THE VIEWFINDER
PROJECT DESCRIPTION
— — — 37.92 KW SOLAR PV PROJECT
PROJECT ADDRESS
11600 SW 72ND AVE.
TIGARD, OR 97223
CONTACT INFORMATION
RANDALLFELDHAUS
503-803-5537
randy@bestroofusa.com
STRINGING LAYOUT
REVISION DATE REASON
SW 72ND AVENUE
NOTES:
8' SPACING BETWEEN ATTACHMENTS EXCEPT DESIGNED BY
WHEN OTHERWISE NOTED RANDALL FELDHAUS
DRAWN BY
TYPICAL SLEEPER TO CONTINUE T PAST LAST Z JUSTIN GUADAGNI
ATTACHMENT ON EITHER END OF ROW —
DRAWN ON
1/31/2021 SHEET NUMBER
SCALE
PV5.0
1/8" = 1'
COMPETITIVE
COMMERCIAL
ROOFING
POLARIS ELECTRIC 1465 OR-35
SIGNING SUPERVISOR #53165 HOOD RIVER, OR 97031
P 541.400.0972
CCB#: 174631
(3) STRINGS OF 16 (3) STRINGS OF 16
16 16 161 16 16 16 * WIRE SIZING ON SHEET PV7.0
37.92 kW PV ARRAY
(96) HANWHA 395W #10 PV WIRE IN OPEN AIR UNDER ARRAY
PV MODULES #6 CU GROUND
(48) SOLAREDGE P860
DC OPTIMIZERS
- OUTSIDE OF ARRAY I I I - OUTSIDE OF ARRAY
I I (2) #6 THWN-2 CU CONDUCTORS I I I (2) #8 THWN-2 CU CONDUCTORS
J-BOXES I I 1 (1 ) #8 THWN-2 CU GROUND I I - - --J-BOXES (1 ;1 #8 THWN-2 CU GROUND
i I I 1 " EMT (NO MORE THAN 3 I I 3/4" EMT (NO MORE THAN 3 STRINGS IN A CONDUIT)
I I I STRINGS IN A CONDUIT)
ON ROOF I I I I I
INVERTER 1 INVERTER 2
SOLAREDGE SOLAREDGE
SE14AKUS SE14AKUS
I I
14AKW 14AKW
208VAC 208VAC
3PH, 4W 3PH, 4W
40A OUTPUT 40A OUTPUT
I I
RS 485 CAT 5 OR 6 TO ETHERNET ROUTER
- -
i
(3) #8 THWN-2 CU CONDUCTORS
i I (1 ) #8 THWN-2 CU NEUTRAL
- -- - - -- - - r - - - - - - - - - - - - - - - - - J (1 ) #8 THWN-2 CU GROUND
i 1 " EMT SOLAREDGE P860
DC OPTIMIZER
3P 3P
100A 50A ` 50A LL
COMBINER 3P W
120/208V, 100A DC 0
3PH, 4W ± 7
U.
3:
