Plans I `11�-
GENERAL NOTES AERIAL VIEW
CODE AND STANDARDS
1.ALL WORK SHALL COMPLY WITH 2017 OREGON ELECTRIC SPECIALTY CODE(OESC),2019 OREGONUE RAVEN
STRUCTURAL SPECIALTY CODE,2017 OREGON RESIDENTIAL SPECIALTY CODE,AND ALL STATE AND LOCAL
BUILDING AND ELECTRICAL CODES.
2.DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS.
1403 N.Research Way
SITE NOTES/OSHA REGULATION r Orem,UT 84097
1.A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 1110 800.377.4480
2.THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM. # * #
...t_. Ak,..: ,.,...� :.:.. .:,: _•�,. .,v..... WWW.BLUERAVENSOLAR.COM
3.THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING.MECHANICAL,OR BUILDING ROOF VENTS.
CONFIDENTIAL-THE INFORMATION
4.ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND
THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT HEREIN CONTAINED SHALL NOT BE
THE BUILDING OR STRUCTURE. (,1'
OFFICE COPY USED FOR THE BENEFIT OF ANYONE
Z�JJr j r 1 �` * EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
SOLAR CONTRACTOR IN PART TO OTHERS OUTSIDE
1.MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730. RECIPIENTS ORGANIZATION,EXCEPT
2.IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PER IN CONNECTION WITH THE SALE AND
THE MANUFACTURER'S INSTALLATION REQUIREMENTS. USE OF THE RESPECTIVE EQUIPMENT,
WITHOUT THE WRITTEN PERMISSION
3,AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF
OF BLUE RAVEN SOLAR LLC.
STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ.
4.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO
LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.
5.CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A / N AB C E P 1,
SUITABLE SEALING COMPOUND. --
6.DC WIRING LIMITED TO MODULE FOOTPRINT W/ENPHASE AC SYSTEM. CERTIFIED
7.ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/SUITABLE WIRING CLIPS.
8.MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT PV INSTALLATION
AVAILABLE.
9.ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS,AC PROFESSIONAL
PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT COMBINERS,AND Scott Gurney
CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND #PV-011719-015866
LISTED FOR THE APPLICATION PER NEC 690.4(B).
10.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. CONTRACTOR:
11.TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS(WHEN PROVIDED) BRS FIELD OPS
IN ACCORDANCE WITH NEC CODE 110.14(D)ON ALL ELECTRICAL CONNECTIONS.
800-377-4480
EQUIPMENT LOCATIONS ECEIVE
1.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT
WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS
SPECIFIED BY NEC 690.31(A)AND NEC TABLE 310.15(B). JUL 19 2017
3.ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC 0
APPLICABLE CODES. C1W OF TIGARD 0
4.ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE.
UPING DIVISION i>.
< N co
PROJECT INFORMATION: CITY OF TIGARD N rl-
NUMBER OF STORIES: 2 REVIEWED FO ODE COMPLIANCE O0 0 O N
CONDUIT RUN: Interior
ECOBEE QTY: 1 Approved:
LIGHT BULB QTY: 0 OTC: [ `z
L
PV METER: Not Required Z DESIGN CRITERIA SITE SPECIFICATIONS SHEET INDEX
W p W
Permit#: I ZUZ2 lib 23 p F_
ROOF TYPE (1) INFORMATILQtitlrcSs; Iqq W tDQO WIND SPEED: 100 MPH CONSTRUCTION -V-B PVI -COVER SHEET � -2
ROOF TYPE: Comp Shin�c � �l_l�� ,� GROUND SNOW LOAD: 40 Ib/ftz ZONING: RESIDENTIAL PV2 - SITE PLAN Shall
plans N > � Cn
FRAMING TYPE: Manuil ic'tu#' Truss -� II be On �
SHEATHING TYPE: S�If': � Date: � ZZ_ WIND EXPOSURE FACTOR: C PV3 - ROOF PLAN job site. U � � a 0
ATTACHMENT: SEM Infinity as I SEISMIC DESIGN CATEGORY: D PV4-STRUCTURAL
PV5- ELECTRICAL 3-LINE DIAGRAM DRAWING BY:
RACKING: Unirac SFM Infinity @ 48"OC Portrait/48" OC Landscape SCOPE OF WORK PV6- ELECTRICAL CALCULATIONS
NUMBER OF ATTACHMENTS: 49 PV7 -WARNING LABELS AND LOCATIONS PremiumCAD
ROOF TYPE (2) INFORMATION (IF APPLICABLE): INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM AND ANY (ALL OTHER SHEETS AS REQUIRED) PLOT DATE.
SEE PV4.2
* NECESSARY ADDITIONAL WORK NEEDED FOR INSTALLATION. SS- PRODUCT SPEC. SHEETS
July 7, 2022
PROJECT NUMBER:
SYSTEM TO BE INSTALLED INFORMATION: THE ISSUANCE OFA PERMIT LIABILITY UTILITY COMPANY:
SYSTEM SIZE: 7.6 kW DC BASED ON CONSTRUCTION The City of Tigard and its Portland General Electric (PGE) 522968
MODULE TYPE: 19 fo
Q.Peak duo blk ml- 110+_365-405 DOCUMENTS AND OTHER empiaye shall not be SHEET NAME:
9 DATA SHALL NOT PREVENT responsible for discrepancies
INVERTER TYPE: Enphase IQ7PLUS-72-2-US which may appear herein. COVER SHEET
MONITORING: Enphase IQ Combiner 3 X-IQ-AM1-240-3 THE CODE OFFICIAL FROM PERMIT ISSUER:
REQUIRING THE CORRECTION City of Tigard REVISION: PAGE NUMBER:
OF ERRORS. ORSC 105.4 0 PV 1
LEGEND
JUNCTION BOX
13LUE RAVEN
UTILITY METER
\ \ 1403 N.Research Way
MSP MAIN SERVICE PANEL Orem,UT 84097
\ \ 800.377.4480
OAC AC DISCONNECT WWW BLUERAVENSOLAR.COM
CONFIDENTIAL-THE INFORMATION
FRONT OF HOME cB COMBINER BOX HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
11964 Sw Wildwood St \ \ EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
LOAD CENTER IN PART TO OTHERS OUTSIDE
LC RECIPIENTS ORGANIZATION,EXCEPT
\ IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
SUB SUBPANEL WITHOUT THE WRITTEN PERMISSION
OF BLUE RAVEN SOLAR LLC7-7 .
/ PV PV METER -.._. .
TRANSFER SWITCH CERTIFIED
/ PV INSTALLATION
/ \ ESS SUNPOWER ESS PROFESSIONAL
Scott Gurney
/ \ #PV-011719-015866
/
FH UB SUNPOWER HUB+
/ CONTRACTOR:
BRS FIELD OPS[RPO REMOTE POWER OFF
800-377-4480
FIRE SETBACK
\ \ i TRENCHING
\ i PROPERTY LINE O
I
\ > SCALE: 3/64" = 1'-0" Q "- N
�s 2 C/)L V 0 O O) LU
\ U- 0 o N
m Z-0Cn
W -o O W
m s m e
O Li (0 70 Cl)
\ / N 70 C Cl)
L
n
\ / / DRAWING BY:
PremiumCAD
\ \1 PLOT DATE:
/ VVV Jul 7, 2022
\ / Y
/ PROJECT NUMBER:
522968
\ / SHEET NAME:
\✓� SITE PLAN
REVISION: PAGE NUMBER:
---- 0 PV2
LEGEND
0 JUNCTION BOX
FRONT OF HOMEL RAVEN
UTILITY METER
1403 N.Research Way
FMS
MAIN SERVICE PANEL Orem,UT 84097
800.377.4480
DAC AC DISCONNECT WWW BLUERAVENSOLAR.COM
CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
CB COMBINER BOX USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
LOAD CENTER IN PART TO OTHERS OUTSIDE
LC RECIPIENTS ORGANIZATION,EXCEPT
IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
SUB SUBPANEL WITHOUT THE WRITTEN PERMISSION
OF BLUE RAVEN SOLAR LLC.
PV PV METER
TS TRANSFER SWITCH CERTIFIED
POINT OF INTERCONNECTION PV INSTALLATION
CHIMNEY - ESS SUNPOWER ESS PROFESSIONAL
UNDERGROUND SERVICE LINE Scott Gurney
#PV-011719-015866
HUB SUNPOWER HUB+
MSP M CONTRACTOR:
i ❑ BRS FIELD OPS
REMOTE POWER OFF 80
1 AC 800-377-4480
1' FIRE SETBACK
CB
1
TRENCHING
�- U
9C %C ffC , CHIMNEY i 0
PROPERTY LINE
ff
� � � LSC SCALE: 118" = V-0" N m
_0 ti ~
ffC ffC ffc ffC p o rn W
u. 0
o N
LC Z
tic ffC 11C 11C ff7c ffC 9C w _0 LU
0 LL
,yF- fA
L
MP2
MP1 #OF MODULES: 3 V a
#OF MODULES: 16 AZIMUTH: 201
AZIMUTH: 202 PITCH: 30 DRAWING BY:
PITCH: 30 TSRF: 81% PremiumCAD
TSRF: 87% AREA: 349 ft.2
AREA: 633 ft.Z PLOT DATE:
July 7, 2022
PROJECT NUMBER:
522968
SHEET NAME:
1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER ROOF PLAN
2. ROOF ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24
IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 3 FT. OF A REVISION PAGE NUMBER:
ROOF EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3) 0 PV3
STRUCTURAL INFORMATION: STRUCTURAL NOTES: PV MODULE UNIRAC SFM 2" MICRORAIL UNIRAC SFM 6.5" SPLICE
ROOF TYPE (1): 1. AC DISCONNECT TO BE LOCATED WITHIN 10 FT. OF METER
2. ROOF ATTACHMENTS SHALL BE SPACED NO GREATER i
ROOF TYPE: Comp Shingle THAN 24 IN. OC IN ANY DIRECTION WHERE LOCATED WITHIN 4�
SHEATHING TYPE: SKIP 3 FT. OF A ROOF EDGE, HIP, EAVE, OR RIDGE (OSISC 305.4.3)
1403 N.Research Way
FRAMING TYPE: Manufactured Truss
FRAMING SIZE: 2x4 @ 24" OC Lower smaller plane is framed with rafters. Larger higher plane is — 23 — 48" MAX. — LANDSCAPE Orem,UT 84097
CEILING JOIST SIZE: 2x4 @ 24"OC manufactured truss. MAX. 800.377.4480
WWW.BLU ERAV ENSOLAR.COM
ATTACHMENT: SFM Infinity Flashkit CONFIDENTIAL-THEINFORMATION
RACKING: Unirac SFM Infinity PV MODULE UNIRAC SFM 2" MICRORAIL UNIRAC SFM 6.5"SPLICE CONFIDENTIAL-
HEREICONTAINED TIAL- HE INFOSHALRMATION
USED FOR THE BENEFIT OF ANYONE
48" OC Portrait/48" OC Landscape EXCEPT BLUE RAVEN SOLAR NOR
NUMBER OF ATTACHMENTS: 49 SHALL IT BE DISCLOSED IN WHOLE OR
N PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,EXCEPT
PV MODULE COUNT: 19 Modules N CONNECTION WITH THE SALE AND
TOTAL ARRAY AREA: 332.7 ft2 (17.51 ft2/panel) USE OF THE RESPECTIVE EQUIPMENT,
TOTAL ROOF AREA: 3127 ft2 WITHOUT THE WRITTEN PERMISSION
_ 23" _ OF BLUE RAVEN SOLAR LLC.
ARRAY/ROOF AREA: 10.6% MAX. 48" MAX. — PORTRAIT
ARRAY WEIGHT: 950 lbs (50 lbs/panel) ATTACHMENT SPACING- FRONT VIEW -RACKING ATTACHMENTS TO BE STAGGERED
`NOTE:LISTED NUMBER OF ATTACHMENT POINTS ARE AN ESTIMATE ONLY AND MAY VARY I
DISTRIBUTED LOAD: 2.86 Ibs/ft2 BASED ON FIELD CONDITIONS.MAXIMUM ATTACHMENT SPACING TO BE FOLLOWED PER C BY SHIFTING EACH SUBSEQUENT ROW OF i NABCEF
POINT LOAD: 19.39 lbs/attachment ENGINEER OF RECORD SPECIFICATIONS. SCALE: 3/4" = 1'-0" ATTACHMENTS OVER ONE RAFTER. CERTIFIED
UNIRAC SFM INFINITY UNIRAC SFM MICRORAIL/SPLICE A PV INSTALLATION
PV MODULE PROFESSIONAL
�— Scott Gurney
Q.PEAK_DUO_BLK_ML-GL10+ 365-405 B #PV-011719-015866
PV MODULE PORTRAIT
CONTRACTOR:
UNIRAC SFM SLIDER BRS FIELD OPS
ROOF STRUCTURE 800-377-4480
o (E) ROOF MODULE
SHEATHING WIDTH
FLASHING A
(1)5/16"STAINLESS STEEL LAG BOLT B0 U
WITH 2-1/2" MIN. EMBEDMENT �_ LANDSCAPE
AND FLAT WASHER 212" MIN. EMBED. 30' N
MODULEC/) N t0
WIDTH1 _0 � ti
- 0 O M LJ.I
A MIDDLE/TOP STANDOFF DETAIL ATTACHMENT SPACING- SIDE VIEW Z o N
SCALE: 3" - 1'-0" 65
(E) BUILDING STRUCTURE D _ 0
SCALE: 1/2" = V-0"
W - 0 W
Q.PEAK_DUO_BLK_ML-GL10+_365-405 O _
PV MODULE0 LL
U (.
