Report GENERAL
THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND CORRELATION OF ALL ITEMS AND WORK NECESSARY
FOR COMPLETION OF THE PROJECT AS INDICATED BY THE CONTRACT DOCUMENTS. SHOULD ANY QUESTION ARISE
REGARDING THE CONTRACT DOCUMENTS OR SITE CONDITIONS, THE CONTRACTOR SHALL REQUEST
INTERPRETATION AND CLARIFICATION FROM THE ENGINEER BEFORE BEGINNING THE PROJECT. THE ABSENCE OF
SUCH REQUEST SHALL SIGNIFY THAT THE CONTRACTOR HAS REVIEWED AND FAMILIARIZED HIMSELF WITH ALL
ASPECTS OF THE PROJECT AND HAS COMPLETE COMPREHENSION THEREOF. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR CONFORMANCE TO ALL SAFETY REGULATIONS DURING CONSTRUCTION.
THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. UNLESS OTHERWISE
SPECIFICALLY NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION OR CONSTRUCTION LOADS. ONLY
THE CONTRACTOR SHALL PROVIDE ALL METHODS, DIRECTION AND RELATED EQUIPMENT NECESSARY TO PROTECT
THE STRUCTURE, WORKMEN AND OTHER PERSONS AND PROPERTY DURING CONSTRUCTION. THE CONTRACTOR
SHALL, AT HIS OWN EXPENSE, ENGAGE PROPERLY QUALIFIED PERSONS TO DETERMINE WHERE AND HOW
TEMPORARY PRECAUTIONARY MEASURES SHALL BE USED AND INSPECT SAME IN THE FIELD. ANY MATERIAL NOT AS
SPECIFIED OR IMPROPER MATERIAL INSTALLATION OR WORKMANSHIP SHALL BE REMOVED AND REPLACED WITH
SPECIFIED MATERIAL IN A WORKMANLIKE MANNER AT THE CONTRACTOR'S EXPENSE.
THESE PLANS, SPECIFICATIONS, ENGINEERING AND DESIGN WORK ARE INTENDED SOLELY FOR THE PROJECT
SPECIFIED HEREIN. MILLER CONSULTING ENGINEERS DISCLAIMS ALL LIABILITY IF THESE PLANS AND
SPECIFICATIONS OR THE DESIGN, ADVICE AND INSTRUCTIONS ATTENDANT THERETO ARE USED ON ANY PROJECT
OR AT ANY LOCATION OTHER THAN THE PROJECT AND LOCATION SPECIFIED HEREIN. OBSERVATION VISITS TO THE
JOB SITE AND SPECIAL INSPECTIONS ARE NOT PART OF THE STRUCTURAL ENGINEER'S RESPONSIBILITY UNLESS
THE CONTRACT DOCUMENTS SPECIFY OTHERWISE.
NON STRUCTURAL PORTIONS OF PROJECT, INCLUDING BUT NOT LIMITED TO PLUMBING, FIRE PROTECTION, LAND
USE, SITE PLANNING, EROSION CONTROL, ELECTRICAL, MECHANICAL, FLASHING AND WATER-PROOFING ARE
BEYOND THE SCOPE OF THESE DRAWINGS AND ARE PROVIDED BY OTHERS. EXISTING STRUCTURAL ELEMENTS ARE
DESIGNED BY OTHERS. ANALYSIS FOR MOVEMENT DUE TO VORTEX SHEDDING OF WIND FORCES IS NOT INCLUDED
IN THE SCOPE OF WORK. IF MOVEMENT CAUSED BY VORTEX SHEDDING IS A CONCERN, WIND TUNNEL TESTING OR
OTHER ANALYTICAL MODELS SHALL BE UTILIZED TO EVALUATE THE STRUCTURE.
IN ACCORDANCE WITH SECTION 1704.2 EXECPTION 1, NO SPECIAL INSPECTIONS ARE REQUIRED FOR [WELDS OR
POST-INSTALLED ANCHORS]AS THE LOADING IS A MINOR FRACTION OF THE CAPACITY OF THESE ELEMENTS.