ui
P860 DC OPTIMIZER DETAIL
(3) #3 THWN-2 CU CONDUCTORS
(1 ) #8 THWN-2 CU NEUTRAL W
(1 ) #8 THHN-2 CU GROUND
1 .25" EMT Z
100A INVERTER AC
LOCKABLE DISCONNECT
AC DISCONNECT O PV MODULES PV RACKING
G
I
I HOUSE PANEL
I
(3) #3 THWN-2 CU CONDUCTORS
I (1 ) #8 THWN-2 CU NEUTRAL
(1 ) #8 THHN-2 CU GROUND BONDING OCCURS
1 .25" EMT AT HARDWARE
L_ _ __ __ _ _ _ _ _ _ _
CONNECTIONS
i #8 CU THWN #8 CU THHN #8 CU THHN NEUTRAL BUS
I
I
HOUSE
3P GROUNDING
1200A, HOUSE PANEL 100A GROUNDING PLAN SYSTEM
120/208V, 3PH, 4W
MAIN ELECTRICAL INTERCONNECTION
ROOM 117 THROUGH 100A
PV BREAKER
THE VIEWFINDER
I PROJECT DESCRIPTION
37.92 KW SOLAR PV PROJECT
PROJECT ADDRESS
11600 SW 72ND AVE.
TIGARD, OR 97223
CONTACT INFORMATION
31P RANDALL FELDHAUS
1200A 503-803-5537
randy@bestroofusa.com
2000A, MAIN
DISTRIBUTION PANEL3P
120/208V, 3PH, 4W, 2000A WIRING DIAGRAM
37.6 KAIC
REVISION DATE REASON
M
TO GRID
DESIGNED BY
RANDALLFELDHAUS
DRAWN BY
JUSTIN GUADAGNI
DRAWN ON
1/31/2021 SHEET NUMBER
SCALE PV6.0
NTS
QCOMPETITIVECOMMERCIAL
ROOFING
POLARIS ELECTRIC
SIGNING SUPERVISOR #53165 1465 OR-35
HOOD RIVER, OR 97031
P 541.400.0972
CCB#: 174631
WIRE AND CONDUIT CALCULATIONS
Derated
Conduit Length Cont. Max Identical Parallel Conductors Conduit Conduit Ambient Neutral Conductor Wire Temp 90C 75C
Start Point End Point Wire Runs Runs (1-way) Amperage Amperage Voltage AC/DC Wire Type Wire Runs Runs? Per Run EGC Size Type Size Temp (C) Size Size Material Fill Derate Derate Ampacity Ampacity Impedance Vdrop
Modules Junction Box 6 6 93 18 22.5 400 DC (PV) wire-600 6 NO 2 8 EMT 3/4 31-35 n/a 10 Cu 1 0.96 30.72 30 0.9989 0.0084
Junction Box 1 Inverter 1 1 1 190 18 22.5 400 DC THHN/THWN-2 1 NO 2 8 EMT 3/4 31-35 n/a 6 Cu 1 0.96 72 65 0.3951 0.0068
Junction Box 2 Inverter 1 1 1 155 18 22.5 400 DC THHN/THWN-2 1 NO 2 8 EMT 3/4 31-35 n/a 6 Cu 1 0.96 72 65 0.3951 0.0055
Junction Box 3 Inverter 1 1 1 140 18 22.5 400 DC THHN/THWN-2 1 NO 2 8 EMT 3/4 31-35 n/a 6 Cu 1 0.96 72 65 0.3951 0.0050
Junction Box 4 Inverter 2 1 1 98 18 22.5 400 DC THHN/THWN-2 1 NO 2 8 EMT 3/4 31-35 n/a 8 Cu 1 0.96 52.8 50 0.6282 0.0055
Junction Box 5 Inverter 2 1 1 35 18 22.5 400 DC THHN/THWN-2 1 NO 2 8 EMT 3/4 31-35 n/a 8 Cu 1 0.96 52.8 50 0.6282 0.0020
Junction Box 6 Inverter 2 1 1 25 18 22.5 400 DC THHN/THWN-2 1 NO 2 8 EMT 3/4 31-35 n/a 8 Cu 1 0.96 52.8 50 0.6282 0.0014
Inverter 1 Combiner 1 1 3 40 50 208 AC- 3PH THHN/THWN-2 1 NO 2 8 EMT 1 31-35 8 8 Cu 1 0.96 72 50 0.6282 0.0007
Inverter 2 Combiner 1 1 6 40 50 208 AC- 3PH THHN/THWN-2 1 NO 2 8 EMT 1 31-35 8 8 Cu 1 0.96 72 50 0.6282 0.0014
Combiner Disconnect 1 1 67 80 100 208 AC- 3PH THHN/THWN-2 1 NO 3 8 EMT 1.25 26-30 8 3 Cu 1 1 115 100 0.22942 0.0105
Disconnect POI 1 1 15 80 100 208 AC- 3PH THHN/THWN-2 1 NO 3 8 EMT 1.25 26-30 8 3 Cu 1 1 115 100 0.22942 0.0026
I
Note: Modules to Junction box length represents the longest length of the 6 strings DC Voltage Drop 1.51%
PV wire runs in open air when under array and in .75" EMT when exposed between rows (single string with 2 conductors) AC Voltage Drop 1.46%
Module voltage and amperage governed by do to do optimizer ( NN
#6 Bare Cu connects and grounds each row of racking, #8 THHN-2 Cu runs from edge of array to inverter protected within EMT
W
0
Z
H
W
W
SYSTEM INFORMATION _
PV MODULE RATING DC OPTIMIZER RATING INVERTER RATING
/PPGEy
MODULE MAKE HANWHA OPTIMIZER MAKE SOLAREDGE INVERTER MAKE SOLAREDGE '°' ' , rt�Lv�e•
MODULE MODEL Q. PEAK DUO L-G5.2 395 OPTIMIZER MODEL P860 INVERTER MODEL SE14AKUS CUSTGOARHAM: Shat
aw BwAy at and wr r2rd aw
MAX POWER 395 MAX OUTPUT CURRENT 18 MAX OUTPUT POWER 14400
OPEN CIRCUIT VOLTAGE 48.7 MAX OUTPUT VOLTAGE 85 MAX DC VOLTAGE 600 ►+GR: WW" anown WR M277•aS6
MAX POWER POINT VOLTAGE 40.71 SAFETY OUTPUT VOLTAGE 1 NOMINAL AC VOLTAGE 208 P E: 50"T2-SM
SHORT CIRCUIT CURRENT 10. 19 MAX AC CURRENT 40 3-PHASE SECONDARY LINE-UNE FAULT CURRENT rM�
MAX POWER POINT CURRENT 9.7 MAX INVERTER EFFICIENCY 97 TRANSFORMER DATA PADMCWW Y�
XFMR In"i (%). 5.82 '11 34P" MUSME oYM
TRANSFORMER MMa YN KWA x111riw* W
Sccondery VOLTAGE {t. to LT M v WYE M 5AW? No
VAMTw-,*P VAULT ( or Pole -;I- Polel SECONDARY
S.IcordmyWim LFAGTM: 1 FWK HARE SIZE THE VIEWFINDER
Nuffiew of SIL-CONOAAY RUNS! 9 I M O*f: PROJECT DESCRIPTION
S WIRE R;CWMauaco R 0jolm 100 37.92 KW SOLAR PV PROJECT
WIRE PhhWtimm 1{: Q_ PROJECT ADDRESS
11600 SW 72ND AVE.
PAM
� ���y A 97223
1fAL�.Tt � Parl�l -� or lVi:_L?rt�l
CON
CONTACTCTINFORMATION MATION
SaVk a WW LEWGTW 15 Fern VME SIZE RANDALL FELDHAUS
4F Swvkw RUN& d Rundsa of-. 503-803-5537
randy@bestroofusa.com
So vk* W RE Rpt X 0.02614 c hm!010001
WIRE CALCS
REVISION DATE I REASON
MAXIMUM FAULT CURRENT": 37j662 Al
111iturnim �"t&�fr.m thas" ftr 100x, af
Saint m n ommi ma of: 2wmalm Amo
TO Pied Tft Pte;-cm M- rand -ft#li#srhm Dft-
DESIGNED BY
RANDALLFELDHAUS
DRAWN BY
JUSTIN GUADAGNI
DRAWN ON
1/31/2021 SHEET NUMBER
SCALE P V 7.0
NTS