U 0
UNIRAC SFM TRIMRAIL
I FLASHING DRAWING BY:
UNIRAC SFM SLIDER AND
PremiumCAD
TRIMRAIL ROOF ATTACHMENT (E) ROOF
SHEATHING PLOT DATE:
July 7, 2022
(1) 5/16" STAINLESS STEEL LAG BOLT PROJECT NUMBER:
WITH 2-1/2" MIN. EMBEDMENT 52296H
AND FLAT WASHER 2'2" MIN. EMBED.
SHEET NAME:
STRUCTURAL
BOTTOM STANDOFF DETAIL REVISION: PAGE NUMBER:
B (E) BUILDING STRUCTURE
SCALE: 3" = V-0" 0 PV4
'11 111 11"1HHN11KWN,1,CU-I1LA"ILI 1 10 AWG rHHINfTRWN-2,CU,,BLA M" IZI A 12-2TC-ER,T)4#041THWN-1 CU MM LZ,I A AC
2 uve ior N"w�c�T+0HN/T1iwN-zs0u"
23'0 A Ac 1(2) cx 1"1) �'IAx L"AAEI
15 (1) 10 AWG THHN/THWN-4 CU,,RED(L2) 240 V AC 3 12) 10 AWG THMN/T1141WN-2.CU.,RED(12) 240 VACI Jill u 240 V 6 AWG BARE.CU jEGC 1 240 V AC
�(1) 10 AVVG tHHNfThWN4.CU,WMTE(N) (1) 10 AWG TMNITHINN4.U,GREEN VEC<)
(1) 10 A"TMHN/ThWft-2,CV-GREEN(EGCI
(1) 3/4 iNCR EMT Clfrfpti,3� (1) 3/4 jNCJ4 ENIT, INTERIOR x I F 1q;OR
0a BLIE RA"VEN
1403 N.Research Way
Orem,UT 84097
800.377.4480
WWW.BLUERAVENSOLAR.COM
DESIGNER NOTES: ELECTRICAL NOTES: CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
LOAD SIDE BREAKER IN MSP,INTERIOR POI. ALL CONDUIT TO BE RAN AT LEAST 7/8 IN.ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
IN PART TO OTHERS OUTSIDE
(19)Q.Peak-duo-bIk_mI-gI10+_365-405 RECIPIENTS ORGANIZATION,EXCEPT
ILL 1703 COMPLIANT IN CONNECTION WITH THE SALE AND
(E)200A MAIN SERVICE PANEL ENPHASE IQ COMBINER 3 (19) Enphase IQ7PLUS-72-2-US USE OF THE RESPECTIVE EQUIPMENT.
(E)200A/2P MAIN BREAKER (SOLAR LOAD ONLY) WITHOUT THE WRITTEN PERMISSION
4"x4"x4"PVC JB-1 EZ SOLAR ILL 1741 COMPLIANT OF BLUE RAVEN SOLAR LLC.
PV AC DISCONNECT �I JUNCTION BOX JUNCTION BOX
(E)200A/2P NON-FUSED (N)20A/2P
rTry
Ll LOCKABLE,VISIBLE OPEN ILl JB Ll —jB-1 Ll (1)CIRCUIT OF
L2 L2 L2 "NABCEP'\
L2 30A,240V.2-POLE
N EGO 10 MODULES
i f # I CERTIFI�Dj
(E)LOADS
*PV BREAKER TO BE LOCATED
AT OPPOSITE END OF BUSSING
'c— i F——— C X2 1
JB
I
I
I
FROM MAIN BREAKER PV INSTALLATION
(N)30A 2P
Ll (N)20A 2P L,
L2 L2 Ll JB-1 L' (1)CIRCUIT OF PROFESSIONAL
k
�L I L2 L2 Scott Gurney
N N G
EGO 9 MODULES #PV-01 1719-015866
E� DGLO
EGC
——— --
---------------------------------------—————————————————————————————————————— ...... LGC ————————————————————— r————
-T-
120/240 VAC N _j 3 CONTRACTOR:
60HZ 15 15 _j
BRS FIELD OPS
1 PHASE
TO UT800-377-4480
UTILITY
GRID
Amw
Av
Z
(E)GROUNDING 0
ELECTRODE(S)
U)
N co
0 0')
0
0
ILL C: N
z -0
AoQ)
LU
LU -0
0F
C) LL Cf) 70 Cj)
F- -0
FU
rl
cl)
> C))
0
DRAWING BY:
PrerniurnCAD
PLOT DATE:
July 7, 2022
INTERCONNECTION NOTES rt
PROJECT NUMBER:
705.12(6)(3)THE FOLLOWING METHOD(S)SHALL BE USED TO
DETERMINE THE RATINGS OF BUSBARS: (2)WHERE TWO SOURCES, 522968
ONE A PRIMARY POWER SOURCE AND THE OTHER ANOTHER POWER
SHEET NAME
SOURCE, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT
CONTAINS LOADS, THE SUM OF 125 PERCENT OF THE ELECTRICAL
POWER-SOURCES)OUTPUT CIRCUIT CURRENT AND THE RATING OF REVISION PAGE NUMBER:
THE OVERCURRENT DEVICE PROTECTING THE BUS BAR SHALL NOT
EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR. UTILITY COMPANY: Portland General Electric (PGE) PERMIT ISSUER: City of Tigard 0 PV5
MODULE SPECIFICATIONS Q,Peak duo blk mi-gI10-_365-405 DESIGN LOCATION AND TEMPERATURES
RATED POWER(STC) 7- CONDUCTOR SIZE CALCULATIONS
MODULE VOC 400 W 'TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURFIRENT(ISC)= 1.2.1 A AC
45-3 VDC I STATE Oregon iJUNCTION BOX(1) MAX.CURRENT(I SC X1_25)= 15-1 AAC
MODULE VMP 37-1 V DC CITY I No�
Portland CONDUCTOR(TC-ER,COPPER(90*C))= 12 AWG %
MODULE IMP 10.8 ADC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING z 30 A
AMBTEMP
6
IMODULE ISC 111 ADC 1ASHRAE EXTREME LOW TEMP(-C) , .AMP,CORRECTION;: 32 0.96 BLUE RA
1v'0C CORRECTION „0_27 %/'C 32 ADJUSTED AMP, 2&S 15-1 1403 N.Research Way
VMp CORRECTION -0.34 %rC Orem,UT 84097
ISERIES FUSE RATING JUNCTION BOX TO MAX SHORT CIRCUIT CURRRENT(LSC) 111 AAC
20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR I CIA 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X125)= 15.1 AAC 800.377.4480
AL1), MODULE VOC @ ASHRAE LOW TEMP 49.1 VDC NUMBER OF MODULES PER MPPTWWW.BLUERAVENSOLAR.COM
10 CONDUCTOR(UF-8,COPPER(60-0)- 16 12 AWG
AD) MODULE VMP @ ASHRAE 2%AVG,HIGH TEMP 32.2 V DC DC POWER RATING PER CIRCUIT(STC) 4WO 36W CONFIDENTIAL-THE INFORMATION
CONDUCTOR RATING= 16 20 A HEREIN CONTAINED SHALL NOT BE
TOTAL MODULE NUMBER 19 MODULES CONDUIT FILL DEBATE= 2 1 USED FOR THE BENEFIT OF ANYONE
LE'S
i EXCEPT BLUE RAVEN SOLAR NOR
MICROINVERTER SPECIFICATIONS Enphase IQ7+Mkroinverter5 STC RATING OF ARRAY 760OW DC AMB,TEMP.AMP,CORRECTION= 32 0.96 SHALL IT BE DISCLOSED IN WHOLE OR
POWE R POINT TRACKING(MppT)MIN/MAX 22 - W V DIC AC CURRENT @ MAX POWER POINT(IMP) 121 10.9 ' )-4- 1 CIN PART TO OTHERS OUTSIDE
MAXIMUM INPUT VOLTAGE 60 VDC MAX,CURRENT(IMP}41.25) 15.1 ADJUSTED AMP,= 19,2 > 15.1 RECIPIENTS ORGANIZATION,EXCEPT
25 116125 JUNCTION BOX T MAX.sm IN CONNECTION WITH THE SALE AND
0 ORT CIRCUIT CURRRENT(ISQ= IZI AAC USE OF THE RESPECTIVE EQUIPMENT,
MAXIMUM DC SHORT CIRCUIT CURRENT 15 ADC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(31 MAX.CURRENT(ISC X1.25)= 15.1 AAC
IMAXIMUM USABLE DC INPUT POWER 440 W WITHOUT THE WRITTEN PERMISSION
MAX.COMB.ARRAY AC CURRENT(IMP) 23.0 CONDUCTOR(UF-8,COPPER(60*C))= 20 12 AWG OF BLUE RAVEN SOLAR LLC.
,MAXIMUM OUTPUT CURRENT 1-21 AAC MAX,ARRAY AC POWER SSIOW AC CONDUCTOR RATING= 20 20A
1AC OVERCURRENT PROTECTION
IM"MUi 20 A CONDUIT FILL DERATE z 4 0.8
M OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(M COND. VRISE(V) VEND(V) %VRISE AMB.TEMP,AMP,CORRECTION 32 0-96 / NABCEP ,,
ICEC WEIGHTED EFFICIENCY - 97 % VRISE SEC.I(MICRO TO JBOX) -36 12 Cu. 1.45 Z41 0.6196 ADJUSTED AMP.= 15.36 > 15-1 CERTIFIED
VRISE SEC,2()BOX TO COMBINER BOX) so 12 Cu, 2.44 242.44 1,02% COMBINER BOX TO INVERTER RATED AMPS= 21.0 A AC PV INSTALLATION
AC PHOTOVOLATI-C MODULE MARKING(NEC 690.52) �VRISE SEC.3 tCOMBINER BOX TO POI) 5 10 Cu. 0,29 240.29 0.12% MAJ N PV OCPO(15) MAX.CURRENT(RATED AMPS X1.25) 2&74 AAC PROFESSIONAL
NOMINAL OPERATING AC VOLTAGE 240 VAC TOTAL VRISE 4.19 244.19 CONDUCTOR(THWN�2,COPPER(75'C TERM)) 30 10AWG Scott Gurney
NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC #PV-01 1 71 9-01 5866
CONDUCTOR RATING z 30 35 A
MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690,54)
CONDUIT FILL DEBATE= 3 1 CONTRACTOR:
MAXIMUM AC CURRENT 1'0 AACOUTPUT CURRENT 23.0 A AC AMS,TEMP,AMP.CORRECTION= 32 O,96 BRS FIELD OPS
MAXIMUM CCPD RATING FOR AC MODULE 20 AAC [NOMINALAC VOLTAGE 240 V AC ADJUSTED AMP,z 33,6 28,7 j 800-377-4480
GROUNDING NOTES WIRING & CONDUIT NOTES 0
1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE Q
PROVIDED. PER [NEC 690,47], THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDIN1
G MAY BE .ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE
USED AND BE BONDED AT THE APPLICATIONS. 0
SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE
INADEQUATE. OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR).
USED AT THE INVERTER LOCATION CONSISTING OF A ILL LISTED 8 FT GROUND ROD WITH ACORN CLAMP.
2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE U)
PER [NEC 250.64(B)I. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, _0
#6 AWG COPPER WIRE 4. UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF
THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN LIVE PARTS,MEYERS HUBS RECOMMENDED
EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. 0 0
SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)], 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE LL 0 C: N
3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. z > 0
COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE-CONDUCTOR CABLE LISTED AND 70
4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.211,[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT,ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS
PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.46]. REQUIRED.
UJI LU
5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE
6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS.
MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 0
7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE 0
MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE >_
310.15(B)(3)(A)],&[NEC 310.15(B)(3)(C)]. V)
8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90'C RATED,WET AND UV RESISTANT,AND UL
GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. 0
9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES LISTED RATED FOR 60OV, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP
EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. EDGES.
10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHNITHWN-2 INSULATED, 90°C RATED,
10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V PAWING BY
EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND D
11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS,
MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
DAMAGE). 3.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PremiumCAD
12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 114. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS DC PLOT DATE:
GREEN IF4 AWG OR LARGER).
