Manufacture Module Model/Series Msrtlutatwn Mad le Mop9/Spies 800.377.4480 WWW.BLUERAVENSOLAR.COM M3nPra4 Snit—, A`xri r,A4-00-EILX,SPIta-tAX3-XXX'R. CONFIDENTIAL THE INFORMATION SunYtmM hwnPeak 2 Series X"4Per•, C Serles d P-Scent HEREIN CONTAINED SHALL NOT BE Tw rak lnP 7 01.117 Seder Solemn St h S iPsres•860 rtnee USED FOR THE BENEFIT OF ANYONE GUaf-y EXCEPT BLUE RAVEN twrmRvi 2 71 _ SHALL IT BE DISCLOSE SOLAR WHOLE OR Tatman-. TPS77 Tt'39b.1'PbS4.1P6E0. IN PART TO OTHERS OUTSIDE Twinibax 15erles 1s4mrV 7l>b12,N,po Msrn+rt RECIPIENTS ORGANIZATION,EXCEPT TP41B1arat SC.SC B.S(81.SC 82 IN CONNECTION WITH THE SALE AND RirreWt> V11nn7 Swirl,A156 Sees Teruel, T�xxH.tRxx5 USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION Risen RSM 72"6 1MDG)(M).R9440 6 r'Ae1,roe:.LIDOS,eC 04 D004,►[Q4, OF BLUE RAVEN SOLAR LLC. SE&Solar SEG-xxa-U40-NV Trim P014.PC14.0D14.DEo9A5,DE14.Ot1S, / 5-Ineras, SN77 R 5N60 Serves NOnun1 . Pf1111 //�V, SerdPlNm SEC 6 d SO,6Sent-✓. � up4.1..N.tn- (NABCEI 111rsdAio 11PMxn>rMTB) sh., Ntl SA X Nu-SC.Series CERTIFIED STA,SIC,l c Stews 6 Stltxx{BLorte&W71412 D]MvntHi7A,Lr71MII( HM suao Me/eocJnu:TL 7 IJRE fAtias 4CBSait8G1.FAMawart7G-Oe PV INSTALLATION tinlamn usA Sr-1ht,•X3-ArAtho7'DN eAmA=A 8cT-8N PROFESSIONAL . ... _._�.____. _.._...PunrrX1 nuR-l4C/PC iID) EI4ea. ScottHPV-0 Gurney Sntarur Pon,rXi-sss{-PD 015866 Poste XT xaAR-PM(AC) Sanera CONTRACTOR: sAAAA tly/t nowt wairee AC 6 lwrra StcrtY Sala'Mwia vm,s„rQ lV`�T A WSPSa.rrwt BRS FIELD OPS ivrnvw9ul3 Ptm .. .. 385-498-6700 SSM-160 to 1901oreel Teasel .Gt 5.3U4 WINOS Ss-14-5,90 W sop Sirisr, 7N Steno FxM677,75046.104144.t66-7094 Soo* SS-M-4481e 410 5tee3, SS-M-410 to 460&Facial Sales. 557SE1-765 Santntsps '. f-Ser1es,R-Stow L 14,0(FXS Sews Sonar* MY Series 3 Ootmtin Seder 1 DRAWING BY. PLOT DATE: PROJECT NUMBER. SHEET NAME: SPEC SHEET REVISION: PAGE NUMBER: ED 16.3.le(1-Jul-2022)Mandatory ____ S S