July 20, 2022
Subject: Proposed Solar Panel Installation
Marshall Clark Residence, 11630 SW Lomita Ave,Tigard,OR
To Whom it May Concern,
Our engineering department has reviewed information,gathered by our field crews, related to the proposed solar
panel installation at the above-referenced address. The purpose of our review was to determine the structural
adequacy of the existing roof. Based on our review and analysis of the available information, and in accordance
with governing building codes, it is our professional opinion that the existing structure is permitted to remain
unaltered for the proposed solar installation.
Design Parameter Summary
Governing Building Code:2019 Oregon Structural Specialty Code (2019 OSSC)
Risk Category: II
Design Wind Speed: 110 mph (per ASCE 7-16)
Ground Snow Load: 11 psf
Roof Information
Roof Structure:2x4 Manufactured Trusses @ 24"O.C.
Roofing Material:Asphalt Shingles(1 layer)
Roof Slope:23 degrees
Roof Connection Details
RT Minis into 2x rafters or truss top chords at 48"O.C., install per design drawings and manufacturer specs
Locations per design drawings
Note:Required embedment length excludes the tapered tip of the screw,and embedment into sheathing.
Analysis
The proposed installation -including weight of panels, racking, and mounts -will be approximately 2.62 psf. In the
areas where panels are installed, roof live loads will not be present.The reduction of roof live load is adequate to
fully or partially compensate for the addition of the panel installation. Because the member forces in the area of
the solar panels are not increased by more than 5%, the stresses in the members are not increased by more than
5%,and so per section 3408.6.2 of the 2019 OSSC(IEBC Section 806.2),the structure need not be altered for gravity
loading.
The proposed installation will be 6" max. above the roof surface (flush mounted) and parallel to the roof surface.
Therefore, any increase in wind loading on the building structure from the solar panel installation is expected to be
negligible. Wind is the governing lateral load case. Because the increase in lateral loading is not increased by more
than 10%,per section 3408.6.3 of the OSSC(IEBC 806.3),the structure need not be altered for lateral loading.
Wind uplift on the panels has been calculated in accordance with the relevant provisions of ASCE 7-16.This loading
has been used to verify the adequacy of the connection specified above. Connection locations should be in
accordance with design drawings.
Conclusion
The roof structure need not be altered for either gravity or lateral loading. Therefore, the existing structure is
permitted to remain unaltered. Connections to the roof must be made per the "Roof Connection Details" section
above. Copies of all relevant calculations are enclosed.
Limitations and Disclaimers
The opinion expressed in this letter is made in reliance on the following assumptions: the existing structure is in
good condition; the existing structure is free from defects in design or workmanship;and the existing structure was
code-compliant at the time of its design and construction. These assumptions have not been independently
verified, and we have relied on representations made by the property owner and his or her agents with respect to
the foregoing.The undersigned has not inspected the structure for patent or latent defects.
Electrical engineering is beyond the scope of this analysis. Solar panels must be installed per manufacturer
specifications. Structural design and analysis of the adequacy of solar panels, racks, mounts, rails, and other
components is performed by each component's respective manufacturer and the undersigned makes no statement
of opinion regarding such components. This letter and the opinions expressed herein are rendered solely for the
benefit of the permitting authority(city or county building department), and may not be utilized or relied on by any
other party.
If you have any questions or concerns, please contact our office at (855)-709-1181, or email me directly at
Trevor.Jones@solgenpower.com.
Sincerely,
Trevor A.Jones, P.E.
iR6,a PROP(
�i}> ss
;p4'OR Dv.
EXPIRES: 06/30/23
7/20/2022
RECE#VI._
DEC 0 ) ;.?C':''?
1 CITY OF TIC,,r t
S O L G N BUILDING DIVISION
pow ER Note: All calculations per ASCE 7
Load Comparison
This calculation justifies the additional solar load by comparing existing to proposed gravity loads
in the location of the solar panels.
Without Solar With Solar
Dead Load
Asphalt Shingles 3 3 psf
1/2" Plywood 1 1 psf
Framing 3 3 psf
Insulation 1 1 psf
1/2" Gypsum Ceiling 2 2 psf
M,E, & Misc 1.5 1.5 psf
Solar Panel 0 2.62 psf
Total Dead Load 11.5 14.12 psf
Snow Load
Ground Snow Load, Ps 11 psf
Exposure Factor, Ce 1
Thermal Factor, Ct 1.1
Importance Factor, IS 1
Flat Roof Snow Load _ Eqn. 7.3-1 or jurisdiction min.
Slope 23 degrees
Unobstructed Slippery Surface?
Slope Factor, CS 1.00 1.00
Sloped Roof Snow Load 8.5 8.5 psf
Live Load
Roof Live Load 20 0 psf
Load Combination
D+ Lr 31.5 14.1 psf
D + S 20.0 22.6 psf
Max. Load 31.5 22.6 psf
%of original 72%
Result: Because the total forces are decreased, per the relevant code
provisions stated in the body of the letter, the existing roof
structure is permitted to remain unaltered.
1 SOLGEN
POWER
RT Mini Connection Calculation
This calculation justifies the connection of the solar panels to existing roof members, by showing the connection
capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail in 1/2 panel length
Spacing parallel to rail in Max spacing
Effective Wind Area on each connection 10.8 ft`
Roof Angle 23 degrees sw R / -
Wind Speed 110 mph I.FOOT
Exposure Coefficient, lc = /11o�
Topographic Factor, Kip 1 ROOMINI 1
F nem
-y,., . NO
Directionality Factor, Kd 0.85 >rNO
Elevation Factor, Ke 0.99 `,
Velocity Pressure,qz 22.2 psf
Mu exIsdr tl mol et�.NYq -'--'�^ /
Mo erlstlry ref0.2
Zone 1 Zone 2r Zone 3
GCp(max) 1.90 1.97 1.97
Exposed Panels?(yE=1.5)
Pressure Equalization Factor,ya 0.79 0.79 0.79
Uplift Force 33.1 34.5 34.5 psf
Max. Uplift Force/Connection(1.0 WL) 358.7 373.2 373.2 lbs
ASD Factored(0.6 WL) 215.2 223.9 223.9 lbs
Solar Dead Load(0.6 DL) 17.0 17.0 17.0 lbs
Max. Uplift Force(0.6 WL-0.6 DL) 198.2 206.9 206.9 lbs
Connection Capacity
Connection Type RT Mini into 2x Rafter
Total Allowable Capacity 447.0 lbs (per manufacturer)
Compare ASD Factored Demand to Capacity
Demand 206.9 lbs
Capacity 447.0 lbs
Result Capacity exceeds demands.Therefore,connection passes.