13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY)
GROUNDED BUSHINGS AT BOTH ENDS. 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED July 7, 2022
DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK)
14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR 1-1-BLACK, PHASE B OR 1_2- RED
ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY PROJECT NUMBER.
15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE
CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] -USE-2 IS AVAILABLE AS UV WHITE
522968
REGARDLESS OF VOLTAGE. 17 RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES.
18, IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME
FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING
MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.15].
19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC EHEC CALLS
230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)].
REVISION PAGE NUMBER
0 p
STANDARD LABELS ADDITIONAL LABELS
{ l \
LABEL 8 BLUE A
RNINAR � '..
PERMANENT PLAQUE OR DIRECTORY DENOTING THE
LABEL 1 LOCATION OF ALL ELECTRIC POWER SOURCE
ELECTRIC SHOCK HAZARD MAIN DISTRIBUTION UTILITY DISCONNECT(S) DISCONNECTING MEANS ON OR IN THE PREMISES 1403 N.Research Way
FOR PV SYSTEM DISCONNECTING MEANS WHERE THE Orem,UT 84097
LINE AND LOAD TERMINALS MAY BE ENERGIZED IN THE POWER TO THIS BUILDING IS ALSO SUSHALL BE INSTALLED AT EACH SERVICE EQUIPMENT
PPLIED
TERMINALS ON THE LINE AND OPEN POSITION.[NEC 690.13(8)] I FROM A ROOF MOUNTED SOLAR ARRAY WITH LOCATION AND AT THE LOCATION(S)OF THE SYSTEM
LOAD SIDES MAY BE ENERGIZED A RAPID SHUTDOWN DISCONNECTING MEANS DISCONNECT(S)FOR ALL ELECTRIC POWER 800.377.4480
IN THE OPEN POSITION GROUPED AND LABELED WITHIN LINE OF PRODUCTION SOURCES CAPABLE OF BEING WWW.BLUERAVENSOLAR.COM
_- SIGHT AND 10 FT OF THIS LOCATION INTERCONNECTED.[2017 NEC 705.10] CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
PH
• . • LABEL 9 EXCEPT BLUE RAVEN SOLAR NOR
LTAIC SYSTEM PERMANENT PLAQUE OR DIRECTORY DENOTING THE SHALL IT BE DISCLOSED IN WHOLE OR
LABEL 2 LOCATION OF ALL ELECTRIC POWER SOURCE IN PART TO OTHERS OUTSIDE
A I SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT POWER TO THIS BUILDING IS ALSO DISCONNECTING MEANS ON OR IN THE PREMISES RECIPIENTS ORGANIZATION,EXCEPT
THE DISCONNECTING MEANS AS A POWER SOURCE SHALL BE INSTALLED AT EACH SERVICE EQUIPMENT IN CONNECTION WITH THE SALE AND
RATED AC OUTPUT CURRENT 22,99 A AND WITH THE RATED AC OUTPUT CURRENT AND THE SUPPLIED FROM MAIN DISTRIBUTION LOCATION AND AT THE LOCATION(S)OF THE SYSTEM USE OF THE RESPECTIVE EQUIPMENT,
WITHOUT THE WRITTEN PERMISSION
NOMINAL OPERATING AC VOLTAGE.(NEC 690.541 UTILITY DISCONNECT LOCATED DISCONNECT(S)FOR ALL ELECTRIC POWER OF BLUE RAVEN SOLAR LLC.
_ NOMINAL OPERATING AC VOLTAGE 240 V PRODUCTION SOURCES CAPABLE OF BEING
� I � INTERCONNECTED.[2017 NEC 705.10]
_.._
..
LABEL 10 �' `
1<*AN N WPOWER
PERMANENT PLAQUE OR DIRECTORY TO BECERTIFIED
LABEL3 LOCATED AT MAIN SERVICE EQUIPMENT DENOTINGDUAL POWER SUPPLY IF INTERCONNECTING LOAD SIDE,INSTALL THIS LABEL TO THIS BUILDING IS ALSO SUPPLIED THE LOCATION OF THE RAPID SHUTDOWN SYSTEM
ANYWHERE THAT IS POWERED BY BOTH THE UTILITY DISCONNECTING MEANS IF SOLAR ARRAY RAPID PV INSTALLATION
AND THE SOLAR PV SYSTEM,IE.MAIN SERVICE PANEL FROM A ROOF MOUNTED SOLAR ARRAY.SOLAR jl SHUTDOWN DISCONNECTING SWITCH IS NOT PROFESSIONAL
SOURCES: UTILITY GRID AND AND SUBPANELS.(NEC 705.12(8)(3)] ARRAY RAPID SHUTDOWN DISCONNECT IS GROUPED AND WITHIN LINE OF SITE OF MAIN Scott Gurney
.
PV SOLAR ELECTRIC SYSTEM SERVICE DISCONNECTING MEANS
LOCATED OUTSIDE NEXT TO THE UTILITY METER. #PV-011719-015866
(2017 NEC 705.10 AND 690.56(C)(1)]
CONTRACTOR:
h BRS FIELD OPS
IR t
LABEL 4
rel 800-377-4480
POWER SOURCE OUTPUT CONNECTION LABEL 11
APPLY TO THE DISTRIBUTION EQUIPMENT ADJACENT PHOTOVOLTAIC SYSTEM PERMANENT PLAQUE OR DIRECTORY TO BE
DO NOT RELOCATE TO THE BACK-FED BREAKER FROM THE POWER COMBINER PANEL LOCATED AT AC COMBINER PANEL.(NEC 110.21 8
SOURCE.(NEC 705.12(8)(2)] ( )]
THIS OVERCURRENT
DEVICE DO NOT ADD LOADS
Z �
AN LABEL 12 Q
IWARNING: PHOTOVOLTAIC I AT EXPOSED RACEWAYS,CABLE TRAYS,COVERS AND
POWER .• ENCLOSURES OF JUNCTION BOXES,AND OTHER
WIRING METHODS.(NEC 690.31(G)(3&4)] Q 4- N Cfl
THIS EQUIPMENT FED BY MULTIPLE 1 LABEL 5 _0 ti ti
SOURCES.TOTAL RATING OF ALL
APPLY TO THE PV COMBINER BOX SUBPANELO 00O W
OVERCURRENT DEVICES,EXCLUDING (NEC 705.12(3)(3)] UTILITY MAIN (IF INTERCONNECTION AC PV PV COMBINER 0Q N
MAIN SUPPLY OVERCURRENT METER SERVICE PANEL IS MADE HERE) DISCONNECT METER BOX Z O
DEVICE,SHALL NOT EXCEED — O� U)
OO OO OO OO — �
AMPACITY F BUSBAR.
W 70W i � O �
LL 7
2 2 �
3 3
SOLAR PV SYSTEM EQUIPPED
LABEL 6 O O O O O O O ( in
WITH RAPID SHUTDOWN BUILDINGS WITH PV SYSTEMS SHALL HAVE A IF BREAKER V Q
PERMANENT LABEL LOCATED AT EACH SERVICE O O O OO
TURN RAPID SHUTDOWN EQUIPMENT LOCATION TO WHICH THE PV SYSTEMS IS USED 0 a
OR PLACARD
SWITCH TO THE ARE CONNECTED OR AT AN APPROVED READILY
"OFF"POSITION TO sour+E�crwc
SHUT DOWN PV SYSTEM VISIBLE LOCATION AND SHALL INDICATE THE LOCATION DRAWING BY:
AND REDUCE OF RAPID SHUTDOWN INITIATION DEVICES. �$ OR 0
SHOCK HAZARD Premium CAD
IN THE ARRAY [NEC 690.56(0)]
OR PLACARD
PLOT DATE:
RAPID SHUTDOWN LABEL 7 July 7, 2022
SWITCH FOR SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT
SOLAR SWITCH(NEC 690.56(C)(2)] PROJECT NUMBER.
522968
LABELING NOTES SHEET NAME
1)LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO DETERMINE EXACT LABELS
REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL
2)LABELING REQUIREMENTS BASED ON THE 2017&2020 NEC CODE,OSHA STANDARD 19010.145,ANSIZ535. REPRESENTATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED :
3)MATERIAL BASED SU TO
THE REQUIREMENTS THE AHJ. PAGE NUMBER'
MAY VARY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON 3 LINE
REVISION
4)LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND SHALL NOT BE O ���
HANDWRITTEN[NEC 110.211 DIAGRAM. 3 LINE DIAGRAM ON PV5 TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK.
Data Sheet Enphase IQ 7 and IQ 7+ Microinverters
Enphase Microinverters E RAVEN
Region:AMERICAS INPUT DATA (DC) IQ7-60-2-US Q7PLUS 72-27PVmodules
77
Commonly used module pairings' 235W-350W+ 235W-440W+
Module compatibility 60-cell/120 half-cell PV modules 60-cell/120 ha72-
only cell/144 half-c 1403 N RESEARCH WAY.BUILDING J
Maximum input DC voltage 48V 60V OREM,UT 84097
Peak power tracking voltage 27 V-37 V 27V-45V 800-377-4480
Operating range 16 V-48 V 16 V-60 V P` WWW.BLUERAVENSOLAR.COM
Min/Max start voltage 22 V/48 V 22 V/60 V
CONFIDENTIAL-THE INFORMATION
Enphase The high-powered smart grid-ready Max DC short circuit current(module Isc) 15 A 15A HEREIN CONTAINED SHALL NOT BE
Overvoltage class DC port II 11 USED FOR THE BENEFIT OF
Enphase IQ 7 MicroTM'and Enphase IQ 7+ Micro"" ANYONE EXCEPT BLUE RAVEN
p P DC port backfeed current 0 A 0 A
SOLAR NOR SHALL IT BE
IQ 7 and IQ 7+ dramatically simplify the installation process while PV array configuration 1 x 1 ungrounded array;No additlo al DC side protection required; DISCLOSED IN WHOLE OR IN PART
AC side protection requires max 2 per branch circuit TO OTHERS OUTSIDE RECIPIENTS
Microinverters achieving the highest system efficiency. ORGANIZATION.EXCEPT IN
OUTPUT DATA(AC) IQ 7 Microinverter IQ 7+Microinverter CONNECTION WITH THE SALE AND
Part of the Enphase IQ System,the IQ 7 and Peak output power 250 VA 295 VA USE OF THE RESPECTIVE
Maximum continuous output power 240 VA 290 VA EQUIPMENT..WITHOUT THE
IQ 7+ Microinverters integrate with the Enphase Nominal(L-L)volta 9 e/ran g e2 240 V/ 208 V/ 240 V/ 208 V 1 WRITTEN PERMISSION RAVEN SOLAR LLCC.. BLUE
rM TM
IQ Envoy , Enphase IQ Battery , and the Enphase 211-264 V 183-229 V 211-264 V 183-229 V
Maximum continuous output current 1.0 A(240 V) 1.15 A(208 V) 1.21 A(240 V) 1.39 A(208 V)
Enlighten" monitoring and analysis software. Nominal frequency 60 Hz 60 Hz
�' NABCEP ,
IQ Series Microinverters extend the reliability Extended frequency range 47-68 Hz 47-68 Hz CERTIFIED
AC short circuit fault current over 3 cycles 5.8 Arms 5.8 Arms _
Standards Set forth by previous generations and Maximum units per 20 A(L-L)branch circuit3 16(240 VAC) 13(208 VAC) 13(240 VAC) 11 (208 VAC) PV INSTALLATION
undergo over a million hours of power-on testing, Overvoltage class AC port III III PROFESSIONAL
AC port backfeed current 18 mA 18 mA Scott Gurney
enabling Enphase to provide an industry-leading Power factor setting 1.0 1.0 #PV-01 1719-015866
warranty Of Up to 25 years. Power factor(adjustable) 0.85 leading ..0.85 lagging 0.85 leading...0.85 lagging CONTRACTOR:
EFFICIENCY @'240 V 0208 V @240 V 0208 V BRS FIELD OPS
Peak efficiency a 97.6% ~ 97.6% 97.5% 97.3% 385.498.6700
CEC weighted efficiency 97.0% 97.0% 97.0% 97,0%
- - MECHANICAL DATA
Ambient temperature range -40°C to+65'C
Easy to Install Relative humidity range 4%to 100%(condensing)
Connector type MC4(or Amphenol H4 UTX with additional Q-DCC-5 adapter)
Lightweight and simple Dimensions(HxWxD) 212 mm x 175 mm x 30.2 mm(without bracket)
Faster installation with improved,lighter two-wire cabling Weight 1.08 kg(2.38 lbs)
Built-in rapid shutdown compliant(NEC 2014&2017) Cooling Natural convection-No fans
Approved for wet locations Yes
Pollution degree PD3
Productive and Reliable Enclosure Class II double-insulated,corrosion resistant polymeric enclosure
Optimized for high powered 60-cell/120 half-cell and 72- Environmental category/UV exposure rating NEMA Type 6/outdoor
cell/144 half-cell`modules FEATURES
More than a million hours of testing Communication Power Line Communication(PLC)
Class II double-insulated enclosure Monitoring Enlighten Manager and MyEnlighten monitoring options.
