Permit Support Document COMcheck Software Version COMcheckWeb
init
11 Mechanical Compliance Certificate
Project Information 4 Y ►'C ,
Energy Code: 90.1 (2019) Standard 9 ,;
Project Title: Safeway Tigard # 1478 TI
Location: Tigard, Oregon :VfY'OF.1iGArit)
K
Climate Zone: 4c M DING DF''Pr9ON
Project Type: Addition
/ c2o/2- 0i137
Construction Site: Owner/Agent: Designer/Contractor:
15570 SW Pacific Hwy Oregon Louis Leon
Tigard,Oregon 97224 Protemp Associates Inc
9788 SE 17th Ave
Portland, Oregon 97222
5035193083
louis@protmp.com
Mechanical Systems List
QuantitySystem Type & Description
1 HVAC System (Single Zone):
Split System Heat Pump
Heating Mode: Capacity= 22 kBtu/h, ���
Proposed Efficiency= 11.80 HSPF, Required Efficiency=8.20 HSPF �,��
Cooling Mode: Capacity= 22 kBtu/h, OF
Proposed Efficiency= 20.00 SEER, Required Efficiency= 14.00 SEER
Proposed Part Load Efficiency=0.00 , Required Part Load Efficiency=0.00
Fan System: FAN SYSTEM 1--Compliance(Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply. Single-Zone VAV, 2235 CFM, 1.5 motor nameplate hp, 1.00 fan energy index
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 90.1 (2019) Standard requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
ZIP
‘717
_J-,,,, .>"" ......---- /___4.4L____
a e-Title Signature Date
Project Title: Safeway Tigard # 1478 TI Report date: 12/06/22
Data filename: Page 1 of 9
ritCOMcheck Software Version COMcheckWeb
If
Inspection Checklist
Energy Code: 90.1 (2019) Standard
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement,the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
4.2.2, Plans, specifications, and/or ❑Complies Requirement will be met.
6.4.4.2.1, calculations provide all information ❑Does Not
6.7.2 ,with which compliance can be
[PR2]1 determined for the mechanical DNot Observable
systems and equipment and ❑Not Applicable i
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
4.2.2, Plans, specifications,and/or ❑Complies '
8.4.1.1, calculations provide all information '❑Does Not
8.4.1.2, with which compliance can be
8.7 determined for the electrical systems :❑Not Observable
[PR6]2 and equipment and document where :❑Not Applicable
exceptions are claimed.Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
4.2.5.2 Commissioning shall be performed as ❑Complies Requirement will be met.
(PR5]1 stated in Sections 5.9.2,6.9.2,7.9.2, ;❑Does Not
8.9.2, 9.9.2, 10.9.2, 11.2(d),and
G1.2.1(c).Commissioning must utilize ❑Not Observable
ASHRAE/IES Standard 202 or other Observable_
Applicable
generally accepted engineering
standards acceptable to the building
official. FPT and verification
requirements for commissioning are
as stated in Section 4.2.5.1.
Commissioning shall document
compliance of the building systems,
controls, and building envelope with
required provisions of this standard.
Commissioning requirements shall be
incorporated into the construction
documents.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Safeway Tigard # 1478 TI Report date: 12/06/22
Data filename: Page 2 of 9
Section Mechanical Rough-In I Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
& Req,ID
6.4.1.4, HVAC equipment efficiency Efficiency:_ Efficiency: ;❑Complies See the Mechanical Systems list
6.4.1.5 verified. Non-NAECA HVAC j❑Does Not for values.
[ME1]2 equipment labeled as meeting
90.1. :❑Not Observable I
❑Not Applicable
6.4.3.4.1 Stair and elevator shaft vents ❑Complies Exception: Requirement
[ME3]3 have motorized dampers that ❑Does Not does not apply.
automatically close.
❑Not Observable I
❑Not Applicable :
6.4.3.4.2, Outdoor air and exhaust systems ❑Complies I Requirement will be met.
6.4.3.4.3 have motorized dampers that ❑Does Not
[ME4]3 automatically shut when not in
use and meet maximum leakage ❑Not Observable
rates. Check gravity dampers ❑Not Applicable
where allowed.
6.4.3.4.5 Enclosed parking garage ❑Complies Exception: Requirement
[ME39]3 ventilation has automatic ❑Does Not does not apply.
contaminant detection and
capacity to stage or modulate [Not Observable
fans to 50%or less of design ❑Not Applicable j
capacity.
