Loading...
Specifications F. A SPECIAL PRECAUTIONS For All Schier Grease Interceptor Installations- Failure to follow this guidance voids your warranty Installation Instructions installation High Temperature Kitchen Water Installation instructions and additional instructions If water is entering the interceptor at excessive temperature(over140 F),a components are included with the inside drain water tempering valve(DIV)and approved backf low prevention assembly interceptor.Read all:instructions prior must be installed.Most state and local plumbing codes prohibit water above Eo installation.This interceptor is 140 F being discharged into the sanitary sewer.Water above 140 F will weaken intended to be installed by a licensed or deform PVC Schedule 40 pipe,poly drainage fixtures like interceptors and plumber in conformance with all erode the coating of cast iron(leading to eventual failure). local codes, --� When Installing Interceptor Inside cold water supply line high temperature effluent(>140 F) If your dishwashing approved backflow prevention assembly sinks)discharges �a a ;.f' DTV(drain water tempering valve) sink(nto a flain(ddrrain), • sink(drain),you \ j flow into the drain ' �I �,-- to avoid an overflow T MI — must regulate the �, of water onto the I Alm 1 1 1 1 �In[I t e> cr kitchen floor.This Fernco or similar v Intercept or E can be done by rubber flow I 1 I 1 installing a valve or restriction end cap flow restriction cap on the sink piping that discharges into the drain.See drawing above for guidance.For detailed guidance on indirect connections,go to: http//webtools.schierproducts.com/TechnicaLData/Indirect_Connections.pdf directly connected indirectly connected Flush-to-Grade Burials Fully Support Flush-to-Grade buried installations p `� concrete floor (without a riser)are not recommended h ! Base of Unit 1 1 _ ? for heavy foot traffic areas without the .• Install unit on solid,level surface in r P use of an internal support system contact with the entire footprint of iInrercep'nrl�— (sold additionally). """""' unit base;for suspended installations design trapeze to support the wet weight of the unit.Do not partially support unit or suspend unit using metal U-channel to create a trapeze suspended installation Support Inlet and r—pipe supports Outlet Piping � For above grade installations ensureIrttercepcor1 heavy inlet and outlet piping(such as I 1 1 I cast iron or long runs)is properly supported or suspended during the entire installation process to prevent connection failure or damage to bulkhead fittings. rSCHIE. MODEL NUMBER: DESCRIPTION:50/75GPct Polyethylene Grease Interceptor GBS :� LIFETIME GUARANTEED PART s:4070A01-03 DWG BY:B.Kemer DATE 9/1V2018 REV: MO:C"J. GREASE INTERCEPTORS 9500 Woodend Road Edwardsville,KS 66111 Te1:913-961-3300 www.schierproducts.com ,Copyright 2018 Schier,All Rights Reserved SPECIFICATION 37' i Outlet'A'(Optional) rto✓✓ a v v v v v v v v o v - v v v v� Notes o00000000aoo 000o Shown with 000000000 > a0000000 � -a0000 1. 4'FPT inlet/outlet with 3'and 4'plain end fittings. 0 0 00a 0000® - ►Civ:�i,_oaoa000° optional pumpout 2. Unit weight-69 lbs.(wet weight 404 lbs.) o O o 0 o c ,I 1 -1i o 0 0 o port kit S. Capacities Liquid:40 gal. ooa000a000v ,;i oc 0000a 050 GPM-Grease:2721bs.(37.2 gal.) os.o°O°o°_ ��f f� 0000 0\0 @75 GPM-Grease:175lbs.(17.4 gal.) A 1 \ IIrlj A Soilt-in.9gal. 1 .• Ilia! +�I -1 4. Built-in flow control. 28' 5. For gravity drainage applications only. OEI 0 11V\ 6. Do not use for pressure applications. Inlet ' IH` ��t�ti�ji 7. Cover placement allows full access to tank for O o O O rr Ir 1 1 - p p'p'p Outlet"B' proper maintenance. O000vO00o0 i I `'oa ate (Standard} 000000 • a0000 8. Vent not required unless per local code. o 0 0 0 0♦ p 0 0 0 0000000 ° 000 8. Engineered inlet and outlet diffusers are removable O o 0 0 0 0 0 =� ?` ' Outlet foot 00000000. -.-, . to inspect/clean liepiping./ o00000000000o000000`a', �00000000o must face this 10.Integralairrelief/anti-siphon. \� J direction in all Engineer Specification Guide Outlet'C'(Optional) I- 13' I configurations Schier Great Basin"'grease interceptor model *GB3 TOP VIEW shall be lifetime guaranteed and made in USA of seamless,rotationally-molded polyethylene.Interceptor shall be furnished for above or below grade installation. Interceptor shall be certified to ASME A112.14.3(type C) q of plainend 0 21-t/2"Cover and CSA B481.1,with field cut riser system,built-in flow inlet and outlet - See Note a10 control,built-in test caps and three outlet options. Interceptor flow rate shall be 50 or 75 GPM. =1.11 -- ' assir;c: Interceptor grease capacity shall be 272lbs.@ 50 GPM 6" ,I- - ! ,,, �f G!� or 175 lbs.@ 75 GPM.Cover shall provide water/gas-tight 1 I I __ ii ____ Iill I seal and have minimum 450 lbs.load capacity. Certified Performance 21" I •_ ::-.'... - - Elrn . 