Both options require installation of an Enphase IQ Envoy.
UL listed Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break
disconnect required by NEC 690.
Smart Grid Read Compliance CA Rule 21 (UL 1741-SA)
Ready UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B, ICES-0003 Class B,
CAN/CSA-C22.2 NO,107.1-01
Complies with advanced grid support,voltage and This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC 2014,NEC
frequency ride-through requirements 2017,and NEC 2020 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems,
Remotely updates to respond to changing for AC and DC conductors,when installed according manufacturer's instructions.
grid requirements
Configurable for varying grid profiles
Meets CA Rule 21 (UL 1741-SA)
1,No enforced DC/AC ratio.See the compatibility calculator at httos//enRLa5e com/en_u_s/sRport/module_cgn atibility+
The IQ 7+Micro is required to support 72-cell/144 half-cell modules. 2.Nominal voltage range can be extended beyond nominal if required by the utility.
3.Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area.
SHEET NAME
To learn more about Enphase offerings,visit enphase.com
ENPHASE, To learn more about Enphase offerings,visit enphase.com n ENPHASE SPEC SHEET
V
2020 Enphase Energy all rights reserved.Enphase,the Enphase logo,Enphase IQ 7,Enphase IQ 7+,Enphase IQ Battery,
Enphase Enlighten,Enphase IQ Envoy,and other trademarks or service names are the trademarks of Enphase Energy,Inc Data subject to change.2020-08-12 PAGE NUMBER
SS 0
Data Sheet Enphase IQ Combiner 3
Enphase Networking MODEL NUMBER
NOW-
IQ Combiner 3 IQ Combiner 3 with Enphase IQ Envoys"printed circuit board for Integrated revenue grade PV SLUE RAVEN
X-IQ-AMI-240-3 production metering(ANSI C12.20+/-0.5%)and optional*consumption monitoring(+/-2.5%).
ACCESSORIES and REPLACEMENT PARTS (not included,order separately)
Enphase Mobile Connect`" 1403 N RESEARCH WAY BUILDING J
CELLMODEM-03(413/12-year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60 OREM,UT 84097
- CELLMODEM-01 (313/5-year data plan) microinverters.(Available in the US,Canada,Mexico,Puerto Rico,and the US Virgin Islands,
CELLMODEM-Mi_(4G based LTE-M/5-year data plan) where there is adequate cellular service in the installation area.) 800-377-4480
WWW.BLUERAVENSOLAR.COM
Enphase n_ TM Consumption Monitoring*CT Split core current transformers enable whole home consumption metering(+/-2.5%).
The LC 7 �� ! 3 "` � ' with Enphase CT-200-SPLIT CONFIDENTIAL-THE INFORMATION
Consumption monitoring is required for Enphase Storage Systems HEREIN CONTAINED SHALL NOT BE
IQ En consolidates interconnection Wireless USB adapter Installed at the IQ Envoy.For communications with Enphase Encharge'"storage and Enphase USED FOR THE BENEFIT OF
Q Combiner 3 COMMS-KIT-01 Enpower'smart switch.Includes USB cable for connection to IQ Envoy or Enphase IQ Combiner" ANYONE EXCEPT BLUE RAVEN
SOLAR NOR SHALL IT BE
equipment Into a Single enclosure and and allows redundant wireless communication With Encharge and Enpower. DISCLOSED IN WHOLE OR IN PART
Circuit Breakers Supports Eaton BR210,BR215,BR220,BR230,BR240,BR250,and BR260 circuit breakers. TO OTHERS OUTSIDE RECIPIENTS
(MI) AM1-240-3) streamlines PV and storage installations by BRK-10A-2-240 Circuit breaker,2 pole,10A,Eaton BR210 ORGANIZATION EXCEPT IN
BRK-15A-2-240 Circuit breaker,2 pole,15A,Eaton BR215 CONNECTION WITH THE SALE AND
BRK-20A-2P-240 Circuit breaker,2 pole,20A,Eaton BR220 USE OF THE RESPECTIVE
providing a consistent, pre-wired solution for EQUIPMENT.WITHOUT THE
EPLC-01 Power line carrier(communication bridge pair),quantity-One pair WRITTEN PERMISSION OF BLUE
residential applications. It offers U to f
pP p our XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 3(required for EPLC-01) RAVEN SOLAR LLC.
2-pole Input circuits and Eaton BR series XA-ENV-PCBA-3 Replacement IQ Envoy printed circuit board(PCB)for Combiner 3
busbar assembly.
ELECTRICAL SPECIFICATIONS NABCEP
Rating Continuous'duty CERTIFIED
System voltage 120/240 VAC,60 Hz PV INSTALLATION
Eaton BR series busbar rating 125 A PROFESSIONAL
Scott Gurney
Max.continuous current rating(output to grid) 65A #PV-011719-015866
Max.fuse/circuit rating(output) 90A CONTRACTOR:
Branch circuits(solar and/or storage) Up to four 2-pole Eaton BR series Distributed Generation(DG)breakers only(not included) BRS FIELD OPS
Smart Max.continuous current rating(input from PV) 64A
385.498.6700
"
Includes IQ Envoy for communication Max.total branch circuit breaker rating(input) 80A of distributed generation/90A with IQ Envoy breaker included
•
and control Production Metering CT 200 A solid core pre-installed and wired to IQ Envoy
• Flexible networking supportsWi-Fi, MECHANICAL DATA
Ethernet,or cellular
Dimensions(WxHxD) 49.5 x 37.5 x 16.8 cm(19.5"x 14.75"x 6.63").Height is 21.06"(53.5 cm with mounting brackets).
y Optional AC receptacle available for PLC Weight 7.5 kg(16.5 lbs)
bridge
Ambient temperature range -40°C to+46°C(-400 to 1150 F)
Provides production metering and optional
consumption monitoring Cooling Natural convection,plus heat shield
Enclosure environmental rating Outdoor,NRTL-certified,NEMA type 3R,polycarbonate construction
Wire sizes 20 A to 50 A breaker inputs: 14 to 4 AWG co
Simple 60 A breaker branch inut: 4 to 1/0 AWG pper conductors
p p copper conductors
• Main lug combined output: 10 to 2/0 AWG copper conductors
• Reduced size from previous combiner Neutral and ground: 14 to 1/0 copper conductors
Always follow local code requirements for conductor sizing.
• Centered mounting brackets support single Altitude To 2000 meters(6,560 feet)
stud mounting
. Supports back and side conduit entry INTERNET CONNECTION OPTIONS
Integrated Wi-Fi 802.11b/g/n
• Up to four 2-pole branch circuits for 240 VAC
plug-in breakers(not included) Ethernet Optional,802.3,Cat5E(or Cat 6)UTP Ethernet cable (not included)
• 80 A total PV or storage branch circuits Cellular Optional,CELLMODEM-01 (3G)or CELLMODEM-03(4G)or CELLMODEM-M1(413 based LTE-M)
(not included)
COMPLIANCE
Reliable Compliance,Combiner LIL 1741, CAN/CSA C22.2 No.107.1,47 CFR,Part 15,Class B,ICES 003
Production metering:ANSI C12.20 accuracy class 0.5(PV production)
• Durable NRTL-certified NEMA type Compliance,IQ Envoy UL 60601-1/CANCSA 22.2 No.61010-1
3R enclosure
UL • Five-year limited warranty
UL listed To learn more about Enphase offerings,visit enphase com SHEET NAME
LISTED C,2018En Enphase SPEC SHEET
p gy,All rights reserved.Enphase,the Enphase logo,IQ Combiner 3,and other trademarks or service names are the
=' E N P H r --04 PAGE NUMBER REVISION
of Enphase Energy,Inc E N P H A S Ex
To learn more about Enphase offerings,visit enphase com r..� 04
SS 0
Nor-
BLUE RAVEN
powered by
MECHANICAL SPECIFICATION 1403 N.Research Way
Orem,UT 84097
Format 74.0 in x 41.1in x 1.26in(including frame)
(1879mm x 1045mm x 32mm)
Weight 48.51bs(22.0 kg) '
Q.,108s"""' -� ua-,�ate' 800.377.4480
Front Cover 0.13in(3.2moll thermally pre-stressed glass with - ! - ,.- WWW.BLUERAVENSOLAR.COM
anti-positefilm chnobgy 4; W� n„°oie,,4sm CONFIDENTIAL-THE INFORMATION
Back Cover Composite �� HEREIN CONTAINED SHALL NOT BE
Frame Black anodized aluminum USED FOR THE BENEFIT OF ANYONE
Cell 6 x 22 monocrystanine Q.ANTUM solar half cells ® "`"0 s EXCEPT BLUE RAVEN SOLAR NOR
Junction Box 2.09-3.98inx1.26-2.36inx0.59-0.71in -_ SHALL IT BE DISCLOSED IN WHOLE OR
(53-101mm x 32-60mm x 15-18mm),IP67,with bypass diodes IN PART TO OTHERS OUTSIDE
Cable 4mm2Solarcablet(+)>49.2in(1250mm),I-)>-49.2in(1250mm) a.a RECIPIENTS ORGANIZATION,EXCEPT
Connector Staubli MC4;IP68 IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
Q -„45m,T{c Ta ,as� WITHOUT THE WRITTEN PERMISSION
OF BLUE RAVEN SOLAR LLC.
• . Quality
Controlled PV ELECTRICAL CHARACTERISTICS
POWER CLASS
N AB C E P
.385 390 395 400 405
1 I
TWRh.rFltaFld MINIMUMPERFORM ✓ W
ANCEATSTANDARD TEST CONDITIONS. jPOER 70LERANCE+5W -Ow`
Power at MPP=
P [ ] 385 390
CERTIFIED
399
� www.tuv.ppm h,� w �
1D 1111232625 Short Circuit Current'- tl
E IES [A] 1104 1107
_ .. __._._-._-.______
YR E Open Circuit Voltage- V.,;, [`✓] 45.19 45.23 45.27 tae sa PV INSTALLATION
��Z5
Current at MPP 10 59 1065 10n to as PROFESSIONAL
`tOElRAM6.al Voltage at MPPy,. [VI 36.36 36.62 36.88 ... c
_ 373.,
9 [%] ?19.6 >_199 >201 - Scott Gurney
' Efficiency! #PV-01 Gu-015866
A L rr� MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS,NMOP
USA
Warranty 21 Q CELLS Power at MPP P,;,, [w] 288 8 292.6 296.3 303,8_
P.o6ungPMorme°ce YIeIC3acurity E Short Circuit Current 9.0 - CONTRACTOR:
Isc IA] 8.90 8.92 8.95
Open Circuit Voltage v [V] 42.62 42.65 42.69 42.76- BRS FIELD OPS
BREAKING THE 20%EFFICIENCY BARRIER 2 Current at MPPss 385-498-6700
[A] 8.35 8.41 8.46
Q.ANTUM DUO Z Technology with zero gap cell layout Voltage At MPP V„N, [v] 34.59 34.81 35.03
35.46
boosts module efficiency up t0 20.9%. 'Measurementtolerances P..,.,.3%,Imo',V--±5%at STC:1000 W/m'.25x2°C.AM 1.5 according to IEC 60904-3.'SOO W/m2.NMOT,spectrum AM L5
O CELLS PERFORMANCE WARRANTY - PERFORMANCE AT LOW IRRADIANCE
THE MOST THOROUGH TESTING PROGRAMME IN THE INDUSTRY r.
-
QCELLS is the first solar module manufacturer to pass the most comprehen- At least s8%of nominal power during
a y - first year.Thereafter max.0.5% 'z
$6 sive quality programme in the industry:The new"Quality Controlled PV"of °o s degradation per year.At least
91 5% y _
the independent certification institute TUV Rheinland. of nominal power up to 10 years.At -
'-9 least 86%of nominal power up to /f
w
pz 'D -_- _--- 25 Years.
a
INNOVATIVE ALL-WEATHER TECHNOLOGY o x
i1 0 86 All data within measurement tolerant- N
ao 0
Optimal yields,whatever the weather with excellent � es.Full warranties m accordance with � .aa � .aR -- � N
the warranty terms of the Q CELLS oinncE;w;R.=}
low-light and temperature behavior. o sales organisation of your respective '"i1EA a
.o country.
TEMPERATURE COEFFICIENTS
u rEaas Typical module performance under low irradiance conditions in
ENDURING HIGH PERFORMANCE '�
comparison to STC conditions(25°C 1000 W/m2)
Long-term yield security with Anti LID Technology,Anti PID
TS
Technology',Hot-Spot Protect and Traceable Quality Tra.Qr".