6.4.3.4.4 Ventilation fans>0.75 hp have ❑Complies Requirement will be met.
[ME5]3 automatic controls to shut off fan ❑Does Not
when not required.
g? ❑Not Observable
❑Not Applicable
6.4.3.8 Demand control ventilation ❑Complies ;Requirement will be met.
[ME6]1 provided for spaces >500 ft2 and ❑Does Not
>25 people/1000 ft2 occupant
density and served by systems Not Observable
with air side economizer, auto ❑Not Applicable
;modulating outside air damper
;control, or design airflow>3,000 :ivc -.,s
I ]cfm.
6.5.3.2.1 DX cooling systems>= 75 kBtu/h ❑Complies ;Requirement will be met.
[ME40]2 (>= 65 kBtu/h effective 1/2016) ❑Does Not
and chilled-water and See the Mechanical Systems list
evaporative cooling fan motor hp ❑Not Observable 'for values.
>= 1/4 designed to vary supply ❑Not Applicable
fan airflow as a function of load ,
and comply with operational
requirements.
6.4.4.1.1 Insulation exposed to weather ❑Complies Requirement will be met.
[ME7]3 protected from damage. ❑Does Not
Insulation outside of the
conditioned space and associated ['Not Observable
with cooling systems is vapor ❑Not Applicable
retardant. ,
6.4.4.1.2 HVAC ducts and plenums ; R- R-_ OComplies Requirement will be met.
[ME8]V insulated per Table 6.8.2.Where ❑Does Not
ducts or plenums are installed in :
or under a slab,verification may ❑Not Observable
need to occur during Foundation ❑Not Applicable
Inspection.
6.4.4.1.3 HVAC piping insulation thickness. : _in. _in. ;❑Complies Requirement will be met.
[ME9]2 Where piping is installed in or ❑Does Not
under a slab,verification may
need to occur during Foundation ['Not Observable
Inspection. ❑Not Applicable
6.4.4.1.4 Thermally ineffective panel ❑Complies Requirement will be met.
[ME41]3 surfaces of sensible heating ❑Does Not
panels have insulation>= R-3.5.
❑Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Safeway Tigard # 1478 TI Report date: 12/06/22
Data filename: Page 4 of 9
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
& Req.ID
6.4.4.2.1 :Ducts and plenums having ❑Complies Exception: Requirement
[ME10]2 pressure class ratings are Seal ❑Does Not does not apply.
Class A construction.
❑Not Observable
DNot Applicable
6.8.1-15, Electrically operated DX-DOAS ❑Complies ,Exception: Requirement
6.8.1-16 units meet requirements per ❑Does Not does not apply.
[ME110]2 Tables 6.8.1-15 or 6.8.1-16.
DNot Observable
DNot Applicable
6.4.4.2.2 Ductwork operating >3 in.water ❑Complies Requirement will be met.
[ME11]3 column requires air leakage ❑Does Not
testing. ❑Not Observable
DNot Applicable
6.5.2.3 !Dehumidification controls ❑Complies Requirement will be met.
[ME19]3 provided to prevent reheating, ❑Does Not
recooling,mixing of hot and cold
airstreams or concurrent heating ['Not Observable
and cooling of the same ONot Applicable
airstream.
6.5.2.4.1 Humidifiers with airstream ❑Complies ;Requirement will be met.
[ME68]3 mounted preheating jackets have ❑Does Not
preheat auto-shutoff value set to
activate when humidification is ❑Not Observable
not required. ❑Not Applicable
6.5.2.4.2 Humidification system dispersion ❑Complies Requirement will be met.
[ME69]3 tube hot surfaces in the ❑Does Not
airstreams of ducts or air-
handling units insulated >= R- DNot Observable
0.5. ❑Not Applicable
6.5.2.5 Preheat coils controlled to stop ❑Complies Requirement will be met.
[ME70]3 heat output whenever ❑Does Not
mechanical cooling, including
economizer operation, is active. ❑Not Observable
ElNot Applicable
6.5.2.6 Units that provide ventilation air ❑Complies Requirement will be met.
[ME106]3 to multiple zones and operate in ❑Does Not
conjunction with zone heating
and cooling systems are ❑Not Observable
prevented from using heating or :Not Applicable
heat recovery to warm supply air
above 60°F when representative
building loads or outdoor air
temperature indicate that most
zones demand cooling.