7 - Great Basin"'hydromechanical grease interceptors are third :-.. party performance-tested and listed by IAPMO to ASME 15" �. *A112.14.3 and CSA 8481.1 grease interceptor standards and a' 13'Invert greatly exceed requirements for grease separation and 1-i' storage.They are compliant to the Uniform Plumbing Code, IL. the National Standard Plumbing Code,the National Plumbing _!�`` . i‘as„Code of Canada and the International Plumbing Code. _- 1131111, ngineered inlet Static water and outlet diffuser line c SECTION A-A I 28' I I I Q I I 1 1 E OUTLET END VIEW rti SC H I ER MODEL NUMBER: GB3 DESCRIPTION:50/75 GPM Polyethylene Grease Interceptor LIFETIME GUARANTEED .C.,t. l GREASE INTERCEPTORS PART*:4070-001-03 DWG BY:B.Karrer DATE:9/11/2018 REV: ECO: 9500 Woodend Road Edwardsville,KS 6u111 ICI:913-951-3300 wwwschicrproducts.eom nCOpyright201a Schier,AiIRiyhts Reserved FCR1 Specification field cut riser system For Use with Grease Interceptors Models GB1, GB2 and GB3 C� 0 25-8/4- 0 21-7/8" 1.1/ f 12"Max Extension 12-8/4" Overall 0 21-1/2" Notes 1. Rotationally molded polyethylene body 2. Injection molded polypropylene top cover ring j 3. EPDM sponge tank-to-riser gasket i 4. Silicone fin riser body to riser top gasket t r 5. Unit weight:10 lbs. t j 6. Risers not designed to hold water I I 2.1/8'Min Engineer Specification Guide: Extension Field-cut adjustable riser system to consist of rotationally molded polyethylene body,injection molded polypropylene top cover ring, EPDM sponge gasket at bottom,silicone fin gasket at top flange. Risers shall allow field adjustability of cover to grade. Installation Note Minimum install height:2-1/8'.Maximum install height:12'. Riser system may be stacked no more than two units high to a maximum of 25'extension.Access to internal components will not be compromised. riSCH 1 E R MODEL NUMBER: DESCRIPTION:12"Field Cut Riser Extension System L""+bLIFETIME GUARANTEEDt. FCRI GREASE INTERCEPTORS PART#:8010-005-01 DWG BY:B.Karrer DATE5/4/2017 REV: ECO: 9500Woodend Road Edwardsville.KS.GG1I1 i Tel'913-751-33OG;vdwwsehierpe»ducts.corn C>Copyright 2017Schior.AI1Rights Reserved . . . ASPECIAL PRECAUTIONS For All Schier Grease Interceptor Installations - Failure to follow this guidance voids your warranty Installation Instructions installation High Temperature Kitchen Water Installation instructions and additional instructions If water is entering the interceptor at excessive temperature(over140 F),a components are included with the inside drain water tempering valve(DIV)and approved backflow prevention assembly interceptor.Read all instructions prior must be installed.Most state and local plumbing codes prohibit water above to installation.This interceptor is 140 F being discharged into the sanitary sewer.Water above 140 F Will weaken intended to be installed by a licensed or deform PVC Schedule 40 pipe.poly drainage fixtures like interceptors and plumber in conformance with all erode the coating of cast iron(leading to eventual failure). local codes. cold water supply line When Installing Interceptor Inside high temperature effluent(›140 F) If your dishwashing approved backfbw prevention assembly sink(s)discharges IX '\` DTV(drain water tempering valve) into a floor drain/ l 1J sink drain),you • t must regulate the �.. flow into the drain '.._. to avoid an overflow — of water onto the )tote captor - u1 Interceptor kitchen floor.This Fernco or similar as:. II j el�— can be done by rubber flow installing a valve or restriction end cap r�� flow restriction cap ••"'1� on the sink piping that discharges into the drain.See drawing above for guidance.For detailed guidance on indirect connections,go to: http//webtools.schierproducts.com/fechnical_Data/Indirect_Connections.pdf directly connected indirectly connected Flush-to-Grade Burials Fully Support Flush-to-Grade buried installations F concrete floor (without a riser)are not recommended Y Base of UnitQ o for heavy foot traffic areas without the y,.,: Install unit on solid,level surface in — t ...pRt use of an internal support system contact with the entire footprint of !Ir iercept�r�— (sold additionally). " """"" """"" unit base;for suspended installations „ D design trapeze to support the wet weight of the unit.Do not partially support unit or suspend unit using metal U-channel to create a trapeze suspended installation Support Inlet and . pipe supports Outlet Piping For above grade installations ensure iInn orri III heavy inlet and outlet piping(such as 11I cast iron or long runs)is properly supported or suspended during the entire installation process to prevent connection failure or damage to bulkhead fittings. fIrlit. MODEL SC H I E R FCR1 NUMBER: DESCRIPTION:12'Field Cut Riser Extension System A .„ LIFETIME GUARANTEED C",t. GREASE INTERCEPTORS pARTe:8o10-0o&ul DWG BY:B,Kamer DATE:5/4/2017 REV: ECO: 9500 Woodend Road Edwardsville,KS 66111 -Tel:913.951.3300 wwwschierproducts.com o Copyright 2017 Senior,All Rights Roserued