Temperature coefficient of l
P c [%/K] +0.04 Temperature Coefficient of V p [%/K]
EXTREME WEATHER RATING Temperature Coefficient of PM„ y [%/K] -0.34 Nominal Module Operating Temperature NMOT [°F] 109±5.4(43±3°C)
(Z� High-tech aluminum alloy frame,certified for PROPERTIES FOR SYSTEM DESIGN -
7' high snow(5400 Pa)and wind loads(4000 Pa)_
MaximumSystem Voltage Vss [V] 1000(IEC)/1000(UL) PV module classification Class II -
,� A RELIABLE INVESTMENT Maximum Series Fuse Rating [A DC] 20 Fire Rating based on ANSI%UL 61730 TYPE 2m
Q Max.Design Load.Push/Pull' [lbs/ft2] 75(3600 Pa) 55(2660 Pa) Permitted Module Temperature -40°F up to+185°F
Inclusive 25-year product warranty and 25-year on Continuous Duty
(-40*C up to 85 -F
linear performance Warfantyz. Max.Test Load,Push/PuIF [Ibs/ft2] 113(5400 Pa)/84(4000 Pa)
3See Installation Manual
B allSBAR 12 aus"Al 'APT test conditions according to IEC/TS 62804-1:2015.method A(-1500 V,96h) QUALIFICATIONS AND CERTIFICATES CELL TECHNOLOGY CELLTECHNOLOGY 2See data sheet onrear for further information, PACKAGING
UL6ll3pnn compiia fG 1, r�/� Sa, �� _ DRAWING BY:
lEc 6yC hd6.tEC 30 Rh-nlanti I�t/"1 �_Q
IEC 61215:2016.IEC 61730.2016. Q
THE IDEAL SOLUTION FOR: US Patent 9.893,2151 ells). m ( Dull.. °. Horizontal 76.4in 43.3m 48.Oin 16561bs 24 24 32
CUS \ ° n packaging 1940mm 1100mm 1220mm 751 kg pallets pallets modules n
residential buildings
PLOT DATE:
Not.:Installation instructions must be followed.Seethe installation and operating manual or contact our technical service department for further information on approved installation and use of
this product.
CELLSHanwhaoCELLSA Inc. PROJECT NUMBER'
Engineered Irl Germany 40C SP _)r zll U ...CA 92618,JSAI TEL-1 949 748 59 96 1 EMAiL,n aus
quiry� .q-cells.coml WEB www.q-cells-us
SHEET NAME:
SPEC SHEET
REVISION: PAGE NUMBER:
SS
BLUE RAVEN
Product data sheet DU221 RB Ordering Sh�p1lip-9 del;J�13 1403 N.Research Way
charack"ris tics Safety switch, general duty, non fusible, 30A, Cau.WY 001 06-D&D I U SW,.NE I MA3R,30-1 200A Orem,UT 84097
------------ ------------ 800.377.4480
2 poles, 3 hp, 240 VAC, NEMA 3R, bolt-on Discount Schedule DEIA WWW.BLUERAVENSOLAR.COM
provision GTIN 007S$901490340 ----------
CONFIDENTIAL-THE INFORMATION
Nbc of unds in pkq 1 HEREIN CONTAINED SHALL NOT BE
Product availabilirty Slock-Normally stocked in distinburtion facility P7 ackage hi I iLbS) ...... i�I it�6S.1,'2' USED FOR THE BENEFIT OF ANYONE
------------------- EXCEPT BLUE RAVEN SOLAR NOR
Yes SHALL IT BE DISCLOSED IN WHOLE OR
IN PART TO OTHERS OUTSIDE
Country r �'o fo rigari MX RECIPIENTS ORGANIZATION,EXCEPT
IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
Packing UnIs WITHOUT THE WRITTEN PERMISSION
-6--t Ty��-of ge-1, OF BLUE RAVEN SOLAR LLC.
Price' : 177.00 USD
Package 1 Height 5,40in03-716cmill
7-80 in(19$12 cm) 'NAB—�P
Package I Length 9,90 in(25,146 cmil
U,mt-Type-, of I P I ac I k I age 2 111 CA I R CERTIFIED
NumW of Units in Pac"ge 2 PV INSTALLATION
Package 2 Weight 24,60%b(US)(11.158 kq) PROFESSIONAL
_16.i6 (27.432 ort) Scott Gurney
—------- #PV-01 1719-015866
10,50 in(215,67 cim
Package 2 Length 2180 in 460 452 cm) CONTRACTOR:
rwt Type of P at;kaq a 3 PAt BRS FIELD OPS
Nutirtw of Units Package 3 160 385-498-6700
Package 3 Weight 814.00 lb(US)(369 224 kg)
Package 3 Height 4 6-50 in(118.11 cm
Package 3 width 40,00 at(1016 cm)
Main Package 3 Length 48,00.n(121 92 Cm)
Product Single Throw Safety Sw,"
Current Rating 30 A Offer
Certifications UL listed Re E2875 Sustainable offer status Green Premium product
Enclosure Rating NEMA 3R s Catorriza proposition 65 WARNING This product can expose you to eh is including:Lead and lead compounds,wh4ch
is krKywn to the State of Calftmia to cause carr and borth defects or other reprod-idive rtarm For
Citsconnact Type Nion-fuistble disconnect svivich
morti information go to www,P65WarrwVs ca gov,
Factory Installed Neutral None I
.......... REACh Regulation
nq Type Surface R.EA-Ch I fte.e of,SV I HC I'll Yes
.I ------
Number of Poles 2 a ........... ...... .. ...................
—–---------- -------------------- EU RoHS Directive Comp ant
E Connecoon Lugs
buit-y–Ra-6h" General duty Toxic heavy metal free Yes
VoUge Raling 240 V AC Mercury free Yes
Wire Size AWG 14.AWG 6 copper
RoHS exemption inloirrvahon
AWG 12,.AWG 6 aluxviinium
CNna RoHS Regulation
Pro-active China RoHS declaration(out of China RoHS,!,,l scope)
mplernentay E n vi mom en W Ossclosui r e
Cor
Stuu
I arQA withstand 200 kA Q PVC free Yes
Maximum Horse Power Rating 3 rip 240 V AC 60 Hz I phase NEC 430 52
Tightening Tongue 30 ItIfin(3.39 N.m)0(X7 0.02 W(208. .13.3 mfrvl)AWG 14.AWG 6)
. .. .... ...........
hiirigh
t 9,63 in(244.60 own) Warranhj 18 ninths
Width 7.75 in(196.85 nwn)
3.75 in(95,25 mm}
SHEET NAME:
P".0 1i'_-drxspyrr_uvo'.4,w4 W246 3 :v t "two niatrf.,_txa
SPEC SHEETS
REVISION: PAGE NUMBER:
0 SS
wall SUN ' BLUE RAVEN
1 1 E
.
me 1 FRAMESFM1 1403 N.Research Way
■ . 1 MI RA L Trem,UT I� INSTALLATION GUIDE I PAGE 0800377.44807
-
------ ------ -
_... -
r. - CONFIDENTIAL- INFORMATION
-"-- 1 HEREIN CONTAINED SHALL NOT BE
_ USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
IN PART TO OTHERS OUTSIDE
i RECIPIENTS ORGANIZATION,EXCEPT
{ j
_ N CONNECTION WITH THE SALE AND
L = USE OF THE RESPECTIVE EQUIPMENT,
boo
WITHOUT THE WRITTEN PERMISSION
OF BLUE RAVEN SOLAR LLC.
T i
i _ I A SC FE
i CERTIFIED
s
PV INSTALLATION
PROFESSIONAL
__-----------------___.._.__ _____--- Scott Gurney
E-W BONDING PATH: #PV-°,1719-°'5866
E-W module to module bonding is accomplished CONTRACTOR:
rBRS FIELD OPS
with 2 pre-installed bonding pins which engage
385-498-6700
—' on the secure side of the MicrorailTM and splice.
7
-
_ _ __ _- - T - -- - T _ ---- -- _. _
1
I �
j{ jg _
?
T 1
N-S BONDING PATH:
a
N-S module to module bonding is
accomplished with bonding clamp with 2 integral
bonding pins.
- DRAWING BY:
LUG D TAIL & TOR'jUE 1i�,�;0 L L'G DETA1L c_ I O�R'QUE C' ��.�1�
DETAIL � � INFO
t
Ilsco Lay-In Lug (GBL-4DBT) Ilsco Flange Lug(SGB-4) Wiley WEEBLug (6.7) r � �� PLOT DATE
• 10-32 mounting hardware 0 1/4" mounting hardware 1/4" mounting hardware — L
• Torque = 5 ft-lb • Torque = 75 in-lb • Torque = 10 ft-lb PROJECT NUMBER
• AWG 4-14-Solid or Stranded 0 AWG 4-14-Solid or Stranded 0 AWG 6-14-Solid or Stranded
TRIMRAIL BONDING PATH:
NOTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION Trimrail to module bonding is accomplished with SHEET NAME:
System bonding is accomplished through modules. System grounding accomplished by attaching bonding clamp with integral bonding pin and SPEC SHEET
a ground Lug to any module at a Location on the module specified by the module manufacturer. bonding T-bolt. REVISION: PAGE NUMBER
---- SS
sell
i
M SUN
UL
me
COMPLIANCEi i BLUE RAVEN CODE
0 11F M FRAM
N I MICRORAIL I N STA L LAT I D G D I D , PAGE 14 Orem UT 84093 N.Research�aY
800.377.4480
--——————————————————————————————————————————————————————————————————————————————————————————————————————————————————————————————————————————— WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL-THE INFORMATION
SYSTEM LEVEL FIRE CLASSIFICATION HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
The system fire class rating requires installation in the manner specified in the performance is inherent in the SFM design and no additional mitigation measures SHALLITBTTOOT OTHERS OUTSIDE� IN PART TO OTHERS OUTSIDE
SUNFRAME MICRORAIL (SFM) Installation Guide. SFM has been classified to are required.The fire classification rating is valid for any roof pitch.There is no INRECIPIENTSONNETION WITH
D
IN CONNECTION WITH THE SALE AND
the system level fire portion of UL 1703. This UL 1703 classification has been required minimum or maximum height limitation above the roof deck to maintain WITHOUSE OF T
THEWRITT N EQUIPMENT,
WITHOUT THE WRITTEN PERMISSION
incorporated into the UL 2703 product certification. SFM has achieved Class A, the Class A, B & C fire rating for SFM.SUNFRAME MICRORAUmcomponentsshall OF BLUE RAVEN SOLAR LLC.
B & C system level performance for low slope & steep sloped roofs when used be mounted over a fire resistant roof covering rated for the application.
in conjunction with type 1 and type 2 modules.Class A, B & C system level fire
E
CERTIFIED
®_ PV INSTALLATION
Module Type I Roof Slope 1 System Level Fire Ratina Microrail Direction = Module Orientation Mitigation Required
PROFESSIONAL
# �
Type 1 and Type 2 I Steep Slope & Low Slope Class A, B & C I East-West I Landscape OR Portrait None Required Scott Gurney
#PV-011719-015866
CONTRACTOR:
OPS
UL2703 TEST MODULES gas 4198 6 00
See pages V and W for a list of modules that were electrically and mechanically tested or
qualified with the SUNFRAME MICRORAIL (SFM) components outlined within this Installation Guide.
• Maximum Area of Module = 27.76 sqft
• UL2703 Design Load Ratings:
a) Downward Pressure - 113 PSF / 5400 Pa
b) Upward Pressure - 50 PSF / 2400 Pa
C) Down-Slope Load - 21.6 PSF / 1034 Pa
• Tested Loads:
a) Downward Pressure - 170 PSF / 8000 Pa
b) Upward Pressure - 75 PSF / 3500 Pa
C) Down-Slope Load - 32.4 PSF / 1550 Pa
• Maximum Span = 6ft DRAWING BY:
• Use with a maximum over current protection device OCPD of 30A
• System conforms to UL Std 2703, certified to LTR AE-001-2012
PLOT DATE:
• Rated for a design load of 2400 Pa / 5400 Pa with 24 inch span
• PV modules may have a reduced load rating, independent of the SFM load rating. Please consult
the PV module manufacturer's installation guide for more information PROJECT NUMBER:
• Down-Slope design load rating of 30 PSF/ 1400 Pa for module areas of 22.3 sq ft or less
SHEET NAME:
SPEC SHEET
REVISION: PAGE NUMBER:
---- SS
SUN
NNESFM FSATESTBLUE RAVEN
■■ ' I C I TM 1403 N Research Way
____________'____________________ INSTALL__A_T__1.0____G__G__I E , PAGE Orem.UT 84097
800.377.4480
-- - �' WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL-THE INFORMATION
Manufacture Module Model/Series HEREIN CONTAINED SHALL NOT BE
Manufacture Module Model/Series Manufacture Module Model/Series USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
Aleot SHALL IT BE DISCLOSED IN WHOLE OR
P-Series — a
ECO$olargy Orion �OOO&Apollo IO �OOO IN PART TO OTHERS OUTSIDE
_ _...._ LGXXXN2T-A4 RECIPIENTS ORGANIZATION,EXCEPT
IN CONNECTION WITH THE SALE AND
CHSM6612P,CHSM6612P/HV,CHSM6612M, ET Solar ET M672BHxxxTW LGxxx(A1C/E1C/E1K/N1C/N1K/N2T/N2W/ USE OF THE RESPECTIVE EQUIPMENT.
