2010 Oregon Solar Installation Specialty Code
Check List for Prescriptive Installation of Roof-Mounted
PhotoVoltaic Solar Panel System
Property Information
Installation Address: 11774 SW 125th Ct
City: Tigard,OR Zip: 97223
Owner's Name: Chris Garsteck Date: 10/6/2022
Contractor's Name: A&R SOLAR CCB #: 207641
Design Parameters of the Property/Structure
If"Yes", does not
Flood Hazard Is the installation Yes qualify for the
Area Located in a flood prescriptive path, follow
plain/flood way? ❑� No OSSC or ORSC for
design requirements.
Wind Exposure Is the wind exposure Yes If"Yes",qualifies for
"C"or less? ❑ No the prescriptive path.
Installations on detached Is the Ground Snow
single/two-family Load 70 psf or less?
dwelling/single/two- If"Yes",qualifies for
family townhomes ❑✓ Yes the prescriptive path.
and/or their accessory
Ground structures. ❑ No
Snow Load Is the Ground Snow
Installations on all Load 50 psf or less?
If"Yes", qualifies for
structures other than
❑ Yes the prescriptive path.
above
❑ No
1
I:Building/Forms/Ph oto V oltaic-Checklist02-0 I-11.docx
Is the construction
material wood and does ✓❑ Yes
Type of If"Yes",qualifies for
the construction qualify
Construction No the prescriptive path.
as"conventional light ❑
frame"construction?
Is the spacing 24 inches
or less?
If"Yes", qualifies for
Pre-engineered trusses. d❑ Yes the prescriptive path.
❑ No
Roof framing
members Is the spacing 24 inches
or less?
Nominal lumber. If"Yes",qualifies for
❑✓ Yes the prescriptive path.
❑ No
Is the combined weight ✓❑ Yes
of the PV modules and If"Yes",qualifies for
racking less than or ❑ No the prescriptive path.
Solar equal to 4.5 psf?
installation Is the solar installation
layout in accordance ❑✓ Yes
with Section 305.4(3)of If"Yes",qualifies for
the 2010 Oregon Solar ❑ No the prescriptive path.
Code?
❑ Metal
Single layer If roofing material is
RoofingCheck the of wood
type of ❑ one of the three types
material roofing material shingle/shake checked,qualifies for
Max.two layers the prescriptive path.
E of composition
shingle.
Is the roof mounted ✓❑ Yes
Connections of solar assembly
If"Yes",qualifies for
the solar assembly connected to roof ❑ No the prescriptive path.
to the roof framing or blocking
directly?
2
I:/Build ing/Forms/Photo V oltaic-Checkli st02-01-11.docx
ti
❑ Yes If"Yes",qualifies for
Is the gauge 26 or less?
❑ No the prescriptive path.
115 lbs for 60 inch
spacing or less?
If"Yes",qualifies for
E Yes the prescriptive path.
❑ No
Minimum Uplift rating
of Clamps? 75 lbs for 48 inches
spacing or less?
If"Yes",qualifies for
❑ Yes the prescriptive path.
❑ No
Attachment of
roof mounted Minimum 24 inches If the spacing falls
solar systems Spacing of clamps? within 24 inches and 60
directly to inches Maximum 60 inches inches, qualifies for the
standing seam
prescriptive path.
metal panels Width of roofing If the width of the panel
panels? 18 inches or less is less than 18 inches,
inches qualifies for the
prescriptive path.
Minimum#10 at 24
inches o/c?
Size and spacing of If"Yes",qualifies for
fastener? ❑ Yes the prescriptive path.
❑ No
Is the roof decking of
WSP min. 'A"thickness, ❑ Yes
decking connected to If"Yes",qualifies for
framing members ❑ No the prescriptive path.
w/min. 8d nails @
6"/12"o/c?
Is the height less than or
Maximum 18 inches equal to 18 inches?
Height of the from the top of the If"Yes",qualifies for
Yes
solar modules module to the roof the prescriptive path.
surface. ❑ No
3
I:Building/Forms/PhotoVoltaic-Checklist02-01-11.docx
Submittal Documents required for Prescriptive Installations
Show the location of the PV system in relation to buildings, structures,
property lines, and,as applicable, flood hazard areas.
Site Plan Details must be clear and easy to read.
Minimum size of the plan is 8.5 x 11 inches.
Attach a simple structural plan showing the roof framing(rafter size,type,and
spacing)and PV module system racking attachment.
System must be shown in sufficient detail and clarity to assess whether it
Structural Plan meets the prescriptive construction requirements as listed earlier above in the
matrix.
Minimum size of the plan is 8.5 x 11 inches.
PV Modules
Manufacturer: Hanwha Q.Cells
Model Number: Q.peak DUO-BLK ML-G10+400
Listing Agency: UL 61730,CE-compliant,IEC 61215:2016,IEC 61730:2016
4
I:Building/Fo ms/PhotoVoltaic-Checklist02-01-11.docx
RECEIVED
OCT -6 202?