6.5.3.6 Motors for fans>= 1/12 hp and ❑Complies Requirement will be met.
[ME72]2 < 1 hp are electronically- ❑Does Not
commutated motors or have a
minimum motor efficiency of ['Not Observable
70%.These motors are also ❑Nat Applicable
speed adjustable for either
balancing or remote control.
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Safeway Tigard# 1478 TI Report date: 12/06/22
Data filename: Page 5 of 9
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
& Req.ID
6.5.3.4 Parallel-flow fan-powered VAV air ❑Complies Requirement will be met.
[ME108]2 terminals have automatic ❑Does Not
controls to a)turn off the
terminal fan except when space Not Observable
heating is required or if required ElNot Applicable
for ventilation; b)turn on the
terminal fan as the first stage of
heating before the heating coil is
activated; and c)during heating
for warmup or setback
temperature control, either
operate the terminal fan and
heating coil without primary air
or reverse the terminal damper
logic and provide heating from
the central air handler through
primary air.
6.5.3.7 Required minimum outdoor air ❑Complies Requirement will be met.
[ME109]2 rate is the larger of minimum ❑Does Not
outdoor air rate or minimum
exhaust air rate required by ['Not Observable
Standard 62.1, Standard 170,or ❑Not Applicable
applicable codes or accreditation
standards.Outdoor air ventilation
systems shall comply with one of
the following: a)design minimum
system outdoor air provided <
135%of the required minimum
outdoor air rate, b) dampers,
ductwork, and controls allow the
system to supply<=the
required minimum outdoor air
rate with a single set-point
adjustment., or c)system
includes exhaust air energy
recovery complying with Section
6.5.6.1.
6.5.3.3 Multiple zone VAV systems with ❑Complies Exception: Requirement
[ME42]3 DDC of individual zone boxes ❑Does Not does not apply.
have static pressure setpoint
reset controls. ❑Not Observable See the Mechanical Systems list
❑Not Applicable for values.
6.5.4.2 HVAC pumping systems with >= ❑Complies Requirement will be met.
[ME25]3 3 control values designed for ❑Does Not
variable fluid flow(see section
details). ENot Observable
❑Not Applicable
6.5.6.1.1 Exhaust Air Energy Recovery for ❑Complies Requirement will be met.
[ME56]1 Nontransient Dwelling Units ❑Does Not
ENot Observable
❑Not Applicable
6.5.6.1.2 Exhaust air energy recovery for ❑Complies Requirement will be met.
[ME111]1 spaces other than Nontransient ❑Does Not
;dwelling units meeting Tables
.6.5.6.1.2-1, and 6.5.6.1.2-2. ENot Observable
ENot Applicable
6.5.7.2.1 Kitchen hoods>5,000 cfm have ❑Complies Exception: Requirement
[ME32]2 make up air>=50%of exhaust ❑Does Not does not apply.
air volume.
❑Not Observable i
ENot Applicable
1 High Impact(Tier 1) j j Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Safeway Tigard# 1478 TI Report date: 12/06/22
Data filename: Page 6 of 9
Section Mechanical Rough-In Plans Verified Field Verified
Complies? Comments/Assumptions
& Req.ID Inspection Value Value
6.5.7.1 :Conditioned supply air to space ❑Complies Requirement will be met.
[ME100]2 ;with mechanical exhaust<=the ❑Does Not
greater of criteria of supply flow,
required ventilation rate, exhaust ❑Not Observable
flow minu the available transffer ❑Not Applicable
air(see section details).
6.5.3.8 Occupied standy controls for ❑Complies Requirement will be met.
[ME112]' zones serving rooms that are ❑Does Not
required to have automatic
partial OFF or automatic full OFF ['Not Observable
lighting controls per Section ❑Not Applicable
9.4.1.1 shall meet the following
within five minutes of all rooms in
;that zone entering occupied-
standby mode: a)Active heating
set point shall be setback at least
1°F, b)Active cooling set point
shall be setup at least 1°F and
c)All airflow supplied to the zone
shall be shut off whenever the
'space temperature is between
the active heating and cooling
set points.
6.5.7.2.4 Approved field test used to ❑Complies Requirement will be met.
[ME49]3 evaluate design air flow rates Does Not
and demonstrate proper capture
.and containment of kitchen ❑Not Observable
exhaust systems. ❑Not Applicable
6.5.8.1 "'Unenclosed spaces that are ❑Complies Requirement will be met.