Astroner — ,
WITHOUT THE WRITTEN PERMISSION
gy CHSM6612M/HV,CHSM6610M (BL)(BF)/(HF), FreeVott Mono PERC Q1C/Q1K/S1C/S2W)-A5 OF BLUE RAVEN SOLAR LLC.
CHSM72M-HC
GCL GCL-P6 & GCL-M6 Series LGxxxN2T-B5 -
_. _ LGxxxN1K-B6
NASCE_P
LGxxx(A1C/M1C/M1K/N1C/N1K/Q1C/Q1K/
AXN6M610TAXN6P610T, TD AN3, ,
Auxin Hansol TD-AN4CERTIFIED
AXN6M612T&AXN6P612T UB-AN1,UD-AN1
LG Electronics , OAC/QAK)-A6
AXlblackpremium 60(35mm), Hetiene 36M,60M,60P,72M & 72P Series PV INSTALLATION
® LGxxx(N1C/N1K/N2T/N2W)-E6 PROFESSIONAL
_..
AXlpower 60(35mm),
Axitec AXlpower 72 (40mm), HT60-156(M) (NDV)(-F), Scott Gurney
HT Solar LGxxx(N1C/N1K/N2W/S1C/S2W)-G4 -011719-015866
aPv
HT 72-156(M/P) LGxxxN2T-15
__ =-
AXlpremium 60(35mm), ---"" - ----
_----- --.-_"""-- ----___.__ _ CONTRACTOR:
KG,MG,TG,RI,RG,TI,MI,HI & KI Series LGxxx(N1K/N1W/N2T/N2W)-L5 BRS FIELD OPS
AXlpremium 72 (40mm). Hyundai
HiA SxxxHG
LGxxx(N1C/Q1C/Q1K)-N5 385-498-6700
A tos DNA 120-(BF/MF)26 _ ITEK -_ _ ___ .._ __ __ __ _ __
p
IT iT HE & IT SE Serres
xx /N_2W/01C/01K)-
V5DNA 144-(BF/MF)26 ------
Japan
Solar JPS-60&JPS-72 Series LR4-60(HIB/HIH/HPB/HPH)-xxxM
BVM6610,
Boviet
BVM6612 JAP6 60-xxx,1AM6-60-xxx/SI,JAM6(K)-60/ LR4-72(HIH/HPH)-xxxM
Y
BYD P6K & MHK-36 Series xxx,1AP6(k)-72-xxx/4BB,JAP72SYY-xxx/ZZ, LR6-60(BP/HBD/HIBD)-xxxM (30mm)
LR6-60(BK)(PE)(HPB)(HPH)-xxxM (35mm)
JAP6(k)-60-xxx/4BB,JAP60SYY-xxx/ZZ,
CS1(H/K/U/Y) MS
JA Solar JAM6(k)-72-xxx/ZZLONGi LR6-60(BK)(PE)(PB)(PH)-xxxM (40mm)
,1AM72SYY-xxx/ZZ,
CS3(K/L/U),CS3K-MB-AG,CS3K-(MS/P) LR6 72(BP)(HBD)(HIBD) xxxM(30mm)
Canadian Solar CS3N-MS,CS3U-MB-AG,CS3U-(MS/P),CS3W ! JAM 6(k)-60-xxx/ZZ,JAM 60SYY-xxx/ZZ.
i.YY:01,02,03,09,10 LR6-72(HV)(BK)(PE)(PH)(PB)(HPH)-xxxM
CS5A-M,CS6(K/U),CS6K-(M/P),CS6K-MS
n.ZZ (35mm)
CS6P-(M/P),CS6U-(M/P),CS6V-M,CS6X-P SC,PR BP,HIT,IB,MW,MR
LR6 72(BK)(HV)(PE)(PB)(PH)-xxxM (40mm)
entroso ar America C Serres& E Series JKM &JKMS Series Mission Solar JinkEnergy MSE Series
o Eagle JKMxxxM __ _".
CT2xxMxx 01,CT2xxPxx 01, Mitsubishi MJE & MLE Series
JKMxxxM-72HL-V �� -- --"-- -- -"
ertainTeed
CTxxxMxx 02,CTxxxM 03, ------- Neo Solar Power Co. D6M & D6P Series
CTxxxMxx-04,CTxxxHC11-04 Kyocera KU Series
__"_ — ---------- ---"- -- — -
Dehui DH-60M
DRAWING BY:
PLOT DATE:
• Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx" PROJECT NUMBER:
• Items in parenthesis are those that may or may not be present in a compatible module's model ID
• Slashes 7" between one or more items indicates that either of those items may be the one that is present in a module's model ID SHEET NAME:
• Please see the SFM UL2703Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM SPEC SHEET
• SFM Infinity is not compatible with module frame height of Less than 30mm and more than 40mm. See Module Mounting section, page L for further information
REVISION: PAGE NUMBER:
SS
sell SUNBLUE RAVEN
00811 FRAME
�� 1 N STA FIAT G�� G G I D E ; PAGE 1403 N Research Way
■ ■ MICRORAIL Orem,UT 84097
800.377.4480
WWW.BLUERAVENSOLAR.COM
CONFIDENTIAL THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
Manufacture Module Model /Series Manufacture Module Model /Series Manufacture Module Model /Series EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
IN PART TO OTHERS OUTSIDE
TwinPeak Series SC,SC RECIPIENTS ORGANIZATION,EXCEPT
B,SC B1,SC B2 IN CONNECTION WITH THE SALE AND
VBHNXXXSAIS & SA16, Tesla USE OF THE RESPECTIVE EQUIPMENT,
TwinPeak 2 Series TXXXS WITHOUT THE WRITTEN PERMISSION
VBHNxxxSA17 & SA18, ___ _.._-_ - ___
OF BLUE RAVEN SOLAR LLC.
TwinPeak 2 BLK2 Series PA05,PD05,DD05,DE06,DD06,PE06,
VBHNxxxSA17(E/G) & SA18E, REC(cont.)
Panasonic TwinPeak 2S(M)72(XV) ! Trina PD14,PE14,DD14,DE09.05,DE14,DE15,
VBHNxxxKA01 & KA03 & KA04,
�NAECEP''
V13HNxxxZA01,VI3HNxxxZA02, TwinPeak 3 Series(38mm) PE15H
__----------- _.. ____._____ ____ _.. ___. CERTIFIED
VBHNxxxZA03,VBHNxxxZA04 TP4(Black) UP-MXXXP(-B), _...
_-_- ----_ _-_ _ U solar
P PV INSTALLATION
Renesola Vitrus2 Series & 156 Series UP-MxxxM( B)
Peimar SGxxxM (FB/BF) __ _. _ _ ____ . -----_. -_---._ __- -- __------. __ _. PROFESSIONAL
Risen RSM72-6(MDG) (M) RSM60 6 D7MxxxH7A,D7(M/K)xxxH8A Scott Gurney
Phono Solar _ PS 60,PS 72
- S Energy SN72 & SN60 Series(40mm) URE FAKxxx(C8G/E8G),FAMxxxE7G-BB aPv-o1n1s-otssss
Prism Solar P72 Series _ _.____..______ __.._..--. .m_..._ ----_,_ __.,___.__ _._._ -________ _.___-_--___
Seraphim SEG-6 & SRP-6 Series FAMxxxE8G(-BB) CONTRACTOR
Plus,Pro,Peak,G3,G4,G5,G6(+),G7,G8(+) --__-_._ __ _.m_._._.__ �__.______ ___---__-- - -___-- .--_.__---_----___.
_ .. __.______ _-------..__--- .__ __-- ------_------ _-- _ -._- _ BRS FIELD OPS
Sharp NU-SA& NU-SC Series Eldora, 385-498-6700
Pro,Peak L-G2,L-G4,L-G5,L-G6,L-G7
SLA, SLG,BC Series & SlLxxx(BL/NL/NT/HL/ Vikram Solivo,
O.PEAK DUO BLK-G6+ Silfab Somera
O.PEAK DUO BLK-G6+/TS ML/BK/NX/NU/HC) -- - - -- - --
PowerXT xxxR (AC/PD/BD) Waaree AC&Adiya Series
O.PEAK DUO (BLK)-G8(+) _ ___ __ .
O.CellsPowerXT-xxxC-PD Wlnaico WST&WSP Serres
Solaria
O.PEAK DUO L-G8.3/BFF _-_--
O.PEAK DUO(BLK) ML G9(+) PowerXT-xxxR-PM (AC) Yingll YGE &YLM Series
O.PEAK DUO XL-G9/G9.2/G9.3 Sunmodule Protect, ZN Shine ZXM6 72
SolarWorld
Q.PEAK DUO (BLK) ML-G10(+) Sunmodule Plus
O.PEAK DUO XL-G(10/10.2/10.3/10.c/10.d) Sonali SS 230-265
Alpha (72) (Black)(Pure) Suntech STP
N-Peak(Black) Suniva MV Series & Optimus Series
N-Peak 2 (Black) Sun Edison/Flextronics F-Series,R-Series & FLEX FXS Series
REC
__- --
PEAK Energy Series
SunPower X-Series,E-Series & P-Series
PEAK Energy BLK2 Series _.-- -_ --.__. ._______ -
TP572,TP596,TP654,TP660,
PEAK Energy 72 Series Talesun
TP672,HiporM Smart
DRAWING BY:
PLOT DATE:
PROJECT NUMBER:
• Unless otherwise noted,all modules listed above include all wattages and specific models within that series. Variable wattages are represented as "xxx"
• Items in parenthesis are those that may or may not be present in a compatible module's model ID SHEET NAME:
• Slashes 7" between one or more items indicates that either of those items may be the one that is present in a module's model ID SPEC SHEET
• Please see the SFM UL2703Construction Data Report at Unirac.com to ensure the exact solar module selected is approved for use with SFM
• SFM Infinity is not compatible with module frame height of less than 30mm and more than 40mm. See Module Mounting section, page L for further information REVISION: PAGE NUMBER:
---- SS ]
n tertek AUTHORIZATION TO MARK ntertek AUTHORIZATION TO MARK BLUE RAVEN
Toted Quaft.Assurl TOW 1403 N.Research Way
Orem,UT 84097
This authorizes thea application of the Certification Marks shown below to the models described in the Products This authorizes the application of the Certification Marks shown below to the models described in the Products 8ERAV.4480
pp ( ) ( ) pp Mark(s) Product(s) WWW.BLUERAVENSOLAR.COM
Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing
Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
Report. Report. USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
This document is the property of Intertek Testing Services and is not transferable. The certification marks may be This document is the property of Intertek Testing Services and is not transferable. The certification marks may be SHALL IT BE DISCLOSED IN WHOLE OR
P P Y 9 ( ) Y P P Y g ( ) Y IN PART TO OTHERS OUTSIDE
applied only at the location of the Party Authorized To Apply Mark. applied only at the location of the Party Authorized To Apply Mark. RECIPIENTS ORGANIZATION,EXCEPT
IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
WITHOUT THE WRITTEN PERMISSION
Applicant: Unirac, Inc Manufacturer: Applicant: Unirac, Inc Manufacturer: OF BLUE RAVEN SOLAR LLC.
Address:
1411 Broadway Blvd NE Address: Address: 1411 Broadway Blvd NE Address: NAB CEP
Albuquerque, NM 87102 Albuquerque, NM 87102
CERTIFIED
Country: USA Country: Country: USA Country:
PV INSTALLATION
Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL
Report Issuing Office: Intertek Testing Services NA, Inc., ake Forest CA Report Issuing Office: Intertek Testing Services NA, Inc., Lake Forest, CA Scott Gurney
t #{ - p�, �(J #PV-011719-015866
AAf
Control Number: 5003705 Authorized by: Control Number: 5014989 Authorized by: l`
foF L. Matthew Snyder, Certification Manager for L. Matthew Snyder, Certification Manager CONTRACTOR:
BRS FIELD OPS
385-498-6700
C( Us c %,US
Intertek Intertek
This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number.
This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are
limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned
by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is
restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must
first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the
agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect.
Intertek Testing Services NA Inc. Intertek Testing Services NA Inc.