City of Tigard CITY OF HGA D
g St RIDING DIVISION
Building Division
13125 SW Hall Blvd,Tigard,OR 97223
Phone: 503.718.2439 Fax: 503.598.1960
T I G A R❑ Inspection Line: 503.639.4175
www.tigard-or.gov
2010 Oregon Solar Installation Specialty Code
Check List for Prescriptive Installation of Roof-Mounted
PhotoVoltaic Solar Panel System
Property Information
Installation Address: 11774 SW 125th Ct
City: Tigard,OR Zip: 97223
Owner's Name: Chris Garsteck Date: 10/6/2022
Contractor's Name: A&R SOLAR CCB #: 207641
Design Parameters of the Property/Structure
If"Yes", does not
Flood Hazard Is the installation ❑ Yes qualify for the
Area Located in a flood prescriptive path, follow
plain/flood way? ❑✓ No OSSC or ORSC for
design requirements.
Wind Exposure
Is the wind exposure Yes If"Yes",qualifies for
"C"or less? ❑ No the prescriptive path.
Installations on detached Is the Ground Snow
single/two-family Load 70 psf or less?
dwelling/single/two- If"Yes",qualifies for
family townhomes ❑ Yes the prescriptive path.
and/or their accessory
Ground structures. ❑ No
Snow Load Is the Ground Snow
Installations on all Load 50 psf or less?
structures other than If"Yes",qualifies for
❑ Yes the prescriptive path.
above
❑ No
1
I/Building/Fonns/PhotoVoltaic-Checklist02-01-11.docx
Is the construction
ID material wood and does Yes
Type of If"Yes",qualifies for
the construction qualify
Construction as"conventional light ElNo the prescriptive path.
frame"construction?
Is the spacing 24 inches
or less?
If"Yes",qualifies for
Pre-engineered trusses. ✓❑ Yes the prescriptive path.
❑ No
Roof framing
members Is the spacing 24 inches
or less?
If"Yes",qualifies for
Nominal lumber. ❑✓ Yes the prescriptive path.
❑ No
Is the combined weight gh El Yes
of the PV modules and If"Yes",qualifies for
racking less than or ❑ No the prescriptive path.
Solar equal to 4.5 psf?
installation Is the solar installation
layout in accordance El Yes
with Section 305.4(3) of If"Yes",qualifies for
the 2010 Oregon Solar ❑ No the prescriptive path.
Code?
❑ Metal
Single layer If roofing material is
Roofing Check the type of ❑ of wood one of the three types
material roofing material shingle/shake checked, qualifies for
Max. two layers the prescriptive path.
❑✓ of composition
shingle.
Is the roof mounted 0 Yes
Connections of solar assembly If"Yes",qualifies for
the solar assembly connected to roof ❑ No
to the roof framing or blocking the prescriptive path.
directly?
2
lBuilding/Forms/PhotoVoltaic-Checklist02-01-11.docx
❑ Yes If"Yes",qualifies for
Is the gauge 26 or less?
❑ No the prescriptive path.
115 lbs for 60 inch
spacing or less?
If"Yes",qualifies for
❑ Yes the prescriptive path.
❑ No
Minimum Uplift rating
of Clamps? 75 lbs for 48 inches
spacing or less?
If"Yes",qualifies for
❑ Yes the prescriptive path.
❑ No
Attachment of
roof mounted If the spacing falls
solar systems Spacing of clamps? Minimum 24 inches within 24 inches and 60
directly to inches Maximum 60 inches inches,qualifies for the
standing seam prescriptive path.
metal panels Width of roofing If the width of the panel
is less than 18 inches,
panels? 18 inches or less qualifies for the
inches
prescriptive path.
Minimum#10 at 24
inches o/c?
Size and spacing of ❑ Yes If"Yes",qualifies for
fastener? the prescriptive path.
❑ No
Is the roof decking of
WSP min. '/2"thickness, ❑ Yes
decking connected to If"Yes",qualifies for
framing members ❑ No the prescriptive path.
w/min. 8d nails @
6"/12"o/c?
Is the height less than or
Maximum 18 inches equal to 18 inches?
Height of the from the top of the If"Yes",qualifies for
El
solar modules module to the roof Yes the prescriptive path.
surface. ❑ No
3
lBuilding/Forms/PhotoVoltaic-Checklisto2-01-11.docx
Submittal Documents required for Prescriptive Installations
Show the location of the PV system in relation to buildings, structures,
property lines,and,as applicable,flood hazard areas.
Site Plan Details must be clear and easy to read.
Minimum size of the plan is 8.5 x 11 inches.
Attach a simple structural plan showing the roof framing(rafter size,type, and
spacing)and PV module system racking attachment.
System must be shown in sufficient detail and clarity to assess whether it
Structural Plan meets the prescriptive construction requirements as listed earlier above in the
matrix.
Minimum size of the plan is 8.5 x 11 inches.
PV Modules
Manufacturer: Hanwha Q.Cells
Model Number: Q.peak DUO-BLK ML-G 10+400
Listing Agency: UL 61730,CE-compliant,IEC 61215:2016,IEC 61730:2016