CONTRACTOR TO VERIFY ALL CONDITIONS PRIOR TO FABRICATION OR INSTALLATION. ENGINEER OF RECORD FOR
THE PROJECT IS TO BE NOTIFIED IF CONDITIONS DIFFER FROM WHAT IS SHOWN ON THE DRAWINGS.
BUILDING CODE
ALL PHASES OF THE WORK SHALL CONFORM TO THE 2019 OREGON STRUCTURAL SPECIALTY CODE, BASED ON THE
2018 INTERNATIONAL BUILDING CODE, INCLUDING ALL REFERENCE STANDARDS, UNLESS NOTED OTHERWISE.
`�
(,��,C5,D PROF
40 G t N
r, ��s�o
7252 PE
r •N o ,�
y 6 a , �csQ•
�
✓OSEPH '
EXPIRES:12-31-2022
Zoomcare Wall Sign Project#
MILLER
221333
Project Name 1
it CONSULTING Location 11958 SW Garden Place, Tigard, OR
ENGINEERS
Client Tube Art Displays Inc.
9600 SW Oak St#400 503.246.1250 CJM El-14J 9/2/2022 2 of 3
Portland,OR 97223 miller-se.com By Ck'd Date Page
DESIGN LOADS
THE FOLLOWING ARE THE DESIGN REQUIREMENTS:
STRUCTURAL DESIGN CRITERIA
RISK CATEGORY II
WIND DESIGN DATA
BASIC WIND SPEED(3 SEC GUST) 98 MPH
EXPOSURE B
POST-INSTALLED ANCHORS
ANCHORS SHALL BE AS SPECIFIED ON THE DRAWINGS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH
THE MANUFACTURER'S INSTALLATION CRITERIA.
ALUMINUM
ALL STRUCTURAL ALUMINUM SHAPES AND PLATES TO BE 6061-T6. ALL WELDS TO USE 4043 ALUMINUM FILLER
ALLOY. A PROTECTIVE BARRIER SHALL BE PROVIDED BETWEEN ALL STEEL AND ALUMINUM TO PREVENT
CORROSION.ALL WELDING TO CONFORM TO AMERICAN WELDING SOCIETY(AWS) D1.2.WELD LENGTHS SHOWN ARE
EFFECTIVE AS SPECIFIED PER THE ALUMINUM DESIGN MANUAL. WELDING SHALL BE BY AWS CERTIFIED WELDERS
FOR WELD TYPES SPECIFIED. WHERE WELD LENGTHS ARE NOT SHOWN, THE WELD SHALL BE FULL LENGTH OF
MEMBERS BEING JOINED. ALL BUTT WELDS SHALL BE FULL PENETRATION WELDS UNLESS NOTED OTHERWISE ON
STRUCTURAL DRAWINGS. ALL WELDS TO RECEIVE THE SAME FINISH COAT AS THE MEMBER BEING WELDED. ALL
FASTENERS IN CONTACT WITH ALUMINUM TO BE HOT DIPPED GALVANIZED WITH MATCHING NUTS OR HAVE A
PROTECTIVE BARRIER TO PREVENT CORROSION. NUTS SHALL BE TIGHTENED TO A SNUG TIGHT CONDITION.
L
I PROP�ss�o
szk- ''4.1Q7252 PE 15
N
9'P!2G Y 0 8 • ryo�Q�
✓OSEPN MP�o
EXPIRES:12-31-2022
Project Name Zoomcare Wall Sign Project# 221333
ArtMILLER
CONSULTING Location 11958 SW Garden Place, Tigard, OR
ENGINEERS
Client Tube Art Displays Inc.
9600 SW Oak St#400 503.246.1250 OM l 9/2/2022 3 of 3
Portland,OR 97223 miller-se.com By Ck'd Date Page