545 East Algonquin Road,Arlington Heights, IL 60005 545 East Algonquin Road,Arlington Heights, IL 60005
Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672
Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat-
Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:29May2019] Standard(s): Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:29May2019]
PV Module and Panel Racking Mounting System and Accessories [CSA TIL No.A-40:2020] PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:20201
Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2021NOV29 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2021NOV29 DRAWING BY:
Brand Name: Unirac Brand Name: Unirac
PLOT DATE:
Models: Unirac SFM I jModels: Unirac SFM
PROJECT NUMBER:
SHEET NAME:
ATM for Report 102393982LAX-002 Page 1 of 4 ATM Issued: 7-Jan-2022 ATM for Report 102393982LAX-002 Page 2 of 4 ATM Issued: 7-Jan-2022 SPEC SHEET
ED 16.3.15(16-Oct-2021)Mandatory ED 16.3.15(16-Oct-2021)Mandatory
REVISION: PAGE NUMBER:
-- SS
intertek AUTHORIZATION TO MARK Lntertek AUTHORIZATION TO MARK BLUE R N
Toth Toth Quaft.AsSuli 1403 N.Research Way
Orem,UT 84097
This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) 8WWW.BLUERAV.4480
RAVENSOLAR.COM
Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing
Report. This authorization also applies to multiple listee models Identified on the correlation page of the Listing Report. This authorization also applies to multiple listee models Identified on the correlation page of the Listing CONFIDENTIAL-THE INFORMATION
p pp p ( ) � p g g p pp P ( ) � P 9 g HEREIN CONTAINED SHALL NOT BE
Report. Report. USED FOR THE BENEFIT OF ANYONE
EXCEPT BLUE RAVEN SOLAR NOR
This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be This document is the property of Intertek Testing Services and is not transferable. The certification marks ma be SHALL IT BE DISCLOSED IN WHOLE OR
( ) y IN PART TO OTHERS OUTSIDE
applied only at the location of the Party Authorized To Apply Mark. applied only at the location of the Party Authorized To Apply Mark. RECIPIENTS ORGANIZATION,EXCEPT
IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
WITHOUT THE WRITTEN PERMISSION
Applicant: Unirac, Inc Manufacturer: Applicant: Unirac, Inc Manufacturer: OF BLUE RAVEN SOLAR LLC.
Address:
1411 Broadway Blvd NE Address: Address: 1411 Broadway Blvd NE Address: 'NAEP
Albuquerque, NM 87102 Albuquerque, NM 87102
CERTIFIED
Country: USA Country: Country: USA Country:
PV INSTALLATION
Party Authorized To Apply Mark: Same as Manufacturer Party Authorized To Apply Mark: Same as Manufacturer PROFESSIONAL
Report Issuing Office: Intertek Testing Services NA, Incka�
Lake Forest, CA Report Issuing Office: Intertek Testing Services NA, Inc., Lake Forest, CA Scott Gurney
—1 #PV-011719.015866
Control Number: 5019851 Authorized by: Control Number: 5021866 Authorized by:
f r L. Matthew Snyder, Certification Manager for L.Matthew Snyder, Certification Manager CONTRACTOR:
AIIIIIIIIIIIIIIIIIIIIIII BRS FIELD OPS
385-498-6700
Calus C ,US
Intertek Intertek
This document supersedes all previous Authorizations to Mark for the noted Report Number. This document supersedes all previous Authorizations to Mark for the noted Report Number.
This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are
limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned
by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of intertek's Certification mark is by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is
restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must
first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the
agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect.
Intertek Testing Services NA Inc. Intertek Testing Services NA Inc.
545 East Algonquin Road,Arlington Heights, IL 60005 545 East Algonquin Road,Arlington Heights, IL 60005
Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672
Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat-
Standard(s):
Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R: Standard( )
29May2019] s : Plate Photovoltaic Modules and Panels [UL 2703:2015 Ed.1+R:29May2019]
PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:20201 PV Module and Panel Racking Mounting System and Accessories[CSA TIL No. A-40:2020]
Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2021 NOV29 Product: Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2021 NOV29 DRAWING BY:
Brand Name: Unirac Brand Name: Unirac
PLOT DATE:
Models: Unirac SFM Models: Unirac SFM
PROJECT NUMBER:
SHEET NAME:
ATM for Report 102393982LAX-002 Page 3 of 4 ATM Issued: 7-Jan-2022 ATM for Report 102393982LAX-002 Page 4 of 4 ATM Issued: 7-Jan-2022 SPEC SHEET
ED 16.3.15(16-Oct-2021)Mandatory ED 16.3.15(16-Oct-2021)Mandatory
REVISION: PAGE NUMBER:
---- SS
Listing Constructional Data Report (CDR) witertek Listing Constructional Data Report (CDR) BLUE RAVEN
Totem OuOtv.ASM00I Total tV.AsSuMd. 1403 N.Research Way
Orem,UT 84097
800.377.4480
. `I t@ttCf.ctttt�;A 4�TE�.SS I .,,.._:. t naif afid.A411d WWW.BLUERAVENSOLAR.COM
;;b4: 102393982LAX-002 Original 11-A r-2016 Revised: 2-Jan-2022 Ntltlll}8P 102393982LAX-002 Original 11-A r-2016 Revised: 2-Jan-2022 CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use EXCEPT BLUE RAVEN SOLAR NOR
with Flat-Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.1+R:29May2019] SHALL IT BE DISCLOSED IN WHOLE OR
d{s{ IN PART TO OTHERS OUTSIDE
RECIPIENTS ORGANIZATION,EXCEPT
PV Module and Panel Racking Mounting System and Accessories[CSA TIL No.A-40:2020] IN CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE EQUIPMENT,
WITHOUT THE WRITTEN PERMISSION
Unlrac, Inc Manu'fadurtr 2', OF BLUE RAVEN SOLAR LLC.
1411 m Broadway Blvd NE ss ens . ',, ,^E P
Albuquerque, NM 87102
USA CERTIFIED
Klaus Nicolaedis
Todd GanshawAl
PV INSTALLATION
PROFESSIONAL
505-462-2190 Scott Gurney
#PV-011719-015866
505-843-1418
NA
CONTRACTOR:
klaus.nicolaedis@unirac.com BRS FIELD OPS
toddg@unirac.com 385-498-6700
fi� sir 8 btu rr
AX
P
IF3C:'''. :.: ..
DRAWING BY:
8 PLOT DATE:
f;
PROJECT NUMBER:
Page 1 of 136 Page 2_of 136
This report is for shpt exodus ie use Of 's Client and is provided®ursaEin¢to the a7eernerre between Intertek and its Client Intsrtek's responsaybity and This report is far the ex:lustre use of Imenek's Client and is provided ptirsuarit to the aVeemem between Intertek and its Client ( 's r amtf
kablity are limaed to the tssms and coryftons of me agreement lntertek assumes no liabtrty to any party..other than to the Chem in with the liabillity are linvtod to th0 terns and oondruons of the aVeamenit, Infertelk assumes no hatbdity to any Pauly.oeber thein 10 the Ckie.w in with.the
agreerivent for any Inas,expense or damage occasioned try the use of this report Only the Chervil as au&RYLred to pennA copy4V or dtatnbutlon of 9"report and sweerneryt kx any toss,expense or damage occasioned oy the use of this report Only the Client sot authpriZed to permit Wpyxv or distribution of this report and SHEET NAME:
then only A its enerety Any use of the"Ortek name or one off 0 narks for the sate 4r aleertrstrrrtent of the lesled material,product 4f Mrist first be then only riits entirety Any use of ere Intettilik name or one od its marks for the sate or Odwertilltnneint Of the 14$404 M',alenal,prgtlrzt 4r$00fi fe MV$t first be
approved in wilting by hmertek The observations and test results an this report are relevant only t0 the samo(e tested.This moon by Ased does not inVy that the approved in witting by k t nek.The otseniations and best results n thus report are relevant Only to the sarnpie tested.This report by 4setf does not irf' that&,e SPEC SHEET
Material producl,or is or has ever been under anInterbek certificationprogram product.,or semce is ort exr been under an Intertek cevtificabt
REVISION: PAGE NUMBER:
---- SS
Report No. 102393982LAX-002 Page 3 of 136 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 4 of 136 Issued: 11-Apr-2016 BLUE RAVEN
Unirac, Inc Revised: 2-Jan-2022 Unirac, Inc
Revised:2-Jan-2022
2.0;Product. escri tion y�
s1 l #;1rI6SG1t h011 1403 N.Research Way
{g Unirac SFM Orem,UT 84097
1F9rb Photovoltaic Mounting System, Sun Frame Microrail Installation Guide, PUB2021NOV29
ah-dham+Egr '�� Unirac NA 800.377.4480
W W W.BLUERAVENSOLAR.COM
The product covered by this report is the Sun Frame Micro Rail roof mounted Photovoltaic CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
Rack Mounting System.This system is designed to provide bonding and grounding to USED FOR THE BENEFIT OF ANYONE
photovoltaic modules.The mounting system employs anodized or mill finish aluminum brackets . Fuse Rating: 30A EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
that are roof mounted using the slider, outlined in section 4 of this report. There are no rails IN PART TO OTHERS OUTSIDE
within this product, whereas the 3" Micro Rail, Floating Splice, and 9"Attached Splice Module Orientation: Portrait or Landscape RECIPIENTS ORGANIZATION,EXCEPT
IN CONNECTION WITH THE SALE AND
electrically bond the modules together forming the path to ground. Maximum Module Size: 17.98 ft' USE OF THE RESPECTIVE EQUIPMENT,
UL2703 Design Load Rating: 33 PSF Downward, 33 PSF Upward, 10 PSF Down-Slope WITHOUT THE WRITTEN PERMISSION
The Micro Rails are installed onto the module frame by using a stainless steel bolt anodized Tested Loads-50 psf/2400Pa Downward, 50psf/2400Pa Uplift, 15psf/720Pa Down Slope OF BLUE RAVEN SOLAR LLC.
with black oxide with a stainless type 300 bonding pin, torqued to 20 ft-lbs, retaining the Trina TSM-255PD05.08 and Sunpower SPR-E20-327 used for Mechanical Loading
modules to the bracket. The bonding pin of the Micro Rail when bolted and torqued, penetrateg
i �'- u _P
the anodized coating of the photovoltaic module frame(at bottom flange)to contact the metal, VIncreased size ML test:
creating a bonded connection from module to module. Maximum Module Size: 22.3 ftz CERTIFIED
UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 30 PSF Down-Slope
PV INSTALLATION
The grounding of the entire system is intended to be in accordance with the latest edition of the LG355S2W-A5 PROFESSIONAL
National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar used for Mechanical Loading test.
Photovoltaic Systems or the Canadian Electrical Code, CSA C22.1 Part 1 in accordance to the
Mounting configuration: Four mountings on each Ion side of panel with the longest span of 24" Scott Gurney
9 9 9 9 P 9 P #PV-011719-015866
revision in effect in the jurisdiction in which the project resides.An local electrical codes must " UL2703 Design Load Rating:46.9 PSF Downward,40 PSF Upward, 10 PSF Down-Slope
1 P 1 Y ;. 9 9� P P
be adhered in addition to the national electrical codes.The Grounding Lug is secured to the LG395N2W-A5, CONTRACTOR:
photovoltaic module, torqued in accordance with the installation manual provided in this LG360S2W-A5 and LG355S2W-A5 used for used for Mechanical Loading test. BRS FIELD OPS
document. Mounting configuration: Six mountings for two modules used with the maximum span of 74.5" 385-498-6700
IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 50psf/2400Pa Uplift
Other optional grounding includes the use of the Enphase UL2703 certified grounding system,
which requires a minimum of 2 micro-inverters mounted to the same rail, and using the same `rigs: Mechanical Load test to add FlashLoc Slider and Trim Assemblies to UL2703 and IEC 61646
engage cable. Certifications, & Increase SFM System UL2703 Module Size:
Maximum Module Size: 27.76 ft'
UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward,21.6 PSF Down-Slope
Jinko Eagle 72HM G5 used for Mechanical Loading test.
Mounting configuration: Four mountings on each long side of panel with the longest span of 24"
Mamzimum module size:21.86 ft2
IEC 61646 Test Loads- 112.78 psf/5400Pa Downward, 75psf/3600Pa Uplift
SunPower model SPR-A430-COM-MLSD used for Mechanical Loading
Fire Class Resistance Rating:
-Class A for Steep Slope Applications when using Type 1 Modules. Can be installed at any
interstitial gap. Installations must include Trim Rail.
-Class A for Steep Slope Applications when using Type 2 Modules. Can be installed at any
interstitial gap. Installations must include Trim Rail.
-Class A Fire Rated for Low Slope applications with Type 1 or 2 listed photovoltaic modules.