[ME34]2 heated use only radiant heat. ElDoes Not
['Not Observable
ElNot Applicable
6.4.3.9 Heating for vestibules and air ElComplies Requirement will be met.
[ME63]2 curtains with integral heating ❑Does Not
include automatic controls that
shut off the heating system when ['Not Observable
outdoor air temperatures>45F. ❑Not Applicable
Vestibule heating and cooling
systems controlled by a
thermostat in the vestibule with
heating setpoint<= 60F and
cooling setpoint>=80F.
6.5.10 Doors separating conditioned ❑Complies Requirement will be met.
[ME73]3 space from the outdoors have ❑Does Not
controls that disable/reset
heating and cooling system when ❑Not Observable
open. ❑Not Applicable
Additional Comments/Assumptions:
11 High Impact(Tier 1) :` ;4Medium Impact(Tier 2) j 3 Low Impact(Tier 3)
Project Title: Safeway Tigard # 1478 TI Report date: 12/06/22
Data filename: Page 7 of 9
. Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
8.4.2 At least 50%of all 125 volt 15-and ❑Complies
[EL10]2 20-Amp receptacles are controlled by ❑Does Not
an automatic control device.
❑Not Observable
❑Not Applicable
8.4.3 New buildings have electrical energy '❑Complies
[EL11]2 use measurement devices installed. ,ODoes Not
Where tenant spaces exist, each
[tenant is monitored separately. In ❑Not Observable
buildings with a digital control system ❑Not Applicable
the energy use is transmitted to to
control system and displayed
graphically.
10.4.1 Electric motors meet requirements .❑Complies Requirement will be met.
[EL9]2 where applicable. ❑Does Not
:Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) . Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Safeway Tigard # 1478 TI Report date: 12/06/22
Data filename: Page 8 of 9
Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
6.4.3.1.2 Thermostatic controls have a 5 °F I❑Complies Requirement will be met.
(FI3j3 deadband. j❑Does Not
i❑Not Observable I
❑Not Applicable
6.4.3.2 'Temperature controls have setpoint ,❑Complies Requirement will be met.
[F12013 'overlap restrictions. ❑Does Not
❑Not Observable
j❑Not Applicable
6.4.3.3.1 HVAC systems equipped with at least ❑Complies Requirement will be met.
[F121]3 one automatic shutdown control. '❑Does Not
❑Not Observable
❑Not Applicable
6.4.3.3.2 ;Setback controls allow automatic I❑Complies Requirement will be met.
[FI22j3 `restart and temporary operation as ❑Does Not
required for maintenance.
❑Not Observable
❑Not Applicable
6.4.3.5 Heat pump controls prevent '❑Complies Requirement will be met.
[F15]3 supplemental electric resistance heat iODoes Not
from coming on when not needed. ❑Not Observable
❑Not Applicable
6.4.3.6 When humidification and ❑Complies Requirement will be met.
[FI6]3 dehumidification are provided to a ❑Does Not
zone, simultaneous operation is
prohibited. Humidity control prohibits ONot Observable
the use of fossil fuel or electricity to ❑Not Applicable
produce RH > 30%in the warmest
zone humidified and RH < 60%in the
coldest zone dehumidified.
6.7.2.1 ,Furnished HVAC as-built drawings ❑Complies Requirement will be met.
[FI713 submitted within 90 days of system ❑Does Not
'acceptance.
:Not Observable
❑Not Applicable
6.7.2.2 'Furnished O&M manuals for HVAC ❑Complies Requirement will be met.
[FI8]3 systems within 90 days of system ❑Does Not
acceptance.
❑Not Observable'
❑Not Applicable !.
6.7.2.3 An air and/or hydronic system ❑Complies Requirement will be met.
[FI9]1 balancing report is provided for HVAC ❑Does Not
systems serving zones>5,000 ft2 of ❑Not Observable
conditioned area.
j❑Not Applicable
10.4.3 Elevators are designed with the ;❑Complies ,Exception: Requirement does not apply.
[F12412 proper lighting, ventilation power, and ❑Does Not
standby mode.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact(Tier 2) .3''Low Impact(Tier 3)
Project Title: Safeway Tigard# 1478 TI Report date: 12/06/22
Data filename: Page 9 of 9