This system was evaluated with a 5"gap between the bottom of the module and the roof's
surface
See section 7.0 illustractions# 1, 1 a, 1 b, and 1 c for a complete list of PV modules evaluated DRAWING BY:
with these racking systems
PLOT DATE:
NA
PROJECT NUMBER:
SHEET NAME:
SPEC SHEET
ED 16.3.15(16-Oct-2021)Mandatory ED 16 3,15(16-Oct-2021)Mandatory
REVISION: PAGE NUMBER:
---- SS
Report No. 102393982LAX-002 Page 42 of 136 Issued: 11-Apr-2016 Report No. 102393982LAX-002 Page 43 of 136 Issued: 11-Apr-2016 BLUE RAVEN
Unirac, Inc Revised: 2-Jan-2022 Unirac, Inc Revised:2-Jan-2022
�. #Iltfstrsttil s T.Q I UB �iOtis 1403 N.Research Way
Illustration 1 -Approved PV Modules Illustration 1a -Approved PV Modules Continue Orem,UT 84097
W W W.BLUERAVENSOLAR.COM
Manufacture Module Model J genes Manufacture Module Madel!Series Manufacture Module Model/Series ": Manufacture Modute Modet/Series
_.. _ CONFIDENTIAL-THE INFORMATION
Atea P-Series Eco Sofargy 0r an
_. __-..____ HEREIN CONTAINED SHALL NOT BE
".. 1.:OGO&Apotta 100E _....
` xxxSA15 USED FOR THE BENEFIT OF ANYONE
CHSM6612P,CHSM66 P.+iV.CH'SM661"M --TSGIar ET-M6 BFfxxxT',4' V13*iN &SA16,.
EXCEPT BLUE RAVEN SOLAR NOR
LGxxnc(A1Cr`E10EiKtN14N1Kr'N2T+VAN','
As;ronergy CHShi6612 M;'HV.CrlSM6610M E )BF');+{HF1. �reeVott Mona FERC V13HNxxxSA17 3 SA18, SHALL IT BE DISCLOSED IN WHOLE OR
-_ CtIGU_?K+SiC53YY1 A5 VBHNxxxSA17(EA;)&SA12E, IN PART TO OTHERS OUTSIDE
CHSM72M HC GC GCL-P6&GCL-M6 Seres LGxo N?T BS Panason c VBHNxxxKA01&KAG3&K Od. RECIPIENTS ORGANIZATION,EXCEPT
--
AXN6M610T-AXN6P6:{7f, TD-,AN3,7D-A.144, LGxxxN1K-66 IN CONNECTION WITH THE SALE AND
Auxin Hansol VBHNxxxZA01,VBHNxxxZA02. USE OF THE RESPECTIVE EQUIPMENT,
A-XNb�46�2T&AXtd6P6127 s:B-ANI.UD-ANl LGxxx(A1G`t-114+h11 K,+N 1C,'N1KrO1G+C)1iCi VB64,NxxxZA03,VBS-NxxxZA04 WITHOUT THE WRITTEN PERMISSION
AXIblackpremium 60 i35mmi. He:,erle 36M.50M.6GP,72es =_G Eieetronics OAC.
4 3 72P Seres __.. ___ ..-_w. _-_-__-_ _.... ......_ ___.. OF BLUE RAVEN SOLAR LLC.
.-.._.-_ _ __ mxx
Peiar SGxM(FB;BR
AX Ipower 6 `
0 i35 mm). _. t�xxx(N1C1TJ1K'N TM•Y.'7-E6 .
HT6C-156{M);hF04,
:Satar Phono Soar PS bG PS.-,2
Axitec .AXlpower?_(40mm). , LGxxx(N1C+`N1K,+TJctiY.+3 CJ52YJ;rG4
AXIprem,um:60(35mm}, LG.x 142T-.5 PrsmS°Lar P72 Ser' ��,��3t�1=
KG,MG.TG,R!,RG.T=.MI.HI&<1 Se r es
AXlprem um?:740mm i. y LGxxxM.3KlAl1 NJ'1d2T;'PF2W1-L5 _. . P!us,aro,Peak G3,G4,C5.G6(+„G7.G8+1 C E RT I F I E D
LGxxx N'
DNA-120 iBF"MP?26 _. (TEC _. �T, T-HE&7-SE Ser es ( -G•Q1C'O1K)NS . Pro.Peak L-G Z.,L-G4,L-G5,L-G6.L-G?
' O5 , _.. ._ ._ _. .__ _LGxxx Nlr-�'N1KN2W/O1C,-C71K)-Vs D.P£AK u4 BLK-G6+ PV INSTALLATION
DNA-144+61=•'4F}�6 ... _._. ..__ _
_. Japan Solar 3P5-60&JAS-72 Serres _.. _- _.
BVM661G, _. _._ __. _-_ .._._ __ _-._. LR4-6C(H18/HIHf}1P&'HPtfi-x"M
B°�,e� D_PE.AK DUO BLK-G6+,7s PROFESSIONAL
"_- BV46612 1AP6 60-xxx,JAM6 60 xxx+'S4,JAM6(K)-60* LR4 72,,-flH,,HPH)-xxxM
.._-._. _.._.--_ ..._ O.P£AK DUO BLK)-G8(+) Scott Gurney
BYD P6K&MHK-36 Seres _. xxx..1AP6Ik)-?2-xxxl48B,SAP72SYY-xxx,+=. LR6 6Gt,83':1,€8D/4-I;BO}-xxxM�;3f:m�m;� Q.Cetls 0,PEAK DUO L-G8.3,BFF #PV-011719-015866
...._. _. __....__.._ _.. .__._ _....... +AP6(k)60-xxx;488,JAP60SYY-xxx=._ LR6-60MK)(PE)(HP3)-7i PH)-xxxM(35mm) d AK OU G4(+'�
C 31 M,9€,'U'Y'rMS 4_PE DUO ML .
-.JA Sciar i:AM&,k' .2-xx.x,,=,JAll 72SYY xxxi�7. : LONGi LR6-60�SKjETE1(PB)tPH)-xxx.M(40rnrn) CONTRACTOR:
C53{Xl U?.C53K-MB-AG.C53K-tMS:Pi O_P£AKnUi}XLG9,%G9 'G3.3 BRS FIELD OPS
Canadian Solar C53N-MS.CS3ix'-MB-AG.C53U-'4 a, 'AMb;'kj-64-xx x,?',lA'A6GSYY-xxx;ZZ. LR6 713P)(H6DN{HJBD)-x M(3Gmm) O.P£.AK DUO S00ML 61G;+)
$ Sv r.C53'W i.YV:01,0_2,03.04.10 LR6'4`HV)(BK)'',PE)',PHj(PB)(HPHI;
CSSA-M,CS6{K V),CS6K-[M;•P?,C56K-MS : O_PEAK DUO XL-G?, 102.+'1G3
"i_ZZ.SC PR,BP,HiT i8,MW.MR (35mm)
CS6P(M/Pr C56U-(M/P).CS6V-M,CS6X-P _ AIpts {72)(Black)(Pure)
. xxx mm
CentrosMarAmerica C-Sexes&£Seres ;KM& KMS Series
I N-Peak(BLack)
4:ssicn Solar Energy MSE Seres
.....-_..-_ _..-.. _-_-_.- .-._.. ._.._..-.___.-. J°:nko Ea Ie JKMxxx4 P
CT2xxMxx 01,CT1xxPxx-01_ 4 -..._ ._ _—. _ _... REC. N- eak.2{Black)
3Khxxx M-72iL-V M2subisfi MiE&MLE Seres
CerainTeed CTxMxx-02,CTxxM-03, ------- .. -..._
PEAK energy Series
'.
Neo Solar Power Co. DW&DbF Series PEAK£ire BtX2 Series
CTxx Mxx-04,CTx HC11-04 Kyocera KU Ser es _.._--....._ __ ...- 'r4Y
Dehui DH-601M PEAK Energy 72 Seres
DRAWING BY:
PLOT DATE:
PROJECT NUMBER:
SHEET NAME:
SPEC SHEET
ED 16.3.15(16-Oct-2021)Mandatory ED 16.3.15(16-Oct-2021)Mandatory
REVISION: PAGE NUMBER:
---- SS
Report No. 102393982LAX-002 Page 44 of 136 Issued: 11-Apr-2016 BLUE RAVEN
Unirac, Inc Revised: 2-Jan-2022
7.0 UIUStf1tIGR5 1403 N.Research Way
Illustration 1b-Approved PV Modules Continue Orem,UT 84097
800.377.4480
WWW.BLUERAVENSOLAR.COM
Manufacture Modute Modet/Series Manufacture Module MadeL(Series
CONFIDENTIAL-THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
TwinPeak Series SC SC 9.SC 31.SC Bim'
Tia USED FOR THE BENEFIT OF ANYONE
TwinPeak Series TxxxS EXCEPT BLUE RAVEN SOLAR NOR
SHALL IT BE DISCLOSED IN WHOLE OR
Tw•inPeak 2 BLK2 Ser•es PAGS,PDOS.DDGS,DE06,DD06,-E06.
REC{cont.} IN PART TO OTHERS OUTSIDE
TmriPeak!_S(M)72;XV1 Tr Ra PD14,PE14,DD14.DE09.05,DE14,DEIS. RECIPIENTS ORGANIZATION,EXCEPT
TwinPeak 3 Series(3&mm) PE1SH IN CONNECTION WITH THE SALE AND
'P4,'8ack} -- _ - .- - _ USE OF THE RESPECTIVE EQUIPMENT,
UP-hixxxP{B% WITHOUT THE WRITTEN PERMISSION
Renesoia Yitrus2 Seres&156 Series Upsaar p_ ,._ OF BLUE RAVEN SOLAR LLC.
U hlxxxa t{$h
Risen RSM72-6{MDG}(M},RSM67-6 D7t•+xxxH7A_D7+1IA)xxxHSA -
S-Energy _.._ SN72&51460 Series(40mm).. .. 'tTRE FAKxxx(CSG;r'FSG),1=AMxxxE7G-1313
Seraphim SEG-6&SRP-6 Series .. FAMxxxE8G(-661
NAA' L:
Sharp &NU-SA NU-SC Seres Eldora.
CERTIFIED
SLA, SLG,3C Seres& Vikram Sotivo, ___------.--_.—_---
Siifab MVBK 'HC) PV INSTALLATION
Somers
PowerX.-F-xxxR-(AC.+'PD,r67y Waaree AC&Aaiya Seri PROFESSIONAL
x€aria Po werX?-xxxC-PD NJinaico WST&W°SP Seres Scott Gurney
-- #PV-011719-015866
PowerXT-xxxR-PM(AC'i
Y7,ngLi YGE&YLM Series
_----SunmCONTRACTOR:
adute Prated. N Sh ne 23CM6%'2
SoarLMarLd .._ ..... ... _.
o
SLmrndule Ptus
_- BRS FIELD OPS
Sonati SS 230-265
385-498-6700
Suntech STP
------. -----------
Suniva MV Series&Optimus Ser es
Sun Edson/Rextron.cs F Series,R-Series&FLEX FXS Series
SunPower X Series.F Series&P-Series
----------
7P572,
--- TP572,TPS 96,TP654.TP660.
Tatesun
TP672,Hipor M,Srnar
DRAWING BY:
PLOT DATE:
PROJECT NUMBER:
SHEET NAME:
SPEC SHEET
ED 16.3.15(16-Oct-2021)Mandatory
REVISION: PAGE NUMBER:
---- SS
1 1 SUNBLUE RAVEN
FRAME FLASHING & SLIDERS1 1
1 1
1 1403 N RESEARCH WAY BUILDING J
OREM.UT 84097
SFM MICRORAW■■ 1 INSTALLATION GUIDE 1 PAGE 800-377-4480
WWW BLUERAVENSOLAR COM
CONFIDENTIAL-THE INFORMATION
INSTALL SLIDERS AND HEREIN CONTAINED SHALL NOT BE
— j USED FOR THE BENEFIT
ANYONE EXCEPT BLUE RAVEN
ROOF ATTACHMENTS: SOLAR NOR SHALL IT BE
DISCLOSED IN WHOLE OR IN PART
, Follow manufacturer instructions
UP-SLOPE TO OTHERS OUTSIDE RECIPIENTS
F for flashing installation procedures ORGANIZATION EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT..WITHOUT THE
IL _ WRITTEN PERMISSION OF BLUE
j RAVEN SOLAR LLC.
I
NASCEF
CERTIFIED
- -- j PV INSTALLATION
PILOT HOLES: FLASHINGS: PROFESSIONAL
ott Gurney
Drill pilot holes for lag Screws or Place flashings ! Mold NS + 1"
#PV-01 1719-015866
structural screws (as necessary) at i CONTRACTOR:
marked attachement points 1 BRs FIELD OPS
385.498.6700
Y
I
I
a = I
Mad NS + 1°
INSTALL SLIDERS AND TRIMRAIL ROOF ATTACHMENTS:
• Insert flashings per manufacturer instructions
=, -
3
I
• Attach sliders to rafters
• Verify proper row to row spacing for module size (Mod NS+ 1')
• Ensure that TrimrailTM roof attachments in each row have sufficient u' I; I; ; ? I
- ------- --- I DOWN-SLOPE
engagement with slider dovetails for proper attachment. } J,
9 ) SHEETNAME
SPEC SHEET
PAGE NUMBER REVISION
SS 0